+ All Categories
Home > Documents > Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System,...

Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System,...

Date post: 28-Apr-2021
Category:
Upload: others
View: 7 times
Download: 0 times
Share this document with a friend
152
116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03 Configuration Handbook Autroprime Interactive Fire Detection System 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03 Release 2
Transcript
Page 1: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03

Configuration Handbook

Autroprime Interactive Fire Detection System 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03

Release 2

Page 2: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 2

COPYRIGHT ©

This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS and its subsidaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it. No information in this publication should be regarded as a warranty made by Autronica Fire and Security AS. The information in this publication may be updated without notice. Product names mentioned in this publication may be trademarks. They are used only for identification.

Page 3: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 3

Table of Contents

1.  Introduction ....................................................................... 8 

1.1  About the Handbook ......................................................................... 8 1.2  The Reader ....................................................................................... 8 1.3  Reference Documentation ................................................................ 8 1.4  Ready-to-use in a Pre-configured State ............................................ 9 1.5  Saving a Configuration and Restarting the System .......................... 9 1.6  Configuration Examples .................................................................... 9 

2.  Service Commands .......................................................... 10 

2.1  Site-specific Configuration ................................................................ 10 2.2  Access Level 3 – Service Menu ........................................................ 10 2.3  Service Menu .................................................................................... 10 2.4  Entering the Service Menu ................................................................ 12 

3.  System Settings ................................................................ 14 

3.1  Menu Selections - Overview ............................................................. 14 3.2  Save Configuration ............................................................................ 14 3.3  Restart System .................................................................................. 15 3.4  Day Mode Operation Times .............................................................. 16 

3.4.1  Viewing Existing Day Mode Operation Times......................... 17 3.4.2  Adding new Day Mode Operation Times ................................ 17 

3.5  Service Mode Password ................................................................... 18 3.6  Date and Time ................................................................................... 18 3.7  Set Operator Panel Connection ........................................................ 19 3.8  Sound Patterns .................................................................................. 20 3.9  Automatic Resound ........................................................................... 22 3.10  Detection Zone (DZ) Delay Timers ................................................... 22 3.11  Detection Zone (DZ) Global Dependency ......................................... 23 3.12  Battery Parameters ........................................................................... 23 3.13  Panel Name ....................................................................................... 24 3.14  Language .......................................................................................... 24 3.15  FARE and FWRE Disablement ......................................................... 25 3.16  Mains Power Fault Indication ............................................................ 25 3.17  Printer Setup ..................................................................................... 26 3.18  Configuration Check .......................................................................... 26 3.19  System S hutdown ............................................................................ 27 3.20  Restore Factory Settings ................................................................... 28 

4.  Loop Operation ................................................................. 29 

4.1  Accessing the Menu Selections ........................................................ 29 4.2  Enable ............................................................................................... 30 4.3  Disable .............................................................................................. 30 4.4  Change Disable Time Span .............................................................. 31 

Page 4: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 4

4.5  Show Polluted Detectors ................................................................... 31 4.6  Show Low Current Units ................................................................... 32 

5.  Unit Configuration ............................................................ 33 

5.1  Menu Selections - Overview ............................................................. 33 5.2  Detection Zones ................................................................................ 34 

5.2.1  Accessing the Menu Selections .............................................. 34 5.2.2  Configure Properties for a Detection Zone ............................. 35 5.2.3  Connect to Alarm Zone ........................................................... 36 5.2.4  Connect to Output ................................................................... 36 5.2.5  Connect to Disable Input Device ............................................ 37 5.2.6  Connect to Local Alarm Delay Unit ......................................... 37 5.2.7  Connect to Panel .................................................................... 37 5.2.8  Disconnect from Alarm Zone .................................................. 38 5.2.9  Disconnect from Output .......................................................... 38 5.2.10 Disconnect from Disable Input Device .................................... 38 5.2.11 Disconnect from Local Alarm Delay Unit ................................ 38 5.2.12 Disconnect from Panel ............................................................ 39 5.2.13 Show Member Points .............................................................. 39 5.2.14 Show Connected Units ........................................................... 39 

5.3  Alarm Zones ...................................................................................... 40 5.3.1  Accessing the Menu ................................................................ 40 5.3.2  Configure Properties for an Alarm Zone ................................. 41 5.3.3  Connect to Neighbour Alarm Zone ......................................... 41 5.3.4  Disconnect from Neighbour Alarm Zone................................. 42 5.3.5  Show Member Fire Alarm Devices ......................................... 42 5.3.6  Show Neighbour Alarm Zones ................................................ 42 5.3.7  Show Activating Detection Zones ........................................... 43 

5.4  Points................................................................................................. 44 5.4.1  Accessing the Menu ................................................................ 44 5.4.2  Configure Properties for a Point ............................................. 45 5.4.3  Move to Detection Zone (/Create New) .................................. 46 5.4.4  Connect to Output ................................................................... 47 5.4.5  Connect to Activation Group (/Create New) ........................... 48 5.4.6  Disconnect from Output .......................................................... 49 5.4.7  Disconnect from Activation Group .......................................... 49 5.4.8  Show Connected Units ........................................................... 50 

5.5  Fire Alarm Devices ............................................................................ 51 5.5.1  Accessing the Menu ................................................................ 51 5.5.2  Configure Properties for a Fire Alarm Device ......................... 52 5.5.3  Move to Alarm Zone ................................................................ 52 5.5.4  Show Connected Units ........................................................... 53 

5.6  Loop Outputs ..................................................................................... 54 5.6.1  Accessing the Menu ................................................................ 54 5.6.2  Configure Properties for a Loop Output .................................. 55 5.6.3  Connect to Output ................................................................... 56 5.6.4  Connect to Activation Group ................................................... 56 5.6.5  Disconnect from Output .......................................................... 57 5.6.6  Disconnect from Activation Group .......................................... 57 5.6.7  Show Activating Detection Zones ........................................... 58 5.6.8  Show Activating Points ........................................................... 58 5.6.9  Show Activating Inputs ............................................................ 59 5.6.10 Show Activating Groups .......................................................... 59 5.6.11 Show Activating Outputs ......................................................... 60 5.6.12 Show Connected Units ........................................................... 60 

5.7  Local Outputs .................................................................................... 61 5.7.1  Accessing the Menu ................................................................ 61 5.7.2  Configure Properties for a Local Output ................................. 62 

Page 5: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 5

5.7.3  Connect to Output ................................................................... 63 5.7.4  Connect to Activation Group ................................................... 63 5.7.5  Disconnect from Output .......................................................... 64 5.7.6  Disconnect from Activation Group .......................................... 64 5.7.7  Show Activating Detection Zones ........................................... 65 5.7.8  Show Activating Points ........................................................... 65 5.7.9  Show Activating Inputs ............................................................ 66 5.7.10 Show Activating Groups .......................................................... 66 5.7.11 Show Activating Outputs ......................................................... 67 5.7.12 Move to Alarm Zone ................................................................ 67 5.7.13 Show Connected Units ........................................................... 68 

5.8  Loop Inputs ........................................................................................ 69 5.8.1  Accessing the Menu ................................................................ 69 5.8.2  Configure Properties for a Loop Input ..................................... 70 5.8.3  Connect to Output ................................................................... 71 5.8.4  Connect to Alarm Zone ........................................................... 71 5.8.5  Disconnect from Output .......................................................... 71 5.8.6  Disconnect from Alarm Zone .................................................. 72 5.8.7  Show Connected Units ........................................................... 72 

5.9  Local Inputs ....................................................................................... 73 5.9.1  Accessing the Menu ................................................................ 73 5.9.2  Configure Properties for a Local Input .................................... 74 5.9.3  Connect to Output ................................................................... 75 5.9.4  Connect to Alarm Zone ........................................................... 75 5.9.5  Disconnect from Output .......................................................... 75 5.9.6  Disconnect from Alarm Zone .................................................. 76 5.9.7  Show Connected Units ........................................................... 76 

5.10  Loop I/O Carriers ............................................................................... 77 5.10.1 Description .............................................................................. 77 5.10.2 Accessing the Menu ................................................................ 78 5.10.3 Configure Properties for a Loop IO Carrier ............................. 79 5.10.4 Show All Carrier Units ............................................................. 79 5.10.5 Show Carrier Points ................................................................ 80 5.10.6 Show Carrier Inputs ................................................................ 80 5.10.7 Show Carrier Outputs ............................................................. 81 

5.11  Mimic Panels ..................................................................................... 82 5.11.1 Accessing the Menu ................................................................ 82 5.11.2 Configure Properties for a Mimic Panel .................................. 82 5.11.3 Configure Mimic Inputs and Outputs ...................................... 83 

5.12  Activation Groups .............................................................................. 84 5.12.1 Accessing the Menu ................................................................ 84 5.12.2 Configure Properties for an Activation Group ......................... 85 5.12.3 Connect to Output ................................................................... 85 5.12.4 Disconnect from Output .......................................................... 86 5.12.5 Show Member Points .............................................................. 86 5.12.6 Show Connected Units ........................................................... 87 

5.13  External Interfaces ............................................................................ 87 5.13.1 Accessing the menu ................................................................ 87 5.13.2 Serial Port Settings ................................................................. 88 5.13.3 TCP/IP Port Settings ............................................................... 88 5.13.4 ESPA ....................................................................................... 89 5.13.5 MODBUS ................................................................................ 92 5.13.6 VDR ......................................................................................... 96 5.13.7 Remote Access ....................................................................... 97 

5.14  Detection Loops ................................................................................ 100 5.15  Operator Panels ................................................................................ 101 

Page 6: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 6

6.  Unit Test ............................................................................ 102 

6.1  Menu Selections - Overview ............................................................. 102 6.2  Testing Detection Zones ................................................................... 102 6.3  Testing Alarm Zones ......................................................................... 103 6.4  Testing Fire Alarm Devices ............................................................... 104 6.5  Testing Loop Outputs ........................................................................ 105 6.6  Testing Local Outputs ....................................................................... 106 6.7  Testing Mimic Panels ........................................................................ 107 

7.  System Topology .............................................................. 108 

7.1  Menu Selections - Overview ............................................................. 108 7.2  Show Properties ................................................................................ 108 7.3  Show Topology .................................................................................. 109 7.4  Show All Faults .................................................................................. 109 7.5  Clear Loop Config. – Restart System ............................................... 110 7.6  Deactivate ......................................................................................... 111 7.7  Activate .............................................................................................. 111 

8.  Export and Import ............................................................. 112 

8.1  Menu Selections - Overview ............................................................. 112 8.2  USB Output ....................................................................................... 112 8.3  Export Log ......................................................................................... 113 8.4  Select Configuration & Restart System ............................................. 114 8.5  Backup Current Configuration ........................................................... 114 8.6  Export Configuration.......................................................................... 115 8.7  Import Configuration .......................................................................... 116 

9.  Configuration Examples ................................................... 117 

9.1  Before you Start ................................................................................ 117 9.2  Example 1: Basic Configuration Example ......................................... 118 

9.2.1  Site information – Excel Sheet ................................................ 120 9.2.2  Buttons .................................................................................... 120 9.2.3  Initial Startup – Default Configuration ..................................... 121 9.2.4  Save Configuration / Restart System ...................................... 121 9.2.5  Site-specific Configuration – Example 1 ................................. 122 9.2.6  Step 1: Create Detection Zones and Connect Points ............. 123 9.2.7  Add a Site-specific Name to each Point (if needed) ............... 124 9.2.8  Step 2: Connect the new Detection Zones to the Alarm

Zone ........................................................................................ 125 9.2.9  Step 3: Save Configuration / Restart System ......................... 125 

9.3  Example 2: Configuration with several alarm zones and control functions ................................................................................ 126 9.3.1  Site-specific Configuration – Example 2 ................................. 128 9.3.2  Step 1: Create Detection Zones and Connect Points ............. 129 9.3.3  Add a Site-specific Name to each Point (if needed) ............... 130 9.3.4  Step 2: Connect Fire Alarm Devices to new alarm

zones (5.5.3) ........................................................................... 131 9.3.5  Step 3: Connect already configured detection zones to

a new alarm zone (Alarm Zone 1). (5.2.3) .............................. 131 9.3.6  Step 4: Connect the new detection zones to a new

alarm zone (Alarm Zone 2). (5.2.3) ......................................... 132 9.3.7  Step 5: Define Alarm Zone 1 and Alarm Zone 2 as

Neighbour Alarm Zones (5.3.3) .............................................. 132 

Page 7: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 7

9.3.8  Step 6: Connect a point in Detection Zone 6 to the Parent Alarm Zone (5.2.3) ...................................................... 133 

9.3.9  Step 7: Configure outputs for ventilation control and door control (5.4.4 and 5.2.4) ................................................. 133 

9.3.10 Step 8: Save Configuration / Restart System ......................... 134 

10. Other Functions ................................................................ 135 

10.1  Clipboard Functions .......................................................................... 135 10.1.1 Copy ........................................................................................ 135 10.1.2 Cut ........................................................................................... 135 10.1.3 Paste ....................................................................................... 136 10.1.4 View Content ........................................................................... 136 

10.2  Capital and Small Letters –Toggle functionality ................................ 137 

11. Configuration Tool ............................................................ 138 

11.1  Introduction ........................................................................................ 138 11.2  Setup Wizard ..................................................................................... 138 11.3  Starting the Configuration Tool ......................................................... 140 11.4  Help File ............................................................................................ 141 

12. Appendix ........................................................................... 142 

12.1  Alarm Organization............................................................................ 142 12.1.1 Detection Zones with Different Properties .............................. 142 12.1.2 The Actioning of Alarm Zones................................................. 142 12.1.3 Immediate Action Detection Zones ......................................... 143 12.1.4 Dependency Action Detection Zones ..................................... 143 12.1.5 Delayed Action Detection Zones ............................................ 144 12.1.6 Delayed Dependency Detection Zones .................................. 145 12.1.7 SOLAS Detection Zones ......................................................... 146 12.1.8 Silent, Small and Large Alarm – Overview ............................. 146 

13. Reader’s Comments ......................................................... 149 

Page 8: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Introduction

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 8

1. Introduction

1.1 About the Handbook

This document describes in detail how to configure site-specific installations of the Autroprime Interactive Fire Detection System by means of the operating buttons on the panel.

1.2 The Reader

This handbook is intended for technicians and service personnel who are responsible for the site-configuration of the Autroprime system. We assume that the reader is familiar with the manoeuvre and utility buttons which are described in detail in the Operator’s Handbook.

1.3 Reference Documentation

The table below shows an overview of the complete technical documentation that is available in several languages:

Documents Part number File name System Description 116-P-APRIME2-SYSTEM/XGB aprime2system_xgb Getting Started 116-P-APRIME2-GESTAR/EGB aprime2gestar_egb Installation Handbook 116-P-APRIME2-INSTAL/DGB aprime2instal_dgb Connecting Loop Units 116-P-CONNECTLOOPUNIT/DGB connectloopunit_dgb Configuration Handbook 116-P-APRIME2-CONFIG/EGB aprime2config_egb Operator’s Handbook 116-P-APRIME2-OPERAT/FGB aprime2operat_fgb User Guide 116-P-APRIME2-USERGU/LGB aprime2usergu_lgb Wall Chart 116-P-APRIME2-WALLC/LGB aprime2wallc_lgb Menu Structure 116-P-APRIME2-MENUS/MGB aprime2menus_mgb Datasheet; Fire Alarm Control Panel BS-200 116-P-BS200/CGB bs200_cgb Datasheet; Fire Alarm Control Panel BS-200M

116-P-BS200M/CGB bs200m_cgb

Datasheet; Fire Alarm Control Panel BS-200L

116-P-BS200L/CGB bs200l_cgb

Datasheet; Repeater Panel BS-211 116-P-BS211/CGB bs211_cgb Datasheet; Information Panel BV-210 116-P-BV210/CGB bv210_cgb Datasheet; Fire Brigade Panel BU-210 116-P-BU210/CGB bu210_cgb Datasheet; Mimic Driver BUR-200 116-P-BUR200/CGB bur200_cgb

Page 9: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Introduction

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 9

1.4 Ready-to-use in a Pre-configured State

Autroprime is provided to the user in a pre-configured state, in this state the panel is set to recognize detectors and other loop units connected to the detection loops and the availability of routing equipment, etc. As such, the system is fully functional and ready-to-use simply by turning ON the power, but not configured to respond in any non-default way. A functional verification of the panel is run to assure the panel itself is fully functional. By default the system has one Detection Zone and one Alarm Zone. A point in alarm will activate all Fire Alarm Devices and Fire Alarm Routing Equipment. Site-specific configuration can be performed by means of the panel buttons. Refer to chapter 2.1, Site-specific Configuration.

1.5 Saving a Configuration and Restarting the System

Note that you always have to save a configuration and restart the system; after an initial startup (part of the start-up procedure) each time a configuration has been changed. This menu selections are found in the Service Menu/System Settings (see chapter 2).

1.6 Configuration Examples

Chapter 9 in this handbook deals with two configuration examples, one basic configuration example and an example with several alarm zones and control functions. These examples shows how to perform typical configurations of a medium-sized installation (to simplify the understanding of the configuration principle, the basic configuration example deals with one loop and 8 points only).

Page 10: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Service Commands

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 10

2. Service Commands

2.1 Site-specific Configuration

Site-specific configuration can be performed by means of the panel buttons (configuration level 2), typically including: naming and assigning detectors/manual call points to Detection

Zones naming and defining the number and type of Detection Zones

(Immediate Action, Dependency Action, Delayed Action, Delayed Dependency Action, SOLAS)

assigning Fire Alarm Devices to Alarm Zones specifying the Detections Zones that can activate selected Alarm

Zones configuring “conditions” for outputs, for example, coincidence

action; meaning that at least two detectors in the same detection zone must be in alarm state before actions are initiated

assigning Detection Zones to disable devices (BW-200) All these options and many more are available in the Service menu.

2.2 Access Level 3 – Service Menu

From the operator panel you can perform service commands. To use the Service Commands, access level 3 is required.

Access Level Access Remedy Description

3 Password restricted Accessible by persons trained and authorized to do reconfiguration of site specific data and maintenance according to the manufacturer’s published instruction.

4 Mechanical tool Accessible by persons doing repair work and changing firmware.

2.3 Service Menu

The entire Service Menu is shown on the next page.

Page 11: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Service Commands

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 11

Access Level 1: No key or password requiredAccess Level 2: Access by keyAccess Level 3: Password restricted

Menu Structure English

Enter Service Mode

Service System SettingsLoop OperationUnit ConfigurationUnit TestSystem TopologyExport and Import

Save ConfigurationRestart SystemDay Mode Operation TimesService Mode PasswordDate and TimeSet Operator Panel ConnectionSound PatternsAutomatic ResoundDZ Delay TimersDZ Global DependencyBattery ParametersPanel NameLanguageFARE and FWRE DisablementMains Power Fault IndicationPrinter SetupConfiguration CheckSystem ShutdownRestore Factory Settings

Enable UnitsDisable UnitsChange Disable Time SpanShow Polluted DetectorsShow Low Current Units

Detection ZonesAlarm ZonesPointsFire Alarm DevicesLoop OutputsLocal OutputsLoop InputsLocal InputsLoop I/O CarriersMimic PanelsActivation GroupsExternal InterfacesDetection LoopsOperator Panels

Detection ZonesAlarm ZonesFire Alarm DevicesLoop OutputsLocal OutputsMimic Panels

Show TopologyShow All FaultsClear Loop Config. – Restart SystemDeactivate/Activate

Export LogSelect Configuration & Restart SystemBackup Current ConfigurationExport ConfigurationImport Configuration

Exit Service Mode

(Functions)

116-P-APRIME2-MENUS/MGB, 2012-01-10

(Applicable only if Mimic Panels are used)

Connect to Alarm ZoneConnect to OutputConnect to Disable Input DeviceConnect to Local Alarm Delay UnitConnect to Panel (special panel only)Disconnect from Alarm ZoneDisconnect from OutputDisconnect from Disable Input DeviceDisconnect from Local Alarm Delay UnitDisconnect from Panel (special panel only)Show Member PointsShow Connected Units

Connect to Neighbour Alarm ZoneDisconnect from Neighbour Alarm ZoneShow Member Fire Alarm DevicesShow Neighbour Alarm ZonesShow Activating Detection Zones

Move to Detection Zone (/Create New)Connect to OutputConnect to Activation Group (/Create New)Disconnect from OutputDisconnect from Activation GroupShow Connected Units

Move to Alarm ZoneShow Connected Units

Connect to OutputConnect to Activation GroupDisconnect from OutputDisconnect from Activation GroupShow Activating Detection ZonesShow Activating PointsShow Activating InputsShow Activating GroupsShow Activating Outputs

Move to Alarm Zone (applies to FAD only)

Show Connected Units

Connect to OutputConnect to Alarm ZoneDisconnect from OutputDisconnect from Alarm ZoneShow Connected Units

Show All Carrier UnitsShow Carrier PointsShow Carrier InputsShow Carrier Outputs

ConfigureShow Mimic InputsShow Mimic Outputs

Connect to OutputDisconnect from OutputShow Member PointsShow Connected Units

(Not applicable to FAD, FARE and FWRE:)

(Not applicable to FARE and FWRE:)

Serial Port SettingsTCP/IP Port SettingsESPAMODBUSVDRRemote Access

Configure ESPA SettingsConfigure ESPA EventsConfigure ESPA Receivers TableSend ESPA Test Event

Configure MODBUS SettingsCongigure Status RegistersConfigure Command RegistersSet Testbit to 0Set Testbit to 1Assign Unique MODBUS Indexes

Configure VDR SettingsSend VDR Test Event

Server and Web AccessUser ManagementClientsClient Proxy Server

Page 12: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Service Commands

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 12

2.4 Entering the Service Menu

First, to enter the Menu Mode from operation mode or the panel’s

idle state, press and hold down the Enter button for a few seconds.

The following will appear in the display:

Use the arrow down button to scroll down and select Enter

Service Mode.

Press Enter twice, then use the alphanumeric keypad and type

the password that has been selected during commissioning (4 characters).

To accept the password, press Enter once more. The menu selections Service and Exit Service now appear in the display.

Page 13: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Service Commands

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 13

To enter the Service menu, use the arrow down button to scroll down and select Service, then press the Enter.

Page 14: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 14

3. System Settings

3.1 Menu Selections - Overview

All system settings are global settings, meaning that the settings affect the entire system. From the Service Menu, perform the following: Press Enter to select System Settings. The following menu selections appear: Save Configuration (chapter 3.2) Restart System (chapter 3.3) Day Mode Operation Times (chapter 3.4) Service Mode Password (chapter 3.5) Date and Time (chapter 3.6) Set Operator Panel Connection (chapter 3.7) Sound Patterns (chapter 3.8) Automatic Resound (chapter 3.9) Detection Zone Delay Timers (chapter 3.10) Detection Zone Global Dependency (chapter 3.11) Battery Parameters (chapter 3.12) Panel Name (chapter 3.13) Language (chapter 3.14) FARE and FWRE Disablement (chapter 3.15) Mains Power Fault Indication (chapter 3.16) Printer Setup (chapter 3.17) Configuration Check (chapter 3.18) System Shutdown (chapter 3.19) Restore Factory Settings (chapter 3.20) The following chapters describe the menus in detail (following the sequence of the System Settings Menu).

3.2 Save Configuration

Each time a configuration has been changed, this command should be run. The changes will not become effective until a Restart System command is performed. From the Service Menu, perform the following: Press Enter to select System Settings. Press Enter twice to select Save Configuration. Type a new Site Name, or accept the existing one by pressing the

arrow down button. Type a new Operator Name, or accept the existing one by

pressing the arrow down button. Press Enter to type a new Site Configuration Version then press

Enter, or accept the existing one by pressing the arrow down button.

Press Enter to type a new Description then press Enter, or accept the existing one by pressing the arrow down button.

To confirm, press Enter.

Page 15: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 15

3.3 Restart System

Note that you always have to save a configuration (chapter 3.2) and restart the system in order to activate a configuration: each time a configuration has been changed after an initial startup (part of the start-up procedure) From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Restart System, then press

Enter. If the system is to be restarted after a configuration has been

changed, the following message will appear: ”System configuration data has been changed. If the system is restarted without saving configuration data, the changes will be lost. Save data before restarting?” o Use the left arrow button to select Accept, then press Enter

twice. o Type a new Site Name, or accept the existing one by pressing

the arrow down button. o Type a new Operator Name, or accept the existing one by

pressing the arrow down button. o Press Enter to type a new Site Configuration Version then

press Enter, or accept the existing one by pressing the arrow down button.

o Press Enter to type a new Description then press Enter, or accept the existing one by pressing the arrow down button.

o To confirm, press Enter. After a short period the message “Configuration has been saved” will appear.

o Press the left arrow button, then press Enter to confirm. If the system is to be restarted after an intitial startup, the

following message will appear: “Restart of the system will perform a controlled shutdown before restart. This may take a while, depending on the system size.” o Use the left arrow button to select Accept, then press Enter to

confirm. The message ”System is now shutting down…” will appear, and a bar will appear at the bottom showing the progress of the reboot.

Page 16: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 16

3.4 Day Mode Operation Times

By default the entire system is set to Night Mode, meaning that the system is set to immediate output actioning. The system menu Day Mode Operation Times allows you to configure settings for automatic delay of the activation of outputs to Fire Alarm Devices (FAD) and/or Fire Alarm Routing Equipment (FARE) at certain periods. The settings will only affect points that have been set to “Override Delay and Dependency NO” in detection zones configured as Delayed Action Detection Zones or Delayed Dependency Detection Zones. To achieve this, you simply choose the days in the week when you want the system to automatically enable the delays, plus the exact duration of the disablement in hours and minutes (the start time and end time). A maximum of 14 settings are available (for example, 7 days; 2 intervals per day, or, for example, 14 intervals for one specific day). Note that overlapping settings are not possible. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Day Mode Operation

Times, then press Enter twice. Use the left/right arrow button to select among the following days:

o Unspecified o Every day o Monday to Friday o Saturday, Friday, Thursday, Wednesday, Tuesday, Monday,

Sunday. Press Enter. Use the alphanumeric keypad to specify the start time*

(hours:minutes), then press Enter. Specify the end time* (hours:minutes), then press Enter. * Note that if an invalid input is given, a message indicating this will appear in the display. It is recommended that all settings (for example, settings for 4 different days) are done before the settings finally are confirmed. To view existing Day Mode Operation Times, refer to chapter 3.4.1. To add new Day Mode Operation Times to existing ones at a later point of time, refer to chapter 3.4.2. Press and hold down the Function button a few seconds

(“Long press to accept or cancel”). To confirm the new settings (Accept), press Enter.

Page 17: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 17

3.4.1 Viewing Existing Day Mode Operation Times

To view existing Day Mode Operation Times, do as follows: o If you have left the Day Mode Operation Times menu (if you

have not, go directly to the next step), return to the System Settings menu, press the arrow down button to select Day Mode Operation Times, then press Enter.

o In the Day Mode Operation Times menu, scroll downwards using the arrow down button several times (pressing the arrow down button 3 times will reveal the next setting, pressing 3 times more will reveal the next setting, etc.).

3.4.2 Adding new Day Mode Operation Times

To add a new Day Mode Operation Time at a later point, provided that there are available settings (maximum 10), do as follows: o In the System Settings menu, press the arrow down button to

select Day Mode Operation Times, then press Enter twice.

o Scroll downwards using the arrow down button several times until “Unspecified “ is shown (pressing the arrow down button 3 times will reveal the next setting, pressing 3 times more will reveal the next setting, etc.). The number of times you have to press the arrow down button before “Unspecified” is shown in the display depends on the number of settings that already are defined. For example, if there is 1 previous setting, you have to press the arrow down button 3 times before “Unspecified” is shown. If there are 2 previous settings, you have to press the arrow down button 6 times before “Unspecified” is shown.

o When “Unspecified” is shown in the display, use the left/right

arrow button to select among the days that are available, and continue as described in chapter 3.4.

Page 18: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 18

3.5 Service Mode Password

This menu allows you to change the Service Mode Password. A total of 4 characters must be used. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Service Mode Password,

then press Enter twice. Type the new password, then press Enter. Type the new password once more, then press Enter. To confirm the new password, press Enter once more.

The message “Please wait…” will appear in the display and the new password will take effect within a couple of seconds.

3.6 Date and Time

This menu allows you to set/change the date and time. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Date and Time, then press

Enter twice. To change the time, overwrite the time (hours, minutes, seconds),

then press Enter. To change the date, overwrite the date (day, month, year), then

press Enter. To confirm the new settings, press Enter once more.

Page 19: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 19

3.7 Set Operator Panel Connection

This command allows the operator to specify how the operator panel is connected. If the panel is to be operated as a standalone panel (and the

panel is connected accordingly, i.e. J7), the menu selection Operator Panel must be selected (default).

If the panel is to be connected to a panel bus, the menu selection Auxiliary terminal block (J4) must be selected.

From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Operator Panel

Connection, then press Enter twice. Use the arrow left/right button to select;

J7, Operator Panel (default) if the panel is to operate as a standalone panel or; J4, Auxiliary terminal block if the panel is to be connected to a panel bus.

To confirm the chosen settings, press Enter twice.

IMPORTANT NOTE: The default panel connection setting (Service Menu/System Settings/“Set Operator Panel connection”) is set to “J7, Operator Panel” (connector J7). Likewise, the cables from the integrated operator panel BS-210 are connected to connector J7. All panels delivered from our factory are thus prepared for operating as a standalone cabinet with an integrated BS-210 and with no external panel bus. If an external panel bus with additional panels is to be connected to the cabinet or the operator panel BS-210 is to be placed outside the cabinet, the panel connection setting and cabling (communication cables) must be changed during installation/commissioning in order to achieve redundancy and fault monitoring of the panel bus.

Page 20: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 20

3.8 Sound Patterns

The standard setup of the system provides the following default sound patterns in the following prioritized order:

Sound signal Default sound patterns Default Prolong Signal (the last bit)

Custom-defined Pattern 1 0000000000000000 0 seconds General Alarm Pattern 0101010101010101 2 seconds Evacuate Pattern 1100110011001100 0 seconds Alert Pattern 1000000010000000 0 seconds Custom-defined Pattern 2 0000000000000000 0 seconds Custom-defined Pattern 3 0000000000000000 0 seconds

Pattern Activation Detection zones are connected to alarm zones (Main Alarm Zones). An alarm signal from the detection zones activates the EVACUATE pattern in these alarm zones. Neighbour Alarm zones may be connected to the Main Alarm Zones. The Neighbour Alarm Zones will have the ALERT pattern activated. The remaining patterns may be activated from an input signal configured as “Activate all Alarms” (refer to 5.9.2). Be aware of the priority given in the table above. The following settings are available for each sound pattern: The Sound Pattern is set by choosing a predefined 16 bit number (binary) which determines the pattern (for example, the Alert Pattern, including the following bits; 1000000010000000). The one-digits correspond to ON, and the zero-digits correspond to OFF. Prolong Signal: It is possible to prolong the last signal (i.e. the last bit) for a chosen sound pattern from 1 to a maximum of 99 seconds. Sound Level: It is possible to choose between High, Medium or Low sound level. (Not applicable for BBL-100 and BBL-100/IP). Sound Tone: It is possible to choose between Continuous or Slow Whoop. (Not applicable for BBL-100 and BBL-100/IP).

Page 21: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 21

Example: 7 short signals and one long signal, used as a standard evacuation signal onboard ships.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1

From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Sound Patterns, then press

Enter. Scroll downwards to select the desired Sound Pattern, then press

Enter twice. To change the pattern, use the Cancel button to delete the bits,

then type the new ones and press Enter. To change the bit values, use the arrow down/up buttons.

To prolong the last signal, type the seconds (from 1 to 99), then press Enter.

To select the Sound Level (High, Medium or Low), use the arrow left/right button, then press Enter.

To define the Sound Tone (Continuous or Slow Whoop), use the arrow left/right button, then press Enter.

To confirm the new settings, press Enter once more.

bits 0=OFF 1=ON

Page 22: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 22

3.9 Automatic Resound

During normal operation: When pressing the Silence button in the event of an alarm, all fire alarm devices (FADs) will be deactivated. The red Fire Alarm indication lamp will switch from a pulsing to a steady light. At this stage, the resound timer will start. The resound timer will restart on each operation of the Silence button. Holding the Silence button down for more than 7 seconds will activate the Resound function (this message appears in the information field). The alarm zones are by default automatically resounded to their alarm states on timeout (configurable) of the Silence resound timer. The menu selection Automatic Resound allows you to determine whether an automatic resound is possible or not. By default, automatic resound is off (No) and the time delay is set to 12 minutes. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Automatic Resound, then

press Enter twice. To select YES, press the right arrow button, then press Enter. To change the Time Delay, use the Cancel button to delete it,

then type the new one and press Enter. To confirm the new settings, press Enter once more.

3.10 Detection Zone (DZ) Delay Timers

During normal operation, when the operator panel receives a fire alarm signal from a point in a Delayed Action detection zone (configurable), the actioning of outputs to Fire Alarm Devices (FAD) can be delayed. Also the actioning of outputs to Fire Alarm Routing Equipment (FARE) can be delayed with the exception of manual call points. The delay is divided into two (configurable) delay periods, Initial delay, T1 and Prolonged Delay, T2. The default value for T1 is 60 seconds The default value for T2 is 120 seconds. The maximum delay (T1 plus T2) is 10 minutes (600 seconds).

The (T1) delay period is started when a Fire Alarm signal from a point is received. Acti ons will be initiated after the T1 delay period has expired. Pressing the Prolong Delay button, will terminate T1 and the delay period T2 will start. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Detection Zone Delay

Timers, then press Enter twice. To change the delay timers, use the Cancel button to delete the

present T1 Delay Timer (seconds), then type the new one and press Enter.

Repeat this procedure for the T2 Delay Timer, then press Enter.

Page 23: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 23

To confirm the new settings, press Enter once more.

3.11 Detection Zone (DZ) Global Dependency

This menu selection allows you to turn on Detection Zone Global Dependency, meaning that an alarm in a detecion zone will require a second alarm from another point, in any detection zone, before the detection zone activates any output. A fire alarm signal from a single detector will initiate no actions, i.e. there will be no actioning of outputs to; Fire Alarm Devices (FAD) Fire Alarm Routing Equipment (FARE) Fire Protection Equipment (FPE) From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select DZ Global Dependency,

then press Enter. The following message appears: “If enabled, an alarm in a DZ will require alarm from another point, in any DZ, before the DZ activates any output. Turn on DZ Global Dependency?”

To answer YES, press Enter, then press the right arrow button,

and press Enter once more. To confirm the new setting, press Enter once more.

3.12 Battery Parameters

This menu allows you to specify the following: the minimum charge voltage the battery low voltage limit the maximum charge current the maximum resistance limit From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Battery Parameters, then

press Enter twice. Press the right arrow button to select the minimum charge voltage

(default 21000mV, minimum 20000mV, maximum: 31000mV), then press Enter.

Press the right arrow button to select the battery low voltage limit (default 21000mV, minimum 17900mV, maximum: 31000mV), then press Enter.

Press the right arrow button to select the maximum charge current (default 1500mA, minimum 1000mA, maximum: 2000mA), then press Enter.

Press the right arrow button to select the maximum resistance limit (default 800mOhm, minimum 200mOhm, maximum: 5000 mOhm), then press Enter.

To confirm the new setting, press Enter once more.

Page 24: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 24

3.13 Panel Name

This menu allows you to change the Panel Name. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Panel Name, then press

Enter twice. The current Panel Name will appear.

Press Enter, then overwrite the Name. The Panel Type will appear in the display.

To confirm the new Name, press Enter. Use the Cancel button to leave this menu selection.

3.14 Language

This menu allows you to change the language. Autroprime supports the following languages (listed in alphabetical order): Danish Dutch English Finnish German French Hungarian Icelandic Italian Norwegian Polish Portuguese (Brazilian) Russian Spanish Swedish

From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Language, then press

Enter twice. To select the desired language, use the left arrow button to the

language appears in the display, then press Enter. To change the date, overwrite the date (day, month, year), then

press Enter. To confirm the new language, press Enter once more.

The message “Please wait…” will appear in the display, meaning that the selected language file is now being imported. The import of the new language file may take a couple of minutes.

Page 25: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 25

3.15 FARE and FWRE Disablement

This menu selection allows you to disable Fire Alarm Routing Equipment (FARE) and Fault Warning Routing Equipment (FWRE) when the system is in access level 2 or 3. In this way, the outputs to Fire Alarm Routing Equipment (FARE) and Fault Warning Routing Equipment (FWRE) will – assuming that this setting has been chosen -always be disabled during service (in access level 2 and 3). Note that the disablement will only have effect on the system when the system is in access level 2 or 3. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select FARE and FWRE

Disablement, then press Enter twice. To disable FARE in access level 2 and 3, use the right arrow

button to select YES, then press Enter. To disable FWRE in access level 2 and 3, use the right arrow

button to select YES, then press Enter. To confirm the settings, press Enter once more.

3.16 Mains Power Fault Indication

This menu selection allows you to specify a delay period (in minutes) before a Power Fault indication is shown in the event of a power outage or electrical power failure. According to EN 54 regulations, this delay period can be a maximum of 30 minutes. If you have specified a delay, it is possible to choose whether or not you want to disable the outputs to Fire Warning Routing Equipment as well. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Mains Power Fault

Indication, then press Enter twice. Type the desired number of minutes (Delay Fault Indication), then

press Enter. Use the right arrow button to choose whether you want to disable

the outputs to Fire Warning Routing Equipment (YES/NO), then press Enter.

To confirm the settings, press Enter once more.

Page 26: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 26

3.17 Printer Setup

The menu selection allows you to enable printing of alarm events. Whenever any alarm events occur, the system will automatically printout these events. In addition, you can initiate a printer test instantly to verify that the communication with the printer is established. The printer’s operational status is monitored once every hour, and a fault message is presented in the panel display whenever any printer fault is detected. The printer should use its factory default parameters. Refer to the printer user's guide. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Printer Setup, then press

Enter twice. Use the right or left arrow button to choose whether you want to

enable printing of alarm events (YES/NO), then press Enter. Use the right or left arrow button to choose whether you want to

reverse print direction (YES/NO) Use the right or left arrow button to choose whether you want to

initiate an instant printer test (YES/NO), then press Enter. To confirm the settings, press Enter once more.

3.18 Configuration Check

The menu selection allows you to check the consistency of the running configuration. The default value is YES, meaning that if the configuration contains at least one Detection Zone that does not activate any Alarm Zone, a fault messages will appear. Selecting YES will result in the following behaviour: After system startup, the fault message ”DZ does not activate any AZ” will appear if one or several Detection Zones are not connected to an Alarm Zone. The fault message can be acknowledged and a reset can be performed, but the fault message will reappear if the fault still exists. Selecting NO will result in the following behaviour: No fault messages will appear if one or several Detection Zones are not connected to an Alarm Zone. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Configuration Check, then

press Enter twice. Use the right arrow button to choose YES or NO, then press

Enter. To confirm the settings, press Enter once more.

Page 27: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 27

3.19 System S hutdown

This menu selection allows you to bring the panel to a safe state when the intention is to subsequently switch the power off by disconnecting the mains power cable. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select System Shutdown. Press Enter, and the following message will appear in the display: The following message will appear in the display: ”System

Shutdown will do a controlled shutdown of the services. When state System Fault is entered, it is safe to power off the system.”

To execute the command, use the left arrow button, then press Enter.

Page 28: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Settings

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 28

3.20 Restore Factory Settings

This menu selection allows you to restore factory settings. Note that all configuration data will be deleted, and the system will return to its pre-configured state (factory settings). After the command “Restore Factory Settings” is run, the fault message “Missing Configuration File” will appear in the display, which is normal. The command “Save Configuration” and “Restart System” must then be run. When these two commands are executed, the configuration file including the factory settings will take effect, and the fault message will no longer be shown. From the Service Menu, perform the following: Press Enter to select System Settings. Press the arrow down button to select Restore Factory Settings. Press Enter, and the following message will appear in the display:

”All configuration data will be deleted and the system restarted. Are you sure you want to continue?”

To execute the command, use the left arrow button, then press Enter. The following message will appear in the display: “Please Wait…. System is now shutting down.”

Page 29: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Loop Operation

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 29

4. Loop Operation

4.1 Accessing the Menu Selections

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Loop Operation, then press Enter.

All loops are listed in the display. Use the arrow up/down buttons to select the detection loop in

question.

To view properties for the selected detection loop, press Enter. The following information is shown: o Name o Limit for maximum loop current o Measured loop current o Loop resistance – wire o Loop resistance + wire

To access available functions for a selected detection loop, press

the Function button , or use, if necessary, the multiselect feature to select several detection loops by pressing the Select button to mark the detection zones that are to be configured, and then press the Function button .

The following menu selections will appear:

o Enable (chapter 4.2) o Disable (chapter 4.3) o Change Disable Time Span (chapter 4.4) o Show Polluted Detectors (chapter 4.5) o Show Low Current Units (chapter 4.6)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 30: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Loop Operation

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 30

4.2 Enable

This menu selection allows you to enable detection loops that are currently disabled. To execute the command, access level 3 is required. From the Service Menu, perform the following: After pressing the Function button for the selected detection

loop(s), select Enable (the first menu selection), then press Enter. To confirm the enablement, press Enter once more.

The display will return to the list of loops.

4.3 Disable

During service a technician is able to disable one or several loops. To execute the command, access level 3 is required. From the Service Menu, perform the following: After pressing the Function button for the selected detection

loop(s), use the arrow down button to select Disable, then press Enter twice.

Enter the hours and minutes, then press Enter. To confirm the disablement, press Enter once more. The display will return to the list of loops.

Page 31: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Loop Operation

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 31

4.4 Change Disable Time Span

This menu selection allows a technician to change the disable time span. From the Service Menu, perform the following: After pressing the Function button for the selected detection

loop(s), use the arrow down button to select Change Disable Time Span, then press Enter twice.

Enter the hours and minutes, then press Enter. To confirm the new disable time span, press Enter once more. The display will return to the list of loops.

4.5 Show Polluted Detectors

This menu selection allows you to specify a limit (default 80) for black and white dust pollution. All units exceeding the specified limit will be listed in the display. The menu also allows you to reset the compensation level for units exceeding the limit. From the Service Menu, perform the following: After pressing the Function button for the selected detection

loop(s), use the arrow down button to select Show Polluted Detectors, then press Enter twice.

Use the alpanumeric keypad to specify a limit for dust pollution, then press Enter.

To confirm the setting, press Enter once more. All points that exceed the specified limit are listed. To reset the compensation level for a point exceeding the

specified limit, select the point, then press the Function button .

Select Reset Compensation Level, then press Enter. To confirm the setting, press Enter once more.

Page 32: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Loop Operation

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 32

4.6 Show Low Current Units

The command allows you to identify low current loop units (100mA, 150mA, 200mA and 250mA) that are not intended to be on a high current loop (300mA, 350mA and 400mA). An attempt to increase the loop current to 300mA, 350mA or 400mA for a selected detection loop (command: Service/Unit Configuration/Detection Loop) will be rejected by the system if low current units are on this detection loop (a fault message “Low current loop unit detected” will tell you that there are one or several low current loop units on the high current detection loop). From the Service Menu, perform the following: After pressing the Function button for the selected detection

loop(s), use the arrow down button to select Show Low Current Units, then press Enter twice.

All low current units are listed.

Page 33: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 33

5. Unit Configuration

5.1 Menu Selections - Overview

The Unit Configuration menu includes the following menu selections: Detection Zones (chapter 5.2) Alarm Zones (chapter 5.3) Points (chapter 5.4) Fire Alarm Devices (chapter 5.5) Loop Outputs (chapter 5.6) Local Outputs (chapter 5.7) Loop Inputs (chapter 5.8) Local Inputs (chapter 5.9) Loop I/O Carriers (chapter 5.10) Mimic Panels (BUR-200), (chapter 5.11)

(Menu selection available only if Mimic Panels are connected). Activation Groups (chapter 5.12) External Interfaces (chapter 5.13) Detection Loops (chapter 5.14) Operator Panels (chapter 5.15)

Page 34: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 34

5.2 Detection Zones

5.2.1 Accessing the Menu Selections

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter twice. Use the arrow up/down buttons to select the detection zone that

is to be configured. To view or change properties for the selected detection zone

(name and alarm organization), refer to Configure Properties for a Detection Zone (chapter 5.2.2).

To access available functions for a selected detection zone, press the Function button , or use, if necessary, the multiselect feature to select several detection zones by pressing the Select button to mark the detection zones that are to be configured, and then press the Function button .

The following menu selections will appear: o Connect to Alarm Zone (chapter 5.2.3) o Connect to Output (chapter 5.2.4) o Connect to Disable Input Device (chapter 5.2.5) o Connect to Local Alarm Delay Unit (chapter 5.2.6) o Connect to Panel* (chapter 5.2.7) o Disconnect from Alarm Zone (chapter 5.2.8) o Disconnect from Output (chapter 5.2.9) o Disconnect from Disable Input Device (chapter 5.2.10) o Disconnect from Local Alarm Delay Unit (chapter 5.2.11) o Disconnect from Panel* (chapter 5.2.12) o Show Member Points (chapter 5.2.13 ) o Show Connected Units (chapter 5.2.14)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter. * Menu selection available only if a “Mimic” panel is connected.

Page 35: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 35

5.2.2 Configure Properties for a Detection Zone

The following properties apply: view/change the name of a detection zone change the alarm organization, i.e. the detection zone type

(Immediate Action, Dependency Action, Delayed Action, Delayed Dependency Action, SOLAS).

Note that the default Detection Zone will always have the detection zone type “Immediate Action”, i.e. it cannot be changed. The system provides the following types of detection zones with different properties: Immediate Action detection zone Dependency Action detection zone Delayed Action detection zone Delayed Dependency detection zone SOLAS (Safety of Life at Sea) detection zone The property of a detection zone as well as the type of point (detector or manual call point) will determine how the system responds to the signal - with respect to action. For information on alarm organization and the different types of detection zones, refer to Appendix. From the Detection Zones Menu (5.2.1), perform the following: After selecting the detection zone in question by means of the

arrow down/up buttons, press Enter twice. Type a new Name then press Enter, or accept the existing one by

pressing the arrow down button. If the detection zone is the default detection zone, press Enter to

confirm the setting.

If the detection zone in question is not the default detection zone, you can select among 5 different detection zone types (alarm organization).

Use the left or right arrow button to select the detection zone type, then press Enter.

To confirm the setting, press Enter once more.

Page 36: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 36

5.2.3 Connect to Alarm Zone

This menu allows you to connect a detection zone to an existing alarm zone. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), select Connect to Alarm Zone (the first menu selection), then press Enter.

Use the arrow down button to select an existing alarm zone. Press Enter to connect the detection zone to this alarm

zone. To confirm the setting, press Enter once more.

5.2.4 Connect to Output

This menu allows you to connect a detection zone to an output. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Connect to Output, then press Enter. Only local outputs of the type General Output will be listed.

Use the arrow down button to select the output, then press Enter twice.

Use the arrow left/right buttons to select the Detection Activation State (Prealarm, Small Alarm, Large Alarm, Silent Alarm), then press Enter.

To confirm the setting, press Enter once more.

Page 37: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 37

5.2.5 Connect to Disable Input Device

This menu allows you to connect a detection zone to a Disable Input Device (DID). From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Connect to Disable Input Device, then press Enter twice.

Use the arrow button to select the Disable Input Device, then press Enter.

To confirm the setting, press Enter once more.

5.2.6 Connect to Local Alarm Delay Unit

This menu allows you to connect a detection zone to a Local Alarm Delay Unit. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Connect to Local Alarm Delay Unit, then press Enter twice.

Use the arrow button to select the Local Alarm Delay Unit, then press Enter.

To confirm the setting, press Enter once more.

5.2.7 Connect to Panel

This menu allows you to connect a detection zone to a “Larmlagring” Panel. Note that the menu selection is available only if a such panel is connected to the system. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Connect to Panel, then press Enter twice.

Use the arrow button to select the Panel, then press Enter. To confirm the setting, press Enter once more.

Page 38: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 38

5.2.8 Disconnect from Alarm Zone

This menu allows you to disconnect a detection zone from an alarm zone. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Disconnect from Alarm Zone, then press Enter twice.

Use the arrow down/up button to select the alarm zone to be disconnected, then press Enter.

To confirm the setting, press Enter once more.

5.2.9 Disconnect from Output

This menu allows you to disconnect a detection zone from an output. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Disconnect from Output, then press Enter twice.

Use the arrow down/up button to select the output to be disconnected, then press Enter.

To confirm the setting, press Enter once more.

5.2.10 Disconnect from Disable Input Device

This menu allows you to disconnect a detection zone from a Disable Input Device (DID). From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Disconnect from Disable Output Device, then press Enter twice.

Use the arrow down/up button to select the device to be disconnected, then press Enter.

To confirm the setting, press Enter once more.

5.2.11 Disconnect from Local Alarm Delay Unit

This menu allows you to disconnect a detection zone from a Local Alarm Delay Unit. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Disconnect from Local Alarm Delay Unit, then press Enter twice.

Use the arrow down/up button to select the device to be disconnected, then press Enter.

To confirm the setting, press Enter once more.

Page 39: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 39

5.2.12 Disconnect from Panel

This menu allows you to disconnect a detection zone from a “Larmlagring” Panel. Note that the menu selection is available only if a such panel is connected to the system. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Disconnect from Panel, then press Enter twice.

Use the arrow down/up button to select the panel to be disconnected, then press Enter.

To confirm the setting, press Enter once more.

5.2.13 Show Member Points

This menu allows you to view a list of all points belonging to a selected detection zone. From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Show Member Points, then press Enter.

To view detailed information for a selected point, use the arrow down/up button to select the point, then press Enter.

The following information will appear:

o the point’s name/type o information on whether the point is set to override delay and

dependency or not (YES/NO) o the point’s performance class day settings o the point’s operation class day settings o the point’s performance class night settings o the point’s operation class night settings

5.2.14 Show Connected Units

This menu allows you to view all connections related to a selected detection zone, i.e. what the detection zone activates (for example, alarm zone, outputs, etc.). From the Detection Zones Menu (5.2.1), perform the following: After pressing the Function button for the selected detection

zone(s), use the arrow down button to select Show Connected Units, then press Enter.

To view detailed information (name, parent alarm zone and immediate activation status) for all connections related to a selected detection zone, use the arrow down/up button to select an alarm zone, then press Enter.

Page 40: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 40

5.3 Alarm Zones

5.3.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Alarm Zones, then press

Enter once more. Use the arrow up/down buttons to select the alarm zone that

is to be configured. To view or change properties for the selected alarm zone

(name), refer to Configure Properties for an Alarm Zone (chapter 5.3.2).

To access available functions for a selected alarm zone, press the Function button , or use, if necessary, the multiselect feature to select several alarm zones by pressing the Select button to mark the alarm zones that are to be configured, and then press the Function button .

The following menu selections will appear:

o Connect to Neighbour Alarm Zone (chapter 5.3.3) o Disconnect from Neighbour Alarm Zone (chapter 5.3.4) o Show Member Fire Alarm Devices (chapter 5.3.5) o Show Neighbour Alarm Zones (chapter 5.3.6) o Show Activating Detection Zones (chapter 5.3.7)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 41: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 41

5.3.2 Configure Properties for an Alarm Zone

To configure properties for an alarm zone, it is assumed that fire alarm devices (FADs) have already been connected to an alarm zone (the menu selection Fire Alarm Device). From the Alarm Zones Menu (5.3.1), perform the following: After selecting the alarm zone in question by means of the arrow

down/up buttons, press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter. Use the left or right arrow button to select a Parent Alarm Zone,

then press Enter. Use the right or left arrow buttons to choose whether you want

Immediate Activation or not (YES/NO), then press Enter. To confirm the setting, press Enter once more. * Parent Alarm Zone (default alarm zone): The top-level Alarm Zone is called the Parent Alarm Zone. A system consists of a Parent Alarm Zone, usually with several “sub-level” alarm zones in an hierarchy. Each “sub level”-alarm zone is related to a specific area of, for example, a building. If an alarm occurs in a Parent Alarm Zone, all Fire Alarm Devices (FADs) within the Parent Alarm Zone, plus all FADs belonging to all “sub-level”-alarm zones will be activated.

5.3.3 Connect to Neighbour Alarm Zone

This menu allows you to define a neighbour alarm zone for a selected alarm zone, or define the neighbourhood relation between alarm zones. From the Alarm Zones Menu (5.3.1), perform the following: After pressing the Function button for a selected alarm zone,

select Connect to Neighbour Alarm Zone (the first menu selection), then press Enter.

From the list of alarm zones, select an alarm zone that is to be defined as a neighbour alarm zone, then press Enter.

To confirm the setting, press Enter once more.

If you want to define another alarms zone as neighbour alarm zone to the selected alarm zone, repeat the procedure above.

Page 42: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 42

5.3.4 Disconnect from Neighbour Alarm Zone

This menu allows you to disconnect neighbourhood relations between alarm zones. From the Alarm Zones Menu (5.3.1), perform the following: After pressing the Function button for the selected alarm zone(s),

use the arrow down button to select Disconnect Neighbour Alarm Zone, then press Enter.

A list will appear, listing all alarm zones that have neighbourhood

relations. Select the alarm zone that is to be disconnected, then press

Enter. To confirm the setting, press Enter once more.

5.3.5 Show Member Fire Alarm Devices

This menu allows you to view all Fire Alarm Devices (FADs) belonging to an alarm zone. From the Alarm Zones Menu (5.3.1), perform the following: After pressing the Function button for the selected alarm zone(s),

use the arrow down button to select Show Member Fire Alarm Devices, then press Enter.

A list of all Fire Alarm Devices (FADs) will appear in the display. Use the arrow down button to select the FAD in question, then

press Enter. The name of the FAD and the unit function will appear in the display.

5.3.6 Show Neighbour Alarm Zones

This menu allows you to view the neighbour alarm zones for a selected alarm zone. From the Alarm Zones Menu (5.3.1), perform the following: After pressing the Function button for the selected alarm zone(s),

use the arrow down button to select Show Neighbour Alarm Zones, then press Enter.

A list of all Neighbour Alarm Zones will appear in the display. Use the arrow down button to select the Neighbour Alarm Zone

in question, then press Enter. The name of the Neighbour Alarm Zone and the unit function will appear in the display.

Page 43: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 43

5.3.7 Show Activating Detection Zones

This menu allows you to view all detection zones that activate a selected alarm zone. From the Alarm Zones Menu (5.3.1), perform the following: After pressing the Function button for the selected alarm zone(s),

use the arrow down button to select Show Activating Detection Zones, then press Enter.

A list of all Detection Zones will appear in the display. Use the arrow down button to select the Detection Zone in

question, then press Enter. The name of the Detection Zone and the alarm organization will appear in the display.

Page 44: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 44

5.4 Points

5.4.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Points, then press Enter

once more. Use the arrow up/down buttons to select the point that

is to be configured.

To view or change properties for the selected point, refer to Configure Properties for a Point (chapter 5.4.2).

To access available functions for a selected point, press the Function button , or use, if necessary, the multiselect feature to select several points by pressing the Select button to mark the points that are to be configured, and then press the Function button .

The following menu selections will appear:

o Move to Detection Zone (/Create New) (chapter 5.4.3) o Connect to Output (chapter 5.4.4) o Connect to Activation Group (/Create New) (chapter 5.4.5) o Disconnect from Output (chapter 5.4.6) o Disconnect from Activation Group (chapter 5.4.7) o Show Connected Units (chapter 5.4.8)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 45: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 45

5.4.2 Configure Properties for a Point

The following properties can be changed: name of a point override delay and dependency

In an alarm situation, the actioning of outputs will be delayed when; the detection zone has been defined as a Delayed Action detection zone (configurable) and the point(s) in this Delayed Action detection zone has not been set to Override Delay and Dependency, i.e. set to No.

performance class day setting (Normal 1, Normal 2; Industrial); depends on the type of detector

operation class day setting (depends on the type of point; MultiSensor with heat, MultiSensor only, Heat only)

performance class night setting (Normal 1, Normal 2; Industrial) operation class night setting (MultiSensor with heat, MultiSensor

only, Heat only) From the Points Menu (5.4.1), perform the following: After selecting the point in question by means of the arrow

down/up buttons, press Enter twice. Type a new Name then press Enter, or accept the existing one by

pressing the arrow down button. Use the left or right arrow button to select Yes or No (Override

Delay and Dependency or not), then press Enter. Use the left or right arrow button to select the desired

performance class day setting, then press Enter. Use the left or right arrow button to select the desired

operation class day setting, then press Enter. Use the left or right arrow button to select the desired

performance class night setting, then press Enter. Use the left or right arrow button to select the desired

operation class night setting, then press Enter. To confirm the setting, press Enter once more.

Page 46: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 46

5.4.3 Move to Detection Zone (/Create New)

This menu allows you to: move (connect) a selected point to an existing detection zone create a new detection zone for a selected point and, at the same

time, connect this point to the new detection zone When creating a new detection zone, the alarm organization for the new detection zone is determined (refer to Detection Zone / Configure Properties, chapter 5.2.2). From the Points Menu (5.4.1), perform the following: After pressing the Function button for the selected point(s), select

Move to Detection Zone (/Create New), (the first menu selection), then press Enter.

To connect the selected point to a new detection zone: o With the uppermost menu selection highlighted, press Enter

twice. o Type a name for the new detection zone, then press Enter. o Use the left or right arrow button to select the desired

alarm organization, then press Enter. o To confirm the setting, press Enter once more.

To move (connect) the selected point to an existing detection

zone: o Use the arrow down button to select the detection zone that

is to be connected to the point, then press Enter. o To confirm the setting, press Enter once more.

Page 47: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 47

5.4.4 Connect to Output

This menu allows you to connect a selected point to an output. The following settings can be done: Point State:

meaning which alarm level (pre-alarm or alarm) the point must have before the output is activated.

Activate on Point Disable (Yes/No): Yes: meaning that the output is activated if the selected point is disabled. No: meaning that the output is not activated if the selected point is disabled.

Activate on Point Fault (Yes/No): Yes: meaning that the output is activated if there is a fault on the selected point. No: meaning that the output is not activated if there is a fault on the selected point.

From the Points Menu (5.4.1), perform the following: After pressing the Function button for the selected point(s), use

the arrow down button to scroll downwards to Connect to Output, then press Enter.

A list of all available outputs will appear in the display.

Use the arrow up/down button to select the output that is to be connected to the selected point, then press Enter twice.

Use the left or right arrow button to set the Point State, then press Enter.

Use the left or right arrow button to set Yes or No for Activate on Point Disable, then press Enter.

Use the left or right arrow button to set Yes or No for Activate on Point Fault, then press Enter.

To confirm the setting, press Enter once more.

Page 48: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 48

5.4.5 Connect to Activation Group (/Create New)

This menu allows you to: connect a selected point to an existing activation group create a new activation group for a selected point and, at the

same time, connect this point to the new activation group When creating a new activation group, the following settings are determined: Activate group on Unit State:

meaning which alarm level the points within this activation group will react to (pre-alarm, alarm, fault and disablement).

Activation Group Dependency: meaning how many points within this activation group must be in alarm state before actions are initiated (1-5 and All).

Refer also to chapter 5.12 Activation Groups. From the Points Menu (5.4.1), perform the following: After pressing the Function button for the selected point(s), use

the arrow down button to scroll downwards to Connect to Activation Group (/Create New), then press Enter.

To connect the selected point to a new activation group: o With the uppermost menu selection highlighted, press Enter

twice. o Type a name for the new activation group, then press Enter. o Use the left or right arrow button to select the desired

unit state (Prealarm/Alarm), then press Enter. o Use the left or right arrow button to determine how many points

within this activation group that must be in alarm state before actions are initiated (1-5 and All).

o To confirm the setting, press Enter once more.

To move (connect) the selected point to an existing detection zone: o Use the arrow down button to select the activation group

that is to be connected to the point, then press Enter. o To confirm the setting, press Enter once more.

Page 49: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 49

5.4.6 Disconnect from Output

This menu allows you to disconnect a selected point from an existing output. From the Points Menu (5.4.1), perform the following: After pressing the Function button for the selected point(s), use

the arrow down button to scroll downwards to Disconnect from Output, then press Enter.

In the display you will now see a list of all outputs that are connected to the selected point . To disconnect the selected point from an output, use the arrow

down button to select the output, then press Enter. To confirm the setting, press Enter once more.

5.4.7 Disconnect from Activation Group

This menu allows you to disconnect a selected point from an existing activation group. From the Points Menu (5.4.1), perform the following: After pressing the Function button for the selected point(s), use

the arrow down button to scroll downwards to Disconnect from Activation Group, then press Enter.

A list of the activation groups the selected point is connected to will appear in the display. To disconnect the selected point from an activation group, use

the arrow down button to select the activation group, then press Enter.

To confirm the setting, press Enter once more.

Page 50: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 50

5.4.8 Show Connected Units

This menu allows you to view units that are activated by the selected point (detection zones, outputs etc.). From the Points Menu (5.4.1), perform the following: After pressing the Function button for the selected point(s), use

the arrow down button to scroll downwards to Show Connected Units, then press Enter.

A list will appear in the display, showing all detection zones, outputs etc. that are activated by the selected point.

Page 51: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 51

5.5 Fire Alarm Devices

5.5.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Fire Alarm Device, then

press Enter once more. Use the arrow up/down buttons to select the Fire Alarm Device

that is to be configured.

To view or change properties for the selected Fire Alarm Device, refer to Configure Properties for a Fire Alarm Device (chapter 5.5.2).

To access available functions for a selected Fire Alarm Device, press the Function button , or use, if necessary, the multiselect feature to select several Fire Alarm Devices by pressing the Select button to mark the Fire Alarm Devices that are to be configured, and then press the Function button .

The following menu selections will appear:

o Move to Alarm Zone (chapter 5.5.3) o Show Connected Units (chapter 5.5.4)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 52: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 52

5.5.2 Configure Properties for a Fire Alarm Device

The following properties can be changed: name of a Fire Alarm Device (FAD) the “unit function” for local outputs that are assigned the unit

function Fire Alarm Device (FAD). (Refer to the Local Outputs menu).

From the Fire Alarm Devices Menu (5.5.1), perform the following: After selecting the FAD in question by means of the arrow

down/up buttons, press Enter twice. Type a new Name and press Enter, or accept the existing one by

pressing the arrow down button. To confirm the setting, press Enter once more. If a local output (that is assigned unit function FAD) is selected,

and not a FAD, use the arrow left/right buttons to select among the following unit functions: o Fire Alarm Device o General Output o RESET Out o Silence Alarm Output o Silence Out o Small Alarm Output o FWRE o FARE

Press Enter. To confirm the setting, press Enter once more.

5.5.3 Move to Alarm Zone

This menu allows you to connect a selected Fire Alarm Device to an existing alarm zone or create a new alarm zone, and at the same time connect the new alarm zone to the Fire Alarm Device. From the Fire Alarm Devices Menu (5.5.1), perform the following: After pressing the Function button for the selected FAD(s), select

Move to Alarm Zone (the first menu selection), then press Enter. Use the arrow button to select an existing alarm zone, or select

the menu Create New Alarm Zone. o If an existing alarm zone is selected, press Enter twice to

connect the detection zone to this alarm zone. o If a new alarm zone is to be created, select Create New

Alarm Zone, press Enter twice, type the name, then press Enter.

o Use the left/right arrow buttons to select the Parent Alarm Zone”, then press Enter twice to confirm.

Page 53: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 53

5.5.4 Show Connected Units

This menu allows you to view the alarm zone that belongs to a selected Fire Alarm Device (FAD). The name of the alarm zone, and this alarm zone’s parent alarm zone will appear in the display. From the Fire Alarm Devices Menu (5.5.1), perform the following: After pressing the Function button for the selected FAD(s), use

the arrow down button to select Show Connected Units, then press Enter.

In the display you will now see the alarm zone that belongs to the selected Fire Alarm Device. Press Enter.to view the name of the alarm zone.

Page 54: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 54

5.6 Loop Outputs

5.6.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Loop Outputs, then

press Enter once more. Use the arrow up/down buttons to select the Loop Output

that is to be configured (if any). To view or change properties for the selected Loop Output, refer

to Configure Properties for a Loop Output (chapter 5.6.2).

To access available functions for a selected loop output, press the Function button , or use, if necessary, the multiselect feature to select several loop outputs by pressing the Select button to mark the loop outputs that are to be configured, and then press the Function button .

The following menu selections will appear: (Menu selections not applicable to FAD, FARE and FWRE):

o Connect to Output (chapter 0) o Connect to Activation Group (chapter 5.6.4) o Disconnect from Output (chapter 5.6.5) o Disconnect from Activation Group (chapter 5.6.6) o Show Activating Detection Zones (chapter 5.6.7) o Show Activating Points (chapter 5.6.8) o Show Activating Inputs (chapter 5.6.9) o Show Activating Groups (chapter 5.6.10) o Show Activating Outputs (chapter 5.6.11)

(Menu selection applies to FAD only):

o Move to Alarm Zone (Menu selection not applicable to FARE, FWRE):

o Show Connected Units (chapter 5.6.12) Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 55: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 55

5.6.2 Configure Properties for a Loop Output

The properties for a loop output depends on the type of output. From the Loop Outputs Menu (5.6.1), perform the following: After selecting the Loop Output in question by means of the arrow

down/up buttons, press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter, then use the arrow left/right buttons to select among

the unit functions that are available for the selected Loop Output (see overview below).

Press Enter. To confirm the setting, press Enter once more. Unit functions for different types of loop outputs: Door Unit

o Name o Function o Activation Group Dependency (how many Activation Groups

must be in alarm before the output is activated, the default value is 1, see example below)

o Supervisory o Supervisory Text o Activation o Activation Timer o Monitoring Timer

Standard Control Unit

o Name o Function o Supervisory

Example. Door Control in engine room scenario

1. Monitoring Timer

If a door's position has been changed, for example, from open to closed (or visa versa), an indication of the door’s status (open / ajar / closed) will be given within a certain period (seconds). The Monitoring Timer determines this period.

2. Activation Timer If a command is sent to close a door (regardless of whether the door is open or closed), a technical alarm will be activated if the door is not closed within a certain period (seconds). The Activation Timer determines this period.

3. Activation Monitoring Timer

If a door is closed because a “close” command is sent, it can be opened and it can stay open / ajar for a certain period (seconds). If the door is not closed within this period, a technical alarm will be activated. The Activation Monitoring Timer determines this period (supervisory).

Output

Act. Group 2

Act. Group 1

Page 56: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 56

5.6.3 Connect to Output

This menu allows you to determine, for a selected loop output, which outputs that are to be activated on the activation of this loop output. In the example below, loop output 1 will on activation, activate output 2 and 3. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), select Connect to Output (the first menu selection), then press Enter.

A list of all available outputs will appear in the display. Use the arrow up/down button to select the output(s) that

is to be activated on the activation of the loop output, then press Enter.

To confirm the setting, press Enter once more.

5.6.4 Connect to Activation Group

This menu allows you to connect a selected loop output to an Activation Group by which it will be activated. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Connect to Activation Group, then press Enter.

A list of all available activation groups will appear in the display. Use the arrow up/down button to select the activation group that

is to be connected to the loop output, then press Enter. To confirm the setting, press Enter once more.

Loop Output 1

Output 3

Output 2

Page 57: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 57

5.6.5 Disconnect from Output

This menu allows you to disconnect a selected loop output from an output, meaning that the selected loop output will, on activation, not activate the output. In the example below, loop output 1 will on activation, no longer activate output 3 (only output 2). Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.

In the display you will now see a list of all outputs that are connected to the selected loop output. To disconnect the selected loop output from an output, use the

arrow down button to select the output, then press Enter.

To confirm the setting, press Enter once more.

5.6.6 Disconnect from Activation Group

This menu allows you to disconnect a selected loop output from an Activation Group. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Disconnect from Activation Group, then press Enter.

In the display you will now see a list of all activation groups that are connected to the selected loop output. To disconnect the selected loop output from an activation group,

use the arrow down button to select the activation group, then press Enter.

To confirm the setting, press Enter once more.

Loop Output 1

Output 3

Output 2

Page 58: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 58

5.6.7 Show Activating Detection Zones

This menu allows you to view all detection zones that are connected to the selected loop output. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Show Activating Detection Zones, then press Enter.

In the display you will now see a list of all detection zones that are connected to the selected loop output.

5.6.8 Show Activating Points

This menu allows you to view all points that are connected to the selected loop output. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Show Activating Points, then press Enter.

In the display you will now see a list of all points that are connected to the selected loop output.

Page 59: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 59

5.6.9 Show Activating Inputs

This menu allows you to view all inputs that are connected to the selected loop output. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Show Activating Inputs, then press Enter.

In the display you will now see a list of all inputs that are connected to the selected loop output.

5.6.10 Show Activating Groups

This menu allows you to view all activating groups (groups; meaning “Activation Groups”) the selected loop output is connected to. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Show Activating Groups, then press Enter.

In the display you will now see a list of all activation groups that are connected to the selected loop output.

Page 60: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 60

5.6.11 Show Activating Outputs

This menu allows you to view all outputs that are connected to the selected loop output. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Show Activating Outputs, then press Enter.

In the display you will now see a list of all outputs that are connected to the selected loop output.

5.6.12 Show Connected Units

This menu allows you to view all connections that are connected to the selected loop output (and that activate the selected loop output). Note that the menu selection does not apply to Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Loop Outputs Menu (5.6.1), perform the following: After pressing the Function button for the selected Loop

Output(s), use the arrow down button to scroll downwards to Show Connections, then press Enter.

In the display you will now see a list of all connections that are connected to the selected loop output.

Page 61: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 61

5.7 Local Outputs

5.7.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Local Outputs, then

press Enter once more. Use the arrow up/down buttons to select the Local Output

that is to be configured. To view or change properties for the selected Local Output, refer

to Configure Properties for a Local Output (chapter 5.7.2).

To access available functions for a selected local output, press the Function button , or use, if necessary, the multiselect feature to select several local outputs by pressing the Select button to mark the local outputs that are to be configured, and then press the Function button .

The following menu selections will appear: Menu selections not applicable to FAD, FARE and FWRE:

o Connect to Output (chapter 5.7.3) o Connect to Activation Group (chapter 5.7.4) o Disconnect from Output (chapter 5.7.5) o Disconnect from Activation Group (chapter 5.7.6)

Menu selectoins applicable to Open Collector Outputs (general output 1 and 2):

o Show Activating Detection Zones (chapter 5.7.7) o Show Activating Points (chapter 5.7.8) o Show Activating Inputs (chapter 5.7.9) o Show Activating Groups (chapter 5.7.10) o Show Activating Outputs (chapter 5.7.11)

Menu selections applicable to Monitored Outputs (1 and 2): o Move to Alarm Zone (chapter 5.7.12)

(Menu selection applicable to FAD only) o Show Connected Units (chapter 5.7.13)

(Menu selection not applicable to FARE and FWRE) Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 62: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 62

5.7.2 Configure Properties for a Local Output

The following properties can be changed: the name of the local output the “unit function” for a local output – applies only to the standard

outputs on the main board’s terminal block J1.

Terminal Output hardware type Default function J1.12 Monitored Output 1 +24V FAD 1 J1.13 Monitored Output 1 0V FAD 1 J1.14 Monitored Output 2 +24V FAD 2 J1.15 Monitored Output 2 0V FAD 2 J1.16 Open Collector Output 1 General Output 1 J1.17 Open Collector Output 2 General Output 2 J1.18 Auxiliary +24V Out Intended used for Open collector J1.19 Relay Output 1 Com

FARE J1.20 Relay Output 1 NO J1.21 Relay Output 1 NC J1.22 Relay Output 2 Com

FWRE J1.23 Relay Output 2 NO J1.24 Relay Output 2 NC

From the Local Outputs Menu (5.7.1), perform the following: After selecting the Local Output in question by means of the

arrow down/up buttons, press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter, then use the arrow left/right arrow buttons to select

among the following unit functions: o Fire Alarm Device:

equipment giving warning of fire, for example, a sounder or visual indicator.

o Disable Out: output that is activated when there are disablements in the system

o General Output: output that is activated according to the configured events, for example, Pre Alarm, Alarm, Input Activated etc.

o RESET Out: output activated for approx. 2 seconds when the Reset button is operated.

o Silent Alarm Output: output dedicated to be activated at Silent Alarm regardless of alarm origin

o Silence Out: output activated for approx. 2 seconds when the Silence button is operated

o Small Alarm Output: output dedicated to be activated at Small Alarm regardless of alarm origin

o Fire Alarm Routing Equipment (FARE): equipment routing an alarm signal from control and indicating equipment to a Fire Alarm Receiving Station.

o Fault Warning Routing Equipment (FWRE): equipment routing a fault warning signal from control and indicating equipment to a fault warning receiving station.

Press Enter. To confirm the setting, press Enter once more.

Page 63: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 63

5.7.3 Connect to Output

This menu allows you to connect a selected local output to an output. The menu selection applies to open collector 1 and 2. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), select Connect to Output (the first menu selection), then press Enter.

A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that

is to be connected to the selected local output, then press Enter. To confirm the setting, press Enter once more.

5.7.4 Connect to Activation Group

This menu allows you to connect a selected local output to an Activation Group. The menu selection applies to open collector 1 and 2. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Connect to Activation Group, then press Enter.

A list of all available activation groups will appear in the display. Use the arrow up/down button to select the activation group that

is to be connected to the local output, then press Enter. To confirm the setting, press Enter once more.

Page 64: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 64

5.7.5 Disconnect from Output

This menu allows you to disconnect a selected local output from an existing output. The menu selection applies to onboard General Outputs only. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.

In the display you will now see a list of all outputs that are connected to the selected local output. To disconnect the selected local output from an output, use the

arrow down button to select the output, then press Enter.

To confirm the setting, press Enter once more.

5.7.6 Disconnect from Activation Group

This menu allows you to disconnect a selected local output from an existing Activation Group (refer to chapter 5.12). The menu selection applies to onboard General Outputs only. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Disconnect from Activation Group, then press Enter.

In the display you will now see a list of all Activation Groups that are connected to the selected local output. To disconnect the selected local output from an Activation Group,

use the arrow down button to select the activation group, then press Enter.

To confirm the setting, press Enter once more.

Page 65: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 65

5.7.7 Show Activating Detection Zones

This menu allows you to view all detection zones that are connected to the selected local output. The menu selection applies to onboard General Outputs only. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Show Activating Detection Zones, then press Enter.

In the display you will now see a list of all detection zones that are connected to the selected local output. Use the arrow up/down button to select a detection zone, then

press Enter. The name of the detection zone and unit function will appear in the display.

5.7.8 Show Activating Points

This menu allows you to view all points that are connected to the selected local output. The menu selection applies to onboard General Outputs only. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Show Activating Points, then press Enter.

In the display you will now see a list of all points that are connected to the selected local output. Use the arrow up/down button to select a point, then press Enter. The point’s properties will appear in the display.

Page 66: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 66

5.7.9 Show Activating Inputs

This menu allows you to view all inputs that are connected to the selected local output. The menu selection applies to onboard General Outputs only. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Show Inputs, then press Enter.

In the display you will now see a list of all inputs that are connected to the selected local output. Use the arrow up/down button to select an input, then press

Enter. The input’s properties will appear in the display.

5.7.10 Show Activating Groups

This menu allows you to view all activation groups (groups; meaning “Activation Groups”) that are connected to the selected local output. The menu selection applies to onboard General Outputs only. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Show Activation Groups, then press Enter.

In the display you will now see a list of all activation groups that are connected to the selected local output. Use the arrow up/down button to select the Activation Group,

then press Enter. The following information will appear in the display (for information on unit state and coincidence, refer to chapter 5.4.4):

o the name of the Activation Group o the Unit State o the Coincidence

Page 67: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 67

5.7.11 Show Activating Outputs

This menu allows you to view all outputs that are connected to the selected local output. The menu selection applies to onboard General Outputs only. Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Show Outputs, then press Enter.

In the display you will now see a list of all outputs that are connected to the selected local output. Use the arrow up/down button to select an output, then press

Enter. The output’s properties will appear in the display.

5.7.12 Move to Alarm Zone

This menu allows you to connect a selected Local Output (applies only to local outputs related to Fire Alarm Devices) to an alarm zone or create a new alarm zone, and at the same time connect the new alarm zone to the Local Output (Fire Alarm Device). Note that the menu selection applies to Fire Alarm Devices (FAD) only. From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to select Move to Alarm Zone, then press Enter.

Use the arrow button to select an existing alarm zone, or select the menu Create New Alarm Zone. o If an existing alarm zone is selected, press Enter twice to

connect the local output to this alarm zone. o If a new alarm zone is to be created, select Create New

Alarm Zone, press Enter twice, type the name, then press Enter.

o Use the left/right arrow buttons to select the Parent Alarm Zone, then press Enter twice to confirm.

Page 68: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 68

5.7.13 Show Connected Units

This menu allows you to view all connections that are connected to the selected local output. The menu selection applies to onboard General Outputs only. Note that the menu selection does not apply to Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE). From the Local Outputs Menu (5.7.1), perform the following: After pressing the Function button for the selected Local

Output(s), use the arrow down button to scroll downwards to Show Connections, then press Enter.

In the display you will now see a list of all connections that are connected to the selected local output. Use the arrow up/down button to select a connection, then press

Enter. In the display you will now see the name and unit function.

Page 69: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 69

5.8 Loop Inputs

5.8.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Loop Inputs, then

press Enter once more. Use the arrow up/down buttons to select the Loop Input

that is to be configured. To view or change properties for the selected Loop Input, refer

to Configure Properties for a Loop Input (chapter 5.8.2).

To access available functions for a selected loop input, press the Function button , or use, if necessary, the multiselect feature to select several loop inputs by pressing the Select button to mark the loop inputs that are to be configured, and then press the Function button .

The following menu selections will appear: o Connect to Output (chapter 5.8.3) o Connect to Alarm Zone (chapter 5.8.4) o Disconnect from Output (chapter 5.8.5) o Disconnect from Alarm Zone (chapter 5.8.6) o Show Connected Units (chapter 5.8.7)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 70: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 70

5.8.2 Configure Properties for a Loop Input

The following properties can be changed: the name of the loop input supervisory (Yes/No);

If Yes is selected, the inputs that are defined for technical alarms will be activated during normal operation, meaning that an indication of an event will appear in the display (supervisory text) on the activation of the loop input. The panel will be in Supervisory Condition.

From the Loop Inputs Menu (5.8.1), perform the following: After selecting the Loop Input in question by means of the

arrow down/up buttons, press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter. Use the left/right arrow buttons to select Supervisory:Yes or No,

then press Enter. To confirm the setting, press Enter once more.

Page 71: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 71

5.8.3 Connect to Output

This menu allows you to connect a selected loop input to an output. From the Loop Inputs Menu (5.8.1), perform the following: After pressing the Function button for the selected loop input(s),

select Connect to Output (the first menu selection), then press Enter.

A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that

is to be connected to the selected loop input, then press Enter. To confirm the setting, press Enter once more.

5.8.4 Connect to Alarm Zone

This menu allows you to connect a selected loop input to an alarm zone. In this way, the system will be able to activate Fire Alarm Devices (FADs) in the alarm zone. From the Loop Inputs Menu (5.8.1), perform the following: After pressing the Function button for the selected loop input(s),

use the arrow down button to scroll downwards Connect to Alarm Zone (the first menu selection), then press Enter.

A list of all alarm zones will appear in the display. Use the arrow up/down button to select the alarm zone that

is to be connected to the selected loop input, then press Enter. To confirm the setting, press Enter once more.

5.8.5 Disconnect from Output

This menu allows you to disconnect a selected loop input from an existing output. From the Loop Inputs Menu (5.8.1), perform the following: After pressing the Function button for the selected loop input(s),

use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.

In the display you will now see a list of all outputs (if any) that are connected to the selected loop input. To disconnect the selected loop input from an output, use the

arrow down button to select the output, then press Enter. To confirm the setting, press Enter once more.

Page 72: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 72

5.8.6 Disconnect from Alarm Zone

This menu allows you to disconnect a selected loop input from an alarm zone. From the Loop Inputs Menu (5.8.1), perform the following: After pressing the Function button for the selected loop input(s),

use the arrow down button to scroll downwards to Disconnect from Alarm Zone, then press Enter.

In the display you will now see a list of all alarm zones (if any) that are connected to the selected loop input. To disconnect the selected alarm zone from the loop input, use

the arrow down button to select the input, then press Enter. To confirm the setting, press Enter once more.

5.8.7 Show Connected Units

This menu allows you to view all connections that are connected to the selected loop input. From the Loop Inputs Menu (5.8.1), perform the following: After pressing the Function button for the selected loop input(s),

use the arrow down button to scroll downwards to Show Connected Units, then press Enter.

In the display you will now see a list of all connections (if any) that are connected to the selected loop input. Use the arrow up/down button to select a connection, then press

Enter. In the display you will now see the name and unit function of the connections that are connected to the selected loop input.

Page 73: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 73

5.9 Local Inputs

5.9.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Local Inputs, then

press Enter once more. Use the arrow up/down buttons to select the Local Input

that is to be configured. To view or change properties for the selected Local Input, refer

to Configure Properties for a Local Input (chapter 5.9.2).

To access available functions for a selected local input, press the Function button , or use, if necessary, the multiselect feature to select several local inputs by pressing the Select button to mark the local inputs that are to be configured, and then press the Function button .

The following menu selections will appear: o Connect to Output (chapter 5.9.3) o Connect to Alarm Zone (chapter 5.9.4) o Disconnect from Output (chapter 5.9.5) o Disconnect from Alarm Zone (chapter 5.9.6) o Show Connected Units (chapter 5.9.7)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 74: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 74

5.9.2 Configure Properties for a Local Input

The following properties can be changed: the name of the local input

the unit function for a local input supervisory (YES/NO) supervisory text hardware type

From the Local Inputs Menu (5.9.1), perform the following: After selecting the Local Input in question by means of the

arrow down/up buttons, press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter, then use the arrow left/right arrow buttons to select

among the following unit functions: o Day/Night Input:

input used for Day/Night Mode o User Configurable Input:

input to be used for Supervisory function or general output activation

o Morse Input: input that activates onboard Fire Alarm Devices (local outputs) similar to a morse key

o Mute FAD Input: input that turns all FADs off while active

o Reset In Input: input used as an external System Reset (similar to operating the Reset button)

o Silence In Input: input used as an external silence of Fire Alarm Devices (similar to operating the Silence button)

o FARE Feedback: input used as an acknowledge signal from the Fire Alarm receiving station, activates a separate LED on the panel

o Activate All Alarms*: input used to activate all Fire Alarm Devices with a selectable sound pattern

o FWRE: It is possible to use a monitored input for the FWRE function. This requires a special electrical connection using, for example, an optocoupler. Only available if no other input/output is configured as FWRE.

Press Enter, use arrow left/right arrow buttons to select Supervisory YES or NO (where applicable), then press Enter.

Type a Supervisory text (where applicable), then press Enter. State the hardware type, then press Enter. To confirm the setting, press Enter once more. * NOTE: If “Activate All Alarms” is selected, do as follows: press Enter after this selection is highlighted, press the arrow down button several times until you can press Enter to accept and return to the menu level above. Now you must select the same Loop Input again, then press the arrow down button once. The selections “Supervisory” and “Supervisory Text” are no longer shown, and are replaced by the selection “Sound Patterns”. Now you will be able to select one of several sound patterns (see chapter 1.1).

Page 75: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 75

5.9.3 Connect to Output

This menu allows you to connect a selected local input to an output. From the Local Inputs Menu (5.9.1), perform the following: After pressing the Function button for the selected local input(s),

select Connect to Output (the first menu selection), then press Enter.

A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that

is to be connected to the selected local input, then press Enter. To confirm the setting, press Enter once more.

5.9.4 Connect to Alarm Zone

This menu allows you to connect a selected local input to an alarm zone. From the Local Inputs Menu (5.9.1), perform the following: After pressing the Function button for the selected local input(s),

use the arrow down button to scroll downwards to Connect to Alarm Zone, then press Enter.

A list of all available alarm zones will appear in the display. Use the arrow up/down button to select the alarm zone that

is to be connected to the selected local input, then press Enter. To confirm the setting, press Enter once more.

5.9.5 Disconnect from Output

This menu allows you to disconnect a selected local input from an existing output. From the Local Inputs Menu (5.9.1), perform the following: After pressing the Function button for the selected local input(s),

use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.

In the display you will now see a list of all outputs that are connected to the selected local input. To disconnect the selected local input from an output, use the

arrow down button to select the output, then press Enter.

To confirm the setting, press Enter once more.

Page 76: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 76

5.9.6 Disconnect from Alarm Zone

This menu allows you to disconnect a selected local input from an alarm zone. From the Local Inputs Menu (5.9.1), perform the following: After pressing the Function button for the selected local input(s),

use the arrow down button to scroll downwards to Disconnect from Alarm Zone, then press Enter.

In the display you will now see a list of all alarm zones that are connected to the selected local input. To disconnect the selected local input from an alarm zone, use

the arrow down button to select the alarm zone, then press Enter.

To confirm the setting, press Enter once more.

5.9.7 Show Connected Units

This menu allows you to view all connections that are connected to the selected local input. From the Local Input Menu (5.9.1), perform the following: After pressing the Function button for the selected local input(s),

use the arrow down button to scroll downwards to Show Connected Units, then press Enter.

In the display you will now see a list of all connections that are connected to the selected local input. Use the arrow up/down button to select a connection, then press

Enter. In the display you will now see the name and unit function of the connections that are connected to the selected local input.

Page 77: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 77

5.10 Loop I/O Carriers

5.10.1 Description

The loop units BN-303, BN-304, BN-305 and BN-306 are defined as Loop I/O Carriers. A Loop I/O Carrier is a loop unit hosting one or several I/O subunits. The Loop I/O Carrier itself and all the input/outputs are assigned separate loop unit IDs. The Loop I/O Carrier’s dipswitch setting determines which function is assigned to the inputs/outputs. A Loop I/O Carrier may only have one function, which falls into one of the following categories: Point

Inputs with function Prealarm and/or Alarm and/or Fault, all latching, except BN-30x/E Prealarm

Input Inputs are either On or Off Inputs may also give “Supervisory Alarm” (configurable)

Output Outputs are either On or Off

Outputs may also give "Supervisory Alarm" (configurable). Outputs configured to function K, L or M are either Steady On or Off. These units are also using sensor inputs (used for monitoring of the output). The sensor inputs are either On, Off, or Undetermined. The subunits of a Loop I/O carrier are also present in the listing of units of menu commands Points, Loop Inputs and Loop Outputs.

Page 78: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 78

5.10.2 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Loop IO Carriers, then

press Enter once more. Use the arrow up/down buttons to select the Loop IO Carrier

that is to be configured. To view or change properties for the selected Loop IO Carrier,

refer to Configure Properties for a Loop IO Carrier (chapter 5.10.3).

To access available functions for a selected Loop IO Carrier, press the Function button , or use, if necessary, the multiselect feature to select several Loop IO Carriers by pressing the Select button to mark the ones that are to be configured, and then press the Function button .

The following menu selections will appear: o Show All Carrier Units (chapter 5.10.4) o Show Carrier Points (chapter 5.10.5) o Show Carrier Inputs (chapter 5.10.6) o Show Carrier Outputs (chapter 5.10.7)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 79: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 79

5.10.3 Configure Properties for a Loop IO Carrier

The name of the Loop IO Carrier can be changed. From the Loop IO Carriers Menu (chapter 5.10.2), perform the following: After selecting the Loop IO Carrier in question by means of the

arrow down/up buttons, press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter to view the Function/Switch. Press Enter, then type a new Unit Function, or accept the existing

one by pressing the arrow down button. Press Enter, then type another Production Number, or accept the

existing one by pressing the arrow down button. Press Enter, then state the hardware type, or accept the existing

one by pressing the arrow down button. To confirm the setting, press Enter once more.

5.10.4 Show All Carrier Units

This menu allows you to view all Carrier Units. It not possible to change unit properites of the listed points, inputs or outputs.The command only helps the operator to show what type of I/O subunits the selected carrer is hosting. To change properites of the Carrier's subunits, use one of the commands corresponding to the unit type. From the Loop IO Carriers Menu (chapter 5.10.2), perform the following: After pressing the Function button for the selected Loop IO

Carrier(s), use the arrow down button to scroll downwards to Show All Carrier Units, then press Enter.

In the display you will now see a list of all Carrier Units. "Show all Carrier Units" creates a list of units independent of the IO Carrier configuration (i.e. dip switch setting).

Page 80: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 80

5.10.5 Show Carrier Points

This menu allows you to view Carrier Points. From the Loop IO Carriers Menu (chapter 5.10.2), perform the following: After pressing the Function button for the selected Loop IO

Carrier(s), use the arrow down button to scroll downwards to Show Carrier Points, then press Enter.

In the display you will now see a list of all Carrier Points. Use the arrow up/down button to select a Carrier Point, then

press Enter. In the display you will now see the relevant properties.

5.10.6 Show Carrier Inputs

This menu allows you to view Carrier Inputs. From the Loop IO Carriers Menu (chapter 5.10.2), perform the following: After pressing the Function button for the selected Loop IO

Carrier(s), use the arrow down button to scroll downwards to Show Carrier Inputs, then press Enter.

In the display you will now see a list of all Carrier Inputs. Use the arrow up/down button to select a Carrier Input, then

press Enter. In the display you will now see the relevant properties.

Page 81: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 81

5.10.7 Show Carrier Outputs

This menu allows you to view Carrier Outputs. From the Loop IO Carriers Menu (chapter 5.10.2), perform the following: After pressing the Function button for the selected Loop IO

Carrier(s), use the arrow down button to scroll downwards to Show Carrier Outputs, then press Enter.

In the display you will now see a list of all Carrier Outputs. Use the arrow up/down button to select a Carrier Output, then

press Enter. In the display you will now see the relevant properties.

Page 82: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 82

5.11 Mimic Panels

This menu selection is available only if Mimic Panels (Mimic Driver BUR-200) are connected to the system.

5.11.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select a Mimic Panels, then

press Enter once more.

To view or change properties for the selected mimic panel, refer to Configure Properties for a Mimic Panel (chapter 5.11.2), or;

To access available functions for the selected Mimic Panel, press the Function button Continue following the instructions in chapter 5.11.3)

5.11.2 Configure Properties for a Mimic Panel

From the Mimic Panels Menu (5.11.1), perform the following: After selecting the mimic panel in question by means of the

arrow down/up buttons, press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter To confirm the setting, press Enter once more.

Page 83: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 83

5.11.3 Configure Mimic Inputs and Outputs

From the Mimic Panels Menu (5.11.1), perform the following: After pressing the Function button for the selected mimic panel(s),

the command Mimic Boards (Mimic Drivers, BUR-200) will appear, then press Enter.

To access available functions for the Mimic Board, press the Function button

The following alternatives will appear: Mimic Input Units Mimic Output Units Use the arrow down button to select either Mimic Input Units or

Mimic Output Units, then press the Function button once more.

The following commands will appear: Connect to Output Connect to Alarm Zone Disconnect from Output Disconnect from Alarm Zone Show Connected Units

Page 84: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 84

5.12 Activation Groups

Points and general outputs can be assigned to Activation Groups (configurable). An Activation Group can be configured to trigger an output in the event of an alarm. An output unit connected to this output will then initiate a signal to activate external equipment, as for example, doors, sprinkler systems, ventilation valves, horns and fire lights.

5.12.1 Accessing the Menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Activation Groups, then

press Enter once more. Use the arrow up/down buttons to select the Activation Group

that is to be configured. To view or change properties for the selected Activation Group,

refer to Configure Properties for an Activation Group (chapter 5.12.2).

To access available functions for a selected activation group, press the Function button , or use, if necessary, the multiselect feature to select several activation groups by pressing the Select button to mark the activation groups that are to be configured, and then press the Function button .

The following menu selections will appear: o Connect to Output (chapter 5.12.3) o Disconnect from Output (chapter 5.12.4) o Show Member Points (chapter 5.12.5) o Show Connected Units (chapter 5.12.6)

Scroll with the arrow up/down buttons to select the desired menu,

then follow the instructions in the relevant chapter.

Page 85: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 85

5.12.2 Configure Properties for an Activation Group

The following properties can be changed: the name of the local output Activate group on Unit State:

meaning which alarm level the points within this activation group will react to (pre-alarm, alarm, fault and disablement).

Activation Group Dependency: meaning how many points within this activation group that must be in alarm state before actions are initiated (1-5 and All).

From the Activation Groups Menu (5.12.1), perform the following: After selecting the Activation Group in question by means of the

arrow down/up buttons, press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter, then use the left or right arrow button to select the

desired unit state (pre-alarm, alarm, fault and disablement), then press Enter.

Use the left or right arrow button to determine how many points within this activation group that must be in alarm state before actions are initiated (1-5 and All).

To confirm the setting, press Enter once more.

5.12.3 Connect to Output

This menu allows you to connect a selected Activation Group to an output. From the Activation Groups Menu (5.12.1), perform the following: After pressing the Function button for the selected activation

group(s), select Connect to Output (the first menu selection), then press Enter.

A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that

is to be connected to the selected Activation Group, then press Enter.

To confirm the setting, press Enter once more.

Page 86: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 86

5.12.4 Disconnect from Output

This menu allows you to disconnect a selected local input from an existing Activation Group. From the Activation Groups Menu (5.12.1), perform the following: After pressing the Function button for the selected activation

group(s), use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.

In the display you will now see a list of all outputs that are connected to the selected Activation Group. To disconnect the selected local input from an Activation Group,

use the arrow down button to select the output, then press Enter.

To confirm the setting, press Enter once more.

5.12.5 Show Member Points

This menu allows you to view all points that are connected to the selected Activation Group. From the Activation Groups Menu (5.12.1), perform the following: After pressing the Function button for the selected activation

group(s), use the arrow down button to scroll downwards to Show Connections, then press Enter.

In the display you will now see a list of all connections that are connected to the selected Activation Group. Use the arrow up/down button to select a connection, then press

Enter.

Page 87: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 87

5.12.6 Show Connected Units

This menu allows you to view all outputs (or units that will be activated by the group) that are connected to the selected Activation Group. From the Activation Groups Menu (5.12.1), perform the following: After pressing the Function button for the selected activation

group(s), use the arrow down button to scroll downwards to Show Connections, then press Enter.

In the display you will now see a list of all connections that are connected to the selected Activation Group. Use the arrow up/down button to select a connection, then press

Enter. In the display you will now see the name and unit function.

5.13 External Interfaces

5.13.1 Accessing the menu

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select External Interfaces, then

press Enter once more. A list of all related interfaces will appear in the display, including:

o Serial Port Settings (chapter 5.13.2) o TCP/IP Port Settings (chapter 5.13.3) o ESPA (chapter 5.13.4) o MODBUS (5.13.5) o VDR (chapter 5.13.6) o Remote Access (chapter 5.13.7)

Use the arrow up/down buttons to select the External Interface

that is to be configured, then follow the instructions in the relevant chapter.

Page 88: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 88

5.13.2 Serial Port Settings

This menu selection allows you to define all serial port settings. Note that ESPA and Voice Data Recorder (VDR) require the use of the serial port. MODBUS can use either the serial or ethernet port. From the External Interfaces Menu (5.13.1), perform the following: Select Serial Port Settings (the first menu selection), then press

Enter twice. Use the arrow left/right button to select “Bits per second”, then

press Enter. Use the arrow left/right button to select “Word Length”, then

press Enter. Use the arrow left/right button to select “Parity”, then press Enter. Use the arrow left/right button to select “Stop Bits”, then press

Enter. Use the arrow left/right button to select “Hardware Interface”,

then press Enter. To confirm the setting, press Enter once more.

TCP/IP Port Settings

This menu selection allows you to define all Ethernet(TCP/IP) port settings. MODBUS can use either the serial or ethernet port. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select TCP/IP Port Settings, then

press Enter twice. Use the arrow left/right button to select “Own IP Address”, then

press Enter. Use the arrow left/right button to select “Gateway IP Address”,

then press Enter. Use the arrow left/right button to select “Subnet Mask”, then

press Enter. To confirm the setting, press Enter once more.

Page 89: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 89

5.13.4 ESPA

This menu selection includes the following submenus: Configure Settings (chapter 5.13.4.1) Configure Events (chapter 5.13.4.2) Configure Receivers (chapter 5.13.4.3) Send Test Event (chapter 5.13.4.4)

Note that ESPA always requires the use of the serial port.

5.13.4.1 Configure Settings

This menu selection allows you to configure ESPA settings. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select ESPA, then press Enter. Select Configure Settings (the uppermost menu), then press

Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter, use the arrow left/right buttons to select the port

(not in use or serial), then press Enter. Use the arrow left/right buttons to select whether you want to

restore factory settings or not (No/Yes), then press Enter. o If No is selected, the next menu selection will be shown and

all following values must be selected. o If Yes is selected, default values will be used.

Use the arrow left/right buttons to select the display size (default

128), then press Enter. Use the arrow left/right buttons to select the line length

(default 12), then press Enter. Use the arrow left/right buttons to select the alphabet type (7 bits,

8 bits, or GSM), then press Enter. Use the arrow left/right buttons to select the fault detail (Yes/No),

then press Enter. Use the arrow left/right buttons to select whether you want to

prepare for a startup message, then press Enter. To confirm the settings, press Enter once more.

Page 90: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 90

5.13.4.2 Configure Events

This menu selection allows you to configure event properties. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select ESPA, then press Enter. Use the arrow down button to select Configure Events, then

press Enter and you can define a text, the number of beeps and transmissions for the following events: o Alarm o Prealarm o Fault o Supervisory o Startup o Test

Select Alarm (the uppermost menu), then press Enter twice. Type a freely chosen text, then press Enter. Enter the number of beeps (refer to the paging system’s

specifications), then press Enter. Enter the number of transmissions (normally 2 transmissions for

normal calls and 3 transmissions for alarms), then press Enter. To confirm the settings, press Enter once more.

Configure the properties for all other events as described above.

5.13.4.3 Configure Receivers

This menu selection allows you to configure user properties. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select ESPA, then press Enter. Use the arrow down button to select Configure Receivers, then

press Enter. You can now define the properties for 10 differenet users. Select User 1 (the uppermost selection), then press Enter twice. Enter the user name, then press Enter. Enter the receiver number, then press Enter. Use the left and right arrow button to select the events that are to

be displayed, including one of the following selections: o no events o all events o alarm o alarm + prealarm o alarm + prealarm + supervisory

To confirm the settings, press Enter once more.

Configure the properties for all other users as described above.

Page 91: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 91

5.13.4.4 Send Test Event

This command is used for test purposes. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select ESPA, then press Enter. Use the arrow down button to select Send Test Event, then press

Enter. The following message will appear: “Text Message Transmitted”.

o A text message is transmitted to verify that there is a proper communication between Autroprime and the paging system.

Page 92: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 92

5.13.5 MODBUS

This menu selection includes the following submenus: Configure Settings (chapter 5.13.5.1) Configure Status Registers (chapter 5.13.5.2) Configure Command Registers (chapter 5.13.5.3) Set Testbit to 0 (chapter 5.13.5.4) Set Testbit to 1 (chapter 5.13.5.5) Assign Unique MODBUS Indexes (chapter 5.13.5.6)

MODBUS can use either the serial or ethernet port.

5.13.5.1 Configure Settings

This menu selection allows you to configure MODBUS settings. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select MODBUS, then press Enter. Select Configure Settings, then press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter, use the arrow left/right buttons to select the port

(not in use, serial or TCP/IP), then press Enter. If Ethernet is selected, use the arrow left/right buttons to select

the TCP/IP Address, then press Enter (not in use when serial is selected).

If Ethernet is selected, use the arrow left/right buttons to select the Port Number, then press Enter (not in use when serial is selected).

Use the arrow left/right buttons to select the mode (slave or master), then press Enter.

Use the arrow left/right buttons to select whether you want to restore factory settings or not (Yes/No), then press Enter.

Select the default slave 1, or use the alphanumeric keypad to type another slave address, then press Enter.

Select the default slave ID (12) (normally not changed), or use the alphanumeric keypad to type another slave ID, then press Enter.Use the arrow left/right buttons to select Handshake (Yes/No), then press Enter.

Use the arrow left/right buttons to select Report Fault (Yes/No), then press Enter.

Select the Fault Timer (default 10 seconds), or use the alphanumeric keypad to type another Fault Timer, then press Enter.

To confirm the settings, press Enter once more.

Page 93: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 93

5.13.5.2 Configure Status Registers

This menu selection allows you to configure Status Registers. The Status Register is either the Input Register or the Holding Register. This depends on whether the Modbus mode is configured as Slave or Master. Modbus Master - Holding Register: The Start Address for the Status Register is in the range 40001 to 45000. Modbus Slave – Input Register: The Start Address for the Status Register is in the range 30001 to 35000. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Configure Status Registers,

then press Enter twice. Type the Start Address, then press Enter. Type the Number of Registers, then press Enter. To confirm the settings, press Enter once more.

5.13.5.3 Configure Command Registers

This menu selection allows you to configure command registers. The Command Register is identical to the Holding Register. Only the Start Address (first Register Number) is specified, and the Command Register consists of 3 Registers where only the the Start Address (first Register Number) is defined. Note that when using Modbus Master, make sure that the range for the Command Register and Status Register does not overlap. See example below.

Register Type Register Number Range of Command Register

40001 40002 40003

Range of Status Register

40004 40xxx 40004 + number of registers -1

Page 94: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 94

From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Configure Command

Registers, then press Enter twice. Type the Start Address, then press Enter. To confirm the setting, press Enter once more.

5.13.5.4 Set Testbit to 0

This command is used for test purposes. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Set Testbit to 0, then press

Enter. The following message will appear: “Test finished”.

Page 95: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 95

5.13.5.5 Set Testbit to 1

This command is used for test purposes. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Set Testbit to 1, then press

Enter. The following message will appear: “Test message transmitted”.

5.13.5.6 Assign Unique MODBUS Indexes

This command is used for test purposes. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Assign Unique MODBUS

Indexes, then press Enter. To confirm the setting, press Enter once more.

Page 96: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 96

5.13.6 VDR

This menu selection allows you to define all settings for the Voyage Data Recorder (VDR), including the following submenus: Configure Settings (chapter 5.13.6.1) Send Test Event (chapter 5.13.6.2) Note that the Voyage Data Recorder (VDR) requires the use of the serial port.

5.13.6.1 Configure Settings

This menu selection allows you to configure VDR settings. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select VDR, then press Enter. Select Configure Settings (the uppermost selection), then press

Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter, use the arrow left/right buttons to select the port

(not in use or serial), then press Enter. Use the arrow left/right buttons to select whether you want to

restore factory settings or not (Yes/No), then press Enter. Use the arrow left/right buttons to select Log Volume Mini

(Yes/No), then press Enter. If Yes is selected, the amount of information which is sent to the VDR will be limited; only information on alarms and door control will be sent.

Use the arrow left/right buttons to select Alive Time (default 4 minutes), then press Enter. Alive Time determines how often a message is sent to the VDR to ensure that there is a proper communication between the system and the VDR.

Use the arrow left/right buttons to select Update Time (default 120 minutes), then press Enter. Update Time determines how often the VDR receives a full update of all fire alarms and fault statuses.

To confirm the settings, press Enter once more.

5.13.6.2 Send Test Event

This command is used for test purposes. From the External Interfaces Menu (5.13.1), perform the following: Use the arrow down button to select VDR, then press Enter. Use the arrow down button to select Send Test Event, then press

Enter The following message will appear: “Test message transmitted”.

Page 97: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 97

5.13.7 Remote Access

Autroprime can be configured to act as a TCP/IP network node, allowing Autroprime to communicate with WWW based applications for monitoring and control (chapter 5.13.7.1) or, for example, an AutroMaster Integrated Safety and Emergency Management System (chapter 5.13.7.2, 5.13.7.3 and 5.13.7.4).

5.13.7.1 Server and Web Access

Server and Web Access must be configured in order to allow external WWW clients access Autroprime. From the External Interfaces Menu (5.13.1), perform the following: Select Remote Access, then press Enter twice. Select Server and Web Access, then press Enter. Use the arrow left/right button to select Server Access Level (Off,

Monitoring or Monitoring and Control), then press Enter. Monitoring is to be selected if you want the external system to

only receive information from Autroprime. Monitoring and Control is to be selected if you want

Autroprime to both receive information from and transmit information to an external system (for example AutroMaster).

Use the arrow left/right button to select Web Application Access Level (Off, Monitoring or Monitoring and Control), then press Enter. Monitoring is to be selected if you want the Web application

to only receive information from Autroprime. Monitoring and Control is to be selected if you want

Autroprime to both receive information from and transmit information to a Web Application.

Use the arrow left/right button to select Select Access Time Unlimited (NO or YES) If YES is selected, the Client or Web application will have

continuous access. If NO is selected, the Autroprime system will close the

communication with a PC Web-application or Client after a time span given by Time Limitation.

Select Time Limitation (hours) if applicable. Press Enter. To confirm, press Enter once more.

Page 98: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 98

5.13.7.2 User Management

Autroprime can be configured as a Client being able to access and communicate with a server-based application, for example, AutroMaster ISEMS. The required configuration is performed in the User Management menu (plus the Clients menu, described in next chapter). From the External Interfaces Menu (5.13.1), perform the following: Select Remote Access, then press Enter. Use the arrow down button to select User Management, then

press Enter twice. Press Enter, then type a User Name, then press Enter Type a Password (minimum 8 characters), then press Enter To confirm, press Enter once more.

5.13.7.3 Clients

Autroprime can be configured as a Client being able to access and communicate with a server-based application, for example, AutroMaster ISEMS. The required configuration is performed in the Clients menu (plus the User Management menu described in previous chapter). From the External Interfaces Menu (5.13.1), perform the following: Select Remote Access, then press Enter.. Use the arrow down button to select Clients, then press Enter

(maximum 4 Clients can be defined) Use the arrow down button to select one of the 4 Clients, then

press Enter twice. Type a Client name, then press Enter. Type the User, then press Enter. Use the arrow left/right button to select Account Status, then

press Enter. Select Active to activate this client. Select Suspended to deactivate this client.

Use the arrow left/right button to select Client Access Level (Off, Monitoring or Monitoring and Control), then press Enter. Monitoring is to be selected if you want Autroprime to only

receive information from the Client. Monitoring and Control is to be selected if you want

Autroprime to both receive information from and transmit information to the Client.

Use the arrow left/right button to set the External Server Address (for example,10.62.63.79:10002), then press Enter.

To confirm, press Enter once more.

Page 99: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 99

5.13.7.4 Client Proxy Server

If the network is using a Proxy Server, the Client Proxy Server must be defined in the following menu: From the External Interfaces Menu (5.13.1), perform the following: Select Remote Access, then press Enter. Use the arrow down button to select Client Proxy Server, then

press Enter twice. If a proxy server is to be connected, type the Proxy Server

Address (for example, 10.64.1.46:8080), then press Enter. To confirm, press Enter once more.

Page 100: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 100

5.14 Detection Loops

This menu selection allows you to: define the name of a detection loop override the system calculated preset current set a different limit for the maximum possible loop current for a

selected detection loop. The following different default settings are possible: 100mA, 150mA, 200mA, 250mA, 300mA, 350mA and 400mA.

Note that the high current settings 300mA, 350mA and 400mA are only available with BSA-200A or BSD-200A (revision A required). Due to limitations of the power supply, the system will not allow configuration of a total loop current exceeding 1200 mA. When the system is powered up, or the loop driver is enabled, the system will automatically calculate and set a current limit which is optimized for each loop individually, depending on the number and type of loop units. If the operator has configured a maximum loop current value being higher than the system preset value, this value will not be changed by the system. In some cases the system may allow the operator to override the system preset loop current and decrease the maximum loop current to a value being 50 mA lower the preset loop current. This should only be used if the system reports a fault on the loop resistance being too high. Overriding and decreasing the preset loop current with 50 mA may be sufficient to avoid this fault. The maximum power consumption is determined by the following

parameters: o the number of loop units o the loop unit type, i.e. the specified maximum current for the

loop unit type From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Detection Loops, then

press Enter. Use the arrow up/down buttons to select the Detection Loop

that is to be configured, then press Enter twice. Type a new Name, or accept the existing one by pressing

the arrow down button. Press Enter, use the arrow left/right button to select (if allowed by

the system) if the preset loop current shall be overrided, then press Enter.

Press Enter, use the arrow left/right button to set the limit for maximum loop current, then press Enter.

To confirm, press Enter once more.

Page 101: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Configuration

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 101

5.15 Operator Panels

This menu selection allows you to define the name and panel type for a selected Operator Panel (including all Autroprime panel types). From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to select Operator Panels, then

press Enter once more. Use the arrow up/down buttons to select the Operator Panel

that is to be configured, then press Enter twice. Type a new Name, or accept the existing one by pressing the

arrow down button. Press Enter, then use the arrow left/right button to type the panel

type.

Page 102: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Test

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 102

6. Unit Test

6.1 Menu Selections - Overview

The Unit Test menu includes the following menu selections: Detection Zones (chapter 6.2) Alarm Zones (chapter 6.3) Fire Alarm Devices (chapter 6.4) Loop Outputs (chapter 6.5) Local Outputs (chapter 6.6) Mimic Panels (chapter 6.7)

6.2 Testing Detection Zones

To be able to manually test points (detectors or manual call points) without automatic actioning of Fire Protection Equipment (FPE), Fire Alarm Routing Equipment (FARE) or Fire Alarm Devices (FAD), selected detection zones, can be set to test mode. In this mode, any point connected to the selected detection zone(s) can be tested individually (with, for example, test gas) without automatic actioning (i.e. without audible indication) from sounders, bells, etc.

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Test, then press Enter. Press Enter once more to select Detection Zones (the uppermost

selection). Use the arrow button to select the detection zone that is to be

tested. Use, if necessary, the multiselect feature to select several detection zones.

(To view detailed information for one selected detection zone before testing, you can press Enter, then return to the previous level by pressing the Cancel button ). Press the Function button To start the test, press Enter. Press Enter once more to confirm.

To stop the test, use the arrow up/down button to select the

detection zone(s) that is set to test mode, press the Function button , use the arrow down button to select Stop Test, then press Enter twice.

Page 103: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Test

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 103

6.3 Testing Alarm Zones

This manual test activates all Fire Alarm Devices (FAD) in a selected alarm zone (with audible indication). The duration of the signal and the interval between each signal is 1 second ON and 7 seconds OFF. The test signal is given the lowest priority. In the event of an alarm, the alarm signal will thus override the test signal.

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Test, then press Enter. Scroll down to Alarm Zone, then press Enter. Use the arrow button to select the Alarm Zone that

is to be tested. Use, if necessary, the multiselect feature to select several alarm zones.

(To view detailed information for one selected alarm zone before testing, you can press Enter, then return to the previous level by pressing the Cancel button ). Press the Function button To start the test, press Enter. Press Enter once more to confirm.

To stop the test, use the arrow up/down button to select the

alarm zone(s) that is set to test mode, press the Function button , use the arrow down button to select Stop Test, then press

Enter twice.

Page 104: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Test

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 104

6.4 Testing Fire Alarm Devices

This chapter describes how to test each Fire Alarm Device (FADs) individually.

When the test is initiated for a selected Fire Alarm Device (FAD), a test signal will be sent to this FAD. The duration of the signal and the interval between each signal is 1 second ON and 7 seconds OFF. The test signal is given the lowest priority. In the event of an alarm, the alarm signal will thus override the test signal.

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Test, then press Enter. Scroll down to Fire Alarm Devices, then press Enter. Use the arrow button to select the Fire Alarm Device (FAD) that

is to be tested. (To view detailed information for the selected Fire Alarm Device before testing, you can press Enter, then return to the previous level by pressing the Cancel button ). Press the Function button To start the test, press Enter. Press Enter once more to confirm. To stop the test, use the arrow up/down button to select the Fire

Alarm Device that is set to test mode, press the Function button , use the arrow down button to select Stop Test, then press

Enter twice.

Page 105: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Test

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 105

6.5 Testing Loop Outputs

This chapter describes how to test each Loop Outputs individually. When the test is initiated for a selected loop output, a test signal will be sent to this output. From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Test, then press Enter. Scroll down to Loop Outputs, then press Enter. Use the arrow button to select the Loop Output that

is to be tested. (To view detailed information for the selected loop output before testing, you can press Enter, then return to the previous level by pressing the Cancel button ). Press the Function button To start the test, press Enter. Press Enter once more to confirm.

To stop the test, use the arrow up/down button to select the loop

output that is set to test mode, press the Function button , use the arrow down button to select Stop Test, then press Enter twice.

NOTE:

Before this test is performed, make sure that all extinguishers (or other similar equipment) that are to be tested are disconnected. During the test, use a measuring instrument to measure the output on the Fire Protection Equipment that is to be tested.

Page 106: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Test

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 106

6.6 Testing Local Outputs

This chapter describes how to test each Local Output individually. When the test is initiated for a selected local output, a test signal will be sent to this output. From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Test, then press Enter. Scroll down to Local Outputs, then press Enter. Use the arrow button to select the Local Output that

is to be tested. (To view detailed information for the selected local output before testing, you can press Enter, then return to the previous level by pressing the Cancel button ). Press the Function button To start the test, press Enter. Press Enter once more to confirm.

To stop the test, use the arrow up/down button to select the local

output that is set to test mode, press the Function button , use the arrow down button to select Stop Test, then press Enter twice.

NOTE:

Before this test is performed, make sure that all extinguishers (or other similar equipment) that are to be tested are disconnected. During the test, use a measuring instrument to measure the output on the Fire Protection Equipment that is to be tested.

Page 107: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Unit Test

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 107

6.7 Testing Mimic Panels

This chapter describes how to test each mimic panel individually. When the test is initiated for a selected mimic panel, a test signal will be sent to this panel. From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Test, then press Enter. Scroll down to Mimic Panels, then press Enter. Use the arrow button to select the mimic panel that

is to be tested. Note that mimic panels will appear only if mimic panels are physically connected to the system. If not, the message “No Units Found” will appear in the display. Press the Function button To start the test, press Enter. Press Enter once more to confirm.

To stop the test, use the arrow up/down button to select the

mimic panel that is set to test mode, press the Function button , use the arrow down button to select Stop Test, then press

Enter twice.

Page 108: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Topology

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 108

7. System Topology

7.1 Menu Selections - Overview

The System Topology menu includes the following menu selections: Show Topology Show All Faults Clear Loop Config. – Restart System Deactivate/Activate

7.2 Show Properties

To view detailed information on the properties for a selected detection loop or the panel bus, follow the instructions below. From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

System Topology, then press Enter. A list appears, including all loops and the panel bus.

Use the arrow button to select the panel bus or a detection loop you want to view.

To view the properties, press Enter. The following properties will appear in the display. Detection Loop

o The name of the detection loop o The limit for maximum loop current o The measured loop current o The loop resistance – wire o The loop resistance + wire

Panel bus: o The name of the panel bus o The panel type (for example, BS-200)

Page 109: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Topology

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 109

7.3 Show Topology

This menu provides detailed information on the topology of the panel bus and a selected loop. From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

System Topology, then press Enter. A list appears, including all loops and the panel bus.

Use the arrow button to select the panel bus or the loop you want to view.

Press the Function button Select Show Topology (the uppermost selection), then press

Enter. The topology details, including Position, Type and Info, will appear in the display. It is possible to toggle betweent the tagname and the production number by using the left and right arrow buttons.

7.4 Show All Faults

This menu selection allows you to view detailed fault information related to the panel bus and a selected loop. From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

System Topology, then press Enter. A list appears, including all loops and the panel bus.

Use the arrow button to select the panel bus or the loop you want to view.

Press the Function button Use the arrow down button to select Show All Faults, then press

Enter. All faults related to the panel bus, or the selected loop in the entire system will appear in the display.

Page 110: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Topology

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 110

7.5 Clear Loop Config. – Restart System

This command allows you to delete all points on a selected detection loop.

The command is useful in the following cases: When major changes are to be done on an existing detection

loop, i.e. a large amount of points on a detection loop are to be removed and others are to be added. The advantage: you do not have to accept points - one by one – that are removed before the new configuration is saved. Fault messages will not appear after system restart.

When the configuration of a detection loop is not completed by the end of the day, and the service technician intends to complete the configuration of this detection loop the next day, executing this command will save the configuration and the detection loop in question will be fully functional and resume normal operation after system restart. The technician can complete the configuration the next day without dealing with unnecessary fault messages.

Expanding a system:

If a loop is to be moved from one panel to another, all topology information for this loop on the replaced panel will be deleted.

Note that the Clear Loop Config. – Restart System command will not affect the detectors’ Performance Class settings. For example, an optical detector that has been set to “Industrial” will still have this setting after the command is executed. From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

System Topology, then press Enter. A list appears, including all loops and the panel bus.

Use the arrow button to select the panel bus or the loop. Press the Function button Use the arrow down button to select Clear Loop Config. –

Restart System, then press Enter. The following message will appear: “The configuration related to any unit on this loop will be deleted and the loop will be completely restarted.” Use the left arrow button to select Accept, then press Enter.

NOTE: All existing configuration on the selected detection loop will be deleted.

Page 111: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

System Topology

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 111

7.6 Deactivate

This menu selection allows you to deactivate a selected detection loop. If for example, a detection loop is not in use for any reason, this detection loop can be deactivated.

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

System Topology, then press Enter. A list appears, including all loops and the panel bus.

Use the arrow button to select the detection loop you want to run this command for.

Press the Function button Use the arrow buttons to select Deactivate, then press Enter. The selected detection loop will be deactivated (until it is manually activated by running the Activate command).

7.7 Activate

This menu selection allows you to activate a selected detection loop or the panel bus which is deactivated.

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

System Topology, then press Enter. A list appears, including all loops and the panel bus.

Use the arrow button to select the panel bus or the detection loop you want to run this command for.

Press the Function button Use the arrow buttons to select Activate, then press Enter. The selected detection zone will be activated.

Note that deactivation of a loop is only allowed when the loop does not contain any loop units.

Note that activation of a loop is only allowed when the loop does not contain any loop units.

Page 112: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Export and Import

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 112

8. Export and Import

E-1

676

This product contains static-sensitive devices. Please avoid any electrostatic discharge during these operations.

8.1 Menu Selections - Overview

The Export and Import menu includes the following menu selections: Export Log Select Configuration & Restart System Backup Current Configuration Export Configuration Import Configuration

8.2 USB Output

By means of a USB memory stick, configuration data can be exported or imported. The USB output J12 is used for this purpose. It is easily accessible from the inside of the front panel door.

We recommend that the USB memory stick that is to be used contains Autronica-related files only.

Note that the maximum load on the USB port is 100mA.

The USB port is provided with a resettable fuse.

USB output J12

Page 113: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Export and Import

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 113

8.3 Export Log

To be able to analyse system behaviour for service and maintenance purposes, a number of events are recorded, including: The date, time and identity of detection zones entering an alarm

state. The date, time and identity of an individual component, a group, a

zone, etc. issuing a fault warning signal. The date, time and identity of an individual component, a group, a

zone, etc. entering the disabled/enabled state. The date, time of all user operations. The date, time of all manually initiated tests. The Export Log command allows you to export the following two files to a USB device (memory stick): ExportLogRaw.txt (a coded file for internal use only)

ExportLog.txt (a file including all events written in clear text)

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Export and Import, then press Enter. Select Export Log (the uppermost selection), then press Enter. To execute the command, use the left arrow button to select

Accept, then press Enter. The log will be exported to the USB device. To read the ExportLog.txt file, connect the USB device to a

computer, then open the ExportLog.txt file in an editor, for example, WordPad.

NOTE:

When exporting log files and configuration files, existing log files and configuration files on the USB memory stick will be overwritten.

Page 114: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Export and Import

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 114

8.4 Select Configuration & Restart System

This command allows you to restart the system by using one of the configuration files available (current configuration, imported configuration or backup configuration). From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Export and Import, then press Enter. Press the arrow down button to select Select Configuration &

Restart System, then press Enter twice. The following message will appear: ” Restart the system by using one of the configurations available”.

If several configurations are available, use the left/right arrow

buttons to select the configuration (Current Configuration, Imported Configuration or Backup Configuration).

Press Enter twice. To execute the command, press Enter once more.

8.5 Backup Current Configuration

This command allows you to take an internal backup of the current configuration.

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Export and Import, then press Enter. Press the arrow down button to select Backup Current

Configuration, then press Enter. The following message will appear: ” Create backup of the current configuration. Please save the configuration if configuration has been changed”. To execute the command, use the left arrow button to select

Accept, then press Enter.

Make sure to save all recent configuration changes (using the Save Configuration command in the System Settings menu, chapter 3.2) before executing the Backup Current Configuration command.

Page 115: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Export and Import

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 115

8.6 Export Configuration

This command allows you to export configuration files from the system to a USB memory stick.

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Export and Import, then press Enter. Press the arrow down button to select Export Configuration, then

press Enter. The following message will appear: ” Copy the last saved configuration file to a USB device.” To execute the command, use the left arrow button to select

Accept, then press Enter. A Configuration Report is generated and written to the USB memory stick when the Export Configuration command is run. The report is written to the file “Config Report.csv” and can be opened in Excel. The report provides a complete overview of the current configuration, including any configuration changes that may not have been saved.

Make sure to save all recent configuration changes (using the Save Configuration command in the System Settings menu, chapter 3.2) before executing the Export Configuration command. NOTE: When exporting log files and configuration files, existing log files and configuration files on the USB memory stick will be overwritten.

Page 116: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 116

8.7 Import Configuration

This command allows you to import configuration files from a USB memory stick.

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Export and Import, then press Enter. Press the arrow down button to select Import Configuration, then

press Enter. The following message will appear: ”Import configuration files from the USB device The imported configuration will not have any impact on the running system. To use the imported configuration, please restart the system.” To execute the command, press the left arrow button to select

Accept, then press Enter.

The imported configuration will have no impact on the running system. To use the imported configuration the system must be restarted (Restart System, chapter 8.4.).

Page 117: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 117

9. Configuration Examples

9.1 Before you Start

Autroprime is provided to the user in a pre-configured state, in this state the panel is set to recognize detectors and other loop units connected to the detection loops and the availability of routing equipment, etc. To simplify the understanding of the configuration principles, the first example (1) deals with 1 loop and 8 points only. The default setup provides the following: Loop Units/Points: All loop units, including; detectors, manual

call points (points), electronic sounders and I/O units, are automatically assigned addresses (sequencially numbered) starting with address A1001, followed by address A1002, A1003 and so on. The addresses are used as names in the configuration menu.

Detection Zones and Alarm Zones: By default the system has one Detection Zone and one Alarm Zone.

Activation of Outputs: A point in alarm will activate all Fire Alarm Devices and Fire Alarm Routing Equipment.

Detection Zone Type: All detection zones are defined as Immediate Action Detection Zones.

Based on this default configuration, a site-specific configuration can be carried out. The examples (example 1 and 2) in this chapter deals with a site-specific configuration of a typical medium-sized installation.

Page 118: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 118

9.2 Example 1: Basic Configuration Example

In the example, a building is divided into three different sections with a total of 4 detection zones. Detection Zones:

o Detection Zone 1 (green) o Detection Zone 2 (blue) o Detection Zone 3 (yellow) o Detection Zone 4 (purple)

All detection zones are defined as Immediate Action Detection Zones.

All loop units are connected to one detection loop. The system consist of 8 loop units (4 detectors, 1 manual

callpoint and 3 electronic sounders) The system has one Alarm Zone (red) One output is used for Fire Alarm Routing Equipment One output is used for Fault Warning Routing Equipment One output is used for Fire Alarm Devices (sounder) A sounder (FAD) is located outside at the front door. A point in alarm is to be configured to activate all Fire Alarm

Devices. A point in alarm is to be configured to activate all Fire Alarm

Routing Equipment.

Page 119: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 119

SALES OFFICEDetection Zone 2

CORRIDOR SOUTHDetection Zone 3

BD-300 BH-300

BBR-200

BH-320

Output to F

AR

EO

utput to FW

RE

Output to F

ire Alarm

Device (F

AD

)

Autronica

Sounder

CANTEENDetection Zone 1

A1002

A1004

A1005

A1001

Alarm Zone (indicated in red)

BBR-200

A1003

BBR-200

A1006

A1007

BH-300

BF-300PRESS H ERETRYKK HER

K NUS G LA SSET

B REAK G LASS

A1008

Detection Zone 4

SALES OFFICEDetection Zone 2

CORRIDOR SOUTHDetection Zone 3

BD-300 BH-300

BBR-200

BH-320

Output to F

AR

EO

utput to FW

RE

Output to F

ire Alarm

Device (F

AD

)

Autronica

Sounder

CANTEENDetection Zone 1

A1002

A1004

A1005

A1001

Alarm Zone (indicated in red)

BBR-200

A1003

BBR-200

A1006

A1007

BH-300

BF-300PRESS H ERETRYKK HER

K NUS G LA SSET

B REAK G LASS

A1008

Detection Zone 4

Page 120: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 120

9.2.1 Site information – Excel Sheet

The site information Excel sheet contains information on the site-specific configuration and it forms the basis for the panel configuration.

9.2.2 Buttons

Arrow Up/Down Arrow Left/Right

Select Cancel / Back

Function

Alpha- numeric Keypad

Enter

Page 121: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 121

9.2.3 Initial Startup – Default Configuration

When the power is turned on, the green Power indicator lights up with a steady green light, and an initialization starts.

When the initialization procedure is completed, the panel will recognize detectors and other loop units and the system topology is shown in the display. Turn the key clockwise. To enter Service Mode, press and hold down the Enter button for

a few seconds. Use the Arrow down button to select Service, then press Enter

(the Service Menu will appear in the display).

9.2.4 Save Configuration / Restart System

From the Service Menu, perform the following: Select System Settings (the uppermost menu selection which is

highlighted), then press Enter. Select Save Configuration (the uppermost menu selection which

is highlighted), then press Enter. Type the Site Name, then press Enter. Type the Operator Name, then press Enter. Type the Site Configuration Version, then press Enter. Type a Description, then press Enter. Press Enter once more to confirm. Use the Arrow down button to select Restart System. Use the left Arrow button to select Accept, then press Enter.

The message “System is now shutting down…” will appear, and the system will reboot automatically.

Before you start the site-specific configuration, two commands should be executed; Save Configuration and Restart System. In this way, prior to the site-specific configuration, you can verify that the system works properly using the default configuration. Furthermore, you will have a fully operational system while you are performing the site-specific configuration.

When the system reboot is completed, you can enter Service Mode, and start the first step of the site-specific configuration.

Page 122: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 122

9.2.5 Site-specific Configuration – Example 1

Step 1: Create Detection Zones and connect the points (loop units) to the Detection Zones (5.4.3) Note that the electronic sounders (Fire Alarm Devices, FADs) in this example are not to be connected to detection zones.

Add a site-specific name to each address (point) if needed (see chapter 9.2.7). For example, you can add CANTEEN to address A1001 (the name will appear as A1001 CANTEEN in the display if an event occurs). (5.4.2).

Step 2: Connect the new detection zones to the alarm zone (5.2.3) The new Detection Zones, DZ1, DZ2, DZ3 and DZ4 have to be connected to the Alarm Zone (Default Alarm Zone).

Step 3: Save the configuration and restart the system (3.2 and 3.3) When the site-specific configuration is completed, you have to save the new configuration and restart the system (refer to chapter 9.2.4).

In this example, only one Alarm Zone is defined. By default, all

Fire Alarm Devices are connected to the one default Alarm Zone. Therefore, no configuration is required (you do not have to connect Fire Alarm Devices to the Alarm Zone). Refer to chapter 5.5.3

In this example, all points activate outputs to Fire Alarm Devices

(FAD), Fault Warning Routing Equipment (FWRE) and Fire Alarm Routing Equipment (FARE). As this specific functionality already is provided by the default configuration, no configuration is required. Refer to chapter 5.2.4, 5.4.4 and 5.6.

Step 1, Step 2 and Step 3 have to be carried out in this example.

Page 123: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 123

9.2.6 Step 1: Create Detection Zones and Connect Points

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to scroll downwards to Points.

Use the multiselect feature* to select all points that are to be

connected to the same detection zone, for example starting with Detection Zone 1, including: A1001 A1002 *To select both points at the same time, press and hold down the Select button to mark the first point A1001, then while still holding down the Select button, press the Arrow Down button to select the second point (A1002).

Press the Function button Press Enter to select the uppermost menu selection Move to

Detection Zone. Press Enter to select the uppermost menu selection Create New

Detection Zone. Press Enter, then use the alphanumeric keypad to enter the name

of the detection zone; Detection Zone 1 (type the first letter, use the right arrow button, then type the next one, and so on).

When the name is completed, press Enter. Press Enter to select Immediate. The default Alarm Organization

is Immediate Action (detection zone type). Press Enter to confirm the settings (Accept). Repeat this procedure for the points that are to be connected to

Detection Zone 2 (including point A1004), Detection Zone 3 (including point A1007) and Detection Zone 4 (including the manual callpoint A1008).

Page 124: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 124

9.2.7 Add a Site-specific Name to each Point (if needed)

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to scroll downwards to Points.

Select the first point A1001 that is to be added a site-specific

name, then press Enter twice. Type space and the name CANTEEN after the address,

for example, A1001 CANTEEN, then press Enter.

As all other properties use the default settings in this example, simply press Enter or the arrow down button a number of times (depending on the type of detector) to accept the settings.

Press Enter to confirm the settings (Accept). Use the arrow down button to select the next point that is to be

added a site-specific name. Repeat the procedure for each point according to the list below: A1001 CANTEEN A1002 CANTEEN A1003 CANTEEN A1004 SALES OFFICE A1005 SALES OFFICE A1006 CORRIDOR SOUTH A1007 CORRIDOR SOUTH A1008 Manual Call Point CORRIDOR SOUTH

Page 125: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 125

9.2.8 Step 2: Connect the new Detection Zones to the Alarm Zone

From the Points menu, perform the following: Press the back/cancel button to move back one level to Unit

Configuration. Use the arrow up button to scroll upwards to Detection Zones,

then press Enter. As all Detection Zones (DZ1, DZ2, DZ3 and DZ4) are to be

connected to the Alarm Zone in this example, use the multiselect feature* to select all four Detection Zones. * To select all four Detection Zones at the same time, press and hold down the Select button to mark the first Detection Zone DZ1, then while still holding down the Select button, press the Arrow Down button to select the second, third and fourth (DZ2, DZ3 and DZ4).

Press the Function button Press Enter to select the uppermost menu selection Connect to

Alarm Zone. Press Enter to connect all four Detection Zones to this

Alarm Zone. Press Enter to confirm the settings (Accept).

9.2.9 Step 3: Save Configuration / Restart System

Refer to chapter 9.2.4.

Page 126: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 126

9.3 Example 2: Configuration with several alarm zones and control functions

The example below is based on Example 1 (Basic Configuration Example). A second building is added to this configuration. Detection Loop B covers the fire detection for this building (storage and workshop). Note that the configuration written in italic is already done in Example 1. The configuration now includes the following detection/alarm zones: 4 Detection Zones. Detection Zone 1, 2, 3 and 4 (already

configured in Example 1). 3 new Detection Zones, Detection Zone 5 (white), 6 (red) and 7

(grey) in the second building. 2 Alarm Zones (Alarm Zone 1 and 2), one assigned to each

building. Both zones are defined as Neighbour Alarm Zones. 1 Parent Alarm Zone. The manual call point in Detection Zone 6 is

connected to this top-level Alarm Zone. The following functionality is to be configured: One output is used for Fire Alarm Routing Equipment (relay

output 1, already configured in Example 1). One output is used for Fault Warning Routing Equipment (relay

output 2, already configured in Example 1). One output is used for the sounder outside the main building

(Alarm Zone 1). One output is used for the sounder outside the Storage/Workshop

building (Alarm Zone 2) One output is used for the ventilation control in the

Storage/Workshop building (open collector output 1). One output is used for door control in the main building (Sales

Office/Canteen/Corridor South, open collector output 2). Points in alarm in Detection Zone 1, 2, 3 and 4 are to be

configured to activate Fire Alarm Devices belonging to Alarm Zone 1 and to activate a Neighbour alarm in Alarm Zone 2.

Points in alarm in Detection Zone 5, 6 and 7 are to be configured to activate Fire Alarm Devices belonging to Alarm Zone 2 and to activate a Neighbour alarm in Alarm Zone 1.

A manual activation of the manual callpoint in Detection Zone 6 is to be configured to activate all Fire Alarm Devices belonging to Alarm Zone 1 and 2 (Parent Alarm Zone).

A point in alarm is to be configured to activate all Fire Alarm Routing Equipment.

Output configuration

Points in alarm

Zonal configuration

Page 127: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 127

Fire Alarm Control Panel

BS-200

SALES OFFICEDetection Zone 2

CORRIDOR SOUTHDetection Zone 3

BD-300 BH-300

BBR-200

BH-320

Output to F

AR

EO

utput to FW

RE

Output to F

ire Alarm

Device (F

AD

)O

utput to Fire A

larmD

evice(F

AD

)O

utput for the ventilation control in the storage/workshop

Output for

the door controlinthe m

ain building(S

ales Office)

Autronica

Sounder

CANTEENDetection Zone 1

A1002

A1004

A1005

A1001

Alarm Zone 1 (indicated in red)

BBR-200

A1003

BBR-200

A1006

A1007

BH-300

BD-300

BH-300

B1006

B1001

BBR-200

B1005

BH-300

B1004

BF-300

B1002

PRESS HERETRYKK HERK NU S G LA SSET

B REAK G LA SS

BBR-200

B1003

STORAGEDetection

Zone 5

WORKSHOPDetection

Zone 7

Alarm Zone 2 (indicated in blue)

Dotted line indicates the Parent Alarm Zone

Detection Loop B

Detection Loop A

Detection Zone 6

Autronica

Sounder

BF-300

A1008

Detection Zone 4PRESS HERETRYKK HER

K NU S G LA SSET

B REAK G LA SS

Fire Alarm Control Panel

BS-200

SALES OFFICEDetection Zone 2

CORRIDOR SOUTHDetection Zone 3

BD-300 BH-300

BBR-200

BH-320

Output to F

AR

EO

utput to FW

RE

Output to F

ire Alarm

Device (F

AD

)O

utput to Fire A

larmD

evice(F

AD

)O

utput for the ventilation control in the storage/workshop

Output for

the door controlinthe m

ain building(S

ales Office)

Autronica

Sounder

CANTEENDetection Zone 1

A1002

A1004

A1005

A1001

Alarm Zone 1 (indicated in red)

BBR-200

A1003

BBR-200

A1006

A1007

BH-300

BD-300

BH-300

B1006

B1001

BBR-200

B1005

BH-300

B1004

BF-300

B1002

PRESS HERETRYKK HERK NU S G LA SSET

B REAK G LA SS

BBR-200

B1003

STORAGEDetection

Zone 5

WORKSHOPDetection

Zone 7

Alarm Zone 2 (indicated in blue)

Dotted line indicates the Parent Alarm Zone

Detection Loop B

Detection Loop A

Detection Zone 6

Autronica

Sounder

BF-300

A1008

Detection Zone 4PRESS HERETRYKK HER

K NU S G LA SSET

B REAK G LA SS

Page 128: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 128

9.3.1 Site-specific Configuration – Example 2

Step 1: Create the new detection zones and connect the points (loop units) to the new detection zones (5.4.3) All new points in the Storage/Workshop building have to be connected to the new detection zones, DZ5, DZ6 and DZ7. Note that the electronic sounders (Fire Alarm Devices, FADs) in this example are not to be connected to detection zones. Add a site-specific name to each new address (point) if needed

(9.2.7/ 5.4.2).

Step 2: Connect Fire Alarm Devices to new alarm zones (5.5.3) One FAD is to be connected to Alarm Zone 1 and another FAD is to be connected to Alarm Zone 2.

Step 3: Connect already configured detection zones to a new

alarm zone (Alarm Zone 1). (5.2.3) The detection zones, DZ1, DZ2, DZ3 and DZ4 have to be connected to the new Alarm Zone 1.

Step 4: Connect the new detection zones to a new alarm zone

(Alarm Zone 2). (5.2.3) The new detection zones, DZ5, DZ6 and DZ7 have to be connected to the new Alarm Zone 2.

Step 5: Define Alarm Zone 1 and Alarm Zone 2 as Neighbour

Alarm Zones (5.3.3) Step 6: Connect a point in Detection Zone 6 to the Parent

Alarm Zone (5.2.3) A manual activation of the manual call point in Detection Zone 6 is to be configured to activate all Fire Alarm Devices belonging to Alarm Zone 1 and 2 (Parent Alarm Zone).

Step 7: Configure outputs for ventilation control and door control

(5.4.4 and 5.2.4)

Step 8: Save the configuration and restart the system When the additional configuration is completed, you have to save the new configuration and restart the system (9.2.4/3.2/3.3).

In this example, all points activate outputs to Fire Alarm Devices (FAD), Fault Warning Routing Equipment (FWRE) and Fire Alarm Routing Equipment (FARE). As this specific functionality already is provided by the default configuration, no configuration is required. Refer to chapter 5.2.4, 5.4.4 and 5.6.

Configuration Example 2 is based on the steps that are already performed in Configuration Example 1. The following steps cover the configuration that has to be added/changed in order to complete Configuration Example 2.

Page 129: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 129

9.3.2 Step 1: Create Detection Zones and Connect Points

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to scroll downwards to Points.

Use the multiselect feature* to select all points that are to be

connected to the same detection zone, for example starting with Detection Zone 5, including: B1001 B1005 B1006 *To select both points at the same time, press and hold down the Select button to mark the first point B1001, then while still holding down the Select button, press the Arrow Down button to select the point B1005 and B1006.

Press the Function button Press Enter to select the uppermost menu selection Move to

Detection Zone. Press Enter to select the uppermost menu selection Create New

Detection Zone. Press Enter, then use the alphanumeric keypad to enter the name

of the detection zone; Detection Zone 5 (type the first letter, use the right arrow button, then type the next one, and so on).

When the name is completed, press Enter. Press Enter to select Immediate. The default Alarm Organization

is Immediate Action (detection zone type). Press Enter to confirm the settings (Accept). Repeat this procedure for the points that are to be connected to

Detection Zone 6 (including point B1002) and Detection Zone 7 (including point B1003 and B1004).

Page 130: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 130

9.3.3 Add a Site-specific Name to each Point (if needed)

From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to scroll downwards to Points.

Select the first point B1001 that is to be added a site-specific

name, then press Enter twice. Type space and the name STORAGE after the address,

for example, B1001 STORAGE, then press Enter.

As all other properties use the default settings in this example, simply press Enter or the arrow down button a number of times (depending on the type of detector) to accept the settings.

Press Enter to confirm the settings (Accept). Use the arrow down button to select the next point that is to be

added a site-specific name. Repeat the procedure for each point according to the list below: B1001 STORAGE B1005 STORAGE B1006 STORAGE B1002 Manual Call Point STORAGE B1003 WORKSHOP B1004 WORKSHOP

Page 131: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 131

9.3.4 Step 2: Connect Fire Alarm Devices to new alarm zones (5.5.3)

One FAD (the sounder outside CORRIDOR SOUTH in the example) is to be connected to Alarm Zone 1 and another FAD (the sounder outside the STORAGE) is to be connected to Alarm Zone 2. In this example, the Default Alarm Zone is to be defined as the Parent Alarm Zone for both Alarm Zone 1 and Alarm Zone 2. From the Service Menu, perform the following: Use the arrow down button to scroll downwards to

Unit Configuration, then press Enter. Use the arrow down button to scroll downwards to Fire Alarm

Devices.

Use the arrow up/down button to select the first FAD (the sounder in Alarm Zone 1), then press the Function button

Select Move to Alarm Zone (the first menu selection), then press Enter.

Select Create New Alarm Zone (the first menu selection), then press Enter twice.

Type the name of the new Alarm Zone, for example Alarm Zone 1, then press Enter.

The cursor will move to the line below: Parent Alarm Zone. In this

example the Default Alarm Zone is the Parent Alarm Zone. Press Enter to select Default Alarm Zone. Press Enter to confirm the settings (Accept). In the Fire Alarm Devices menu, select the second FAD (the

sounder in Alarm Zone 2) and repeat the entire procedure described above (create Alarm Zone 2 and connect the second FAD to this alarm zone, then select the Default Alarm Zone as the Parent Alarm Zone).

9.3.5 Step 3: Connect already configured detection zones to a new alarm zone (Alarm Zone 1). (5.2.3)

The detection zones, DZ1, DZ2, DZ3 and DZ4 have to be connected to the new Alarm Zone 1. From the Detection Zone Menus (5.2.1), perform the following: Press and hold down the Select button to mark all four

detection zones (DZ1, DZ2, DZ3 and DZ4), then press the Function button

Select Connect to Alarm Zone (the first menu selection), then press Enter.

Use the arrow down button to select Alarm Zone 1. Press Enter to connect the detection zones to this alarm

zone. To confirm the setting, press Enter once more.

Page 132: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 132

9.3.6 Step 4: Connect the new detection zones to a new alarm zone (Alarm Zone 2). (5.2.3)

The new detection zones, DZ5, DZ6 and DZ7 have to be connected to the new Alarm Zone 2. From the Detection Zone Menus (5.2.1), perform the following: Press and hold down the Select button to mark all three

detection zones (DZ5, DZ6 and DZ7), then press the Function button

Select Connect to Alarm Zone (the first menu selection), then press Enter.

Use the arrow down button to select Alarm Zone 2. Press Enter to connect the detection zones to this alarm

zone. To confirm the setting, press Enter once more.

9.3.7 Step 5: Define Alarm Zone 1 and Alarm Zone 2 as Neighbour Alarm Zones (5.3.3)

In this example, Alarm Zone 2 is to be the neighbour zone to Alarm Zone 1, and Alarm Zone 1 is to be the neighbour alarm zone to Alarm Zone 2. From the Alarm Zones Menu (5.3.1), perform the following: Select Alarm Zone 1, then press the Function button Select Connect to Neighbour Alarm Zone (the first menu

selection), then press Enter. Select Alarm Zone 2 as the neighbour alarm zone, then press

Enter. To confirm the setting, press Enter once more.

Use the arrow up/down button to select Alarm Zone 2, then press

the Function button Select Connect to Neighbour Alarm Zone (the first menu

selection), then press Enter. Select Alarm Zone 1 as the neighbour alarm zone, then press

Enter. To confirm the setting, press Enter once more.

Page 133: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 133

9.3.8 Step 6: Connect a point in Detection Zone 6 to the Parent Alarm Zone (5.2.3)

A manual activation of the manual callpoint in Detection Zone 6 is to be configured to activate all Fire Alarm Devices belonging to Alarm Zone 1 and 2 (Parent Alarm Zone). From the Detection Zone Menus (5.2.1), perform the following: Select Detection Zone 6, then press the Function button. Select Connect to Alarm Zone (the first menu selection), then

press Enter. Use the arrow down button to select Default Alarm Zone (the

Parent Alarm Zone). Press Enter to connect Detection Zone 6 to the Parent Alarm

Zone. To confirm the setting, press Enter once more.

9.3.9 Step 7: Configure outputs for ventilation control and door control (5.4.4 and 5.2.4)

This menu allows you to connect a selected point to an output, and give this point certain properties. From the Points Menu (5.4.1), perform the following: Select the point. Press the Function button and use the arrow down button to scroll

downwards to Connect to Output, then press Enter. A list of all available outputs will appear in the display.

Use the arrow up/down button to select the output that is to be connected to the selected point, then press Enter twice.

Use the left or right arrow button to set the Point State, then press Enter.

Use the left or right arrow button to set Yes or No for Activate on Point Disable, then press Enter.

Use the left or right arrow button to set Yes or No for Activate on Point Fault, then press Enter.

To confirm the setting, press Enter once more. This menu allows you to connect a detection zone to an output. From the Detection Zone Menus (5.2.1), perform the following: Select the detection zone. Press the Function button and use the arrow down button to

select Connect to Output, then press Enter. Only local outputs of the type General Output will be listed.

Use the arrow down button to select the output, then press Enter twice.

Use the arrow left/right buttons to select the Detection Activation State (Prealarm, Small Alarm, Large Alarm, Silent Alarm), then press Enter.

Page 134: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Examples

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 134

To confirm the setting, press Enter once more.

9.3.10 Step 8: Save Configuration / Restart System

Refer to chapter 9.2.4.

Page 135: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Other Functions

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 135

10. Other Functions

10.1 Clipboard Functions

Autroprime features clipboard functions (similar to Windows functionality) which is useful during configuration when entering names (typically when typing letters and numbers for detection zones, alarm zones etc).

10.1.1 Copy

The Copy function is useful when similar names are to be used in a configuration several times, when, for example, naming detection zones, “Main Building, 1st floor”, “Main Building, 2nd floor”, etc. To copy an already written name for, for example, a detection zone, proceed as follows:

Go to the detection zone in question, and press Enter to highlight the name field (the name appears on a black background with light green text).

Press and hold down the Select button , then press the arrow

left button repeatedly until the entire name is selected (the name appears in inverse video; on a light green background with black text).

Press the Function button Use the arrow down button to select Copy, then press Enter

The name is now copied, and is placed in the clipboard.

10.1.2 Cut

To cut an already written name for, for example, a detection zone, proceed as follows:

Go to the detection zone in question, and press Enter to highlight the name field (the name appears on a black background with light green text).

Press and hold down the Select button , then press the arrow

left button repeatedly until the entire name is selected (the name appears in inverse video; on a light green background with black text).

Press the Function button

Select Cut (the first menu selection), then press Enter The name is cut, and is placed in the clipboard.

Page 136: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Other Functions

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 136

10.1.3 Paste

To paste a name (for example, for a detection zone) which is already placed in the clipboard, proceed as follows:

Go to the detection zone in question, and press Enter to highlight the name field (the name appears on a black background with light green text).

Now you can either overwrite the existing name, or paste the content of the clipboard where the cursor is positioned.

To overwrite the existing name: o Press and hold down the Select button , then press the

arrow left button repeatedly until the entire name is selected (the name appears in inverse video; on a light green background with black text).

o Press the Function button o Use the arrow down button to select Paste, then press

Enter

Paste the content of the clipboard where the cursor is positioned. o Press the Function button

o Use the arrow left/right buttons to move the cursor to the desired position.

o Use the arrow down button to select Paste, then press

Enter

10.1.4 View Content

This command allows you to view the content of the clipboard. Note that this command can be used only when entering name and numbers, i.e. when the name field is active (blinking cursor). Press the Function button Use the arrow down button to select View Content, then

press Enter

Page 137: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Other Functions

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 137

10.2 Capital and Small Letters –Toggle functionality

To toggle between capital letters and small letters, use the #-key.

Page 138: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Tool

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 138

11. Configuration Tool

11.1 Introduction

The Autroprime system features a pc-based configuration tool which simplifies the customized configuration work, allowing customers and service personnel to; enter tag names for points, alarm zones and detection zones connect detection zones to alarm zones define global settings (variables) define the detection zone type (directly in the loop window)

11.2 Setup Wizard

Insert the CD into you disk drive, then follow the instructions in the setup wizard.

Page 139: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Tool

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 139

Page 140: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Tool

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 140

11.3 Starting the Configuration Tool

Double-click the program icon, and the configuration tool will

appear.

Page 141: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Configuration Tool

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 141

11.4 Help File

For detailed information on the Autroprime Configuration Tool, refer to the help file located in the Help Menu.

Page 142: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Appendix

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 142

12. Appendix

12.1 Alarm Organization

12.1.1 Detection Zones with Different Properties

When handling events in Operation Mode, it is important to be aware of how the alarm organization is configured, that is, the system’s detection zone configuration. The system provides the following types of detection zones with different properties: Immediate Action detection zone Dependency Action detection zone Delayed Action detection zone Delayed Dependency detection zone SOLAS (Safety of Life at Sea) detection zone The property of a detection zone as well as the type of point (detector or manual call point) will determine how the system responds to the signal - with respect to action.

12.1.2 The Actioning of Alarm Zones

The actioning of alarm zones can be controlled by detection zones, with or without Delay/Dependency properties. For example, a detection zone in alarm can activate a number of alarm zones. The delay period before activation can be defined according to the property of the chosen detection zone type. An alarm zone can give both an alarm signal and a neighbouring alarm zone signal with a different pattern. The top-level alarm zone (default) is called the Parent Alarm Zone. A system consists of a Parent Alarm Zone, usually with several “sub-level” alarm zones in an hierarchy. Each “sub level”-alarm zone is related to a specific area of, for example, a building. If an alarm occurs in a Parent Alarm Zone, all Fire Alarm Devices (FADs) within this zone, plus all FADs belonging to all “sub-level”-alarm zones will be activated.

Page 143: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Appendix

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 143

12.1.3 Immediate Action Detection Zones

A signal from an Immediate Action detection zone, will initiate all actions immediately, without any delay. Immediate Action applies to all units that can be activated by a Immediate Action Detection Zone.

12.1.4 Dependency Action Detection Zones

In areas where points may be exposed to a high level of pollution, for example, unwanted alarms may occur. In order to avoid this problem, the Dependency Action alarm organization is used. A fire alarm signal from a single detector in a system defined as Dependency Action will initiate no actions, i.e. there will be no actioning of outputs to; Fire Alarm Devices (FAD) Fire Alarm Routing Equipment (FARE) Fire Protection Equipment (FPE) Silent Alarm At least two detectors in the same detection zone must be in alarm state before actions are initiated. It is also possible to configure the system in such a way that a Large Alarm will be initiated if at least two detectors in the entire system are in alarm state, regardless of which detection zone each detector belongs to.

Note that an activation of a manual call point in a dependency action detection zone will always initiate actions (provided that the point has been set to Override Delay and Dependency, YES).

Page 144: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Appendix

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 144

12.1.5 Delayed Action Detection Zones

Delays to any output depends on the Day Mode operation of the system (i.e. the LED for Delayed Action is ON). In Night Mode (i.e. the LED for Delayed Action is OFF) all outputs will be activated at first point in alarm. When the operator panel receives a fire alarm signal from a point in a Delayed Action detection zone (configurable), the actioning of outputs to Fire Alarm Devices (FAD) and/or Fire Alarm Routing Equipment (FARE) can be delayed. The purpose of this type of alarm organization is to give an immediate warning, but to delay the activation of outputs. In this way the cause of the alarm can be investigated before the system automatically initiates the evacuation of the protected premises and signals the local fire brigade. Delayed Action is based on the first point reporting the fire. A second point in alarm in the same detection zone will not affect the delay of the connected outputs. In an alarm situation, the actioning of outputs will be delayed when the detection zone has been defined as a Delayed Action detection zone (configurable) and the point(s) in this Delayed Action detection zone has been set to Override Delay and Dependency, NO.

The operation of delays to outputs for Fire Alarm Devices (FAD) apply to: detectors and/or manual call points and/or signals from specific zones

The operation of delays to outputs for Fire Alarm Routing Equipment (FARE) apply to: detectors and/or signals from specific zones The delay is divided into two delay periods, Initial delay, T1 (configurable) and Prolonged Delay, T2 (configurable). The default value for T1 is 1 minute and 2 minutes for T2.

The T1 delay period is started when a Fire Alarm signal from a point is received. Acti ons will be initiated after the T1 delay period has expired. Pressing PROLONG DELAY, will terminate T1 and the delay period T2 will start.

Note that activation of a manual call point will normally give immediate output actioning (provided that the point has been set to Override Delay and Dependency, YES), even though the immediate output actioning has been disabled (configurable).

Page 145: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Appendix

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 145

T1 for different detection zones may start at different times, however, when Prolong Delay has been pressed, T2 for all detection zones will start at the same time. If one or more Delayed Action detection zones have entered the Fire Alarm state and are in their T1 or T2 periods, the delayed actions can be immediately initiated by pressing the Activate Outputs button. Activation of a manual call point will also give immediate action (provided that the point has been set to Override Delay and Dependency, YES).

12.1.6 Delayed Dependency Detection Zones

Detection zones configured as Delayed Dependency Detection Zones have the following properties in Day and Night Mode: In Day Mode, outputs that are configured to be activated by these detection zones will operate according to their actual configuration, i.e. Silent Alarm, Small Alarm or Large Alarm as follows: When a fire alarm signal from the first detector in alarm is

received, the following will occur: o The detection zone will enter the Silent Alarm state, and all

FPE outputs configured to be activated on Silent Alarm will be activated. The T1 delay period will start.

o When the T1 delay period expires, the detection zone will enter the Small Alarm state. All FPE outputs configured to be activated on Small Alarm will be activated. The T2 delay period will start.

o When the T2 delay period expires, the detection zone will enter the Large Alarm state. All FPE outputs configured to be activated on Large Alarm will operate.

Note that, at any time, if an alarm from a second detector within the same detection zone is received, the detection zone will always enter the Large Alarm State. This means that all (not yet activated) FPEs configured to be activated on Silent, Small and Large Alarm will be activated.

In Night Mode, outputs are always activated on the first detector in alarm and the system will always enter the Large Alarm state. As with Day Mode this means that all (not yet activated) FPEs configured to be activated on Silent, Small and Large Alarm will operate.

Note that when a point sends an alarm signal, and this point has been set to Override Delay and Dependency, YES, the Delayed Dependency detection zone will enter the Large Alarm state directly, regardless of Day or Night Mode.

Page 146: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Appendix

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 146

12.1.7 SOLAS Detection Zones

Note: Applies to Fire Alarm Control Panel BS-200M only. A detection zone configured as SOLAS Detection Zone (Safety of Life at Sea), has a two-minute delay from when a Point enters an alarm condition until the associated Detection Zone initiates the activation of the configured Fire Alarm Devices (FADs) and outputs. During this period a countdown timer is shown in the panel display and the user has the ability to block the activation of FADs and/or outputs during the two minute period. The Activate Outputs button can be used to activate the FADs and outputs that are in this two minute transition period or that have previously been blocked. It is also possible to configure a SOLAS Detection Zone to immediately activate certain FADs and outputs, without the two minute delay. These FADs and outputs will thus start to operate at the moment the first Point in a Detection Zone enters the Alarm condition. The Silence button can be used to control the FADs independently of the Block operation. The Silence function will affect all FADs that have been activated. Autroprime also has a Resound function that will reverse the effect of Silence.

12.1.8 Silent, Small and Large Alarm – Overview

A few differences can be found in national guidelines regarding alarm organization and output delays. To be able to meet these guidelines you can select between different types of detection zones and control the activation of outputs. Three “levels” have been defined regarding the progress of a fire alarm situation that can be utilized to activate outputs. If delays are activated, the normal situation will be that all activations will take place at the ‘Large Alarm’ level, both signalling the fire brigade (FARE), sounders (FADs) and any other delayed output (FPE). Activating outputs (FPE) at other levels may be obtained selecting these levels through configuration. Onboard (BSA-200) outputs may be configured to be dedicated outputs for the Silent Alarm and Small Alarm levels. In this case they will only be activated at these levels. The table on the next page indicates which levels are available for different types of detection zones.

Page 147: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Appendix

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 147

Silent Alarm Any fire alarm signal will be indicated at the panel without any delay, and this is the Silent Alarm level. An output may be configured to be activated at this level, as an example to trigger a coded message through a voice alarm system or an output to make on site technical personnel aware of the situation. The delay timer T1 will be started and a countdown timer will be shown in the display. For a Delayed detection zone the operator may now initiate a prolonged T2 period. Small Alarm In the case of a Delayed Dependency detection zone there is an automatic transfer from the initial T1 delay period to the prolonged T2 delay period. When this transfer occurs the level will be increased to Small Alarm. Looking at a shopping centre this level may be used for another voice alarm message making the employees start the preparations for an evacuation. The display will show the T2 countdown. (Small alarm level is also shown for Delayed and Dependency zones, but should not be used as an activation criteria for outputs.) Large Alarm The table below shows that this level is the last one (or only) for all types of detection zones. There are different ways of getting to this level, either elapsed timers (T1 and/or T2), a second alarm signal or a panel operation. If not configured otherwise, all outputs will be activated at this level, fire brigade (FARE), sounders (FAD) and any other outputs (FPE).

Silent Alarm Small Alarm Large Alarm Immediate Action Detection Zone x Delayed Action Detection Zone x x Dependency Action Detection Zone x x Delayed Dependency Detection Zone x x x SOLAS Detection Zone x x

Page 148: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …
Page 149: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Reader’s Comments

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

13. Reader’s Comments Please help us to improve the quality of our documentation by returning your comments on this manual: Title: Configuration Handbook, Autroprime Interactive Fire Detection System,

Ref. No.: 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03

Your information on any inaccuracies or omissions (with page reference):

Please turn the page

Page 150: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Reader’s Comments

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Suggestions for improvements

Thank you! We will investigate your comments promptly.

Would you like a written reply? Yes No

Name: ------------------------------------------------------------------------------------------------

Title: ------------------------------------------------------------------------------------------------

Company: ------------------------------------------------------------------------------------------------

Address: ------------------------------------------------------------------------------------------------

------------------------------------------------------------------------------------------------

------------------------------------------------------------------------------------------------

Telephone: ------------------------------------------------------------------------------------------------

Fax: ------------------------------------------------------------------------------------------------

Date: ------------------------------------------------------------------------------------------------

Please send this form to: Autronica Fire and Security AS

N-7483 Trondheim

Norway

Tel: + 47 73 58 25 00

Fax: + 47 73 58 25 01

www.autronicafire.com

Page 151: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Reader’s Comments

Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS

Page 152: Configuration HandbookConfiguration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03, Autronica Fire and Security AS Page 7 …

Autronica Fire and Security is an international company, headquartered in Trondheim, one of the largest cities in Norway. The company is owned by United Technologies Corporation and employs more than 319 persons with experience in developing, manufacturing and marketing of fire safety equipment. Our products cover a broad range of systems for integrated solutions, including fire detection systems, integrated fire and gas detection systems, control and presentation systems, voice alarm systems, public address systems, emergency light systems, plus suppression systems. All products are easily adaptable to a wide variety of applications, among others, hospitals, airports, churches and schools, as well as to heavy industry and high-risk applications such as power plants, computer sites and offshore installations, world wide. The company's strategy and philosophy is plainly manifested in the business idea: Protecting life, environment and property.

Quality Assurance

Stringent control throughout Autronica Fire and Security assures the excellence of our products and services. Our products are CE marked and developed for worldwide standards and regulations, and conform with the CEN regulation EN54. Our quality system conforms to the Quality System Standard NS-EN ISO 9001:2000 and is valid for the following product and service ranges: marketing, sales, development, engineering, manufacture, installation, commissioning and servicing of suppression, integrated fire and gas detection and alarm systems, plus petrochemical, oil and gas instrumentation systems for monitoring and control.

Autronica Fire and Security AS Headquarters, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01. Head Office Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99. Division Oil & Gas, Oslo, Norway. Phone: + 47 23 17 50 50, Fax: + 47 23 17 50 51 Division Oil & Gas, PO Box 416, Farnborough GU14 4AT, UK. Phone: + 47 51 84 09 00, Fax: + 44 84 52 80 20 55 Division Maritime, Suppression/New Build Detection & Alarm. Norway. Phone: + 47 31 29 55 00, Fax: + 47 31 29 55 01 Division Maritime, After Sales/Service Detection & Alarm, Norway. Phone: +47-73 58 25 00, Fax: +47-73 58 25 01

Visit Autronica Fire and Security's Web site: www.autronicafire.com


Recommended