Introduction What is ECOHEAT?
A software which could be used to calculate/estimate the Cooling & Heating Load needed for a particular space.
Main usage is to assist the designer in sizing the indoor units.
Developed based on the most recent ASHRAE handbook.
Available MethodsTransfer Function Method
Involves many calculation steps.More oriented to average hourly cooling load than peak design
load.Total Equivalent Temperature Differential (TETD) method
Needs a lot of user judgment (e.g. time averaging period) primary usefulness has always been to the experienced engineer.
Cooling Load Temperature Differential (CLTD) methodSingle step technique that proceeded directly from raw data to
cooling load without intermediate conversion of radiant heat gain to cooling load.
Factors such as CLTD, cooling load factor (CLF) are limited to specific building types and conditions-> invalid beyond the range of applicability.
Available Methods 1996 –ASHRAE Load Calculations Technical Committee funds RP-875;
goal is to replace existing methods with:Heat Balance Method (most fundamental method)Radiant Time Series Method (simplified method, intended to be
derived directly from HBM, but be much easier to use; a “spreadsheet method”)
2001 –HBM and Radiant Time Series (RTS) Method are published in ASHRAE Handbook of Fundamentals.
The primary benefit of HB and RTS calculations is their somewhat reduced dependency on purely subjective input in conventional methods:determining a proper time-averaging period for TETD/TA; Ascertaining appropriate safety factors to add to the rounded-off TFM
results;determining whether CLTD/CLF factors are applicable to a specific
unique application.
RTS Concept / TheoryWhat Radiant Time Series does??
Used to convert the radiant portion of heat gain to cooling load. (by a series of coefficients dependent on building type)
Internal Heat GainResidential Calculation: utilises correlation
to get the total heating/cooling load.Function of number of people, floor area.
Internal Heat GainNon-Residential Calculation: treat the
internal heat gain individually More EXACT !!!
Consists of peoples, lighting, PCs, monitors.It is general, can be used for residential
applications as well.
Surface ElementsWall/Door/Window Exterior : Wall/Door/Window
exposed to direct sunlight.Wall/Door/Window Interior : Wall/Door/Window
NOT exposed to direct sunlight.Floor:
On-Grade: Attached to earth (adiabatic for cooling load, no infiltration)
Below Grade: Attached to underground (adiabatic for cooling load, no infiltration)
Above Grade: Floor above earth level (infiltration happens, heat transfer occurs)