Generator Protection 55 g Multilin Secure, high-speed protection elements for complete generator protection, compliant with IEEE C37.102 Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P&C lifecycle costs Advanced fault and disturbance recording, including internal relay operating signals thus eliminating the need for external recording devices Robust network security enabling Critical Infrastructure Protection through user command logging, and dual permission access control Advanced automation capabilities for providing customized protection and control solutions Phasor Measurement Unit - Synchronised phasor information according to IEEE C37.118 standard Available Ethernet Global Data (EGD) eases integration with new and existing GE Energy control systems Reduced relay to relay wiring and associated installation costs through high-speed inter-relay communications Ambient temperature monitoring with alarming when outside temperature exceeds upper thresholds Medium to large generators typically driven by steam, gas or hydraulic turbines Pumped Storage generators used as pumping motors for reservoir storage Stand-alone protection or component in automated substation control system Standard protection product offering on new General Electric generator installations. Metering - current, voltage, power, energy, frequency Oscillography – analog and digital parameters at 64 samples/cycle Event Recorder - 1024 time tagged events with 0.5ms scan of digital inputs Data Logger - 16 channels with sampling rate up to 1 sample / cycle Advanced relay health diagnostics Synchronised measurement of voltage & current and sequence component phasors - 1 to 60 phasors/sec Monitoring and Metering Robust communications with up to 8 HardFiber Bricks Seamless integration with existing G60 functions Redundant architecture for dependability and security IEC 61850 Process Bus Interface Protection and Control Generator stator differential 100% stator ground protection Loss of excitation Power swing blocking and out-of-step tripping Backup distance Reverse / low forward power Restricted ground fault Overexcitation Generator unbalance Split phase protection Phase sequence reversal for pumped storage Communications Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703, C37.94 Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD) Direct I/O – secure, high-speed exchange of data between URs for Direct Transfer Trip and I/O Extension applications Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber optic ports and 2 copper ports FEATURES G60 GENERATOR PROTECTION SYSTEM Comprehensive protection for generators FEATURES APPLICATIONS KEY BENEFITS EnerVista™ Software Graphical Logic Designer and Logic Monitor to simplify designing and testing procedures Document and software archiving toolset to ensure reference material and device utilities are up-to-date EnerVista™ Integrator providing easy integration of data in the G60 into new or existing monitoring and control systems
Transcript

Gen

erat

or P

rote

ctio

n

55g Multilin

• Secure,high-speedprotectionelementsforcompletegeneratorprotection,compliantwithIEEEC37.102

• CompleteIEC61850ProcessBussolutionprovidingresourceoptimizationandminimizingtotalP&Clifecyclecosts

• Advancedfaultanddisturbancerecording,includinginternalrelayoperatingsignalsthuseliminatingtheneedforexternalrecordingdevices

• RobustnetworksecurityenablingCriticalInfrastructureProtectionthroughusercommandlogging,anddualpermissionaccesscontrol

• Advancedautomationcapabilitiesforprovidingcustomizedprotectionandcontrolsolutions

• PhasorMeasurementUnit-SynchronisedphasorinformationaccordingtoIEEEC37.118standard

• AvailableEthernetGlobalData(EGD)easesintegrationwithnewandexistingGEEnergycontrolsystems

• Reducedrelaytorelaywiringandassociatedinstallationcoststhroughhigh-speedinter-relaycommunications

• Ambienttemperaturemonitoringwithalarmingwhenoutsidetemperatureexceedsupperthresholds

• Mediumtolargegeneratorstypicallydrivenbysteam,gasorhydraulicturbines

• PumpedStoragegeneratorsusedaspumpingmotorsforreservoirstorage

• Stand-aloneprotectionorcomponentinautomatedsubstationcontrolsystem

• StandardprotectionproductofferingonnewGeneralElectricgeneratorinstallations.

• Metering-current,voltage,power,energy,frequency• Oscillography–analoganddigitalparametersat

64samples/cycle• EventRecorder-1024timetaggedeventswith0.5msscanof

digitalinputs• DataLogger-16channelswithsamplingrateupto

1sample/cycle• Advancedrelayhealthdiagnostics• Synchronisedmeasurementofvoltage&currentand

sequencecomponentphasors-1to60phasors/sec

Monitoring and Metering

• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingG60functions• Redundantarchitecturefordependabilityandsecurity

IEC 61850 Process Bus InterfaceProtection and Control• Generatorstatordifferential• 100%statorgroundprotection• Lossofexcitation• Powerswingblockingandout-of-steptripping• Backupdistance• Reverse/lowforwardpower• Restrictedgroundfault• Overexcitation• Generatorunbalance• Splitphaseprotection• Phasesequencereversalforpumpedstorage

Communications• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,

RS232,RS422,G.703,C37.94• MultipleProtocols-IEC61850,DNP3.0Level2,ModbusRTU,

ModbusTCP/IP,IEC60870-5-104,EthernetGlobalData(EGD)• DirectI/O–secure,high-speedexchangeofdatabetween

URsforDirectTransferTripandI/OExtensionapplications• EmbeddedManagedEthernetSwitchwith4-100MbitFiber

opticportsand2copperports

FEaturEs

G60GEnErator

ProtECtIon systEMComprehensiveprotection

forgenerators

FEaturEs

aPPlICatIons

KEy BEnEFIts

EnerVista™ software• GraphicalLogicDesignerandLogicMonitortosimplify

designingandtestingprocedures• Documentandsoftwarearchivingtoolsettoensure

referencematerialanddeviceutilitiesareup-to-date• EnerVista™Integratorprovidingeasyintegrationofdatain

theG60intoneworexistingmonitoringandcontrolsystems

Gen

erat

or P

rote

ctio

n

www.GEMultilin.com

G60Generator Protection system

56

Protection and ControlThe G60 Generator Protection Systemprovides comprehensive protection formediumand large generators, includinglarge steam and combustion turbines,combined-cycle generators and multi-circuit hydro units. The G60 includesadvancedautomationandcommunicationcapabilities, extensive I/O options, andpowerfulfaultrecordingfeaturesthatcansimplifypostmortemdisturbanceanalysisand helpminimize generator downtime.AspartoftheURFamily,theG60providessuperior protection and control thatincludes:

Generator stator Differential

High-speed stator differential protectionprovides sub-cycle detection and highspeed clearing of stator phase faults.Advanced CT saturation detectionalgorithms maintain immunity to highcurrentACandlowcurrentDCsaturationconditionsthatmayoccurduetoexternaldisturbancessuchas transformer inrushorneargeneratorfaultswithoutsacrificingspeedorsensitivity.

100% stator Ground

100% stator ground fault protection isprovided through a voltage differentialfeaturethatrespondstotheunbalanceofthethirdharmonicatthemachineterminalsandat theneutral point . Thismethod is

50G64REF 51G

64TN

51P 51N 46 67P 67N67_2 68 78

24 59P27P 59_2

Metering

TRIPSUPERVISED CLOSE

32 50/2740

59N 81U81O

27TN 59X27X

G60 Generator Protection System

G

52

R

87

50N

81R

50P21P

25

DEVICENUMBER

21P242527P27TN27X32404650G50N50P50SP50/2751G

Phase Distance BackupVolts Per HertzSynchrocheckPhase UndervoltageThird Harmonic Neutral UndervoltageAuxiliary UndervoltageSensitive Directional PowerLoss of ExcitationGenerator UnbalanceGround Instantaneous OvercurrentNeutral Instantaneous OvercurrentNeutral Instantaneous OvercurrentSplit Phase Protection Accidental EnergizationGround Time Overcurrent

FUNCTION

ANSI DEVICE NUMBERS AND FUNCTIONS

51P59N59P59X59_264TN67_267N67P68/7881O81R81U87G87S

Phase Time OvercurrentNeutral OvervoltagePhase OvervoltageAuxiliary OvervoltageNegative Sequence Overvoltage100% Stator GroundNegative Sequence Directional OvercurrentNeutral Directional OvercurrentPhase Directional OvercurrentPower Swing DetectionOverfrequencyRate of Change of FrequencyUnderfrequencyRestricted Ground FaultStator Differential

DEVICENUMBER FUNCTION

Functional Block Diagram

insensitive to the absolute value of thethird harmonic and is easily setwithoutthe need for on-linemeasurements. Forgenerator with delta connected PTs, athird harmonic undervoltage element isalso offered for detecting a loss of thethirdharmonic voltageat thegeneratorneutral.

loss of Excitation

Generator loss of excitation protectionis provided via twonegative offsetmhocharacteristics as per IEEE C37.102.

InadvertentpickuptimedelaysettingsandblockinginputprovidesecurityforblownVTfusesandpowerswingconditions.

Power swing / out-of-step

Thepowerswingblockingelementprovidesblockingofthebackupdistanceelementandotherprotectionsunderpowerswingconditions. Additionally, the out-of-steptrippingelementcanbeusedfortrippingthe generator when an unstable powerswingisdetected.

The G60 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.

DeviceNumber Function21P PhaseDistanceBackup24 VoltsPerHertz25 SynchronismCheck27P PhaseUndervoltage27TN ThirdHarmonicNeutralUndervoltage27X AuxiliaryUndervoltage32 SensitiveDirectionalPower40 LossofFieldRelay46 GeneratorUnbalance50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50SP SplitPhaseInstantaneousOvercurrent50/27 AccidentalEnergization51G GroundTimeOvercurrent51P PhaseTimeOvercurrent59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage59_2 NegativeSequenceOvervoltage64RGF RestrictedGroundFault64TN 100%StatorGround67_2 NegativeSequenceDirectionalOvercurrent67N NeutralDirectionalOvercurrent67P PhaseDirectionalOvercurrent68 PowerSwingBlocking78 Out-of-StepProtection81O Overfrequency81R RateofChangeofFrequency81U Underfrequency87 GeneratorStatorDifferential

ANSIDeviceNumbers&Functions

G60 - Protection, Metering, Monitoring and Control

Gen

erat

or P

rote

ctio

n

www.GEMultilin.com 57

G60Generator Protection system

protection for both the generator andtheunittransformer.User-programmableFlexCurvescaneasecoordinationissues.

split Phase Protection

Split phase protection is provided forsensitivedetectionforinter-turnfaultsandcanberuninconjunctionwiththeprimarystatordifferentialprotection.Independentsettingsareprovidedonaper-phasebasisand a single-slope bias characteristic isusedtoallowoperationonmachineswithasectionofwindingbypassed.

Pumped storage Generator

The G60 can be used for protectinggenerators thatarealso runaspumpedstorage motors without the need forswitchingtheCTsecondarycircuitry.TheG60isabletoautomaticallycompensatefor thephase reversal that occurswhenthegeneratorisbeingrunasamotor.

synchronism Check

The G60 provides elements to monitor

Backup Phase Distance

Threeseparatephasedistanceelementsprovide time-delayed backup protectionfor generator faults that have nototherwise been cleared by the primarysystem and generator protections. Eachzone can independently compensate forpowertransformers,socompensationcanbeappliedforzonesreachingoutintothesystemthroughtheunittransformer,whilezones looking into thestatorcanremainuncompensated.

sensitive Directional Power

Twoseparatedirectionalpowerelementsareprovidedtodetectgeneratormotoringtoprotecttheprimemoverfromdamage.Eachelementrespondstoeitherreverseorlowforwardpowerflowandcanbeusedto provide independent alarm and tripsettings.

restricted Ground Fault (rGF)

Restricted Ground Fault protection (alsoknown as zero sequence differential)extendsprotectioncoveragetotheneutralpoint of the stator winding, where faultcurrentsmaybebelowthepickupof themainstatordifferentialelement.Thelow-impedance RGF protection provided theG60usesanoptimizedadaptiverestraintsignal thatprovidessecurity forexternalfault conditions that may cause CTsaturationwhilestillmaintainingsensitivityforinternalfaults.

overexcitation Protection

Two separate Voltz-per-Hertz elementscan be used to provide overexcitation

The G60 Percent Differential Element has enhanced saturation detection algorithms to provide additional security against AC and DC saturation that can occur during faults near the generator.

differences in voltage magnitudes,phase angles, and frequencies toperform synchronism check across uptotwobreakers.TheG60canbeused inconjunctionwithanexternalsynchronizeras an independent check of thesynchronizerpriortoclosingthegeneratorbreaker.

IEC 61850 Process BusThe IEC 61850 Process Bus module isdesignedtointerfacewiththeGEMultilinHardFiberSystem,allowingbi-directionalIEC 61850 fiber optic communications.The HardFiber System is designed tointegrate seamlessly with the existingUniversal Relay applications, includingprotection functions,FlexLogic,meteringandcommunications.

The GEMultilin HardFiber System offersthefollowingbenefits:

• CommunicatesusingopenstandardIEC61850messaging

• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations

• IntegrateswithexistingG60’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule

• DoesnotintroducenewCyberSecurityconcerns

VisittheHardFiberSystemproductpageontheGEMultilinwebsiteformoredetails.

advanced automationTheG60incorporatesadvancedautomationfeatures including powerful FlexLogic™

Use the G60 to protect Pumped Storage Generators when motoring without having to switch CT secondary wiring.

Gen

erat

or P

rote

ctio

n

www.GEMultilin.com

G60Generator Protection system

58

programmablelogic,communication,andSCADAcapabilitiesthatfarsurpasswhatis found in the averagegenerator relay.TheG60integratesseamlesslywithotherURrelaysforcompletesystemprotection,includingtheunitandauxiliarytransformers,andBalanceofPlantprotection.

Flexlogic™

FlexLogic™ is the powerful UR-platformprogramming logic engine thatprovidesthe ability of creating customizedprotection and control schemes therebyminimizingtheneed,andtheassociatedcosts,ofauxiliarycomponentsandwiring.Using FlexLogic™, the G60 can beprogrammedtoproviderequiredtrippinglogic along with custom scheme logicfor generator breaker control (includinginterlockingwithexternalsynchronizers),transfer tripping schemes for remotebreakers and dynamic setting groupchanges.

scalable HardwareTheG60isavailablewithamultitudeofI/Oconfigurationstosuitthemostdemandingapplicationneeds.Theexpandablemodulardesignallowsforeasyconfigurationandfutureupgrades.

• MultipleCT/VTconfigurationsallowforimplementationofmanydifferent

schemes,includingconcurrentsplit-phaseanddifferentialprotection

• Flexible,modularI/Ocoveringabroadrangeofinputsignalsandtrippingschemes

• Typesofdigitaloutputsincludetrip-ratedForm-AandSolidStateRelay(SSR)mechanicallylatching,andForm-Coutputs

• Form-AandSSRoutputsavailablewithoptionalcircuitcontinuitymonitoringandcurrentdetectiontoverifycontinuityandhealthoftheassociatedcircuitry

• Mechanicallylatchingoutputscanbeusedtodevelopsecureinterlockingapplicationsandreplaceelectromechanicallockoutrelays

• RTDsandDCmAinputsareavailabletomonitorequipmentparameterssuchastemperature&pressure

Monitoring and MeteringTheG60includeshighaccuracymeteringandrecordingforallACsignals.Voltage,current,andpowermeteringarebuiltintothe relay as a standard feature. Currentandvoltageparameters are availableas total RMS magnitude, and asfundamental frequency magnitude andangle.

Fault and Disturbance recording

The advanced disturbance and eventrecording features within the G60 cansignificantly reduce the timeneeded forpostmortem analysis of power systemeventsandcreationofregulatoryreports.Recordingfunctionsinclude:

• SequenceofEvent(SOE)-1024timestampedevents

• Oscillography

-64digital&upto40Analogchannels

• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel

• FaultReports-Powerfulsummaryreportofpre-faultandfaultvalues

The very high sampling rate and largeamount of storage space available fordata recording in theG60caneliminatetheneed for installingcostly standalonerecordingequipment.

advanced Device Health Diagnostics

The G60 performs comprehensivedevice health diagnostic tests duringstartup and continuously at runtime totest its ownmajor functions and criticalhardware.Thesediagnostictestsmonitorforconditionsthatcould impactsecurityandavailabilityofprotection,andpresentdevicestatusviaSCADAcommunicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issues helps improve systemuptime.

• Comprehensivedevicehealthdiagnosticperformedduringstartup

• MonitorstheCT/VTinputcircuitrytovalidatetheintegrityofallsignals

CommunicationsThe G60 provides advanced commun-icationstechnologiesforremotedataandengineering access,making it easy andflexibletouseandintegrateintonewandexisting infrastructures. Direct supportfor fiber optic Ethernet provides high-bandwidth communicationsallowing forlow-latency controlsandhigh-speed file

FlexlogictM Designer

FlexLogicTM allows for customizing the G60 outputs for most generator protection schemes and applications.

Gen

erat

or P

rote

ctio

n

www.GEMultilin.com 59

G60Generator Protection system

transfersof relay faultandevent recordinformation. The available redundantEthernet option and the embeddedmanaged Ethernet switch providethe means of creating fault tolerantcommunicationarchitectures inaneasy,cost-effectivemannerwithouttheneedforintermediarycommunicationhardware.

The G60 supports the most popularindustrystandardprotocolsenablingeasy,direct integration into DCS and SCADAsystems.

• IEC61850

• DNP3.0

• EthernetGlobalData(EGD)

• IEC60870-5-104

• ModbusRTU,ModbusTCP/IP

Interoperability with Embedded IEC61850

UsetheG60withintegratedIEC61850tolower costs associated with generatorprotection, control and automation. GE

Multilin’s leadership in IEC61850 comesfrom thousandsof installeddevicesandfollows on seven years of developmentexperiencewithUCA2.0.

• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging

• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVista™ViewpointEngineer

• IntegrateGEMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVista™ViewpointMonitoring

Direct I/o Messaging

DirectI/Oallowsforsharingofhigh-speeddigital information betweenmultiple URrelaysviadirectback-to-backconnectionsor multiplexed through a standard DS0multiplexerchannelbank. Regardlessoftheconnectionmethod,DirectI/Oprovidescontinuousreal-timechannelmonitoringthat suppliesdiagnostics informationonchannelhealth.

DirectI/Oprovidessuperiorrelay-to-relaycommunications that can be used inadvancedinterlocking,generationrejectionandotherspecialprotectionschemes.

• Communicationwithupto16URrelaysinsingleorredundantringsratherthanstrictlylimitedtosimplisticpoint-to-pointconfigurationsbetweentwodevices

• ConnecttostandardDS0channelbanksthroughstandardRS422,G.703orIEEEC37.94interfacesorviadirectfiberopticconnections

• Noexternalorhandheldtesterrequiredtoprovidechanneldiagnosticinformation

Multi-language

TheG60supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista™ setup software, andproductmanual. Easily switch between Englishandanadditional languageon the localdisplayswithoutuploadingnewfirmware.

Analyze generator faults using both analog and digital power system quantities that are measured and recorded up to a rate of 64 samples per cycle.

Log generator operating parameters to allow for analyzing generator loading and performance over weeks and months.

Record the operation of the internal G60 elements and external connected devices with 1ms time-stamped accuracy to identify the Sequence of Operation of station devices during generator faults and disturbances.

Power system troubleshootingTheG60containsmanytoolsandreportsthatsimplifyandreducetheamountoftimerequiredfortroubleshootingpowersystemevents.

Gen

erat

or P

rote

ctio

n

www.GEMultilin.com

G60Generator Protection system

60

EnerVistatM softwareTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifieseveryaspectofusing theG60relay.TheEnerVista™ suite provides all the toolsto monitor the status of the protectedasset ,maintain the relay, and integrateinformation measured by the G60 intoDCS or SCADA monitoring systems.Convenient COMTRADE and Sequenceof Events viewers are an integral partof the UR Setup software included witheveryUR relay, tocarryoutpostmortemeventanalysistoensureproperprotectionsystemoperation.

EnerVista™ launchpad

EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneededforconfiguringandmaintainingGEMultilinproducts. The setup software withinLaunchpad allows configuring devicesin real-time by communicating usingserial,Ethernet,ormodemconnections,orofflinebycreatingsettingfilestobesenttodevicesatalatertime.

Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:

• Manuals

• ApplicationNotes

• GuideformSpecifications

• Brochures

• WiringDiagrams

• FAQs

• ServiceBulletins

Viewpoint Monitoring

Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems.ViewpointMonitoringprovidesacompleteHMIpackagewiththefollowingfunctionality:

• Plug&PlayDeviceMonitoring

• SystemSingle-LineMonitoring&Control

• AnnunciatorAlarmScreens

• TrendingReports

• AutomaticEventRetrieval

• AutomaticWaveformRetrieval

Viewpoint Engineer

Viewpoint Engineer is a set of powerfultools that will allow the configurationandtestingofURrelaysatasystemlevelin an easy-to-use graphical drag-and-drop environment . Viewpoint Engineerprovides the followingconfigurationand

commissioningutilities:

• GraphicalLogicDesigner

• GraphicalSystemDesigner

• GraphicalLogicMonitor

• GraphicalSystemMonitor

Viewpoint Maintenance

ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:

• SettingsSecurityAuditReport

• DeviceHealthReport

• SingleClickFaultDataRetrieval

EnerVista™ Integrator

EnerVista™IntegratorisatoolkitthatallowsseamlessintegrationofGEMultilindevicesintoneworexistingautomationsystems.IncludedinEnerVista™Integratoris:

• OPC/DDEServer

• GEMultilinDrivers

• AutomaticEventRetrieval

• AutomaticWaveformRetrieval

The internal operation of the G60 elements, logic, and outputs can be monitored in real time to simplify commissioning and troubleshooting procedures

Create G60 Setting File Templates to ensure critical settings are not altered

simplifying Commissioning and testing simplifying G60 Configuration

Gen

erat

or P

rote

ctio

n

www.GEMultilin.com 61

G60Generator Protection system

user InterfaceThe G60 front panel provides extensivelocalHMI capabilities. The local displayisusedformonitoring,statusmessaging,faultdiagnosis,anddeviceconfiguration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.

LEDindicators

Multi-LanguageDisplay• English• Russian• French• Chinese

UserProgrammablePushbuttons

typical Wiring

G60-H00-HCH-F8F-H6G-M8H-PXX-uXX-WXX

1

PowerSupply

9

CPU

JU MX LW KV BHT DN G FPS Rminimum GROUNDBUS

G60 GENERATOR MANAGEMENT RELAY

RS-232

DB-9

(front)

UR

CO

MPU

TER

1

TXD

RXD

RXD

TXD

SGN

DSG

ND

18 3 2 20 7 6 4 5 22

CO

NN

ECTO

RC

ON

NEC

TOR

22

33

44

55

66

77

88

99

6

Inputs/outputs

8

VT/CT

8

CT

TC

TC

2

1

SURGE

H6a

H8a

H5b

H7b

H8b

H5a

H7a

H6c

H8c

H5c

H7c

H1a

H2b

H1cH1b

H2c

H2a

H4a

H4c

H3bH3a

H4b

H3c

H1

H2

H3

H4

6G I

V

I

V

I

V

I

V

CRITICALFAILURE

OUTPUT

CONTROLPOWER

HILO

1

FILTERSURGE

B3a

B1b

B8a

B6b

B8b

B6a

B3b

B1aB2b

B5b

DC

F1c

F4a

F8c

F8a

F3c

F5a

F5c

F7c

F6a

F7a

F6c

F2c

VX

VA VB

VC

F4c

F1a

F4b

F1b

F2a

F3a

F2b

F3b

VX

VA VB

VC IA IB IC IGIA5

IA1

IB5

IC5

IG5

IB1

IC1

IG1

M3c

M4c

M4b

M4a

M1c

M1a

M1b

M3b

M2a

M3a

M2b

M2c

IA IB IC IGIA5

IA1

IB5

IC5

IG5

IB1

IC1

IG1

ABC

R

PROVIDED

F FFFFF

5a 5c 7c6a 7a6c

VA VB

VCVA VB

VC

Multilin

com

10BaseFL

10BaseFL

10BaseT

D1aD2a

D4bD3a

D4a IRIG-BInput

IRIG-BOutput

COM1

RS485

ALTERNATE

NORMAL

Tx2Rx2

Tx1Rx1

BNC

BNC

FibreOptic

*

RemoteDevice

Shielded

Co-axial

Co-axial

com

10BaseFL

10BaseFL

10BaseT

D1aD2a

D4bD3a

D4a IRIG-BInput

IRIG-BOutput

COM1

RS485

ALTERNATE

NORMAL

Tx2Rx2

Tx1Rx1

BNC

BNC

FibreOptic

*

RemoteDevice

Shielded

Co-axial

Co-axial

Gen

erat

or P

rote

ctio

n

G60 - * 00 - H * * - F ** - H ** - M ** - P ** - u ** - W/X ** For full sizeBaseUnit G60 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable) G RS485+multi-modeST10BaseF H RS485+multi-modeSTRedundant10BaseF J RS485+multi-modeST100BaseFX K RS485+multi-modeSTRedundant100BaseFX N RS485+10/100BaseT S RS485+6port,100Mbps,ManagedEthernetSwitchSoftwareOptions 00 NoSoftwareOptions 01 EthernetGlobalData(EGD) 03 IEC61850 04 EthernetGlobalData(EGD)+IEC61850 05 PhasorMeasurementUnit(PMU) 06 IEC61850+PhasorMeasurementUnit(PMU)Mount/Coating H Horizontal(19”rack)-Standard A Horizontal(19”rack)-HarshEnvironmentCoating V Vertical(3/4size)-Standard B Vertical(3/4size)-HarshEnvironmentCoatingUserInterface K EnhancedEnglishFrontPanel L EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttons M EnhancedFrenchFrontPanel N EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttons Q EnhancedRussianFrontPanel T EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttons U EnhancedChineseFrontPanel V EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons F VerticalFrontPanelwithEnglishdisplayPowerSupply H 125/250VAC/DC H RH 125/250VAC/DCwithredundant125/250VAC/DC L 24-48V(DConly)CT/VTDSP 8L 8L Standard4CT/4VTw/enhanceddiagnostics 8M 8M SensitiveGround4CT/4VTw/enhanceddiagnostics 8N 8N Standard8CTw/enhanceddiagnostics 8R 8R SensitiveGround8CTw/enhanceddiagnosticsIEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX Nomodule 4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs 4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs 4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish 4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs 67 67 67 67 67 8Form-A(NoMonitoring)Outputs 6C 6C 6C 6C 6C 8Form-COutputs 6D 6D 6D 6D 6D 16DigitalInputs 6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs 6F 6F 6F 6F 6F 8FastForm-COutputs 6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs 6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs 6M 6M 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs 6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs 6P 6P 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs 6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs 6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs 6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs 6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs 6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputsTransducerI/O 5A 5A 5A 5A 5A 4dcmAInputs,4dcmAOutputs 5C 5C 5C 5C 5C 8RTDInputs 5D 5D 5D 5D 5D 4RTDInputs,4dcmAOutputs 5E 5E 5E 5E 5E 4dcmAInputs,4RTDInputs 5F 5F 5F 5F 5F 8dcmAInputsInter-RelayCommunications 7A 820nm,multi-mode,LED,1Channel 7B 1300nm,multi-mode,LED,1Channel 7C 1300nm,single-mode,ELED,1Channel 7H 820nm,multi-mode,LED,2Channels 7I 1300nm,multi-mode,LED,2Channels 7J 1300nm,single-mode,ELED,2Channels 7S G.703,2Channels 7W RS422,2Channels 76 IEEEC37.94,820nm,multi-mode,LED,1Channel 77 IEEEC37.94,820nm,multi-mode,LED,2Channel 2S 6port,100Mbps,ManagedEthernetSwitch,HI(125/250VAC/DC) 2T 6port,100Mbps,ManagedEthernetSwitch,LO(24-48Vdc)

www.GEMultilin.com

G60Generator Protection system

62

ordering note: ToviewthelatestoptionsavailablefortheG60,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.

ordering

• URApplicationsILearningCD TRCD-URA1-C-S-1

• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1

• ViewpointEngineer VPE-1

• ViewpointMaintenance VPM-1

• ViewpointMonitoringIEC61850 VP-1-61850

accessories for the G60 • ViewGuideformSpecifications

• Downloadtheinstructionmanual

• Reviewapplicationsnotesandsupportdocuments

• BuyaG60online

• ViewtheURFamilybrochure

Visit www.GEMultilin.com/G60 to: