+ All Categories
Home > Documents > Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit...

Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit...

Date post: 25-May-2020
Category:
Upload: others
View: 12 times
Download: 0 times
Share this document with a friend
12
© 2010 Mitsubishi Electric & Electronics USA, Inc. Suwanee, GA 30024 All Rights Reserved. The three diamond logo is a registered trademark of Mitsubishi Electric Corporation www.mitsubishipro.com Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: Wireless Receiver and Cable (MIFH1) Remote Controller (MRCH1) Portable Central Controller (MCCH1) Outdoor Air Sensor (MOS1) DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical shock or equipment damage. Must be installed by a trained, experienced technician. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition. Installation at a glance This document covers linking and installation procedures for the Mitsubishi Split-Zoning Ductless and Ducted Systems' RedLINK™ control devices and accessories. Before you begin, you must attach the cable to the CN105 connector on the indoor unit control board, then follow the steps in this document. Remote controllers are linked to specific indoor units. Each indoor unit must have a dedicated remote controller and wireless receiver. Wireless receiver Wireless outdoor air sensor Portable central controller M32309 Remote controller
Transcript
Page 1: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

© 2010 Mitsubishi Electric & Electronics USA, Inc.Suwanee, GA 30024 All Rights Reserved.

The three diamond logo is a registered trademarkof Mitsubishi Electric Corporation

www.mitsubishipro.com

Controller Kit Installation ManualMIFH1, MRCH1, MCCH1, MOS1

69-2426-01

Installation guide for:

• WirelessReceiverandCable(MIFH1)

• RemoteController(MRCH1)

• PortableCentralController(MCCH1)

• OutdoorAirSensor(MOS1)

DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical shock or equipment damage.

Must be installed by a trained, experienced technician. Read these instructionscarefully.Failuretofollowtheseinstructionscandamagetheproductorcause a hazardous condition.

Installation at a glance

This document covers linking and installation procedures for the Mitsubishi Split-Zoning Ductless and Ducted Systems' RedLINK™ control devices and accessories.

Before you begin, you must attach the cable to the CN105 connector on the indoor unit control board, then follow the steps in this document.

Remote controllers are linked to specific indoor units. Each indoor unit must have a dedicated remote controller and wireless receiver.

Wireless receiver

Wireless outdoor

air sensor

Portable central

controller

M32309

Remote controller

Page 2: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

Wireless System Installation Guide

69-2426—01 2

M28474

1 Install batteries in wireless devices

Installbatteriesinalldevices.Makesurebatteriesareinsertedproperly(seepolaritymarksonthedevices).

2 Install cable and receiver

M28472A

Remote Controller

Portable Central Controller (optional): Install 3 fresh AA batteries

Outdoor air sensor (optional): Install 2 fresh AA lithium batteries

Install 2 fresh AA batteries

Install quick reference card

1 Before mounting indoor unit, connect cable to the 5-pin CN105 connector on the control board in the indoor unit.

2 Mount indoor unit. Route cable to preferred location of the wireless receiver.

3 Route cable through hole in base of wireless receiver and attach to 5 pin connector on receiver board.

4 Pushtheexcesscablebackthroughtheindoorunit or behind the wireless receiver. Do not cut or modify the cable. Use zip tie connections on back of receiver if needed.

5 Mountwirelessreceivernexttotheindoorunit(seebelow)orinaremotelocation.

Mount in the orientations shown. Do not block vents.

MCR31400

X

X

OR OR

Page 3: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

3 69-2426—01

3 Link all devices to wireless network

1 Remove cover from wireless receiver.

2 VerifyPOWERlightissolidgreen.

3 PressandreleasetheCONNECT button.

4 IfCONNECTlightdoesnotflash,anotherreceiver or RedLINK wireless adapter may be in wirelesssetupmode.Exitwirelesssetupattheother device.

M28925

Wireless Setup

Next

M32308

Connect

Back

Wireless Setup

M32307Done

ConnectedWireless Setup

Link remote controller to wireless networkZone name

Presss or t to change the name or location of this zone, then press NEXT.

Example:67=MeetingRoom

See complete zone list on page 8.

PressCONNECT to establish a link to the wireless network.

If E0 or E1 appears, see error codes on page 10.

After a brief pause, the confirmation screen at left should be displayed to verify that the wireless connection has been established.

PressDONE to display the home screen.

POWER LED

Solid Green:Poweredandcommunicationis established.

Slow Flashing Green (1 flash/second): Receiver is powered. Waitapproximately30secondsforcommunication to be established between the wireless receiver and the indoor unit. Check cable connection if flashing does not stop after 30 seconds.

Fast Flashing Green (5 flashes/second): Error in communication between wireless receiver and the indoor unit. Check cable connection.

CONNECT LED

Flashing Green: In wireless setup mode.

Solid Green: RedLINK communication is established.

Yellow:Pleasewait.

Red: RedLINK device is not communicating.

Flashingstatuslighttimesoutafter15minutesofinactivity.PressCONNECT again if necessary.

Page 4: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

Wireless System Installation Guide

69-2426—01 4

Link Portable Central Controller to RedLINK™ network (optional)

Link outdoor sensor to RedLINK™ network (optional)

CONNECT

WIRELESS SETUP

M28481

M28483

NOYES

CONNECT MORE?

M28482

1 MakesuretheCONNECTlightonthewireless receiver is flashing.

2 PressCONNECTatthePortableCentralController. There will be a short delay as the PortableCentralControllerseeksasignalfrom the wireless network.

3 Whenthescreendisplays"Connected,"press DONE.

4 PressNOatthenextscreentosaveandexit.(OrpressYES and repeat steps 1-4 to link anotherreceiver.)

1 MakesuretheCONNECTlightonthewireless receiver is flashing.

2 PressandreleasetheCONNECT button on the back of the sensor.

3 Check remote controller to verify that the outdoor sensor is working. After about 15 seconds, the remote controller should display outdoor temperature and humidity.

Presstolinkanother receiver

Presstosaveandexit

If E1 appears, see error codes on page 10.

The linking procedure may time out if there is no keypress within 15 minutes. To begin again, press and holdtheblankspace(orarrow,ifpresent)inthelowerrightcornerofthescreenuntilthedisplaychanges(about3seconds).

Pressandrelease

Page 5: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

5 69-2426—01

Exit wireless setup

4 Customize remote controller (installer setup)

PressandreleasetheCONNECTbuttonatthewirelessreceivertoexitwirelesssetup(lightshouldstopflashingandremainsolid).Replacecoveronwirelessreceiver.

Followthestepsbelowtobegininstallersetup.Ateachfunctionscreen,presss or t to change the setting as desired, then press NEXTtoadvancetothenextfunctionscreen.

Seetablesonpages6-8foradescriptionofoptionsforeachfunction.

Presss or t to change setting(seetablesonpages6-8).

PressNEXTtodisplaynextfunction screen.

Note:Thewirelessreceiverwillautomaticallyexitwirelesssetupafter15minutesof inactivity.

Note:Ifinstallingmorethanonereceiver,youmustexitwirelesssetupbeforeinstalling remote controller and additional receiver.

To begin, press and hold the FAN and s buttonsuntilthedisplaychanges."WAIT"will be displayed for up to 40 seconds.

Function

PressDONEtosave&exit.

Setting

M28927BackDone

Next

M28488A

M289871

Fan

Page 6: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

Wireless System Installation Guide

69-2426—01 6

Installer setup tables

Setup function Settings & options (factory default in bold)101 Unit automatically

restarts after power outage

1 OFF2 ON3 Not Supported

103 Ventilation Air 1 Not Supported2 IDUdoesnotintakeoutdoorairthroughLOSSNAY3 IDUdoesintakeoutdoorairthroughLOSSNAY

104 Power Voltage 1 230V2 208V3 Not Supported

105 Auto energy-savings operation

1 ON2 OFF3 Not Supported

107 Change Filter Duration 1 100Hours2 2500Hours3 OFF

108 Auto Fan (speed setting) 1 Quiet2 Standard3 HighCeiling

109 No. of Air Outlets (PLA only)

1 4 directions2 3 directions3 2 directions

110 High Performance Filter Installed

1 NO2 YES3 Not Supported

111 Airflow Direction Settings

1 NoVanes(orVane#3forPLA)2 Vane#1Setting(typicallykeptatthedefaultsetting)3 Vane#2Setting(typicallykeptatthedefaultsetting)

115 Indoor Unit Coil Frost Prevention Temperature

1 36°F(2°C)2 37°F(3°C)3 Not Supported

117 Defrost Control 1 Standard2 HighHumidity3 Not Supported

123 Airflow Oscillate Mode 1 Not Available2 Available3 Not Supported

124 Heating Mode Temperature Offset

1 ON2 OFF3 Not Supported

125 Thermal Off Fan Operation (Heat Mode)

1 ExtraLow2 Stop3 SelectableFanSpeed

127 Thermal Off Fan Operation (Cool Mode)

1 SelectableFanSpeed2 Stop3 Not Supported

128 Display System Error 1 ON2 OFF3 Not Supported

DefaultsettingsforSetupfunctions101-128areautomaticallydeterminedbytheHVACequipment.Itmaytakeupto40secondstoentersetup,and30secondstoexitsetup.

Page 7: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

7 69-2426—01

Installer setup tables

Setup function Settings & options (factory default in bold)134 Central Controller

(AG-150 or similar) Present

0 Not Installed 1 Installed

136 Residential/Commercial 1 Commercial0 Residential

138 Permanent Hold Lock (Non-programmable)

0 OFF (Programmable)1 ON(Non-programmable)

139 Fahrenheit/Celsius Display

0 Fahrenheit1 Celsius

140 Commercial Override Duration

3 3 Hours0 OFF1–12 1–12Hours

142 System Type 0 Heat & Cool (Heat Pump)1 CoolOnly

144 System Changeover 1 System Changeover (Auto, Heat, Off, Cool)0 ManualChangeover(Heat,Off,Cool)2 SystemChangeoverOnly(AutoOnly)3 System Changeover Single Setpoint - only with AG-150 or

similar(Auto,Heat,Off,Cool)145 System Changeover

Deadband Value3 3 °F (2 °C)2–8 2–8°F(1.5–4.5°C)

146 Drying Mode 0 OFF1 ON

148 Schedule Format 0 5-21 5-1-1

150 Optimal Start 1 ON0 OFF

152 Scheduled Off 0 Not Shown * See page 9 for feature information1 Shown

154 Power Off Timer ("Sleep Timer")

0 Not Shown1 Resumeoperationatnextscheduledperiod2 PermanentlyOffuntiluserchangesSystemmode

160 Full Lockout 0 No1 Yes

162 Lockout On/Off 0 No1 Yes

164 Lockout System Mode (Heat, Cool, Auto, Drying)

0 No1 Yes

165 Lockout Fan Mode 0 No1 Yes

166 Lockout Setpoint 0 No1 Yes

168 Lockout Set Clock/Day/Schedule

0 No1 Yes

170 Max Heat Setpoint 90 90 °F (32 °C) * Subject to40–89 40to89°F(4.5to31.5°C) HVAC Equipment

172 Min Cool Setpoint 50 50 °F (10 °C) * Subject to51–99 51to99°F(10.5to37°C) HVAC Equipment

173 Sensing Location 1 Sense at Remote Controller0 Sense at Indoor Unit

174 Indoor Temperature Display Offset

0 0 °F (0 °C)-3to3°F(-1.5to1.5°C)

Page 8: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

Wireless System Installation Guide

69-2426—01 8

Installer setup tables

Setup function Settings & options (factory default in bold)176 Outdoor Temperature

Display Offset0 0 °F (0 °C)

-5to5°F(-2.5to2.5°C)178 Outdoor Humidity

Display Offset3 0%0 -15%1 -10%2 -5%4 5%5 10%6 15%

192 Zone Name 52 THERMOSTAT 34 MASTER BED1 BASEMENT 35 MEDIAROOM2 BATHROOM 36 MUSICROOM3 BATHROOM1 37 NURSERY4 BATHROOM2 38 OFFICE5 BATHROOM3 39 OFFICE16 BEDROOM 40 OFFICE27 BEDROOM1 41 PANTRY8 BEDROOM2 42 PLAYROOM9 BEDROOM3 43 POOLROOM10 BEDROOM4 44 PORCH11 BOATHOUSE 45 RECROOM12 BONUSROOM 46 SEWINGROOM13 COMPUTERROOM 47 SPA14 DEN 48 STORAGEROOM15 DININGROOM 49 STUDIO16 EXERCISEROOM 50 SUNROOM17 FAMILYROOM 51 THEATER18 FIREPLACE 52 THERMOSTAT19 FOYER 53 UPPERLEVEL20 GAMEROOM 54 UTILITYROOM21 GARAGE 55 WALKINCLOSET22 GREATROOM 56 WINECELLAR23 GUESTROOM 57 WORKSHOP24 GYM Commercial Names25 KID’SROOM 64 CONFERENCERM26 KITCHEN 65 DRESSINGROOM27 KITCHEN1 66 MACHINEROOM28 KITCHEN2 67 MEETINGROOM29 LAUNDRYROOM 68 OPENAREA130 LIBRARY 69 OPENAREA231 LIVINGROOM 70 SERVER 132 LOWERLEVEL 71 SERVER 233 MASTERBATH 72 STOCKROOM

194 Wireless Setup 1 Remote controller is connected to wireless system0 Disconnect Remote controller from wireless system

198 Reset Schedule to Factory Defaults

0 No1 Yes

199 Reset Installer Setup to Factory Defaults

0 No1 Yes

Page 9: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

9 69-2426—01

Special functions

Installer test

Followtheprocedurebelowtotestforproperoperation.

M28488A

To begin, press and hold the s and t buttons untilthedisplaychanges(about3seconds).

Presss or t to check system status

PressNEXT to advancetonexttest

PressDONE to terminate system test

M32306

Next

BackDone

System test number System status

System test System status

02 Wireless test 0 Off1 Testradiosignal(afterabriefpause,screendisplays5-10toshow

signalstrength;5orhigherrecommended)

50 Cool/Heat test 0 Off1 Cool2 Heat

70 Configuration Data 1 (remotecontroller)

71 Softwarerevisionnumber(majorrevisions)72 Softwarerevisionnumber(minorrevisions)73 Configurationidentificationcode(major)74 Configurationidentificationcode(minor)75 Productionconfigurationdatecode(week)76 Productionconfigurationdatecode(year)

80 Configuration Data 2 (remotecontroller)

81 Softwarerevisionnumber(majorrevisions)82 Softwarerevisionnumber(minorrevisions)83 Softwarerevisionnumber(buildrevisions)

90 Configuration Data 1 (wirelessreceiver)

91 Softwarerevisionnumber(majorrevisions)92 Softwarerevisionnumber(minorrevisions)93 Softwarerevisionnumber(buildrevisions)

95 Configuration Data 2 (wirelessreceiver)

95 Softwarerevisionnumber(majorrevisions)96 Softwarerevisionnumber(minorrevisions)97 Softwarerevisionnumber(buildrevisions)

Commercial Override (SetupFunction140):Allowsanemployeeduringanunoccupiedperiodto temporarily activate an occupied temperature. Each press of HOLDextendstheoccupiedtemperatureout1hour(orasinstalled).

Optimal Start (SetupFunction150):Allowstheremotecontrollerto“learn”howlongtheequipment will take to reach programmed temperature settings, so the temperature is reached at the scheduled time.

Scheduled Off (SetupFunction152):Allowstheusertoscheduleaperiodwherethesplit-zoningsystemiscompletelyoffandresumesoperationatthenextscheduledperiod.

Power Off Timer (SetupFunction154):Allowsusertoscheduleindoorunitcompletelyoffforoneinstance: FollowScheduleOption:indoorunitwillresumeoperationatthenextscheduledperiod. PermanentlyOffOption:indoorunitwillremainoffindefinitelyuntiltheuserchangesthesystemmode.

Page 10: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

Wireless System Installation Guide

69-2426—01 10

Outdoor sensor (optional)

5 Mount remote controller & outdoor sensor1 Separate the wallplate from the remote controller.

2 Mount the wallplate using the included screws and anchors 5 feet from the floor on an interior wall. If the remote controller is configured to sense indoor temperature, mount in the same room as the indoor unit.

Drill3/16"holesfordrywall. Drill7/32"holesforplaster.

3 Snap the remote controller to the wallplate on the wall.

M28491

M28492

Mountthesensoronaverticalexteriorwall,atleast6inchesbelowanyoverhang. Choose a location protected from direct sunlight.

Placesensorsecurelyin bracket, facing

away from wall.

RedLINK™ error codes

E0 27 Verify device temperature is within operating range. If within range for at least 30 minutes and problem persists, replace Remote Controller.

E0 91 Communication was established between wireless receiver and the indoor unit, but communication has been lost for 10 minutes. Check cable connection. Try replacing the cable.

E1 29 Attempting to connect incompatible wireless devices.

E1 34 Low signal strength. Move wireless device to a different location and try again.

E1 38 Make sure Connect light on wireless receiver is flashing and you are 2+ feet away from wireless receiver.

E1 54 Indoor unit does not support wireless receiver.

Forfulllistoferrorcodes,pleaserefertoyourequipment'stechnicalservicemanual.

Page 11: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

11 69-2426—01

Replacing system components

Note:OnlyuseMitsubishiElectriccomponentsorotherdesignatedcomponentsforinstallation.Failuretocomplymaydamagetheproductorcauseahazardouscondition.

Remote Controller

To replace a remote controller, install batteries and follow the procedures on page 3tolinkittothewirelessnetwork.Ifnecessary,modifysettingsasneeded(seetablesonpages6–8).

Portable Central Controller & outdoor sensor

ToreplaceaPortableCentralControlleroroutdoorairsensor,installbatteriesandfollow the procedures on page 4 to link it to the wireless network.

Wireless receiver

After installing a new wireless receiver, you must re-set the remote controller and PortableCentralControllertocommunicatewiththenewequipment,asdescribedbelow.

Removing all wireless devices:1 Pressandhold the CONNECT button on the wireless receiver for 10 seconds.

2 To reconnect, see procedure on page 3.

Attheremotecontroller:

1 Pressandhold the FAN and s buttons for 3 seconds until display changes. "WAIT"willbedisplayedforupto17seconds.

2 PressNEXTuntilFunction194isdisplayed(wirelesssetup).

3 PressttochangeFunction194settingto0(disconnectfromoldwirelessreceiver).

4 Followtheproceduresonpage3tolinktonewwirelessreceiver.

AtthePortableCentralController:1 Pressandholdtheblankspace(orarrowif

present)inthelowerrightcornerofthescreenuntilthedisplaychanges(about3seconds).

2 PressREMOVE, then YES to disconnect from old wireless receiver.

3 Followtheprocedureonpage4tolinktonewwireless receiver.

Page 12: Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 · 2014-03-13 · Controller Kit Installation Manual MIFH1, MRCH1, MCCH1, MOS1 69-2426-01 Installation guide for: •

© 2010 Mitsubishi Electric & Electronics USA, Inc.Suwanee, GA 30024 All Rights Reserved.The three diamond logo is a registered trademarkof Mitsubishi Electric Corporation69-2426—01M.S.11-10PrintedinU.S.A.

Regulatory informationFCC Compliance Statement (Part 15.19) (USA only) ThisdevicecomplieswithPart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:

1 This device may not cause harmful interference, and2 This device must accept any interference received, including interference that may cause undesired operation.

FCC Warning (Part 15.21) (USA only) Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoidtheuser’sauthoritytooperate the equipment.

FCC Interference Statement (Part 15.105 (b)) (USA only) ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuanttoPart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferenceinaresidentialinstallation.This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,maycauseharmfulinterferencetoradiocommunications.However,thereisnoguaranteethatinterferencewillnotoccur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:

• Reorientorrelocatethereceivingantenna.• Increasetheseparationbetweentheequipmentandreceiver.• Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected.• Consultthedealeroranexperiencedradio/TVtechnicianforhelp.

Wireless receiver, remote controller and outdoor sensor TocomplywithFCCandIndustryCanadaRFexposurelimitsforgeneralpopulation/uncontrolledexposure,theantenna(s)usedfor these transmitters must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-locatedoroperatinginconjunctionwithanyotherantennaortransmitter.

Portable Central Controller ThisportabletransmitterwithitsantennacomplieswithFCCandIndustryCanadaRFexposurelimitsforgeneralpopulation/uncontrolledexposure.Thisdevicemustnotbeco-locatedoroperatinginconjunctionwithanyotherantennaortransmitter.

Section 7.1.5 of RSS-GEN Operationissubjecttothefollowingtwoconditions:

1 this device may not cause interference, and2 this device must accept any interference, including interference that may cause undesired operation of the device.

Specifications & replacement partsOperating Ambient Temperature

Remote Controller:32to120°F(0to48.9°C)Portable Central Controller:32to120°F(0to

48.9°C)Wireless receiver:-40to165°F(-40to73.9°C)Outdoor air sensor:-40to140°F(-40to60°C)

Operating Relative HumidityRemote Controller:5%to90%(non-

condensing)Portable Central Controller:5%to90%(non-

condensing)Wireless receiver:5%to95%(non-condensing)Outdoor air sensor:0%to100%(condensing)

Physical Dimensions(height,width,depth)Remote Controller:3-9/16x5-13/16x1-1/2

inches(91x147x38mm)Wireless receiver:6-7/16x3-1/4x1-5/16

inches(164x82.5x34mm)Outdoor air sensor:5x3-1/2x1-11/16inches

(127x89x43mm)Portable Central Controller:6-1/4x3-1/8x

1-5/8inches(158.2x79.9x42mm)

Item Part Number

PortableCentralController MCCH1

Outdoorairsensor MOS1

RemoteController MRCH1

ReceiverandCable MIFH1

Cable MRC1

Accessories & Replacement Parts


Recommended