44
8209 Foothill Boulevard, Suite A124 Sunland, CA 91040 Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Page 1 © Confidential - for client use only. Use by any unauthorized persons is prohibited. Confidential Property Condition Assessment Report 4321 Somewhere Street, Los Angeles, CA 91040 Prepared for: John Doe Prepared By: Robert Gaudreault This report is the exclusive property of the inspection company and the client whose name appears herewith and its use by any unauthorized person. Alliance Inspections. (818) 353-2885
Transcript
Page 1: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

8209 Foothill Boulevard, Suite A124 Sunland, CA 91040

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040

Page 1

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Confidential Property Condition Assessment Report

4321 Somewhere Street, Los Angeles, CA 91040

Prepared for: John Doe Prepared By: Robert Gaudreault

This report is the exclusive property of the inspection company and the client whose name appears herewith

and its use by any unauthorized person. Alliance Inspections. (818) 353-2885

Page 2: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Page 2

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:

Report Table of Contents

GENERAL INFORMATION 3

RESOURCES/DEFINITIONS AND LIFE SPANS: 5

GENERAL SITE DESCRIPTION: 8

SPRINKLER SYSTEM 13

PLUMBING SYSTEM 14

HEATING, VENTILATION & AIR CONDITIONING 19

ELECTRICAL SYSTEMS 24

ROOF & ATTIC 29

STRUCTURE: 35

BUILDING FOUNDATION: 37

INTERIORS: 38

BATHROOM 42

Page 3: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 3

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

GENERAL INFORMATION

Client/User Information:

1.1 Date of Walkthrough Survey:August 26/2020.

1.2 Time:9:00.

1.3 Occupied:Yes-Client should understand that there are many stored items throughout the interiors restricting access

and view to certain, components, systems and general interiors. Some issues, such as and not limited todefects, stains and cracks may go unnoted in this report that were not in view at the time of theinspection.

1.4 Consultant:Robert Gaudreault. UCLA degree in construction management: Disciplines of study entailed, projectengineering, estimating projects, overall management of construction process from documents,coordination and scheduling to final completion. General B contractors licensed and C designation

(Inactive). ITC certified in thermo imaging and member of the California Real Estate InspectionAssociation as master inspector.

Property Characteristics and Type:

1.5 Main Entry Faces:East.

1.6 Building Type:Standard Type V. Conventional framing. Group A-Assembly (Group A) - places used for peoplegathering for entertainment, worship, and eating or drinking. Such as: churches, restaurants (with 50 or

more possible occupants), theaters, and stadiums. Group A is divided into five sub groups:A-1 Buildings intended for the production and viewing of performing arts or motion pictures (theaters,concert halls).

A-2 Buildings intended for food and/or drink consumption (restaurants).A-3 Buildings intended for worship, recreation or amusement and other assembly uses not otherwiseclassified.

A-4 Buildings intended for viewing of indoor sporting events and activities with spectator seating(arenas).

A-5 Buildings intended for participation in or viewing outdoor activities (stadiums.

1.7 Stories:One story.

Page 4: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 4

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Climatic Conditions:

1.8 OUTSIDE TEMPERATURE (F):70s.

Utilities:

1.9 Water Source:Public.

1.10 Sewage Disposal:Public.

1.11 Electric:Municipal.

1.12 Fuel:Natural Gas. Supplied by local utility company.

1.13 Utility Status:All utilities on.

Purpose Scope:

1.14 ASTM E 2018:The purpose, as defined by ASTM E 2018 and use of this guide, is to define good commercial practice inthe USA for conducting a baseline property conditions assessment (PCA) of the improvements locatedon a parcel of commercial real estate by performing a walk-through survey and conducting research as

outlined within the guide. The goal is to identify and communicate physical deficiencies to a use. The

term physical deficiencies includes the conspicuous defects and material deferred maintenance

of a subject property's material systems, components or equipment as observed duringcompletion of the PCA.

This definition excludes deficiencies that may be remedied with routine maintenance,miscellaneous minor repairs, normal operating maintenance, etc., and excludes de minimis

conditions that generally do not present material physical deficiencies of the subject property.

1.15 Deviations from Standards:Deviations from standards are as such: No plan or document reviews conducted, no interviewsconducted. We did not conduct any record research. For example, outstanding citations related to

building code violations with local building department nor did we conduct any research as to anyoutstanding fire code violations.

Page 5: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 5

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

RESOURCES/DEFINITIONS AND LIFE SPANS:

STANDARD TERMS:

2.1 GENERAL DEFINITIONS:Cladding: This is the actual skin of the structure. It can be glass, brick veneer, stone, stucco etc.

Facade: Face of structure. Concrete or brick. It is considered part of the structural aspect of the buildingunlike cladding.

HVAC: Heating Ventilation and Air Conditioning

Main disconnect: This is the main electrical shut off for the structure.

Not Technically Exhaustive: Appropriate due diligence according to this guide is not to be construed astechnically exhaustive. There is a point at which the cost of information obtained or the time required to

conduct the PCA and prepare the PCR may outweigh the usefulness of the information and, in fact, maybe a material detriment to the orderly and timely completion of a commercial real estate transaction. It isthe intent of this guide to attempt to identify a balance between limiting the costs and time demands

inherent in performing a PCA and reducing the uncertainty about unknown physical deficiencies resultingfrom completing additional inquiry.

PCR (Property Conditions Report): This is the report that generates the Property Conditions Surveyconducted by observer or consultant

Physical Deficiencies: In defining good commercial and customary practice for conducting a baselinePCA, the goal is to identify and communicate physical deficiencies to a user. The term physical

deficiencies means the presence of conspicuous defects or material deferred maintenance of a subjectproperty's material systems, components, or equipment as observed during the field observer's

walk-through survey. This definition specifically excludes deficiencies that may be remedied with routinemaintenance, miscellaneous minor repairs, normal operating maintenance, etc., and excludes de minimisconditions that generally do not present material physical deficiencies of the subject property.

Plumbing: This is the water supply lines, water heaters and sanitary waste and ventilation part of thestructure

Principles: The following principles are an integral part of this guide. They are intended to be referred to

in resolving ambiguity, or in exercising discretion accorded the user or consultant in conducting a PCA,or in judging whether a user or consultant has conducted appropriate inquiry or has otherwise conductedan adequate PCA

Property Conditions Assessment: The PCA performed per ASTM standards is site-specific in that it

relates to the physical condition of real property improvements on a specific parcel of commercial realestate. Consequently, this guide does not address many additional issues in real estate transactionssuch as economic obsolescence, the purchase of business entities, or physical deficiencies relating to

Page 6: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 6

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

off-site conditions.

Representative Observations: The purpose of conducting representative observations is to convey tothe user the expected magnitude of commonly encountered or anticipated conditions. Recommendedrepresentative observation quantities for various asset types are provided in Annex A1; however, if in the

field observer's opinion such representative observations as presented in Annex A1 are unwarranted asa result of homogeneity of the asset or other reasons deemed appropriate by the field observer, the field

observer may survey sufficient units, areas, systems, buildings, etc. so as to comment with reasonableconfidence as to the representative present condition of such repetitive or similar areas, systems,buildings, etc. To the extent there is more than one building on the subject property, and they are

homogeneous with respect to approximate age, use, basic design, materials, and systems, it is not arequirement of this guide for the field observer to conduct a walk-through survey of each individualbuilding's systems to describe or comment on their condition within the PCR. The descriptions and

observations provided in the PCR are to be construed as representative of all similar improvements

System: Refers to the complexities of a part of the structure. For example the electrical system hasmany parts, the plumbing and HVAC system have many components parts that make up the whole

system

The consultant (Observer): is the qualified professional conducting the walk through assessment of the

property, structure

Uncertainty Not Eliminated: No PCA can wholly eliminate the uncertainty regarding the presence ofphysical deficiencies and the performance of a subject property's building systems. Preparation of a PCRin accordance with this guide is intended to reduce, but not eliminate, the uncertainty regarding the

potential for component or system failure and to reduce the potential that such component or systemmay not be initially observed. This guide also recognizes the inherent subjective nature of a consultant'sopinions as to such issues as workmanship, quality of original installation, and estimating the RUL of any

given component or system. The guide recognizes a consultant's suggested remedy may be determinedunder time constraints, formed without the aid of engineering calculations, testing, exploratory probing,

the removal or relocation of materials, design, or other technically exhaustive means. Furthermore, theremay be other alternative or more appropriate schemes or methods to remedy a physical deficiency. Theconsultant's opinions generally are formed without detailed knowledge from those familiar with the

component's or system's performance.

User: Otherwise, client. Person who has interest in obtaining a Property Conditions Assessment as part

of their due diligence.

RESOURCES:

2.2 Cost to Cure Source:Cost estimates are obtained from a multitude of sources, such as R. S. Means, the National Contractorestimator 55th Edition, local contractors and specialty tradesman, the web site, manufacturers and

installers. Also cost are based on historical references. It should be understood that this PCR should not

Page 7: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 7

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

be used as a bid and it is not intended for this purposes. Any client should obtain their own estimates. Itshould also be understood that estimates can very greatly to a greater or lesser degree.

Other variables that can affect estimates are and not limited to, weather, strikes, union or non union bidsand availability of resources, such as material and supplies.

2.3 Immediate Needs Cost Source:All the immediate repair costs will be itemized in section 1. These are cost per the opinion of the

consultant performing the PCA that are safety concerns, at the end of their serviceable life and should bereplaced or suffering from extensive deferred maintenance.

2.4 5 to 12 year Expected Cost Expenditures:Not provided unless requested by Bank or Lender for an additional nominal fee.

Page 8: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 8

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

GENERAL SITE DESCRIPTION:

Overall Lot Observations:

3.1 Storm Water Drainage:

Sub and surface drainage. Efficiency and effectiveness of drainage can not be determined. Crackingand damage noted to parking drain swale. Budget for replacement or repairs.

3.2 Landscaping:Generally fair with some maintenance needed.

3.3 Access to Lot:Street. East.

Paving:

3.4 Access & Egress:Street access as observed during walkthrough appeared functional.

3.5 Paving Materials:Asphalt.

3.6 Driveway Approach(s):

Page 9: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 9

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

The driveway needs action. Repair or replacement is indicated. The driveway is broken into segments. This is unsightly and likely to continue movement.

3.7 Curbs:

Page 10: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 10

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Some displacement due to tree roots.

3.8 Walkways:Concrete. Satisfactory - The walkway surface material is in satisfactory condition with only normaldeterioration noted.

Fences & Gates:

3.9 Condition:

Masonry. Ho claim is made as to actual ownership of fencing. Some lean and fractures noted however to

south side wall.

Page 11: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 11

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Chain link along north side damaged.

Retaining Walls:

3.10 Location:Along north section of property.

3.11 Condition Material:

Masonry. Lean and damage due to tree roots.

Page 12: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 12

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Trash Enclosures:

3.12 Location:Back side of property.

3.13 Condition Material:Satisfactory.

Page 13: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 13

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

SPRINKLER SYSTEM

It is not within the scope of this report to determine the degree of salinity or volume of any well water. Inquire withthe sellers of the property or check with the local agricultural extension service for these tests. We suggest youhave the sellers instruct you as to the operation of this system. Ongoing maintenance of damaged or cloggedsprinkler heads is necessary with most sprinkler systems.

Supply & Distribution:

4.1 Valves:Type: Manifold Valves. Covers displaced.Maintenance indicated.

Visible Supply Lines:

4.2 Visible Supply Lines:No leakage noted at the time of inspection.

Electric Controls:

4.3 Subpanels & Timers:NOTE: Automatic function of the timer/control box was not tested.

Sprinkler Heads:

4.4 Overall Condition:Good.

Page 14: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 14

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

PLUMBING SYSTEM

Water quality or hazardous materials (lead) testing is available from local testing labs, and not included in this walkthrough. All underground piping related to water supply, waste, or sprinkler use are excluded from this walk throughsurvey. Leakage or corrosion in underground piping cannot be detected by a visual observation, nor can thepresence of mineral build-up that may gradually restrict their inner diameter and reduce water volume. Plumbingcomponents such as gas pipes, potable water pipes, drain and vent pipes, and shut-off valves are not generallytested if not in daily use. The consultant cannot state the effectiveness or operation of any anti-siphon devices,automatic safety controls, water conditioning equipment, fire and lawn sprinkler systems, on-site water quality andquantity, on-site waste disposal systems, foundation irrigation systems, spa and swimming pool equipment, solarwater heating equipment, or observe the system for proper sizing, design, or use of materials.

Waste and drainpipes pipe condition is usually directly related to their age. Older ones are subject to damagethrough decay and root movement, whereas the more modern ABS ones are virtually impervious to damage,although some rare batches have been alleged to be defective. Older structures with galvanized or cast iron supplyor waste lines can be obstructed and barely working during a walk through but later fail under heavy use. If thewater is turned off or not used for periods of time (such as a vacant building waiting for closing), rust or depositswithin the piping can further clog the piping system. However, inasmuch as significant portions of drainpipes areconcealed, we can only infer their condition by observing the draw at drains at the time of walk through. Nonetheless, blockages will still occur in the life of any system.

WATER SUPPLY:

5.1 SOURCE::City/Municipal. Meter is located at Front parkway. Shut valve is located, at back side.

WASTE DISPOSAL:

5.2 SEWAGE DISPOSAL TYPE:Client should understand that the sewer line from the building to the street sewer is not visible in thistype of general visual inspection. Inspector can not determine condition or adequacy of this waste pipe.We always recommend contracting with a qualified sewer line inspector who uses a scope and camera

to view the system and render a report as to its condition.

Page 15: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 15

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

5.3 MATERIAL & CONDITION:Predominant waste line material is cast iron. Only 1% of the waste disposal system is visible to theinspector. Most of the waste drainage system is within walls, into common areas and below grade and

therefore can not be viewed.

5.4 WASTE VENTING:Satisfactory. In plumbing, a vent, or more precisely, a drain waste vent, helps to remove sewage andgreywater from a building or home. The vent also helps to regulate air pressure in the plumbing pipes to

ensure that the water flows unimpeded through them.

5.5 LOCATION OF CLEANOUTS:Various exterior locations.

OTHER PLUMBING:

5.6 LAWN SPRINKLERS:Backflow preventer device installed for the lawnsprinkler system. The Environmental Protection

Agency requires installation of an approved backflowprevention device and that it be tested annually.Consult tenant or owner for documentations.

Page 16: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 16

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

WATER HEATER:

5.7 LOCATION:Interiors. Adjacent to kitchen.

5.8 Model & Serial Numbers:76 Gallon gas fired water heater.

5.9 AGE:18 year old. Average life span of a water heater is 12 to 15 years.

5.10 CONDITION:Operational at this time though beyond its life span. Budget for replacement.

5.11 COMBUSTION AIR:Adequate amount of fresh air supply to ensure complete combustion.

5.12 DRIP LEG?:No drip leg installed on the incoming gas line to the water heater. Installation of a drip leg is

recommended to prevent debris from getting into the gas valve.

5.13 VENT PIPE CONDITION:

Page 17: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 17

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Evidence of poor drafting. This means that the gases

are spilling back down rather than expelling to theexteriors.

5.14 WATER PIPES:Rust and corrosion noted to water pipes. Repairs are needed at this time.

5.15 TEMPERATURE CONTROL:Not operated or tested.

5.16 TPRV:Temperature and pressure relief valve is installed and it has a drain tube that terminates to approved

location.

5.17 BRACING:Satisfactory.

Be aware that the consultant can not detect gas leaks and is only commenting on visual portions of the gas

lines. Consultant does not operate gas valves nor light pilots to appliances that are off at the time of thewalk through survey. Much of the gas lines, such as to any pool heater or BBQ are below grade and

therefore not visible as mentioned above and can not be located or viewed for observation. Consultant isalso not performing any calculations as to pipe sizing for certain appliances or adequacy and efficiency offlow and pressure. This can only be done by qualified licensed professional plumbing contractor with the

use of special gauges and instruments.

GAS SERVICE:

5.18 METER LOCATION:

Page 18: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 18

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Rear side. An automatic seismic gas shut off valve

is installed.

5.19 GAS SUPPLY TYPE:Natural Gas.

5.20 CONDITION:Most manufacturers recommend that a

sediment trap be installed at fuel burningappliance, such as water heaters andfurnaces. Sediment traps prevent particles

from entering gas orifice witch could affectoperation.

Consultants Opinion to Remedy:Findings: Recommendations:

Water heater beyond its serviceable life. Some

venting deficiencies present. Gases are not efficientlyexpelling to exteriors.

Budget for repairs. Improve venting.

5.23 Cost to Cure:Best Cost: $4,500.00 Worst Cost: $5,500.00.

Page 19: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 19

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

HEATING, VENTILATION & AIR CONDITIONING

Consultant can only readily open access panels provided by the manufacturer or installer for routine maintenance,and will not operate components when weather conditions or other circumstances apply that may cause equipmentdamage. The consultant does not light pilot lights or ignite or extinguish solid fuel fires, nor are safety devicestested. The consultant is not equipped to observe furnace heat exchangers for evidence of cracks or holes, or viewconcealed portions of evaporator and condensing coils, heat exchanger or firebox, electronic air filters, humidifiersand de-humidifiers, ducts and in-line duct motors or dampers, as this can only be done by dismantling the unit. Thermostats are not checked for calibration or timed functions. Adequacy, efficiency or the even distribution of airthroughout a building cannot be addressed by a visual observation. Have these systems evaluated by a qualifiedindividual. The consultant does not perform pressure tests on coolant systems, therefore no representation ismade regarding coolant charge or line integrity.

Please note that even modern heating systems can produce carbon monoxide, which in a poorly ventilated roomcan result in sickness and even death. Therefore, it is essential that any recommendations that are made forservice or further evaluation be scheduled before the close of escrow. A specialist could reveal additional defects orrecommend further upgrades that could affect your evaluation of the property, and our service does not include anyform or warranty or guarantee. Normal service and maintenance is recommended on a yearly basis. Determiningthe presence of asbestos materials commonly used in heating systems can ONLY be preformed by laboratorytesting and is beyond the scope of this walkthrough survey. Determining the condition of oil tanks, whether exposedor buried, is beyond the scope of this walkthrough. Leaking oil tanks represent an environmental hazard which issometimes costly to remedy.

System:

6.1 Type and Location:A forced air furnace is installed as the primary source

of heat. Located at north east end of roof top.

6.2 Fuel Source:Natural gas.

6.3 Equipment Description:

Page 20: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 20

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

System is Carrier brand. Mid efficiency furnace.

6.4 Capacity & Efficiency:BTUs 180,000 BTUs.

6.5 Approximate Age:18 year old. Typical service life for a forced air natural gas furnace is 18 - 20 years.

6.6 Burners / Heat Exchangers:General conditions prohibit a visual inspection of a large percentage of the heat exchanger. This isprimarily due to the style and shape of the heat exchanger, but the visible portions were inspected.

6.7 Secondary Air Adequacy:Availability of secondary air for combustion and flue draft appears to be adequate; however, no

calculation was performed by the consultant. Secondary air is the air required in fossil fuel-firedappliances to mix with the products of combustion and for removal of the products of combustion up theflue.

6.8 Normal Controls:General condition appears serviceable.

6.9 AIR CONDITIONING:Package unit.

6.10 Model/ Serial Number/ Size:12.5 ton. 18 year old. The typical service life for an AC unit is 12 - 15 years.

6.11 Condition:Operational at this time.

6.12 Service Disconnect:Installed service disconnect is located within sight of the condensing coil cabinet and not more than 50

feet from the unit.

6.13 Condensate Line:

Page 21: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 21

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Attention Needed - Condensate drain line installed.However it is overflowing onto roof top indicating

blockage.

6.14 Evidence of Maintenance:No. Maintenance lacking.

6.15 Ducts Condition:Loss of air flow into ceiling plenum due to poorly sealed duct joints. Implications are affected efficiencyhigh utility bills.

System 2:

6.16 Type and Location:A forced air furnace is installed. Located at roof top.South west side.

6.17 Fuel Source:Natural gas.

6.18 Equipment Description:

Page 22: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: R3 Real Estate Developers PCR 11604 Valley Blvd. El Monte CA Address:Page 22

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

System is Carrier brand. Mid efficiency furnace.

6.19 Capacity & Efficiency:180,000 BTUs.

6.20 Approximate Age:18 year old.

6.21 Burners / Heat Exchangers:General conditions prohibit a visual inspection of a large percentage of the heat exchanger. This isprimarily due to the style and shape of the heat exchanger, but the visible portions were inspected.

6.22 Pump / Blower Fan:Action Necessary - Blower assembly is not functioning as intended. Cleaning, repair, or replacement is

needed. Vibration was noted. Replacement or repairs are needed.

6.23 Secondary Air Adequacy:Availability of secondary air for combustion and flue draft appears to be adequate; however, nocalculation was performed by the consultant.

6.24 Normal Controls:General condition appears serviceable.

6.25 AIR CONDITIONING:Package unit.

6.26 Model/ Serial Number/ Size:12.5 ton.

6.27 Condition:Operational in cooling mode.

6.28 Service Disconnect:Installed service disconnect is located within sight of the condensing coil cabinet and not more than 50

feet from the unit.

6.29 Condensate Line:

Page 23: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 23

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Disconnected or damaged. Condensation

overflowing onto roof top as a result.

6.30 Evidence of Maintenance:Lacking.

6.31 Ducts Condition:Air loss into ceiling plenum. Improvements needed to ensure efficient use.

Consultants Opinion to Remedy:Findings: Recommendations:

Systems are in need of immediate servicing at this

time to ensure safe and efficient use.

Contact service technician for maintenance at this

time. Budget for replacement in the not to distantfuture. Cost to Cure will reflect replacement cost.

Service cost should be minimal.

6.34 Cost to Cure:Best Cost: $26,000.00 Worst Cost: $31,000.00.

Page 24: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 24

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

ELECTRICAL SYSTEMS

In accordance with the standards of practice we only test a representative number of switches and outlets and donot perform load-calculations to determine if the supply meets the demand. However, every electrical deficiency orrecommended upgrade should be regarded as a latent hazard that should be serviced as soon as possible, alongwith evaluation and certification of the entire system as safe by a licensed contractor. Therefore, it is essential thatany recommendations that are made for service or upgrades should be completed before the close of escrow orduring contingency period, because an electrician could reveal additional deficiencies or recommend additionalupgrades for which we disclaim any responsibility. Any electrical repairs or upgrades should be made by a licensedelectrician. Aluminum wiring requires periodic inspection and maintenance by a licensed electrician. SmokeAlarms should be installed within 15 feet of all bedroom doors, and tested regularly.

Operation of time clock motors is not verified. Inoperative light fixtures often lack bulbs or have dead bulbsinstalled. The consultant is not required to insert any tool, probe, or testing device inside the panels, test or operateany over-current device except for ground fault interrupters, nor dismantle any electrical device or control otherthan to remove the covers of the main and auxiliary distribution panels. Any ancillary wiring or system that is notpart of the primary electrical distribution system is not part of this PCA but may be mentioned for informationalpurposes only, including but not limited to low voltage systems, security system devices, heat detectors, carbonmonoxide detectors, telephone, security, cable TV, intercoms, and built in vacuum equipment.

PRIMARY POWER SOURCE:

7.1 SERVICE VOLTAGE:400 amp. 208/480 volt.

7.2 SERVICE TYPE & CONDITION:

Underground service to the structure is desirable for safety and appearance. Contact the utility company

to mark the location of underground cable before digging.

Page 25: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 25

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

MAIN PANEL:

7.3 MAIN PANEL LOCATION:Interiors.

7.4 MANUFACTURER:I-T-E.

7.5 ACCESS:Electrical panel box is temporarily blocked. For safety reasons, be sure that there is a clear and readyaccess to the panel.

7.6 PANEL TYPE & CONDITION:Breakers - Structure is equipped with a breaker type main power panel. Power panel, as a container for

safely covering electrical circuitry and components, is functioning as intended, minimizing the risk ofelectrical shock. Balance of multi wire components not verified.

7.7 BREAKER/FUSE:Satisfactory - Breakers/fuses in the main power panel appear to be in serviceable condition.

7.8 PANEL COVER REMOVED:Panel covers are not removed when business is being conducted. A thermal scan was performed in lieu

Page 26: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 26

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

of removing covers. No anomalies detected.

7.9 GROUNDING:Grounding conductor to the water service line was noted, and it is correctly connected to the street sideof the main water line.

SUB PANEL 1:

7.10 LOCATION:Office.

7.11 ACCESS:Electrical panel box is temporarily blocked. For safety reasons, be sure that there is a clear and ready

access to the panel.

SUB PANEL 2:

7.12 LOCATION:Back utility area adjacent to main pane.

7.13 ACCESS:Electrical panel is in a location that makes it readily accessible.

Page 27: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 27

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

7.14 PANEL TYPE & CONDITION:Power panel, as a container for safely covering electrical circuitry and components, is functioning as

intended, minimizing the risk of electrical shock. Balance of multi wire components not verified.

WIRING TYPE & CONDITION:

7.15 WIRING TYPE & CONDITION:Copper - The structure is wired using plastic insulated copper single conductor. Less than 3% is visible

to inspector. Wiring is mostly concealed within walls and therefore not visible for inspection. Inspectorcan not make any reliable comment to areas which can not be viewed for inspection.

OUTLETS & SWITCHES:

7.16 RECEPTACLES:A representative sampling of receptacles was achieved. These tested appeared to be operating properly.

7.17 GROUND FAULT CIRCUIT INTERUPTERS:At least one of the Ground Fault Circuit Interruptprotected outlets tested did not break the currentflow or reset as required. Action is necessary to

repair or replace. Such as roof top.

7.18 SWITCHES:A representative sampling of switches was achieved. These tested appeared to be operating properly.

7.19 LIGHTING:

Page 28: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 28

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

A representative sampling of lighting was achieved.These tested appeared to be operating proper

However one ceiling light damaged or askew withindining side utility closet.

7.20 EXTERIOR ELECTRICAL:Lighting at exterior patio section not operational at this time.

Parking lighting did function as intended.

Opinion to Remedy:

7.21 Recommendations:No recommendations as a result of this assessment.

Page 29: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 29

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

ROOF & ATTIC

Roof systems require periodic maintenance, such as checking the seals around flashings, removing foliageand cleaning out gutters. The consultant does not certify the roof system or determine how well it performs

under extreme weather conditions. Consultant does not perform any roof structure calculations, leak testor determine efficiency and actual R value of any insulation. Consultant can not comment on attic framing

or roof structures that do not have an accessible attic space nor can he/she determine integrity of roofdeck as it is covered by roof material when observed.

ROOFING:

8.1 ROOF TYPE:Flat low slope. Rolled bitumen used as roof covering.

Tile roofing over tower section.

8.2 Pitched Roof Condition:Tile covering material is in a condition that is consistent with its age and method of installation.

8.3 Flat Roof Condition:

Page 30: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 30

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Poorly patched sections noted at various locations. Patch work is of poor and unreliable repair.

Page 31: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 31

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

General granular loss seen. Asphalt matt and fiberglass is exposed as a result.

Ponding noted. Ponding water does promote leaks and damage to roofing material.

8.4 FLASHING:

Page 32: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 32

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Copping flashing along top of parapet wall damage.

Inadequate welds at parapet wall flashings. Implications are potential for leak.

Page 33: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 33

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

ROOF DRAINAGE:

8.5 GUTTERS & DOWNSPOUTS:Drain grate cover displaced. Implications are greater

potential for clogging.

ROOF ASSEMBLY & VENTILATION:

8.6 FRAMING:A truss system is installed in the attic cavity that is

used to support the roof decking and transmit theroof load to the exterior walls. A precursory review of

the truss system was achieved. Visible pointsappeared satisfactory. No visible defects.

8.7 ROOF DECKING:

Page 34: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 34

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Not fully visible. Insulation does hinder viewing of

roof deck. Some notable water stains seen howeveras exposed sections from prior roof leaks.

8.8 INSULATION:Insulation missing at some locations. Implications are efficiency loss. Maintain as needed.

Opinion to Remedy:

8.9 NOTE:

Bird activity present. Excessive droppings noted at roof top. Consult licensed pest control operator onhow to best maintain and eradicate bird activity at roof top.

Findings: Recommendations:

Roof system is in poor repair and lacking

maintenance.

Replacement indicated. Consult licensed roofing

agency for options and methods of repairs.

8.12 Cost to Cure:Best Cost: $25,000.00 Worst Cost: $39,000.00.

Page 35: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 35

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

STRUCTURE:

While the observer makes every effort to find all areas of concern, some areas can go unnoticed. Duringthe course of the walk-through, the consultant does not enter any area or perform any procedure that may

damage the property or its components or be dangerous to or adversely affect the health of the consultantor other persons.

STRUCTURE:

9.1 TYPE OF CONSTRUCTION:Conventional wood framing, with stucco cladding. No probing of wood with any device to determine the

significance of water damage.

9.2 OBSERVATIONS:Siding is in serviceable condition. Some damageseen however at north side.

9.3 PAINT SURFACE:Satisfactory - The finish or exposed painted surfaces are satisfactory.

DOORS & WINDOWS:

9.4 WINDOWS CONDITION:

Page 36: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 36

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Repairs needed. Caulking or mastic defective or of poor appearance. Leaks eminent. Obtain theservices of a glazing contractor for repairs.

FRAMING:

9.5 FRAMING MEMBERS.Exposed percentages of wall framing members is minimal. Therefore, no assumption should be madeas to the condition of the unexposed framing members. This is only a comment on the visible portions of

the wall framing.

9.6 FLOOR/CEILING FRAMING:Inspection only refers to the exposed ceiling/floor framing members. This is only a visual inspection anddoes not comment on unexposed framing members.

PATIO:

9.7 MATERIALS/CONDITION:Concrete. Satisfactory.

Page 37: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 37

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

BUILDING FOUNDATION:

All structures are dependent on the soil beneath them for support, but soils are not uniform. Some thatappear to be firm and solid can become unstable during seismic activity or may expand with the influx of

water, moving structures with relative easy and fracturing slabs and other hard surfaces. In accordancewith our standards of practice, we identify foundation types and look for any evidence of structural

deficiencies. However, minor cracks or deteriorated surfaces are common in many foundations and mostdo not represent a structural problem. If major cracks are present along with bowing, we routinely

recommend further evaluation be made by a qualified structural engineer. All exterior grades should allowfor surface and roof water to flow away from the foundation. All concrete floor slabs experience somedegree of cracking due to shrinkage in the curing process. In most instances floor coverings prevent

recognition of cracks or settlement in all but the most severe cases. Where carpeting and other floorcoverings are installed, the materials and condition of the flooring underneath cannot be determined.

Areas hidden from view by finished walls or stored items cannot be judged and are not a part of the walkthrough.

FOUNDATION:

10.1 TYPE:Slab on grade - Refers to a concrete slab

poured at grade level. Some slabs are withsteel reinforcement. Some with wire meshreinforcement.

10.2 FOUNDATION SLAB:Monolithic slab as viewed from common observation appears to be performing as intended. It needs to

be understood that a slab foundation can not be adequately inspected due to floor coverings. There isalways a possibility that significant cracks can go unseen.

Page 38: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 38

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

INTERIORS:

Walk-through survey of living space includes the visually accessible areas of walls, floors, cabinets and closets, andthe testing of a representative number of windows and doors, switches and outlets. We do not evaluate windowtreatments, move furnishings or possessions, lift carpets or rugs, empty closets or cabinets, nor comment oncosmetic deficiencies. Floor covering damage or stains may be hidden by furniture, and the condition of floorsunderlying floor coverings may go unnoted. Determining the condition of insulated glass windows is not alwayspossible due to temperature, weather and lighting conditions. Check with owners for further information. Testing,identifying, or identifying the source of environmental pollutants or odors (including but not limited to lead, mold,allergens, odors from household pets and cigarette smoke) is beyond the scope of our service, but can becomeequally contentious or difficult to eradicate.

UNIT 1:

11.1 TYPE OF UNITDining room.

11.2 Doors:

Page 39: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 39

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Satisfactory. Exit signs posted. Panic hardware installed to facilitate egress.

11.3 General Interiors:

Several water stains noted from previous leaks.

11.4 Floor Condition:

Page 40: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 40

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Tile make a hollow sound when tapped on. This would give indication that these tile are not fully packedor adhering to subfloor. Use caution when moving heavy items over these tiles as they can crack or

break as a result. Sections of base wall tile displaced.

11.5 KITCHEN:No comments made. Kitchen and all appliances are disclaimed from report. Such as and not limited to,refrigeration, ovens, burners, venting, sinks and fire suppression devices.

COMMENTS:

11.6 Note:

Page 41: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 41

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

Interiors are suffering from deferred maintenance

and repairs.

Grease pits and floor drainage efficiency andmaintenance not part of this assessment other thanto note their existence.

Page 42: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 42

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

BATHROOM

Shower pans are not tested as this should only be done by a pest control operator who is licensed by the state ofCalifornia. Efficiency of hot water flow to fixtures is not part of this PCA and it does not comment on whether or nottemperature of hot water is adequate. Client should have a licensed plumber set water heater thermostat to desiredhot water setting. When away for long periods be sure to set your water heater thermostat to vacation mode.Functional drainage flow is only judged as seen while running water under normal conditions. Excessive use ofimproper use can always cause back ups.

Bathroom :

12.1 Location:Dining side.

12.2 Basin & Drain:The basin and drainage fixture appears to be satisfactory.

12.3 Faucet fixture:Angle stop shut off valve(s) located within cabinet

under sink are corroded.

Page 43: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 43

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

12.4 Toilet:

Fasteners rusted and corroded. Implications are loose toilet.

12.5 Urinal:Sings of back up or leak.

12.6 Dispensers:Fair. Dispensers are fair in appearance. Some maintenance needed.

12.7 Walls/Ceiling:The walls in this bathroom are satisfactory.

12.8 Flooring:Flooring in this bathroom is satisfactory.

12.9 Lighting:The ceiling light and fixture in this bathroom are in satisfactory condition.

12.10 Exhaust Fan:There is an exhaust fan installed, but it would not activate using normal controls. Repair or replacement

is necessary.

Page 44: Confidential Property Condition Assessment Report · Such as: churches, restaurants (with 50 or more possible occupants), theaters, and stadiums. Group A is divided into five sub

Report: Doe PCR 4321 Somewhere Street, Los Angeles, CA 91040 Address:Page 44

© Confidential - for client use only. Use by any unauthorized persons is prohibited.

12.11 GFCI(S)There is a Ground Fault Circuit Interrupt outletinstalled in the area of the bathroom lavatory. However, it failed to stop the current flow or did not

reset after testing. Replacement is necessary.


Recommended