    Process Instrumentation,

    part 2:Control Loops and the ControlValve

    CM4120Unit Operations Lab

    January 2010

    1

  • 7/30/2019 Control Valves and the Control Loop

    2/29

    Outline What is a Control Loop?

    A look at Regulatory Control Valves PID Controllers and terminology

    Instrument Connections to a Distributed

    Control System

    2

  • 7/30/2019 Control Valves and the Control Loop

    3/29

    Typical Control Loop

    3

    All elements of a loop have same loop number

  • 7/30/2019 Control Valves and the Control Loop

    4/29

    Elements of Control Loop

    Input side:

    TE Element to measuretempRTD vs. T/C

    TT Transmitter sends signal

    Dashed line - signal

    transmission line

    4

  • 7/30/2019 Control Valves and the Control Loop

    5/29

    Elements of Control Loop

    Controller: TIC Temperature Indicating Controller Shared Display, Analog signal

    5

  • 7/30/2019 Control Valves and the Control Loop

    6/29

    Elements of Control LoopOutput side:

    TV Valve to regulatesteam flow

    TY Transducer converts

    electric signal topneumatic

    Solid line w/ dashes ispneumatic signal line

    F.C. is Fail position

    6

  • 7/30/2019 Control Valves and the Control Loop

    7/29

    Regulatory Control Valve

    7

    Trim setdesirable to have

    flow linearly

    proportional to

    valve position forgood control

    Actuator

    (F.O. or F.C.?)

  • 7/30/2019 Control Valves and the Control Loop

    8/29

    Valve Trim I nherent Characteristics

    8

    Quick Openingsafety by-pass type

    Large flow response when valve starts opening ismore important than linear response

    Equal Percentage~ 80% of all control valvesprovides linear response to valve position

    Linearused when majority of system pressure drop isdue to valve position

  • 7/30/2019 Control Valves and the Control Loop

    9/29

    Valve Trim Sizing: Flow

    Coefficient vs. Valve Position

    0

    0.5

    1

    0 20 40 60 80 100Stem Position (% Open)

    f(x)

    =%

    QOLinear

    9

    By definition:for Cv = 1,

    1 gpm flow w/

    1 psi pressure dropacross valve

  • 7/30/2019 Control Valves and the Control Loop

    10/29

    Valve Selection Example

    C.W.

    FT

    10

    Control flow of reflux to distillation column

    Determine pressure drop:

    @ design flow

    @ expected min/max flow

  • 7/30/2019 Control Valves and the Control Loop

    11/29

    System Response based on

    Pump/ Piping System

    11

    Design Range of flow is 100 to 200 gpm:

    Increase in valveopening lessP

    across valve, but w/

    increased line lossesand decreased total

    available head from

    pump 0

    5

    10

    15

    20

    25

    0 50 100 150 200Flow Rate (GPM)

    PressureD

    rop(psi)

    Line Losses

    Pump Head

    Valve P

  • 7/30/2019 Control Valves and the Control Loop

    12/29

    Installed Characteristic

    12

    Size the valve trim, then select valve characteristic

    w/ the most linear response:

    use Equal Percent Characteristic valve to achieve

    a linearInstalled Characteristic

    0

    50

    100

    150

    200

    0 20 40 60 80 100Stem Position (% Open)

    InstalledFlowRate

    (GPM

    )

    Linear Valve

    =% Valve

  • 7/30/2019 Control Valves and the Control Loop

    13/29

    PID Controllers

    13

  • 7/30/2019 Control Valves and the Control Loop

    14/29

    Review of Controller Terminology

    Process Variable ( PV) = Measured variable of

    interest, in EU

    Setpoint ( SP) = Desired value of the PV, in EU

    Output (OP) = Controller output, 0-100%

    Error = Difference between Setpoint and PV

    14

  • 7/30/2019 Control Valves and the Control Loop

    15/29

    Relating this to our Control Loop:

    15

    Process Variable

    Output

    Setpoint

  • 7/30/2019 Control Valves and the Control Loop

    16/29

    Controller TerminologyPI D control Dynamic equation that is used to match the

    controllers response to a measureddisturbance.

    Goal is to minimize disturbance and return to

    setpoint Equation is tuned to match process

    response using up to 3 tuning constants

    16

  • 7/30/2019 Control Valves and the Control Loop

    17/29

    Controller TerminologyTuning Constants:Proportional term Adjusts outputproportional to the error, Gain

    I ntegral term Added to output based on

    error existing over time, Reset

    Derivative term Additional adjustment to

    output based on rate of change of error, Rate

    17

  • 7/30/2019 Control Valves and the Control Loop

    18/29

    Evolution of Controllers1930s Pneumatic Controllers air pressure w/ flappers, bellows, and valves

    adjust valve position based on measured

    process variable for P, PI, later PID control1950s Electronic Controllers transistors, resistors, and capacitors for P, PI,

    PID control capable of remote installation1960s Mainframe Computer Control Refineries were typical users

    Alarming capability and supervisory control Single point of failure, no user-friendly

    graphical interface

    18

  • 7/30/2019 Control Valves and the Control Loop

    19/29

    Evolution of Controllers

    Late 1970s Distributed Control Systems(DCS)

    Networked computers distributed thru plant Pre-configured controllers Data archival capabilities Included an operator console Hardware is proprietaryLate 1990s DSCs built on commodity

    hardware platforms Better scalability Affordable Interactive graphical interface

    19

  • 7/30/2019 Control Valves and the Control Loop

    20/29

    Emersons DeltaV System current state of the Technology

    20

    PID control

    Discrete logic control

    Signal conversions

    AlarmingFuzzy control, etc.

    are continuouslyexecutedby the MD controller

    http://www.easydeltav.com/index.asp
  • 7/30/2019 Control Valves and the Control Loop

    21/29

    Wiring Systems ConnectTransmitters

    to DCS at the Instrument End:

    21

    Wiring to fieldjunction cabinet

    RTD or T/C head

    Temperature

    transmitters

    Wiring from

    transmitter to temp

    measuring element

    Level transmitter

  • 7/30/2019 Control Valves and the Control Loop

    22/29

    Wiring Systems ConnectTransmitters

    to DCS at a Marshalling Cabinet:

    22

    Single pairs

    from field

    devices

    8 pr. Cables to

    controller

    cabinet

    8-pr. cables run from Field Junction Box (Marshalling

    Cabinet) to Distributed Control System

  • 7/30/2019 Control Valves and the Control Loop

    23/29

    Wiring Systems ConnectTransmitters

    to DCS in the Controller Cabinet:

    23

    DeltaV MD controller

    8 pr. cables from

    field junction cabinet

    Power-limiting

    Zener barriers

    I/O cards

    2nd I/O chassis w/4-20

    mA Output cards

    http://www.easydeltav.com/index.asp
  • 7/30/2019 Control Valves and the Control Loop

    24/29

    Wiring Systems Connect DCS to

    Transducers at Marshalling Cabinet:

    24

    Wire prs. to transducers

    Current to pneumatic

    transducers

    Air lines to

    control valves

    8-pr. cable from

    controller cabinet

  • 7/30/2019 Control Valves and the Control Loop

    25/29

    Regulatory Control Valve

    25

    Air line from I/P transducer

    Actuator w/ positioner

    Control valve

    Block valves

    Bypass valve

  • 7/30/2019 Control Valves and the Control Loop

    26/29

    Output Signals from Control System

    to Control Solenoids

    26

    8-pr. cable from

    controller cabinetSolenoids for 2-position

    air-actuated ball valves

    Air lines to

    ball valves

    Wire prs. to solenoids

  • 7/30/2019 Control Valves and the Control Loop

    27/29

    Installed Field Devices:

    Ball Valve w/ Actuator

    27

    Air line from

    solenoid

    Actuator

    Ball valve body

    Process line

  • 7/30/2019 Control Valves and the Control Loop

    28/29

    DeltaV &Foundation Fieldbus

    28

    (4) mass flows, (4) densities,

    and (4) RTD temps

    (3) 8-multiplexed RTD temps(2) temp-only transmitters

    (1) wire

    http://plantweb.emersonprocess.com/Home/index.asphttp://www.easydeltav.com/index.asp
  • 7/30/2019 Control Valves and the Control Loop

    29/29

    ReferencesMiller, Richard W., Flow Measurement

    Engineering Handbook, 3rd Ed., McGraw-Hill,

    New York, 1996.Riggs, James B., Chemical Process Control, 2nd

    Ed., Ferret Publishing, Lubbock, TX, 2001.Taylor Instrument Division, The Measurement of

    Process Variables, no date.www.emersonprocess.com/rosemount/,

    Rosemount, Inc., Oct. 2006.

    www.emersonprocess.com/micromotion/, MicroMotion, Inc., Oct. 2006.

    www.ametekusg.com/, Ametek, Inc. Oct. 2006.

    29