Nalan Karunanayake 1 EC 350 - Control Systems Laboratory 02 DC motor Control and PID Control Model a DC motor using the physical model approach Use SIMULINK simscape to model the electromechanical system as follows, Change PSS-converter block parameter to A (Amperes). Change Model Configuration Parameter as, Solver-> ode15s RUN the simulation and observe the current produce and comment on it Model the mechanical portion of the system as follows,
Transcript
  • Nalan Karunanayake 1

    EC 350 - Control Systems

    Laboratory 02 DC motor Control and PID Control

    Model a DC motor using the physical model approach

    Use SIMULINK simscape to model the electromechanical system as follows,

    Change PSS-converter block parameter to A (Amperes).

    Change Model Configuration Parameter as, Solver-> ode15s

    RUN the simulation and observe the current produce and comment on it

    Model the mechanical portion of the system as follows,

  • Nalan Karunanayake 2

    RE-RUN the model and observe the output current and comment on it.

    Modified the simulation file as follows,

    Change PSS-simulink converter 1 parameter to RPM.

    RE-RUN the Simulink model again and observe the scope 1 and comment on it.

  • Nalan Karunanayake 3

    Produce translational motion as follows,

    What does Wheel and Axle block do?

    RE-RUN the model again and observe the scope 1 and comment on it.

    Disconnect PSS Simulink converter 1 from port W of the Ideal Rotational Motion Sensor and

    reconnect it with port A (change the PSS Simulink converter parameter to deg)

    RE-RUN the model and observe the scope 1 and comment on it.

    Change the spring rate of the Translation spring to 100 and 10, RE-RUN the model and observe

    the output of the scope 1 and comment on it.

    PID Control System

    Introduction

    Recall the open-loop transfer function of the DC Motor.

    () = ()

    ()=

    (( + )( + ) + 2)

    The structure of the control system has the form shown in the figure below.

  • Nalan Karunanayake 4

    Transfer function for a PID controller has the following form.

    () = +

    + =

    2 + +

    A proportional controller ( ) will have the effect of reducing the rise time and will reduce but

    never eliminate the steady-state error. An integral control ( ) will have the effect of eliminating

    the steady-state error for a constant or step input, but it may make the transient response slower.

    A derivative control ( ) will have the effect of increasing the stability of the system, reducing the

    overshoot, and improving the transient response.

    The effects of each of controller parameters, , , and on a closed-loop system are

    summarized as in the table below.

    Parameter Rise Time Overshoot Settling Time Steady State Error

    Kp Decrease Increase Small Change Decrease

    Ki Decrease Increase Increase Eliminate

    Kd Small Change Decrease Decrease No Change

    The structure of the control system has the form shown in the figure below.

  • Nalan Karunanayake 5

    Transfer function for a PID controller has the following form.

    () = +

    + =

    2 + +

    Where = Proportional gain, = Integral gain and = Derivative gain

    Use below coding to directly define a PID controller in MATLAB using the transfer function:

    Kp = 1;

    Ki = 1;

    Kd = 1;

    s = tf('s');

    C = Kp + Ki/s + Kd*s

    Alternatively MATLAB's pid controller object can be used to generate an equivalent continuous time

    controller as follows:

    C = pid(Kp, Ki, Kd);

    1. Proportional control

    The closed-loop transfer function of a system with a proportional controller is shown below

    Use Matlab to answer below questions

  • Nalan Karunanayake 6

    Questions

    1.1 Draw a rough sketch of the response of the system to a step reference with different

    values of Kp

    1.2 Comment on the effect of increasing proportional gain on overshoot and settle time?

    2. PD control

    The closed-loop transfer function of the given system with a PD controller is shown below

    Initially set the value of Kp = 300 and test derivative gain Kd value set to 10. Change your m-file to obtain

    the step response of the above system with PD control.

    Questions

    2.1 Draw a rough sketch of the response of the system to a step reference with different

    values of Kd.

    2.2 Briefly explain the use of Proportional-Derivative Controller in a particular system?

    Comment on the effect of increasing derivative gain (Kd) on overshoot and settle time?

    3. PI control

    The closed-loop transfer function of the given system with a PI controller is shown below

    Initially set the value of Kp = 30 and test integral gain Ki value set to 70. Change your m-file to obtain the

    step response of the above system with PI control.

    Questions

    3.1 Draw a rough sketch of the response of the system to a step reference with different

    values of Ki.

    3.2 Explain the effect of increasing Ki in the particular system?

  • Nalan Karunanayake 7

    4. PID control

    The closed-loop transfer function of the given system with a PID controller is shown below

    Now modify the above m file as = 350, = 300, and = 50 to obtain the step response of the above

    system with PID control.

    Questions

    4.1 Draw a rough sketch of the response of the system to a step reference with different

    values of Kp, Ki and Kd?

    Use the Matlab command stepinfo to obtain the precise characteristics of the step response.

    4.2 Comment on the effect of Kp, Ki and Kd parameters on the system?

    PID control design with Control System Toolbox

  • Nalan Karunanayake 8

    >> pidtool(sys)

    Change the controller type P, PI, PID and obtain the Step Plot and comment.

    From the Show Parameters, obtain the PID gains and characteristics of the system.

    Change the Response Time and Phase Margin and see what happened to the Step Plot.

    Tune PID controller for a DC Motor in MATLAB SIMULINK

    Consider an example of designing a PID controller for a dc motor. The model of a closed loop system

    uses the new PID Controller block. This block generates a voltage signal driving the dc motor to track

    desired shaft rotation speed. In addition to voltage, the dc motor subsystem takes torque disturbance as

    an input, allowing us to simulate how well the controller rejects disturbances.

    Open the CSlab2.slx

  • Nalan Karunanayake 9

    The PID controller is a discrete-time controller running at 0.02 seconds (the red color shows the sampling

    time in the model). Lets now look at the dialog of the PID Controller block. In the upper half of the dialog

    we specified basic configuration of the PID controller: type (PID, PI, PD, P, or I), time-domain, integration

    methods, and sample time. In the lower part, we specified PID controller form and gains (shown at default

    values).

    Block documentation provides detailed information about the block and all its parameters.

  • Nalan Karunanayake 10

    Check the scope of the PID block

    PID Tuning

    Our first task is to tune the PID controller. Pressing the Tune button in the PID Controller block

    dialog, we launch PID Tuner, which linearizes the model at the default operating point and automatically

    determines PID controller gains to achieve reasonable performance and robustness based on linearized

    plant model.

  • Nalan Karunanayake 11

    Update the PID Tuner

    Check the PID controller values again

  • Nalan Karunanayake 12

    Then again RE-RUN the Simulink model and observe the PID scope and comment on it.

    How to make the system faster?

    What are the drawbacks of that method?