+ All Categories
Home > Documents > Component of power system

Component of power system

Date post: 04-Apr-2018
Category:
Upload: chi-huy
View: 219 times
Download: 0 times
Share this document with a friend

of 21

Transcript
  • 7/30/2019 Component of power system

    1/21

    1

    1. COMPONENTS OF ELECTRIC POWER SYSTEMS

    1.1 Introduction

    The intention of this chapter is to lay the groundwork for the study of electric power

    systems. This is done by developing some basic tools involving concepts, definitions, and some

    procedures fundamental to electric power systems. The chapter can be considered as a simple

    review of topics that will be utilized throughout this work. We start by introducing the principal

    electrical quantities that we will deal with in subsequent chapters.

    1.2 Power Concepts

    1.2.1 Single-Phase Systems

    The electric power systems specialist is in many instances more concerned with electric

    power in the circuit rather than the currents. To study steady-state behavior of circuits, some

    further definitions are necessary. Consider a sinusoidal voltage, v(t) in given by

    ( ) ( )tVtv m cos= (1.1)

    ( ) ( ) = tIti m cos (1.2)Note that in this case, the current lags the voltage by an angle . The instantaneous power isdefined as

    ( ) ( ) ( )

    ( ) ( ) ( ) ==

    tItVtp

    titvtp

    mm coscos(1.3)

    P

    V

    I

    V I cos

    t

    Figure 1.1. Current, Voltage, and Power Plotted Versus Time.

    The angle in these equations is positive for current lagging the voltage and negative for current

    leading the voltage. Using the trigonometric identity

  • 7/30/2019 Component of power system

    2/21

    2

    ( ) ( )[ ] ++= coscoscoscos21 ,

    the instantaneous power can be written as:

    ( ) ( )[ ] += tIV

    tp mm 2coscos2

    (1.4)

    A more useful quantity is the average power that is being delivered. This can be obtained by

    averaging the instantaneous power over a specified time-period, typically for one cycle. Since

    the average of ( ) t2cos is zero, through one complete cycle, the average power, P,becomes

    cos2

    mm IVP = (1.5)

    It is more convenient to use the effective (rms) values of voltage and current than the maximumvalues. Substituting rmsm VV 2= and rmsm II 2= , we get

    cosrmsrms IVP = (1.6)where, cos() is called the power factor (PF).

    Lagging power factor means the current lags the voltage by an angle , see Figure 1.2.

    Leading power factor means the current leads the voltage by an angle , see Figure 1.3.

    I

    Isin

    V

    IcosI

    Isin

    V

    Icos

    Figure 1.2. Phasor Diagram for Figure 1.3. Phasor Diagram for

    Lagging Power Factor. Leading Power Factor.

    COMPLEX POWER

    If the phasor expressions for voltage and current are known, the calculation of real and

    reactive power is accomplished conveniently in complex form. For a certain load or part of a

    circuit, the rms values of the voltage drop and the current flow are expressed as:

    == IIVV and0 It is common convention in the electric power industry to set the voltage angle as the angular

    reference. The complex power or the apparent power S is defined as the product of voltage

    times the conjugate of current, or

    sincos

    *

    IVjIVS

    IVIVS

    +=

    ==(1.7)

    where is the phase angle between the voltage and current. Equation (1.7) can be written as:

    ( )VAQjPS += (1.8)where

  • 7/30/2019 Component of power system

    3/21

    3

    ( ) ( )

    ( ) ( )VArIVQ

    WIVP

    sin

    cos

    =

    =(1.9)

    The power factor is therefore:

    S

    P

    QP

    P

    PQ =

    +=

    =

    22arctancoscos (1.10)

    POWER TRIANGLE

    Equation 1.8 suggests a graphical method of obtaining the overall P, Q, and phase angle,

    , for several loads in parallel. A power triangle can be drawn for an inductive load as shown inFigure 1.4. The signs ofP and Q are important in knowing the direction of the power flow, that

    is, whether power is being generated or absorbed when a voltage and current are specified.

    S = V I*

    Q = V Isin

    P = V Icos

    Figure 1.4. Power Triangle for an Inductive Load.

    EXAMPLE 1.1

    Consider the circuit shown in Figure 1.5 with the following parameters:

    R = 0.5 L = 2.122 mH

    C= 1600 F V= 1000 V

    R

    L

    C

    +

    -

    +

    -

    V I2 I1

    IS

    Figure 1.5. Circuit of Example 1.1.

    Find the following: (a) the source current, (b) the active, reactive, and apparent power

    into the circuit, (c) the power factor of the circuit.

    a) source current

    ( )( )( ) ( )( )( )

    A8.275.63A903.60A0.580.106

    A903.60F106.1s/r377V100

    A0.580.106H10122.2s/r3775.0

    V0100

    21

    3

    2

    31

    =+=+====

    =+

    =

    +=

    III

    jCjVI

    jLjR

    VI

    S

  • 7/30/2019 Component of power system

    4/21

    4

    b) power flows

    ( )( )

    Var2962

    W5617

    VA29625617

    VA8.276350A8.275.63V0100*

    ==

    +====

    Q

    P

    jS

    IVS

    c) power factor

    ( ) ( ) lagging88.08.27coscos

    8.27

    ====

    PF

    1.2.2 Three-Phase SystemsThe major assumption of all the electric power presently used is generated, transmitted,

    and distributed using balanced three-phase voltage systems. Three-phase operation is preferable

    to single-phase because a three-phase system is more efficient than a single-phase system, and

    the flow of power is constant.

    A balanced three-phase voltage system is composed of three-single phase voltage sources

    having the same magnitude and frequency but time-displaced from one another by 120 of acycle as shown in the phasor diagrams of Figure 1.6.

    120

    120

    120

    VA

    VB

    VC

    IA

    IB

    IC

    120

    120

    120

    Figure 1.6. Phasor Diagrams of a Balanced Three-Phase System.

    There are two possible connections of loads and sources in three-phase systems: wye-connection and delta-connection. Figure 1.7 shows the two types of connections for three-

    identical impedances.

    Because of the connections, new voltages and current quantities can be defined. Starting

    with the voltage, the line voltage or line-to-line voltage is that quantity between two supply lines

    or load terminals. For voltage variables, line-to-line quantities have subscripts with two phases

    (i.e., ab, bc, or ca). The line-to-neutral or line-to-ground voltage is that quantity between a

    supply line and the neutral or ground node of the circuit. The voltage variables for these have

    subscripts of only one phase or one phase and n for neutral or g for ground. For currents, a

    similar convention is used. A current flowing through an impedance or source between two lines

    is given a double subscript notation denoting the two phases. A current flowing though an

    impedance or source between a line and the neutral point may be either a single subscript or onefollowed by an n. A line current flowing from a source to a load may be a single or a double

  • 7/30/2019 Component of power system

    5/21

    5

    subscript notation denoting the particular phase or the symbols representing the nodes at each

    end of the line (i.e., a or Aa).

    Z Z

    Z

    Z

    Z

    Z

    n

    Ia

    Ic

    Ib

    Ia

    Ic

    IabIca

    Ibc

    Ib

    Vca

    Vca

    Van

    c

    b

    c b

    a a

    Figure 1.7. (a) Wye-Connected Load (b) Delta-Connected Load

    CURRENT AND VOLTAGE RELATIONS IN THE WYE CONNECTION

    The voltage appearing between any two of the line terminals a, b, and c have different

    relationships in magnitude and phase to the voltages appearing between any one terminal and the

    neutral point n. The set of voltages Vab, Vbc, and Vca are called the line voltages, and the set of

    voltages Van, Vbn, and Vcn are referred to as the phase voltages. Analysis of a phasor diagram

    provides the required relationships.

    30Van = Vp 0

    Vbn = Vp -120

    Vcn = Vp 120 Vab = 3 Vp 30

    Vca = 3 Vp 150

    Vbc = 3 Vp -90

    Figure 1.8. Phasor Diagram of the Phase and Line Voltages of a Wye-Connection.

    The effective values of the phase voltage are shown in Figure 1.8 as V an, Vbn, and Vcn.

    Each has the same magnitude, and each is displaced 120 from the other two phasors. The

    relation between the line voltage and the phase voltage at the terminal a and b can be written as:

  • 7/30/2019 Component of power system

    6/21

    6

    ==

    =

    303

    1200

    p

    pp

    bnanab

    V

    VV

    VVV

    (1.11)

    Similarly,

    =

    =

    1503

    903

    pca

    pbc

    VV

    VV

    Thus the relation between line-to-line voltage, VL and phase voltage Vp for a balanced wye-

    connected, three-phase voltage system is

    += 303 pL VV (1.12)

    The current flowing out of a line terminal is the same current that is flowing through the

    phase terminal. Thus the relation between the line current IL and phase current Ip for a wye-

    connected, three-phase system is

    pL II = (1.13)

    CURRENT AND VOLTAGE RELATIONS IN THE DELTA CONNECTION

    Consider now the case when three single-phase sources are rearranged to form a three-

    phase delta connection as shown in Figure 1.9. It is clear from the circuit shown that the line and

    phase voltages are the same. Thus:

    pLVV = (1.14)

    Ia

    Ib

    Iab

    Ica Ibc

    Ic

    c b

    a

    Vab

    Figure 1.9. Delta-Connected, Three-Phase Source.

    The phase and line currents, however, are not identical and the relationships between them can

    be obtained as:

  • 7/30/2019 Component of power system

    7/21

    7

    ==

    =

    120

    120

    0

    pca

    pbc

    pab

    II

    II

    II

    Also, from Figure 1.9, the relation between the line and phase currents can be obtained as:

    =

    ==

    1503

    0120

    p

    ppabcaa

    I

    IIIII

    Similarly,

    =

    =

    903

    303

    pc

    pb

    II

    II

    The phasor diagram in Figure 1.10 illustrates these relations. Thus the relation between line and

    phase currents for a balanced delta-connected system is:

    += 303 pL II (1.15)

    Note that in the equations above, VL, Vp, IL, and Ip are the rms or effective values of

    voltages and currents.

    Iab = Ip 0

    Ibc = Ip -120

    Ica = Ip 120 Ib = 3 Ip 30

    Iba = - Iab

    Ia = 3 Ip150

    Ic = 3 Ip -90

    Figure 1.10. Relation between Phase and Line Currents in a Delta Connection.

    POWER RELATIONSHIPS

    Assume that a balanced three-phase voltage source is supplying a balanced load. The

    three sinusoidal phase voltages can be written as:

    ( )

    ( )

    ( )+=

    =

    =

    120sin2)(

    120sin2)(

    sin2)(

    tVtV

    tVtV

    tVtV

    pc

    pb

    pa

    with the currents given by

  • 7/30/2019 Component of power system

    8/21

    8

    ( )

    ( )

    ( )

    +=

    =

    =

    120sin2)(

    120sin2)(

    sin2)(

    tItI

    tItI

    tItI

    pc

    pb

    pa

    where is the phase angle between the current and voltage in each phase or the power factorangle.

    The three-phase power can be defined as:

    coscoscos3 ++= ccbbaa IVIVIVP Using a trigonometric identity, we get the following:

    ( ) ( ) ( )[ ]{ } +++= 2402cos2402cos2coscos33 tttIVP pp The summation of the last three terms, in the above equation, is zero. Thus the three-phase

    power can be obtained as:

    ( ) cos33 ppIVP = (1.16)

    In wye-connected systems, Lp II = and 3Lp VV = , and in delta-connected systems,

    3Lp II = and Lp VV = . Thus, the power equation, Equation 1.16, reads in terms of linequantities:

    ( ) cos33 LLIVP = (1.17)Note that Equations 1.16 and 1.17 apply for both wye- and delta-connected systems.

    COMPLEX POWER

    The above analysis can be extended to include the reactive power, Q, or to get the

    apparent power, S, for a three-phase system.

    =

    =

    LL

    pp

    IV

    IVS

    3

    3 *3(1.18)

    If = 0pp VV and = pp II , then

    =pp

    IVS 33

    or in complex notation:

    ( )

    33

    3 sincos3

    jQP

    jIVS pp

    +=

    +=

    where

    cos3cos33 LLpp IVIVP == (1.19)

    sin3sin33 LLpp IVIVQ == (1.20)

  • 7/30/2019 Component of power system

    9/21

    9

    EXAMPLE 1.2

    A wye-connected, balanced three-phase load consisting of three impedances of 1030each as shown in Figure 1.11, is supplied with a balanced set of line-to-neutral voltages:

    ==

    =

    120220

    240220

    0220

    VV

    VV

    VV

    cn

    bn

    an

    a) Calculate the phasor currents in each line, b) calculate the line-to-line phasor voltages and

    show the corresponding phasor diagram, and c) calcualte the apparent power, active power, and

    reactive power supplied to the load.

    Z = 1030

    Z

    Z

    n

    Ia

    Ic

    Ib

    Van = 220V 0

    c

    b

    a

    Figure 1.11 Load Connection for Example 1.2.

    a) The phase currents of the loads are obtained as:

    = =

    =

    =

    =

    =

    90223010120220

    210223010

    240220

    30223010

    0220

    AVI

    AV

    I

    AV

    I

    cn

    bn

    an

    b) The line voltages are obtained as

    =

    ==

    303220

    2402200220

    V

    VV

    VVV baab

    or

  • 7/30/2019 Component of power system

    10/21

    10

    ( )

    =

    +=

    +=

    303220

    3003220

    303

    V

    V

    VV ananab

    Similarly,

    ( )

    =

    +=

    +=

    903220

    302403220

    303

    V

    V

    VV bnbnbc

    ( )

    =

    +=

    +=

    1503220

    301203220

    303

    V

    V

    VV cncnca

    30Van = 220V 0

    Vca Vab = 220 3 V 30Vcn

    Vbn

    Vbc

    Figure 1.13. Relation between Phase and Line Voltages in a Wye-Connection.

    c) The powers are given by:

    ( )( )

    VArQ

    WP

    VAj

    AV

    IVIVSananpp

    0.7260

    69.12574

    0.726069.12574

    300.14520302202203

    33

    3

    3

    3

    =

    =+=

    ==

    ==

  • 7/30/2019 Component of power system

    11/21

    11

    EXAMPLE 1.3

    A delta-connected, balanced three-phase load consisting of three impedances of

    1030 each as shown in Figure 1.13, is supplied with a balanced set of line-to-line voltages:

    V1502203

    V902203

    V302203

    =

    =

    =

    ca

    bc

    ab

    V

    V

    V

    a) Calculate the phasor voltage across each phase load, b) calculate the phase and line currents

    and show the corresponding phasor diagram, and c) calculate the apparent power, active power,

    and reactive power supplied to the load.

    Z Z

    Z

    Ia

    Ic

    IabIca

    Ibc

    Ib

    Vca

    cb

    a

    Vab

    Vca

    Figure 1.13 Load connection for example 1.3.

    a) For a delta connected load,

    V1502203

    V902203

    V302203

    =

    =

    =

    =

    ca

    bc

    ab

    LLphs

    V

    V

    V

    VV

    b) The phase currents in each of the impedances are:

    A120223

    A240223

    A02233010

    V302203

    =

    =

    =

    =

    ca

    bc

    ab

    I

    I

    I

    The line currents can be obtained as:

    A30661202230223 == =caaba

    III

  • 7/30/2019 Component of power system

    12/21

    12

    or

    ( ) ====

    30663003223303

    303

    AAII

    II

    aba

    pL

    Similarly,

    ==

    ==

    9066303

    21066303

    AII

    AII

    cac

    bcb

    -30

    Iab = 3 220 A

    IbIa = 66-30 A

    Ibc

    Ica

    Ic

    Figure 1.14 Relation between Phase and Line Currents in a Delta Connection.

    c) The apparent, active, and reactive powers are computed.

    ( )( )

    VAR0.21780

    W04.37724

    VA0.2178004.37724

    VA304356002233022033

    33

    3

    3

    3

    =

    =+=

    ==

    ==

    Q

    P

    j

    IVIVS ababpp

    g

    1.3 Power System Representation

    A major portion of the modern power system utilizes three-phase as circuits and devices.

    A balanced three-phase system is solved as a single-phase circuit made of one line and the

    neutral return. Standard symbols are used to indicate the various components. The simplified

    one-line diagram is called the single-line diagram. From the one-line diagram the impedance, or

    reactance, diagram can be conveniently developed, as shown in the following section. A further

    advantage of the one-line diagram is in the power flow studies. The one-line diagram rather

    becomes second nature to power system engineers as they attempt to visualize a widespread

    complex network.

  • 7/30/2019 Component of power system

    13/21

    13

    generator or motor

    transformer

    transmission line

    oil circuit breaker

    air circuit breaker

    static load

    delta connection

    ungrounded wye connection

    grounded wye connection

    Figure 1.15. Symbolic Representation of Elements of a Power System.

    Using the symbols in Figure 1.15, a section of a one-line diagram of a power system is

    shown in Figure 1.16.

    G1

    G2

    M

    Figure 1.16. A One-Line Diagram of a Portion of a Power System.

    1.3.1 Equivalent Circuit and Reactance Diagram

    We note from Figure 1.16 that the power system components are: generators,

    transformers, transmission lines, and loads. Equivalent circuits of these components may then be

    interconnected to obtain a circuit representation for the entire system. In other words, the one-

    line diagram may be replaced by an impedance diagram or a reactance diagram (if resistances are

    neglected).

    Thus, corresponding to Figure 1.16, the impedance and reactance diagrams are shown in

    Figures 1.17(a) and 1.17(b), respectively, on a per phase basis. In the equivalent circuit of the

    components in Figure 1.17(a) is based on the following assumptions:

    1. A generator can be represented by a voltage source in series with an inductive

    reactance. The internal resistance of the generator is negligible compared to the

    reactance.

    2. The motor load is inductive.

    3. The static load has a lagging power factor.4. A transformer is represented by a series impedance on a per phase basis.

  • 7/30/2019 Component of power system

    14/21

    14

    5. The transmission line is of medium length and can be represented by a T section.

    The reactance diagram, shown in Figure 1.17(b), is drawn by neglecting all theresistances, static loads, and capacitances of the transmission line. Reactance diagrams are

    generally used for short-circuit calculation, whereas the impedance diagram is used for power-

    flow studies.

    Transmission LineTransformer Transformer Motor &

    Static Load

    Generators

    (a) Impedance Diagram

    Transmission LineTransformer Transformer Motor &

    Static Load

    Generators

    (b) Corresponding Reactance Diagram

    Figure 1.17. Electrical Diagrams of the System Illustrated in Figure 1.16.

    1.4 Per-Unit Representation

    The per-unit (pu) system is used extensively in power system calculations. The

    representation simplifies the vast scaling of sizes from super-large generation and transmissionnetworks to the industrial distribution system or a residential load. The definition of the per-unit

    value of any quantity is given as:

    dimensionsametheofvaluebase

    valueactualvaluepu = (1.21)

    In any electrical network, a minimum of four base quantities is required to define completely a

    per-unit system: voltage, current, power, and impedance (or admittance).

    powerbase

    poweractualpowerunitper = (1.22)

  • 7/30/2019 Component of power system

    15/21

    15

    voltagebase

    voltageactualvoltageunitper = (1.23)

    currentbase

    currentactualcurrentunitper = (1.24)

    impedancebase

    impedanceactualimpedanceunitper = (1.25)

    If any two of these quantities are chosen arbitrarily, the other two become fixed. For example,

    selecting base values for voltage and power fixes the base values for current and impedance.

    Therefore, on a per phase basis the following relationships hold:

    voltagebasepowerbasecurrentbase = (1.26)

    currentbase

    voltagebaseimpedancebase = (1.27)

    EXAMPLE 1.4

    Calculate the base impedance and base current for a single-phase system if the base

    voltage is 7.2 kV and the base apparent power is 10 MVA.

    ( ) ( )

    A9.1388

    V7200

    VA000,000,10

    184.5

    VA000,000,10

    V720022

    =

    ==

    =

    ==

    Base

    Base

    Base

    Base

    Base

    Base

    BaseBase

    I

    V

    SI

    Z

    S

    VZ

    g

    For three-phase systems, we use the total or three-phase power and the line-to-line

    voltage as the base. For currents and impedance values, it is common practice to convert the

    system to a wye-connected network, and use the phase current and phase impedance as the bases.Hence, the base impedance and the base current can be computed directly from the three-phase

    values of the base apparent power and the line-to-line base voltage. Delta-connections for the

    moment are converted to wye-connected equivalents.

    Recall for wye-connections,pLL

    VV = 3 , and from Equations 1.18 and 1.27 we find:

    BaseLL

    Base

    BaseLL

    Base

    Basep

    Base

    BaseV

    S

    V

    S

    V

    SIcurrentbase

    ===

    33

    3,

    331 (1.26)

    Base

    BaseLL

    Base

    Basep

    Base

    I

    V

    I

    VZimpedanceBase

    3,

    == (1.27)

  • 7/30/2019 Component of power system

    16/21

    16

    and

    ( ) ( ) ( )Base

    BaseLL

    Base

    BaseLL

    Base

    Basep

    BaseS

    V

    S

    V

    S

    VZ

    === 3

    2

    3

    2

    1

    2

    3

    3(1.28)

    EXAMPLE 1.5

    A three-phase system delivers 18,000 kW to a pure resistive wye-connected load. The

    line-to-line voltage at the load terminals is 108 kV. Assuming the three-phase power base is

    30,000 kVA and the voltage base is 120 kV, find the following per unit quantities for the load:

    a) the per unit voltage,

    b) the per unit power,

    c) the per unit current, and

    d) the per unit impedance.

    a) The line-to-line base voltage is:

    kVVBaseLL 120=

    and the phase base voltage is:

    kVkV

    VV BaseLL

    Basep

    2.693

    120

    3

    ==

    =

    The actual line-to-neutral voltage is:

    kVkV

    VV LL

    p

    4.623

    108

    3

    ==

    =

    The per unit voltage is:

    pukV

    kV

    kV

    kV

    V

    V

    V

    VVBaseLL

    LL

    Basep

    p

    pu

    900.0120

    108

    2.69

    4.62===

    ==

    b) The three-phase base power is:

    kVAS 000,303 =

    and the single-phase base power is:

  • 7/30/2019 Component of power system

    17/21

    17

    kVAkVA

    SS

    000,103

    000,30

    331

    1

    ==

    =

    The per unit power is:

    puVA

    W

    VA

    W

    S

    P

    S

    PP

    BaseBase

    pu

    600.0000,30

    000,18

    000,10

    6000

    3

    3

    1

    1

    ===

    ==

    c) The per unit current is:

    pupu

    puj

    V

    SI

    pu

    pu

    pu

    667.0900.0

    0.0600.0=

    +=

    =

    The base current is:

    ( )A

    kV

    kVA

    V

    SI

    BaseLL

    Base

    Base

    3.1441203

    000,30

    3

    3

    =

    =

    =

    To verify the results, first calculate the actual current, which is:

    ApuA

    IIIpuBasep

    2.96)667.0)(3.144( ==

    =

    Calculate the load current from actual voltage and power:

    AII

    A

    kV

    kVAI

    pp

    p

    2.96

    2.96

    4.62

    000,6

    ==

    ==

    d) The per unit impedance is:

    pujpu

    pu

    I

    VZ

    pu

    pu

    pu

    0.0350.1667.0

    900.0+==

    =

    The base impedance is:

  • 7/30/2019 Component of power system

    18/21

    18

    ( )

    ( )==

    ==

    48030

    1202

    3

    2

    31

    MVA

    kV

    S

    V

    I

    VZ

    Base

    Base

    Base

    Base

    Base

    To verify the results, first calculate the actual impedance, which is:

    ==

    =

    648)350.1)(480( pu

    ZZZpuBasep

    Calculate the load resistance from actual voltage and current:

    ==

    ==

    648

    6482.96

    4.62

    pp

    p

    ZZ

    A

    kVZ

    1.4.2 Changing the Base of Per-Unit Quantities

    Often the per-unit impedance of a component of a system is expressed on a base other

    than the one selected as base for the part of the system in which the component is located. Since

    all impedances in any one part of a system must be expressed on the same impedance base when

    making computations, it is necessary to have a means of converting per-unit impedances from

    one base to another. From Equations (1.25) and (1.27) the per unit impedance can be given as:

    ( )23

    BaseLL

    BaseActualp

    Base

    Actualp

    puV

    SZ

    Z

    ZZ

    == (1,29)

    Equation (1.29) shows that per-unit impedance is directly proportional to base power and

    inversely proportional to the square of the base voltage. Therefore, to change from per-unit

    impedance on a given base to per-unit impedance on a new base, the following equation applies:

    2

    3

    3

    =

    newBaseLL

    oldBaseLL

    oldBase

    newBase

    puoldpunewV

    V

    S

    SZZ

    (1.30)

    Equation (1.30) is important in changing the per-unit impedance given on a particular

    base to a new base. In some problems, when transformers are involved we must choose morethan one voltage base for each primary and secondary side of the transformers and one power

    base for the entire system. The following examples will illustrate the procedure.

    EXAMPLE 1.6

    A three-phase 13.0 kV transmission line delivers 8 MVA at 13.6 kV to a resistive load.

    The per phase impedance of the line is (0.01 + j0.05) p.u. on a 13.0 kV, 8 MVA base. What is

    the voltage drop across the line in per unit and in volts?

    a) Choose the base voltage to be 13 kV and the base power equal to 8 MVA.

    The base current and the load current are:

  • 7/30/2019 Component of power system

    19/21

    19

    =

    =

    =

    =

    =

    =

    0956.03.355

    06.339

    06.3396.133

    0.8

    3.355

    0.133

    0.8

    puA

    AI

    AkV

    MWI

    A

    kV

    MVAI

    puLoad

    Load

    Base

    The voltage drop is calculate as:

    =+=+=

    =

    7.780487.00478.000956.0)05.001.0)(0956.0( jj

    ZIV linelinedrop

    b) The actual values for the line-to-line voltage drop and the phase voltage drop are:

    ==

    ==

    7.783663

    )0.13()7.780487.0(

    7.78633)0.13)(7.780487.0(

    VkV

    V

    VkVV

    pdrop

    LLdrop

    EXAMPLE 1.7

    The per phase reactance of a three-phase, 220 kV, 6.25 kVA transmission line is 8.4 .Find the reactance value in per unit, based on the rated values of the line. Convert the per unit

    reactance value to a 230 kV, 7.5 kVA base.

    a)

    ( )

    ( )==

    =

    744.7000,250,6

    000,2202

    3

    2

    VA

    V

    S

    VZ

    Base

    BaseLL

    Base

    pu

    Z

    XX

    Base

    pu

    085.1744.7

    4.8

    ==

    =

    b)

    pukV

    kV

    kVA

    kVApu

    V

    V

    S

    SXX

    newBase

    oldBase

    oldBase

    newBase

    puoldpunew

    19.1230

    220

    25.6

    5.7085.1

    2

    2

    =

    =

    =

  • 7/30/2019 Component of power system

    20/21

    20

    EXAMPLE 1.8

    Consider the system in Figure 1.18. Find the new per-unit values for each element of thesystem above based on a 2.0 MVA system base. Draw the impedance diagrams of the system.

    1 MVA

    11 kV

    j0.1 pu

    0.5 MVA

    11 kV

    j0.15 pu

    2 MVA

    11/33 kV

    j0.15 pu

    3 MVA

    33/11 kV

    j0.1 pu

    2 MVA

    12 kV

    j0.05 pu

    10 + j20

    Figure 1.18. Small Power System of Example 1.7.

    The per-unit values for each element of the three-phase system shown above are as follows:

    Machine 1 1.00 MVA, 11 kV, Z = j0.1 pu

    Machine 2 0.50 MVA, 11 kV, Z = j0.15 pu

    Machine 3 2.00 MVA, 12 kV, Z = j0.05 pu

    Transmission Line Z = 10 + j20

    Transformer 1 2.00 MVA, 11 / 33 kV, Z = j0.15 pu

    Transformer 2 3.00 MVA, 33 / 11 kV, Z = j0.10 pu

    a) The power base for the entire system is 2.00 MVA. The base voltages are chosen for the

    following areas as:

    Zone 1 kVVB 111 =

    Zone 2 kVVB 333311

    112 ==

    Zone 3 kVVB 111133

    333 ==

    1 MVA

    11 kV

    j0.1 pu

    0.5 MVA

    11 kV

    j0.15 pu

    2 MVA

    11/33 kV

    j0.15 pu

    3 MVA

    33/11 kV

    j0.1 pu

    2 MVA

    12 kV

    j0.05 pu

    10 + j20

    Zone 1

    11 kV

    Zone 2

    33 kV

    Zone 3

    11 kV

  • 7/30/2019 Component of power system

    21/21

    Figure 1.19. Three Voltage Zones of Example 1.7.

    The per-unit values for each element of the above system can be obtained by using Equation 1.30as follow:

    Machine 1: pujkV

    kV

    MW

    MWjZ newpu 20.0

    11

    11

    0.1

    0.210.0

    2

    =

    =

    Machine 2: pujkV

    kV

    MW

    MWjZ

    newpu 60.011

    11

    5.0

    0.215.0

    2

    =

    =

    Transformer 1: pujZ newpu 15.0=

    Transmission Line: ( ) == 5.5440.2

    332

    MVAkVZ

    Base

    pujj

    Zpu 037.0

    5.544

    20=

    =

    Transformer 2: pujkV

    kV

    MW

    MWjZ

    newpu 067.033

    33

    0.3

    0.210.0

    2

    =

    =

    Machine 3: pujkV

    kV

    MW

    MWjZ

    newpu06.0

    11

    12

    0.2

    0.205.0

    2

    =

    =

    b) The reactance diagram is shown in Figure 1.20.

    L1T1

    G1

    j0.2 j0.6

    j0.15

    G2

    j0.037 j0.067

    T2

    G3

    j0.6

    Figure 1.20. Reactance Diagram of Example 1.7.


Recommended