— RELION® 670 SERIES
IEC 61850 Edition 1, 670 series Version 2.1 Communication protocol manual
Document ID: 1MRK 511 349-UEN Issued: March 2019
Revision: AProduct version: 2.1
© Copyright 2016 ABB. All rights reserved
This product includes software developed by the OpenSSL Project for use in the OpenSSLToolkit. (http://www.openssl.org/) This product includes cryptographic software written/developed by: Eric Young ([email protected]) and Tim Hudson ([email protected]).
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product namesmentioned in this document may be trademarks or registered trademarks of their respectiveholders.
Disclaimer
This document has been carefully checked by ABB but deviations cannot be completely ruledout. In case any errors are detected, the reader is kindly requested to notify the manufacturer.Other than under explicit contractual commitments, in no event shall ABB be responsible orliable for any loss or damage resulting from the use of this manual or the application of theequipment.
Conformity
Table of contents
Section 1 Introduction.........................................................................................................51.1 This manual......................................................................................................................................... 51.2 Intended audience............................................................................................................................. 51.3 Product documentation................................................................................................................... 51.3.1 Product documentation set........................................................................................................ 51.3.2 Document revision history...........................................................................................................61.3.3 Related documents....................................................................................................................... 61.4 Document symbols and conventions.............................................................................................61.4.1 Symbols........................................................................................................................................... 61.4.2 Document conventions.................................................................................................................7
Section 2 Introduction to IEC 61850................................................................................. 92.1 Overview.............................................................................................................................................. 92.2 Related documentation to IEC 61850.......................................................................................... 10
Section 3 Substation Configuration description Language (SCL).............................. 113.1 The substation section....................................................................................................................123.2 The communication section...........................................................................................................123.3 The IED section................................................................................................................................. 133.4 Tool concept......................................................................................................................................153.5 Engineering concept in IEC 61850-6.............................................................................................16
Section 4 Communication profile.................................................................................... 17
Section 5 Supported services...........................................................................................19
Section 6 Data sets and control blocks...........................................................................236.1 Data sets............................................................................................................................................236.2 Report control block (URCB/BRCB)..............................................................................................236.3 GOOSE Control Blocks (GoCB)...................................................................................................... 26
Section 7 Logical node data model................................................................................. 297.1 Common data objects in each logical node............................................................................... 297.2 Logical nodes for control............................................................................................................... 307.2.1 Bay control CBAY......................................................................................................................... 307.2.1.1 Bay control QCBAY...................................................................................................................307.2.2 Switch controller CSWI............................................................................................................... 327.2.2.1 Switch controller SCSWI..........................................................................................................327.3 Logical nodes for conversion functions......................................................................................347.3.1 Integer to Boolean converter FCVB......................................................................................... 347.3.1.1 Integer to Boolean 16 conversion with logic node representation ...............................347.3.2 Boolean to integer converter FCVI...........................................................................................357.3.2.1 Boolean to integer conversion with logical node representation, 16 bit BTIGAPC.....35
Table of contents
1Communication protocol manual
7.4 Logical nodes for protection functions...................................................................................... 367.4.1 Protection trip conditioning PTRC...........................................................................................367.4.1.1 Logic for group alarm ALMCALH...........................................................................................367.4.1.2 Logic for group indication INDCALH.................................................................................... 377.4.1.3 Tripping logic common 3-phase output SMPPTRC...........................................................387.4.1.4 Logic for group warning WRNCALH..................................................................................... 397.4.2 Multipurpose analog protection GAPC...................................................................................407.4.2.1 General currrent and voltage protection CVGAPC............................................................ 407.5 System logical nodes...................................................................................................................... 477.5.1 Generic security application component................................................................................477.5.1.1 Generic security application component AGSAL............................................................... 477.5.2 Physical device information LPHD........................................................................................... 497.5.3 Logical node zero LLNO............................................................................................................. 497.5.4 Access point diagnostic for redundant Ethernet ports RCHLCCH................................... 507.5.5 Access point diagnostic for non-redundant Ethernet port SCHLCCH............................. 517.6 Logical nodes for protection related functions.........................................................................527.6.1 Disturbance recorder RDRE....................................................................................................... 527.6.1.1 Disturbance report DRPRDRE................................................................................................ 527.7 Logical nodes for generic references.......................................................................................... 537.7.1 Generic process I/O GGIO..........................................................................................................537.7.1.1 Logic rotating switch for function selection and LHMI presentation SLGAPC........... 537.7.1.2 Selector mini switch VSGAPC................................................................................................ 547.7.1.3 Generic communication function for Double Point indication DPGAPC...................... 567.7.1.4 Single point generic control 8 signals SPC8GAPC.............................................................567.7.1.5 Event counter with limit supervision L4UFCNT.................................................................597.7.1.6 IEC 61850 generic communication I/O functions SPGGIO...............................................617.7.1.7 IEC 61850 generic communication I/O functions 16 inputs SP16GGIO.........................617.7.1.8 Generic communication function for Measured Value MVGAPC.................................... 637.7.1.9 Trip matrix logic TMAGAPC....................................................................................................647.7.1.10 Elapsed time integrator with limit transgression and overflow supervision
TEIGGIO......................................................................................................................................657.8 Logical nodes for sensors and monitoring.................................................................................677.8.1 Circuit breaker monitoring SSCBR...........................................................................................677.8.1.1 SSCBR......................................................................................................................................... 677.8.2 Insulation medium supervision (gas) SIMG............................................................................ 717.8.2.1 SSIMG.......................................................................................................................................... 717.8.3 Insulation medium supervision (liquid) SIML.........................................................................737.8.4 Through fault monitoring STHR............................................................................................... 747.8.4.1 Through fault monitoring PTRSTHR ....................................................................................747.9 Logical nodes for switchgear........................................................................................................ 757.9.1 Circuit breaker XCBR...................................................................................................................757.9.1.1 Circuit breaker SXCBR............................................................................................................. 757.9.2 Switch XSWI.................................................................................................................................. 787.9.2.1 Circuit switch SXSWI................................................................................................................78
Section 8 Flexible product naming.................................................................................. 818.1 Introduction...................................................................................................................................... 81
Table of contents
2Communication protocol manual
8.1.1 Mapping example........................................................................................................................ 818.1.2 Mapping possibilities and requirements................................................................................82
Section 9 Glossary............................................................................................................. 85
Table of contents
3Communication protocol manual
4
Section 1 Introduction
1.1 This manualGUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v19
1.2 Intended audienceGUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v10
1.3 Product documentation
1.3.1 Product documentation setGUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v15
IEC07000220-4-en.vsd
Plan
ning
& p
urch
ase
Engi
neer
ing
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gD
eins
tallin
g &
disp
osal
Application manual
Operation manual
Installation manual
Engineering manual
Communication protocol manual
Cyber security deployment guideline
Technical manual
Commissioning manual
IEC07000220 V4 EN-US
Figure 1: The intended use of manuals throughout the product lifecycle
The engineering manual contains instructions on how to engineer the IEDs using the varioustools available within the PCM600 software. The manual provides instructions on how to setup a PCM600 project and insert IEDs to the project structure. The manual also recommends asequence for the engineering of protection and control functions, LHMI functions as well ascommunication engineering for IEC 60870-5-103, IEC 61850, DNP3, LON and SPA.
The installation manual contains instructions on how to install the IED. The manual providesprocedures for mechanical and electrical installation. The chapters are organized in thechronological order in which the IED should be installed.
1MRK511349-UEN A Section 1Introduction
5Communication protocol manual
The commissioning manual contains instructions on how to commission the IED. The manualcan also be used by system engineers and maintenance personnel for assistance during thetesting phase. The manual provides procedures for the checking of external circuitry andenergizing the IED, parameter setting and configuration as well as verifying settings bysecondary injection. The manual describes the process of testing an IED in a substation whichis not in service. The chapters are organized in the chronological order in which the IED shouldbe commissioned. The relevant procedures may be followed also during the service andmaintenance activities.
The operation manual contains instructions on how to operate the IED once it has beencommissioned. The manual provides instructions for the monitoring, controlling and setting ofthe IED. The manual also describes how to identify disturbances and how to view calculatedand measured power grid data to determine the cause of a fault.
The application manual contains application descriptions and setting guidelines sorted perfunction. The manual can be used to find out when and for what purpose a typical protectionfunction can be used. The manual can also provide assistance for calculating settings.
The technical manual contains operation principle descriptions, and lists function blocks, logicdiagrams, input and output signals, setting parameters and technical data, sorted perfunction. The manual can be used as a technical reference during the engineering phase,installation and commissioning phase, and during normal service.
The communication protocol manual describes the communication protocols supported bythe IED. The manual concentrates on the vendor-specific implementations.
The point list manual describes the outlook and properties of the data points specific to theIED. The manual should be used in conjunction with the corresponding communicationprotocol manual.
The cyber security deployment guideline describes the process for handling cyber securitywhen communicating with the IED. Certification, Authorization with role based access control,and product engineering for cyber security related events are described and sorted byfunction. The guideline can be used as a technical reference during the engineering phase,installation and commissioning phase, and during normal service.
1.3.2 Document revision historyGUID-C8027F8A-D3CB-41C1-B078-F9E59BB73A6C v2.1.1
Document revision/date History
January 2016 First Release
March 2019 Maintenance Release
1.3.3 Related documentsGUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v4
1.4 Document symbols and conventions
1.4.1 SymbolsGUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v12
The electrical warning icon indicates the presence of a hazard which couldresult in electrical shock.
Section 1 1MRK511349-UEN AIntroduction
6Communication protocol manual
The warning icon indicates the presence of a hazard which could result inpersonal injury.
The caution hot surface icon indicates important information or warning aboutthe temperature of product surfaces.
The caution icon indicates important information or warning related to theconcept discussed in the text. It might indicate the presence of a hazard whichcould result in corruption of software or damage to equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project orhow to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand thatunder certain operational conditions, operation of damaged equipment may result indegraded process performance leading to personal injury or death. It is important that theuser fully complies with all warning and cautionary notices.
1.4.2 Document conventionsGUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v8
• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossaryalso contains definitions of important terms.
• Parameter names are shown in italics.For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signalname may be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must beconnected to another function block in the application configuration to achieve avalid application configuration.
• Dimensions are provided both in inches and millimeters. If it is not specifically mentionedthen the dimension is in millimeters.
1MRK511349-UEN A Section 1Introduction
7Communication protocol manual
8
Section 2 Introduction to IEC 61850
2.1 OverviewGUID-66925336-B6C3-4B22-95F4-A3321B63FABB v7
The general scope of the IEC 61850 protocol standard is designed to support thecommunication of all functions being performed in the substation. Its’ main goal isinteroperability; this is the ability for IEDs from one or different manufacturers to exchangeinformation and use the information for their own functions. Moreover, the standard allows afree allocation of these functions and accepts any system philosophy, from a distributedarchitecture (for example, decentralised substation automation) to a centralised configuration(for example, RTU based).
The standard separates the functionality represented by the data model and the relatedcommunication services from the communication implementation (stack).
The data model of the standard is an object-oriented one, grouping the data into the smallestpossible sets referring to the smallest possible functions to be implemented independently.These smallest possible data groups or functions are named logical nodes. The logical nodesand all data and attributes contained are named according to a standardised semantic, whichis mandatory.
This manual describes how the IEC 61850 standard is applied in the IEDs. References and briefdescriptions of the standard are also included. It is assumed that the reader has basicknowledge of the IEC 61850 standard.
The following parts of the IEC 61850 standard are of importance as they relate to this manual:
• Station Configuration description Language (SCL) is described in IEC 61850-6. The SCL isan XML based definition of how to describe the parts of a substation. This part of thestandard also includes the roles of different tools as well as the engineering concepts.
• Communication profile (IEC 61850 stack) is described in IEC 61850-8-1. This part of thestandard includes a number of possible communication profiles, and how the servicesdefined in IEC 61850-7-2 are mapped to the communication profile.
• Communication services are described in IEC 61850-7-2. This part deals mainly with thecommunication facilities from client and server point of view. It includes the differentpossibilities of communication functionality.
• Logical node data model. This is described in IEC 61850-7-3 and IEC 61850-7-4.• Conformance tests and the basis for conformance documents are handled in IEC
61850-10.
Detailed information regarding the IEC 61850 implementation of the IED is described insidethe conformance documents.
• MICS, Modeling Information Conformance Statement, contains the declaration of theused logical node types.
• PICS, Protocol Information Conformance Statement, contains the details and what issupported regarding protocol facilities.
• PIXIT, Protocol Extra Information, contains additional information on how the IEC 61850 isimplemented and used.
• TICS, Tissue Information Conformance Statement, contains the supported Tissues, whichare handled in the Tissues process as defined by UCA, Utility Communication Architectureforum. The Tissues handling is found in http://www.tissue.iec61850.com.
1MRK511349-UEN A Section 2Introduction to IEC 61850
9Communication protocol manual
The conformance documents are unique for each product release and refer to each other. Theidentities included in the related documents refer to a specific version of the IED series.
The communication profile in IEC 61850 uses the MMS standard, which uses Ethernet andTCP/IP to handle the information transport within the substation.
The data modelling uses the concept of logical nodes to identify the published information forcommunication. The standard defines a set of logical nodes, each representing acommunication view of a process function with a number of data objects. For example, atransformer differential - or line differential protection, because the standard defines only adifferential protection. Therefore, it is possible to adapt the logical node, which is defined inthe standard, as a logical node class. The standard defines methods to describe the actuallyused logical node as a logical node type which is then based upon the logical node class. Thisallows all partners to interpret the logical node type information because the description iscompletely given in the standard. The type description of all logical nodes is part of the DataType Template (DTT) section in the SCL description file of a station or the IED.
Besides the information about the configuration of the communication facilities, this manualcontains the full description of all logical nodes available in the IEDs. The information aboutthe logical nodes and their data objects may be used to identify which signals are available forthe functions as described in the technical manual. The link to the technical manual is done inthe logical node tables by listing the signal name as given in the function block, or as seen inPCM600 or the LHMI.
2.2 Related documentation to IEC 61850GUID-906D4C7F-29FD-4922-8A8B-8A3A3E2B811E v5
Use the latest revision of the documents listed, unless stated otherwise.
Section 2 1MRK511349-UEN AIntroduction to IEC 61850
10Communication protocol manual
Section 3 Substation Configurationdescription Language (SCL)
SEMOD129808-4 v8
Four different types of SCL files - SCD, CID, IID, and ICD, can be exported from PCM 600.
The SCL language is based on XML. However, detailed knowledge of the XML contents is notneeded.
The SCL XML file (ICD/SCD/CID/IID) contains five sections, which are specified in IEC 61850–6clause 9.
• Header• Substation section describes the functional structure and its relation to primary devices.• Communication section describes the connection between the IED access points to the
respective subnetwork. and includes also the properties (addresses) of the access points.• IED section contains a description of the supported communication services, the access
point(s) and the IEDs logical devices, logical nodes and their attributes.• Data type template section contains a declaration of all types used in the SCL file, logical
nodes type, DO types, attributes and enums.
The system structure is defined by the organization of the plant structure in PCM600. Thesignal engineering and the signal routing are IET600 tasks, signal engineering regarding DS,rcb,gcb, GOOSE subscribers can be done also in PCM600. The IED needs to be configured withPCM600 before the system is configured with IET600.
The SCL engineering must be done in an SCL engineering tool. The data sets and the controlblocks are logically defined as part of the logical nodes (see IEC 61850–7–2 clause 9). The IEDalso needs a correctly configured communication section for GOOSE engineering, which canbe done in IET600 or PCM600.
The data type templates section provides the correct content description of each logical nodetype to all tools and users (clients) of the information. Each IED and vendor may have their ownlogical node type definitions included in the data type template section together with all otherlogical node types based on the standard.
1MRK511349-UEN A Section 3Substation Configuration description Language (SCL)
11Communication protocol manual
IEC08000178.vsd
IED Name AccessPoint Address GSEIED Name AccessPoint Address GSE
Services
AuthenticationLDevice
DAI
DOType
DAType
EnumType
SubstationVoltageLevel
BayLNode
IED LD LNIED LD LN
CommunucationSubnetwork
Connected AP
IEDAccessPoint
Server
GOOSE Control
LN0 LNDataSet DOI
DataTypeTemplates
Report Control
Inputs
DOI
SettingControl
LNodeType
DOType
DAType
EnumType
DO
DA
IED
SDO
BDAStation
Com
mun
IEC08000178 V1 EN-US
Figure 2: IEC 61850: Principle structure of the SCL XML file
The arrows show the link between the different sections given when an IED is integrated in thesubstation structure and/or in the communication structure. All needed logical nodes of anIED are linked to the substation section by the SCL tool.
A reference to GOOSE Control Blocks (GoCB) is included in the communication section whenGoCB is configured.
3.1 The substation sectionSEMOD129763-4 v4
3.2 The communication sectionSEMOD129771-4 v3
The organization of the physical IEDs to the communication network is independent of thesubstation structure. The IEC 61850 standard defines the communication network with norelation to an existing media or protocol. The mapping to an existing media and protocol isspecified in IEC 61850–8–1.
The IEC 61850 standard describes in part 7–2 the ACSI in a media and protocol independentform. Part 8–1 specifies the mapping of this ACSI to the existing MMS.
Section 3 1MRK511349-UEN ASubstation Configuration description Language (SCL)
12Communication protocol manual
The communication section describes how information is routed between the IEDs andcontains the following parts:
• Subnetworks• IEDs connected to different subnetworks• Access points per IED to subnetworks• Address• IP address of LAN network (is exceptionally part of the address elements)• Link to GoCB message in transmission direction (extended during signal engineering and
routing)
en06000101.vsd
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
AP
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
AP
IED(client)
- Access Point (AP)- Address- GSE; GoCBs
Communication
IED(client)
- Access Point (AP)- Address- GSE; GoCBs
Communication
Subnetwork
IEC06000101 V1 EN-US
Figure 3: IEC 61850–6: Communication network
Additional information about the server is part of the IED.
3.3 The IED sectionSEMOD129775-4 v6
The IED section describes the complete IED as it is needed for IEC 61850 communication andsignal engineering. The data type template part of an IED may be seen as part of the IED, evenwhen separated in its own section. The IED's ICD files include the description of the logicalnodes, their data type templates and the used or supported services. The structure of the IEDsection follows the definitions made in the IEC 61850 standard.
Two basic IED types are used in system configuration.
• Station level IEDsare located on the station level and are identified as client IEDs when they read or writeinformation from or to the bay IEDs. This functionality is represented by logical nodes ofgroup “Information (I)”. These are the logical nodes (LN) = ITCI, IHMI and ITMI. Client IEDsare the receiver of information in monitoring direction and sender of commands (control).These logical nodes have no data objects. They are only used to link the report controlblocks (BRCBs) from the server IEDs. They have to read their information about the signalsand the signal configuration from the bay IEDs. This is possible by checking all controlblocks for a link to it as a client.
• Bay level IEDs
1MRK511349-UEN A Section 3Substation Configuration description Language (SCL)
13Communication protocol manual
are located on the bay level and are identified as server IEDs when they read or writeinformation vertically. When GOOSE messages are received, the bay level IED also has theclient role.
en06000104.vsd
AP
Subnetwork
Control
IED
CVMMXU1
SB1.LD0
Server
LPHD
SXCBR1
SCSWI1
SXSWI1
SCSWI2
SXSWI2
SCSWI3
SXSWI3
SCSWI4
SXSWI4
SCSWI5
LLN0
Mod
CBOpCap
Origin
Data
DataAttribute
Beh
Health
NamePlt
ctlValPos
Loc
OpCnt
BlkOpn
BlkCls
stVal
q
t
LogicalNode
ctlModel
IEC06000104 V2 EN-US
Figure 4: Organization of LDs, LNs, DOs and DAs in an IED
• A server represents the communication interface to the subnetwork (Ethernet).• One or more logical device(s) (LD) are connected to a server.• A set of logical nodes belong to a LD.• The LN LLN0 is a special logical node per LD and contains for example the data sets, the
various control blocks, inputs (from GOOSE messages). In the IED series, the data setsand the control blocks shall be located to LD0.
• The LN LPHD is a special logical node per LD and contains data objects that describe thestatus of the physical device (the IED)
• Each logical node represents a function and contains a number of data objects (DO)• Each DO includes a number of data attributes (DA)
The data objects represent information signals that may be routed to station level IEDs or toother bay IEDs that are communicating via GOOSE. The signal engineering task is to select therequested signals (DOs) and link them to the client IEDs as receiver. When using a dataset forMMS, the requested signals are DOs but when creating a dataset for GOOSE messaging, DAsare used.
Section 3 1MRK511349-UEN ASubstation Configuration description Language (SCL)
14Communication protocol manual
The number of data objects and data attributes per DO is defined by the used LN type in theIED. The content of logical node types and DO types are defined in the DTT. This also meansthat the definitions in the DTT section have to be unique within an SCD file.
3.4 Tool conceptGUID-93477EC1-9BB4-4CCE-8603-0D910BDD661B v6
The IEC 61850-6 defines a number of roles for tools. In the Relion® series, PCM600 is defined asthe IED tool, and IET600 is defined as the system engineering tool.
The sections in SCL contain properties that are to be configured by these tools. There is norelation between one section and one specific tool. The task of the IED tool is to configure allproperties for the IED, while the system tool has the task to define the place of the IED in thesystem and its communication dependencies. For example, the plant structure in PCM600results in the subsystem section in SCL regarding the subsystem structure down to the IEDlevel. The PCM600 also configures the IED section as a result of the IED configuration. InPCM600, the configuration properties for SCL are handled automatically as a result of theconfiguration, except for the receiving of GOOSE information that has a dependency with thesystem tool.
IEC 61850 engineering with PCM600, PCM600 IEC 61850 Configuration tool and IET600
PCM600:
• When an IED is instantiated, its place in the plant structure creates the correspondingstructure in the substation section in SCL. The communication facilities is also created inthe communication section.
• The functionality of the IED is configured by using ACT in PCM600. For each function, thecorresponding logical device and logical node(s) is created in the IED section togetherwith its type definition in data type template section
• The above forms the IED capabilities from a communication perspective and will then beincluded in the file exported from PCM600 as SCD, ICD, IID and CID file
PCM600: IEC 61850 Configuration tool
• Included in PCM600 is the new IEC 61850 Configuration tool which allows the user todefine data sets and control blocks for both Client Server and GOOSE communication.
• The IEC 61850 Configuration tool gives the user the possibility to make the IEC 61850engineering without export / import step.
It does NOT however allow the User to define the substation part.
IET600:
• Open a SCD file or import/merge a SCD, ICD or CID file for the particular IED(s).• For each IED, the user defines the datasets, the control blocks for reporting (this means
unbufffered/buffered reporting and GOOSE) and the properties for each report controlblock.
1MRK511349-UEN A Section 3Substation Configuration description Language (SCL)
15Communication protocol manual
Data sets (DS) are generated automatically in PCM600. Report controlblocks (RCBs) are not generated automatically in PCM600.
• If client definitions (like client. ICD) are required in the system configuration, they aremerged into IET600 and connected to the unbuffered/buffered report control blocks.
• Logical nodes, which are not related to the conducting equipment, must be included in thebay level in the substation section.
• The resulting SCD file is exported from IET600.
PCM600:
Define the inputs for the client in IET600 and cross-reference the signals in SMT. Import theSCD file to PCM600 to receive GOOSE data. For each IED that shall receive GOOSE information,the received data is connected to the applications using SMT in PCM600.To be able to importscd-file to PCM600 61850 engineering in PCM must be set to disabled.
If input signals are not defined for clients in IET600, they will not be visible inSMT. Inputs (GOOSE clients) can also be defined in PCM600.
3.5 Engineering concept in IEC 61850-6GUID-FFE87459-FBC1-4D85-A6B3-7BD6F576ECE4 v3
• Top-down approach means that the system engineering tool has ICD files available foreach IED to be included in the system configuration. The ICD files may be of the templatetype and represent a pre-configured IED.
….IED A IED B IED Z
Client A Client B
IEDtool
Systemtool
IEC09000151-1-en.vsdIEC09000151 V1 EN-US
Figure 5: Relation between system and IED tools
Section 3 1MRK511349-UEN ASubstation Configuration description Language (SCL)
16Communication protocol manual
Section 4 Communication profile
GUID-25495333-A2B7-44A7-908D-68EC06694AD5 v6
The IEC 61850 standard is conceptually written to be independent of an existingcommunication media and message transmission concept. Out of this, a specificcommunication profile is decided and has been commonly used. The profile contains:
• Ethernet as the media• TCP/IP• ISO session and presentation layer• MMS (Manufacturing Message Specification (ISO 9506-1 and ISO 9506-2)
The IEC 61850 standard describes its requested services in ACSI, which is contained in part 7-2of the standard. The mapping to the MMS for all aspects of services and Ethernet usage isspecified in part 8-1 of IEC 61850.
Each device manufacturer, which is a partner of an IEC 61850 based communication network,has to take these two specifications and adapt their respective product to the requirementsand definitions given in the standard. To make this profile visible to all other partners, so theycan check what they can expect and what they have to support, the PICS document is defined.The PICS contains in a table based form the possibility of a product or product family.
IED (server)(61850 services; part 7-2)
Communication(MMS services; part 8-1)
- Access Point (AP) / Address- GSE
IEC08000179.vsd
AP
IED (client)(61850 services; part 7-2)
Subnetwork
IED (server)(61850 services part; 7-2)
Communication(MMS services; part 8-1)
Communication(MMS services; part 8-1)
- Access Point (AP) / Address- GSE
- Access Point (AP) / Address- GSE
IEC08000179 V1 EN-US
Figure 6: IEC 61850 Protocol: related standards for communication
1MRK511349-UEN A Section 4Communication profile
17Communication protocol manual
SV GOOSE TimeSync(SNTP) MMS Protocol Suite GSSE
TCP/IPT-Profile
ISO COT-Profile
ISO/IEC 8802-2 LLC
GSSET-ProfileUDP/IP
ISO/IEC 8802-3 Ethertype
SampledValues(Multicast)
GenericObjectOrientedSubstationEvent
TimeSync
CoreACSIServices
GenericSubstationStatusEvent
ISO/IEC 8802-3
IEC09000153-1-en.vsdIEC09000153 V1 EN-US
Figure 7: Overview of functionality and profiles according to IEC 61850-8-1
Out of this content, the implementation supports:
• Sampled values according to 9-2LE• GOOSE• TimeSync using SNTP• The peer-to-peer/vertical communication using MMS protocol suite with the T-profile
TCP/IP
For each of the above, the resulting underlying protocols as stated in Figure 7.
See the PICS and PIXIT for more information.
Section 4 1MRK511349-UEN ACommunication profile
18Communication protocol manual
Section 5 Supported services
GUID-E08C91D7-A59B-478B-B39A-26E786591E2A v7
IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describes how the servicesare applied in the communication. The conformance documents contain the description of thesupported services in the IED.
Services that are not mentioned in this chapter or in the conformance document are notsupported by the IED.
Data set
Define data sets by the SCD description.
Create data sets under LD0/LLN0.
For more information on data sets, see the PIXIT-related documents.
Substitution
Substitution is supported for the respective DATA, according to IEC 61850-7-4, that have thesubstitution attributes defined.
Setting group control block
There is only one setting group control block, which is located in LD0/LLN0 (Logical Device0/Logical Node 0).
The Setting range is expressed in the minVal and maxVal data attributes (DAs) in each settingdata object (DO). When writing settings a check will be done to compare the new value withthe minVal and maxVal attributes, when applicable (this depends on the data type and if theminVal and maxVal are mapped). So if the minVal and maxVal is not mapped, all values in therange of the data type will be accepted. If the written value is outside the range, Object-Value-Invalid will be returned to the client.
Note that the actual number of used setting groups is defined by theparameter MaxNoSetGRP in the function SETGRPS, which is configured in PSTin PCM600. But six setting groups is the maximum and it cannot be exceeded.
Setting parameter values via IEC 61850 Edition 2
Some parameters values can be set over IEC 61850 Edition 2 communication, provided that theparameter Enable61850Setting has been set to Enabled in Main menu/Configuration/Communication/Station communication/IEC61850–8–1/IEC61850–8–1:1/EnableSettings byPCM600 or in the LHMI.
1MRK511349-UEN A Section 5Supported services
19Communication protocol manual
IEC15000002-1-en.vsdIEC15000002 V1 EN-US
Figure 8: Enabling parameter setting via IEC 61850
Setting parameter values over the communication link doesn't require anyauthorization if Enable61850Setting has been set to Enabled.
Write to parameters with functional constraint (FC) = SP
• Issue: write to parameter
Writes to parameters where (FC) = SP should not be done while there is anongoing setting group edit session.
Write to parameters with functional constraint FC = SE
• Issue: write to SelectEditSG(n). (n) is the setting group• Issue: write to one or several parameters• Issue: write to ConfirmEditSG (CnfEdit=TRUE)
If a second SelectEditSG(n) is issued where n differs from the actual, anysetting changes are discarded and a new edit session is started.
Cancellation of an ongoing edit session. there are two ways to cancel an ongoing editsession:
Section 5 1MRK511349-UEN ASupported services
20Communication protocol manual
• Issue: write to ConfirmEditSG (CnfEdit=FALSE)
or
• Issue: write to SelectEditSG(0)
Reading values where FC = SP
• Issue: read from parameter
Report control block
For properties about report control blocks, see PIXIT.
UnBuffered reporting as well as Buffered reporting is supported.
Generic object oriented substation event (GOOSE)
The structured GOOSE is supported. This means that the data sets can be defined with FCDAas well as explicit attributes.
Note that the data sets that are used or referred to by GOOSE control blockscan only include a data attribute once. In other words, there may not be thesame data attribute in more than one data set.
When publishing a measured value, the user must take care of which measured value dataattributes are added to a data set. If the measured value is event-handled (like in the case ofMMXU functions), then one can add that value directly to the data set. If the value is not event-handled, (like in the case of Synchrocheck function), it is recommended to connect the valuedesired to be published to a MVGAPC function block (in ACT) and then use the measured valuegiven by the MVGAPC.
Example of functions that have event-handled measured values (can be added directly to thedata set).
• CVMMXN - Measurements• CMMXU - Phase current measurement• VMMXU - Phase-phase voltage measurement• CMSQI - Current sequence component measurement• VMSQI - Voltage sequence measurement• VNMMXU - Phase-neutral voltage measurement• MVGAPC - IEC 61850 generic communication I/ O functions
Generic function blocks are provided to make available to the 61850 bus signals that are notdefined inside any of the available function blocks. Example of such functions include:
• SPGAPC - IEC 61850 generic communication I/ O functions• DPGAPC - IEC 61850 generic communication I/ O functions• MVGAPC - IEC 61850 generic communication I/ O functions
Control
Of the different control sequences, the ‘direct-with-normal-security’ and ‘SBO-with-enhanced’security are supported (defined by the ctlModel parameter, IEC 61850-7-2).
1MRK511349-UEN A Section 5Supported services
21Communication protocol manual
Check bits; interlock check and synchrocheck check, are only valid for LN types based uponCSWI class.
Verification of Originator Category is supported, see also PIXIT.
Section 5 1MRK511349-UEN ASupported services
22Communication protocol manual
Section 6 Data sets and control blocks
6.1 Data setsSEMOD129786-5 v7
IEC 61850 has defined data sets and report control blocks to transmit signals for monitoringpurposes. Data sets are also used for GOOSE messages in horizontal communication amongIEDs. The project defines the data objects or single data attributes that should be collected ina data set. Figure 9 shows a data set where all position information of the apparatuses of abay are put into one data set.
PCM600 will generate default data sets, based on the current ACT configuration. The defaultdata sets can be modified or removed in the engineering tools. No RCBs are createdautomatically by PCM600. However, the configured IEDs are delivered with RCBs for all defaultthe data sets.
Figure 9: IEC 61850–7–2: Example of a data set for MMS
General rules for data set configuration:
• All data objects or their data attributes can be selected for a data set.• Only those data attributes of a data object can/will be selected which have the same
function constraint (FC).• Data objects with different FC can be selected for a data set. For example, DOs with FC =
ST and DOs with FC=MX can be member in one data set.• A single data attribute can be selected when it is specified with a trigger option. For
example, the data attribute stVal of the data object Pos can be selected as a member of adata set, because it is specified with the trigger option data change detected (dchg).
The description of the data sets with name and the list of data object members (FCDAs isincluded in the SCL file in the IED section in the Logical device subsection. As specified in IEC61850–7–2 clause 9, the data sets are part of a logical node. They are most likely included in theLLN0.
6.2 Report control block (URCB/BRCB)SEMOD129786-17 v5
To be able to transmit the signals configured in a DataSet, a report control block must beconfigured to handle and specify how the events are transmitted to the clients. There are twotypes of report control blocks; unbuffered and buffered. The buffered report control blockstores the events during a communication interrupt, while the unbuffered is sent upon datachange and not stored during interruption.
The content of a BRCB is listed in IEC 61850-7-2 in clause 14. The BRCB contains manyattributes which are of interest to handle and secure the communication between the clientand the server and may be set once as default in a project. Others are of application interest inthe way events are handled in a project.
• Buffer time (valid only for BRCB)
• This parameter describes how long the report should wait for other expected eventsbefore it sends the report to the client. When it is known, that additional events aregenerated as a follow up, it is useful to wait, for example, 500 ms for additionalevents stored in the report. This feature reduces the number of telegramstransmitted in case of a burst of changes. Parameter IEC61850BufTimEnable
1MRK511349-UEN A Section 6Data sets and control blocks
23Communication protocol manual
enables/disables the buffer time. For more information, refer section IEC 61850-8-1communication protocol in Technical manual.
• Trigger options
• The data attributes know three different trigger options (dchg, qchg, dupd). Withinthe BRCB, the two other can be defined (integrity and general interrogation). Theattribute Trigger option is a multiple choice and allows to mask the supportedtrigger options in this BRCB.
• Integrity period
• When integrity is selected in the trigger option attribute, it is needed to define anintegrity period to force the transmission of all data listed in the DataSet. This isdone by the attribute Integrity period. This feature can be used as a backgroundcycle to ensure that the process image in all partners is the same.
• General interrogation
• A general interrogation is only done on request from a client. Not all Data-sets maycontain information which is needed for a general update of the client. For exampledata with T(ransient) = TRUE are not part of a GI. When the BRCB attribute generalinterrogation is set to TRUE a GI request from the client will be handled. The reporthandler will transmit all data defined in the Data-set with their actual values. The IEC61850 standard defines that all buffered events shall be transmitted first before theGI is started. A running GI shall be stopped and a new GI shall be started, when a newGI request is received while a GI is running.
• Purge buffer (valid only for BRCB)
• This BRCB attribute can be used by a client to clean the event buffer from old events.The events are discarded on request of the client. This feature can be used to deleteold events not transmitted to the client due to stopped communication. After thelink is reestablished the client can decide to clean the buffer or to receive the history.
Trigger Options
IEC 61850 has defined in total five different TrgOp. Three of them belonging to data attributesand marked per data attribute in the column TrgOp of the CDC tables in part 7–3. The othertwo belonging to the configuration of control blocks.
• dchg = data-change
• Whenever a process value has changed its value either binary or a measurement atransmission is done.
• qchg = quality change
• Looking to the possibilities of the quality data attribute type (q) any changes in thequality description will be transmitted.
• dupd = data value update
• This trigger option give the possibility to define that a transmission should be doneon a condition which can be controlled by the application.
• integrity
• This trigger forces the transmission of all process values defined in the data setwhen a timer value (the integrity period) expires.
• general interrogation
• This trigger is forced by the clients (= station level IED; NCC gateway, stationHMI, ...). Normally a GI is asked for, when the client and the server start or restart asession. When the client is able to receive the actual values and when the logicaldevice has scanned all process values at least once, an image of the actual processsignal status can be transmitted to the client.
Section 6 1MRK511349-UEN AData sets and control blocks
24Communication protocol manual
Note that the possible trigger options for each attribute are includedand defined in the datatype template section in SCL.
Link BRCB to a client LN
The BRCB has to know to whom the events shall be transmitted. This is the signal routingengineering step. The IEC standard 61850–6 describes that this is given by including the LN ofthe client IED in the ReportBlockEnabled option.
The selected client IED with the corresponding LN, for example, ITCI is included in the SCLstructure of the Report Control description of the IED section.
The description of the BRCB with selected DataSet, configured parameters and selected IEDsis included in the SCL file in the IED section in the LN0 structure for the LD where this LN0belongs to.
1MRK511349-UEN A Section 6Data sets and control blocks
25Communication protocol manual
6.3 GOOSE Control Blocks (GoCB)SEMOD129786-83 v6
en06000109.vsd
Send
Data-set
Rec
eive
Rec
eive
LN
LN
LNLN
LN
Send
Data-set
Rec
eive
Rec
eive
LNLN
LN LN
Send
Data-set
Rec
eive
Rec
eive
LN
LNLN
LNLN
LN
Subnetwork
LN0
GoCB
DataSet
InputGoCBGoCB
DataSetDataSet
InputInput
Comm.GSE
LD0
Server
LN0
GoCB
DataSet
InputGoCBGoCB
DataSetDataSet
InputInput
Comm.GSE
LD0
Server
IEC06000109 V2 EN-US
Figure 10: IEC 61850: Principle operation of GOOSE messages
The Generic Object Oriented Substation Event (GOOSE) class model is used to distribute inputand output data values between IEDs on bay level (in horizontal direction) through the use ofmulticast services. GOOSE messages enable fast transmission from a publisher to one orseveral subscribers (receivers).
The GOOSE service model of IEC 61850-7-2 provides the possibility for fast and reliablesystem-wide distribution of input and output data values. This implementation uses a specificscheme of re-transmission to achieve the appropriate level of reliability. When a GOOSE servergenerates a SendGOOSEMessage request, the current data set values are encoded in a GOOSEmessage and transmitted on the multicast association. The event that causes the server toinvoke a SendGOOSE service is a local application issue as defined in IEC 61850-7-2. Eachupdate may generate a message in order to minimize throughput time.
Additional reliability is achieved by re-transmitting the same data (with gradually increasingSqNum and retransmission time).
Section 6 1MRK511349-UEN AData sets and control blocks
26Communication protocol manual
T0 retransmission in stable conditions (no event for a long time)
(T0) retransmission in stable conditions may be shortened by an event
T1 shortest retransmission time after the event
T2, T3 retransmission times until achieving the stable conditions time
Time of transmission
T0 (T0) T1 T1 T2 T3 T0
eventIEC09000152-1-en.vsd
IEC09000152 V1 EN-US
Figure 11: Transmission time for events
Each message in the retransmission sequence carries a timeAllowedToLive parameter thatinforms the receiver of the maximum time to wait for the next re-transmission. If a newmessage is not received within that time interval, the receiver assumes that the association islost. The specific intervals used by any GOOSE publisher are a local issue. ThetimeAllowedtoLive parameter informs subscribers of how long to wait.
The GOOSE message concept is used for all application functions where two or more IEDs areinvolved. Typical example is the station-wide interlocking procedure or breaker failureprotection.
Figure 10 shows the GOOSE concept for three IEDs which interchange GOOSE messagesbetween each other.
To send GOOSE messages a GoCB must be defined and a data set is needed that contains thedata objects of single data attributes to be sent.
A GOOSE message is forced to be transmitted when a trigger change is detected for a dataattribute. All members of the data set are copied in the send buffer with their actual value andthe message is sent. The subscribers, who knows the address of this GOOSE message,receives the telegram. The GOOSE message includes a sequence number to verify that allmessages are received.
1MRK511349-UEN A Section 6Data sets and control blocks
27Communication protocol manual
28
Section 7 Logical node data model
GUID-EFBB8957-ABA9-4B25-B1CC-630B892A3FC7 v3
The data model used by IEC 61850 is based on logical nodes containing a set of data objects.The data model is defined in the standards.
• IEC 61850-7-4 Compatible logical node classes and data classes• IEC 61850-7-3 Common data classes
The standard describes only classes of logical nodes and data objects on one side andcommon data classes for the data object attributes. Also here it is given has the elements inthese classes are defined as:
• Mandatory (M)• Optional (O)• Conditional optional (Cxxx)• In addition, the IEC 61850 states rules for adding vendor-specific definitions to the
standard, in order to cope with extra functionality.
The possible description of the data model according to the standard allows to adapt a logicalnode of a LN class to that what the product is supporting or using for this LN. This definitionof what parts of a class is used in the actual product and possible addition is called a type,according to IEC 61850-6. There are LN types based upon LN classes. The LN type attributesare called Data Objects (or DATA) and are in of DO types, base upon respective CDC class. Thisallows all partners in the IEC 61850 project who need this LN to understand the LN in all detailsfor the communication part.
The IEC 61850 standard does not describe the functionality and way of operation. Eachsupplier has to describe this separately. ABB has described their function blocks thatrepresent a logical node and all other function blocks in the technical manuals. This chapter inthe communication protocol manual has two purposes:
• Describe the Logical Node types and their data object attribute types.• Make the link to the description of the function block.
7.1 Common data objects in each logical nodeGUID-8400E43A-6199-4539-BB74-CAC865C85508 v3
The IEC 61850 standard describes in part 7-5, a Common Logical Node. The data objectscontained in that LN are both mandatory and optional. The mandatory data objects have to beincluded in each LN. This clause describes the general handling of the data objects in the IEDs.
The mandatory data objects as defined in IEC 61850-7-4 as part of the Common Logical Nodeare Mode, Behavior, Health and NamePlate.
Mode
The operation modes ON (enabled) and BLOCKED are supported remotely by a command orlocally from the LHMI of the IED.
If the setting “RemoteModControl” is set to “Off” (default), all remote writes toMod will be rejected.
Behaviour
1MRK511349-UEN A Section 7Logical node data model
29Communication protocol manual
The operational mode as given by the Mode control is shown in the data object Beh accordingto priority rules described for Beh in clause 6 of IEC 61850-7-4.
The Beh shows the actual state of the function depending on the hierarchy described in clause6 of IEC 61850-7-4.
It is possible that the behavior is influenced also by other sources independent from the Mod,for example Insertion of the test handle, loss of SV, IED configuration tool (PCM600), or LHMI.
In case the setting “operation” of a function is set to Off from the LHMI or PCM600, the Behwill be set to Off independent of the value of the Mod.
The state Off can be set from the LHMI or the PCM600 for the functions having the setting“operation”.
Health
Health will reflect the current status of the IED HW and configuration. Possible values are: OK,Warning, and Alarm.
Health indicates OK, Warning, or Alarm, depending on the IED status.
NamePlt
The name of the logical node and its relation to namespace definition are shown in the dataobject NamePlt as specified for the SCL structure.
7.2 Logical nodes for control
7.2.1 Bay control CBAY
7.2.1.1 Bay control QCBAYGUID-2BD411B4-2371-4B97-8D8D-DB632B15BC85 v1
PID-4086-LOGICALNODEDATA v3
QCBAY (revision 1) Q CBAY
Table 1:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
30Communication protocol manual
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
LocSwPos v1_dINS stVal ST - - Mon Position of the Local/Remoteswitch
q ST - - Mon Quality: Position of the Local/Remote switch
t ST - - Mon Timestamp: Position of theLocal/Remote switch
SrcOpPrm v1_dINS stVal ST - PSTO Mon Value for the operator placeallocation
q ST - PSTO Mon Quality: Value for the operatorplace allocation
t ST - PSTO Mon Timestamp: Value for theoperator place allocation
BlkCmd v1_dSPC Oper.ctlVal CO - - Cmd Special block command valueused for blockCommand
Oper.origin.orCat CO - - Cmd Special block command valueused for blockCommand
Oper.origin.orIdent CO - - Cmd Special block command valueused for blockCommand
Oper.ctlNum CO - - Cmd Special block command valueused for blockCommand
Oper.T CO - - Cmd Special block command valueused for blockCommand
Oper.Test CO - - Cmd Special block command valueused for blockCommand
Oper.Check CO - - Cmd Special block command valueused for blockCommand
stVal ST - CMD_BLKD Mon Function is blocked forcommands
q ST - CMD_BLKD Mon Quality: Function is blocked forcommands
t ST - CMD_BLKD Mon Timestamp: Function isblocked for commands
BlkUpd v1_dSPC Oper.ctlVal CO - - Cmd Special block command valueused for blockUpdate
Oper.origin.orCat CO - - Cmd Special block command valueused for blockUpdate
Oper.origin.orIdent CO - - Cmd Special block command valueused for blockUpdate
Oper.ctlNum CO - - Cmd Special block command valueused for blockUpdate
Oper.T CO - - Cmd Special block command valueused for blockUpdate
Oper.Test CO - - Cmd Special block command valueused for blockUpdate
Oper.Check CO - - Cmd Special block command valueused for blockUpdate
stVal ST - UPD_BLKD Mon Update of position is blocked
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
31Communication protocol manual
BlkUpd v1_dSPC q ST - UPD_BLKD Mon Quality: Update of position is
blocked
t ST - UPD_BLKD Mon Timestamp: Update of positionis blocked
BlkMeas v1_dSPS stVal ST - - Mon Update of measurand isblocked
q ST - - Mon Quality: Update of measurandis blocked
t ST - - Mon Timestamp: Update ofmeasurand is blocked
Loc v1_dSPS stVal ST - LOC Mon Local operation allowed
q ST - LOC Mon Quality: Local operationallowed
t ST - LOC Mon Timestamp: Local operationallowed
Rem v1_dSPS stVal ST - REM Mon Remote operation allowed
q ST - REM Mon Quality: Remote operationallowed
t ST - REM Mon Timestamp: Remote operationallowed
7.2.2 Switch controller CSWI
7.2.2.1 Switch controller SCSWIGUID-4F40A4BA-6781-41BF-8389-D8EFD791D005 v1
PID-3955-LOGICALNODEDATA v1
SCSWI (revision 1) S CSWI
Table 2:
Pos a_dDPC Cancel.ctlVal CO - - Cmd Command parameter forIEC61850
Cancel.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
SBOw.ctlVal CO - - Cmd Command parameter forIEC61850
SBOw.origin.orCat CO - - Cmd Command parameter forIEC61850
SBOw.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Cancel.origin.orIdent CO - - Cmd Command parameter forIEC61850
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
32Communication protocol manual
Pos a_dDPC Cancel.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
SBOw.ctlNum CO - - Cmd Command parameter forIEC61850
SBOw.T CO - - Cmd Command parameter forIEC61850
Cancel.T CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Cancel.Test CO - - Cmd Command parameter forIEC61850
SBOw.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SBOw.Check CO - - Cmd Command parameter forIEC61850
stVal ST - POSITION Mon Position indication
q ST - POSITION Mon Quality: Position indication
t ST - POSITION Mon Timestamp: Position indication
stSeld ST - SELECTED Mon Select conditions are fulfilled
subEna SV - - - Substitute enable
subVal SV - - - Substituted double positionvalue
ctlModel CF - CtlModel - Specifies control model type
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
33Communication protocol manual
OpCls b_dACT general ST T EXE_CL Mon Execute command for closedirection
q ST T EXE_CL Mon Quality: Execute command forclose direction
t ST T EXE_CL Mon Timestamp: Execute commandfor close direction
OpOpn b_dACT general ST T EXE_OP Mon Execute command for opendirection
q ST T EXE_OP Mon Quality: Execute command foropen direction
t ST T EXE_OP Mon Timestamp: Execute commandfor open direction
BlkCmd v1_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - CMD_BLK Mon Commands are blocked
q ST - CMD_BLK Mon Quality: Commands are blocked
t ST - CMD_BLK Mon Timestamp: Commands areblocked
7.3 Logical nodes for conversion functions
7.3.1 Integer to Boolean converter FCVB
7.3.1.1 Integer to Boolean 16 conversion with logic node representationSEMOD158419-1 v3
PID-3627-LOGICALNODEDATA v3
IB16FCVB (revision 0) IB16 FCVB
Table 3:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
34Communication protocol manual
Mod a_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
ISCSO b_dINC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
stVal ST - - Mon Integer to be converted to bitpattern OUT1 to OUT16
q ST - - Mon Quality: Integer to be convertedto bit pattern OUT1 to OUT16
t ST - - Mon Timestamp: Integer to beconverted to bit pattern OUT1to OUT16
ctlModel CF - - - Used by CH
7.3.2 Boolean to integer converter FCVI
7.3.2.1 Boolean to integer conversion with logical node representation, 16 bitBTIGAPC
SEMOD175753-1 v4
PID-6944-LOGICALNODEDATA v2
LN type LN prefix LN class Function block name
B16IFCVI (revision 0) B16I FCVI BTIGAPC
1MRK511349-UEN A Section 7Logical node data model
35Communication protocol manual
Table 4: BTIGAPC Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviourparameter
OutInt b_dINS stVal ST - OUT Mon Output value
q ST - OUT Mon Quality: Output value
t ST - OUT Mon Timestamp: Output value
7.4 Logical nodes for protection functions
7.4.1 Protection trip conditioning PTRC
7.4.1.1 Logic for group alarm ALMCALHPID-6510-LOGICALNODEDATA v1
LN type LN prefix LN class Function block name
ALMCALH (revision 1) ALM CALH ALMCALH
Table 5: ALMCALH Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
36Communication protocol manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviourparameter
GrAlm a_dSPS stVal ST - ALARM Mon OR function betweeen inputs 1to 16
q ST - ALARM Mon Quality: OR function betweeeninputs 1 to 16
t ST - ALARM Mon Timestamp: OR functionbetweeen inputs 1 to 16
7.4.1.2 Logic for group indication INDCALHPID-6511-LOGICALNODEDATA v1
LN type LN prefix LN class Function block name
INDCALH (revision 1) IND CALH INDCALH
Table 6: INDCALH Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviourparameter
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
37Communication protocol manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
GrAlm a_dSPS stVal ST - IND Mon OR function betweeen inputs 1to 16
q ST - IND Mon Quality: OR function betweeeninputs 1 to 16
t ST - IND Mon Timestamp: OR functionbetweeen inputs 1 to 16
7.4.1.3 Tripping logic common 3-phase output SMPPTRCGUID-B56D86A1-47D9-4B45-A90B-B622C3AE5D2D v2
PID-6907-LOGICALNODEDATA v2
LN type LN prefix LN class Function block name
SMPPTRC (revision 3) SMP PTRC SMPPTRC
Table 7: SMPPTRC Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Str a_dACD general ST - START Mon Common start signal
dirGeneral ST - - Mon Common direction signal
phsA ST - STL1 Mon Start signal from phase L1
dirPhsA ST - - Mon Direction signal from phase L1
phsB ST - STL2 Mon Start signal from phase L2
dirPhsB ST - - Mon Direction signal from phase L2
phsC ST - STL3 Mon Start signal from phase L3
dirPhsC ST - - Mon Direction signal from phase L3
q ST - START Mon Quality: Common start signal
t ST - START Mon Timestamp: Common startsignal
Op a_dACT general ST - TRIP Mon General trip output signal
phsA ST - TRL1 Mon Trip signal from phase L1
phsB ST - TRL2 Mon Trip signal from phase L2
phsC ST - TRL3 Mon Trip signal from phase L3
q ST - TRIP Mon Quality: General trip outputsignal
t ST - TRIP Mon Timestamp: General trip outputsignal
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
38Communication protocol manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
LORs v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SPTr v1_dSPS stVal ST - TR1P Mon Tripping single-pole
q ST - TR1P Mon Quality: Tripping single-pole
t ST - TR1P Mon Timestamp: Tripping single-pole
TwoPTr v1_dSPS stVal ST - TR2P Mon Tripping two-pole
q ST - TR2P Mon Quality: Tripping two-pole
t ST - TR2P Mon Timestamp: Tripping two-pole
TPTr v1_dSPS stVal ST - TR3P Mon Tripping three-pole
q ST - TR3P Mon Quality: Tripping three-pole
t ST - TR3P Mon Timestamp: Tripping three-pole
ClsLO v1_dSPS stVal ST - CLLKOUT Mon Circuit breaker lockout output(set until reset)
q ST - CLLKOUT Mon Quality: Circuit breaker lockoutoutput (set until reset)
t ST - CLLKOUT Mon Timestamp: Circuit breakerlockout output (set until reset)
7.4.1.4 Logic for group warning WRNCALHPID-6512-LOGICALNODEDATA v1
LN type LN prefix LN class Function block name
WRNCALH (revision 1) WRN CALH WRNCALH
1MRK511349-UEN A Section 7Logical node data model
39Communication protocol manual
Table 8: WRNCALH Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviourparameter
GrAlm a_dSPS stVal ST - WARNING Mon OR function betweeen inputs 1to 16
q ST - WARNING Mon Quality: OR function betweeeninputs 1 to 16
t ST - WARNING Mon Timestamp: OR functionbetweeen inputs 1 to 16
7.4.2 Multipurpose analog protection GAPC
7.4.2.1 General currrent and voltage protection CVGAPCPID-3857-LOGICALNODEDATA v1
GF2LLN0 instance 1 (revision 0) - LLN0
GF2MMXN instance 1 (revision 3) GF2 MMXN
GF2PHAR instance 1 (revision 2) GF2 PHAR
GF2PTOV instance 1 (revision 2) GF2 PTOV
GF2PTOV instance 2 (revision 2) GF2 PTOV
GF2PTUC instance 1 (revision 2) GF2 PTUC
GF2PTUC instance 2 (revision 2) GF2 PTUC
GF2PTUV instance 1 (revision 2) GF2 PTUV
GF2PTUV instance 2 (revision 2) GF2 PTUV
GF2PVOC instance 1 (revision 2) GF2 PVOC
GF2PVOC instance 2 (revision 2) GF2 PVOC
PH1PTRC instance 1 (revision 3) PH1 PTRC
Section 7 1MRK511349-UEN ALogical node data model
40Communication protocol manual
Table 9:
Mod aINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh aINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
IvdCrv v1SPS stVal ST - - Mon Error signal from overcurrentfunctions
q ST - - Mon Quality: Error signal fromovercurrent functions
t ST - - Mon Timestamp: Error signal fromovercurrent functions
UnVBehMem v1SPS stVal ST - Mon Low voltage for directionalpolarization
q ST - Mon Quality: Low voltage fordirectional polarization
t ST - Mon Timestamp: Low voltage fordirectional polarization
Table 10:
Beh aINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Amp bMV mag.f MX - CURRENT Mon Measured current value
q MX - CURRENT Mon Quality: Measured current value
t MX - CURRENT Mon Timestamp: Measured currentvalue
Vol bMV mag.f MX - VOLTAGE Mon Measured voltage value
q MX - VOLTAGE Mon Quality: Measured voltage value
t MX - VOLTAGE Mon Timestamp: Measured voltagevalue
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
41Communication protocol manual
Mod cINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
AmpPwrFact v2MV mag.f MX - ICOSFI Mon Measured current multipliedwith cos (Phi)
q MX - ICOSFI Mon Quality: Measured currentmultiplied with cos (Phi)
t MX - ICOSFI Mon Timestamp: Measured currentmultiplied with cos (Phi)
VolAmpAng v2MV mag.f MX - Mon Angle between voltage andcurrent
q MX - Mon Quality: Angle between voltageand current
t MX - Mon Timestamp: Angle betweenvoltage and current
Table 11:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - BLK2ND Mon Block from second harmonicdetection
q ST - BLK2ND Mon Quality: Block from secondharmonic detection
t ST - BLK2ND Mon Timestamp: Block from secondharmonic detection
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Table 12:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon Start signal from overvoltagefunction OV1
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
42Communication protocol manual
Str b_dACD q ST - Mon Quality: Start signal from
overvoltage function OV1
t ST - Mon Timestamp: Start signal fromovervoltage function OV1
Op b_dACT general ST T TROV1 Mon Trip signal from overvoltagefunction OV1
q ST T TROV1 Mon Quality: Trip signal fromovervoltage function OV1
t ST T TROV1 Mon Timestamp: Trip signal fromovervoltage function OV1
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Table 13:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon Start signal from overvoltagefunction OV2
q ST - Mon Quality: Start signal fromovervoltage function OV2
t ST - Mon Timestamp: Start signal fromovervoltage function OV2
Op b_dACT general ST T TROV2 Mon Trip signal from overvoltagefunction OV2
q ST T TROV2 Mon Quality: Trip signal fromovervoltage function OV2
t ST T TROV2 Mon Timestamp: Trip signal fromovervoltage function OV2
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
1MRK511349-UEN A Section 7Logical node data model
43Communication protocol manual
Table 14:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon Start signal from undercurrentfunction UC2
q ST - Mon Quality: Start signal fromundercurrent function UC2
t ST - Mon Timestamp: Start signal fromundercurrent function UC2
Op b_dACT general ST T TRUC2 Mon Trip signal from undercurrentfunction UC2
q ST T TRUC2 Mon Quality: Trip signal fromundercurrent function UC2
t ST T TRUC2 Mon Timestamp: Trip signal fromundercurrent function UC2
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Table 15:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon Start signal from undercurrentfunction UC1
q ST - Mon Quality: Start signal fromundercurrent function UC1
t ST - Mon Timestamp: Start signal fromundercurrent function UC1
Op b_dACT general ST T TRUC1 Mon Trip signal from undercurrentfunction UC1
q ST T TRUC1 Mon Quality: Trip signal fromundercurrent function UC1
t ST T TRUC1 Mon Timestamp: Trip signal fromundercurrent function UC1
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Section 7 1MRK511349-UEN ALogical node data model
44Communication protocol manual
Table 16:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon Start signal from undervoltagefunction UV1
q ST - Mon Quality: Start signal fromundervoltage function UV1
t ST - Mon Timestamp: Start signal fromundervoltage function UV1
Op b_dACT general ST T TRUV1 Mon Trip signal from undervoltagefunction UV1
q ST T TRUV1 Mon Quality: Trip signal fromundervoltage function UV1
t ST T TRUV1 Mon Timestamp: Trip signal fromundervoltage function UV1
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Table 17:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon Start signal from undervoltagefunction UV2
q ST - Mon Quality: Start signal fromundervoltage function UV2
t ST - Mon Timestamp: Start signal fromundervoltage function UV2
Op b_dACT general ST T TRUV2 Mon Trip signal from undervoltagefunction UV2
q ST T TRUV2 Mon Quality: Trip signal fromundervoltage function UV2
t ST T TRUV2 Mon Timestamp: Trip signal fromundervoltage function UV2
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
1MRK511349-UEN A Section 7Logical node data model
45Communication protocol manual
Table 18:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon Start signal from overcurrentfunction OC2
dirGeneral ST - DIROC2 Mon Directional mode of OC2(nondir, forward,reverse)
q ST - Mon Quality: Start signal fromovercurrent function OC2
t ST - Mon Timestamp: Start signal fromovercurrent function OC2
Op b_dACT general ST T TROC2 Mon Trip signal from overcurrentfunction OC2
q ST T TROC2 Mon Quality: Trip signal fromovercurrent function OC2
t ST T TROC2 Mon Timestamp: Trip signal fromovercurrent function OC2
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
IvdCrv v1_dSPS stVal ST - - Mon Error signal from overcurrentfunction OC2
q ST - - Mon Quality: Error signal fromovercurrent function OC2
t ST - - Mon Timestamp: Error signal fromovercurrent function OC2
Table 19:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon Start signal from overcurrentfunction OC1
dirGeneral ST - DIROC1 Mon Directional mode of OC1(nondir, forward,reverse)
q ST - Mon Quality: Start signal fromovercurrent function OC1
t ST - Mon Timestamp: Start signal fromovercurrent function OC1
Op b_dACT general ST T TROC1 Mon Trip signal from overcurrentfunction OC1
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
46Communication protocol manual
Op b_dACT q ST T TROC1 Mon Quality: Trip signal from
overcurrent function OC1
t ST T TROC1 Mon Timestamp: Trip signal fromovercurrent function OC1
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
IvdCrv v1_dSPS stVal ST - - Mon Error signal from overcurrentfunction OC1
q ST - - Mon Quality: Error signal fromovercurrent function OC1
t ST - - Mon Timestamp: Error signal fromovercurrent function OC1
Table 20:
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Str b_dACD general ST - Mon General start signal
q ST - Mon Quality: General start signal
t ST - Mon Timestamp: General startsignal
Op b_dACT general ST - TRIP Mon General trip signal
q ST - TRIP Mon Quality: General trip signal
t ST - TRIP Mon Timestamp: General trip signal
Mod c_dINC stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
7.5 System logical nodes
7.5.1 Generic security application component
7.5.1.1 Generic security application component AGSALPID-7016-LOGICALNODEDATA v2
LN type LN prefix LN class Function block name
AGSAL instance 1 (revision 2) A GSAL AGSAL
SECLLN0 instance 1 (revision 1) - LLN0 AGSAL
1MRK511349-UEN A Section 7Logical node data model
47Communication protocol manual
Table 21: AGSAL Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
AcsCtlFail a_dSEC cnt ST - - Mon Mapping tag
t ST - - Mon Timestamp: Mapping tag
AuthFail a_dSEC cnt ST - - Mon Mapping tag
t ST - - Mon Timestamp: Mapping tag
Ina a_dSEC cnt ST - - Mon Mapping tag
t ST - - Mon Timestamp: Mapping tag
SvcViol a_dSEC cnt ST - - Mon Mapping tag
t ST - - Mon Timestamp: Mapping tag
Mod c_dINC stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
OpCntRs f_dINC Oper.ctlVal CO - - Cmd Mapping tag
Oper.origin.orCat CO - - Cmd Mapping tag
Oper.origin.orIdent CO - - Cmd Mapping tag
Oper.ctlNum CO - - Cmd Mapping tag
Oper.T CO - - Cmd Mapping tag
Oper.Test CO - - Cmd Mapping tag
Oper.Check CO - - Cmd Mapping tag
stVal ST - - Mon Mapping tag
q ST - - Mon Quality: Mapping tag
t ST - - Mon Timestamp: Mapping tag
NumCntRs o_dINS stVal ST - - Mon Mapping tag
q ST - - Mon Quality: Mapping tag
t ST - - Mon Timestamp: Mapping tag
Table 22: AGSAL Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
48Communication protocol manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
7.5.2 Physical device information LPHDPID-4023-LOGICALNODEDATA v3
LPHD (revision 6) - LPHD
Table 23:
PhyNam b_dDPL swRev DC - - - Firmware version
serNum DC - - - Serial Number
model DC - - - IEDModel for IEC61850
PhyHealth n_dINS stVal ST - PhyHealth Mon Physical health
q ST - PhyHealth Mon Quality: Physical health
t ST - PhyHealth Mon Timestamp: Physical health
7.5.3 Logical node zero LLNOPID-5185-LOGICALNODEDATA v1
LLN0 (revision 2) - LLN0
Table 24:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
49Communication protocol manual
Beh a_dINS q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
NamPlt ln0_dLPL swRev DC - - - Firmware version
Health n_dINS stVal ST - - Mon Physical health
q ST - - Mon Quality: Physical health
t ST - - Mon Timestamp: Physical health
7.5.4 Access point diagnostic for redundant Ethernet portsRCHLCCH
PID-6819-LOGICALNODEDATA v2
LN type LN prefix LN class Function block name
RCHLCCH (revision 1) RCH LCCH RCHLCCH
Table 25: RCHLCCH Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
ChLiv a_dSPS stVal ST - LinkAUp Mon Channel A link status
q ST - LinkAUp Mon Quality: Channel A link status
t ST - LinkAUp Mon Timestamp: Channel A linkstatus
RedChLiv a_dSPS stVal ST - LinkBUp Mon Channel B link status
q ST - LinkBUp Mon Quality: Channel B link status
t ST - LinkBUp Mon Timestamp: Channel B linkstatus
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
50Communication protocol manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
FerCh b_dINS stVal ST - ErrorRateA Mon Channel A redundancy errorrate
q ST - ErrorRateA Mon Quality: Channel A redundancyerror rate
t ST - ErrorRateA Mon Timestamp: Channel Aredundancy error rate
RedFerCh b_dINS stVal ST - ErrorRateB Mon Channel B redundancy errorrate
q ST - ErrorRateB Mon Quality: Channel B redundancyerror rate
t ST - ErrorRateB Mon Timestamp: Channel Bredundancy error rate
7.5.5 Access point diagnostic for non-redundant Ethernet portSCHLCCH
PID-6818-LOGICALNODEDATA v2
LN type LN prefix LN class Function block name
SCHLCCH (revision 1) SCH LCCH SCHLCCH
Table 26: SCHLCCH Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
ChLiv a_dSPS stVal ST - LINKUP Mon Access point link status
q ST - LINKUP Mon Quality: Access point linkstatus
t ST - LINKUP Mon Timestamp: Access point linkstatus
1MRK511349-UEN A Section 7Logical node data model
51Communication protocol manual
7.6 Logical nodes for protection related functions
7.6.1 Disturbance recorder RDRE
7.6.1.1 Disturbance report DRPRDREGUID-0B12001D-5AD2-451B-8AFE-0920B947F5C1 v1
PID-3949-LOGICALNODEDATA v3
DRPRDRE (revision 0) DRP RDRE
Table 27:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - ModeSt Mon Mode status parameter for61850
q ST - ModeSt Mon Quality: Mode status parameterfor 61850
t ST - ModeSt Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
RcdMade a_dSPS stVal ST - RECMADE Mon Disturbance recording made
q ST - RECMADE Mon Quality: Disturbance recordingmade
t ST - RECMADE Mon Timestamp: Disturbancerecording made
FltNum b_dINS stVal ST - FaultNumber Mon Disturbance fault number
q ST - FaultNumber Mon Quality: Disturbance faultnumber
t ST - FaultNumber Mon Timestamp: Disturbance faultnumber
Section 7 1MRK511349-UEN ALogical node data model
52Communication protocol manual
7.7 Logical nodes for generic references
7.7.1 Generic process I/O GGIO
7.7.1.1 Logic rotating switch for function selection and LHMI presentationSLGAPC
SEMOD114936-1 v4
PID-6641-LOGICALNODEDATA v2
LN type LN prefix LN class Function block name
SLGGIO (revision 7) SL GGIO SLGAPC
Table 28: SLGAPC Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviourparameter
IntIn b_dINS stVal ST - SWPOSN Mon Switch position (integer)
q ST - SWPOSN Mon Quality: Switch position(integer)
t ST - SWPOSN Mon Timestamp: Switch position(integer)
SwPosC1 v5_dISC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
valWTr.posVal ST - - Mon Position
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
53Communication protocol manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
SwPosC1 v5_dISC Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
q ST - - Mon Quality: Position
t ST - - Mon Timestamp: Position
ctlModel CF - - - Control model type for jumpcmd
sboTimeout CF - - - Maximum time between selectand execute signals for jumpcmd
sboClass CF - - - Select for many used for jumpcmd
SPCCO v6_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
ctlModel CF - - - Control model type for stepcmd
sboTimeout CF - - - Maximum time between selectand execute signals for stepcmd
sboClass CF - - - Select for many used for stepcmd
7.7.1.2 Selector mini switch VSGAPCSEMOD158754-1 v3
PID-3829-LOGICALNODEDATA v3
VSGGIO (revision 1) VS GGIO
Table 29:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
54Communication protocol manual
Mod a_dINC Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviourparameter
DPCSO d_dDPC Cancel.ctlVal CO - - Cmd Command parameter forIEC61850
Cancel.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
SBOw.ctlVal CO - - Cmd Command parameter forIEC61850
SBOw.origin.orCat CO - - Cmd Command parameter forIEC61850
SBOw.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Cancel.origin.orIdent CO - - Cmd Command parameter forIEC61850
Cancel.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
SBOw.ctlNum CO - - Cmd Command parameter forIEC61850
SBOw.T CO - - Cmd Command parameter forIEC61850
Cancel.T CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Cancel.Test CO - - Cmd Command parameter forIEC61850
SBOw.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
55Communication protocol manual
DPCSO d_dDPC SBOw.Check CO - - Cmd Command parameter for
IEC61850
stVal ST - POSITION Mon Position indication, integer
q ST - POSITION Mon Quality: Position indication,integer
t ST - POSITION Mon Timestamp: Positionindication, integer
stSeld ST - - Mon Select conditions are fulfilled
ctlModel CF - CtlModel - Specifies the type for controlmodel according to IEC 61850
7.7.1.3 Generic communication function for Double Point indication DPGAPCSEMOD55384-1 v4
PID-4139-LOGICALNODEDATA v3
DPGGIO (revision 0) DP GGIO
Table 30:
Mod aINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh aINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviourparameter
DPCSO bDPC stVal ST - POSITION Mon Double point indication
q ST - POSITION Mon Quality: Double point indication
t ST - POSITION Mon Timestamp: Double pointindication
7.7.1.4 Single point generic control 8 signals SPC8GAPCSEMOD176448-1 v3
PID-3575-LOGICALNODEDATA v3
SPC8GGIO (revision 2) SPC8 GGIO
Section 7 1MRK511349-UEN ALogical node data model
56Communication protocol manual
Table 31:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
SPCSO1 d_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SPCSO2 d_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SPCSO3 d_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
57Communication protocol manual
SPCSO3 d_dSPC Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SPCSO4 d_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SPCSO5 d_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SPCSO6 d_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
58Communication protocol manual
SPCSO6 d_dSPC Oper.Check CO - - Cmd Command parameter for
IEC61850
SPCSO7 d_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SPCSO8 d_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
7.7.1.5 Event counter with limit supervision L4UFCNTGUID-C7139F45-E03E-440A-85FD-2102B6470688 v1
PID-3553-LOGICALNODEDATA v3
L4UFCNT (revision 0) L4U FCNT
Table 32:
CntRs a_dBCR actVal ST - VALUE Mon Counted value
q ST - VALUE Mon Quality: Counted value
t ST - VALUE Mon Timestamp: Counted value
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
59Communication protocol manual
Mod a_dINC Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
RsCnt v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Lim1 v1_dSPS stVal ST - LIMIT1 Mon Counted value is larger than orequal to CounterLimit1
q ST - LIMIT1 Mon Quality: Counted value is largerthan or equal to CounterLimit1
t ST - LIMIT1 Mon Timestamp: Counted value islarger than or equal toCounterLimit1
Lim2 v1_dSPS stVal ST - LIMIT2 Mon Counted value is larger than orequal to CounterLimit2
q ST - LIMIT2 Mon Quality: Counted value is largerthan or equal to CounterLimit2
t ST - LIMIT2 Mon Timestamp: Counted value islarger than or equal toCounterLimit2
Lim3 v1_dSPS stVal ST - LIMIT3 Mon Counted value is larger than orequal to CounterLimit3
q ST - LIMIT3 Mon Quality: Counted value is largerthan or equal to CounterLimit3
t ST - LIMIT3 Mon Timestamp: Counted value islarger than or equal toCounterLimit3
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
60Communication protocol manual
Lim4 v1_dSPS stVal ST - LIMIT4 Mon Counted value is larger than orequal to CounterLimit4
q ST - LIMIT4 Mon Quality: Counted value is largerthan or equal to CounterLimit4
t ST - LIMIT4 Mon Timestamp: Counted value islarger than or equal toCounterLimit4
7.7.1.6 IEC 61850 generic communication I/O functions SPGGIOGUID-900EC450-B37E-4578-ADAA-901CB8CC497D v2
PID-3780-LOGICALNODEDATA v3
SPGGIO (revision 1) SP GGIO
Table 33:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Ind c_dSPS stVal ST - OUT Mon Output status
q ST - OUT Mon Quality: Output status
t ST - OUT Mon Timestamp: Output status
7.7.1.7 IEC 61850 generic communication I/O functions 16 inputs SP16GGIOGUID-E6D85EF8-3DA5-4814-9337-24DB15B76BF5 v2
PID-3781-LOGICALNODEDATA v3
SP16GGIO (revision 2) SP16 GGIO
1MRK511349-UEN A Section 7Logical node data model
61Communication protocol manual
Table 34:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Ind c_dSPS stVal ST - OUT1 Mon Output 1 status
q ST - OUT1 Mon Quality: Output 1 status
t ST - OUT1 Mon Timestamp: Output 1 status
Ind2 c_dSPS stVal ST - OUT2 Mon Output 2 status
q ST - OUT2 Mon Quality: Output 2 status
t ST - OUT2 Mon Timestamp: Output 2 status
Ind3 c_dSPS stVal ST - OUT3 Mon Output 3 status
q ST - OUT3 Mon Quality: Output 3 status
t ST - OUT3 Mon Timestamp: Output 3 status
Ind4 c_dSPS stVal ST - OUT4 Mon Output 4 status
q ST - OUT4 Mon Quality: Output 4 status
t ST - OUT4 Mon Timestamp: Output 4 status
Ind5 c_dSPS stVal ST - OUT5 Mon Output 5 status
q ST - OUT5 Mon Quality: Output 5 status
t ST - OUT5 Mon Timestamp: Output 5 status
Ind6 c_dSPS stVal ST - OUT6 Mon Output 6 status
q ST - OUT6 Mon Quality: Output 6 status
t ST - OUT6 Mon Timestamp: Output 6 status
Ind7 c_dSPS stVal ST - OUT7 Mon Output 7 status
q ST - OUT7 Mon Quality: Output 7 status
t ST - OUT7 Mon Timestamp: Output 7 status
Ind8 c_dSPS stVal ST - OUT8 Mon Output 8 status
q ST - OUT8 Mon Quality: Output 8 status
t ST - OUT8 Mon Timestamp: Output 8 status
Ind9 c_dSPS stVal ST - OUT9 Mon Output 9 status
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
62Communication protocol manual
Ind9 c_dSPS q ST - OUT9 Mon Quality: Output 9 status
t ST - OUT9 Mon Timestamp: Output 9 status
Ind10 c_dSPS stVal ST - OUT10 Mon Output 10 status
q ST - OUT10 Mon Quality: Output 10 status
t ST - OUT10 Mon Timestamp: Output 10 status
Ind11 c_dSPS stVal ST - OUT11 Mon Output 11 status
q ST - OUT11 Mon Quality: Output 11 status
t ST - OUT11 Mon Timestamp: Output 11 status
Ind12 c_dSPS stVal ST - OUT12 Mon Output 12 status
q ST - OUT12 Mon Quality: Output 12 status
t ST - OUT12 Mon Timestamp: Output 12 status
Ind13 c_dSPS stVal ST - OUT13 Mon Output 13 status
q ST - OUT13 Mon Quality: Output 13 status
t ST - OUT13 Mon Timestamp: Output 13 status
Ind14 c_dSPS stVal ST - OUT14 Mon Output 14 status
q ST - OUT14 Mon Quality: Output 14 status
t ST - OUT14 Mon Timestamp: Output 14 status
Ind15 c_dSPS stVal ST - OUT15 Mon Output 15 status
q ST - OUT15 Mon Quality: Output 15 status
t ST - OUT15 Mon Timestamp: Output 15 status
Ind16 c_dSPS stVal ST - OUT16 Mon Output 16 status
q ST - OUT16 Mon Quality: Output 16 status
t ST - OUT16 Mon Timestamp: Output 16 status
GrInd v1_dSPS stVal ST - OUTOR Mon Output status logic OR gate forinput 1 to 16
q ST - OUTOR Mon Quality: Output status logic ORgate for input 1 to 16
t ST - OUTOR Mon Timestamp: Output statuslogic OR gate for input 1 to 16
7.7.1.8 Generic communication function for Measured Value MVGAPCSEMOD55402-1 v3
PID-3779-LOGICALNODEDATA v2
MVGGIO (revision 1) MV GGIO
Table 35:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
63Communication protocol manual
Mod a_dINC Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
AnIn a_dMV rangeC.hhLim.f CF - MV hhLim - High High limit multiplied withthe base prefix (multiplicationfactor)
rangeC.hLim.f CF - MV hLim - High limit multiplied with thebase prefix (multiplicationfactor)
rangeC.lLim.f CF - MV lLim - Low limit multiplied with thebase prefix (multiplicationfactor)
rangeC.llLim.f CF - MV llLim - Low Low limit multiplied withthe base prefix (multiplicationfactor)
rangeC.max.f CF - MV max - Maximum value multiplied withthe base prefix (multiplicationfactor)
rangeC.min.f CF - MV min - Minimum value multiplied withthe base prefix (multiplicationfactor)
mag.f MX - VALUE Mon Magnitude of deadband value
subMag.f SV - - - Substituted value
range MX - RANGE Mon Range
q MX - VALUE Mon Quality: Magnitude ofdeadband value
t MX - VALUE Mon Timestamp: Magnitude ofdeadband value
subEna SV - - - Enable substitution
db CF - MV db - Cycl: Report interval (s), Db: In% of range, Int Db: In %s
zeroDb CF - MV zeroDb - Zero point clamping in 0,001%of range
7.7.1.9 Trip matrix logic TMAGAPCIP15121-1 v4
PID-4125-LOGICALNODEDATA v2
TMAGGIO (revision 0) TMA GGIO
Section 7 1MRK511349-UEN ALogical node data model
64Communication protocol manual
Table 36:
Mod aINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh aINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviourparameter
Out1 v1SPS stVal ST - OUTPUT1 Mon OR function betweeen inputs 1to 16
q ST - OUTPUT1 Mon Quality: OR function betweeeninputs 1 to 16
t ST - OUTPUT1 Mon Timestamp: OR functionbetweeen inputs 1 to 16
Out2 v1SPS stVal ST - OUTPUT2 Mon OR function between inputs 17to 32
q ST - OUTPUT2 Mon Quality: OR function betweeninputs 17 to 32
t ST - OUTPUT2 Mon Timestamp: OR functionbetween inputs 17 to 32
Out3 v1SPS stVal ST - OUTPUT3 Mon OR function between inputs 1to 32
q ST - OUTPUT3 Mon Quality: OR function betweeninputs 1 to 32
t ST - OUTPUT3 Mon Timestamp: OR functionbetween inputs 1 to 32
7.7.1.10 Elapsed time integrator with limit transgression and overflowsupervision TEIGGIO
GUID-9DD4C562-D0D7-4BFB-B9E0-D016675EB772 v1
PID-4047-LOGICALNODEDATA v3
TEIGGIO (revision 0) TEI GGIO
1MRK511349-UEN A Section 7Logical node data model
65Communication protocol manual
Table 37:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
Alm a_dSPS stVal ST - ALARM Mon Indicator of the integrated timehas reached the alarm limit
q ST - ALARM Mon Quality: Indicator of theintegrated time has reachedthe alarm limit
t ST - ALARM Mon Timestamp: Indicator of theintegrated time has reachedthe alarm limit
RsAccTms v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Wrn v1_dSPS stVal ST - WARNING Mon Indicator of the integrated timehas reached the warning limit
q ST - WARNING Mon Quality: Indicator of theintegrated time has reachedthe warning limit
t ST - WARNING Mon Timestamp: Indicator of theintegrated time has reachedthe warning limit
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
66Communication protocol manual
AccTms v2_dMV mag.f MX - ACCTIME Mon Integrated elapsed time inseconds
q MX - ACCTIME Mon Quality: Integrated elapsedtime in seconds
t MX - ACCTIME Mon Timestamp: Integrated elapsedtime in seconds
7.8 Logical nodes for sensors and monitoring
7.8.1 Circuit breaker monitoring SSCBR
7.8.1.1 SSCBRGUID-30A59448-3B80-4298-965D-19E28BB0BBD8 v3
PID-3267-LOGICALNODEDATA v4
SSCBR (revision 3) S SCBR
Table 38:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
InaTmdCnt v1_dINS stVal ST - INADAYS Mon The number of days CB hasbeen inactive
q ST - INADAYS Mon Quality: The number of days CBhas been inactive
t ST - INADAYS Mon Timestamp: The number ofdays CB has been inactive
RmnLif v1_dINS stVal ST - CBLIFEPH Mon CB Remaining life of respectivephase
q ST - CBLIFEPH Mon Quality: CB Remaining life ofrespective phase
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
67Communication protocol manual
RmnLif v1_dINS t ST - CBLIFEPH Mon Timestamp: CB Remaining life
of respective phase
RsAccAPwr v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
RsCBWear v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
RsTrvTm v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
RsSprChaTm v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
68Communication protocol manual
RsSprChaTm v1_dSPC Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
OpnAlm v1_dSPS stVal ST - TRVTOPAL Mon CB open travel time exceededset value
q ST - TRVTOPAL Mon Quality: CB open travel timeexceeded set value
t ST - TRVTOPAL Mon Timestamp: CB open traveltime exceeded set value
ClsAlm v1_dSPS stVal ST - TRVTCLAL Mon CB close travel time exceededset value
q ST - TRVTCLAL Mon Quality: CB close travel timeexceeded set value
t ST - TRVTCLAL Mon Timestamp: CB close traveltime exceeded set value
OpNumAlm v1_dSPS stVal ST - OPERALM Mon Number of CB operationsexceeds alarm limit
q ST - OPERALM Mon Quality: Number of CBoperations exceeds alarm limit
t ST - OPERALM Mon Timestamp: Number of CBoperations exceeds alarm limit
OpNumLO v1_dSPS stVal ST - OPERLO Mon Number of CB operationsexceeds lockout limit
q ST - OPERLO Mon Quality: Number of CBoperations exceeds lockoutlimit
t ST - OPERLO Mon Timestamp: Number of CBoperations exceeds lockoutlimit
APwrAlm v1_dSPS stVal ST - IPOWALPH Mon Accum I^CurrExponent integrover CB open travel timeexceeds alarm limit
q ST - IPOWALPH Mon Quality: Accum I^CurrExponentintegr over CB open travel timeexceeds alarm limit
t ST - IPOWALPH Mon Timestamp: AccumI^CurrExponent integr over CBopen travel time exceeds alarmlimit
APwrLO v1_dSPS stVal ST - IPOWLOPH Mon Accum I^CurrExponent integrover CB open travel timeexceeds lockout limit
q ST - IPOWLOPH Mon Quality: Accum I^CurrExponentintegr over CB open travel timeexceeds lockout limit
t ST - IPOWLOPH Mon Timestamp: AccumI^CurrExponent integr over CBopen travel time exceedslockout limit
LonTmAlm v1_dSPS stVal ST - MONALM Mon CB 'not operated for long time'alarm
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
69Communication protocol manual
LonTmAlm v1_dSPS q ST - MONALM Mon Quality: CB 'not operated for
long time' alarm
t ST - MONALM Mon Timestamp: CB 'not operatedfor long time' alarm
SprChaAlm v1_dSPS stVal ST - SPCHALM Mon Spring charging time hascrossed the set value
q ST - SPCHALM Mon Quality: Spring charging timehas crossed the set value
t ST - SPCHALM Mon Timestamp: Spring chargingtime has crossed the set value
PosOpn v1_dSPS stVal ST - OPENPOS Mon CB is in open position
q ST - OPENPOS Mon Quality: CB is in open position
t ST - OPENPOS Mon Timestamp: CB is in openposition
PosIvd v1_dSPS stVal ST - INVDPOS Mon CB is in Invalid Position
q ST - INVDPOS Mon Quality: CB is in Invalid Position
t ST - INVDPOS Mon Timestamp: CB is in InvalidPosition
PosCls v1_dSPS stVal ST - CLOSEPOS Mon CB is in closed position
q ST - CLOSEPOS Mon Quality: CB is in closed position
t ST - CLOSEPOS Mon Timestamp: CB is in closedposition
CBLifAlm v1_dSPS stVal ST - CBLIFEAL Mon Remaining life of CB reduced toLife alarm level
q ST - CBLIFEAL Mon Quality: Remaining life of CBreduced to Life alarm level
t ST - CBLIFEAL Mon Timestamp: Remaining life ofCB reduced to Life alarm level
PresLO v1_dSPS stVal ST - GPRESLO Mon Pressure below lockout level
q ST - GPRESLO Mon Quality: Pressure below lockoutlevel
t ST - GPRESLO Mon Timestamp: Pressure belowlockout level
ColOpn v1_dSPS stVal ST - TRCMD Mon Open command issued to CB
q ST - TRCMD Mon Quality: Open command issuedto CB
t ST - TRCMD Mon Timestamp: Open commandissued to CB
TmmsCls v2_dMV mag.f MX - TTRVCL Mon Travel time of the CB duringclosing operation
q MX - TTRVCL Mon Quality: Travel time of the CBduring closing operation
t MX - TTRVCL Mon Timestamp: Travel time of theCB during closing operation
TmmsOpn v2_dMV mag.f MX - TTRVOP Mon Travel time of the CB duringopening operation
q MX - TTRVOP Mon Quality: Travel time of the CBduring opening operation
t MX - TTRVOP Mon Timestamp: Travel time of theCB during opening operation
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
70Communication protocol manual
TmsSprCha v2_dMV mag.f MX - SPCHT Mon The charging time of the CBspring
q MX - SPCHT Mon Quality: The charging time ofthe CB spring
t MX - SPCHT Mon Timestamp: The charging timeof the CB spring
AccAPwr v2_dMV mag.f MX - IPOWPH Mon Accumulated I^CurrExponentintegrated over CB open traveltime
q MX - IPOWPH Mon Quality: AccumulatedI^CurrExponent integrated overCB open travel time
t MX - IPOWPH Mon Timestamp: AccumulatedI^CurrExponent integrated overCB open travel time
PresAlm v3_dSPS stVal ST - GPRESALM Mon Pressure below alarm level
q ST - GPRESALM Mon Quality: Pressure below alarmlevel
t ST - GPRESALM Mon Timestamp: Pressure belowalarm level
OpCnt v5_dINS stVal ST - NOOPER Mon Number of CB operation cycle
q ST - NOOPER Mon Quality: Number of CBoperation cycle
t ST - NOOPER Mon Timestamp: Number of CBoperation cycle
7.8.2 Insulation medium supervision (gas) SIMG
7.8.2.1 SSIMGGUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
PID-3703-LOGICALNODEDATA v3
SSIMG (revision 0) S SIMG
Table 39:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
71Communication protocol manual
Mod a_dINC t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
InsAlm a_dSPS stVal ST - PRES_LO Mon Pressure below lockout level
q ST - PRES_LO Mon Quality: Pressure below lockoutlevel
t ST - PRES_LO Mon Timestamp: Pressure belowlockout level
PresAlm a_dSPS stVal ST - PRES_ALM Mon Pressure below alarm level
q ST - PRES_ALM Mon Quality: Pressure below alarmlevel
t ST - PRES_ALM Mon Timestamp: Pressure belowalarm level
TmpAlm a_dSPS stVal ST - TEMP_ALM Mon Temperature above alarm level
q ST - TEMP_ALM Mon Quality: Temperature abovealarm level
t ST - TEMP_ALM Mon Timestamp: Temperatureabove alarm level
Pres b_dMV mag.f MX - PRESSURE Mon Pressure service value
q MX - PRESSURE Mon Quality: Pressure service value
t MX - PRESSURE Mon Timestamp: Pressure servicevalue
Tmp b_dMV mag.f MX - TEMP Mon Temperature of the insulationmedium
q MX - TEMP Mon Quality: Temperature of theinsulation medium
t MX - TEMP Mon Timestamp: Temperature ofthe insulation medium
LORs v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
TmpLO v1_dSPS stVal ST - TEMP_LO Mon Temperature above lockoutlevel
q ST - TEMP_LO Mon Quality: Temperature abovelockout level
t ST - TEMP_LO Mon Timestamp: Temperatureabove lockout level
Section 7 1MRK511349-UEN ALogical node data model
72Communication protocol manual
7.8.3 Insulation medium supervision (liquid) SIMLGUID-37669E94-4830-4C96-8A67-09600F847F23 v3PID-3706-LOGICALNODEDATA v3
SSIML (revision 0) S SIML
Table 40:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
InsAlm a_dSPS stVal ST - LVL_LO Mon Level below lockout level
q ST - LVL_LO Mon Quality: Level below lockoutlevel
t ST - LVL_LO Mon Timestamp: Level belowlockout level
PresAlm a_dSPS stVal ST - LVL_ALM Mon Level below alarm level
q ST - LVL_ALM Mon Quality: Level below alarm level
t ST - LVL_ALM Mon Timestamp: Level below alarmlevel
TmpAlm a_dSPS stVal ST - TEMP_ALM Mon Temperature above alarm level
q ST - TEMP_ALM Mon Quality: Temperature abovealarm level
t ST - TEMP_ALM Mon Timestamp: Temperatureabove alarm level
Pres b_dMV mag.f MX - LEVEL Mon Level service value
q MX - LEVEL Mon Quality: Level service value
t MX - LEVEL Mon Timestamp: Level service value
Tmp b_dMV mag.f MX - TEMP Mon Temperature of the insulationmedium
q MX - TEMP Mon Quality: Temperature of theinsulation medium
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
73Communication protocol manual
Tmp b_dMV t MX - TEMP Mon Timestamp: Temperature of
the insulation medium
LORs v1_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
TmpLo v1_dSPS stVal ST - TEMP_LO Mon Temperature above lockoutlevel
q ST - TEMP_LO Mon Quality: Temperature abovelockout level
t ST - TEMP_LO Mon Timestamp: Temperatureabove lockout level
7.8.4 Through fault monitoring STHR
7.8.4.1 Through fault monitoring PTRSTHRGUID-7AE60CB5-3CD5-4FE2-8D54-664AA78DD2DE v1
PID-7144-LOGICALNODEDATA v1
PTRSTHR (revision 0) PTR STHR
Table 41:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameterfor 61850
q ST - - Mon Quality: Mode status valueparameter for 61850
t ST - - Mon Timestamp: Mode status valueparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
74Communication protocol manual
Beh a_dINS q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
GenAlm a_dSPS stVal ST - ALARM Mon General fault detection alarm
q ST - ALARM Mon Quality: General fault detectionalarm
t ST - ALARM Mon Timestamp: General faultdetection alarm
GenCmAlm a_dSPS stVal ST - CMLI2TALM Mon General cumulative fault (I^2)talarm
q ST - CMLI2TALM Mon Quality: General cumulativefault (I^2)t alarm
t ST - CMLI2TALM Mon Timestamp: General cumulativefault (I^2)t alarm
GenEvtAlm a_dSPS stVal ST - I2TALM Mon General fault (I^2)t alarm for anevent
q ST - I2TALM Mon Quality: General fault (I^2)talarm for an event
t ST - I2TALM Mon Timestamp: General fault (I^2)talarm for an event
RpRdy a_dSPS stVal ST - REPMADE Mon Report is ready for file transfer
q ST - REPMADE Mon Quality: Report is ready for filetransfer
t ST - REPMADE Mon Timestamp: Report is ready forfile transfer
FltCnt b_dINS stVal ST - TFCNT Mon Overall number of faultsdetected since last reset
q ST - TFCNT Mon Quality: Overall number offaults detected since last reset
t ST - TFCNT Mon Timestamp: Overall number offaults detected since last reset
7.9 Logical nodes for switchgear
7.9.1 Circuit breaker XCBR
7.9.1.1 Circuit breaker SXCBRGUID-C865CD66-9B2F-4D40-9BC0-BCA7DE7A3D8E v1
PID-4055-LOGICALNODEDATA v1
SXCBR (revision 1) S XCBR
1MRK511349-UEN A Section 7Logical node data model
75Communication protocol manual
Table 42:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
BlkCls a_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - CL_BLKD Mon Indication that the function isblocked for close commands
q ST - CL_BLKD Mon Quality: Indication that thefunction is blocked for closecommands
t ST - CL_BLKD Mon Timestamp: Indication that thefunction is blocked for closecommands
BlkOpn a_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - OP_BLKD Mon Indication that the function isblocked for open commands
q ST - OP_BLKD Mon Quality: Indication that thefunction is blocked for opencommands
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
76Communication protocol manual
BlkOpn a_dSPC t ST - OP_BLKD Mon Timestamp: Indication that the
function is blocked for opencommands
Loc a_dSPS stVal ST - - Mon Indication that the function isin local mode (process level)
q ST - - Mon Quality: Indication that thefunction is in local mode(process level)
t ST - - Mon Timestamp: Indication that thefunction is in local mode(process level)
OpCnt b_dINS stVal ST - CNT_VAL Mon Operation counter value
q ST - CNT_VAL Mon Quality: Operation countervalue
t ST - CNT_VAL Mon Timestamp: Operation countervalue
Pos c_dDPC stVal ST - POSITION Mon Apparatus position indication
q ST - POSITION Mon Quality: Apparatus positionindication
t ST - POSITION Mon Timestamp: Apparatus positionindication
subEna SV - - - Substitute enable
subVal SV - - - Substituted double positionvalue
CBOpCap h_dINS stVal ST - CBOPCAP Mon Breaker operating capability 1 =None, 2 = O, 3 = CO, 4 = OCO, 5= COCO, 6+ = More
q ST - CBOPCAP Mon Quality: Breaker operatingcapability 1 = None, 2 = O, 3 =CO, 4 = OCO, 5 = COCO, 6+ =More
t ST - CBOPCAP Mon Timestamp: Breaker operatingcapability 1 = None, 2 = O, 3 =CO, 4 = OCO, 5 = COCO, 6+ =More
BlkUpd v1_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - UPD_BLKD Mon Update of position indication isblocked
q ST - UPD_BLKD Mon Quality: Update of positionindication is blocked
t ST - UPD_BLKD Mon Timestamp: Update of positionindication is blocked
1MRK511349-UEN A Section 7Logical node data model
77Communication protocol manual
7.9.2 Switch XSWI
7.9.2.1 Circuit switch SXSWIGUID-A7AEBCA2-89FD-4F6E-A3B8-57E6A16035C9 v1
PID-4056-LOGICALNODEDATA v1
SXSWI (revision 1) S XSWI
Table 43:
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for61850
q ST - - Mon Quality: Mode status parameterfor 61850
t ST - - Mon Timestamp: Mode statusparameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameterfor 61850
t ST - Beh Mon Timestamp: Behaviourparameter for 61850
BlkCls a_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - CL_BLKD Mon Indication that the function isblocked for close commands
q ST - CL_BLKD Mon Quality: Indication that thefunction is blocked for closecommands
t ST - CL_BLKD Mon Timestamp: Indication that thefunction is blocked for closecommands
BlkOpn a_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Table continues on next page
Section 7 1MRK511349-UEN ALogical node data model
78Communication protocol manual
BlkOpn a_dSPC Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - OP_BLKD Mon Indication that the function isblocked for open commands
q ST - OP_BLKD Mon Quality: Indication that thefunction is blocked for opencommands
t ST - OP_BLKD Mon Timestamp: Indication that thefunction is blocked for opencommands
Loc a_dSPS stVal ST - - Mon Indication that the function isin local mode (process level)
q ST - - Mon Quality: Indication that thefunction is in local mode(process level)
t ST - - Mon Timestamp: Indication that thefunction is in local mode(process level)
OpCnt b_dINS stVal ST - CNT_VAL Mon Operation counter value
q ST - CNT_VAL Mon Quality: Operation countervalue
t ST - CNT_VAL Mon Timestamp: Operation countervalue
Pos c_dDPC stVal ST - POSITION Mon Apparatus position indication
q ST - POSITION Mon Quality: Apparatus positionindication
t ST - POSITION Mon Timestamp: Apparatus positionindication
subEna SV - - - Substitute enable
subVal SV - - - Substituted double positionvalue
SwOpCap f_dINS stVal ST - SWOPCAP Mon Switch operating capability 1 =None, 2 = O, 3 = C, 4 = O and C
q ST - SWOPCAP Mon Quality: Switch operatingcapability 1 = None, 2 = O, 3 = C,4 = O and C
t ST - SWOPCAP Mon Timestamp: Switch operatingcapability 1 = None, 2 = O, 3 = C,4 = O and C
SwTyp g_dINS stVal ST - - Mon 1=LoadBreak,2=Disconnector,3=EarthSw,4=HighSpeedEarthSw
q ST - - Mon Quality:1=LoadBreak,2=Disconnector,3=EarthSw,4=HighSpeedEarthSw
t ST - - Mon Timestamp:1=LoadBreak,2=Disconnector,3=EarthSw,4=HighSpeedEarthSw
BlkUpd v1_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Table continues on next page
1MRK511349-UEN A Section 7Logical node data model
79Communication protocol manual
BlkUpd v1_dSPC Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - UPD_BLKD Mon Update of position indication isblocked
q ST - UPD_BLKD Mon Quality: Update of positionindication is blocked
t ST - UPD_BLKD Mon Timestamp: Update of positionindication is blocked
Section 7 1MRK511349-UEN ALogical node data model
80Communication protocol manual
Section 8 Flexible product naming
8.1 IntroductionGUID-98BC22A7-8EFF-4CD0-829E-FBB5D8FD8024 v2
The Flexible product naming tool in PCM600 allows the customer to use an IED-vendorindependent 61850 model of the IED. This customer model will be exposed in all IEC 61850communication, but all other aspects of the IED will remain unchanged (for example, names onthe local HMI and names in the tools).
This offers significant flexibility to adapt the IED to the customers system and standardsolution.
Benefits:
• IEDs uses the customer model for communication.• Customer specific naming convention for communication can be used.• Other IEDs and station level equipment can be defined from the customer specific
communication model.• Error tracing of communication can be the same between different installations.
8.1.1 Mapping exampleGUID-DD7F097C-1D72-4BA2-8684-61B54EF0D00C v1
FunctionA
Non-affected function views IED 61850 model Customer 61850 modelFPN mapping
FunctionB
LHMI view
PCM view
... view
LD
APTOC
BPTOC
LD
L1PTOC
L2PTOC
LD
LD
IEC15000502-2-en.vsdx
IEC15000502 V2 EN-US
Figure 12: L1PTOC in the customer model mapped to BPTOC in the IED model andL2PTOC mapped to APTOC
Mapping shown in Figure 12 results to mapping shown in Figure 13.
1MRK511349-UEN A Section 8Flexible product naming
81Communication protocol manual
FunctionA
Non-affected function views
FunctionB
LHMI view
PCM view
... view
LD
L1PTOC
L2PTOC
LD
LD
Customer 61850 model
IEC15000503-2-en.vsdx
IEC15000503 V2 EN-US
Figure 13: L1PTOC mapped to FunctionB and L2PTOC mapped to FunctionA
8.1.2 Mapping possibilities and requirementsGUID-AA4E0570-D874-4B82-84A5-729644C67626 v1
The mapping between the IED model and the customer model provides a set of possibilitiesbut also include some requirements.
The mapping is possible at several levels in the structure:
• Logical Node level (LN to LN)• Data Object level (DO to DO)• Data Attribute level (DA to DA).
Custom logical device name (LDName) can be used for addressing.
When the mapping is performed there are some requirements that must be fulfilled betweenthe IED model and the customer model:
• One attribute in the customer model can only be mapped to one attribute in the IEDmodel.
• However one attribute in the IED model can be mapped to several attributes in thecustomer model.
• The functional constraint (FC) of the data attributes must match.• The basic type of the data attributes must match.• Trigger options of the data attributes must match.• The version of the IEC 61850 standard must match.• Number of data sets must not exceed the maximum number of data sets that the IED
supports.
There are also some consequences that must be thought about when doing the mapping forexample,
Section 8 1MRK511349-UEN AFlexible product naming
82Communication protocol manual
• If two DOs in one LN in the customer model are mapped to DOs in different LNs in the IEDmodel the DOs in the customer model might be inconsistent with respect to quality in thecase of different operational states of the IED Functions.
• When several LNs in the customer model are mapped to one function in the IED, the Modof the function will affect all the customer LNs
Several other use cases like this exist. By understanding the concept of mapping from IEDfunctions and IED model to customer model, these cases can be foreseen.
1MRK511349-UEN A Section 8Flexible product naming
83Communication protocol manual
84
Section 9 Glossary
M14893-1 v18
AC Alternating current
ACC Actual channel
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
ADM Analog digital conversion module, with time synchronization
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
ASDU Application service data unit
AWG American Wire Gauge standard
BBP Busbar protection
BFOC/2,5 Bayonet fiber optic connector
BFP Breaker failure protection
BI Binary input
BIM Binary input module
BOM Binary output module
BOS Binary outputs status
BR External bistable relay
BS British Standards
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for serialcommunication
CB Circuit breaker
CBM Combined backplane module
CCITT Consultative Committee for International Telegraph and Telephony. AUnited Nations-sponsored standards body within the InternationalTelecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined megapulses per second
CMT Communication Management tool in PCM600
1MRK511349-UEN A Section 9Glossary
85Communication protocol manual
CO cycle Close-open cycle
Codirectional Way of transmitting G.703 over a balanced line. Involves two twistedpairs making it possible to transmit information in both directions
COM Command
COMTRADE Standard Common Format for Transient Data Exchange format forDisturbance recorder according to IEEE/ANSI C37.111, 1999 / IEC60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves four twistedpairs, two of which are used for transmitting data in both directionsand two for transmitting clock signals
COT Cause of transmission
CPU Central processing unit
CR Carrier receive
CRC Cyclic redundancy check
CROB Control relay output block
CS Carrier send
CT Current transformer
CU Communication unit
CVT or CCVT Capacitive voltage transformer
DAR Delayed autoreclosing
DARPA Defense Advanced Research Projects Agency (The US developer of theTCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFC Data flow control
DFT Discrete Fourier transform
DHCP Dynamic Host Configuration Protocol
DIP-switch Small switch mounted on a printed circuit board
DI Digital input
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE Std 1815-2012
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
DTT Direct transfer trip scheme
ECT Ethernet configuration tool
EHV network Extra high voltage network
EIA Electronic Industries Association
EMC Electromagnetic compatibility
EMF Electromotive force
Section 9 1MRK511349-UEN AGlossary
86Communication protocol manual
EMI Electromagnetic interference
EnFP End fault protection
EPA Enhanced performance architecture
ESD Electrostatic discharge
F-SMA Type of optical fiber connector
FAN Fault number
FCB Flow control bit; Frame count bit
FOX 20 Modular 20 channel telecommunication system for speech, data andprotection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact time-division multiplexer for the transmission of up to sevenduplex channels of digital data over optical fibers
FPN Flexible product naming
FTP File Transfer Protocol
FUN Function type
G.703 Electrical and functional description for digital lines used by localtelephone companies. Can be transported over balanced andunbalanced lines
GCM Communication interface module with carrier of GPS receiver module
GDE Graphical display editor within PCM600
GI General interrogation command
GIS Gas-insulated switchgear
GOOSE Generic object-oriented substation event
GPS Global positioning system
GSAL Generic security application
GSE Generic substation event
HDLC protocol High-level data link control, protocol based on the HDLC standard
HFBR connector type Plastic fiber connector
HLV circuit Hazardous Live Voltage according to IEC60255-27
HMI Human-machine interface
HSAR High speed autoreclosing
HSR High-availability Seamless Redundancy
HV High-voltage
HVDC High-voltage direct current
IDBS Integrating deadband supervision
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers – Part 6: Requirements forprotective current transformers for transient performance
IEC 60870-5-103 Communication standard for protection equipment. A serial master/slave protocol for point-to-point communication
IEC 61850 Substation automation communication standard
IEC 61850–8–1 Communication protocol standard
1MRK511349-UEN A Section 9Glossary
87Communication protocol manual
IEEE Institute of Electrical and Electronics Engineers
IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted-pair or optical fiber cable
IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules. Referencesthe CMC (IEEE P1386, also known as Common Mezzanine Card)standard for the mechanics and the PCI specifications from the PCI SIG(Special Interest Group) for the electrical EMF (Electromotive force).
IEEE 1686 Standard for Substation Intelligent Electronic Devices (IEDs) CyberSecurity Capabilities
IED Intelligent electronic device
IET600 Integrated engineering tool
I-GIS Intelligent gas-insulated switchgear
IOM Binary input/output module
Instance When several occurrences of the same function are available in the IED,they are referred to as instances of that function. One instance of afunction is identical to another of the same kind but has a differentnumber in the IED user interfaces. The word "instance" is sometimesdefined as an item of information that is representative of a type. Inthe same way an instance of a function in the IED is representative of atype of function.
IP 1. Internet protocol. The network layer for the TCP/IP protocol suitewidely used on Ethernet networks. IP is a connectionless, best-effortpacket-switching protocol. It provides packet routing, fragmentationand reassembly through the data link layer.2. Ingression protection, according to IEC 60529
IP 20 Ingression protection, according to IEC 60529, level
IP 40 Ingression protection, according to IEC 60529, level
IP 54 Ingression protection, according to IEC 60529, level
IRF Internal failure signal
IRIG-B: InterRange Instrumentation Group Time code format B, standard 200
ITU International Telecommunications Union
LAN Local area network
LIB 520 High-voltage software module
LCD Liquid crystal display
LDCM Line data communication module
LDD Local detection device
LNT LON network tool
LON Local operating network
MCB Miniature circuit breaker
MCM Mezzanine carrier module
MPM Main processing module
MVAL Value of measurement
MVB Multifunction vehicle bus. Standardized serial bus originally developedfor use in trains.
NCC National Control Centre
NOF Number of grid faults
Section 9 1MRK511349-UEN AGlossary
88Communication protocol manual
NUM Numerical module
OCO cycle Open-close-open cycle
OCP Overcurrent protection
OLTC On-load tap changer
OTEV Disturbance data recording initiated by other event than start/pick-up
OV Overvoltage
Overreach A term used to describe how the relay behaves during a fault condition.For example, a distance relay is overreaching when the impedancepresented to it is smaller than the apparent impedance to the faultapplied to the balance point, that is, the set reach. The relay “sees” thefault but perhaps it should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM Pulse code modulation
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
PELV circuit Protected Extra-Low Voltage circuit type according to IEC60255-27
PMC PCI Mezzanine card
POR Permissive overreach
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in near proximity to themeasured and/or controlled components
PRP Parallel redundancy protocol
PSM Power supply module
PST Parameter setting tool within PCM600
PTP Precision time protocol
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RASC Synchrocheck relay, COMBIFLEX
RCA Relay characteristic angle
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digital data in point-to-point connections
RS485 Serial link according to EIA standard RS485
RTC Real-time clock
RTU Remote terminal unit
SA Substation Automation
SBO Select-before-operate
SC Switch or push button to close
SCL Short circuit location
SCS Station control system
SCADA Supervision, control and data acquisition
1MRK511349-UEN A Section 9Glossary
89Communication protocol manual
SCT System configuration tool according to standard IEC 61850
SDU Service data unit
SELV circuit Safety Extra-Low Voltage circuit type according to IEC60255-27
SFP Small form-factor pluggable (abbreviation)Optical Ethernet port (explanation)
SLM Serial communication module.
SMA connector Subminiature version A, A threaded connector with constantimpedance.
SMT Signal matrix tool within PCM600
SMS Station monitoring system
SNTP Simple network time protocol – is used to synchronize computer clockson local area networks. This reduces the requirement to have accuratehardware clocks in every embedded system in a network. Eachembedded node can instead synchronize with a remote clock,providing the required accuracy.
SOF Status of fault
SPA Strömberg Protection Acquisition (SPA), a serial master/slave protocolfor point-to-point and ring communication.
SRY Switch for CB ready condition
ST Switch or push button to trip
Starpoint point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transport layerprotocol used on Ethernet and the Internet.
TCP/IP Transmission control protocol over Internet Protocol. The de factostandard Ethernet protocols incorporated into 4.2BSD Unix. TCP/IPwas developed by DARPA for Internet working and encompasses bothnetwork layer and transport layer protocols. While TCP and IP specifytwo protocols at specific protocol layers, TCP/IP is often used to referto the entire US Department of Defense protocol suite based uponthese, including Telnet, FTP, UDP and RDP.
TEF Time delayed -fault protection function
TLS Transport Layer Security
TM Transmit (disturbance data)
TNC connector Threaded Neill-Concelman, a threaded constant impedance version of aBNC connector
TP Trip (recorded fault)
TPZ, TPY, TPX, TPS Current transformer class according to IEC
TRM Transformer Module. This module transforms currents and voltagestaken from the process into levels suitable for further signalprocessing.
TYP Type identification
UMT User management tool
Section 9 1MRK511349-UEN AGlossary
90Communication protocol manual
Underreach A term used to describe how the relay behaves during a fault condition.For example, a distance relay is underreaching when the impedancepresented to it is greater than the apparent impedance to the faultapplied to the balance point, that is, the set reach. The relay does not“see” the fault but perhaps it should have seen it. See also Overreach.
UTC Coordinated Universal Time. A coordinated time scale, maintained bythe Bureau International des Poids et Mesures (BIPM), which forms thebasis of a coordinated dissemination of standard frequencies and timesignals. UTC is derived from International Atomic Time (TAI) by theaddition of a whole number of "leap seconds" to synchronize it withUniversal Time 1 (UT1), thus allowing for the eccentricity of the Earth'sorbit, the rotational axis tilt (23.5 degrees), but still showing the Earth'sirregular rotation, on which UT1 is based. The Coordinated UniversalTime is expressed using a 24-hour clock, and uses the Gregoriancalendar. It is used for aeroplane and ship navigation, where it is alsosometimes known by the military name, "Zulu time." "Zulu" in thephonetic alphabet stands for "Z", which stands for longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
3IO Three times zero-sequence current.
1MRK511349-UEN A Section 9Glossary
91Communication protocol manual
92
93
Scan this QR code to visit our website
1MR
K51
134
9-U
EN