Connecting Loop Units

Interactive fire detection systems

116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21

Page 2: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 2

COPYRIGHT ©

This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS and its subsidaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it. No information in this publication should be regarded as a warranty made by Autronica Fire and Security. The information in this publication may be updated without notice. Product names mentioned in this publication may be trademarks. They are used only for identification.

Page 3: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Introduction

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 3

Table of Contents

1.  Introduction ....................................................................... 5 

1.1  About the Handbook .......................................................................... 5 1.2  Reference Documentation................................................................. 5 1.3  The Reader ....................................................................................... 5 

2.  Detectors ........................................................................... 6 

2.1  Connecting Detectors ........................................................................ 6 2.2  LED Connection on Detector............................................................. 6 2.3  Connection of Branch-off ................................................................... 7 2.4  Detector Head / Base Alignment ....................................................... 8 2.5  Detector Label ................................................................................... 8 2.6  Detector Locking Mechanism ............................................................ 9 

2.6.1  Detector Base ......................................................................... 9 2.6.2  Detector head .......................................................................... 9 2.6.3  Removing a locked detector head .......................................... 10 

2.7  Detector Dust Covers ........................................................................ 11 

3.  Manual Callpoints ............................................................. 12 

4.  Input and Output Units ..................................................... 13 

4.1  BN-180 AutroKeeper ......................................................................... 13 4.2  BN-221/01 Extinguishing Control Unit ............................................... 16 4.3  BN-221/02 Monitored Output Unit, 7A Relay .................................... 17 4.4  BN-303 Single Monitored Input Unit .................................................. 18 4.5  BN-303/LS Local Alarm Delay Unit ................................................... 19 4.6  BN-304 Single Monitored Input/Output Unit ...................................... 20 4.7  BN-305 Dual Monitored Input/Output Unit ........................................ 21 4.8  BN-307 Monitored Fire Alarm Device Control Unit ........................... 22 4.9  BNB-330A Conventional Loop Interface ........................................... 23 4.10  BNB-331 Conventional Loop Interface .............................................. 24 4.11  BN-500/EX Input Unit with SelfVerify ................................................ 25 4.12  BN-500/N Input Unit with SelfVerify .................................................. 26 4.13  BN-505/EXD Input Unit with SelfVerify ............................................. 27 

5.  Control Units ..................................................................... 28 

5.1  BW-200 Disable Input with Pushbuttons ........................................... 28 5.2  BW-201 Disable Input with Timer Input ............................................. 29 5.3  BW-202 Day/Night Control Unit with Pushbuttons ............................ 30 5.4  BW-203 Day/Night Control Unit with Timer Input .............................. 31 5.5  BU-200 Remote Alarm Control Unit .................................................. 32 

Page 4: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Introduction

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 4

6.  Alarm Units ........................................................................ 33 

6.1  Introduction ........................................................................................ 33 6.2  BBL-100 Beacon Indoor Addressable ............................................... 33 6.3  BBR-130 Sounder Adressable with Base ......................................... 34 6.4  BBR-230 Sounder Indoor Addressable ............................................. 35 6.5  BBQ-130 Sounder/Strobe with Base ................................................. 36 6.6  BBQ-230 Sounder/Strobe Addressable ............................................ 37 

7.  Detectors for Special Requirements ............................... 38 

7.1  AutroFlame IR Flame Detector BG-201 ........................................... 38 7.2  AutroFlame IR Flame Detector BG-21 .............................................. 39 7.3  Fireray 5000 ...................................................................................... 40 7.4  AutroSense Nano .............................................................................. 41 7.5  AutroSense Micra 25 High Sensitivity Aspirating Detector ............... 42 7.6  AutroSense Micra 100 High Sensitivity Aspirating Detector ............. 43 7.7  AutroSense 200 High Sensitivity Aspirating Detector ....................... 44 7.8  AutroFlame X33AF Multispectrum Infrared Flame Detector ............. 45 7.9  Ex ia Approved Detectors .................................................................. 46 

8.  Discontinued Products..................................................... 47 

8.1  BBR-200 Programmable Electronic Sounders .................................. 47 8.2  BBR-110 Addressable Socket Sounder ............................................ 48 8.3  BN-300 Input Unit with SelfVerify ...................................................... 49 8.4  BN-310 Single Relay Output Unit ...................................................... 50 8.5  BN-201 Monitoring Input Unit ............................................................ 51 8.6  BN-320 Interface with SelfVerify ....................................................... 52 8.7  BN-320/2 Door Control Unit .............................................................. 53 8.8  BN-320/4 Monitoring and Control Unit .............................................. 54 8.9  BN-320/5 Sprinkler Control Unit ........................................................ 55 8.10  BN-330 Interface Unit for Conventional Loops .................................. 56 8.11  AutroSense 75 Aspirating Smoke Detector ....................................... 57 8.12  AutroBeam 25 Infrared Beamdetector .............................................. 58 8.13  AutroBeam 100 Infrared Beamdetector System ............................... 59 

9.  Reader’s Comments ......................................................... 61 

Page 5: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Introduction

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 5

1. Introduction

1.1 About the Handbook

This document provides information on how to connect detectors and other loop units to the interactive fire detection systems Autroprime and AutroSafe. Note that some loop units can be connected to AutroSafe only (the indication “AutroSafe only” is written in the beginning of these chapters). Autronica’s interactive fire detection systems offer a wide range of fire alarm detectors, manual call points and input/output units, control units and alarm units that are developed and approved according to European directives (CPD) requiring EN 54 compliance. Both input and input/output units are also available with the SV-function. Input units can also be delivered in series 500 and 500/Ex.

1.2 Reference Documentation

Detailed information for each loop unit is provided on separate data sheets.

1.3 The Reader

This handbook is intended for technical personnel.

Page 6: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 6

2. Detectors

2.1 Connecting Detectors

P RES S H ER ETRYK K HER

KNU S G LAS SE T

BREA K G LASS

Loop DriverModule

DetectorI/O Unit Manual Call Point

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Input

Output

2.2 LED Connection on Detector

+

-

BU-46

Input

Output

1 - IN2 - OUT3 + COMMON4 - LED

LED

Page 7: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 7

2.3 Connection of Branch-off

If necessary, a branch-off can be connected to a detection loop if the existing cable layout requires this, but this is not recommended, as the safety will be reduced. To ensure a correct addressing of the detectors on a branch-off when configuring the system, there can not be more than one branch-off per detector. For safety reasons, the number of detectors on each branch-off must be kept to a minimum, as the detectors on a branch-off will not operate in case of a break or shortcircuit on the branch-off. The absolute maximum number of detectors on a branch-off (or an open loop) is 32.

Accepted NOT Accepted!

Loop Loop

Branch-off Branch-off

Branch-off

Input

Output

+

-

+ -

1 - IN2 - OUT3 + COMMON4 - LED

Main Loop

Branch-off

Next detector on branch-off

NOTE: Always connect a branch-off to terminal 2 (-) and 3 (+).

Page 8: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 8

2.4 Detector Head / Base Alignment

Alignment

LED

LED

2.5 Detector Label

AUTRONICAFIRE & SECURITYINSPECTION SERTIFICATEREF AFS-OPTICAL DETECTOR BHH 320

ID

ID

EN54/7 CE

001 1998 239 0001

0842

001 1998 239 0001

Location for tagname sticker

Page 9: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 9

2.6 Detector Locking Mechanism

2.6.1 Detector Base

In the detector base a small locking nub will keep the springloaded tongue in an open position to prevent the detector head from being locked. If the locking nub is removed before mounting with a pair of cutting nippers or similar, the detector head will enter a locked position. I Detector base with locking nub

2.6.2 Detector head

The new springloaded tongue (figure 3) on the detector head will lock the head in a correct position if the locking nub has been removed before mounting. Detector head with springloaded tongue

Springloaded tongue

Locking nub

Page 10: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 10

2.6.3 Removing a locked detector head

To remove a locked detector head, use a suitable tool (for example a paper clip or similar) to push the springloaded tongue in, and simply turn the detector head counter-clockwise.

Use this hole to access and release the locking mechanism.

Page 11: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 11

2.7 Detector Dust Covers

Autronica detectors are supplied with a dust cover. To avoid possible contamination of the detector chamber during installation, these should remain in place on the detector until commissioning is started.

IMPORTANT: LEAVE DETECTOR DUST COVERS ON UNTIL COMMISSIONING IS STARTED

Page 12: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Manual Callpoints

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 12

3. Manual Callpoints

P RE SS H ER ETRYK K HER

KNUS GLAS SE T

BREAK GLASS

Loop DriverModule

DetectorI/O Unit Manual Call Point

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Connector on Manual Call

Point

Wires on Detection Loop

Wires on detection loop BF-300V2/

BF-510WP-H

1 Pos (+) in Pos (+) in

2 Pos (+) out Neg (-) in

3 Neg (-) in Pos (+) out

4 Neg (-) out Neg (-) out

5 Internal connection Internal connection

6 Internal connection Internal connection

1 2 3 4 5 6

Manual Call Point

1

2

3

4

5

6

BF-300V2 BF-510WP-H

Page 13: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 13

4. Input and Output Units

4.1 BN-180 AutroKeeper

The AutroKeeper is physically placed between the loop controller (BSD-310) and the detection loop and thus controlling/providing the loop controller access to the loop.

Pin number

Description

1 TTL COM Debug port (internal use only)

2 TTL IN Debug port (internal use only)

3 TTL OUT Debug port (internal use only)

4 GND 5 24V IN Power In (Green LED) 6 0V IN Power In 7 FAILSAFE COM FailSafe Rel. (future) 8 FAILSAFE NO FailSafe Rel. (future) 9 OUTLOOP + To “first” Loop Unit

10 OUTLOOP - --“-- 11 INLOOP + To “last” Loop Unit 12 INLOOP - --“-- 13 OUT + To Loop Driver’s IN + 14 OUT - To Loop Driver’s IN - 15 IN + To Loop Driver’s OUT+ 16 IN - To Loop Driver’s OUT -

DIN rail conn. 1 24V IN Power In DIN rail conn. 2 0V IN Power In DIN rail conn. 3 Not used DIN rail conn. 4 Not used DIN rail conn. 5 GND

Pin no. 1-4

5-8 13-16

Pin no. 1-5(DIN rail connector)

Pin no. 9-12

Page 14: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 14

BN

-180

as

Act

ive

B

N-1

80 a

s S

tand

by

Pat

ente

d co

mpo

nent

to m

eet

the

new

SO

LAS

re

quire

men

t

Page 15: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 15

-2 +1 -5 +4

OU

T

IN

Loop

Driv

er

Mod

ule

BS

D-3

10

-10

+9

-12

+11

OU

T

IN

IN OU

T

-16

+15 -14

+13

1

2

3

1

2

3

2

1

3

2

1

3

IN

OU

T

- 12

+11 -10

+9

-14

+1

3

-16

+1

5

OU

T

IN

Loop

Driv

er M

odul

eB

SD

-31

0

-5 +4 -2 +1

IN

OU

T

Aut

roK

eep

erB

N-1

80A

utro

Kee

per

BN

-180

Com

mun

icat

ion

Mod

ule

BS

L-3

10

3 T

X

7 R

X

10 G

ND

9 C

TS

1 IN

T

Ter

min

atio

nB

lock

Aut

roF

ield

Bus

Pro

toco

l Con

vert

erB

SD

-321

25 T

X P

ort 0

26 R

X P

ort 0

27 G

ND

Por

t 0

13 T

X P

ort 1

14 R

X P

ort 1

15 G

ND

Por

t 116

IE P

ort

128

IE P

ort

0

AF

B A

9

AF

B A

’ 1

1

A

FB

B

3

AF

B B

5

5

AF

B B

6

AF

B B

1

AF

B A

2

AF

B A

Ter

min

atio

nB

lock

Fire

Ala

rm C

ont

rol P

ane

lB

S-4

20F

ire A

larm

Con

tro

l Pan

elB

S-4

20

Pri

mar

y S

yst

emS

eco

nd

ary

Sys

tem

3 T

X

7 R

X

10 G

ND

9 C

TS

1 IN

T

Page 16: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 16

4.2 BN-221/01 Extinguishing Control Unit

The extinguishing control unit BN-221/01 is an interface unit which monitors and controls extinguishing equipment. The extinguishing equipment is powered from a separate 24 VDC supply. The interface unit is used in the AutroSafe interactive fire detection system, and it is connected directly to a detection loop. The extinguishing equipment is powered from a separate 24 VDC supply. The interface unit is used in the AutroSafe interactive fire detection system, and it is connected directly to a detection loop.

Page 17: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 17

4.3 BN-221/02 Monitored Output Unit, 7A Relay

The monitored output unit, 7A relay (BN-221/02) is connected directly to the detection loop in the AutroSafe interactive fire detection system. It controls and monitors external equipment. Typical applications are notification devices such as horns, strobe lights, indicating light etc.

Page 18: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 18

4.4 BN-303 Single Monitored Input Unit

The Single Monitored Input Unit BN-303 has been designed for use with Autronica’s fire detection systems, Autroprime (version 1.1.0 or newer) and AutroSafe (version 4.3.1 or newer), and includes the SelfVerify function. All connections are made to the screw terminals numbered 1-8. Screw terminal Description

1 AL_Com In (+)

2 AL_Com In (-)

3 AL_Com Out (+)

4 AL_Com Out (-)

5 Input (+)

6 Input (common)

7 Not in use

8 Not in use

Page 19: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 19

4.5 BN-303/LS Local Alarm Delay Unit

The local alarm delay unit BN-303/LS enables delay of alarm routing outside the local area which the unit is connected to (Autroprime; 1 detection zone, AutroSafe; up to 10 detection zones), plus temporary stop of smoke detection in the local area.

Loop in + -

Loop out - +

Page 20: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 20

4.6 BN-304 Single Monitored Input/Output Unit

The Single Monitored Input/Output Unit BN-304 has been designed for use with Autronica’s fire detection systems Autroprime (version 1.1.0 or newer) and AutroSafe (version 4.3.1 or newer), and includes the SelfVerifyfunction. All connections are made to the screw terminals numbered 1-8 Screw terminal Description

1 AL_Com In (+)

2 AL_Com In (-)

3 AL_Com Out (+)

4 AL_Com Out (-)

5 Input (+)

6 Input (common)

7 Relay Contact

8 Relay Contact

Page 21: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 21

4.7 BN-305 Dual Monitored Input/Output Unit

The Dual Monitored Input/Output Unit BN-305 has been designed for use with Autronica’s interactive fire detection systems, Autroprime and AutroSafe, and includes the SelfVerify function.

All connections are made to screw terminals numbered 1-12. Terminal Function 1 AL_Com In (+) 2 AL_Com In (-) 3 AL_Com Out (+) 4 AL_Com Out (-) 5 Input 1 (+) 6 Input 1 (common) 7 Relay 1 contact 8 Relay 1 contact 9 Input 2 (+) 10 Input 2 (common) 11 Relay 2 contact 12 Relay 2 contact

LED connectors Terminal Function J2.1 LED1 + (LED Activate) J2.2 LED1 - (LED Activate) J2.3 LED2 + (LED Fault) J2.4 LED2 - (LED Fault)

LED connector: A pin header enables the option to add LED indicators. The indication is a short blink at 0,5Hz period. LED activate: The input or output is in Activation condition. LED fault: There is a fault on the input or the unit itself.

Page 22: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 22

4.8 BN-307 Monitored Fire Alarm Device Control Unit

The Monitored Fire Alarm Device Control Unit BN-307 has been designed for use with Autronica’s fire detection systems, AutroSafe and Autroprime.

BN-307

1

2

3

4

5

6

Al_Com + in

Al_Com - in

Al_Com + out

Al_Com - out

+24V DC

0V DC

2k *

7

8

*End-of-line resistance 2kohm (+/- 5%)

LED1 Activate LED2 Fault

Page 23: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 23

4.9 BNB-330A Conventional Loop Interface

The Conventional Loop Interface BNB-330A is a 2 wire interface unit for interfacing conventional detectors and manual call points onto Autronica’s interactive fire detection systems. BNB-330A replaces BNB-330 and may be used on all the same systems. Connectors

Terminal Function 1 Alarm Out1 2 Alarm Out2 3 N.A. 4 N.A. 5 Conv + 6 Conv - 7 N.A.8 N.A.9 Loop+ 10 Loop In- 11 Loop+ 12 Loop Out - 13 24V 14 0v 15 N.A.16 N.A.

Bottom connectors

Terminal Function

1 24V 2 0V 3 N.A. 4 N.A. 5 Chassis ground

+24V

BNB-330A

CONV EOL

132

(MAX)

Loop Powered Conventional Detector

Interface

AL_Com IN AL_Com OUT

24V A0V

EN54-4POWERSUPPLY

UNIT

ALARMOUT

+

-

1

2

5

6

11 129 10

13

14

+ +- -

Open = normalClosed = alarm

Page 24: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 24

4.10 BNB-331 Conventional Loop Interface

The Conventional Loop Interface BNB-331 is a 2 wire interface unit for interfacing conventional detectors and manual call points onto Autronica’s interactive fire detection systems. Connectors

Terminal Function

1 Alarm Out1 2 Alarm Out2 3 Fault Out 1 4 Fault Out 2 5 Conv + 6 Conv - 7 PSUFlt_IN* 8 PSUFlt_0V* 9 Loop In + (Al_Com) 10 Loop In - (Al_Com) 11 Loop out + (Al_Com) 12 Loop Out - (Al_Com) 13 24V A 14 0v A 15 24V B* 16 0v B*

Bottom connectors

Terminal Function

1 24V A 2 0V A 3 24V B 4 0V B 5 Chassis ground

+24V

FAULTRELAY

BNB-331

CONV.BRANCH

EOLunit

132

(MAX)

Loop PoweredConventional Detector

Interface

AL_Com IN AL_Com OUT

24V A

24V B

0V

+24V

0V

EN54-4POWERSUPPLY

UNIT

ALARMOUT

FAULTOUT

+

PSUFlt

-

1

2

3

4

5

6

11 129 10

7

8

13

14

15

16

+ +- -

Closed = NormalOpen = fault*

Open = normalClosed = alarm

Open = normalClosed = fault

* Dipswitch dependent

Page 25: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 25

1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 5. (-) Input 6. (+) Input

1 2 3 4 5 6

4.11 BN-500/EX Input Unit with SelfVerify

BN-500/EX is an input unit for use in hazardous area zone 0, 1, 2. It must be connected to the approved barrier BZ-500.

Page 26: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 26

4.12 BN-500/N Input Unit with SelfVerify

1 2 3 4 5 6

BN-500/N

1. Pos (+) in * EOL 2 KOHM

2. Pos (+) out

3. Neg (-) in

4. Neg (-) out

5. (-) Input 6. (+) Input

Page 27: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Input and Output Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 27

1. + in 2. + out 3. - in 4. - out 5. - input 6. + input

4.13 BN-505/EXD Input Unit with SelfVerify

BN-505/EXD is an input unit for use in hazardous area zone 1 or 2.

BNB-300/32

100

120

145

166

.

BNB-300/32

100

120

145

166

BNB-300/32

100

120

145

166

.

BSD-310

BSD-310/N

CERTIFICATENEMKO 03ATEX217X

SAFE AREA

Ex, ZONE-2

Exd CONNECTION

BD-505/xxxEXD *

Exd nL CONNECTION

II 2(3)G EEx d [nL IIB] IIC T6 Ta: 70°C

Ex, ZONE-1

BD-505/xxxEXD *ZONE 2

LOOP DRIVER(for smoke/heat) CERTIFICATE NEMKO 04ATEX1406

Detector Loop for smoke/heat detectors or MCP's

CERTIFICATE NEMKO 04ATEX1406

Detector Loop for smoke/heat detectors or MCP's

AUTROSAFE

NEMKO 03ATEX217X:EEx nL IIB T4Tamb: 50°C/70°C

SAFETY DATA:The ratio L/R for the loop cable shall not exceed the stated value Lo/Ro: 30µH/O

II 2(3)G EEx d [nL IIB] IIC T6 Ta: 70°C

* BD-505/xxxEXD used as example.Can also be BN-505/EXD

Page 28: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Control Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 28

5. Control Units

5.1 BW-200 Disable Input with Pushbuttons

The Disable unit is used to disable one or a number of detection zones. The unit is connected to and powered from the detection loop. The disablement time is configurable.

PRESS H ER ETRYKK HERK NU S G LA S SE T

B RE AK G LA S S

BW-200

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

PRESS H ER ETRYKK HERK NU S G LA S SE T

B RE AK G LA S S

BW-200

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

* 1 or 2 units on each loop: Connect detector loop + (1), and detector loop – (3) to 24V input. More than 2 units on each loop: Use external 24V supply Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used.

LED Steady light when disabled Flashing the last 5 min. of disablement

Disable detection zones

Enable detection zones

Detection Loop

24V Input

24V Output

+ + - -

*

Page 29: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Control Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 29

5.2 BW-201 Disable Input with Timer Input

Applies to AutroSafe only. The Disable unit is used to disable one or a number of detection zones. The unit is connected to and powered from the detection loop. An external timer controls the disablement time.

PRESS HERETRYKK HERKNU S G LA SSET

BREAK G LASS

BW-201

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

External Timer

PRESS HERETRYKK HERKNU S G LA SSET

BREAK G LASS

BW-201

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

External Timer

Connection to External timer

24V Output

24V Input

* 1 or 2 units on each loop: Connect detector loop + (1), and detector loop – (3) to 24V input. More than 2 units on each loop: Use external 24V supply Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used.

LED

Detection Loop

+ + - -

*

Page 30: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Control Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 30

 

5.3 BW-202 Day/Night Control Unit with Pushbuttons

Applies to AutroSafe only. The Day/Night Control Unit is used for remote operation of the Disable/Enable ‘Immediate Output Action’ commands. The unit is connected to and powered from the detection loop.

PRES S HER ETRYK K HE RK NU S G LA S SE T

B REAK G LA S S

BW-202

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.LoopDriverModule

PRES S HER ETRYK K HE RK NU S G LA S SE T

B REAK G LA S S

BW-202

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.LoopDriverModule

24V Input

Night Mode

Day Mode Detection Loop

+ + - -

24V Output

LED

*

* 1 or 2 units on each loop: Connect detector loop + (1), and detector loop – (3) to 24V input. More than 2 units on each loop: Use external 24V supply Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used.

Page 31: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Control Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 31

 

5.4 BW-203 Day/Night Control Unit with Timer Input

Applies to AutroSafe only. The Day/Night Control Unit is used for remote operation of the Disable/Enable ‘Immediate Output Action’ commands. The unit is connected to and powered from the detection loop. An external timer controls the monitored input.

P RE SS H ER ETRYK K HE RK NU S G LA S SE T

B R E AK G LA S S

BW-203

BN- 320BR ANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.LoopDriver Module

External Timer

P RE SS H ER ETRYK K HE RK NU S G LA S SE T

B R E AK G LA S S

BW-203

BN- 320BR ANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BR ANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.LoopDriver Module

External Timer

* 1 or 2 units on each loop: Connect detector loop + (1), and detector loop – (3) to 24V input. More than 2 units on each loop: Use external 24V supply Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used.

Detection Loop Connection to

External timer

24V Output

LED

24V Input *

Page 32: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Control Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 32

5.5 BU-200 Remote Alarm Control Unit

Applies to AutroSafe only. The Remote Alarm Control Unit is used for remote / local alarm handling from predefined areas / zones. The main purpose of the unit is to facilitate alarm handling without disturbance of people and unnecessary calls to rescue services, for example, the fire brigade. The unit can send acknowledgement and reset to the Fire Alarm Control Panel. The Remote Alarm Unit is connected to the detection loop. Each loop unit can be connected to one Operation Zone. An Operation Zone can have one or more units, but requires separate 24V DC power.

PRESS HERETRYK K HERK NU S GLA SSE T

B RE AK G LA S S

BW-200

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule 24VDC

PRESS HERETRYK K HERK NU S GLA SSE T

B RE AK G LA S S

BW-200

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule 24VDC BU-200

Page 33: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Alarm Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 33

6. Alarm Units

6.1 Introduction

This chapter deals only with alarm units connected to the detection loop, not the ones that are connected to alarm outputs.

6.2 BBL-100 Beacon Indoor Addressable

Compact beacon for indoor use enclosed in an IP32C plastic casing. Reliable in operation and robust design. Simple mounting in all relevant directions.

- + - +

- Out + Out - In + In

Detection Loop

Page 34: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Alarm Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 34

6.3 BBR-130 Sounder Adressable with Base

BBR-130 is a combined detector base and addressable sounder that is connected directly to the detection loop.

Page 35: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Alarm Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 35

6.4 BBR-230 Sounder Indoor Addressable

BBR-230 is an addressable sounder that is connected directly to the detection loop.

- + - +

- Out + Out - In + In

Detection Loop

Page 36: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Alarm Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 36

6.5 BBQ-130 Sounder/Strobe with Base

BBQ-130 is a combined detector base and addressable sounder/strobe that is connected directly to the detection loop.

Page 37: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Alarm Units

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 37

6.6 BBQ-230 Sounder/Strobe Addressable

BBQ-230 is an addressable sounder/strobe that is connected to the detection loop.

- + - +

- Out + Out - In + In

Detection Loop

Page 38: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 38

7. Detectors for Special Requirements

7.1 AutroFlame IR Flame Detector BG-201

The detector is provided with a pluggable terminal block for ease of connection. Wire: Max. 2,5 mm2 / 14 AWG Interactive detection loop connection:

1 2 3 4

Input Output+

-

-

+

Terminal: 1 2 3 4

Page 39: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 39

7.2 AutroFlame IR Flame Detector BG-21

NOTE: For use with conventional fire alarm systems only.

Terminal Connection

1 + in

2 - in / out

3 +out / alarm resistor

4 alarm resistor

The above connection between detectors on a conventional loop will secure a fault activation at the panel if one of the connectors are unplugged.

Terminal Connection

1 + in

2 - in / EOL

3 alarm resistor / EOL

4 alarm resistor

Connection to the last/single detector:

Connection to the first/ between detectors:

1 2 3 4

I OU1 2 3 4

-

+ -

+

JJ5

LOOP

CONV

STANDARLEGACHIGH LOW SENS.

JJ

IN/OUT

- +LOO

CONVENTIONA

RALARMRESISTOR

Manufacturerlabel

Page 40: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 40

7.3 Fireray 5000

The FireRay® 5000 is a motorised infrared optical beam smoke detector. The detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for the detector. Function A is used (Alarm condition signalling input).

BN-303

BN 303

Page 41: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 41

BN-303

7.4 AutroSense Nano

The AutroSense Nano High Sensitivity Aspirating Detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for AutroSense Nano. Function A is used (Alarm condition signalling input).

PRESS HER ETRYKK HERK NU S G LA SSE T

B REAK G LA SS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-300

PRESS HER ETRYKK HERKNUS G LASSET

BREAK GLA SS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-300

Detection loop Out-+

BN-303

Detection loop In-+

5

6

+ -24V

24V

Ear

th

0V

2K910

AutroSenseNano

FIR

E PRE ALARM FAULT

24V DC

AutroSense Nano

Page 42: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 42

BN-303

7.5 AutroSense Micra 25 High Sensitivity Aspirating Detector

The AutroSense Micra 25 High Sensitivity Aspirating Detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for AutroSense Micra 25. Function A is used (Alarm condition signalling input, non-latching).

PRESS HERETRYK K HERK NU S G LA S SET

B RE AK G LA S S

AutroSense Micra 25

24 V DC

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o.

BN-300

PRESS HERETRYK K HERK NU S G LA S SET

B RE AK G LA S S

AutroSense Micra 25

24 V DC

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o.

BN-300

9102K

Detection loop Out-+

+

AutroSenseMicra 25

1 2 3 4+ + - -

BN-303

-24V

Detection loop In-+

Page 43: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 43

BN-303

7.6 AutroSense Micra 100 High Sensitivity Aspirating Detector

The AutroSense Micra 100 detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for AutroSense Micra 100. Function A is used (Alarm condition signalling input).

AutroSense Micra 100

24 V DC

PRESS HER ETRYKK HERK NU S G LA SSE T

B REAK G LA SS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-300

AutroSense Micra 100

24 V DC

PRESS HER ETRYKK HERK NU S G LA SSE T

B REAK G LA SS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-300

9102K

Detection loop Out-+

+

AutroSenseMicra 25

1 2 3 4+ + - -

BN-303

-24V

Detection loop In-+

AutroSense Micra 100

Page 44: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 44

BN-303

7.7 AutroSense 200 High Sensitivity Aspirating Detector

The AutroSense 200 detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for AutroSense 200. Function F is used (Fault, Pre Alarm and Alarm condition signaling input, non-latching).

PRESS HER ETRYKK HERK NU S G LA S SE T

B RE AK G LA S S

AutroSense 200

24 V DC

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-320

PRESS HER ETRYKK HERKNUS G LASSE T

B RE AK GLA S S

AutroSense 200

24 V DC

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-320

Page 45: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 45

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

24 VDC

PRESS HERETRYKK HERK NUS G LA SSET

B REAK GLASS

BN-320

AutroFlame X33/1

Alarmsignal

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

Power

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

24 VDC

PRESS HERETRYKK HERK NUS G LA SSET

B REAK GLASS

BN-320

AutroFlame X33/1

Alarmsignal

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

Power

24 VDC

PRESS HERETRYKK HERK NUS G LA SSET

B REAK GLASS

BN-320

AutroFlame X33/1

Alarmsignal

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

Power

-+

DetectionLoop In

-+

DetectionLoop Out

24V DC+-

oi TEST 3 (optional)

7.8 AutroFlame X33AF Multispectrum Infrared Flame Detector

The relay output is required only if the 24V supply for flame detectors needs to be controlled (e.g. latching alarms/faults). In this case BN-304 must be set to function G. If the 24V supply is to be permanently connected to X33AF, it is possible to use BN-303 function A, or BN-304 function A or G.

AutroFlame X33AF

BN-304

BN-304

Page 46: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Detectors for Special Requirements

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 46

7.9 Ex ia Approved Detectors

Ex ia-approved detectors can be connected to the system. The Ex-Barrier Unit (BZ-500) is used to separate the safe area from the hazardous (Ex) area. A maximum of 20 Ex ia-approved detectors can be mounted as a branch-off from the Ex-Interface Unit on the loop.

PRESS HERETRYKK HERKNUS GLASSET

BREAK GLASS

Detector

2

Ex ia-approveddetectors

Hazardous Area

Safe AreaEx-InterfaceUnit

Ex24VDC

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface uni t

Nr.

No.Loop DriverModule

EX TERMINALS

NON EX TERMINALS

BARRIERP&F 1.54

24 V

DIN RAILBZB-500

+

-

6 5

123

4

9

101112

8 7

+-

3 2 1

+-12 11 10

Output

+-

Detector on main loop

Branch-off-

-+Ex-Branch for Ex ia-approvedDetectors

+

Input

BZ-500

Safe Area

Ex-Area

Note: The Ex-Barrier Unit BZ-500 is shown upside down on the drawing.

Page 47: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 47

8. Discontinued Products

8.1 BBR-200 Programmable Electronic Sounders

SUBSTITUTE PRODUCT: BBR-230 The Electronic Sounder (BBR-200) has its own address / interface board and can be connected directly to a detection loop. The unit is powered from the detection loop. No external power supply is required.

PRE SS H ER ETRYK K HERKNUS G LAS SE T

BREAK GLASS

Electronic Sounderw/address/interface board

BBR-200

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface uni t

Nr.

No.

Loop DriverModule

Detection loop out

Detection loop in

Page 48: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 48

8.2 BBR-110 Addressable Socket Sounder

SUBSTITUTE PRODUCT: BBR-130 The Socket Sounder (BBR-110) is a combined detector base and addressable sounder. The unit is powered from the detection loop. No external power supply is required.

PRESS HERETRYKK HERKNUS GLASSET

BREAK GLASS

Loop DriverModule

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Socket SounderBBR-110

PRESS HERETRYKK HERKNUS GLASSET

BREAK GLASS

Loop DriverModule

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Socket SounderBBR-110

Detector loop inDetector loop out

- In: Terminal connection 1 - Out: Terminal connection - out on circuit board Common (+ In and + Out): Terminal connection 3 External LED: Terminal connection 4

Detection loop in

Detection loop out

Page 49: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 49

8.3 BN-300 Input Unit with SelfVerify

SUBSTITUTE PRODUCT: BN-303 BN-300 input unit is used to interface different types of signal devices of ON/OFF-type (for fire alarms) onto the detection loop.

PRESS H ERETRYKK HERK NU S G LA SSET

B RE AK G LA S S

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R AN N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-300

PRESS H ERETRYKK HERKNUS G LASSET

BREAK GLASS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R AN N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-300

1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 5. (-) Input 6. (+) Input

1 2 3 4 5 6

BNB-300/32

Page 50: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 50

8.4 BN-310 Single Relay Output Unit

SUBSTITUTE PRODUCT: BN-304 BN-310 single relay output unit contains a potential free change-over contact which can be activated from a detector or a combination of several detectors in alarm.

PRESS HERETRYKK HERKNUS G LASSET

B REAK G LASS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-310

PRESS HERETRYKK HERKNUS G LASSET

B REAK G LASS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

B R A N N A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-310

5. N.A 6. N.A 7. N.A 8. N.A 9. Normally open 10. Normally closed 11. Common

1.Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out

Loop

Relay contact

1 2 3 4

11 10 9 8 7 6 5

Not for use.

Page 51: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 51

5

6

N.O.

910Ohm

2KOhm

Class 1

6

5

910Ohm

N.C.2KOhm

Class 2

6

5 N.O. 2KOhm

Class 3

5 2KOhm

6

Class 4

N.C.

8.5 BN-201 Monitoring Input Unit

SUBSTITUTE PRODUCT: BN-303 The Monitoring Input Unit is used for monitoring of fault or other signal contacts from external equipment (technical alarms).

PRESS HERETRYKK HERK NU S G LA SSET

B RE AK G LA SS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

BR A NN A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-201

PRESS HERETRYKK HERK NU S G LA SSET

B RE AK G LA SS

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

LoopDriverModule BN- 35

BR A NN A LA R M

Tilpasningsenhet

FIRE ALARM

Interface unit

N r.

N o .

BN-201

Four different classes can be configured in order to be able to monitor different setups of the fault contact (s). Each class can be set to latching or non-latching operation.

Class 1: Normal Open contact with ‘activate’ resistor, fault monitored for open and short circuit.

Class 2: Normal Closed contact with ‘activate’ resistor, fault monitored for open and short circuit.

Class 3: Normal Open contact without ‘activate’ resistor, fault monitored for open circuit.

Class 4: Normal Closed contact without ‘activate’ resistor, fault monitored for short circuit.

1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 5. (-) Input 6. (+) Input

1 1 2 3 4 5 6

BNB-200/01

Page 52: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 52

5. (+) input A 6. (-) input A 7. (+) input B 8. (-) input B 9. Normally open 10. Normally closed 11. Common

1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out

Loop

Relay contact

1 2 3 4

11 10 9 8 7 6 5

8.6 BN-320 Interface with SelfVerify

SUBSTITUTE PRODUCT: BN-304/BN-305 The I/O unit BN-320 is connected to the detector loop to control, monitor or identify external equipment. Typical applications are: Interface for AutroFlame detectors Interface for AutroBeam 25

Page 53: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 53

8.7 BN-320/2 Door Control Unit

SUBSTITUTE PRODUCT: BN-305 The Door Control unit controls and monitors fire doors. The unit is connected to the detection loop, and powered from an external 24V DC power supply.

Switch 1 Closed Open Open Closed Switch 2 Open Open Closed Closed Status Door

Open Door in transition

Door Closed Illegal (fault)

PRESS H ERETRYKK HER

K NU S G LA S SE T

B REAK G LA S S

BN-320/2BN- 320

BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

FIRE DOOR

Trigging of electro-magneticdoorholder

Normallyclosedoutput.

CLOSING OFFIRE DOORS

Output

Input A Input B

24 VDC

PRESS H ERETRYKK HER

K NU S G LA S SE T

B REAK G LA S S

BN-320/2BN- 320

BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

FIRE DOOR

Trigging of electro-magneticdoorholder

Normallyclosedoutput.

CLOSING OFFIRE DOORS

Output

Input A Input B

24 VDC

Page 54: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 54

8.8 BN-320/4 Monitoring and Control Unit

SUBSTITUTE PRODUCT: BN-305 The Monitoring and Control Unit monitors and/or controls various external equipment such as control of fire dampers, ventilation valves, fans, lifts, plus fire and smoke hatches. The unit is connected to and powered from the detection loop. External equipment must have separate power supply.

PRESS HERE TRYKK HER KNUS GLASSET BREAK GLASS

BN-320/4

BN- 320 BRANNALARM

Tilpasningsenhet

FIRE ALARM Interface unit

Nr.

No.

Loop Driver Module

Output

Input A Input B

PRESS HERE TRYKK HER KNUS GLASSET BREAK GLASS

-BN- 320

BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

External Equipment

External

Page 55: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 55

8.9 BN-320/5 Sprinkler Control Unit

SUBSTITUTE PRODUCT: BN-303 The Sprinkler Control Unit is used for monitoring and control of sprinkler systems The unit is connected to and powered from the detection loop.

PRESS HERETRYKK HERKNU S G LASSET

BREAK G LASS

BN-320/5

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

Input A SprinklerFlowSwitch

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

PRESS HERETRYKK HERKNU S G LASSET

BREAK G LASS

BN-320/5

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

Input A SprinklerFlowSwitch

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Page 56: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 56

8.10 BN-330 Interface Unit for Conventional Loops

SUBSTITUTE PRODUCT: BNB-331 Applies to AutroSafe only. The Interface Unit for Conventional Loops BN-330 consists of a BNB-330 module* mounted on a DIN-rail inside a PCM-box. The conventional detectors are connected to a two-wire sub loop. The sub loop is monitored for broken line by an end-of line unit BNY-330. The interface unit must have a separate 24V supply.

PRESS HERETRYKK HERK NU S G LA S SE T

B RE AK G LA SS

BN-330

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.LoopDriverModule

+ -

Conventional Loop

24VDC

End-of line unit BNY-330 P RE SS H ER ETRY KK HER

K NUS G LASSE T

B REAK G LA SS

* Variant: The internal Conventional Loop Interface Module BNB-330 is mounted on a DIN-rail onto other internal modules inside the Fire Alarm Control Panel / Controller where it is powered with 24VDC.

BNB-330Module

+

-

Conventional Loop

End-of line unit BNY-330

PRESS H ER ETRYKK HERKNU S GLAS SE T

B RE AK G LAS S

Terminal Signal 1 + AL-Com in

2 - AL_Com in

3 + AL-Com out

4 - AL_Com out

5 + 24V Input

6 0V

7 Conventional loop 15V/24V select

8 T-output / Open collector

9 + conventional loop

10 - conventional loop

Page 57: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 57

 

8.11 AutroSense 75 Aspirating Smoke Detector

P RESS H ER ETRYK K HERKNUS G LAS SE T

BREAK GLASS

AutroSense 75(BW-75/AUT)

24 VDC

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

1 +

2 +

3 -

4 -

+ 24 V DC

+ 24 V DC

0 V

0 V

1 +

2 +

3 -

4 -

+ 24 V DC

+ 24 V DC

0 V

0 V

Loop

Loop

(to next detector)

24V DC out

+ -

24V DC in

+ -

- + Loop in

Loop Connection

Connection to 24V DC

AutroSense 75 (BW-75/AUT)

Page 58: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 58

8.12 AutroBeam 25 Infrared Beamdetector

24 VDC

PRESS HERETRYKK HERKNUS GLASSET

BREAK GLASS

BN-320

AutroBeam 25

Alarmsignal

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

Reflector

1 2 3 4

11 10 9 8 7 6 5 C NC NO - + - +

+ + - -

Main loop in + -

2k

+- 24VDC

12345678

2k 910

+-24V

5

3

7

4

8

6

AutroBeam 25

ALARMRELAY

FAULTRELAY

+ Main loop out-

BN-320

Page 59: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 59

8.13 AutroBeam 100 Infrared Beamdetector System

SUBSTITUTE PRODUCT: FIRERAY 5000

24 VDC

PRESS HERETRYKK HERKNUS GLASSET

BREAK GLASS

BN-40A/3

Alarmsignal

AutroBeam 100Receiver

AutroBeam 100

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

BN- 320BRANNALARM

Tilpasningsenhet

FIRE ALARMInterface unit

Nr.

No.

Loop DriverModule

AutroBeam 100Transmitter

AutroBeam 100AutroBeam 100

(Drawing No. bs-1160)

Power

Fire Alarm Control Panel

Page 60: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Discontinued Products

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 60

Page 61: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Reader’s Comments

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

9. Reader’s Comments Please help us to improve the quality of our documentation by returning your comments on this manual: Title: Connecting Loop Units, Interactive Fire Detection Systems,

Ref. No.: 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21

Your information on any inaccuracies or omissions (with page reference):

Please turn the page

Page 62: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Reader’s Comments

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Suggestions for improvements

Thank you! We will investigate your comments promptly.

Would you like a written reply? Yes No

Name: ------------------------------------------------------------------------------------------------

Title: ------------------------------------------------------------------------------------------------

Company: ------------------------------------------------------------------------------------------------

Address: ------------------------------------------------------------------------------------------------

------------------------------------------------------------------------------------------------

------------------------------------------------------------------------------------------------

Telephone: ------------------------------------------------------------------------------------------------

Fax: ------------------------------------------------------------------------------------------------

Date: ------------------------------------------------------------------------------------------------

Please send this form to: Autronica Fire and Security AS

N-7483 Trondheim

Norway

Tel: + 47 73 58 25 00

Fax: + 47 73 58 25 01

www.autronicafire.com

Page 63: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Reader’s Comments

Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS

Page 64: Connecting Loop Unitsproduct.autronicafire.com/fileshare/fileupload/... · Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21,

Autronica Fire and Security is an international company, headquartered in Trondheim, one of the largest cities in Norway. The company is owned by United Technologies Corporation and employs more than 319 persons with experience in developing, manufacturing and marketing of fire safety equipment. Our products cover a broad range of systems for integrated solutions, including fire detection systems, integrated fire and gas detection systems, control and presentation systems, voice alarm systems, public address systems, emergency light systems, plus suppression systems. All products are easily adaptable to a wide variety of applications, among others, hospitals, airports, churches and schools, as well as to heavy industry and high-risk applications such as power plants, computer sites and offshore installations, world wide. The company's strategy and philosophy is plainly manifested in the business idea: Protecting life, environment and property.

Quality Assurance

Stringent control throughout Autronica Fire and Security assures the excellence of our products and services. Our products are CE marked and developed for worldwide standards and regulations, and conform with the CEN regulation EN54. Our quality system conforms to the Quality System Standard NS-EN ISO 9001:2000 and is valid for the following product and service ranges: marketing, sales, development, engineering, manufacture, installation, commissioning and servicing of suppression, integrated fire and gas detection and alarm systems, plus petrochemical, oil and gas instrumentation systems for monitoring and control.

Autronica Fire and Security AS Headquarters, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01. Head Office Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99. Division Oil & Gas, Oslo, Norway. Phone: + 47 23 17 50 50, Fax: + 47 23 17 50 51 Division Oil & Gas, PO Box 416, Farnborough GU14 4AT, UK. Phone: + 47 51 84 09 00, Fax: + 44 84 52 80 20 55 Division Maritime, Suppression/New Build Detection & Alarm. Norway. Phone: + 47 31 29 55 00, Fax: + 47 31 29 55 01 Division Maritime, After Sales/Service Detection & Alarm, Norway. Phone: +47-73 58 25 00, Fax: +47-73 58 25 01

Visit Autronica Fire and Security's Web site: www.autronicafire.com


Recommended