NGC-40-HTC/NGC-40-HTC3Control and monitoring modules for use with the rayChem ngC-40 system installation instruCtions
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14
HTC3
or
HTC
B
A
DESCRIpTIONThe NGC-40-HTC (for single-phase heaters) and NGC-40-HTC3 (for three-phase heaters) modules are used to control either a solid-state relay or contactor within the NGC-40 control and monitoring system. This module also has one alarm output and one digital input. The alarm output can be used to control an external annunciator. The digital input is programmable and may be used for various functions such as forcing outputs on and off. Other features of this module include ground-fault and line current sensing for both HTC and HTC3. The front panel of the HTC module has LED indicators for various status conditions. The front panel also provides a ground-fault and heater test button.
TOOLS REqUIRED• Smallflat-bladescrewdriver
ADDITIONAL MATERIALS REqUIRED• Powersupply24Vdc@100mAperNGC-40-HTC/HTC3• CustombuiltCANcableswithRJ-45connections• CANTerminationResistor
KIT CONTENTS
Item qty Description
A 1 NGC-40-HTCmodule(single-phaseheaters)
or
B 1 NGC-40-HTC3 module (three-phase heaters)
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire.
For technical support, call Pentair at (800) 545-6258.
WARNING:
AppROvALS
Class I, Div. 2, Groups A,B,C,D T4Class I, Zone 2, AEx nC IIC T4 IP20Ex nL nC IIC T4 X–40˚C ≤ Ta ≤ +65˚C
Conforms to: FM Class Number 3600 (11/98)FM Class Number 3611 (10/99)ANSI/UL STD. 60079-15-2009UL STD. 61010-1
Certified to:CAN/CSA STD. C22.2 No. 213-M1987 (R2004)CAN/CSA STD. C22.2 No. 61010-1:2004EN 61010-1 (2001)CAN/CSA STD. E60079-15:02 (R2006)
Hazardous Locations
(Russia,Kazakhstan,Belarus) ForothercountriescontactyourlocalPentairrepresentative.
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14 2/10
GENERALSupplyvoltage 24Vdc±10%Internal power consumption <2.4WperNGC-40-HTC/HTC3moduleAmbientoperatingtemperature –40ºCto65ºC(–40ºFto149ºF)Ambientstoragetemperature –40ºCto75ºC(–40ºFto167ºF)Environment PD2,CATIIIMax. altitude 2,000m(6,562ft)Humidity 5–90%noncondensingMounting DinRail–35mm
ELECTROMAGNETIC COMpATIbILITyEmissions EN61000-6-3 Emissionstandardforresidential,commercialandlight
industrial environmentsImmunity EN61000-6-2 Immunitystandardforindustrialenvironments
TEMpERATURE SENSORSType 100ΩplatinumRTD,3-wire,α =0.00385ohms/ohm/ºCCanbeextended
witha3-conductorshieldedcableof20Ωmaximumperconductor
100Ω,Ni-Fe,2-wireCanbeextendedwitha2-wireshieldedcableof20Ωmaximum per conductor
Quantity One per NGC-40-HTC/HTC3 module
CURRENT SENSORS (internal to the module)Quantity per NGC-40-HTC/HTC3 1 for ground-fault measurementsQuantity per NGC-40-HTC 1 for single-phase line current measurements Quantity per NGC-40-HTC3 3 for three-phase line current measurementsMaximumLine-LineVoltage: 1000Vac
ALARM RELAyDry contact relay (voltage free) Relaycontactrated250V/3A
50/60Hz(CE)and277V/3A50/60Hz(c-CSA-us).Alarmrelayisprogrammable.NOandNCcontactsavailable.
CONTACTOR OUTpUT RELAyRelaycontactrated250V/3A50/60Hz(CE)and277V/3A50/60Hz(c-CSA-us).
DIGITAL INpUTMulti-purpose input Multi-purpose input for connection to external dry (voltage-free) contact
orDCvoltage.Maybeuserprogrammablefor:notused/forceoff/forceon functions. It can be configured to be active open or active closed.
CAN NETwORKING pORTType 2-wireisolatedCAN-basedpeertopeernetwork.Isolatedto24Vdc–
verifiedby500VrmsdielectricwithstandtestConnection Two8-pinRJ-45connectors(bothmaybeusedforInputorOutput
connections)Protocol ProprietaryNGC-40Topology Daisy chainCable length 10 m (33 ft) maximumQuantity Upto80HTC/HTC3andIOmodulespernetworksegmentAddress Unique,factoryassigned
CONNECTION TERMINALSWiringterminals Cageclamp,0.5to2.5mm2(24to12AWG)
HOUSINGSize 45.1mm(1.78in)widex87mm(3.43in)highx106.4mm(4.2in)deep
LINE CURRENT SENSORSMax current 60AAccuracy ±2%ofreading
GROUND-FAULT SENSORRange 10–250mAAccuracy ±2%ofrange
OUTpUTSSSRoutput 12Vdc@45mAmaxperoutput
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14
Front Top Bottom Back
45.1 mm (1.78 in)
45.1 mm (1.78 in) 45.1 mm (1.78 in)
45.1 mm (1.78 in)
87 m
m (3
.43
in)
87 m
m (3
.43
in)
106.
4 m
m (4
.2 in
)
Bottom Back
45.1 mm (1.78 in)
45.1 mm (1.78 in)
87 m
m (3
.43
in)
3PH
Front
HTC
HTC3
Top
45.1 mm (1.78 in)
45.1 mm (1.78 in)
87 m
m (3
.43
in)
106.
4 m
m (4
.2 in
)1PH
3 / 10
System Components
System Components (Continued)
A. wiring terminalsTerminals Function
1 AlarmrelayN.O.
2 AlarmrelayCOM
3 AlarmrelayN.C.
4 Not used
5 SSROut+
6 SSROut–
7 DigitalIn+
8 Digital In –
9 Line In
10 Line Out
11 Coil Out
12
13 TSCOM(Wht)
14 TSSense(Red)
15 TSSource(Red)
16 Not used
b. CAN bus/module power
C. Reset
D. Status LEDs
Status: Indicates status of HTC/HTC3 module
Off No powerGreen Normaloperation,nointernalfaultsYellow In Factory modeRed HTC/HTC3operatingstatusFlashR InternalFault:FlashR/G FactorystatusFlashR/Y Internalfaultdetected
Network: IndicatesCANnetworkactivityOff NonetworkactivityGreen FlickeronreceiptofnetworkdataYellow Flickerontransmissionofnetwork
dataFlashR Networkcommunicationfailure
Input: ShowsstatusofdigitalinputOff Input is inactive (open)Green Input is active (shorted)FlashR Ext.inputsourcefailure
Output: ShowsstatusofcontactororSSROff Output offGreen Follows output state
Heater: Indicates the heater's alarm status
Off No alarmRed Highorlowcurrentorresistance
alarmFlashR Overcurrent trip alarm
TS: Indicates the temperature alarm status
Off No alarmRed HighorlowtemperaturealarmFlashR Temperature sensor failure
GFI: Indicates ground-fault statusOff No alarmRed Highorlowground-faultalarmFlashR Ground-faulttripalarm
Switch: Indicatescontactor/SSRswitchstatus
Off No alarmRed ContactorcyclecountalarmFlashR Switchfailedshortedon
wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14 4 / 10
CAN terminationhere if last one
in chain
CAN terminationhere if last one
in chain
Cable fromanother moduleor power supply
Cable fromanother moduleor power supply
HTCHTC
1313 1414 1515 1616
Terminal blockTerminal block
RTDRTD
13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used
13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used
HTC RTDWiring
HTC RTDWiring
HTCHTC
1PH1PH
1
2
1
2
EachNGC-40-HTC/HTC3mountsonaDIN35rail.
MOUNTING: InserttherearbottomofthemoduleintotheDINrail,thenpushupand inwards to engage the clip.
Thepowersupply/CANconnectorisanRJ-45connector.
TheCANterminationdevicemustbeinstalledintheunusedport of the last module.
Connections are the same for the HTC3.
ForallRTDterminations,theRTDfieldwiresmustbeterminatedonapanel-mountedterminalblock.
Connections are the same for the HTC3.
REMOvAL: Pushthemoduleupwardstodisengagetheclip,thenrotatethemodule toward you.
Mounting the NGC-40-HTC/HTC3
power Supply/CAN
RTD Input Connections – North American Installation Technique
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14 5/10
1313 1414 1515 1616
Fieldterminal block
Fieldterminal block
RTDRTD
13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used
13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used
HTC RTDWiring
HTC RTDWiring Earth grounding
bar located at theHTC modulebar located
1PH1PH
HTCForallRTDterminations,theRTDfieldwiresmustbeterminatedonapanel-mountedterminalblock.TheRTDcableshieldfromthefieldterminalblocktotheHTCmoduleshouldbe terminated at the earth ground bar located near the module.
Connections are the same for the HTC3.
RTD Input Connections – European Installation Technique
99
1111To heat-tracing
To heat-tracing
contactorcontactor contactorcoilcontactorcoil
Controlpower
Controlpower
L1L1
N or L2N or L2
N or L2N or L2Coil OutCoil Out
L1 (in)L1 (in)
HTC3Three-PhaseHTC3Three-Phase L1L1
NN
L3L3
Circuit breakerCircuit breaker
L2L2
L1L1
NN
L2L2
L3L3
99
1111
To heat-tracing
To heat-tracing
ContactorContactor
Contactorcoil
Contactorcoil
Coil outCoil outControlpowerControlpowerL1 (in)L1 (in)
N or L2N or L2
Terminals9and11switchvoltagetothecontactorcoils.The internal pilot relay will switch the supply voltage (up to 277V)tothecontactorcoil.Refertothediagramattheendofthisdocumentcalled“NGC-40CANbusConnectionsforUp to 10 Modules” for detail wiring.
Note: Exposure to some chemicals may degrade the sealing propertiesoftherelayoutput,manufacturedbyNAIS,PNJQ1P-12V.Periodicallyinspecttherelayoutputfordegradationof properties and replace if any degradation is found.
Connections are the same for the HTC3.
HTC Relay Output Connections to Contactors - Single-phase HTC3 Relay Output to Contactor - Three-phase
wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.
wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14
11
NONO CC
Failsafe Mode:Contacts shown
energized withno alarm condition
Failsafe Mode:Contacts shown
energized withno alarm condition
NCNC
22 33
Alarm RelayAlarm Relay
HTCHTC
1PH1PH
6 / 10
Alarm
1313 1414 1515 1616
Fieldterminal block
Fieldterminal block
RTDRTD
13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used
13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used
HTC RTDWiring
HTC RTDWiring Earth grounding
bar located at theHTC modulebar located
1PH1PH
HTC
1313 1414 1515 1616
Fieldterminal block
Fieldterminal block
RTDRTD
13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used
13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used
HTC RTDWiring
HTC RTDWiring Earth grounding
bar located at theHTC modulebar located
1PH1PH
HTCTerminals5&6switchvoltagetotheSSR.TheinternalSSRdriverwillswitchtheinternalsupplyvoltage(12Vdc)totheSSR.
HTC Output Connections to SSR - Single-phase HTC3 Output Connections to SSR - Three-phase
wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.
wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.
5512
Vdc12
Vdc
++ ––
~~ ~~
66
To heat-tracingTo heat-tracing
N or L2N or L2
L1L1
L1L1
Nor L2Nor L2
SSRSSR
L1L1
Circuit breaker
N or L2
N or L2
HTCSingle-PhaseHTCSingle-Phase
1PH1PH
To heat-tracingTo heat-tracing
L1L1
NN
L3L3
L2L2
L1L1
L3L3
L2L2
HTC3Three-PhaseHTC3Three-Phase
L1L1
NN
L3L3
Circuit breakerCircuit breaker
L2L2
NNL1L1
L3L3
L2L2
55
++
––
66
SSRSSR
++
––~~~~
~~~~
~~~~
SSRSSR
++
––SSRSSR
3PH3PH
Note: Exposuretosomechemicalsmaydegradethesealingpropertiesofthealarmrelay,manufacturedbyNAIS,PNJQ1P-12V.Periodicallyinspectthealarmrelayfordegradationofproperties and replace if any degradation is found.
Multi-purpose.Alarmrelayenergizedinnormalstate.
ThealarmrelayisconfiguredasFailSafe.
ThealarmrelayconnectionsprovideaformCdrycontact,ratedat277Vmax(3A).
TheNO(normallyopen)contactisopeninnon-energizedcondition.Whenenergized,itclosesduringnormalconditionsandwillopenuponanalarmcondition or power failure.
TheNC(normallyclosed)contactisclosedinnon-energizedcondition.Whenenergized,itopensduringnormalconditionsandwillcloseuponanalarmcondition or power failure.
Relaycontactrated250V/3A50/60Hz(CE)277V/3A50/60Hz(c-CSA-us)
Connections are the same for the HTC3.
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14
From user inputFrom user input
Digital InputDigital Input
77 88
++ ––
++ ––
Terminalblock
Terminalblock
Earth groundingbar located at theHTC module
Earth groundingbar located at theHTC module
From user inputFrom user input
Digital InputDigital Input
North AmericanInstallations
North AmericanInstallations
EuropeanInstallations
EuropeanInstallations
77 88
++ ––
++ ––
Terminalblock
Terminalblock
HTCHTC
1PH1PH
HTCHTC
1PH1PH
7 / 10
1. provide suitable panel enclosure
The NGC-40-HTC or NGC-40-HTC3 must be mounted in an enclosure to protect its electronic components. For indoor applications,useaminimumNEMA1enclosure(NEMA12recommended).Foroutdoorapplications,useaNEMA4orNEMA4Xenclosuredependingontherequirements.
Note: TheRaychemNGC-40-HTCorNGC-40-HTC3isde-signed for operation in ambient temperatures from –40°C to65°C(–40°Fto149°F).Iftheambienttemperatureisoutsidethisrange,aspaceheaterand/orcoolingfanwillbe required in the panel.
2. Determine locations for the NGC-40-HTC or NGC-40-HTC3 assembly in the electrical panel.
The NGC-40-HTC or NGC-40-HTC3 should be located in the rear of the panel. The NGC-40-HTC or NGC-40-HTC3 assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or ex-cessive vibration.
*NorthAmericanpanelinstallationtechniques
PS1
PTM
1
CBM
I/O1
I/O2
I/O3
I/O4
I/O5
PS2
PTM
2
HTC
1
HTC
2
HTC
3
HTC
4
HTC
5
HTC
6
HTC
7
HTC
8
HTC
9
HTC
10
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10
PS3
PTM
3
HTC
11
HTC
12
HTC
13
HTC
14
HTC
15
HTC
16
HTC
17
HTC
18
HTC
19
HTC
20
C11
C12
C113 C4 C5 C16
C17
C18
C19
C20
PS4
PTM
4
HTC
21
HTC
22
HTC
23
HTC
24
HTC
25
HTC
26
HTC
27
HTC
28
HTC
29
HTC
30
C21
C22
C23
C24
C25
TB
C26
C27
C28
C29
C30
PanelPaneldoor
Alarmlight
Digital Input Connections – North American and European Installation Techniques
provide Suitable panel Enclosure and Determine Locations for NGC-40-HTC or NGC-40-HTC3 Assembly in panel*
Digital Input Multi-purpose input for connection to external dry (voltage free) contact or DC voltage.
Rating 100Ωmaxloopresistanceor5-24Vdc@1mAmaximum
Connections are the same for the HTC3.
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14 8 / 10
Power/Termination
Module
Power/Termination
Module
CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc
ININ OUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 10
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 4
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 3
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 2
ININ OUTOUT
CAN / 24 Vdc
BridgeModule
80 Modulesper Bridge
Module 1++
––20 Modulesper Power Supply
20 Modulesper Power Supply
20 Modulesper Power Supply
20 Modulesper Power Supply
TerminationBlock
TerminationBlock
100-240 Vac In100-240 Vac In
Optional redundant supplyOptional redundant supply
100-240 Vac In100-240 Vac In
++
––
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
ININ OUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 20
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 14
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 13
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 12
ININ
CAN / 24 Vdc
HTC/HTC3orI/O
Module 11
OUTOUT
TerminationBlock
TerminationBlockCAN / 24 Vdc CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc CAN / 24 Vdc
Power/Termination
Module
Power/Termination
Module
CAN / 24 Vdc
Primary Supply*24 Vdc
Primary Supply*24 Vdc
* Power supply shall have a means for disconnect from line voltage* Power supply shall have a means for disconnect from line voltage
Redundant Supply*24 Vdc
Redundant Supply*24 Vdc
ININ OUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 10
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 4
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 3
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 2
ININ OUTOUT
CAN / 24 Vdc
BridgeModule
80 Modulesper Bridge
Module 1
TerminationBlock
TerminationBlock
++
––
Power/Termination
Module
Power/Termination
Module
Primary Supply*24 Vdc
Primary Supply*24 Vdc
20 Modulesper Power Supply
20 Modulesper Power Supply
TerminationBlock
TerminationBlock
CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc
100-240 Vac In100-240 Vac In
Optional redundant supplyOptional redundant supply
100-240 Vac In100-240 Vac In
++
––
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
Redundant Supply*24 Vdc
Redundant Supply*24 Vdc
20 Modulesper Power Supply
20 Modulesper Power Supply
* Power supply shall have a means for dicsonnect from line voltage* Power supply shall have a means for dicsonnect from line voltage
NGC-40 CAN bus Connections for Up to 10 Modules
NGC-40 CAN bus Connections for Up to 20 Modules
INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087 12/14
Power/Termination
Module
Power/Termination
Module
CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc
Power/Termination
Module
Power/Termination
Module
CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc
Power/Termination
Module
Power/Termination
Module
CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc
Power/Termination
Module
Power/Termination
Module
CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc
ININ OUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 10
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 4
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 3
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 2
ININ OUTOUT
CAN / 24 Vdc
BridgeModule
80 Modulesper BridgeModule 1
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
ININ OUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 20
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 14
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 13
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 12
ININ OUTOUT
CAN / 24 Vdc
BridgeModule
80 Modulesper BridgeModule 11
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
ININ OUT
CAN / 24 Vdc
HTC/HTC3)orI/O
Module 30
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 24
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 23
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 22
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 21
++
––20 Modulesper Power Supply
20 Modulesper Power Supply
100-240 Vac In100-240 Vac In
20 Modulesper Power Supply
20 Modulesper Power Supply
100-240 Vac In100-240 Vac In
Optional redundant supplyOptional redundant supply
++
––
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc CAN / 24 Vdc
ININ OUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 40
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 34
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 33
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 32
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3orI/O
Module 31
TerminationBlock
TerminationBlockCAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
++
––20 Modulesper Power Supply
20 Modulesper Power Supply
TerminationBlock
TerminationBlock
100-240 Vac In100-240 Vac In
20 Modulesper Power Supply
20 Modulesper Power Supply
100-240 Vac In100-240 Vac In
Optional redundant supplyOptional redundant supply
++
––
CAN / 24 Vdc
CAN / 24 Vdc
Primary Supply*24 Vdc
Primary Supply*24 Vdc
* Power supply shall have a means for disconnect from line voltage* Power supply shall have a means for disconnect from line voltage
Redundant Supply*24 Vdc
Redundant Supply*24 Vdc
Primary Supply*24 Vdc
Primary Supply*24 Vdc
Redundant Supply*24 Vdc
Redundant Supply*24 Vdc
9/10
NGC-40 CAN bus Connections for Up to 40 Modules
10 / 10EN-RaychemNGC40HTC-IM-H58087 PCN1244-009548 12/14
The NGC-40-HTC/HTC3 contains no user serviceable parts. ContactyourPentairrepresentativeforserviceandanRMAnumber if required.
wARNING: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2 hazardous and nonhazardous locations
wARNING: Explosion Hazard - Do not replace NGC-40-pTM unless power has been switched off or the area is known to be nonhazardous
wARNING: Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is known to be nonhazardous
AvERTISSEMENT - Risque D'explosion - La substitution de composants peut rendre ce matériel inacceptable pour les emplacements de Classe I, Division 2
AvERTISSEMENT - Risque D'explosion - Couper le courant ou s'assurer que l'emplacement est désigné non dangereux avant de replacer le NGC-40-pTM
AvERTISSEMENT - Risque D'explosion - Avant de déconnecter l'equipement, couper le courant ou s'assurer que l'emplacement est désigné non dangereux
Servicing
INDUSTRIAL HEAT TRACING SOLUTIONS
WWW.PENTAIRThERmAl.COm
AllPentairtrademarksandlogosareownedbyPentairoritsglobalaffiliates.Pentairreservestherighttochangespecificationswithoutpriornotice.
©2007-2014Pentair.
NORTh AmERICA Tel: +1.800.545.6258Fax: +1.800.527.5703Tel: +1.650.216.1526Fax: [email protected]
EuROPE, mIddlE EAsT, AfRICATel: +32.16.213.511Fax: [email protected]
AsIA PACIfICTel: +86.21.2412.1688Fax: [email protected]
lATIN AmERICATel: +1.713.868.4800Fax: [email protected]