Ventilation Plant Report Name of user: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE Location: TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH Report Number: Policy Number: Contract Number: E35223013258 NV09796703 Side 1 of 10 Contractual date of next thorough examination 26-APR-2022 Competent Person Allianz Engineering Date of commencement of examination and tests 26-OCT-2021 26-OCT-2021 Date of Report Engineer Surveyor Andrew Allen If you have a query about this report please contact Andrew Allen on 07870 231604 or by email at [email protected]. For all other enquiries please contact our support team on +44(0) 1483 265837 or +00353 (0) 1 613 4081 Allianz Engineering Inspection Services Ltd, 57 Ladymead, Guildford, Surrey, GU1 1DB Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland, Allianz plc trading as Allianz is regulated by the Irish Financial Regulator. Registered in Ireland Number143108 www.allianzengineering.co.uk V810c Section 1 - Executive Summary and Declaration System Plant Number LEV 043 Ventilation System Type Local Exhaust Ventilation Regulations Applicable COSHH (Control of Substances Hazardous to Health) Examination Type Thorough Examination and Test Declaration (UK only) The Thorough Examination and Test has been conducted regarding the requirements of the current edition of The Health and Safety Executive (HSE) guidance HS(G)258 - Controlling Airborne Contaminants at Work Overall Assessment of Control PASS System Description Multi-point (3) Local Exhaust Ventilation System, incorporating 'air mover' (1) and 'air cleaner' (1), controlling Nickel, Silver and Grinding Medium Dusts produced from Knife Serrator's and Grinder
Transcript
Page 1: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Name of user: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARELocation: TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH Report Number:

Policy Number:Contract Number:

E35223013258NV09796703

Side 1 of 10Contractual date of next thoroughexamination

26-APR-2022 Competent PersonAllianz Engineering

Date of commencement of examinationand tests

26-OCT-2021

26-OCT-2021Date of ReportEngineer Surveyor

Andrew AllenIf you have a query about this report please contact Andrew Allen on 07870 231604 or by email at [email protected]. For all other enquiries pleasecontact our support team on +44(0) 1483 265837 or +00353 (0) 1 613 4081Allianz Engineering Inspection Services Ltd, 57 Ladymead, Guildford, Surrey, GU1 1DBAllianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United KingdomAllianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland, Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.Registered in Ireland Number143108www.allianzengineering.co.uk

V810c

Section 1 - Executive Summary and Declaration

System Plant Number LEV 043

Ventilation System Type Local Exhaust Ventilation

Regulations Applicable COSHH (Control of Substances Hazardous to Health)

Examination Type Thorough Examination and Test

Declaration (UK only) The Thorough Examination and Test has been conductedregarding the requirements of the current edition of TheHealth and Safety Executive (HSE) guidance HS(G)258 -Controlling Airborne Contaminants at Work

Overall Assessment of Control

PASS

System Description

Multi-point (3) Local Exhaust Ventilation System, incorporating 'air mover' (1) and 'air cleaner' (1), controlling Nickel, Silverand Grinding Medium Dusts produced from Knife Serrator's and Grinder

Page 2: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 2 of 10 Report Number: E35223013258

810c

Section 2 - Thorough Examination and Test Results

'A' - Defects

Defects affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. 'Immediate' attention is required.

1. None

'B' - Defects

Defects not affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. These defects should be rectified before the next Thorough Examination and Test.

1. None

'C' - Recommendations

Recommendations providing additional value and information relating to the Ventilation System Management.

1. The following Ventilation system Management documentation has not been presented:Workplace Air Monitoring/SamplingVentilation System User ManualCommissioning/Initial Appraisal ReportThe above should be provided to evidence compliance with the Regulations.

2. The client has made attempts to source the Commissioning Report and User Manual but has been unable to do so.

3. Air Cleaner - No record of filter efficiency and concentration of the contaminant in the return air testing has been seenwhere the LEV system includes arrangements for re-circulating into workplace areas. Relevant testing should be conductedand records made available. The client has made a written statement to Allianz indicating that the process is only used 1 to 2hours a week.

4. Air Mover - Technical Specification of the Air Mover and associated Motor Manufacturers details have not been fullyverified, these should be provided to assist in completing section 3 of this report.

5. Capture Hood - Fixed Capture x 3

6. Capture Hood - No airflow indicator installed at the Capture Hoods. Further guidance for the use of airflow indicators canbe found in HS(G) 258, Controlling Airborne Contaminants at Work. Consideration should be given to the provision of asuitable airflow indicator, which would indicate to the operator that the system is working effectively.

Inaccessible Parts/Limitations (at the time of the Thorough Examination Test)

The following were not presented, accessible or available at the time of the Thorough Examination and Test but did notprevent us from providing an accurate assessment of the ventilation system.

1. none

Ventilation System Set-up Conditions at the time of the Thorough Examination and Test

admin
Sticky Note
See notes bookmark
Page 3: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 3 of 10 Report Number: E35223013258

810c

Normal Operation and Special Condition - LEV operating and fully functional with the process not in use simulatingcontaminant emission utilising smoke

Detail of the Intended Operating Procedure (IOP)

1. At the time of inspection, there was no written Intended Operating Procedure (IOP) presented.The system was therefore tested with two points open as verbally indicated as the normal operating procedure.

Page 4: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 4 of 10 Report Number: E35223013258

810c

Section 3 - Ventilation System Identification

Manufacturer Serial Number Location

Not established NOT ESTABLISHED Handle Department

Total Number of Extraction Points Available 3

Maximum Number of Points that can be used at any one time (system design and use specification) 3

Exhaust Air Direction Number of Air Movers Number of Air Cleaners

Workplace 1 1

Air Mover(s)

Identification Number: 1

Manufacturer: Not established

Serial Number: Not established

Type: Centrifugal

Rotation (from drive end): Clockwise

Size (diameter): (m) 0.20

Volumetric Flow Rate (Manufacturer Specification):(m3s-1)

Not established

Speed (Manufacturer Specification): (rpm) 3450

Motor(s)

Identification Number: 1

Manufacturer: Baldor

Serial Number: Not established

Speed (Manufacturer Specification): (rpm) 3450

Power (Manufacturer Specification): (kw) 0.55

Invertors/Variable Speed: Not applicable

Air Cleaner(s)

Identification: 1

Medium: Fabric filter

Collector Type: Collection tray

Medium Efficiency (Manufacturer Specification): (%) Not established

Page 5: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 5 of 10 Report Number: E35223013258

810c

Section 4 - Examination and Test Result Summary

Examinations and Test Techniques Undertaken

Visual, Tyndall Beam, Smoke, Velocity Measurements, Pressure Measurements

Qualitative Testing Results PASS

Comments 1. Qualitative testing using method as detailed in HS(G)258, including observations of the process andcontaminant sources, effective containment of the hazardous substance, and the way in which theoperators use (or simulation of use) of the LEV system found the visual appraisal of the level of control tobe satisfactory.

Quantitative Testing Results PASS

Comments 1. Quantitative testing carried out on the LEV System was found to satisfy the guidance found in HS(G)258,Table 9 and Table 12 for this type of Hazardous Substance.

2. The comparison of the ventilation system layout/process from the last thorough examination & testwas observed to be unchanged with system performance found to be at approximately the same levelsas recorded at the previous or benchmark examination and test with specific capture/transport velocityfound to be approximately the same.

Ventilation System Performance Results PASS

Comments 1. With the exception of the findings as detailed in Section 2 of this report, the ventilation systemperformance was assessed to provide satisfactory adequate level of control subject to the correct use ofthe LEV Plant.

Hood Examination Results, includingi) Hood types usedii) Effective Capture Distances (moveable hoods)

PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Ducting Examination Results (including exhaust stack, if applicable) PASS

Comments 1. With the exception of the findings as detailed in Section 2 of this report, we observed that the ductingassociated with the LEV System did not display any signs wear or tear and operating in a satisfactorymanner.

Air Mover Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Air Cleaner Examination Results PASS

Comments 1. Filter Media Cleaning system operation witnessed at the time of the examination and test.

Page 6: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 6 of 10 Report Number: E35223013258

810c

Page 7: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 7 of 10 Report Number: E35223013258

810c

Section 5 - Process Identification

Process Function(s) Knife Serrator's and Grinder

Process Machine Serial Number(s) Not established

Hazardous Substances Nickel, Silver and Grinding Medium Dusts

Section 6 - Management System

Risk/COSHH Assessment Reference not established

Where Assessment is Held Clients Intranet Site

Date of Assessment 30-Apr-2019

Created By Martin Carr

Workplace Air Monitoring/Sampling Reference

Where the Report is Held

Date of Report

Created By

Material Safety Data Sheet Reference Multiple Documents

Where the MSDS is Held Clients Intranet Site and Online

Date of Publication 30-Apr-2019

Created By Manufacturers

Ventilation System User Manual Reference

Where the Manual is Held

Date of Publication

Created By

Ventilation System Maintenance Log Book Reference Not established

Where Log Book is Held Clients Intranet Site

Date of Publication Not established

Created By Martin Carr

Page 8: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 8 of 10 Report Number: E35223013258

810c

Commissioning/Initial Appraisal Report Reference

Where Report is Held

Date of Report

Created By

Previous Thorough Examination and Test Report Reference E35223012724

Where Report is Held Clients Intranet Site

Date of Report 29-Apr-2021

Created By Allianz

Evidence of Housekeeping PASS

Comments 1. Housekeeping at the process and surrounding work areas at the time of the Thorough Examination andTest assessed to be satisfactory.

Evidence of Maintenance PASS

Comments 1. System Log Book observed at the time of examination and test, indicating applicable maintenanceschedules and other supporting evidence of periodic service/maintenance or repairs to the ventilationsystem.

Evidence that the Engineering Control is being applied correctly PASS

Comments 1. There is evidence to support that the engineering controls are being properly used or applied (seesection 2 )

Page 9: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 9 of 10 Report Number: E35223013258

810c

Section 7 - Quantitative Test Results

Calibrated Test Equipment

Thermal Anemometer Calibration Date Rotating Vane Anemometer Calibration Date

4302051001 21-Jan-2021 Not used

Electronic Manometer Calibration Date Other Calibration Date

ACEEM047 26-Apr-2021 Not used

Test Datum Date: 30-Apr-2019

Test Datum Reference (Type/Ref. no.) Allianz First Thorough Examination and Test

I.D. Number Air Cleanerinlet Pressure(Pa)

Datum Air Cleaneroutlet Pressure(Pa)

Datum PressureDifference (Pa)

Datum

1 -716 -700 -843 -859 127 159

Other Test Point Reference(s) Other Quantitative Results

Point ID Duct/Face/Point Profile Hood/DuctSize (m)

StaticPressure (Pa)

VelocityPressure (Pa)

Face/DuctVelocity (m/s)

Volume Flow(m3/s)

TP 1 Knife Serrator HoodDuct

Circular 0.1 -123 100 12.9 0.10132

Datum: -71 90 12.33 0.09684

TP 2 Grinder Hood Duct Circular 0.1 -126 84 11.82 0.09283

Datum: -152 81 11.7 0.09189

TP 3 New Serrator HoodFace

Oblong 0 x 0 -12 3.67 0

Datum: -16 4.13 0

Page 10: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 10 of 10 Report Number: E35223013258

810c

Section 8 - System Diagram/Photos

The above items were seen at:(If blank, refer to the location details)

Examination carried out on behalf of: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

This report shall not be reproduced without the approval of Allianz Engineering and the Client for whom it was produced.

Page 11: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Name of user: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARELocation: TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH Report Number:

Policy Number:Contract Number:

E35223012724NV09796703

Side 1 of 10Recommended date of next thoroughexamination

29-OCT-2021 Competent PersonAllianz Engineering

Date of commencement of examinationand tests

29-APR-2021

29-APR-2021Date of ReportEngineer Surveyor

Andrew AllenIf you have a query about this report please contact Andrew Allen on 07870 231604 or by email at [email protected]. For all other enquiries pleasecontact our support team on +44(0) 1483 265837 or +00353 (0) 1 613 4081Allianz Engineering Inspection Services Ltd, 57 Ladymead, Guildford, Surrey, GU1 1DBAllianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United KingdomAllianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland, Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.Registered in Ireland Number143108www.allianzengineering.co.uk

V810c

Section 1 - Executive Summary and Declaration

System Plant Number LEV 043

Ventilation System Type Local Exhaust Ventilation

Regulations Applicable COSHH (Control of Substances Hazardous to Health)

Examination Type Thorough Examination and Test

Declaration (UK only) The Thorough Examination and Test has been conductedregarding the requirements of the current edition of TheHealth and Safety Executive (HSE) guidance HS(G)258 -Controlling Airborne Contaminants at Work

Overall Assessment of Control

PASS

System Description

Multi-point (3) Local Exhaust Ventilation System, incorporating 'air mover' (1) and 'air cleaner' (1), controlling Nickel, Silverand Grinding Medium Dusts produced from Knife Serrator's and Grinder

Page 12: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 2 of 10 Report Number: E35223012724

810c

Section 2 - Thorough Examination and Test Results

'A' - Defects

Defects affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. 'Immediate' attention is required.

1. None

'B' - Defects

Defects not affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. These defects should be rectified before the next Thorough Examination and Test.

1. None

'C' - Recommendations

Recommendations providing additional value and information relating to the Ventilation System Management.

1. The following Ventilation system Management documentation has not been presented:Workplace Air Monitoring/SamplingVentilation System User ManualCommissioning/Initial Appraisal ReportThe above should be provided to evidence compliance with the Regulations.

2. The client has made attempts to source the Commissioning Report and User Manual but has been unable to do so.

3. Air Cleaner - No record of filter efficiency and concentration of the contaminant in the return air testing has been seenwhere the LEV system includes arrangements for re-circulating into workplace areas. Relevant testing should be conductedand records made available. The client has made a written statement to Allianz indicating that the process is only used 1 to 2hours a week.

4. Air Mover - Technical Specification of the Air Mover and associated Motor Manufacturers details have not been fullyverified, these should be provided to assist in completing section 3 of this report.

5. Capture Hood - Fixed Capture x 3

6. Capture Hood - No airflow indicator installed at the Capture Hoods. Further guidance for the use of airflow indicators canbe found in HS(G) 258, Controlling Airborne Contaminants at Work. Consideration should be given to the provision of asuitable airflow indicator, which would indicate to the operator that the system is working effectively.

Inaccessible Parts/Limitations (at the time of the Thorough Examination Test)

The following were not presented, accessible or available at the time of the Thorough Examination and Test but did notprevent us from providing an accurate assessment of the ventilation system.

1. none

Ventilation System Set-up Conditions at the time of the Thorough Examination and Test

admin
Sticky Note
Refer to Notes bookmark
Page 13: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 3 of 10 Report Number: E35223012724

810c

Normal Operation and Special Condition - LEV operating and fully functional with the process not in use simulatingcontaminant emission utilising smoke

Detail of the Intended Operating Procedure (IOP)

1. At the time of inspection, there was no written Intended Operating Procedure (IOP) presented.The system was therefore tested with two points open as verbally indicated as the normal operating procedure.

Page 14: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 4 of 10 Report Number: E35223012724

810c

Section 3 - Ventilation System Identification

Manufacturer Serial Number Location

Not established NOT ESTABLISHED Handle Department

Total Number of Extraction Points Available 3

Maximum Number of Points that can be used at any one time (system design and use specification) 3

Exhaust Air Direction Number of Air Movers Number of Air Cleaners

Workplace 1 1

Air Mover(s)

Identification Number: 1

Manufacturer: Not established

Serial Number: Not established

Type: Centrifugal

Rotation (from drive end): Clockwise

Size (diameter): (m) 0.20

Volumetric Flow Rate (Manufacturer Specification):(m3s-1)

Not established

Speed (Manufacturer Specification): (rpm) 3450

Motor(s)

Identification Number: 1

Manufacturer: Baldor

Serial Number: Not established

Speed (Manufacturer Specification): (rpm) 3450

Power (Manufacturer Specification): (kw) 0.55

Invertors/Variable Speed: Not applicable

Air Cleaner(s)

Identification: 1

Medium: Fabric filter

Collector Type: Collection tray

Medium Efficiency (Manufacturer Specification): (%) Not established

Page 15: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 5 of 10 Report Number: E35223012724

810c

Section 4 - Examination and Test Result Summary

Examinations and Test Techniques Undertaken

Visual, Tyndall Beam, Smoke, Velocity Measurements, Pressure Measurements

Qualitative Testing Results PASS

Comments 1. Qualitative testing using method as detailed in HS(G)258, including observations of the process andcontaminant sources, effective containment of the hazardous substance, and the way in which theoperators use (or simulation of use) of the LEV system found the visual appraisal of the level of control tobe satisfactory.

Quantitative Testing Results PASS

Comments 1. Quantitative testing carried out on the LEV System was found to satisfy the guidance found in HS(G)258,Table 9 and Table 12 for this type of Hazardous Substance.

2. The comparison of the ventilation system layout/process from the last thorough examination & testwas observed to be unchanged with system performance found to be at approximately the same levelsas recorded at the previous or benchmark examination and test with specific capture/transport velocityfound to be approximately the same.

Ventilation System Performance Results PASS

Comments 1. With the exception of the findings as detailed in Section 2 of this report, the ventilation systemperformance was assessed to provide satisfactory adequate level of control subject to the correct use ofthe LEV Plant.

Capture Hood Examination Results, includingi) Hood types usedii) Effective Capture Distances (moveable hoods)

PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Ducting Examination Results (including exhaust stack, if applicable) PASS

Comments 1. With the exception of the findings as detailed in Section 2 of this report, we observed that the ductingassociated with the LEV System did not display any signs wear or tear and operating in a satisfactorymanner.

Air Mover Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Air Cleaner Examination Results PASS

Comments 1. Filter Media Cleaning system operation witnessed at the time of the examination and test.

Page 16: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 6 of 10 Report Number: E35223012724

810c

Page 17: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 7 of 10 Report Number: E35223012724

810c

Section 5 - Process Identification

Process Function(s) Knife Serrator's and Grinder

Process Machine Serial Number(s) Not established

Hazardous Substances Nickel, Silver and Grinding Medium Dusts

Section 6 - Management System

Risk/COSHH Assessment Reference not established

Where Assessment is Held Clients Intranet Site

Date of Assessment 30-Apr-2019

Created By Martin Carr

Workplace Air Monitoring/Sampling Reference

Where the Report is Held

Date of Report

Created By

Material Safety Data Sheet Reference Multiple Documents

Where the MSDS is Held Clients Intranet Site and Online

Date of Publication 30-Apr-2019

Created By Manufacturers

Ventilation System User Manual Reference

Where the Manual is Held

Date of Publication

Created By

Ventilation System Maintenance Log Book Reference Not established

Where Log Book is Held Clients Intranet Site

Date of Publication Not established

Created By Martin Carr

Page 18: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 8 of 10 Report Number: E35223012724

810c

Commissioning/Initial Appraisal Report Reference

Where Report is Held

Date of Report

Created By

Previous Thorough Examination and Test Report Reference E35223012171

Where Report is Held Clients Intranet Site

Date of Report 02-Nov-2020

Created By Allianz

Evidence of Housekeeping PASS

Comments 1. Housekeeping at the process and surrounding work areas at the time of the Thorough Examination andTest assessed to be satisfactory.

Evidence of Maintenance PASS

Comments 1. System Log Book observed at the time of examination and test, indicating applicable maintenanceschedules and other supporting evidence of periodic service/maintenance or repairs to the ventilationsystem.

Evidence that the Engineering Control is being applied correctly PASS

Comments 1. There is evidence to support that the engineering controls are being properly used or applied (seesection 2 )

Page 19: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 9 of 10 Report Number: E35223012724

810c

Section 7 - Quantitative Test Results

Calibrated Test Equipment

Thermal Anemometer Calibration Date Rotating Vane Anemometer Calibration Date

120622 10-Sep-2020 Not used

Electronic Manometer Calibration Date Other Calibration Date

ACEEM013 04-Dec-2020 Not used

Test Datum Date: 30-Apr-2019

Test Datum Reference (Type/Ref. no.) Allianz First Thorough Examination and Test

I.D. Number Air Cleanerinlet Pressure(Pa)

Datum Air Cleaneroutlet Pressure(Pa)

Datum PressureDifference (Pa)

Datum

1 -694 -700 -833 -859 139 159

Other Test Point Reference(s) Other Quantitative Results

Point ID Duct/Face/Point Profile Hood/DuctSize (m)

StaticPressure (Pa)

VelocityPressure (Pa)

Face/DuctVelocity (m/s)

Volume Flow(m3/s)

TP 1 Knife Serrator HoodDuct

Circular 0.1 -120 120 14.13 0.11098

Datum: -71 90 12.33 0.09684

TP 2 Grinder Hood Duct Circular 0.1 -110 107 13.34 0.10477

Datum: -152 81 11.7 0.09189

TP 3 New Serrator HoodFace

Oblong 0 x 0 -9 2.91 0

Datum: -16 4.13 0

Page 20: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 10 of 10 Report Number: E35223012724

810c

Section 8 - System Diagram/Photos

The above items were seen at:(If blank, refer to the location details)

Examination carried out on behalf of: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

This report shall not be reproduced without the approval of Allianz Engineering and the Client for whom it was produced.

Page 21: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Name of user: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARELocation: TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH Report Number:

Policy Number:Contract Number:

E35223012171NV09796703

Side 1 of 10Recommended date of next thoroughexamination

02-MAY-2021 Competent PersonAllianz Engineering

Date of commencement of examinationand tests

02-NOV-2020

02-NOV-2020 UK Tel: +44(0) 1428 722407Date of ReportEngineer Surveyor

Andrew Allen

ROI Tel: +00353 (0) 1 613 4081

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United KingdomAllianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United KingdomAllianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland, Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.Registered in Ireland Number143108www.allianzengineering.co.uk

V810c

Section 1 - Executive Summary and Declaration

System Plant Number LEV 043

Ventilation System Type Local Exhaust Ventilation

Regulations Applicable COSHH (Control of Substances Hazardous to Health)

Examination Type Thorough Examination and Test

Declaration (UK only) The Thorough Examination and Test has been conductedregarding the requirements of the current edition of TheHealth and Safety Executive (HSE) guidance HS(G)258 -Controlling Airborne Contaminants at Work

Overall Assessment of Control

PASS

System Description

Multi-point (3) Local Exhaust Ventilation System, incorporating 'air mover' (1) and 'air cleaner' (1), controlling Nickel, Silverand Grinding Medium Dusts produced from Knife Serrator's and Grinder

Page 22: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 2 of 10 Report Number: E35223012171

810c

Section 2 - Thorough Examination and Test Results

'A' - Defects

Defects affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. 'Immediate' attention is required.

1. None

'B' - Defects

Defects not affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. These defects should be rectified before the next Thorough Examination and Test.

1. None

'C' - Recommendations

Recommendations providing additional value and information relating to the Ventilation System Management.

1. The following Ventilation system Management documentation has not been presented:Workplace Air Monitoring/SamplingVentilation System User ManualCommissioning/Initial Appraisal ReportThe above should be provided to evidence compliance with the Regulations.

2. The client has made attempts to source the Commissioning Report and User Manual but has been unable to do so.

3. Air Cleaner - No record of filter efficiency and concentration of the contaminant in the return air testing has been seenwhere the LEV system includes arrangements for re-circulating into workplace areas. Relevant testing should be conductedand records made available. The client has made a written statement to Allianz indicating that the process is only used 1 to 2hours a week.

4. Air Mover - Technical Specification of the Air Mover and associated Motor Manufacturers details have not been fullyverified, these should be provided to assist in completing section 3 of this report.

5. Capture Hood - Fixed Capture x 3

6. Capture Hood - No airflow indicator installed at the Capture Hoods. Further guidance for the use of airflow indicators canbe found in HS(G) 258, Controlling Airborne Contaminants at Work. Consideration should be given to the provision of asuitable airflow indicator, which would indicate to the operator that the system is working effectively.

Inaccessible Parts/Limitations (at the time of the Thorough Examination Test)

The following were not presented, accessible or available at the time of the Thorough Examination and Test but did notprevent us from providing an accurate assessment of the ventilation system.

1. none

Ventilation System Set-up Conditions at the time of the Thorough Examination and Test

admin
Sticky Note
Refer Notes bookmark
Page 23: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 3 of 10 Report Number: E35223012171

810c

Normal Operation and Special Condition - LEV operating and fully functional with the process not in use simulatingcontaminant emission utilising smoke

Detail of the Intended Operating Procedure (IOP)

1. At the time of inspection, there was no written Intended Operating Procedure (IOP) presented.The system was therefore tested with two points open as verbally indicated as the normal operating procedure.

Page 24: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 4 of 10 Report Number: E35223012171

810c

Section 3 - Ventilation System Identification

Manufacturer Serial Number Location

Not established NOT ESTABLISHED Handle Department

Total Number of Extraction Points Available 3

Maximum Number of Points that can be used at any one time (system design and use specification) 3

Exhaust Air Direction Number of Air Movers Number of Air Cleaners

Workplace 1 1

Air Mover(s)

Identification Number: 1

Manufacturer: Not established

Serial Number: Not established

Type: Centrifugal

Rotation (from drive end): Clockwise

Size (diameter): (m) 0.20

Volumetric Flow Rate (Manufacturer Specification):(m3s-1)

Not established

Speed (Manufacturer Specification): (rpm) 3450

Motor(s)

Identification Number: 1

Manufacturer: Baldor

Serial Number: Not established

Speed (Manufacturer Specification): (rpm) 3450

Power (Manufacturer Specification): (kw) 0.55

Invertors/Variable Speed: Not applicable

Air Cleaner(s)

Identification: 1

Medium: Fabric filter

Collector Type: Collection tray

Medium Efficiency (Manufacturer Specification): (%) Not established

Page 25: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 5 of 10 Report Number: E35223012171

810c

Section 4 - Examination and Test Result Summary

Examinations and Test Techniques Undertaken

Visual, Tyndall Beam, Smoke, Velocity Measurements, Pressure Measurements

Qualitative Testing Results PASS

Comments 1. Qualitative testing using method as detailed in HS(G)258, including observations of the process andcontaminant sources, effective containment of the hazardous substance, and the way in which theoperators use (or simulation of use) of the LEV system found the visual appraisal of the level of control tobe satisfactory.

Quantitative Testing Results PASS

Comments 1. Quantitative testing carried out on the LEV System was found to satisfy the guidance found in HS(G)258,Table 9 and Table 12 for this type of Hazardous Substance.

2. The comparison of the ventilation system layout/process from the last thorough examination & testwas observed to be unchanged with system performance found to be at approximately the same levelsas recorded at the previous or benchmark examination and test with specific capture/transport velocityfound to be approximately the same.

Ventilation System Performance Results PASS

Comments 1. With the exception of the findings as detailed in Section 2 of this report, the ventilation systemperformance was assessed to provide satisfactory adequate level of control subject to the correct use ofthe LEV Plant.

Capture Hood Examination Results, includingi) Hood types usedii) Effective Capture Distances (moveable hoods)

PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Ducting Examination Results (including exhaust stack, if applicable) PASS

Comments 1. With the exception of the findings as detailed in Section 2 of this report, we observed that the ductingassociated with the LEV System did not display any signs wear or tear and operating in a satisfactorymanner.

Air Mover Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Air Cleaner Examination Results PASS

Comments 1. Filter Media Cleaning system operation witnessed at the time of the examination and test.

Page 26: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 6 of 10 Report Number: E35223012171

810c

Page 27: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 7 of 10 Report Number: E35223012171

810c

Section 5 - Process Identification

Process Function(s) Knife Serrator's and Grinder

Process Machine Serial Number(s) Not established

Hazardous Substances Nickel, Silver and Grinding Medium Dusts

Section 6 - Management System

Risk/COSHH Assessment Reference not established

Where Assessment is Held Clients Intranet Site

Date of Assessment 30-Apr-2019

Created By Martin Carr

Workplace Air Monitoring/Sampling Reference

Where the Report is Held

Date of Report

Created By

Material Safety Data Sheet Reference Multiple Documents

Where the MSDS is Held Clients Intranet Site and Online

Date of Publication 30-Apr-2019

Created By Manufacturers

Ventilation System User Manual Reference

Where the Manual is Held

Date of Publication

Created By

Ventilation System Maintenance Log Book Reference Not established

Where Log Book is Held Clients Intranet Site

Date of Publication Not established

Created By Martin Carr

Page 28: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 8 of 10 Report Number: E35223012171

810c

Commissioning/Initial Appraisal Report Reference

Where Report is Held

Date of Report

Created By

Previous Thorough Examination and Test Report Reference E35223011728

Where Report is Held Clients Intranet Site

Date of Report 22-Apr-2020

Created By Allianz

Evidence of Housekeeping PASS

Comments 1. Housekeeping at the process and surrounding work areas at the time of the Thorough Examination andTest assessed to be satisfactory.

Evidence of Maintenance PASS

Comments 1. System Log Book observed at the time of examination and test, indicating applicable maintenanceschedules and other supporting evidence of periodic service/maintenance or repairs to the ventilationsystem.

Evidence that the Engineering Control is being applied correctly PASS

Comments 1. There is evidence to support that the engineering controls are being properly used or applied (seesection 2 )

Page 29: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 9 of 10 Report Number: E35223012171

810c

Section 7 - Quantitative Test Results

Calibrated Test Equipment

Thermal Anemometer Calibration Date Rotating Vane Anemometer Calibration Date

120622 10-Sep-2020 Not used

Electronic Manometer Calibration Date Other Calibration Date

ACEEM047 24-Apr-2019 Not used

Test Datum Date: 30-Apr-2019

Test Datum Reference (Type/Ref. no.) Allianz First Thorough Examination and Test

I.D. Number Air Cleanerinlet Pressure(Pa)

Datum Air Cleaneroutlet Pressure(Pa)

Datum PressureDifference (Pa)

Datum

1 -707 -700 -827 -859 120 159

Other Test Point Reference(s) Other Quantitative Results

Point ID Duct/Face/Point Profile Hood/DuctSize (m)

StaticPressure (Pa)

VelocityPressure (Pa)

Face/DuctVelocity (m/s)

Volume Flow(m3/s)

TP 1 Knife Serrator HoodDuct

Circular 0.1 -77 100 13 0.1021

Datum: -71 90 12.33 0.09684

TP 2 Grinder Hood Duct Circular 0.1 -129 87 12.13 0.09527

Datum: -152 81 11.7 0.09189

TP 3 New Serrator HoodFace

Oblong 0 x 0 -19 3.32 0

Datum: -16 4.13 0

Page 30: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 10 of 10 Report Number: E35223012171

810c

Section 8 - System Diagram/Photos

The above items were seen at:(If blank, refer to the location details)

Examination carried out on behalf of: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

This report shall not be reproduced without the approval of Allianz Engineering and the Client for whom it was produced.

Page 31: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Name of user: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARELocation: TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH Report Number:

Policy Number:Contract Number:

E35223011728NV09796703

Side 1 of 10Recommended date of next thoroughexamination

22-OCT-2020 Competent PersonAllianz Engineering

Date of commencement of examinationand tests

22-APR-2020

22-APR-2020 UK Tel: +44(0) 1428 722407Date of ReportEngineer Surveyor

Andrew Allen

ROI Tel: +00353 (0) 1 613 4081

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United KingdomAllianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United KingdomAllianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland, Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.Registered in Ireland Number143108www.allianzengineering.co.uk

V810c

Section 1 - Executive Summary and Declaration

System Plant Number LEV 043

Ventilation System Type Local Exhaust Ventilation

Regulations Applicable COSHH (Control of Substances Hazardous to Health)

Examination Type Thorough Examination and Test

Declaration (UK only) The Thorough Examination and Test has been conductedregarding the requirements of the current edition of TheHealth and Safety Executive (HSE) guidance HS(G)258 -Controlling Airborne Contaminants at Work

Overall Assessment of Control

PASS

System Description

Multi-point (3) Local Exhaust Ventilation System, incorporating 'air mover' (1) and 'air cleaner' (1), controlling Nickel, Silverand Grinding Medium Dusts produced from Knife Serrator's and Grinder

Page 32: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 2 of 10 Report Number: E35223011728

810c

Section 2 - Thorough Examination and Test Results

'A' - Defects

Defects affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. 'Immediate' attention is required.

1. None

'B' - Defects

Defects not affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. These defects should be rectified before the next Thorough Examination and Test.

1. None

'C' - Recommendations

Recommendations providing additional value and information relating to the Ventilation System Management.

1. The following Ventilation system Management documentation has not been presented:Workplace Air Monitoring/SamplingVentilation System User ManualCommissioning/Initial Appraisal ReportThe above should be provided to evidence compliance with the Regulations.

2. The client has made attempts to source the Commissioning Report and User Manual but has been unable to do so.

3. Air Cleaner - No record of filter efficiency and concentration of the contaminant in the return air testing has been seenwhere the LEV system includes arrangements for re-circulating into workplace areas. Relevant testing should be conductedand records made available. The client has made a written statement to Allianz indicating that the process is only used 1 to 2hours a week.

4. Air Mover - Technical Specification of the Air Mover and associated Motor Manufacturers details have not been fullyverified, these should be provided to assist in completing section 3 of this report.

5. Capture Hood - Fixed Capture x 3

6. Capture Hood - No airflow indicator installed at the Capture Hoods. Further guidance for the use of airflow indicators canbe found in HS(G) 258, Controlling Airborne Contaminants at Work. Consideration should be given to the provision of asuitable airflow indicator, which would indicate to the operator that the system is working effectively.

Inaccessible Parts/Limitations (at the time of the Thorough Examination Test)

The following were not presented, accessible or available at the time of the Thorough Examination and Test but did notprevent us from providing an accurate assessment of the ventilation system.

Ventilation System Set-up Conditions at the time of the Thorough Examination and Test

Normal Operation and Special Condition - LEV operating and fully functional with the process not in use simulatingcontaminant emission utilising smoke

admin
Sticky Note
Refer to Notes bookmark
Page 33: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 3 of 10 Report Number: E35223011728

810c

Detail of the Intended Operating Procedure (IOP)

1. At the time of inspection, there was no written Intended Operating Procedure (IOP) presented.The system was therefore tested with two points open as verbally indicated as the normal operating procedure.

Page 34: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 4 of 10 Report Number: E35223011728

810c

Section 3 - Ventilation System Identification

Manufacturer Serial Number Location

Not established NOT ESTABLISHED Handle Department

Total Number of Extraction Points Available 3

Maximum Number of Points that can be used at any one time (system design and use specification) 3

Exhaust Air Direction Number of Air Movers Number of Air Cleaners

Workplace 1 1

Air Mover(s)

Identification Number: 1

Manufacturer: Not established

Serial Number: Not established

Type: Centrifugal

Rotation (from drive end): Clockwise

Size (diameter): (m) 0.20

Volumetric Flow Rate (Manufacturer Specification):(m3s-1)

Not established

Speed (Manufacturer Specification): (rpm) 3450

Motor(s)

Identification Number: 1

Manufacturer: Baldor

Serial Number: Not established

Speed (Manufacturer Specification): (rpm) 3450

Power (Manufacturer Specification): (kw) 0.55

Invertors/Variable Speed: Not applicable

Air Cleaner(s)

Identification: 1

Medium: Fabric filter

Collector Type: Collection tray

Medium Efficiency (Manufacturer Specification): (%) Not established

Page 35: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 5 of 10 Report Number: E35223011728

810c

Section 4 - Examination and Test Result Summary

Examinations and Test Techniques Undertaken

Visual, Tyndall Beam, Smoke, Velocity Measurements, Pressure Measurements

Qualitative Testing Results PASS

Comments 1. Qualitative testing using method as detailed in HS(G)258, including observations of the process andcontaminant sources, effective containment of the hazardous substance, and the way in which theoperators use (or simulation of use) of the LEV system found the visual appraisal of the level of control tobe satisfactory.

Quantitative Testing Results PASS

Comments 1. Quantitative testing carried out on the LEV System was found to satisfy the guidance found in HS(G)258,Table 9 and Table 12 for this type of Hazardous Substance.

Ventilation System Performance Results PASS

Comments 1. With the exception of the findings as detailed in Section 2 of this report, the ventilation systemperformance was assessed to provide satisfactory adequate level of control subject to the correct use ofthe LEV Plant.

Capture Hood Examination Results, includingi) Hood types usedii) Effective Capture Distances (moveable hoods)

PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Ducting Examination Results (including exhaust stack, if applicable) PASS

Comments 1. With the exception of the findings as detailed in Section 2 of this report, we observed that the ductingassociated with the LEV System did not display any signs wear or tear and operating in a satisfactorymanner.

Air Mover Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Air Cleaner Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Page 36: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 6 of 10 Report Number: E35223011728

810c

Section 5 - Process Identification

Process Function(s) Knife Serrator's and Grinder

Process Machine Serial Number(s) Not established

Hazardous Substances Nickel, Silver and Grinding Medium Dusts

Section 6 - Management System

Risk/COSHH Assessment Reference not established

Where Assessment is Held Clients Intranet Site

Date of Assessment 30-Apr-2019

Created By Martin Carr

Workplace Air Monitoring/Sampling Reference

Where the Report is Held

Date of Report

Created By

Material Safety Data Sheet Reference Multiple Documents

Where the MSDS is Held Clients Intranet Site and Online

Date of Publication 30-Apr-2019

Created By Manufacturers

Ventilation System User Manual Reference

Where the Manual is Held

Date of Publication

Created By

Ventilation System Maintenance Log Book Reference Not established

Where Log Book is Held Clients Intranet Site

Date of Publication Not established

Created By Martin Carr

Page 37: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 7 of 10 Report Number: E35223011728

810c

Commissioning/Initial Appraisal Report Reference

Where Report is Held

Date of Report

Created By

Previous Thorough Examination and Test Report Reference E35223011238

Where Report is Held Clients Intranet Site

Date of Report 29-Oct-2019

Created By Allianz

Evidence of Housekeeping PASS

Comments 1. Housekeeping at the process and surrounding work areas at the time of the Thorough Examination andTest assessed to be satisfactory.

Evidence of Maintenance PASS

Comments 1. System Log Book observed at the time of examination and test, indicating applicable maintenanceschedules and other supporting evidence of periodic service/maintenance or repairs to the ventilationsystem.

Evidence that the Engineering Control is being applied correctly PASS

Comments 1. There is evidence to support that the engineering controls are being properly used or applied (seesection 2 )

Page 38: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 8 of 10 Report Number: E35223011728

810c

Section 7 - Quantitative Test Results

Calibrated Test Equipment

Thermal Anemometer Calibration Date Rotating Vane Anemometer Calibration Date

120622 11-Sep-2018 Not Used 22-Jun-2018

Electronic Manometer Calibration Date Other Calibration Date

ACEEM047 24-Apr-2019 Not used

Test Datum Date: 30-Apr-2019

Test Datum Reference (Type/Ref. no.) Allianz First Thorough Examination and Test

I.D. Number Air Cleanerinlet Pressure(Pa)

Datum Air Cleaneroutlet Pressure(Pa)

Datum PressureDifference (Pa)

Datum

1 -774 -700 -882 -859 108 159

Other Test Point Reference(s) Other Quantitative Results

Point ID Duct/Face/Point Profile Hood/DuctSize (m)

StaticPressure (Pa)

VelocityPressure (Pa)

Face/DuctVelocity (m/s)

Volume Flow(m3/s)

TP 1 Knife Serrator HoodDuct

Circular 0.1 -132 126 14.59 0.11459

Datum: -71 90 12.33 0.09684

TP 2 Grinder Hood Duct Circular 0.1 -155 90 12.33 0.09684

Datum: -152 81 11.7 0.09189

TP 3 New Serrator HoodFace

Oblong 0 x 0 -16 3.45 0

Datum: -16 4.13 0

Page 39: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 9 of 10 Report Number: E35223011728

810c

Section 8 - System Diagram/Photos

The above items were seen at:(If blank, refer to the location details)

Examination carried out on behalf of: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

This report shall not be reproduced without the approval of Allianz Engineering and the Client for whom it was produced.

Page 40: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Name of user: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARELocation: TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH Report Number:

Policy Number:Contract Number:

E35223011238NV09796703

Side 1 of 10Recommended date of next thoroughexamination

29-APR-2020 Competent PersonAllianz Engineering

Date of commencement of examinationand tests

29-OCT-2019

29-OCT-2019 UK Tel: +44(0) 1428 722407Date of ReportEngineer Surveyor

Andrew Allen

ROI Tel: +00353 (0) 1 613 4081

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United KingdomAllianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United KingdomAllianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland, Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.Registered in Ireland Number143108www.allianzengineering.co.uk

V810c

Section 1 - Executive Summary and Declaration

System Plant Number LEV 043

Ventilation System Type Local Exhaust Ventilation

Regulations Applicable COSHH (Control of Substances Hazardous to Health)

Examination Type Thorough Examination and Test

Declaration (UK only) The Thorough Examination and Test has been conductedregarding the requirements of the current edition of TheHealth and Safety Executive (HSE) guidance HS(G)258 -Controlling Airborne Contaminants at Work

Overall Assessment of Control

PASS

System Description

Multi-point (3) Local Exhaust Ventilation System, incorporating 'air mover' (1) and 'air cleaner' (1), controlling Nickel, Silverand Grinding Medium Dusts produced from Knife Serrator's and Grinder

Page 41: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 2 of 10 Report Number: E35223011238

810c

Section 2 - Thorough Examination and Test Results

'A' - Defects

Defects affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. 'Immediate' attention is required.

1. None

'B' - Defects

Defects not affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. These defects should be rectified before the next Thorough Examination and Test.

1. None

'C' - Recommendations

Recommendations providing additional value and information relating to the Ventilation System Management.

1. The following Ventilation system Management documentation has not been presented:Workplace Air Monitoring/SamplingVentilation System User ManualCommissioning/Initial Appraisal ReportThe above should be provided to evidence compliance with the Regulations.

2. The client has made attempts to source the Commissioning Report and User Manual but has been unable to do so.

3. Air Cleaner - No record of filter efficiency and concentration of the contaminant in the return air testing has been seenwhere the LEV system includes arrangements for re-circulating into workplace areas. Relevant testing should be conductedand records made available. The client has made a written statement to Allianz indicating that the process is only used 1 to 2hours a week.

4. Air Mover - The fan and motor technical details could not be fully captured and should be provided.

5. Engineering Control - Contaminant dusts are present on the new knife serrator. It should be ensured that the extractionsystem is used during all grinding operations.

6. Capture Hood - Fixed Capture x 3

7. Capture Hood - In line with HSE Guidance HS(G) 258, each hood should have a dedicated airflow indicator, wherepracticable, to indicate adequate airflow and LEV system performance to the operator.

Inaccessible Parts/Limitations (at the time of the Thorough Examination Test)

The following were not presented, accessible or available at the time of the Thorough Examination and Test but did notprevent us from providing an accurate assessment of the ventilation system.

Ventilation System Set-up Conditions at the time of the Thorough Examination and Test

Normal Operation and Special Condition - LEV operating and fully functional with the process not in use simulatingcontaminant emission utilising smoke

admin
Sticky Note
Refer to Bookmark "Returned air notes" Unable to locate manual due to age.
admin
Sticky Note
This is not due to LEV issues, more of product tapping
admin
Sticky Note
We can see no advantage given the present setup - It is obvious if it is working or not
admin
Sticky Note
Refer to COSHH assessments
Page 42: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 3 of 10 Report Number: E35223011238

810c

Detail of the Intended Operating Procedure (IOP)

1. At the time of inspection, there was no written Intended Operating Procedure (IOP) presented.The system was therefore tested with two points open as verbally indicated as the normal operating procedure.

Page 43: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 4 of 10 Report Number: E35223011238

810c

Section 3 - Ventilation System Identification

Manufacturer Serial Number Location

Not established NOT ESTABLISHED Handle Department

Total Number of Extraction Points Available 3

Maximum Number of Points that can be used at any one time (system design and use specification) 3

Exhaust Air Direction Number of Air Movers Number of Air Cleaners

Workplace 1 1

Air Mover(s)

Identification Number: 1

Manufacturer: Not established

Serial Number: Not established

Type: Centrifugal

Rotation (from drive end): Clockwise

Size (diameter): (m) 0.20

Volumetric Flow Rate (Manufacturer Specification):(m3s-1)

Not established

Speed (Manufacturer Specification): (rpm) 3450

Motor(s)

Identification Number: 1

Manufacturer: Baldor

Serial Number: Not established

Speed (Manufacturer Specification): (rpm) 3450

Power (Manufacturer Specification): (kw) 0.55

Invertors/Variable Speed: Not applicable

Air Cleaner(s)

Identification: 1

Medium: Fabric filter

Collector Type: Collection tray

Medium Efficiency (Manufacturer Specification): (%) Not established

Page 44: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 5 of 10 Report Number: E35223011238

810c

Section 4 - Examination and Test Result Summary

Examinations and Test Techniques Undertaken

Visual, Tyndall Beam, Smoke, Velocity Measurements, Pressure Measurements

Qualitative Testing Results PASS

Comments 1. All Qualitative testing identified effective capture throughout the ventilation system.

Quantitative Testing Results PASS

Comments 1. All Quantitative testing identified effective and expected Quantitative measurements throughout theventilation system.

Ventilation System Performance Results PASS

Comments 1. System performance levels were seen to be operating effectively throughout the ventilation systemwithout any change from previous records.

Capture Hood Examination Results, includingi) Hood types usedii) Effective Capture Distances (moveable hoods)

PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Ducting Examination Results (including exhaust stack, if applicable) PASS

Comments 1. The installed ducting has been assessed as fit for purpose and absent of defect.

Air Mover Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Air Cleaner Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Page 45: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 6 of 10 Report Number: E35223011238

810c

Section 5 - Process Identification

Process Function(s) Knife Serrator's and Grinder

Process Machine Serial Number(s) Not established

Hazardous Substances Nickel, Silver and Grinding Medium Dusts

Section 6 - Management System

Risk/COSHH Assessment Reference not established

Where Assessment is Held Clients Intranet Site

Date of Assessment 30-Apr-2019

Created By Martin Carr

Workplace Air Monitoring/Sampling Reference

Where the Report is Held

Date of Report

Created By

Material Safety Data Sheet Reference Multiple Documents

Where the MSDS is Held Clients Intranet Site and Online

Date of Publication 30-Apr-2019

Created By Manufacturers

Ventilation System User Manual Reference

Where the Manual is Held

Date of Publication

Created By

Ventilation System Maintenance Log Book Reference Not established

Where Log Book is Held Clients Intranet Site

Date of Publication Not established

Created By Martin Carr

Page 46: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 7 of 10 Report Number: E35223011238

810c

Commissioning/Initial Appraisal Report Reference

Where Report is Held

Date of Report

Created By

Previous Thorough Examination and Test Report Reference E35223010823

Where Report is Held Clients Intranet Site

Date of Report 30-Apr-2019

Created By Allianz

Evidence of Housekeeping PASS

Comments 1. There is evidence of effective Housekeeping of the Ventilation System and surrounding Workplace areas,assessed through;- Observations made at the time of the TExT

Evidence of Maintenance PASS

Comments 1. There is evidence of effective Maintenance of the Ventilation System, assessed through;- Observations made at the time of the TExT

Evidence that the Engineering Control is being applied correctly PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Page 47: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 8 of 10 Report Number: E35223011238

810c

Section 7 - Quantitative Test Results

Calibrated Test Equipment

Thermal Anemometer Calibration Date Rotating Vane Anemometer Calibration Date

120622 11-Sep-2018 Not Used 22-Jun-2018

Electronic Manometer Calibration Date Other Calibration Date

ACEEM047 24-Apr-2019 Not used

Test Datum Date: 30-Apr-2019

Test Datum Reference (Type/Ref. no.) Allianz First Thorough Examination and Test

I.D. Number Air Cleanerinlet Pressure(Pa)

Datum Air Cleaneroutlet Pressure(Pa)

Datum PressureDifference (Pa)

Datum

1 -700 -700 -842 -859 142 159

Other Test Point Reference(s) Other Quantitative Results

Point ID Duct/Face/Point Profile Hood/DuctSize (m)

StaticPressure (Pa)

VelocityPressure (Pa)

Face/DuctVelocity (m/s)

Volume Flow(m3/s)

TP 1 Knife Serrator HoodDuct

Circular 0.1 -91 100 13 0.1021

Datum: -71 90 12.33 0.09684

TP 2 Grinder Hood Duct Circular 0.1 -149 81 11.7 0.09189

Datum: -152 81 11.7 0.09189

TP 3 New Serrator HoodFace

Oblong 0 x 0 -9 4.31 0

Datum: -16 4.13 0

Page 48: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 9 of 10 Report Number: E35223011238

810c

Section 8 - System Diagram/Photos

The above items were seen at:(If blank, refer to the location details)

Examination carried out on behalf of: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

This report shall not be reproduced without the approval of Allianz Engineering and the Client for whom it was produced.

Page 49: Contract Number: Policy Number: NV09796703 E35223012724 ...

Take image to prove inspection

1

Page 50: Contract Number: Policy Number: NV09796703 E35223012724 ...

Additional image if required

Thursday, August 8, 2019

Carrs HS Plant Inspection

Comments. Have you �xed any issues? if so action taken. Is further action needed, if so whatHSG-258 p64 notes re-circulated usually ok for contaminants that are; low toxicity, that are particles. This LEV is used approx. 1-2 hours per week and even then not all at the same time. With this in mind trying to measure the TWA of the exhaust fume would result in no �ndings. We will start and inspect the �lters on a regular basis, taking photo’s before and after cleaning (as required). Results from this will indicate of further action is required.

Plant Inspected

LEV Check

Item inspectedhttps://hs.carrs-silver.co.uk/LEV043.pdf

Any action required? If so details in following box

No

2

Page 51: Contract Number: Policy Number: NV09796703 E35223012724 ...

To save time you may wish to edit/paste some of these into the above box   PAT Testing: No Issues/Passed these tests - Earth Value, Earth Results, Leakage Test, IR Value, Wiring Value, Wire Result

Inspected byMartin Carr

Signature: I con�rm that I have performed the above inspection in accordance with the details on the Carrs HS Website and the details recorded are a true record as at this date and time.

3

Page 52: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Name of user: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARELocation: TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH Report Number:

Policy Number:Contract Number:

E35223010823NV09796703

Side 1 of 10Recommended date of next thoroughexamination

30-OCT-2019 Competent PersonAllianz Engineering

Date of commencement of examinationand tests

30-APR-2019

30-APR-2019 UK Tel: +44(0) 1428 722407Date of ReportEngineer Surveyor

Andrew Allen

ROI Tel: +00353 (0) 1 613 4081

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United KingdomAllianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United KingdomAllianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland, Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.Registered in Ireland Number143108www.allianzengineering.co.uk

V810c

Section 1 - Executive Summary and Declaration

System Plant Number LEV 043

Ventilation System Type Local Exhaust Ventilation

Regulations Applicable COSHH (Control of Substances Hazardous to Health)

Examination Type First thorough examination and test

Declaration (UK only) The Thorough Examination and Test has been conductedregarding the requirements of the current edition of TheHealth and Safety Executive (HSE) guidance HS(G)258 -Controlling Airborne Contaminants at Work

Overall Assessment of Control

PASS

System Description

Multi-point (3) Local Exhaust Ventilation System, incorporating 'air mover' (1) and 'air cleaner' (1), controlling Nickel, Silverand Grinding Medium Dusts produced from Knife Serrator's and Grinder

Page 53: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 2 of 10 Report Number: E35223010823

810c

Section 2 - Thorough Examination and Test Results

'A' - Defects

Defects affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. 'Immediate' attention is required.

1. None

'B' - Defects

Defects not affecting the safety to persons, including an identification of remedial action, considering exposure to theidentified Hazardous Substances. These defects should be rectified before the next Thorough Examination and Test.

1. Air Cleaner - No record of filter efficiency and concentration of the contaminant in the return air testing has been seenwhere the LEV system includes arrangements for re-circulating into workplace areas. Relevant testing should be conductedand records made available.

'C' - Recommendations

Recommendations providing additional value and information relating to the Ventilation System Management.

1. The following Ventilation system Management documentation has not been presented:Workplace Air Monitoring/SamplingVentilation System User ManualVentilation System Maintenance Log BookCommissioning/Initial Appraisal ReportThe above should be provided to evidence compliance with the Regulations.

2. Air Mover - The fan and motor technical details could not be fully captured and should be provided.

3. Engineering Control - Contaminant dusts are present on the bench around the capture hoods. It should be ensured thatthe extraction system is used during all grinding operations.

4. Capture Hood - In line with HSE Guidance HS(G) 258, each hood should have a dedicated airflow indicator, wherepracticable, to indicate adequate airflow and LEV system performance to the operator.

Inaccessible Parts/Limitations (at the time of the Thorough Examination Test)

The following were not presented, accessible or available at the time of the Thorough Examination and Test but did notprevent us from providing an accurate assessment of the ventilation system.

Ventilation System Set-up Conditions at the time of the Thorough Examination and Test

Normal Operation and Special Condition - LEV operating and fully functional with the process not in use simulatingcontaminant emission utilising smoke

Detail of the Intended Operating Procedure (IOP)

1. At the time of inspection, there was no Intended Operating Procedure (IOP) presented either verbally or written.The system was therefore tested with two points open as verbally indicated as the normal operating procedure.

admin
Sticky Note
Refer to COSHH 08/08/19 See Return air notes bookmark.
admin
Sticky Note
It should be noted ad-hock usage 08/08/19 1565267630 e-mail sent to inspector
Page 54: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 3 of 10 Report Number: E35223010823

810c

Page 55: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 4 of 10 Report Number: E35223010823

810c

Section 3 - Ventilation System Identification

Manufacturer Serial Number Location

Not established NOT ESTABLISHED Handle Department

Total Number of Extraction Points Available 3

Maximum Number of Points that can be used at any one time (system design and use specification) 3

Exhaust Air Direction Number of Air Movers Number of Air Cleaners

Workplace 1 1

Air Mover(s)

Identification Number: 1

Manufacturer: Not established

Serial Number: Not established

Type: Centrifugal

Rotation (from drive end): Clockwise

Size (diameter): (m) 0.20

Volumetric Flow Rate (Manufacturer Specification):(m3s-1)

Not established

Speed (Manufacturer Specification): (rpm) 3450

Motor(s)

Identification Number: 1

Manufacturer: Baldor

Serial Number: Not established

Speed (Manufacturer Specification): (rpm) 3450

Power (Manufacturer Specification): (kw) 0.55

Invertors/Variable Speed: Not applicable

Air Cleaner(s)

Identification: 1

Medium: Fabric filter

Collector Type: Collection tray

Medium Efficiency (Manufacturer Specification): (%) Not established

Page 56: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 5 of 10 Report Number: E35223010823

810c

Section 4 - Examination and Test Result Summary

Examinations and Test Techniques Undertaken

Visual, Tyndall Beam, Smoke, Velocity Measurements, Pressure Measurements

Qualitative Testing Results PASS

Comments 1. All Qualitative testing identified effective capture throughout the ventilation system.

Quantitative Testing Results PASS

Comments 1. All Quantitative testing identified effective and expected Quantitative measurements throughout theventilation system.

Ventilation System Performance Results PASS

Comments 1. System performance levels were seen to be operating effectively throughout the ventilation systemwithout any change from previous records.

Capture Hood Examination Results, includingi) Hood types usedii) Effective Capture Distances (moveable hoods)

PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Ducting Examination Results (including exhaust stack, if applicable) PASS

Comments 1. The installed ducting has been assessed as fit for purpose and absent of defect.

Air Mover Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Air Cleaner Examination Results PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Page 57: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 6 of 10 Report Number: E35223010823

810c

Section 5 - Process Identification

Process Function(s) Knife Serrator's and Grinder

Process Machine Serial Number(s) Not established

Hazardous Substances Nickel, Silver and Grinding Medium Dusts

Section 6 - Management System

Risk/COSHH Assessment Reference not established

Where Assessment is Held Clients Intranet Site

Date of Assessment 30-Apr-2019

Created By Martin Carr

Workplace Air Monitoring/Sampling Reference

Where the Report is Held

Date of Report

Created By

Material Safety Data Sheet Reference Multiple Documents

Where the MSDS is Held Clients Intranet Site and Online

Date of Publication 30-Apr-2019

Created By Manufacturers

Ventilation System User Manual Reference

Where the Manual is Held

Date of Publication

Created By

Ventilation System Maintenance Log Book Reference

Where Log Book is Held

Date of Publication

Created By

Page 58: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 7 of 10 Report Number: E35223010823

810c

Commissioning/Initial Appraisal Report Reference

Where Report is Held

Date of Report

Created By

Previous Thorough Examination and Test Report Reference E35223010244

Where Report is Held Clients Intranet Site

Date of Report 22-Oct-2018

Created By Allianz

Evidence of Housekeeping PASS

Comments 1. There is evidence of effective Housekeeping of the Ventilation System and surrounding Workplace areas,assessed through;- Observations made at the time of the TExT

Evidence of Maintenance PASS

Comments 1. There is evidence of effective Maintenance of the Ventilation System, assessed through;- Observations made at the time of the TExT

Evidence that the Engineering Control is being applied correctly PASS

Comments 1. With the exception of defects identified within section 2 of this report (if applicable), no furtherobservations arising.

Page 59: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 8 of 10 Report Number: E35223010823

810c

Section 7 - Quantitative Test Results

Calibrated Test Equipment

Thermal Anemometer Calibration Date Rotating Vane Anemometer Calibration Date

120622 11-Sep-2018 Not Used 22-Jun-2018

Electronic Manometer Calibration Date Other Calibration Date

ACEEM068 20-Apr-2018 Not used

Test Datum Date: 30-Apr-2019

Test Datum Reference (Type/Ref. no.) This report

I.D. Number Air Cleanerinlet Pressure(Pa)

Datum Air Cleaneroutlet Pressure(Pa)

Datum PressureDifference (Pa)

Datum

1 -700 -700 -859 -859 159 159

Other Test Point Reference(s) Other Quantitative Results

Point ID Duct/Face/Point Profile Hood/DuctSize (m)

StaticPressure (Pa)

VelocityPressure (Pa)

Face/DuctVelocity (m/s)

Volume Flow(m3/s)

TP 1 Knife Serrator HoodDuct

Circular 0.1 -71 90 12.33 0.09684

Datum: -71 90 12.33 0.09684

TP 2 Grinder Hood Duct Circular 0.1 -152 81 11.7 0.09189

Datum: -152 81 11.7 0.09189

TP 3 New Serrator HoodFace

Oblong 0 x 0 -16 4.13 0

Datum: -16 4.13 0

Page 60: Contract Number: Policy Number: NV09796703 E35223012724 ...

Ventilation Plant Report

Side 9 of 10 Report Number: E35223010823

810c

Section 8 - System Diagram/Photos

The above items were seen at:(If blank, refer to the location details)

Examination carried out on behalf of: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

This report shall not be reproduced without the approval of Allianz Engineering and the Client for whom it was produced.

Page 61: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH

E35223010244

30-APR-2018

22-OCT-2018

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 322-OCT-2018

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 3Maximum number that can be used at one time 3Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Cross-reference with the last Thorough Examination and Test report

(E35223009542 - dated 30/04/2018)

2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.

Page 62: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223010244

3/ Condition at the Time of Test: 2 points open , as verbally indicated as the normal operating procedure.Grinder in use.

4/ No air flow indicators are present at appropriate points on the system to indicate the system isfunctioning correctly. Reference should be made to HSG 258 regarding the installation of air flowindicators.

5/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

6/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. See observations section.

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Page 63: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223010244

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-778 -856 78

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -132 14.59 0.12

TP 2 Grinder Duct 0.10 -142 12.60 0.10

TP 3 New Serator Face 2.74

Calibrated Test Equipment Details

Thermal Anemometer 120622Electronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 64: Contract Number: Policy Number: NV09796703 E35223012724 ...

1

Martin Carr

From: LEV43 <[email protected]>Sent: 15 May 2018 09:57To: [email protected]: EDIT: 4009771310712045095 https://hs.carrs-silver.co.uk/LEV043.pdf

Item LEV43

HS Reference https://hs.carrs-silver.co.uk/LEV043.pdf

Due Date 01-05-2018

Status Completed+

Comments/Notes 01/05/18 Airflow meter to be fitted

Job Type HS Job

Notifier [email protected]

Note you can also reply to this e-mail. 4009771310712045095

Page 65: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH

E35223009542

06-NOV-2017

30-APR-2018

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 330-APR-2018

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 3Maximum number that can be used at one time 3Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Cross-reference with the last Thorough Examination and Test report

(E35223008324 - dated 02/05/2017)

2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.

Page 66: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223009542

3/ Condition at the Time of Test: All points open - Process stood down.

4/ No air flow indicators are present at appropriate points on the system to indicate the system isfunctioning correctly. Reference should be made to HSG 258 regarding the installation of air flowindicators.

5/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

6/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. See observations section.

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Page 67: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223009542

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-658 -856 92

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -71 8.72 0.07

TP 2 Grinder Duct 0.10 -61 6.75 0.05

TP 3 New Serator Face 2.32

Calibrated Test Equipment Details

Thermal Anemometer 120622Electronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 68: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH

E35223008926

02-MAY-2017

06-NOV-2017

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 306-NOV-2017

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 3Maximum number that can be used at one time 3Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Cross-reference with the last Thorough Examination and Test report

(E35223008324 - dated 02/05/2017)

2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.

Page 69: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223008926

3/ Condition at the Time of Test: All points open - Process stood down.

4/ No air flow indicators are present at appropriate points on the system to indicate the system isfunctioning correctly. Reference should be made to HSG 258 regarding the installation of air flowindicators.

5/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

6/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. See observations section.

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Page 70: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223008926

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-733 -846 113

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -68 8.72 0.07

TP 2 Grinder Duct 0.10 -51 7.00 0.06

TP 3 New Serator Face 1.35

Calibrated Test Equipment Details

Thermal Anemometer Not UsedElectronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 71: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH

E35223008324

24-OCT-2016

02-MAY-2017

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 302-MAY-2017

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 3Maximum number that can be used at one time 3Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Cross-reference with the last Thorough Examination and Test report

(E35223006406 - dated 19/10/2015)

2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.

Page 72: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223008324

3/ Condition at the Time of Test: All points open - Process stood down.

4/ No air flow indicators are present at appropriate points on the system to indicate the system isfunctioning correctly. Reference should be made to HSG 258 regarding the installation of air flowindicators.

5/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

6/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. See observations section.

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Page 73: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223008324

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-703 -856 153

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -64 7.69 0.06

TP 2 Grinder Duct 0.10 -58 7.69 0.06

TP 3 New Serator Face (not inuse)

Calibrated Test Equipment Details

Thermal Anemometer Not UsedElectronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 74: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH

E35223007756

18-APR-2016

24-OCT-2016

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 324-OCT-2016

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 3Maximum number that can be used at one time 3Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Cross-reference with the last Thorough Examination and Test report

(E35223007037 - dated 18/04/2016)

2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.

Page 75: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223007756

3/ Condition at the Time of Test: All points open - Process stood down.

4/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

5/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. See observations section.

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Page 76: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223007756

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-762 -859 97

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -55 8.43 0.07

TP 2 Grinder Duct 0.10 -55 7.35 0.06

TP 3 New Serator Face 2.49

Calibrated Test Equipment Details

Thermal Anemometer 120622Electronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 77: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH

E35223007037

19-OCT-2015

18-APR-2016

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 318-APR-2016

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 3Maximum number that can be used at one time 3Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Cross-reference with the last Thorough Examination and Test report

(E35223006406 - dated 19/10/2015)

2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.

Page 78: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223007037

3/ Condition at the Time of Test: All points open - Process stood down.

4/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

5/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. See observations section.

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Page 79: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223007037

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-775 -856 81

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -71 9.01 0.07

TP 2 Grinder Duct 0.10 -61 7.35 0.06

TP 3 New Serator Face 4.21

Calibrated Test Equipment Details

Thermal Anemometer Not UsedElectronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 80: Contract Number: Policy Number: NV09796703 E35223012724 ...

1

Martin Carr

From: Knife Serator and Grinder [[email protected]]Sent: 03 November 2015 11:14To: [email protected]: EDIT: Completed HS Job 03-11-2015

Question Answer

Item Knife Serator and Grinder

HS Reference https://hs.carrs-silver.co.uk/LEV043.pdf

Due Date 03-11-2015

Status Completed

Comments/Notes

21/10/2015 Asked D Woodhead to investigate Its already on the plan when fitting the CATRA sharpener. Is it the bag needs empty or replace? Empty and clean out End user job or Maint? 02/11/15 Daz to investigate and report back 03/11/15 It was agreed that this is a job for the end user, much like removing the waste from the bin. It will now be emptied by those using it.

Job Type HS Job

Notifier [email protected]

Note you can also reply to this e-mail. 321258416690984305

Page 81: Contract Number: Policy Number: NV09796703 E35223012724 ...

Submission ID 321258416690984305

Submission Date 2015-10-21 18:40:16

Item Knife Serator and Grinder

HS Reference https://hs.carrs-silver.co.uk/LEV043.pdf

Due Date 28-10-2015

Status Outstanding

Comments/Notes 21/10/2015 Asked D Woodhead to investigate

Its already on the plan when fitting the CATRA sharpener. Is it the bag needs empty orreplace?

Job Type HS Job

Carrs HS Jobs

Page 82: Contract Number: Policy Number: NV09796703 E35223012724 ...

Submission ID 321258416690984305

Submission Date 2015-10-21 18:40:16

Item Knife Serator and Grinder

HS Reference https://hs.carrs-silver.co.uk/LEV043.pdf

Due Date 28-10-2015

Status Outstanding

Comments/Notes 21/10/2015 Asked DW to investigate

Job Type HS Job

Carrs HS Jobs

Page 83: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH

E35223006406

20-APR-2015

19-OCT-2015

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 319-OCT-2015

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 2Maximum number that can be used at one time 2Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

1/ The increase in pressure differential across the filter bags suggests that they require cleaning /renewing.

Other Observations

1/ Due to the absence of a Commissioning Report and reference to any previous inspection reports, a firstthorough examination and test was carried out (Allianz Report No E35223004707 ,dated 15/04/2014) toestablish a benchmark for the monitoring of performance of the system. Please note the LEV system hasbeen examined and tested in worst case (all points open) or as identified as the normal operatingarrangement.

Page 84: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223006406

2/ Cross-reference with the last Thorough Examination and Test report

(E35223005697 - dated 20/4/2015)

3/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.

4/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

5/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. Process stood down

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Page 85: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223006406

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-457 -816 359

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -100 10.15 0.08

TP 2 Grinder Duct 0.10 -38 9.28 0.07

Calibrated Test Equipment Details

Thermal Anemometer Not UsedElectronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 86: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH

E35223005697

16-OCT-2014

20-APR-2015

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 320-APR-2015

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 2Maximum number that can be used at one time 2Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Due to the absence of a Commissioning Report and reference to any previous inspection reports, a firstthorough examination and test was carried out (Allianz Report No E35223004707 ,dated 15/04/2014) toestablish a benchmark for the monitoring of performance of the system. Please note the LEV system hasbeen examined and tested in worst case (all points open) or as identified as the normal operatingarrangement.

2/ Cross-reference with the last Thorough Examination and Test report

Page 87: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223005697

(E35223005225 - dated 16/10/2014)

3/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.

4/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

5/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. Process stood down

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

admin
Sticky Note
Not available due to age of machine
Page 88: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223005697

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-800 -872 72

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -113 8.42 0.07

TP 2 Grinder Duct 0.10 -94 7.00 0.06

Calibrated Test Equipment Details

Thermal Anemometer Not UsedElectronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 89: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH

E35223005225

15-APR-2014

16-OCT-2014

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 316-OCT-2014

Type of Inspection Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 2Maximum number that can be used at one time 2Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

None

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Due to the absence of a Commissioning Report and reference to any previous inspection reports, a firstthorough examination and test was carried out (Allianz Report No E35223004707 ,dated 15/04/2014) toestablish a benchmark for the monitoring of performance of the system. Please note the LEV system hasbeen examined and tested in worst case (all points open) or as identified as the normal operatingarrangement.

2/ Test results recorded indicate no marked system performance deterioration since the last Thorough

Page 90: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 3 E35223005225

Examination and Test.

3/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

4/ Refer to Report No E35223004707 - dated 15/04/2014, for system diagram.

Condition at Time of Test Normal. Process stood down

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

admin
Sticky Note
See COSHH
admin
Sticky Note
Not available
Page 91: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 3 E35223005225

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-580 -820 240

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -77 9.28 0.07

TP 2 Grinder Duct 0.10 -94 7.35 0.06

Calibrated Test Equipment Details

Thermal Anemometer Not UsedElectronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther Not Applicable

Examination carried out on behalf of:Client NameAddress

This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH

Page 92: Contract Number: Policy Number: NV09796703 E35223012724 ...

Carrs Machine Record Sheet

Submission Date 2014-04-24 14:18:39

Machine ID lev043

Person doing work Shaun Whitaker

Fault http://hs.carrs-silver.co.uk/lev043.pdf

Parts Used Metal sheeting

Work Done Additional guarding and extraction ducting

Further Work retest by insurance inspector

1

Page 93: Contract Number: Policy Number: NV09796703 E35223012724 ...

Date of previous examination and tests

Location

Contract No.Policy No. Report No.

Name of User

005

Date of commencement of examination and tests

Date of Report

Engineer Surveyor

Competent PersonAllianz Engineering

+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081

V810b

Local Exhaust Ventilation Plant Report

CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE

NV09796703

TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH

E35223004707

Unknown

15-APR-2014

Andrew Allen

Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.

www.allianzengineering.co.uk

Health & Safety at Work etc. Act 1974

Side 1 of 515-APR-2014

Type of Inspection Failed First Thorough Examination and Test

Regulations Applicable Regulation 9 of COSHH

Identification of LEV Plant and Process

Plant Number LEV 043Manufacturer Not EstablishedSerial Number Not EstablishedLocation of Air Mover Handle DepartmentLocation of Process Handle DepartmentProcess(es) being controlled Knife Serator and GrinderHazardous substance(s) being controlled Nickel, Silver and Grinding Medium DustsNumber of Extraction Points 2Maximum number that can be used at one time 2Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No

Visual Assessment of the level of control UnsatisfactoryAir Sampling Results We recommend the return air be monitored to

ensure that it is not above the set limits for thecontaminants.

Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements

Defects AFFECTING the level of control and particulars of any repairs or modifications required

1/ Contaminant dusts escape capture at the Knife Serator and can enter the operators breathing zoneand workplace. Suitable repairs/modifications should be carried out to provide adequate EngineeringControl.

Emergency Report and "Do Not Use" label issued to Marc Horner, at the time of inspection.

Defects NOT affecting the level of control and particulars of any repairs or modifications required

None

Other Observations

1/ Due to the absence of a Commissioning Report and reference to any previous inspection reports, a firstthorough examination and test was carried out (Allianz Report No E35223004707 ,dated 15/04/2014) toestablish a benchmark for the monitoring of performance of the system. Please note the LEV system hasbeen examined and tested in worst case (all points open) or as identified as the normal operatingarrangement.

Page 94: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 2 of 5 E35223004707

2/ COSHH Management System Documentation

The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;

Risk Assessment / COSHH Assessment

Material Safety Data Sheet(s)

The following supporting documents have not been witnessed;

Air Monitoring/Sampling Report(s),

Commissioning Report

LEV User Manual/ Logbook

3/ See additional cover for system diagram.

Condition at Time of Test Normal.

Fan Details

Manufacturer Not EstablishedSerial NumberType CentrifugalRotation (viewed from drive end) Clockwise

mØSize 0.20Volume Flow m s3 -1

Speed rpm3450

Motor Details

Manufacturer BaldorSerial no.Speed rpm3450Power kW0.55

Page 95: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 3 of 5 E35223004707

Primary Filter

Medium Fabric BagsCollector Type Metal TrayEfficiency %

Secondary Filter

MediumCollector TypeEfficiency %

Details of Test Results

Primary filter inlet Pressure(Pa)

Primary filter outlet Pressure(Pa)

Pressure Difference(Pa)

-531 -830 299

-13

Test Point and Type Size Results of Inspection

Duct / Face / PointHood / Duct

Size(m)

StaticPressure

(Pa)

Face / DuctVelocity(ms )

Point No.-1

VolumeFlow

(m s )TP 1 Knife Serator Duct 0.10 -97 8.42 0.07

TP 2 Grinder Duct 0.10 -94 7.35 0.06

Calibrated Test Equipment Details

Thermal Anemometer Not UsedElectronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther Not Applicable

Page 96: Contract Number: Policy Number: NV09796703 E35223012724 ...

Report No.

V810b

Local Exhaust Ventilation Plant Report

Health & Safety at Work etc. Act 1974

Side 4 of 5 E35223004707


Recommended