Commissioning for the 2015 IECC Code Lunch & Learn Presentation O’Connell Robertson - TEMA March 10, 2016
Transcript
Page 1: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Commissioning for the 2015 IECC Code

Lunch & Learn Presentation O’Connell Robertson - TEMA March 10, 2016

Page 2: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Learning Objectives

Impact of Statewide Change from IECC 2009 to IECC 2015

At the end of this program, participants will be able to:

• Better informed about the history

• Understand what is driving the need for commissioning (Cx)

– The buildings and systems affected

– What is required, what is voluntary

• Better determine best method for Cx procurement

• Believe!

Page 3: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1982

Page 4: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1982 • ASHRAE convened a committee

to Cx best practices

Page 5: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1982 • ASHRAE convened a committee

to Cx best practices • ET released in summer

Page 6: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1982 • ASHRAE convened a committee

to Cx best practices • ET released in summer • Rocky fights Mr. T

Page 7: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1985 • Rocky brings down the USSR by

defeating Ivan Drago

Page 8: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1985 • Rocky brings down the USSR by

defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear

down the wall

Page 9: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1985 • Rocky brings down the USSR by

defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear

down the wall 1989 • Berlin wall comes down

Page 10: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1985 • Rocky brings down the USSR by

defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear

down the wall 1989 • Berlin wall comes down • You finally start to reconsider your

mullet

Page 11: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

1985 • Rocky brings down the USSR by

defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear

down the wall 1989 • Berlin wall comes down • You finally start to reconsider your

mullet • ASHRAE publishes Guideline 0 –

The Commissioning Process

Page 12: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why? A brief history.

• Guideline 0 – Discusses the process but not

specific systems – Encourages implementing Cx

at Pre-design – Guideline is written around

ensuring that the objectives laid out in the OPR are satisfied

– Cx continues into the occupancy period with surveys

Page 13: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Next stop: Code Implementation • Over next 20+ years other Cx guidelines by:

– AABC – ASHRAE 1.1 – GSA – NEBB – BCxA – ASHE

• In 2009 Cx is required: – LEED 2009 –

• Breaks Cx into mandated Fundamental (construction) & optional Enhanced (pre-design)

– ASHRAE 90.1 – 2010 • Cx of buildings over 50,000sf

– IECC 2012 – • Cx Required for Mech > 40T & Elec

– IECC 2015 – • Cx requirements expand to circ pumps

Page 14: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why Energy Codes?

Page 15: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

2009 IECC to 2015 IECC

• 2009 IECC – April 1, 2011

• 0.25” Thick

Page 16: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

2009 IECC to 2015 IECC

• 2015 IECC – Nov. 1, 2016

• 0.45” Thick

Page 17: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

2009 IECC to 2015 IECC

• Mechanical

– Min efficiency rise

– R5 to R6 indoor insulation

– Energy recovery on systems > 2500 cfm and >10% OA

• with smaller systems having higher allowable % OA

– Either waterside or airside economizers with few exceptions (DX<5T)

Page 18: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

2009 IECC to 2015 IECC

• Controls

– 7-day programmable still allowed but additional features operations required not remotely accessible

– Economizer must be: 1.) fixed dry bulb, 2.) fixed enthalpy/dry bulb, or 3.) diff enthalpy and fixed dry bulb

– DCV for systems serving medium density (>25ppl/1000 SF) rooms over 500 SF

– CHW and HW loop temp resets.

– Variable speed pumping systems > 10HP

– Fans ≥ 7.5HP to vary speed. Low speed NMT 2/3 full speed.

Page 19: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

2009 IECC to 2015 IECC

• Electrical

– Most spaces lights on occ sensor with few exceptions for emergency egress

– Increased daylighting responsive auto controls

• Additional Efficiency – Six additional efficiency or controls options for Mechanical and

Electrical (building must comply with 1)

• Plumbing – Circ pumps to be automatically shut off on temp and demand

Page 20: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

2009 IECC to 2015 IECC

• Commissioning (New requirement as of 2012 IECC) – Required for buildings with cooling load over 40T – Similar to 2012 IECC but with circ pumps added

Page 21: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Why Cx?

• Systems are getting more complex

– More energy recovery

– More economizers

• Controls schemes are more complex

– Cannot get there on raw efficiency increases

– Want to deliver energy only as much and where needed

• Commissioning can ensure the building operates as intended

Page 22: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Next stop: Owner Implementation

Path 1: • Allow contractor to select

and mange – May be better option if

owner does not have manpower to support CxA efforts

– Required by code and likely to get minimum services

Page 23: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

What is required?

• Registered professional provides evidence

• Cx HVAC (select systems only)

• TAB

• O&M

• Functional test lighting controls

• Sampling allowed for identical spaces

• Functional test circ pumps

Cx Payback in… New Buildings: 4.2 years Existing Buildings: 1.1 years

Next stop: Owner Implementation

Page 24: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Next stop: Owner Implementation

What not to expect when doing the minimum code required Cx. • Plan & spec review of milestone design submittals (SD, DD, %CD) • CxA support for writing OPR • Specifications tailored to project • Installation review(s) • Submittal review(s) • System trending • Re-commissioning through warranty • Continuous Commissioning Plan

Page 25: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Next stop: Owner Implementation Path 2: • Owner Provided and/or Selected.

– Can add additional requirements

– CxA acts as an owner advocate

– CxA better understands owner’s expectations

– Owner can make more informed contractor payments as job winds down

– Commissioning specifications better represent the work to be completed on the project

– O&M personnel may be better utilized

Page 26: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Who can commission?

• Registered professional or approved agency for Mech & Plumbing

• For lighting, the registered design professional must provide evidence that systems were tested.

Next stop: Code Implementation

Page 27: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Examples

• VAV boxes simultaneously auto-calibrating

• Causing AHU to shut down on high static pressure

• Critical care AHU in a hospital

Page 28: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Examples

• Relief fan operating on economizer mode

• Setpoint as designed too close to non-economizer mode setpoint

• PID loop not tuned correctly

Page 29: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Examples

Page 30: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Examples

Page 31: Commissioning for the 2015 IECC Code · Why? A brief history. 1985 • Rocky brings down the USSR by defeating Ivan Drago 1986 • Reagan tells Gorbachev to tear down the wall 1989

Questions & Answers