INTEGRATION INSTRUCTIONS FOR DEFENSOR MK5 Building Management Integration 2534752 EN 1304 e-LINKS
Transcript
Page 1: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

INTEGRATION INSTRUCTIONS FOR DEFENSOR MK5

Building Management Integration

2534

752

EN

130

4

e-LINKS

Page 2: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration
Page 3: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

3

Contents

1 Notes for the planning engineer 41.1 Overview 41.2 Network diagrams 41.2.1 BACnet/IP network 51.2.2 LonWorks network 5

2 Wiring 62.1 Wiring diagram for BACnet/IP 62.2 Wiring diagram for LonWorks 7

3 Configuration 83.1 ConfiguringtheDefensorMk5contolunit 83.2 Gatewayconfiguration 83.2.1 SettingtheIPaddressandsubnetmask 83.2.2 ModifyingtheBACnetNodeID 10

4 Communicationtables 124.1 Modbusdataregistertable 124.2 Conversiontablesgatewayvariables 15

Ordering form 23

Page 4: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

4

Itispossibletolinkupamaximumof8unitsviaasingleProtoCessor Gatewaytoabuildingman-agementsystem.TheProtoCessorGatewayisconnectedtotheleadunit.Allotherunits(uptoamaximumof8)aredaisy-chainedviatheNetworkLinkterminals.

Sinceeachunitcanbeseparatelyaddressed,itispossibletomonitorandcontroleachunitindi-vidually.Differentnetworkconfigurationsmaybeachievedandaremostlydependantonthetypeofnetworkpresentatthesite.

1 Notes for the planning engineer

Thee-LINKSoptionallowstheintegrationofDefensorMk5humidifiersintoaBACnet/IP or a Lon-Worksnetwork.Thee-LINKSoptionfeaturesaserial-interfaceGatewaywhichconvertstheinforma-tionfromthehostModbusprotocoltoaspecifiedsecondaryprotocol.

Thefollowingprotocoloptionsareavailableandmustbespecifiedwhenordering(orderingformseepage23):

PartNumber Protocols PartDescription2534859 BACnet/IP BMSMk5MastersetforBACnet/IP2534861 LonWorks BMSMk5MastersetforLonWorks2534862 BMSMk5Slavesetforsuccessiveunits

Thefollowingreadoutandsettingsfunctionsareavailable:

Functions Mk5Readoutofunitstatus(operatingmode,etc.) XReadoutofservicemessages XReadoutoferrorcode XReadoutofanalog(%)andsensor(%rh)demand XReadoutofunittype XReadoutactualsystemrequest XSettingthepowerlimitation XSettingthehumiditysetpoint(%rh/internalcontroller) XSettingtheproportionalrange XSettingtheintegraltime XRemotediagnosiswithsystemcheck X

1.2 Network diagrams

1.1 Overview

Page 5: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

5

Mk5/1 Mk5/2 Mk5/3Mk5/4...8

Mk5/1 Mk5/2 Mk5/3Mk5/4...8

1.2.1 BACnet/IP network

ThediagrambelowshowstheconnectionofaseriesofMk5unitstoanEthernetnetwork.ThisisonlypossibleforBACnetandisessentiallyreferredtoasaBACnet/IPconfiguration.Pleaseseechapter2.1foradditionaldetails.

1.2.2 LonWorks network

ThisdiagrambelowshowstheconnectionofaseriesofMk5unitstoaLonWorksnetworkviaashielded,twisted-paircable.Pleaseseechapter2.2foradditionaldetails.

Ethernet(BACnet/IP)

Gateway(connectedtoleadingunit)

LonWorks Router

LonWorks Device

LonWorks Device

LonWorks Device

Networkviashieldedtwisted-paircable

Gateway(connectedtoleadingunit)

Page 6: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

6

+5V

RxDTxD

12p

123456789CO

M-Po

rt (T

TL) H

4

123456789

10

+5V

GND

GND

RxDTxD

J4-10p

RxD A(–)TxD A(–)

TxD B(+)RxD B(+)

GND

OnOff

1 2 3 4 5 6 7 8

On On Off On Off On On Off

1

34

6789

101112

2

5

Inter

face 1

8813

DSub-9

Net + (Pin 6 + Pin 7)

Net – (Pin 1 + Pin 2)

Net +Net –

123456789

RxD A(–)TxD A(–)

TxD B(+)RxD B(+)

GND

4 5 6 7 8

On Off Off Off Off

DSub-9

123456789

RxD A(–)TxD A(–)

TxD B(+)RxD B(+)

GND

4 5 6 7 8

On Off On On Off

DSub-9

D0D1D0D1 D0D1

+– L1N

PE

*** *** ***

2 Wiring

TheinternalwiringandtheinstallationoftheGatewayoptionintheleadingunitaswellastheinternalwiringofthesuccessiveunitsaremadeatthefactory.Onsiteonlythegatewaymustbeconnectedtothenetwork(BACnet/IPorLonWorks)andthesuccessiveunitsmustbedaisy-chainedviatheNetworkLinkterminalsusingtwo-wirecables(seecorrespondingwiringdiagrams).

2.1 Wiring diagram for BACnet/IP

to network

external

internal

Mk5 / Unit 1(leading unit)

RJ45 Bus cable / Ethernet

24 V DC/ACPower Supply

NetworkLink

Mk5 / Unit 2 Mk5 / Unit 3

NetworkLink NetworkLink

Mk5 with 2-wire RS485 Interface **

** RS485 interface: details see documentation SAP Nr. 2519271 "Serial interface RS232 / RS485 Mk5, with software V1.21"Note: software version V1.21 (or higher) must be installed on Mk5 contol unit to operate the RS interface.

*** Termination of the bus system: to ensure the correct function the bus system must be terminated on both ends. For that purpose the dip switches 6 and 7 on the RS485 interface of the first and the last Mk5 unit in the bus system must be set to ON. On all intermediate Mk5 units the dip switches 6 and 7 must be set to OFF(see above diagram).

The successive units must be connected to the network by daisy-chain via the NetworkLink terminals! max. 50 m

white

brown

Page 7: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

7

+5V

RxDTxD

12p

123456789CO

M-Po

rt (T

TL) H

4

123456789

10

+5V

GND

GND

RxDTxD

J4-10p

RxD A(–)TxD A(–)

TxD B(+)RxD B(+)

GND

OnOff

1 2 3 4 5 6 7 8

On On Off On Off On On Off

1

34

6789

101112

2

5

Inter

face 1

8813

DSub-9

Net + (Pin 6 + Pin 7)

Net – (Pin 1 + Pin 2)

Net +Net –

–+

123456789

RxD A(–)TxD A(–)

TxD B(+)RxD B(+)

GND

4 5 6 7 8

On Off Off Off Off

DSub-9

123456789

RxD A(–)TxD A(–)

TxD B(+)RxD B(+)

GND

4 5 6 7 8

On Off On On Off

DSub-9

D0D1D0D1 D0D1

+– L1N

PE

*** *** ***

2.2 Wiring diagram for LonWorks

to network (via shielded twisted-pair cable)

external

internal

Mk5 / Unit 1(leading unit)

24 V DC/ACPower Supply

NetworkLink

Mk5 / Unit 2 Mk5 / Unit 3

NetworkLink NetworkLink

Mk5 with 2-wire RS485 Interface **

** RS485 interface: details see documentation SAP Nr. 2519271 "Serial interface RS232 / RS485 Mk5, with software V1.21"Note: software version V1.21 (or higher) must be installed on Mk5 contol unit to operate the RS interface.

*** Termination of the bus system: to ensure the correct function the bus system must be terminated on both ends. For that purpose the dip switches 6 and 7 on the RS485 interface of the first and the last Mk5 unit in the bus system must be set to ON. On all intermediate Mk5 units the dip switches 6 and 7 must be set to OFF(see above diagram).

The successive units must be connected to the network by daisy-chain via the NetworkLink terminals! max. 50 m

white

brown

Page 8: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

8

3 Configuration

3.1 ConfiguringtheDefensorMk5contolunit

EachDefensorMk5unitmusthaveauniqueModbusaddress.TheModbusaddresscanbeas-signedinthesetupleveloftheMk5controlunit.

3.2 Gatewayconfiguration

Theprotocolconfigurationismadeatthefactory,priortofinaltesting.Thebaudratesaread-justedtothefollowingvalues:

Protocol Baudrate

BACnet/IP 10/100BaseT

LonWorks 78125bps

Modbus address

1

Access the setup level of each control unit (see Defensor Mk5"Technical Documentation") and set the desired Modbus address.Important:makesuretheModbusaddressforeachunitisunique!

TheModbusparametersoftheDefensorMk5cannotbeadjustedandaresettothefollowingvalues:– 9600baud– 1startbit– 8databits– no parity– 1stopbit

3.2.1 SettingtheIPaddressandsubnetmask

For BACnet/IP and LonWorks application,anIPaddressandthesubnetmaskmustbeassignedtothegatewayinordertoaccessit.TheIPaddressandsubnetmaskmaybeassignedatthefactoryorcanbemodifiedatanytimeviatheintegratedFieldServerGUI(GraphicUserInterface)oftheProtoCessor.

ToconfiguretheIPaddressandthesubnetmaskviatheintegratedFieldServerGUIoftheProtoCes-sorproceedasfollows:

1. ConnecttheProtoCessorgatewaytoaPCusinganEthernetcross-overcable or directlytothenetworkusingastraightcable.

2. Thedefault IPaddressof theProtoCessorGateway isset to10.232.72.172,SubnetMask is255.255.0.0.MakesureyourPCisinthesameIPnetworkastheProtoCessorGateway;otherwiseassignastaticIPaddresstoyourPConthe10.232.72.0network.

3. PoweruptheProtoCessorGateway.

Page 9: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

9

4. Open your internet browser and enter the IP address of the gateway (by default ex factory10.232.72.172),thenconfirmtheentrywiththeEnterkey.

5. TheFieldServerGUIwillbestarted.

Page 10: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

10

6. Selectthemenupoint“Setup>NetworkSettings”inthe“Navigation Tree”.Entertheappropri-ate IP-Address and subnetmask.Toactivatethenewsettings,clickfirstonthebutton<Update IPsettings>andthenonthebutton<SystemRestart>.AfterrestartthegatewayisconfiguredtothenewIPaddressandsubnetmask.

7. InordertoaccesstheProtoCessorgateway,theIPaddressofyourlaptopmustbesettothesamenetworkastheProtoCessor.

3.2.2 Modifying the BACnet Node ID

1. Enterthe(new)IPaddressofthegatewayinyourinternetbrowserandconfirmtheentrywiththeEnterkey.TheFieldServerGUIwillbestarted.

2. Selectthemenupoint“Setup>FileTransfer”inthe“Navigation Tree”.Then,clickinthe“Re-trieve”sectiononthelink“config.csv”andsavetheconfigurationfiletothedesiredloactiononyourlaptop.

Page 11: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

11

3. Opentheconfigurationfile“config.csv”withatexteditor,changeinthesection“Server Side Nodes”ofthewindowtheNodeIDtotheappropriatevalueandsavetheconfigurationfile.

4. Selectthemenupoint“Setup>FileTransfer”inthe“Navigation Tree”.Clickinthe“Update” sectiononthebutton<Browse...>andselecttheconfigurationfileyouhavemodified.Then,clickonthebutton<Submit>inordertouploadconfigurationfileintotheProtoCessor.

Assoonastheuploadisfinishedacorrespondingmessageappearsintheupperpartofthewindow.Clickonthebutton<SystemRestart>torestartthesystemwiththenewsettings.AfterrestarttheNodeIDischangedtothenewvalue.

Page 12: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

12

4 Communicationtables

Thefollowingtableshowsthemodbusdataregistersandtheircorrespondinggatewayvariables.Note:the“_x” inthegatewayvariablenameindicatestheModbusaddressofthecorrespondingDefensorMk5unit.

RefertoDocumentation“2519271–SerialInterfaceRS232/RS485Mk5,withsoftwareV1.21”forfurtherdetailsregardingModbusapplications.

Name Description Register Variable name on Gateway

Read Unit Type 00 = 5kg/h 400V01 = 8kg/h 400V02 = 10kg/h 400V03 = 16kg/h 400V04 = 20kg/h 400V05 = 24kg/h 400V06 = 30kg/h 400V07 = 40kg/h 400V08 = 50kg/h 400V09 = 60kg/h 400V10 = reserve11 = 80kg/h 400V12 = 5kg/h 200V13 = 8kg/h 200V14 = 10kg/h 200V15 = 16kg/h 200V16 = 20kg/h 200V17 = 24kg/h 200V18 = 30kg/h 200V19 = 40kg/h 200V20 = 50kg/h 200V21 = 60kg/h 200V22 = reserve23 = 80kg/h 200V24 = 5kg/h 575V25 = 10kg/h 575V26 = 20kg/h 575V27 = 30kg/h 575V28 = 40kg/h 575V29 = 50kg/h 575V30 = 60kg/h 575V31 = 80kg/h 575V32 = 5kg/h 440-500V33 = 10kg/h 440-500V34 = 16kg/h 440-500V35 = 20kg/h 440-500V36 = 30kg/h 440-500V37 = 40kg/h 440-500V38 = 60kg/h 440-500V39 = 80kg/h 440-500V

40001(0)

nvoUnitType_x

Read Fault Status 0 = no fault1 = fault

40002(1)

nvoFaultStatus_x

Read Humidifier Status 0 = standby1 = humidifying

40003(2)

nvoHumStatus_x

Read Service Requirement Status 0 = no service required1 = service required

40004(3)

nvoServcieStat_x

4.1 Modbusdataregistertable

Page 13: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

13

Name Description Register Variable name on Gateway

Read Fill Level A-Module 1 = Level 02 = Level 1 (red)3 = Level 2 (red-green)4 = Level 3 (green)5 = Level 4 (green-yellow)6 = Level 5 (yellow)

40005(4)

nvoFillLevelAM_x

Read Fill Level B-Module 1 = Level 02 = Level 1 (red)3 = Level 2 (red-green)4 = Level 3 (green)5 = Level 4 (green-yellow)6 = Level 5 (yellow)

40006(5)

nvoFillLevelBM_x

Read Fill Valve 1 A-Module 0 = off1 = on

40007(6)

nvoFillVal1AM_x

Read Fill Valve 2 A-Module 0 = off1 = on

40008(7)

nvoFillVal2AM_x

Read Fill Valve 1 B-Module 0 = off1 = on

40009(8)

nvoFillVal1BM_x

Read Fill Valve 2 B-Module 0 = off1 = on

40010(9)

nvoFillVal2BM_x

Read Drain Pump A-Module 0 = off1 = on

40011(10)

nvoDrainPumpAM_x

Read Drain Pump B-Module 0 = off1 = on

40012(11)

nvoDrainPumpBM_x

Read RH or Demand 0 – 100% 40021(20)

nvoRHorDemand_x

Read Total Steam Request 0 – 100% 40022(21)

nvoTotSteamReq_x

Read Actual Fault Reason 00 = o.k. (no error)01 = reserve02 = reserve03 = reserve04 = reserve05 = reserve06 = reserve07 = reserve08 = reserve09 = reserve10 = reserve11 = Max. drain time exceeded A-module (Level N -> N-1)12 = Max. drain time exceeded B-module (Level N -> N-1)13 = Max. vaporization time exceeded A-module (Level N -> N-1)14 = Max. vaporization time exceeded B-module (Level N -> N-1)15 = Invalid level A-module16 = Invalid level B-module17 = Min. refill time not reached A-module (Level 2 -> 4)18 = Min. refill time not reached B-module (Level 2 -> 4)19 = Min. fill time not reached A-module (Level 2 -> 4)20 = Min. fill time not reached B-module (Level 2 -> 4)

40031(30)

nvoActFaultRea_x

Page 14: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

14

Name Description Register Variable name on Gateway

21 = Steam pressure supervision A-module (3x level 0 in 4 min)22 = Steam pressure supervision B-module (3x level 0 in 4 min)23 = F_COM (System error)24 = F_EEPROM (System error)25 = F_RAM (System error)26 = F_LCD (System error)

Read Small Service due Status 0 = No service required1 = Small service required

40032(31)

nvoSmallSerSta_x

Read Extended Service due Status 0 = No service required1 = Extended service required

40033(32)

nvoExtenSerSta_x

Read Int Safety Chain A-Module Sta-tus

0 = Closed (ok)1 = Open (not ok)

40034(33)

nvoIntSChAMSta_x

Read Int Safety Chain B-Module Sta-tus

0 = Closed (ok)1 = Open (not ok)

40035(34)

nvoIntSChBMSta_x

Read Ext Safety Chain Status 0 = Closed (ok)1 = Open (not ok)

40036(35)

nvoExtSChSta_x

Read Mains Failure B-Module Status 0 = Ok1 = Heating voltage drooped at Unit B

40037(36)

nvoMainsFailBM_x

Read Max Fill Time Exceeded A-Mod-ule

0 = Ok1 = No water A-Module

40038(37)

nvoMaxFillTiAM_x

Read Max Fill Time Exceeded B-Mod-ule

0 = Ok1 = No water B-Module

40039(38)

nvoMaxFillTiBM_x

Read Operating Hours Low Indicates the number of hours the humidifier has been in operating (0- 65535 h)

40051(50)

nvoOperatHours_x

Read Operating Hours High Indicates the number of hours the humidifier has been in operating (multiplied by 65535 h)

40052(51)

Read Hours To Small Service 0 – 750 hEquivalent to 100% demand

40053(52)

nvoH_SmallServ_x

Read Hours To Extended Service 600 – 6000 hEquivalent to 100% demand

40054(53)

nvoH_ExtenServ_x

Read Capacity Limit 10 – 100% 40101(100)

nvoCapaciLimit_xWrite Capacity Limit nviCapaciLimit_xRead Controller Set Point Humidity 10 – 100%rh 40102

(101)nvoSetPointHum_x

Write Controller Set Point Humidity nviSetPointHum_xRead Controller Proportional Band 4 – 100% 40103

(102)nvoProportBand_x

Write Controller Proportion Band nviProportBand_xRead Controller Integral Time 0 – 100 minutes 40104

(103)nvoIntegraTime_x

Write Controller Integral Time nviIntegraTime_xWrite CPU Warm Boot 1 = boot

Unit will reboot completely and does a level check40111 (110)

nviCPUWarmBoot_x

Registers 40001 to 40099: read with Modbus function 03Registers 40100 to 40111: read with Modbus function 03 and write with Modbus function 06

Page 15: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

15

4.2 Conversiontablesgatewayvariables

ThefollowingtablesshowtheProtoCessorgatewayvaribalesandtheirBACnet/IPandLonWorksequivalents.Note:thenumberattheendofthegatewayvariables(e.g.“_1”)indicatetheunitnumber(Modbusnumber)ofthecorrespondingDefensorMk5.IfthereisonlyoneMk5humidifier,allvariablenameswillendin“_1”.Iftwounitsarenetworkedtogether,thesecondunit’svariablenameswillendin“_2”.Forthreenetworkedunits,…“_3”andsoon.

Mk5 / Unit 1

ProtoCessor Gateway BACnet LonWorksVariable Name Type Instance SNVT SNVT # NV Index ElementnvoUnitType_1 AV 01 SNVT_switch 95 1 1nvoFillLevelAM_1 AV 02 SNVT_switch 95 2 1nvoFillLevelBM_1 AV 03 SNVT_switch 95 3 1nvoRHorDemand_1 AV 04 SNVT_count 8 4 1nvoTotSteamReq_1 AV 05 SNVT_count 8 5 1nvoActFaultRea_1 AV 06 SNVT_switch 95 6 1nvoOperatHours_1 AV 07 SNVT_time_hour 124 7 1nvoH_SmallServ_1 AV 08 SNVT_time_hour 124 8 1nvoH_ExtenServ_1 AV 09 SNVT_time_hour 124 9 1nvoCapaciLimit_1 AV 10 SNVT_count 8 10 1nvoSetPointHum_1 AV 11 SNVT_count 8 11 1nvoProportBand_1 AV 12 SNVT_count 8 12 1nvoIntegraTime_1 AV 13 SNVT_count 8 13 1nviCapaciLimit_1 AV 14 SNVT_count 8 14 1nviSetPointHum_1 AV 15 SNVT_count 8 15 1nviProportBand_1 AV 16 SNVT_count 8 16 1nviIntegraTime_1 AV 17 SNVT_count 8 17 1

nvoFaultStatus_1 BV 01 SNVT_switch 95 51 1nvoHumStatus_1 BV 02 SNVT_switch 95 52 1nvoServcieStat_1 BV 03 SNVT_switch 95 53 1nvoFillVal1AM_1 BV 04 SNVT_switch 95 54 1nvoFillVal2AM_1 BV 05 SNVT_switch 95 55 1nvoFillVal1BM_1 BV 06 SNVT_switch 95 56 1nvoFillVal2BM_1 BV 07 SNVT_switch 95 57 1nvoDrainPumpAM_1 BV 08 SNVT_switch 95 58 1nvoDrainPumpBM_1 BV 09 SNVT_switch 95 59 1nvoSmallSerSta_1 BV 10 SNVT_switch 95 60 1nvoExtenSerSta_1 BV 11 SNVT_switch 95 61 1nvoIntSChAMSta_1 BV 12 SNVT_switch 95 62 1nvoIntSChBMSta_1 BV 13 SNVT_switch 95 63 1nvoExtSChSta_1 BV 14 SNVT_switch 95 64 1nvoMainsFailBM_1 BV 15 SNVT_switch 95 65 1nvoMaxFillTiAM_1 BV 16 SNVT_switch 95 66 1nvoMaxFillTiBM_1 BV 17 SNVT_switch 95 67 1nviCPUWarmBoot_1 BV 18 SNVT_switch 95 68 1

Page 16: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

16

Mk5 / Unit 2

ProtoCessor Gateway BACnet LonWorksVariable Name Type Instance SNVT SNVT # NV Index ElementnvoUnitType_2 AV 51 SNVT_switch 95 101 1nvoFillLevelAM_2 AV 52 SNVT_switch 95 102 1nvoFillLevelBM_2 AV 53 SNVT_switch 95 103 1nvoRHorDemand_2 AV 54 SNVT_count 8 104 1nvoTotSteamReq_2 AV 55 SNVT_count 8 105 1nvoActFaultRea_2 AV 56 SNVT_switch 95 106 1nvoOperatHours_2 AV 57 SNVT_time_hour 124 107 1nvoH_SmallServ_2 AV 58 SNVT_time_hour 124 108 1nvoH_ExtenServ_2 AV 59 SNVT_time_hour 124 109 1nvoCapaciLimit_2 AV 60 SNVT_count 8 110 1nvoSetPointHum_2 AV 61 SNVT_count 8 111 1nvoProportBand_2 AV 62 SNVT_count 8 112 1nvoIntegraTime_2 AV 63 SNVT_count 8 113 1nviCapaciLimit_2 AV 64 SNVT_count 8 114 1nviSetPointHum_2 AV 65 SNVT_count 8 115 1nviProportBand_2 AV 66 SNVT_count 8 116 1nviIntegraTime_2 AV 67 SNVT_count 8 117 1

nvoFaultStatus_2 BV 51 SNVT_switch 95 151 1nvoHumStatus_2 BV 52 SNVT_switch 95 152 1nvoServcieStat_2 BV 53 SNVT_switch 95 153 1nvoFillVal1AM_2 BV 54 SNVT_switch 95 154 1nvoFillVal2AM_2 BV 55 SNVT_switch 95 155 1nvoFillVal1BM_2 BV 56 SNVT_switch 95 156 1nvoFillVal2BM_2 BV 57 SNVT_switch 95 157 1nvoDrainPumpAM_2 BV 58 SNVT_switch 95 158 1nvoDrainPumpBM_2 BV 59 SNVT_switch 95 159 1nvoSmallSerSta_2 BV 60 SNVT_switch 95 160 1nvoExtenSerSta_2 BV 61 SNVT_switch 95 161 1nvoIntSChAMSta_2 BV 62 SNVT_switch 95 162 1nvoIntSChBMSta_2 BV 63 SNVT_switch 95 163 1nvoExtSChSta_2 BV 64 SNVT_switch 95 164 1nvoMainsFailBM_2 BV 65 SNVT_switch 95 165 1nvoMaxFillTiAM_2 BV 66 SNVT_switch 95 166 1nvoMaxFillTiBM_2 BV 67 SNVT_switch 95 167 1nviCPUWarmBoot_2 BV 68 SNVT_switch 95 168 1

Page 17: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

17

Mk5 / Unit 3

ProtoCessor Gateway BACnet LonWorksVariable Name Type Instance SNVT SNVT # NV Index ElementnvoUnitType_3 AV 101 SNVT_switch 95 201 1nvoFillLevelAM_3 AV 102 SNVT_switch 95 202 1nvoFillLevelBM_3 AV 103 SNVT_switch 95 203 1nvoRHorDemand_3 AV 104 SNVT_count 8 204 1nvoTotSteamReq_3 AV 105 SNVT_count 8 205 1nvoActFaultRea_3 AV 106 SNVT_switch 95 206 1nvoOperatHours_3 AV 107 SNVT_time_hour 124 207 1nvoH_SmallServ_3 AV 108 SNVT_time_hour 124 208 1nvoH_ExtenServ_3 AV 109 SNVT_time_hour 124 209 1nvoCapaciLimit_3 AV 110 SNVT_count 8 210 1nvoSetPointHum_3 AV 111 SNVT_count 8 211 1nvoProportBand_3 AV 112 SNVT_count 8 212 1nvoIntegraTime_3 AV 113 SNVT_count 8 213 1nviCapaciLimit_3 AV 114 SNVT_count 8 214 1nviSetPointHum_3 AV 115 SNVT_count 8 215 1nviProportBand_3 AV 116 SNVT_count 8 216 1nviIntegraTime_3 AV 117 SNVT_count 8 217 1

nvoFaultStatus_3 BV 101 SNVT_switch 95 251 1nvoHumStatus_3 BV 102 SNVT_switch 95 252 1nvoServcieStat_3 BV 103 SNVT_switch 95 253 1nvoFillVal1AM_3 BV 104 SNVT_switch 95 254 1nvoFillVal2AM_3 BV 105 SNVT_switch 95 255 1nvoFillVal1BM_3 BV 106 SNVT_switch 95 256 1nvoFillVal2BM_3 BV 107 SNVT_switch 95 257 1nvoDrainPumpAM_3 BV 108 SNVT_switch 95 258 1nvoDrainPumpBM_3 BV 109 SNVT_switch 95 259 1nvoSmallSerSta_3 BV 110 SNVT_switch 95 260 1nvoExtenSerSta_3 BV 111 SNVT_switch 95 261 1nvoIntSChAMSta_3 BV 112 SNVT_switch 95 262 1nvoIntSChBMSta_3 BV 113 SNVT_switch 95 263 1nvoExtSChSta_3 BV 114 SNVT_switch 95 264 1nvoMainsFailBM_3 BV 115 SNVT_switch 95 265 1nvoMaxFillTiAM_3 BV 116 SNVT_switch 95 266 1nvoMaxFillTiBM_3 BV 117 SNVT_switch 95 267 1nviCPUWarmBoot_3 BV 118 SNVT_switch 95 268 1

Page 18: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

18

Mk5 / Unit 4

ProtoCessor Gateway BACnet LonWorksVariable Name Type Instance SNVT SNVT # NV Index ElementnvoUnitType_4 AV 151 SNVT_switch 95 301 1nvoFillLevelAM_4 AV 152 SNVT_switch 95 302 1nvoFillLevelBM_4 AV 153 SNVT_switch 95 303 1nvoRHorDemand_4 AV 154 SNVT_count 8 304 1nvoTotSteamReq_4 AV 155 SNVT_count 8 305 1nvoActFaultRea_4 AV 156 SNVT_switch 95 306 1nvoOperatHours_4 AV 157 SNVT_time_hour 124 307 1nvoH_SmallServ_4 AV 158 SNVT_time_hour 124 308 1nvoH_ExtenServ_4 AV 159 SNVT_time_hour 124 309 1nvoCapaciLimit_4 AV 160 SNVT_count 8 310 1nvoSetPointHum_4 AV 161 SNVT_count 8 311 1nvoProportBand_4 AV 162 SNVT_count 8 312 1nvoIntegraTime_4 AV 163 SNVT_count 8 313 1nviCapaciLimit_4 AV 164 SNVT_count 8 314 1nviSetPointHum_4 AV 165 SNVT_count 8 315 1nviProportBand_4 AV 166 SNVT_count 8 316 1nviIntegraTime_4 AV 167 SNVT_count 8 317 1

nvoFaultStatus_4 BV 151 SNVT_switch 95 351 1nvoHumStatus_4 BV 152 SNVT_switch 95 352 1nvoServcieStat_4 BV 153 SNVT_switch 95 353 1nvoFillVal1AM_4 BV 154 SNVT_switch 95 354 1nvoFillVal2AM_4 BV 155 SNVT_switch 95 355 1nvoFillVal1BM_4 BV 156 SNVT_switch 95 356 1nvoFillVal2BM_4 BV 157 SNVT_switch 95 357 1nvoDrainPumpAM_4 BV 158 SNVT_switch 95 358 1nvoDrainPumpBM_4 BV 159 SNVT_switch 95 359 1nvoSmallSerSta_4 BV 160 SNVT_switch 95 360 1nvoExtenSerSta_4 BV 161 SNVT_switch 95 361 1nvoIntSChAMSta_4 BV 162 SNVT_switch 95 362 1nvoIntSChBMSta_4 BV 163 SNVT_switch 95 363 1nvoExtSChSta_4 BV 164 SNVT_switch 95 364 1nvoMainsFailBM_4 BV 165 SNVT_switch 95 365 1nvoMaxFillTiAM_4 BV 166 SNVT_switch 95 366 1nvoMaxFillTiBM_4 BV 167 SNVT_switch 95 367 1nviCPUWarmBoot_4 BV 168 SNVT_switch 95 368 1

Page 19: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

19

Mk5 / Unit 5

ProtoCessor Gateway BACnet LonWorksVariable Name Type Instance SNVT SNVT # NV Index ElementnvoUnitType_5 AV 201 SNVT_switch 95 401 1nvoFillLevelAM_5 AV 202 SNVT_switch 95 402 1nvoFillLevelBM_5 AV 203 SNVT_switch 95 403 1nvoRHorDemand_5 AV 204 SNVT_count 8 404 1nvoTotSteamReq_5 AV 205 SNVT_count 8 405 1nvoActFaultRea_5 AV 206 SNVT_switch 95 406 1nvoOperatHours_5 AV 207 SNVT_time_hour 124 407 1nvoH_SmallServ_5 AV 208 SNVT_time_hour 124 408 1nvoH_ExtenServ_5 AV 209 SNVT_time_hour 124 409 1nvoCapaciLimit_5 AV 210 SNVT_count 8 410 1nvoSetPointHum_5 AV 211 SNVT_count 8 411 1nvoProportBand_5 AV 212 SNVT_count 8 412 1nvoIntegraTime_5 AV 213 SNVT_count 8 413 1nviCapaciLimit_5 AV 214 SNVT_count 8 414 1nviSetPointHum_5 AV 215 SNVT_count 8 415 1nviProportBand_5 AV 216 SNVT_count 8 416 1nviIntegraTime_5 AV 217 SNVT_count 8 417 1

nvoFaultStatus_5 BV 201 SNVT_switch 95 451 1nvoHumStatus_5 BV 202 SNVT_switch 95 452 1nvoServcieStat_5 BV 203 SNVT_switch 95 453 1nvoFillVal1AM_5 BV 204 SNVT_switch 95 454 1nvoFillVal2AM_5 BV 205 SNVT_switch 95 455 1nvoFillVal1BM_5 BV 206 SNVT_switch 95 456 1nvoFillVal2BM_5 BV 207 SNVT_switch 95 457 1nvoDrainPumpAM_5 BV 208 SNVT_switch 95 458 1nvoDrainPumpBM_5 BV 209 SNVT_switch 95 459 1nvoSmallSerSta_5 BV 210 SNVT_switch 95 460 1nvoExtenSerSta_5 BV 211 SNVT_switch 95 461 1nvoIntSChAMSta_5 BV 212 SNVT_switch 95 462 1nvoIntSChBMSta_5 BV 213 SNVT_switch 95 463 1nvoExtSChSta_5 BV 214 SNVT_switch 95 464 1nvoMainsFailBM_5 BV 215 SNVT_switch 95 465 1nvoMaxFillTiAM_5 BV 216 SNVT_switch 95 466 1nvoMaxFillTiBM_5 BV 217 SNVT_switch 95 467 1nviCPUWarmBoot_5 BV 218 SNVT_switch 95 468 1

Page 20: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

20

Mk5 / Unit 6

ProtoCessor Gateway BACnet LonWorksVariable Name Type Instance SNVT SNVT # NV Index ElementnvoUnitType_6 AV 251 SNVT_switch 95 501 1nvoFillLevelAM_6 AV 252 SNVT_switch 95 502 1nvoFillLevelBM_6 AV 253 SNVT_switch 95 503 1nvoRHorDemand_6 AV 254 SNVT_count 8 504 1nvoTotSteamReq_6 AV 255 SNVT_count 8 505 1nvoActFaultRea_6 AV 256 SNVT_switch 95 506 1nvoOperatHours_6 AV 257 SNVT_time_hour 124 507 1nvoH_SmallServ_6 AV 258 SNVT_time_hour 124 508 1nvoH_ExtenServ_6 AV 259 SNVT_time_hour 124 509 1nvoCapaciLimit_6 AV 260 SNVT_count 8 510 1nvoSetPointHum_6 AV 261 SNVT_count 8 511 1nvoProportBand_6 AV 262 SNVT_count 8 512 1nvoIntegraTime_6 AV 263 SNVT_count 8 513 1nviCapaciLimit_6 AV 264 SNVT_count 8 514 1nviSetPointHum_6 AV 265 SNVT_count 8 515 1nviProportBand_6 AV 266 SNVT_count 8 516 1nviIntegraTime_6 AV 267 SNVT_count 8 517 1

nvoFaultStatus_6 BV 251 SNVT_switch 95 551 1nvoHumStatus_6 BV 252 SNVT_switch 95 552 1nvoServcieStat_6 BV 253 SNVT_switch 95 553 1nvoFillVal1AM_6 BV 254 SNVT_switch 95 554 1nvoFillVal2AM_6 BV 255 SNVT_switch 95 555 1nvoFillVal1BM_6 BV 256 SNVT_switch 95 556 1nvoFillVal2BM_6 BV 257 SNVT_switch 95 557 1nvoDrainPumpAM_6 BV 258 SNVT_switch 95 558 1nvoDrainPumpBM_6 BV 259 SNVT_switch 95 559 1nvoSmallSerSta_6 BV 260 SNVT_switch 95 560 1nvoExtenSerSta_6 BV 261 SNVT_switch 95 561 1nvoIntSChAMSta_6 BV 262 SNVT_switch 95 562 1nvoIntSChBMSta_6 BV 263 SNVT_switch 95 563 1nvoExtSChSta_6 BV 264 SNVT_switch 95 564 1nvoMainsFailBM_6 BV 265 SNVT_switch 95 565 1nvoMaxFillTiAM_6 BV 266 SNVT_switch 95 566 1nvoMaxFillTiBM_6 BV 267 SNVT_switch 95 567 1nviCPUWarmBoot_6 BV 268 SNVT_switch 95 568 1

Page 21: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

21

Mk5 / Unit 7

ProtoCessor Gateway BACnet LonWorksVariable Name Type Instance SNVT SNVT # NV Index ElementnvoUnitType_7 AV 301 SNVT_switch 95 601 1nvoFillLevelAM_7 AV 302 SNVT_switch 95 602 1nvoFillLevelBM_7 AV 303 SNVT_switch 95 603 1nvoRHorDemand_7 AV 304 SNVT_count 8 604 1nvoTotSteamReq_7 AV 305 SNVT_count 8 605 1nvoActFaultRea_7 AV 306 SNVT_switch 95 606 1nvoOperatHours_7 AV 307 SNVT_time_hour 124 607 1nvoH_SmallServ_7 AV 308 SNVT_time_hour 124 608 1nvoH_ExtenServ_7 AV 309 SNVT_time_hour 124 609 1nvoCapaciLimit_7 AV 310 SNVT_count 8 610 1nvoSetPointHum_7 AV 311 SNVT_count 8 611 1nvoProportBand_7 AV 312 SNVT_count 8 612 1nvoIntegraTime_7 AV 313 SNVT_count 8 613 1nviCapaciLimit_7 AV 314 SNVT_count 8 614 1nviSetPointHum_7 AV 315 SNVT_count 8 615 1nviProportBand_7 AV 316 SNVT_count 8 616 1nviIntegraTime_7 AV 317 SNVT_count 8 617 1

nvoFaultStatus_7 BV 301 SNVT_switch 95 651 1nvoHumStatus_7 BV 302 SNVT_switch 95 652 1nvoServcieStat_7 BV 303 SNVT_switch 95 653 1nvoFillVal1AM_7 BV 304 SNVT_switch 95 654 1nvoFillVal2AM_7 BV 305 SNVT_switch 95 655 1nvoFillVal1BM_7 BV 306 SNVT_switch 95 656 1nvoFillVal2BM_7 BV 307 SNVT_switch 95 657 1nvoDrainPumpAM_7 BV 308 SNVT_switch 95 658 1nvoDrainPumpBM_7 BV 309 SNVT_switch 95 659 1nvoSmallSerSta_7 BV 310 SNVT_switch 95 660 1nvoExtenSerSta_7 BV 311 SNVT_switch 95 661 1nvoIntSChAMSta_7 BV 312 SNVT_switch 95 662 1nvoIntSChBMSta_7 BV 313 SNVT_switch 95 663 1nvoExtSChSta_7 BV 314 SNVT_switch 95 664 1nvoMainsFailBM_7 BV 315 SNVT_switch 95 665 1nvoMaxFillTiAM_7 BV 316 SNVT_switch 95 666 1nvoMaxFillTiBM_7 BV 317 SNVT_switch 95 667 1nviCPUWarmBoot_7 BV 318 SNVT_switch 95 668 1

Page 22: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

22

Mk5/Unit8

ProtoCessor Gateway BACnet LonWorksVariable Name Type Instance SNVT SNVT # NV Index ElementnvoUnitType_8 AV 351 SNVT_switch 95 701 1nvoFillLevelAM_8 AV 352 SNVT_switch 95 702 1nvoFillLevelBM_8 AV 353 SNVT_switch 95 703 1nvoRHorDemand_8 AV 354 SNVT_count 8 704 1nvoTotSteamReq_8 AV 355 SNVT_count 8 705 1nvoActFaultRea_8 AV 356 SNVT_switch 95 706 1nvoOperatHours_8 AV 357 SNVT_time_hour 124 707 1nvoH_SmallServ_8 AV 358 SNVT_time_hour 124 708 1nvoH_ExtenServ_8 AV 359 SNVT_time_hour 124 709 1nvoCapaciLimit_8 AV 360 SNVT_count 8 710 1nvoSetPointHum_8 AV 361 SNVT_count 8 711 1nvoProportBand_8 AV 362 SNVT_count 8 712 1nvoIntegraTime_8 AV 363 SNVT_count 8 713 1nviCapaciLimit_8 AV 364 SNVT_count 8 714 1nviSetPointHum_8 AV 365 SNVT_count 8 715 1nviProportBand_8 AV 366 SNVT_count 8 716 1nviIntegraTime_8 AV 367 SNVT_count 8 717 1

nvoFaultStatus_8 BV 351 SNVT_switch 95 751 1nvoHumStatus_8 BV 352 SNVT_switch 95 752 1nvoServcieStat_8 BV 353 SNVT_switch 95 753 1nvoFillVal1AM_8 BV 354 SNVT_switch 95 754 1nvoFillVal2AM_8 BV 355 SNVT_switch 95 755 1nvoFillVal1BM_8 BV 356 SNVT_switch 95 756 1nvoFillVal2BM_8 BV 357 SNVT_switch 95 757 1nvoDrainPumpAM_8 BV 358 SNVT_switch 95 758 1nvoDrainPumpBM_8 BV 359 SNVT_switch 95 759 1nvoSmallSerSta_8 BV 360 SNVT_switch 95 760 1nvoExtenSerSta_8 BV 361 SNVT_switch 95 761 1nvoIntSChAMSta_8 BV 362 SNVT_switch 95 762 1nvoIntSChBMSta_8 BV 363 SNVT_switch 95 763 1nvoExtSChSta_8 BV 364 SNVT_switch 95 764 1nvoMainsFailBM_8 BV 365 SNVT_switch 95 765 1nvoMaxFillTiAM_8 BV 366 SNVT_switch 95 766 1nvoMaxFillTiBM_8 BV 367 SNVT_switch 95 767 1nviCPUWarmBoot_8 BV 368 SNVT_switch 95 768 1

Page 23: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration

23

Ordering form

Attention: ................................................................................... Date: .....................................................

Company: ................................................................................... Fax#: .....................................................

From: .................................................................................. Page: of

Subject: e-LINKSInformation

FORYOURINFORMATION RESPONSEREQUESTED

MESSAGE:

Distributor/AgentP.O.Number: ............................. SalesOrderNumber: ...............................................

Desirede-LINKSOption: SettingsforBACnet/IPonly:

BACnet/IP DefaultGatewayAddress/Name: .................................

LonWorks BACnetNodeID(DeviceInstance): .............................

Modbus NetworkNumber: ..........................................................

SubnetMask: ....................................................

ModuleIPAddress: ....................................................

HumidifierOrdering: HumidifierModel/Size Desiredunitorder

Unit1(leadingunit)

Unit2

Unit3

Unit4

Unit5

Unit6

Unit7

Unit8

Condair Ltd.Member of the Walter Meier GroupTalstrasse 35-37, 8808 Pfäffikon, SwitzerlandPh. +41 55 416 61 11, Fax +41 55 416 62 [email protected], www.condair.com

Page 24: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration
Page 25: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration
Page 26: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration
Page 27: Condair e-Links Mk5 · Each Defensor Mk5 unit must have a unique Modbus address. The Modbus address can be as-signed in the setup level of the Mk5 control unit. 3.2 Gateway configuration