1 / 10 NGC-40-HTC/ NGC-40-HTC3 CONTROL AND MONITORING MODULES FOR USE WITH THE RAYCHEM NGC-40 SYSTEM INSTALLATION INSTRUCTIONS INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14 HTC3 or HTC B A DESCRIPTION The NGC-40-HTC (for single-phase heaters) and NGC-40-HTC3 (for three-phase heaters) modules are used to control either a solid-state relay or contactor within the NGC-40 control and monitoring system. This module also has one alarm output and one digital input. The alarm output can be used to control an external annunciator. The digital input is programmable and may be used for various functions such as forcing outputs on and off. Other features of this module include ground-fault and line current sensing for both HTC and HTC3. The front panel of the HTC module has LED indicators for various status conditions. The front panel also provides a ground-fault and heater test button. TOOLS REQUIRED • Small flat-blade screwdriver ADDITIONAL MATERIALS REQUIRED • Power supply 24 Vdc @100 mA per NGC-40-HTC/HTC3 • Custom built CAN cables with RJ-45 connections • CAN Termination Resistor KIT CONTENTS Item Qty Description A 1 NGC-40-HTC module (single-phase heaters) or B 1 NGC-40-HTC3 module (three-phase heaters) This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. For technical support, call Pentair at (800) 545-6258. WARNING: APPROVALS Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx nC IIC T4 IP20 Ex nL nC IIC T4 X –40˚C ≤ Ta ≤ +65˚C Conforms to: FM Class Number 3600 (11/98) FM Class Number 3611 (10/99) ANSI/UL STD. 60079-15-2009 UL STD. 61010-1 Certified to: CAN/CSA STD. C22.2 No. 213-M1987 (R2004) CAN/CSA STD. C22.2 No. 61010-1:2004 EN 61010-1 (2001) CAN/CSA STD. E60079-15:02 (R2006) Hazardous Locations (Russia, Kazakhstan, Belarus) For other countries contact your local Pentair representative.
Transcript

1 / 10

NGC-40-HTC/NGC-40-HTC3Control and monitoring modules for use with the rayChem ngC-40 system installation instruCtions

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14

HTC3

or

HTC

B

A

DESCRIpTIONThe NGC-40-HTC (for single-phase heaters) and NGC-40-HTC3 (for three-phase heaters) modules are used to control either a solid-state relay or contactor within the NGC-40 control and monitoring system. This module also has one alarm output and one digital input. The alarm output can be used to control an external annunciator. The digital input is programmable and may be used for various functions such as forcing outputs on and off. Other features of this module include ground-fault and line current sensing for both HTC and HTC3. The front panel of the HTC module has LED indicators for various status conditions. The front panel also provides a ground-fault and heater test button.

TOOLS REqUIRED• Smallflat-bladescrewdriver

ADDITIONAL MATERIALS REqUIRED• Powersupply24Vdc@100mAperNGC-40-HTC/HTC3• CustombuiltCANcableswithRJ-45connections• CANTerminationResistor

KIT CONTENTS

Item qty Description

A 1 NGC-40-HTCmodule(single-phaseheaters)

or

B 1 NGC-40-HTC3 module (three-phase heaters)

This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire.

For technical support, call Pentair at (800) 545-6258.

WARNING:

AppROvALS

Class I, Div. 2, Groups A,B,C,D T4Class I, Zone 2, AEx nC IIC T4 IP20Ex nL nC IIC T4 X–40˚C ≤ Ta ≤ +65˚C

Conforms to: FM Class Number 3600 (11/98)FM Class Number 3611 (10/99)ANSI/UL STD. 60079-15-2009UL STD. 61010-1

Certified to:CAN/CSA STD. C22.2 No. 213-M1987 (R2004)CAN/CSA STD. C22.2 No. 61010-1:2004EN 61010-1 (2001)CAN/CSA STD. E60079-15:02 (R2006)

Hazardous Locations

(Russia,Kazakhstan,Belarus) ForothercountriescontactyourlocalPentairrepresentative.

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14 2/10

GENERALSupplyvoltage 24Vdc±10%Internal power consumption <2.4WperNGC-40-HTC/HTC3moduleAmbientoperatingtemperature –40ºCto65ºC(–40ºFto149ºF)Ambientstoragetemperature –40ºCto75ºC(–40ºFto167ºF)Environment PD2,CATIIIMax. altitude 2,000m(6,562ft)Humidity 5–90%noncondensingMounting DinRail–35mm

ELECTROMAGNETIC COMpATIbILITyEmissions EN61000-6-3   Emissionstandardforresidential,commercialandlight

industrial environmentsImmunity EN61000-6-2   Immunitystandardforindustrialenvironments

TEMpERATURE SENSORSType 100ΩplatinumRTD,3-wire,α =0.00385ohms/ohm/ºCCanbeextended

witha3-conductorshieldedcableof20Ωmaximumperconductor

100Ω,Ni-Fe,2-wireCanbeextendedwitha2-wireshieldedcableof20Ωmaximum per conductor

Quantity One per NGC-40-HTC/HTC3 module

CURRENT SENSORS (internal to the module)Quantity per NGC-40-HTC/HTC3 1 for ground-fault measurementsQuantity per NGC-40-HTC 1 for single-phase line current measurements Quantity per NGC-40-HTC3 3 for three-phase line current measurementsMaximumLine-LineVoltage: 1000Vac

ALARM RELAyDry contact relay (voltage free) Relaycontactrated250V/3A

50/60Hz(CE)and277V/3A50/60Hz(c-CSA-us).Alarmrelayisprogrammable.NOandNCcontactsavailable.

CONTACTOR OUTpUT RELAyRelaycontactrated250V/3A50/60Hz(CE)and277V/3A50/60Hz(c-CSA-us).

DIGITAL INpUTMulti-purpose input Multi-purpose input for connection to external dry (voltage-free) contact

orDCvoltage.Maybeuserprogrammablefor:notused/forceoff/forceon functions. It can be configured to be active open or active closed.

CAN NETwORKING pORTType 2-wireisolatedCAN-basedpeertopeernetwork.Isolatedto24Vdc–

verifiedby500VrmsdielectricwithstandtestConnection Two8-pinRJ-45connectors(bothmaybeusedforInputorOutput

connections)Protocol ProprietaryNGC-40Topology Daisy chainCable length 10 m (33 ft) maximumQuantity Upto80HTC/HTC3andIOmodulespernetworksegmentAddress Unique,factoryassigned

CONNECTION TERMINALSWiringterminals Cageclamp,0.5to2.5mm2(24to12AWG)

HOUSINGSize 45.1mm(1.78in)widex87mm(3.43in)highx106.4mm(4.2in)deep

LINE CURRENT SENSORSMax current 60AAccuracy ±2%ofreading

GROUND-FAULT SENSORRange 10–250mAAccuracy ±2%ofrange

OUTpUTSSSRoutput 12Vdc@45mAmaxperoutput

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14

Front Top Bottom Back

45.1 mm (1.78 in)

45.1 mm (1.78 in) 45.1 mm (1.78 in)

45.1 mm (1.78 in)

87 m

m (3

.43

in)

87 m

m (3

.43

in)

106.

4 m

m (4

.2 in

)

Bottom Back

45.1 mm (1.78 in)

45.1 mm (1.78 in)

87 m

m (3

.43

in)

3PH

Front

HTC

HTC3

Top

45.1 mm (1.78 in)

45.1 mm (1.78 in)

87 m

m (3

.43

in)

106.

4 m

m (4

.2 in

)1PH

3 / 10

System Components

System Components (Continued)

A. wiring terminalsTerminals Function

1 AlarmrelayN.O.

2 AlarmrelayCOM

3 AlarmrelayN.C.

4 Not used

5 SSROut+

6 SSROut–

7 DigitalIn+

8 Digital In –

9 Line In

10 Line Out

11 Coil Out

12

13 TSCOM(Wht)

14 TSSense(Red)

15 TSSource(Red)

16 Not used

b. CAN bus/module power

C. Reset

D. Status LEDs

Status: Indicates status of HTC/HTC3 module

Off No powerGreen Normaloperation,nointernalfaultsYellow In Factory modeRed HTC/HTC3operatingstatusFlashR InternalFault:FlashR/G FactorystatusFlashR/Y Internalfaultdetected

Network: IndicatesCANnetworkactivityOff NonetworkactivityGreen FlickeronreceiptofnetworkdataYellow Flickerontransmissionofnetwork

dataFlashR Networkcommunicationfailure

Input: ShowsstatusofdigitalinputOff Input is inactive (open)Green Input is active (shorted)FlashR Ext.inputsourcefailure

Output: ShowsstatusofcontactororSSROff Output offGreen Follows output state

Heater: Indicates the heater's alarm status

Off No alarmRed Highorlowcurrentorresistance

alarmFlashR Overcurrent trip alarm

TS: Indicates the temperature alarm status

Off No alarmRed HighorlowtemperaturealarmFlashR Temperature sensor failure

GFI: Indicates ground-fault statusOff No alarmRed Highorlowground-faultalarmFlashR Ground-faulttripalarm

Switch: Indicatescontactor/SSRswitchstatus

Off No alarmRed ContactorcyclecountalarmFlashR Switchfailedshortedon

wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14 4 / 10

CAN terminationhere if last one

in chain

CAN terminationhere if last one

in chain

Cable fromanother moduleor power supply

Cable fromanother moduleor power supply

HTCHTC

1313 1414 1515 1616

Terminal blockTerminal block

RTDRTD

13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used

13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used

HTC RTDWiring

HTC RTDWiring

HTCHTC

1PH1PH

1

2

1

2

EachNGC-40-HTC/HTC3mountsonaDIN35rail.

MOUNTING: InserttherearbottomofthemoduleintotheDINrail,thenpushupand inwards to engage the clip.

Thepowersupply/CANconnectorisanRJ-45connector.

TheCANterminationdevicemustbeinstalledintheunusedport of the last module.

Connections are the same for the HTC3.

ForallRTDterminations,theRTDfieldwiresmustbeterminatedonapanel-mountedterminalblock.

Connections are the same for the HTC3.

REMOvAL: Pushthemoduleupwardstodisengagetheclip,thenrotatethemodule toward you.

Mounting the NGC-40-HTC/HTC3

power Supply/CAN

RTD Input Connections – North American Installation Technique

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14 5/10

1313 1414 1515 1616

Fieldterminal block

Fieldterminal block

RTDRTD

13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used

13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used

HTC RTDWiring

HTC RTDWiring Earth grounding

bar located at theHTC modulebar located

1PH1PH

HTCForallRTDterminations,theRTDfieldwiresmustbeterminatedonapanel-mountedterminalblock.TheRTDcableshieldfromthefieldterminalblocktotheHTCmoduleshouldbe terminated at the earth ground bar located near the module.

Connections are the same for the HTC3.

RTD Input Connections – European Installation Technique

99

1111To heat-tracing

To heat-tracing

contactorcontactor contactorcoilcontactorcoil

Controlpower

Controlpower

L1L1

N or L2N or L2

N or L2N or L2Coil OutCoil Out

L1 (in)L1 (in)

HTC3Three-PhaseHTC3Three-Phase L1L1

NN

L3L3

Circuit breakerCircuit breaker

L2L2

L1L1

NN

L2L2

L3L3

99

1111

To heat-tracing

To heat-tracing

ContactorContactor

Contactorcoil

Contactorcoil

Coil outCoil outControlpowerControlpowerL1 (in)L1 (in)

N or L2N or L2

Terminals9and11switchvoltagetothecontactorcoils.The internal pilot relay will switch the supply voltage (up to 277V)tothecontactorcoil.Refertothediagramattheendofthisdocumentcalled“NGC-40CANbusConnectionsforUp to 10 Modules” for detail wiring.

Note: Exposure to some chemicals may degrade the sealing propertiesoftherelayoutput,manufacturedbyNAIS,PNJQ1P-12V.Periodicallyinspecttherelayoutputfordegradationof properties and replace if any degradation is found.

Connections are the same for the HTC3.

HTC Relay Output Connections to Contactors - Single-phase HTC3 Relay Output to Contactor - Three-phase

wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.

wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14

11

NONO CC

Failsafe Mode:Contacts shown

energized withno alarm condition

Failsafe Mode:Contacts shown

energized withno alarm condition

NCNC

22 33

Alarm RelayAlarm Relay

HTCHTC

1PH1PH

6 / 10

Alarm

1313 1414 1515 1616

Fieldterminal block

Fieldterminal block

RTDRTD

13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used

13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used

HTC RTDWiring

HTC RTDWiring Earth grounding

bar located at theHTC modulebar located

1PH1PH

HTC

1313 1414 1515 1616

Fieldterminal block

Fieldterminal block

RTDRTD

13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used

13 - T.S. COM (Wht)14 - T.S. Sense (Red)15 - T.S. Source (Red)16 - Not used

HTC RTDWiring

HTC RTDWiring Earth grounding

bar located at theHTC modulebar located

1PH1PH

HTCTerminals5&6switchvoltagetotheSSR.TheinternalSSRdriverwillswitchtheinternalsupplyvoltage(12Vdc)totheSSR.

HTC Output Connections to SSR - Single-phase HTC3 Output Connections to SSR - Three-phase

wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.

wARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.

5512

Vdc12

Vdc

++ ––

~~ ~~

66

To heat-tracingTo heat-tracing

N or L2N or L2

L1L1

L1L1

Nor L2Nor L2

SSRSSR

L1L1

Circuit breaker

N or L2

N or L2

HTCSingle-PhaseHTCSingle-Phase

1PH1PH

To heat-tracingTo heat-tracing

L1L1

NN

L3L3

L2L2

L1L1

L3L3

L2L2

HTC3Three-PhaseHTC3Three-Phase

L1L1

NN

L3L3

Circuit breakerCircuit breaker

L2L2

NNL1L1

L3L3

L2L2

55

++

––

66

SSRSSR

++

––~~~~

~~~~

~~~~

SSRSSR

++

––SSRSSR

3PH3PH

Note: Exposuretosomechemicalsmaydegradethesealingpropertiesofthealarmrelay,manufacturedbyNAIS,PNJQ1P-12V.Periodicallyinspectthealarmrelayfordegradationofproperties and replace if any degradation is found.

Multi-purpose.Alarmrelayenergizedinnormalstate.

ThealarmrelayisconfiguredasFailSafe.

ThealarmrelayconnectionsprovideaformCdrycontact,ratedat277Vmax(3A).

TheNO(normallyopen)contactisopeninnon-energizedcondition.Whenenergized,itclosesduringnormalconditionsandwillopenuponanalarmcondition or power failure.

TheNC(normallyclosed)contactisclosedinnon-energizedcondition.Whenenergized,itopensduringnormalconditionsandwillcloseuponanalarmcondition or power failure.

Relaycontactrated250V/3A50/60Hz(CE)277V/3A50/60Hz(c-CSA-us)

Connections are the same for the HTC3.

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14

From user inputFrom user input

Digital InputDigital Input

77 88

++ ––

++ ––

Terminalblock

Terminalblock

Earth groundingbar located at theHTC module

Earth groundingbar located at theHTC module

From user inputFrom user input

Digital InputDigital Input

North AmericanInstallations

North AmericanInstallations

EuropeanInstallations

EuropeanInstallations

77 88

++ ––

++ ––

Terminalblock

Terminalblock

HTCHTC

1PH1PH

HTCHTC

1PH1PH

7 / 10

1. provide suitable panel enclosure

The NGC-40-HTC or NGC-40-HTC3 must be mounted in an enclosure to protect its electronic components. For indoor applications,useaminimumNEMA1enclosure(NEMA12recommended).Foroutdoorapplications,useaNEMA4orNEMA4Xenclosuredependingontherequirements.

Note: TheRaychemNGC-40-HTCorNGC-40-HTC3isde-signed for operation in ambient temperatures from –40°C to65°C(–40°Fto149°F).Iftheambienttemperatureisoutsidethisrange,aspaceheaterand/orcoolingfanwillbe required in the panel.

2. Determine locations for the NGC-40-HTC or NGC-40-HTC3 assembly in the electrical panel.

The NGC-40-HTC or NGC-40-HTC3 should be located in the rear of the panel. The NGC-40-HTC or NGC-40-HTC3 assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or ex-cessive vibration.

*NorthAmericanpanelinstallationtechniques

PS1

PTM

1

CBM

I/O1

I/O2

I/O3

I/O4

I/O5

PS2

PTM

2

HTC

1

HTC

2

HTC

3

HTC

4

HTC

5

HTC

6

HTC

7

HTC

8

HTC

9

HTC

10

C1 C2 C3 C4 C5 C6 C7 C8 C9 C10

PS3

PTM

3

HTC

11

HTC

12

HTC

13

HTC

14

HTC

15

HTC

16

HTC

17

HTC

18

HTC

19

HTC

20

C11

C12

C113 C4 C5 C16

C17

C18

C19

C20

PS4

PTM

4

HTC

21

HTC

22

HTC

23

HTC

24

HTC

25

HTC

26

HTC

27

HTC

28

HTC

29

HTC

30

C21

C22

C23

C24

C25

TB

C26

C27

C28

C29

C30

PanelPaneldoor

Alarmlight

Digital Input Connections – North American and European Installation Techniques

provide Suitable panel Enclosure and Determine Locations for NGC-40-HTC or NGC-40-HTC3 Assembly in panel*

Digital Input Multi-purpose input for connection to external dry (voltage free) contact or DC voltage.

Rating 100Ωmaxloopresistanceor5-24Vdc@1mAmaximum

Connections are the same for the HTC3.

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14 8 / 10

Power/Termination

Module

Power/Termination

Module

CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 10

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 4

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 3

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 2

ININ OUTOUT

CAN / 24 Vdc

BridgeModule

80 Modulesper Bridge

Module 1++

––20 Modulesper Power Supply

20 Modulesper Power Supply

20 Modulesper Power Supply

20 Modulesper Power Supply

TerminationBlock

TerminationBlock

100-240 Vac In100-240 Vac In

Optional redundant supplyOptional redundant supply

100-240 Vac In100-240 Vac In

++

––

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 20

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 14

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 13

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 12

ININ

CAN / 24 Vdc

HTC/HTC3orI/O

Module 11

OUTOUT

TerminationBlock

TerminationBlockCAN / 24 Vdc CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc CAN / 24 Vdc

Power/Termination

Module

Power/Termination

Module

CAN / 24 Vdc

Primary Supply*24 Vdc

Primary Supply*24 Vdc

* Power supply shall have a means for disconnect from line voltage* Power supply shall have a means for disconnect from line voltage

Redundant Supply*24 Vdc

Redundant Supply*24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 10

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 4

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 3

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 2

ININ OUTOUT

CAN / 24 Vdc

BridgeModule

80 Modulesper Bridge

Module 1

TerminationBlock

TerminationBlock

++

––

Power/Termination

Module

Power/Termination

Module

Primary Supply*24 Vdc

Primary Supply*24 Vdc

20 Modulesper Power Supply

20 Modulesper Power Supply

TerminationBlock

TerminationBlock

CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc

100-240 Vac In100-240 Vac In

Optional redundant supplyOptional redundant supply

100-240 Vac In100-240 Vac In

++

––

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

Redundant Supply*24 Vdc

Redundant Supply*24 Vdc

20 Modulesper Power Supply

20 Modulesper Power Supply

* Power supply shall have a means for dicsonnect from line voltage* Power supply shall have a means for dicsonnect from line voltage

NGC-40 CAN bus Connections for Up to 10 Modules

NGC-40 CAN bus Connections for Up to 20 Modules

INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40HTC-IM-H58087     12/14

Power/Termination

Module

Power/Termination

Module

CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc

Power/Termination

Module

Power/Termination

Module

CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc

Power/Termination

Module

Power/Termination

Module

CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc

Power/Termination

Module

Power/Termination

Module

CAN/TermCAN/Term CAN / 24 VdcCAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 10

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 4

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 3

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 2

ININ OUTOUT

CAN / 24 Vdc

BridgeModule

80 Modulesper BridgeModule 1

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 20

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 14

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 13

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 12

ININ OUTOUT

CAN / 24 Vdc

BridgeModule

80 Modulesper BridgeModule 11

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3)orI/O

Module 30

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 24

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 23

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 22

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 21

++

––20 Modulesper Power Supply

20 Modulesper Power Supply

100-240 Vac In100-240 Vac In

20 Modulesper Power Supply

20 Modulesper Power Supply

100-240 Vac In100-240 Vac In

Optional redundant supplyOptional redundant supply

++

––

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc CAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 40

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 34

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 33

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 32

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 31

TerminationBlock

TerminationBlockCAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

++

––20 Modulesper Power Supply

20 Modulesper Power Supply

TerminationBlock

TerminationBlock

100-240 Vac In100-240 Vac In

20 Modulesper Power Supply

20 Modulesper Power Supply

100-240 Vac In100-240 Vac In

Optional redundant supplyOptional redundant supply

++

––

CAN / 24 Vdc

CAN / 24 Vdc

Primary Supply*24 Vdc

Primary Supply*24 Vdc

* Power supply shall have a means for disconnect from line voltage* Power supply shall have a means for disconnect from line voltage

Redundant Supply*24 Vdc

Redundant Supply*24 Vdc

Primary Supply*24 Vdc

Primary Supply*24 Vdc

Redundant Supply*24 Vdc

Redundant Supply*24 Vdc

9/10

NGC-40 CAN bus Connections for Up to 40 Modules

10 / 10EN-RaychemNGC40HTC-IM-H58087 PCN1244-009548 12/14

The NGC-40-HTC/HTC3 contains no user serviceable parts. ContactyourPentairrepresentativeforserviceandanRMAnumber if required.

wARNING: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2 hazardous and nonhazardous locations

wARNING: Explosion Hazard - Do not replace NGC-40-pTM unless power has been switched off or the area is known to be nonhazardous

wARNING: Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is known to be nonhazardous

AvERTISSEMENT - Risque D'explosion - La substitution de composants peut rendre ce matériel inacceptable pour les emplacements de Classe I, Division 2

AvERTISSEMENT - Risque D'explosion - Couper le courant ou s'assurer que l'emplacement est désigné non dangereux avant de replacer le NGC-40-pTM

AvERTISSEMENT - Risque D'explosion - Avant de déconnecter l'equipement, couper le courant ou s'assurer que l'emplacement est désigné non dangereux

Servicing

INDUSTRIAL HEAT TRACING SOLUTIONS

WWW.PENTAIRThERmAl.COm

AllPentairtrademarksandlogosareownedbyPentairoritsglobalaffiliates.Pentairreservestherighttochangespecificationswithoutpriornotice.

©2007-2014Pentair.

NORTh AmERICA Tel: +1.800.545.6258Fax: +1.800.527.5703Tel: +1.650.216.1526Fax: [email protected]

EuROPE, mIddlE EAsT, AfRICATel: +32.16.213.511Fax: [email protected]

AsIA PACIfICTel: +86.21.2412.1688Fax: [email protected]

lATIN AmERICATel: +1.713.868.4800Fax: [email protected]


Recommended