+ All Categories
Home > Documents > Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding...

Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding...

Date post: 09-Feb-2020
Category:
Upload: others
View: 26 times
Download: 2 times
Share this document with a friend
12
TECHNICAL OVERVIEW Considerations for Instrument Grounding
Transcript
Page 1: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

T E C H N I C A L O V E R V I E W

Considerations for Instrument Grounding

Page 2: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 2Find us at www.keysight.com

Many people have heard of the term "grounding", but few fully understand its meaning and importance. Sometimes, even experienced electricians do not treat grounding as a serious issue. The impact of an incorrect or absent grounding ranges from noise interference. resonance or humming during the use of electrical equipment to the worst case where electricity leakage through the chassis causes personal injury or damage to instrument components. Grounding, therefore, is a very practical issue that should be dealt with properly. For those who operate electrical equipment frequently, a complete understanding of grounding theories and applications is necessary in order to become a best-in-class technician.

In the eighteenth century, Benjamin Franklin performed the famous kite experiment to observe how lightning in the sky was conducted to the earth. This experiment led to the invention of lightning rods to avoid lightning strikes. From then on, people began to realize that the vast ground under our feet is a huge electrical conductor. It may not be the best conductor, but it is certainly a good one. It is so enormous in size that it can sustain a tremendous amount of current. That is why the voltage level of the ground is set to be zero. Safety regulations require that all metal parts which do not carry electricity should be kept at zero or the earth voltage level.

There are several reasons for grounding. Some are for safety purposes, and some are for maintaining circuit stability. The following are some examples:

– Power system grounding: As you can see in Figure 1. this design is to prevent the secondary side from being damaged by the high voltage on the primary side, as the current will be conducted to the ground through the Grounding Wire to protect human lives.

– Instrument grounding: By connecting the equipment or chassis to the ground, operators can be protected from electric shocks if there is electricity leakage.

– Signal grounding: A zero voltage reference or a loop-back path is provided for all integrated signals to ensure proper operation or accurate measurements.

– Shielded grounding: This is used to prevent static electricity from being accumulated. Ground isolation or conduction can help to reduce noises and electro-magnetic interference. Examples include shielding rooms, cables, wirelines, guarded terminals of instruments, transformers and filters.

Figure 1.

Transformer

Secondary

Low voltage

Grounding wire

Grounding electrodeEarth ground

High voltage

Primary

Page 3: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 3Find us at www.keysight.com

Types of Instrument Grounding

Figure 2 shows a commonly used instrument grounding on inputs and AC power. In this case. the input signal ground is connected to the power ground and when you are making a measurement, it is important to make sure that the input signal ground is not short-circuited directly to any point where there is a voltage difference to the earth ground. This is very common when measuring commercially available low-cost circuits. To reduce costs, these circuits usually do not use power isolated transformers. Instead, the AC power is directly connected to the circuit. As a result. a loop is formed between the circuit itself and the earth ground, and a voltage difference occurs. If the AC power happens to be plugged in the reverse way, or a considerable voltage difference exists between the neutral line and the earth ground, the combined factors could lead to very unpredictable results. Therefore, caution must be exercised before the input is connected for measurement.

To avoid the problem described above, some instruments provide floating inputs as shown in Figure 3. Each of the inputs is floating from the earth ground. Ideally, as long as the voltage difference between these two inputs is within an acceptable range, the inputs can be connected to any voltage point.

Figure 4(a) and 4(b) show some common instruments for output devices. For DC or low frequency generators, the design shown in 4(a) is usually adopted, while for high frequency (RF) generators, the model in 4(b) is used. Therefore, special attention is required to avoid the problem described in item (1) when performing a high frequency measurement. Otherwise, the voltage difference and conflict may cause damage to the input and output of instrument circuits.

Figure 4.

Figure 2. Figure 3.

Instrument case

AC plug

Signal ground

Power transformer

InputSensing

electronics and

display

+

Instrument case

AC plug

Shieldground

Power transformer

InputSensing

electronics and

display

+

Instrument case

AC plug

Case ground

Power transformer

Output Generating electronics

Instrument case

AC plug

Shield ground

Power transformer

OutputOutput

conditioningelectronics

(a) (b)

Page 4: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 4Find us at www.keysight.com

Guidelines for Instrument Grounding

While there are some guidelines for grounding, there is no hard and fast rule. In practice, it is difficult to follow all the guidelines. Rather, it is dependent on the environment and applications. For instance, before the measurement is performed, evaluations should be made to decide whether the floating method should be used. The following are some general guidelines:

– When dealing with different kinds of grounding such as shielded grounding, power grounding and signal grounding, make sure that they are guided to their own paths to avoid interaction.

– Keep the impedance of the ground line low and the path short. – Avoid multiple ground loops, which may disturb current flows. – Isolate the heavily loaded ground current loop from the small signal loop.

Let’s take a look at the example in Figure 5. For a well-designed power supply equipment. the voltage ripple between output A and B should be very small. However, if for convenience sake, point C instead of point D is used as the signal’s ground reference, a significant pulse voltage will occur and show up on the output circuit even when the resistance between point C and D is small. This is because the transient current in charging or discharging the capacitors is usually very high. As a result, as soon as the power is on, damage can be caused to the connected circuits or instruments.

A

B

D

C

Voltage regulator

Figure 5.

Page 5: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 5Find us at www.keysight.com

Common Causes of Poor Grounding

The AC power (such as 110 V) socket does not provide the ground line (green). as shown in Figure 6. The earth pole on the plug is usually the longest so that it can be connected to the ground first when the AG power cord is plugged into the socket.

The actual impedance to the ground is too high which does not comply with electrical regulations (please refer to the appropriate regulations in your country). Take the example of the third level regulation of grounding. When the AG voltage to the ground is above 300 V. the impedance to the ground must be less than 10 Ω. If the AG voltage to the ground is under 150 V. the impedance to the ground should be within 100 Ω.

The neutral line is mistakenly used as the ground line and these two lines are short-circuited together on the socket. Under normal conditions, the voltage difference between the neutral line and the ground line on the socket must be within 1.0 V, but this should not be accomplished by short-circuiting these two lines together.

Swap the hot line and the neutral line arbitrarily. Take Figure 7 as an example. Equipment A sends out signals while equipment B receives signals. Suppose the AG power sockets to which Equipment A and B are connected do not provide the ground line. and the hot line and neutral line are swapped on one of the equipment. Since equipment A and B both have noise filters installed. a 110 V AG loop is therefore formed accidentally even when the power switch of A and B is not connected.

Figure 6. Figure 7.

Equipment A

Equipment B

Earth

Each pole in the figure represents:L: Line, hot or active conductorN: Neutral or identified conductorG: Ground or earth conductor

NL

G

5-15R

Page 6: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 6Find us at www.keysight.com

Summary

When installing the equipment in a building, make sure to have an electrician check on the impedance to the ground and the grounding device to see if they comply with electrical regulations. 8 AWG wireline should be used as a minimum wire type for instrument grounding.

Use the three-pole AC power socket for the instrument. Make sure the polarity of the hot line and the neutral line is correct (see Figure 6). The voltage difference between the neutral and the ground lines should be less than 1 V. At the socket end. the impedance between the neutral and the ground lines should be lower than 1 Ω.

Find out the appropriate way to do measurements. i.e. whether the instrument's input/output terminals should be grounded or be floating.

Check the stability of the AC power (ex. +5% to –10% within 120 V) and whether there are unpredictable impulses, which may cause the measurement to fail or even damage the instrument. Generally, the transient voltage fluctuation should not exceed ± 15% within 120 V and the voltage should be restored to 120 V within 0.5 second. The total harmonic component should be less than 5%.

Verify the grounding of the equipment or device under test (OUT). If voltage differences exist among equipment, connecting them together may cause conflicting situations. The sudden pulses generated when the equipment is powered on may also damage vulnerable modules. If this happens, the links between the equipment and devices under test should be disconnected before the AC power is turned on. Each equipment and OUT should be reconnected only after all equipment and devices have stabilized. In so doing, the possibilities of damage can be minimized. However, this is not the way to eradicate the problem completely. The best solution is to identify the root causes and fix them.

Reduce and remove unwanted static, interference and noise through proper grounding.

Keysight Test and Measurement Service Centers have been providing comprehensive and precise repair and calibration services to customers for many years. Our pursuit of quality and technical innovation enables us to offer better services to our customers. By sharing this article with you, we hope to help you improve the accuracy of measurements and the life span of your instruments.

Page 7: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 7Find us at www.keysight.com

Appendix 1: AC Power Control Panel

In most countries, electric power companies will provide building occupants AC power electricity with a Y connection configuration (Figure 8), which offers three live/hot lines (a), (b), (c) and one neutral line that is colored white. This configuration is called a 3-phase 4-wire AC power system. The voltage between either one of the live lines and the neutral line is about 108 to 126 V, while the voltage between the two live lines is about 187 to 218 V. The neutral line inside the AC power transformer is connected to earth, which — in the event of an AC power transformer failure — bypasses a potentially damaged current into the ground, thus preventing any damage to the occupant’s equipment. This neutral line also performs as a reference point for balancing three phase voltages.

Builders should provide one independent grounding line (G) colored green, with a resistance of about 1 Ω, connected to the AC power control panel. It is not the responsibility of the electric power company to provide this. In many cases, either the builder or the occupant may overlook this step, resulting in a missing grounding wire, or the neutral line being mis-used as the ground line.

The neutral line (N) should not be used as the ground line. The key concern is that the dynamic loading current. which flows through the neutral line, creates a voltage drop between it (N) and the earth. If the loading current is high, then the voltage drop will be significant. However, in normal circumstances there is no loading current in the ground line and the voltage drop between (G) and the earth is zero. So when we connect the instrument chassis to the ground line, we can obtain an extremely stable and safe reference plane. Moreover, if electricity leakage or ESD occurs, the current will flow to the earth, thereby protecting the instrument. Usually, the voltage drop between (N) and (G) should be within 1 volt AC; it is impossible to achieve zero volt. For precision instrument measurements, if the ground line is left open or is connected to the neutral line, this means we have failed to set up an independent grounding for the instrument. Hence, an ideal grounding reference level required for safe and stable measurement cannot be achieved. In the worst case, when the voltage difference between the instrument chassis and the ground is too high, it may damage the other instrument or the device under test in the same measurement system.

Neutral line (N): Dynamic current flows through it. If wire resistance is high, there will be a significant voltage drop with respect to the earth. (i.e. there is voltage between N and G)

Ground line (G): Normally there is no loading current and voltage drop is zero with respect to the earth. Ground line is connected to the instrument chassis, which protects the operator and offers an ESD bypath.

Figure 8.

Mains supply110 V/ 220 V

Power panel

(a) Live/hot line

(b) Live/hot line

(c) Live/hot line

(N) Neutral line

(G) Ground line

(a) (b) (c)

(G)(N)

Page 8: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 8Find us at www.keysight.com

Appendix 2: Guide on Testing Power

This is to remind you once again. Please check the AC alternating current (use 120 V as an example) and grounding condition prior to the use of an instrument. If the following basic requirements are not met, please do not connect it to the power source. Otherwise, the instrument is extremely vulnerable to damages. This may even lead to dangers to human body.

Step 1Make sure there are 3 holes in the outlet. that is, holes for the Live wire, the Neutral wire and the Ground wire. Do not put on the plug if the outlet is not with 3 holes. (As on Figure 9)

Step 2Make sure the polarity of the 3 wire outlet (Figure 9) is correct: can be tested with

– Polarity Tester on Figure 10 to find the polarity via the red, white and yellow lamps or

– Multi-meter and refer to the test in Step 3

Step 3Use a multi-meter to test the followings: The voltage between the Live wire and the Neutral wire should be in the range of 108 to 126 V. The Voltage surge should not exceed 120 V ± 15%. The voltage between the Neutral wire and the Ground wire should be less than 1.0 V. At the same time. the change should not be more than 1.0 V no matter whether the instrument is on or not. (As on Figure 11)

Figure 9.

Figure 10.

Figure 11.

L: Live WireN: Neutral wireG: Ground wire(Front view of the wall socket)

NL

G

(b)(a)

Holes facing the power source lead<1.0 V

108 ~ 126 V

Page 9: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 9Find us at www.keysight.com

Question 1Why is instrument grounding so important?

Question 2Why is the polarity and grounding of AC power source so important?

Question 3What is the threat of AC power source on the Device-under-test to the instrument?

Figure 12.If we only use the Line and the Neutral Conductor of AC 120 Volts but do not really connect the Ground Wire, voltage will exist between the Ground Wire (and the chassis) and the ground! This is because there is still stray capacitance between the Neutral conductor and the Ground Wire of the power cable or the primary winding of the transformer. Or, there is filtering capacitor for suppressing noise. As Vg1 or Vg2 on the diagram, it may be as high as 20 V to 60 V! If the Live and the Neutral wires are reversely connected in one of the instrument Vg1 ≠ Vg2. Simply imagine what will happen if two objects with different electric potential are put together.

When Vg1 and Vg2 exist, the signal (to the ground) output of Instrument 1 is no longer smaller than v1. lnstead, it is (vl+Vgl). This signal is strong enough to seriously damage the input circuit of Instrument 2. The signal will not only circulate between the output ends of Instrument 1 and input ends of Instrument 2. Ig will flow through the floating ground wire. If the circulation is too strong, permanent damage will be caused! Therefore, only perfect grounding can solve this problem. Vg1 = Vg2 = Vg3 = 0 and makes Ig = O.

Figure 12.

Instrument 1

120 V AC 120 V AC+ HI

— Lo

HI +

Lo — V1

Instrument 2

GNDGND

Vg1. lg Vg2.

Hot line

Hot line Neutral line

Neutral line

GND line

Problem:Reversed live and neutral connection

Problem:No grounding

Problem:Noise, harmonic wave, spikes and voltage fluctuation

Problem:Over-ranged ground resistance and poor grounding

Appendix 3: Serious Damage comes from incorrect polarity and grounding of AC 3-Wire

Page 10: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 10Find us at www.keysight.com

120 V AC+ HI

— Lo

GND line

Instrument 2signal receiver

GND

Vg3. lg Vg2.

Hot line

Neutral line

120 V AC

Device-under-test

Figure 13.

Figure 13.When the Device-under-test is an active component or circuit it may sometimes rely on 120 V AC (but not battery) as a source of power. This device usually uses only 2 wires (Live wire and Neutral wire) and is not connected to the ground due to costing and commercial use factors. There may not be even any isolating transformer in the circuit. Therefore, there may be an unexpected Vg3 voltage. This usually happens in tests using LNB and CATV Amplifier. Without sufficient care, Ig will cause damages.

Page 11: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

Page 11Find us at www.keysight.com

H2H1

L2 L1C

Device under test

Instrument 1signal source

Instrument 2signal analyzer

Figure 15.

Instrument (2)Instrument (1)(v signal)

(H1) (H2)

(L2)(L1)

(30 to 60 V AC)

Device-under-test

When taking measurements, if 11 and L2 are open while HI and H2 are connected, then an unexpected voltage of 30 V to 60 V AC will flow into the loop indicated here and may create damage. However, if both instruments are well grounded, there will not be 30 V to 60 V AC. Only a V signal will exist and no damage source will appear.

Assuming that instrument (1) chasis is not grounded properly, then 30 V to 60 V AC may exist on the chasis

Figure 14.

Figure 14.If the instrument chassis is not grounded. When there is an AC voltage through it (the operator sometimes may not feel the electricity when he touches its chassis). How can the instrument be damaged under such conditions?

The facts are:If the chassis of both instruments (1) and (2) are grounded correctly, both instruments will not have any voltage difference with respect to the earth.

Because the instrument is using a 3-pronged power source, the ground line inside the power cord is located in parallel between the live/hot line and the neutral line, and this will create a stray capacitance between these 3 wire lines. So if the neutral line, instead of the ground line, is connected to the earth, a voltage of about 30 V to 60 V will be coupled to the ground line with respect to the earth. This voltage will appear on the instrument chassis and may injure the operator or damage any DUT and other connected instruments.

When any DUT or other instruments connected to the instrument are not grounded, this unexpected 30 V to 60 V voltage will find another circuit loop to release the power. It will generate a current surge and will damage any sensitive DUT or instruments in the circuit loop. However, if the chassis (ground line) of both instruments are connected beforehand to form an equal potential, the destructive current loop will not result between instruments (1) and (2). This explains why operators do not always find damage to their instruments, even though they do not take instrument grounding precautions. The key principle is that we should connect LI to L2 before connecting HI to H2 for setting up a good reference plane.

Page 12: Considerations for Instrument GroundingTransformer Secondary Low voltage Grounding wire Grounding electrode Earth ground High voltage Primary. Find us at Page 3 Types of Instrument

This information is subject to change without notice. © Keysight Technologies, 2014 - 2019, Published in USA, February 22, 2019, 5989-9200EN

Page 12Find us at www.keysight.com

Learn more at: www.keysight.comFor more information on Keysight Technologies’ products, applications or services,

please contact your local Keysight office. The complete list is available at:

www.keysight.com/find/contactus

Check items Expected specification Tools Check resultsAC power quality

1 3-wire polarity AC power outlet, N-G voltage less than 1 VAC (but N & G cannot be shorted on the outlet), N-L voltage 120 VAC.

– DMM – PGT-602 – Receptacle Tester1933 – GAM-2A

2 Voltage and impedance between neutral and ground line (under full load)

Should be less than 1 VAC and 1 Ω. Grounding wire specification 8 AWG, independent ground wiring.

– PGR75 – Fluke 434 – PGT-602

3 Stable voltage, single phase 120 volt

120 V or 208 V +5%, –10%(i.e. 108 V to 126 V, 187 V to 218 V)

– Fluke 434 – RPM 901

Phase A to neutral:Phase B to neutral:Phase C to neutral:

4 Frequency 60 cycle (Hz) ± 0.5 cycle – Fluke 434 – RPM 901

5 Surge and sag voltage Less than 120 V ± 15%, can endure for max. 0.5 Sec (30 cycle)

– Fluke 434 – RPM 901

6 Impulse, transient voltage If transient voltage > 100 VAC (up to 200 us), equipment may damaged. Normally, ETE can stand for 150% to 200% VAC with max. 0.2 second

– Fluke 434 – RPM 901

7 Total harmonic Less than 5% – Fluke 434 – RPM 901

8 Power factor 0.8 ~ 0.9 – Fluke 434 – RPM 901

9 3-phase unbalance ratio Less than 2.5% – Fluke 434 – RPM 901

10 3-phase load unbalance ratio Each phase max. 5% ~ 20% – Fluke 434 – RPM 901

Environment11 Temperature 20 ºC –25 ºC best with 23 ºC12 Humility 40% ~ 60% best with 50% Testo 61513 Air dust The particle quantity should be less than 45,000

pieces within each cubic fee for those particle size > O.5 Micron

14 Vibration Less than 0.5 g15 EMI Less than 0.5 V/M,

Frequency range: 14 kHz ~ 1 GHzESD process

16 ESD floor, desk, chair, mat, cloth, hat, shoe, wrap, bag, transit box, etc.

Floor resistance > 150 KΩ, < 20,000 MΩ. Refer to specific product spec, the surface resistance are between 103 to 1010 Ω, please refer to product data sheet.

17 ESD fan By necessary18 ESD charge measurement For specific product, it may be able to just endure

several volts ESD only – ACL300 – ME-2B2A

N L

G


Recommended