A-28
Four functional levelsThe Compact NSX can be integrated in a Modbus communication environment. Four
functional levels can be used separately or combined.
Communication of status indications
This level is compatible with all Compact NSX circuit breakers, whatever the trip unit,
and with all switch-disconnectors. Using the BSCM module, the following information
is accessible:
b ON/OFF position (O/F)
b trip indication (SD)
b fault-trip indication (SDE).
Communication of commands
Also available on all circuit breakers and switch-disconnectors, this level
(communicating remote control) can be used to:
b open
b close
b reset.
Communication of measurements with Micrologic 5 / 6 A or E
This level provides access to all available information:
b instantaneous values A, E
b demand values E
b maximeters/minimeters A, E
b energy metering E
b demand current and power E
b power quality E.
Communication of operating assistance with Micrologic 5 / 6 A or E
b protection and alarm settings A, E
b time-stamped histories A, E
b event tables A, E
b maintenance indicators A, E.
1 Modbus network2 Modbus interface3 NSX cord4 Internal terminal block for communication via NSX cord5 BSCM module6 Prefabricated wiring7 Micrologic trip unit8 FDM121 display9 RJ45 cable10 Line terminator (on unused connector if applicable)
Communication components and connections
Connections
b Compact NSX is connected to the Modbus interface or FDM121 display unit via the internal terminal block for the NSX cord equipped with an RJ45 connector. v cord available in three lengths: 0.35 m, 1.3 m and 3 m.v insulated 1.3 m version for installations > 480 V ACv lengths up to 10 m possible using extensions.b The FDM121 display unit is connected to the Modbus interface by a communication cable with RJ45 connectors on both ends.
1.3 m
DB
112060.e
ps
Modbus
24 V DC
10
10
DB
115568.e
ps
All Compact NSX devices can be equipped with the
communication function via a prewired connection
system and a Modbus network interface.
The interface can be connected directly or via the
FDM121 switchboard display unit. Four functional
levels can be combined to adapt to all supervision
requirements.
Compact NSX communication Communications modules
Functions
and characteristics
A-29
Modbus interface module
Functions
This module, required for connection to the network,
contains the Modbus address (1 to 99) declared by the
user via the two dials in front. It automatically adapts
(baud rate, parity) to the Modbus network in which it is
installed.
It is equipped with a lock-out switch to enable or disable
operations involving writing to Micrologic, i.e. reset,
and closing commands, etc.
There is a built-in test function to check the connections
of the Modbus interface module with the Micrologic and
FDM121 display unit.
Mounting
The module is mounted on a DIN rail. A number of
modules may be clipped one next to the other.
For this, a stacking accessory is available for fast
clip-connection of both the Modbus link and the 24 V
DC supply.
The Modbus interface module supplies 24 V DC to the
corresponding Micrologic, FDM121 display and BSCM
module. Module consumption is 60 mA / 24 V DC.
BSCM module
Functions
The optional BSCM Breaker Status & Control Module
is used to acquire device status indications and control
the communicating remote-control function.
It includes a memory used to manage the maintenance
indicators.
Status indications
Indication of device status:
O/F, SD and SDE.
Maintenance indicators
The BSCM module manages the following indicators:
b mechanical operation counter
b electrical operation counter
b history of status indications.
It is possible to assign an alarm to the operation
counters.
Controls
The module can be used to carry out communicating
remote control operations: (open, close and reset) in
different modes (manual, auto).
Mounting
The BSCM module can be installed on all Compact
NSX circuit breakers and switch-disconnectors. It
simply clips into the auxiliary contact slots. It occupies
the slots of one O/F contact and one SDE contact. The
BSCM is supplied with 24 V DC power automatically
via the NSX cord when the communication system is
installed.
DB
112035.e
ps
DB
112083.e
ps
Modbus interface module.
DB
112084.e
ps
Mounting with stacking accessory.
DB
112085.e
ps
BSCM module.
1 Five-point Modbus and 24 V DC connector2 Two Modbus address dials (1 to 99)3
4 Lock-out to disable writing to the NSX5 Test LED6 Test button7 Two connectors for RJ45 cable
A-30
Functions
and characteristicsCompact NSX communication Networks and software
Internet
Modbus Modbus
FDM121
Masterpact Compact NSXCompact NS630b...3200
Modbus
PowerLogicSepam
FDM121
FDM121CCM
Firewall
Automatic
notification
Nomad
mode
Site Intranet
Ethernet (TCP/IP/Modbus)
Consultation
RSU
RCU
Consultation
RSU
RCU
Ethernet (TCP/IP/Modbus)
Modbus
ULP
EGX100/300EGX100/300
DB
415344.e
ps
Compact NSX uses the Modbus communication
protocol, compatible with ION-Enterprise PowerLogic
supervision system.
Also available Micrologic utilities RSU and RCU.
ModbusModbus is the most widely used communication protocol in industrial networks.
It operates in master-slave mode. The devices (slaves) communicate one after the
other with a gateway (master).
Masterpact, Compact NSX, PowerLogic and Sepam products all operate with this
protocol. A Modbus network is generally implemented on an LV or MV switchboard
scale.
Depending on the data monitored and the desired refresh rate, a Modbus network
connected to a gateway can serve 4 to 16 devices. For larger installations, a number
of Modbus networks can be connected to an Ethernet network (TCP/IP/Modbus
protocol) via their gateways.
A-31
GatewayThe gateway has two functions:
b access to the company intranet (Ethernet) by converting Modbus frames
to the TCP/IP/Modbus protocol
b optional web-page server for the information from the devices.
Examples include EGX300 and EGX100.
Micrologic utilitiesb Two utilities, RSU and RCU, presented on the next page, are available to assist
in starting up a communicating installation. Intended for Compact NSX and
Masterpact, the software can be downloaded from the Schneider Electric internet
site.
b The "Live update" function enables immediate updating to obtain the most recent
upgrades. These easy-to-use utilities include starting assistance and on-line help.
They are compatible with Microsoft Windows 2000, XP and Vista.
DB
112125.e
ps
DB
112214.e
ps
RCU mini-supervision screen for current measurements.
PE
86181r-
25.e
ps
EGX300.
A-32
Functions
and characteristicsCompact NSX communication RSU and RCU utilities
RSU (Remote Setting Utility)This utility is used to set the protection functions and alarms for each Masterpact and
Compact NSX device.
After connection to the network and entry of the circuit-breaker Modbus address, the
software automatically detects the type of trip unit installed.
There are two possible operating modes.
Off-line with the software disconnected from the
communication network For each selected circuit breaker, the user can do the following.
Determine the protection settings
The settings are carried out on a screen that shows the front of the trip unit. The
Micrologic setting dials, keypad and screen are simulated for easy use of all
Micrologic setting functions.
Save and duplicate the protection settings
also be duplicated and used as the basis for programming another circuit breaker.
On-line with the software connected to the networkSimilarly, for each selected circuit breaker, the user can do the following.
Display the current settings
The software displays the trip unit and provides access to all settings.
View the corresponding protection curves
A graphic curve module in the software displays the protection curve corresponding
studies.
Modify settings in a secure manner
b There are different levels of security:
v password: by default, it is the same for all devices, but can be differentiated for
each device
v locking of the Modbus interface module which must be unlocked before the
corresponding device can be set remotely
v maximum settings limited by the positions of the two dials on the trip unit.
These dials, set by the user, determine the maximum settings that can be made via
the communication system.
bv either direct, on-line setting of the protection settings on the screen
v or by loading the settings prepared in off-line mode. This is possible only if the
positions of the dials allow the new settings.
All manual settings made subsequently on the device have priority.
Program alarms
b Up to 12 alarms can be linked to measurements or events.
bv Micrologic 5: overload (Ir)
v Micrologic 6: overload (Ir) and ground fault (Ig)
b thresholds, priorities and time delays can be set for 10 other alarms. They may be
selected from a list of 91 alarms
Set the outputs of the SDx relays
assign different signals to the 2 outputs of the SDx relay.
RCU (Remote Control Utility)The RCU utility can be used to test communication for all the devices connected to
the Modbus network. It is designed for use with Compact NSX, Masterpact,
Advantys OTB and Power Meter devices. It offers a number of functions.
Mini supervisor
b Display of I, U, f, P, E and THD measurements for each device, via navigation.
b Display of ON/OFF status.
Open and close commands for each device
When all functions have been tested, this utility is replaced by the supervision
software selected for the installation.
Two utilities, RSU and RCU, are available to assist in
starting up a communicating installation.
They can be downloaded from the Schneider Electric
internet site and include a "Live update" function that
enables immediate updating.
DB
118724R
.eps
DB
118725R
.eps
RSU: Micrologic Remote Setting Utility.
DB
118723R
.eps
RCU: Remote Control Utility for communication tests.
A-33
Types of softwareCompact NSX, Compact and Masterpact communication functions are designed to
interface with software dedicated to electrical installations:
b switchboard supervision
b electrical installation supervision
b power system management: electrical engineering expert systems
b process control
b SCADA (Supervisory Control & Data Acquisition), EMS (Enterprise Management
System) or BMS (Building Management System) type software.
Integration of Compact NSXCompact NSX devices are integrated via Modbus interface modules connected via
FDM121 display units or NSX cords.
by ULP (Universal Logic Plug) symbols. The connection points on compatible
modules are marked in the same manner.
Schneider Electric solutions
Electrical switchboard supervision via EGX300 Web serversA simple solution for customers who want to consult the main electrical parameters
of switchboard devices without dedicated software.
Up to 16 switchboard devices are connected via Modbus interfaces to EGX300
Ethernet gateway integrating the functions of a web page server. The embedded
they provide is updated in real time.
The Web pages can be consulted using a standard Web browser on a PC connected
of alarms and threshold overruns is possible via e-mail or SMS (Short Message
Service).
ION.E electrical engineering expert system softwarePowerLogic® ION.E is a family of web-enabled software products for high-end
power-monitoring applications. It is designed for large power systems.
SMS products offer detailed analysis of electrical events, long-duration data logging
and extensive, economical report-building capabilities (e.g. consumption monitoring
and tariff management).
A wide variety of screens can be displayed in real time, including more than 50
tables, analogue meters, bargraphs, alarms logs with links to display waveforms and
Other software Compact, Masterpact and Compact NSX devices can forward their measurement
and operating information to special software integrating the electrical installation
and other technical facilities:
b SCADA process control software: Vijeo CITECT
b BMS Building Management System software: Vista.
Please consult us.
Supervision software
Schneider Electric electrical installation supervision,
management and expert system software integrates
DB
111370.e
ps
Connection symbol for Compact NSX compatible modules.
PE
86181r-
25.e
ps
EGX300.
PB
104807_
68.e
ps
ION.E software screen.