+ All Categories
Home > Technology > Control Dampers

Control Dampers

Date post: 20-May-2015
Category:
Upload: illinois-ashrae
View: 2,793 times
Download: 16 times
Share this document with a friend
Description:
Control Dampers - March 211 Illinois Chapter of ASHRAE Meeting.
Popular Tags:
56
Air Control Considerations For Energy Conservation & BMS Integration Presenter: James Livingston, Ruskin Company
Transcript
Page 1: Control Dampers

Air Control Considerations For Energy Conservation & BMS Integration

Presenter: James Livingston,

Ruskin Company

Page 2: Control Dampers

� Control Damper Basics

� Control Damper Leakage

� Control Damper Design For Energy

Conservation

� Fire/Smoke Damper Acutators For

Energy Conservation

We Will Discuss

Page 3: Control Dampers

What is a Control Damper?

One or more movable blades

Mounts in ducts or openings

Regulates the flow of air

Page 4: Control Dampers

Control Damper Applications

� Air Handling Units (AHU)

� Mixing Boxes

� Fresh Air (FA)

� Return Air (RA)

� Backdraft Dampers (BD)

� Zone Mixing Dampers (ZMD)

Page 5: Control Dampers

Parts of a Control Damper

Frame

Blade

Linkage

Jamb Seals

Blade Seals

Page 6: Control Dampers

Galvanized

V-Groove Blades

Airfoil Blades

Aluminum

Frames

Damper Construction

Page 7: Control Dampers

V-Groove Blade Dampers

• Velocities less than 1500 FPM

• 3”- 4” Static Pressure

• Noise not a factor

Page 8: Control Dampers

Airfoil Blade Dampers

• Velocities above 2000 FPM

• Above 3”- 4” Static Pressure

• Noise is a concern

• Lowest Pressure Drop Required

Page 9: Control Dampers

How Are Fire, Fire/Smoke and Smoke Dampers Different?

� Maintains fire or

smoke walls

� Fire dampers - steel

construction

� Often have sleeves

� Usually not controlling

air

� That is changing!

Page 10: Control Dampers

Damper Leakage – What is it?

Per AMCA Publication 502, Damper

Application Manual for Heating,

Ventilating and Air Conditioning:

“The Air Leakage, or Sealing

Performance, of a closed damper is

the airflow leakage rate through the

damper for a given pressure

differential across the damper.”

Page 11: Control Dampers

Leakage

Page 12: Control Dampers

Why Are We Concerned?

� Code requirements

� Energy losses due to

escaping conditioned air through closed damper

� Maintaining pressure in system with closed

damper

Page 13: Control Dampers

Control Damper Leakage Classes

Page 14: Control Dampers

Smoke & Fire/Smoke Damper Leakage Classes

Page 15: Control Dampers

Damper Leakage Notes

� Leakage is a function of Pressure, not Airflow

� Generally expressed or plotted as:

� Cfm/ft² of damper face area at a certain pressure

and with a certain seating torque

� Metric: m³/second per m²

� Example for a 24” x 24” opposed blade

damper:

� 32 cfm/ft² @ 4” w.g. pressure with 5 inch-pounds/ft² torque applied holding damper closed

Page 16: Control Dampers

Calculating Leakage

� Most dampers have published leakage at 1”

w.g.

� Multiply the cfm leakage at 1” times the

square root of the desired pressure

� Example

� 10 cfm @ 1” w.g. = 20 cfm @ 4” w.g.

� Be sure the damper is rated for the higher pressure!

Page 17: Control Dampers

17

International codes have been adopted in International codes have been adopted in

All 50 states, D.C. & Puerto RicoAll 50 states, D.C. & Puerto Rico

One or more International Codes currently enforced statewide

www.iccsafe.org

International CodesInternational Codes

Page 18: Control Dampers

International CodesInternational CodesInternational codes mandate…

� Occupancy-based ventilation (IMC 403.3)

� VAV systems shall have controls to monitor and maintain O.A. flow based on 403 requirements, through the entire range of the system (IMC403.3.3)

� All dampers penetrating the building envelope shall be class 1 leakage rated, not to exceed 4cfm/sf @ 1”w.c. (IMC301.2, IBC1301 & IECC)

� Motorized dampers required on building envelope penetrations (IECC 502.4.4 & 503.2.4.4)

D.O.E. mandates ASHRAE 90.1 as a minimum for all

Federal buildings. (IECC 4 CFM Supersedes)

Page 19: Control Dampers

“The occupant load utilized for design of the

ventilation system shall not be less than the

number determined from the estimated maximum

occupant load rate indicated in Table 403.3”

International CodesInternational Codes

Page 20: Control Dampers

International Mechanical CodeInternational Mechanical Code

Page 21: Control Dampers

Regard

ing Ene

rgy

Conser

vation

International Mechanical CodeInternational Mechanical Code

Page 22: Control Dampers

Regard

ing Ene

rgy

Conser

vation

International Building CodeInternational Building Code

Page 23: Control Dampers

International Energy Conservation CodeInternational Energy Conservation Code

Page 24: Control Dampers

• Required in all states that have

adopted the IBC or IMC.

• Addresses OA & EA Damper

leakage

4 cfm/ft2@ 1” w.g.

• Economizers Required (503.3.1 &

503.4.1)

• Refers to 90.1 for climate zones

and as a standard for

applications not covered in the

code.

International Energy Conservation CodeInternational Energy Conservation Code

Page 25: Control Dampers

ASHRAE 90.1

6.4.3.3.3 Motorized dampers

required on OA & EA applications

6.5.1.1 Economizers required

Page 26: Control Dampers

Specifying Low Leakage Dampers

� AMCA 511 Certification

� Independent testing

� Verified catalogs

� Periodic Check Tests

Page 27: Control Dampers

27

Certified Ratings Program…

How do you know the product you specified is licensed by AMCA International?

There are basically four ways to determine if a product is participating in AMCA International’s Certified Ratings Program. They are:

� WWW.AMCA.org

� Manufacture

� Model #

� Manufacture’s Catalog (most are online)

� Certified Ratings Seal on the product (could be too late)

� Contact AMCA International

� Phone 847-394-0150

� Fax 847-253-0088

� Email [email protected]

AMCA International

Page 28: Control Dampers

AMCA 511 Damper Air Leakage

� At least two sizes tested

� 12” x 48”

� Max width x 36”

� Up to two more sizes can be tested, 36” max tall

� AMCA configs 5.4, 5.5 or 5.6

� Round dampers

� Min & Max sizes tested

Page 29: Control Dampers

� AMCA 500 Test Standard

Figure 5.5

Leakage &

Pressure

AMCA 511 Damper Air Leakage

Page 30: Control Dampers

Damper Leakage Chart

Page 31: Control Dampers

Damper Leakage Performance

Page 32: Control Dampers

Air Leakage Certification

Not the same!

Be sure it’s rated for Air Leakage, not just Air Performance!

Page 33: Control Dampers

Energy Saving Damper Construction

Blades

Jamb Seals

Blade Seals

Page 34: Control Dampers

Galvanized

V-Groove Blades

Airfoil Blades

Aluminum

Blades

Generally not Class 1

Class 1 and 1A available

Page 35: Control Dampers

Airfoil Blades

� Advantages

� Best Torsion Performance

� No Twist

� Best Closure Seal For

All Blade Lengths

� Class 1 & 1A available

Page 36: Control Dampers

� Blade Shape Matters

� Airfoil

� 60” Span @ 3.5 w.g.

� 3000 FPM

� 3-VEE

� 48’ Span @ 2.5 w.g.

� 1500 FPM

Airfoil vs. “V” Groove Maximums

Page 37: Control Dampers

24” x 24”

Airfoil

.07 w.g. @ 2000 FPM

3-VEE

.19 w.g. @ 2000 FPM

Almost 3 times the Pressure Drop!

Airfoil vs. “V” Groove Pressure Drop

Page 38: Control Dampers

Jamb Seals

� Between ends of

blades and jamb

frames

� Metallic or synthetic

material

� Compresses when

blades close

Page 39: Control Dampers

Blade Seals

� Blade Seals

� Mechanically Locked

� Inflatable

� Wiper Type

No Adhesive or Clip On Style

Maintenance

Page 40: Control Dampers

Insulated Dampers� Reduces thermal energy loss

� Different methods

� Double airfoil damper -

expensive

� Single airfoil foam injected

blades – less expensive

� Thermal break frames available

� Class 1 leakage

� Applications down to -100°F

Page 41: Control Dampers

41

Louver & Damper in One!

Combination Louvers� Drainable fixed louver & airfoil

control damper in same frame

� Class 1 leakage

� Meets IECC building envelope

leakage requirement!

� Available w/ most electric

actuators

� Less product cost than separate

louver, damper & sleeve

� Less installation cost

Page 42: Control Dampers

Damper Electric Actuators

Page 43: Control Dampers

Electric Actuator Types

� Actuators are available in three types:

1) Two Position Spring Return

2) Modulating

3) Power Open-Power Closed

� Can be controlled by BMS

� Most Damper applications call for

Two Position Spring Return or Modulating

Page 44: Control Dampers

Two Position

� Limit to limit operation – does not float

� Open/close applications

� Spring reverses direction when power fails

� Typically 120V or 24V voltage

� Power draw for common 175 in/lb model� 120V – 60 VA driving, 13 VA holding

� 24V – 40 VA driving, 8 VA holding

Page 45: Control Dampers

Modulating� Actuator moves too any point within

its rotation limits to control airflow

� Requires a control signal� 2-10 Vdc or 4-20 mA

� Signal can come from BMS based on:� Temperature

� Pressure

� Air pollutants and/or occupancy

� Power draw for common 175 in/lb model� 24V – 16 VA driving, 5 VA holding

Page 46: Control Dampers

Actuator Installation Options

Page 47: Control Dampers

Modulating Considerations

� Airflow not linear to blade position

Page 48: Control Dampers

Modulating Considerations

Linear flow damper characteristics

From AMCA Pub 502 Damper Application Manual

Page 49: Control Dampers

Modulating Fire/Smoke and Smoke Damper Actuators

� BMS signal controls

blade position in normal

condition

� Damper closes fully

during fire

� Damper opens fully to

relieve smoke

Page 50: Control Dampers

Modulating Smoke & F/S Dampers

Page 51: Control Dampers

� Eliminates balancing

dampers

� Less pressure drop

� Less cost

� Use smoke dampers for

return air on Air Handlers

� Maintain floor pressure in

multi floor systems

Modulating Smoke & F/S Dampers

Page 52: Control Dampers

Modulating Smoke & F/S Dampers

� Advantage over

manual balancing

dampers

� Modulating actuator goes full-open for

smoke purge

� Smoke system does not have to fight semi-

closed manual dampers

Page 53: Control Dampers

Built in potentiometer to Built in potentiometer to

20% to 100% balance 20% to 100% balance

positionposition

Allows the damper to be SET at Allows the damper to be SET at Allows the damper to be SET at Allows the damper to be SET at Allows the damper to be SET at Allows the damper to be SET at Allows the damper to be SET at Allows the damper to be SET at

any position for BALANCING any position for BALANCING any position for BALANCING any position for BALANCING any position for BALANCING any position for BALANCING any position for BALANCING any position for BALANCING

AIRFLOW under normal AIRFLOW under normal AIRFLOW under normal AIRFLOW under normal AIRFLOW under normal AIRFLOW under normal AIRFLOW under normal AIRFLOW under normal

operations, open or closed for operations, open or closed for operations, open or closed for operations, open or closed for operations, open or closed for operations, open or closed for operations, open or closed for operations, open or closed for

SMOKE CONTROL and closed as SMOKE CONTROL and closed as SMOKE CONTROL and closed as SMOKE CONTROL and closed as SMOKE CONTROL and closed as SMOKE CONTROL and closed as SMOKE CONTROL and closed as SMOKE CONTROL and closed as

required in the fire arearequired in the fire arearequired in the fire arearequired in the fire arearequired in the fire arearequired in the fire arearequired in the fire arearequired in the fire area

No Control No Control No Control No Control

Signal Signal Signal Signal

RequiredRequiredRequiredRequired

3-Position Smoke & F/S Dampers

Page 54: Control Dampers

Summary

� Current building codes require low leakage

dampers

� Damper construction greatly affects leakage

characteristics

� Modulating actuators can be controlled by

BMS to adjust airflow for temperature and

IAQ requirements

� Smoke and Fire/Smoke dampers are

available w/ modulating & 3-position

actuators

Page 55: Control Dampers

Questions?

Page 56: Control Dampers

Thank You!


Recommended