+ All Categories
Home > Documents > controllingmonitoringsubstationautomationnbkrinst

controllingmonitoringsubstationautomationnbkrinst

Date post: 08-Apr-2018
Category:
Upload: abhinav-tyagi
View: 215 times
Download: 0 times
Share this document with a friend

of 16

Transcript
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    1/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 1

    A

    TECHNICAL PAPERONCONTROLLING AND MONITORING

    OF

    SUBSTATION AUTOMATION

    AUTHORS:

    N.VENKATESWARLU, N.KEERTHI KISHORE,

    II/IV B.Tech, II/IV B.Tech,

    Branch: EEE, Branch: EEE,

    Vidyanagar. Vidyanagar.

    Email:[email protected] Email:[email protected]

    N.B.K.R.INSTITUTE OF

    SCIENCE AND TECHNOLOGY

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    mailto:[email protected]:[email protected]://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/mailto:[email protected]:[email protected]
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    2/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 2

    Summary:

    Protection and substation control have

    Under gone dramatic changes since the

    advent of powerful micro-processing and

    digital communication. Smart multi

    functional and communicative feeder

    units, so called IEDs(Intelligent

    Electronic Devices) have replaced

    traditional conglomerations of

    mechanical and static panel

    instrumentation. Combined protection,

    monitoring and control devices and LAN

    based integrated substation automation

    systems are now state of the art.Modern

    communication technologies including

    the Internet are used for remote

    monitoring, setting and retrieval of load

    and faultdata. Higher performance at

    lower cost hasresulted in a fast

    acceptance of the new technology.

    The trend of system integration will

    continue, driven by the cost pressure of

    competition and technological progress.

    The ongoing development towards

    totally integrated substations is expected

    to pick up speed with the approval of the

    open communication standard IEC61850

    in the next years.

    Introduction:

    Increased competition has forced utilities

    to go into cost-saving asset management

    with new risk strategy:

    Plants and lines are higher loaded up

    to thermal and stability limits.

    Existing plants are operated to the

    end of their life-time and not replaced

    earlier by higher rated types.

    Redundancy and back-up for system

    security are provided only with critical

    industrial load.

    Corrective event based repair has

    replaced preventive maintenance.

    Considering this changed environment,

    Power system protection and control

    face new technical and economical

    challenges:

    Modern secondary systems shall enable

    higher system loading at lower

    investment and operation cost without

    compromising system reliability.

    Users widely dispense with special

    custom-built solutions but aim at cost

    reduction by accepting standard products

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    3/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 3

    of global vendors. Manufacturers had to

    compensate the world-wide price drop

    by cost saving. This has mainly been

    achieved by right-sizing of product

    ranges, standardisation of products,

    rationalisation of manufacturing and

    expansion to global markets.In this

    regard, the introduction of the

    digital technology has played a decisive

    role because the price reduction at a

    comparable function range could only be

    achieved with the new generation of

    smart highly integrated IEDs.Besides the

    lower investment cost, theuser gets a

    reduction of the operation cost

    due to the inherent self-monitoring

    capability(corrective instead of

    preventive maintenance)and the possible

    remote operationand diagnosis.

    In the relay business, these advantages

    were obvious for the user. Therefore, the

    transition to the new digital technology

    occurred within a decade (1985-1995).

    FIGURE 1 - Current relay design trend

    In the case of substation control, cost

    comparison between electromechanical

    anddigital technology has often been

    discussedcontroversially.The recently

    practised assessmentof total life cycle

    cost, however, seemsto confirm

    economic use in most cases. Decisive

    is the possibility to rationalise and

    automatesubstation operation and to save

    operatingstaff on site. This pays off in

    particularin industrialised countries with

    high personnelcost.Relaying and control

    IEDs also serve asdata acquisition units

    for power system controland power

    quality monitoring. By usingwide area

    information systems, the data can

    be made available to all involved

    partners.This is becoming more and

    more importantin order to satisfy the

    information demandin the deregulated

    power supply market withfree network

    access.

    Recent development

    of protection and substation

    automation:After more than 20 years ofdevelopment,

    digital protection and substation control

    have reached a mature product state.

    In the mean time, some 100.000 digital

    relaysand some 1000 digital substation

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    4/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 4

    control systemsare in service.As a rule, a

    common IED hardwareplatform is used

    today for relays and baycontrol units

    (figure 1). Its modular designallows

    adaptation of the input/output interface

    to the individual application. Separate

    processing modules are dedicated to the

    communication interfaces to cope with

    theincreased data rates and complex

    transmissionprocedures. GPS time

    synchronisationof microsecond accuracy

    is optionallyoffered with the latest

    device generations.Global products

    designed for the worldmarket meet

    relevant IEC as well asANSI/IEEE

    standard requirements and can

    be adapted to the communication

    standardsused in Europe and USA. The

    informationinterface of relays can for

    examplebe delivered to IEC60870-5-103

    as wellas to DNP3.0 or Modbus.

    Windows compatible PC programs allow

    comfortable local or remote operation of

    IEDs. Unfortunately,there is no common

    operatingstandard, so that the user must

    changebetween vendor dependent

    program versionsto address relays of

    different make.This also concerns

    communication interfacesand protocols.

    An improvement can be expected when

    relays will be equipped with their own

    Internetserver and the operator-relay

    dialoguecan be performed in a simple

    way by usingstandard browsers. First

    Internet enabledIEDs are already

    available.

    Protective relaying:

    The number of functions integrated in

    relays has been steadily expanded in

    parallelwith the increasing processing

    power andstorage capacity. Table 1

    shows a typicalexample of relay

    hardware evolution.

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    5/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 5

    TABLE 1: Development of digital relay

    HW performance (example)

    Protection relays have developed into

    multi-functional universal devices,

    generallydesignated as IEDs (Intelligent

    ElectronicDevices). Non-protection

    tasks, such asmetering,monitoring,

    control and automation,occupy an ever

    increasing share of thescope of

    functions.Complete protection of a

    power systemcomponent (transformer,

    line, etc.) can nowbe provided by only a

    few highly integratedrelays. For

    example, the protection of a larger

    generating unit only needs two or three

    relays, each with about 15 protection

    functions.At the time of traditional

    relaying, severalpanels or cubicles full of

    black-box relayswere necessary for the

    same protection scope.Protection

    functionsBasic digital protection

    functions havepassed innumerable lab

    and field tests andare well-established in

    practice. In the lastyears, they could be

    further improved byapplying intelligent

    algorithms.Examples forthis are: higher

    accuracy and stability in case of

    disturbed measuring values (e.g. during

    c.t. saturation), and better load versus

    faultdiscrimination by adaptive

    measuring principlesand flexible shaping

    of characteristics.The offer of integrated

    functions coversthe world-wide practice

    (global relay). Theuser can for example

    choose between definiteand various

    inverse over-current timecurves or

    between quadrilateral and MHO

    type impedance characteristics. He has

    thefreedom to configure the relay for his

    particularapplication case by software

    parameterisation.This trend will surely

    contribute to aglobal convergence of

    relaying practices.Additional functions

    Metering and event/fault recording are

    now offered as standard even with

    smallestrelays.An accuracy of about 1%

    for meteringof current and voltage and

    of about 2% for active and reactive

    power are usually specifiedfor relays.

    For the total accuracy, theerrors of c.t.s

    and v.t.s (up to 3% with protectioncores)

    have to be added.The storage time for

    fault records is nowin general at least

    10s with a resolution of 600to 2 400 Hz

    dependent on the type of relay.Power

    quality monitoring is partly covered

    by protection relays. The offered

    registrationof voltage dips greater than

    10 msand harmonics up to the 5th or

    10th order issufficient in mostapplication

    cases.Monitoringof fast transients and

    higher harmonics(e.g. up to the 50th)

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    6/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 6

    would requirehigher sampling rates and

    extended relaymemories. The ongoing

    technical improvementand price

    reduction of hardware components

    will however favour a trend towards

    the integration of full scale PQ

    monitoringin protection relays.

    Combined protection and control

    IEDOver the years, there has been a

    globaltrend towards combined units for

    protectionand control on basis of IEDs

    (Intelligent Electronic Devices, Figure

    2). The main application:

    Areas are distribution systems and

    industrial networks. These universal

    devicesintegrate all substation secondary

    functionswith the exception of revenue

    metering.Full scale versions include a

    full graphicmimic display and a key pad

    for supervisory

    FIGURE 2 - Combined Protection and

    Control IED

    control. The devices can be used stand-

    aloneor serially connected to an RTU or

    a centralcontrol unit.Automation

    functions can comfortablybe designed

    and implemented by means ofa graphic

    PC tool (CFC: continuous function

    chart).Computer controlled testing

    Simulation techniques have advanced to

    a degree of virtual reality. This goes in

    particularfor real-time digital simulation

    systems(RTDS) which enable absolute

    practicecompatible lab testing.However,

    even PC-controlled portabletest sets

    allow for dynamic testing under real

    conditions.Among other features,

    programadditions are offered for

    extended relay testing,for example under

    the condition of c.t.saturation.

    This new quality of testing hasdecisively

    contributed to the upgraded performance

    and reliability of digital protection

    systems.

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    7/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 7

    Maintenance Based on the nearly

    complete self-monitoringof modern

    IEDs, event controlled maintenance is

    propagated world-wide asa decisive

    contribution to cost reduction.

    Theoretical studies have shown that the

    availability of digital protection is even

    comparableto a redundant analogue

    protectionscheme providing at the same

    time significantlyhigher security against

    false operation.Complete abolition of

    testing, however, ismostly not accepted

    as even the best selfmonitoringconcept

    cannot cover 100% ofthe protection

    scheme.In the few publications about the

    currentpractice, maintenance intervals of

    four(Germany) to six years (Japan,

    Sweden) wererecommended.

    Newersurveys indicate atrend to longer

    intervals, even up to 10 years.

    3. Current protection

    practice:

    A world wide survey on reasons for

    blackouts and experienced protection

    performance[1] showed the following:

    thejudgement of protection was in

    general reasonablygood. There was,

    however, a numberof maloperations of

    feeder protection.More attention should

    be paid to relay settingand co-ordination

    with overload capabilitiesof the

    protected plants.The survey confirms

    that fast clearanceof fault, in particular

    on busbars, is vital toa systems ability

    to ride through disturbances.Duplication

    of protection and

    POWER SYSTEM FAULT (LIGHTNING

    STRIKES AN OVERHEAD LINE).

    the installation of breaker fail provision

    isessential on crucial busbars and on

    highvoltagelines since back-up operation

    times often result in system splitting and

    cascading.The following developmenttrends canbe observed in the individual

    protectionareas:

    3.1 Transmission system

    protection:

    On higher voltage levels, redundant

    protectionconcepts with stand alone

    relays havebeen kept also with thechangeover to digitaltechnology. Relays

    with dissimilar measuringprinciples (e.g.

    differential and distance)or relays of

    different make are stillpreferred.Control

    functions are provided byindependent

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    8/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 8

    feeder units.Line protection With the

    advent of digital wide-band

    communication more differential

    protectionhas been applied at overhead

    lines of evenup to some 100 km length.

    Phase segregateddesign guarantees zone

    and phase selectivityfor all kind of short-

    circuits. The use isadvantageous in

    particular with complex line

    configurations such as multi circuit,

    multi terminal or tapped lines.

    Differential and distance protection are

    now considered as ideal combination for

    high voltage lines. The transfer of

    protectiondata via communication

    networks, however,requires careful

    planning. GPS synchronisation

    may be necessary in critical cases.

    With short lines up to some 30 km, a

    direct back-to-back connection of the

    relaysat line ends is possible provided

    that dedicatedoptic fibres are available.

    Fault locationUpgrading of fault location

    is a preferredsubject of ongoing studies

    and numerouspublications. In most

    cases, new or improvedmethods are

    discussed and proposed to compensate

    influencing factors such as fault

    resistance, load transfer, parallel line

    coupling,series compensation and line

    chargingcurrent.Fault location based on

    reactance measurementas integral

    function of distance relays has an

    accuracy of about one percent linelength

    under favourable conditions. Larger

    errors will however occur with higher

    fault resistances. Improvement can be

    expected inthe future by GPS based

    synchronisation ofdata acquisition and

    processing of the informationfrom both

    line ends.High accuracy is achieved by

    travellingwave based fault locators.

    ESKOM, SouthAfrica reports about +/-

    150 m on EHV lines[2]. Fault location is

    in this case estimatedby measuring the

    time difference of travellingwave

    propagation from the fault to bothline

    ends. Transformer protectionThe use of

    digital filtering and intelligentalgorithms

    has dramatically upgraded transformer

    differential protection performance.

    Stability against c.t. saturation, inrush-

    currentsand overfluxing is now much

    more reliable.Integrated numerical ratio

    and vectorgroup adaptation belong to the

    standard.Relays with up to five

    stabilizing inputs are offered which

    allow to protect all kind of transformer

    connections. Integrated add-on functions

    now reachfrom overload and overcurrent

    back-up toearth-fault and over excitation

    protection. OLTC control and

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    9/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 9

    transformer monitoringare also

    integrated in some combined devices.

    Busbar protection State-of-the-art is

    decentralized digital design and sub-

    cycle operating time. Bayunits are

    connected to the central unit viafast

    optical fibre links. Sophisticated

    algorithms guarantee far reaching

    independence of c.t. saturation. The

    isolator replica is softwarebased and can

    each be adapted to evencomplex bus

    configurations by means of thesetting

    program. Digital low impedance

    protection is now offered even in

    traditionally high impedanceminded

    regions because high impedance

    protection can by principle not be

    transferred to digital technology.

    Protection of generating units Function

    integration has further proceeded. Even

    larger generating units can now be

    protected by two or three relays with

    each about 15 protection functions

    (protection of auxiliaries nor

    considered).The quality (sensitivity and

    accuracy of measurement, replica reality,

    etc.) of individual protection functions

    has been further improved. In principle,

    however, the longtime established

    protection principles are further used

    Wide Area System Protection Schemes

    (SPS)A more recent development

    concerns System Protection Schemes

    (SPS) [3, 4].They operate on the basis of

    system wide acquired information and

    try to avoid power system collapse

    which can occur during unstable active

    or reactive power conditions as a

    consequence of voltage and frequency

    drop or loss of synchronism. Normally

    one tries to achieve stable partial

    networks by purposeful system splitting,

    GIS

    load shedding and forced control of

    power generation. The SPSs are

    intended to operate already in the initial

    state of instability before system control

    can intervene. Recent developments

    include GPS-based synchrophasor

    measurement for on-line systemstate

    monitoring. A number of SPS systems

    are already in service, mainly in Japan

    [3]

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    10/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 10

    3.2 Distribution System

    Protection:

    The current trend is towards combined

    protection and control IEDs. Driving

    forceis the need for cost cutting.The

    reduction of the former conglomeration

    of black box devices to only one

    multifunctional relay saves on space and

    wiring. Highly integrated switchgear

    panels using small scale CTs and VTs

    are gaining increasing market share.

    Low resistance earthed radial networks

    are generally protected by inverse-time

    OCrelays.Meshed Peterson coil earthed

    networks which occur mostly in Europe

    are also equipped with distance relays.

    Urban cable networks traditionally use

    differential protection. New digital

    relays must be suitable for the existing

    pilot wires. Therefore, proven analogue

    current comparison principles are

    maintained, however, upgraded to digital

    relaying standards. For short cable

    connections also relays with digital

    wire communication can be applied. Inthe more seldom case where optic fibre

    connections exist, relays with direct

    relay-torelay OF connection can be used

    for distances up to about 30 km.

    The growing share of distributed

    generation requires reconsideration of

    distribution protection. In many cases

    changeover to directional OC relays may

    be necessary to cope with the backfeed

    of distributed generators. A particular

    problem provides the loss-of-mains

    protection because traditional frequency

    and voltage relays may be too slow or

    insensitive and vector jump relays tend

    tooverfunction.

    OPEN AIR SWITCHYARD

    Siemens (Germany)

    A number of new principles

    have been proposed but no satisfying

    solution is yet available. Fast fault

    finding and system restoration to

    upgrade power supply quality is getting

    more and more important. For this

    purpose, the state of earth-fault and

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    11/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 11

    shortcircuitindicators are evaluated

    together with the distance-to-fault

    calculation ofrelays.Modern fault

    management includes automatic

    acquisition and processing of these data.

    The results are then indicated in the

    graphic information system of the

    control centre. [5, 6]In many countries,

    fault clearing by distributedreclosers and

    sectionalizes is stillpractised. Protection

    and control functions of these devices

    are now also provided bydigital devices.

    In combination with poletopRTUs and

    radio connections, fast faultclearing and

    load restoration is also achievedin this

    case. [7]Detection of high resistance

    faults(downed conductors) has been

    studied fora long time. Proposed

    algorithms are basedon wave shape

    analysis and recognition oftypical arc

    characteristics.

    A recent survey comes to the conclusion

    that an algorithmsuitable for practical

    application has so farnot been found

    despite costly developmentefforts. [8]

    4. State and trends of substation

    automation Integrated protection and

    control firstappeared in the mid

    eighties and has sincethen matured to

    full scale substation automation.

    4.1 Recent practice:

    Simple systems for distribution or

    industrialnetworks mostly use feeder

    dedicatedcombined protection and

    control IEDs anda PC-based central unit.

    Alternatively,enhanced RTUs with

    decentralised I/Operipherals are applied.

    FIGURE 3 - Communication world of

    substation automation.

    Ethernet is generally accepted as

    substationLAN. Industry standards such

    asProfibus and LON are successfully

    used inEurope while DNP3.0 and

    Modbus are preferredin USA. Recently,

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    12/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 12

    Ethernet withTCP/IP has also been

    introduced. Larger systems typically use

    a specialcentral unit (server) and

    separate bay units for control.

    Independent protection relays are usually

    connected to the bay control unitsin this

    case.The remote control function is

    emulatedeach in the central unit. The

    standard IEC60870-5-101 has in the

    mean time beengenerally adopted for

    communication between substation and

    control centre.Time accurate GPS based

    synchronisingis available as an option.

    Direct peer-to-peer communi- cation

    between bay units is offered in some

    cases.It can be used for control (e.g.

    interlocking),however not for protection

    because of therelatively long reaction

    time (some 100 ms).Figure 3 shows the

    complex communication world of

    protection and substationautomation.The

    upcoming standard IEC61850 foropen

    communication in substations is stillin

    the test phase and not generally

    availablefor application. [9]Some

    vendors in USA already offerUCA2-

    compatible devices according to

    thepreliminary standard draft. A few

    pilot systemsare in operation using

    standard 10Mbit/s Ethernet. It is also

    reported on a successfulimplementation

    of peer-to-peer communicationwith

    quarter cycle reaction time.

    4.2 Internet technology:

    The latest trend goes to using Internet

    technology in an Intranet or the Internet

    itself.Several vendors already offer

    substationautomation systems with

    integratedInternet server. In this way, the

    acquireddata can be exchanged in a cost

    savingwayin an Intranet and distributed

    to a widercircle of users. Classic

    workstations can bereplaced by normal

    Internet browsers.Maintenance work, for

    example implementationof new

    functions, must thenonly be performed at

    the central applicationserver. [10]

    In Japan, some systems have been in

    servicewhere mini-servers are

    implemented inrelays and bay controlunits on basis ofJavaVM (Java Virtual

    Machine) [11]Also NGC in England has

    been testingapplication servers in

    substations.

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    13/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 13

    Relays and other devices are in this case

    connected tothe server via an Ethernet

    information bus.Information gathered onthe SQL data bank of the server can be

    accessed through standardbrowsers

    using ASP (Active ServerPage)

    procedures. [12]An American vendor is

    even a step aheadand offers a monitoring

    system where spaceand administration of

    data is provided onthe vendors own

    server. The user must onlyinstall the

    Internet enabled relays and devicesin his

    substation and connect them to the

    Internet via the local service provider.

    Safety against foreign access is claimed

    to be guaranteed by passwords,

    authenticationprocedures and firewalls.

    FIGURE 4 - Structure of a highly

    The integrated substation

    offer aims at small users where an own

    SCADA system is too expensive or not

    yetinstalled.

    4.3 Highly integrated

    substations:

    The use of electronic sensors instead of

    traditional current and voltage

    transformersin combination with digital

    protectionand control allows to design

    compact substations.In the distribution

    area, there has beena long lasting trendto highly integratedswitchgear panels.

    The current transformersare in this case

    designed as Rogowski coilsor closed-

    core low-signal transformers.Resistive or

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    14/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 14

    capacitive voltage dividers areused as

    voltage sensors. The low signal level

    requires to use shielded cables for the

    connectionof the combined protection

    and controlIEDs. [13] This design

    approach considersthe switchgear panel

    as one totallyintegrated module.

    In high voltage, the development goes to

    optic-electronic current and voltage

    transformers(acc. toFaraday and Pockels

    principles)and data bus systems. (Figure

    4).Currentand voltage sensors provided

    withdigital output are connected to a fast

    fieldbus (Fast Ethernet 100 Mbit/s or

    even 1Gbit/s) in the switchgear bay.

    Discussion at the CIGRE conference

    2000 in Paris showed that the technicalproblemscan be mastered.A number of

    pilot projectsare successful in operation.

    [14, 15, 16]In general, a drastic cost

    reduction isexpected with this novel

    substation design.Broad application,

    however, will only takeplace when

    established standards (IEC61850)

    for open communication are available.

    5. Concluding remarks:

    Modern media and cost pressure have

    been the diving forces for system

    integrationand automation in substations.

    The furtherprogress in data acquisition

    (synchronisedsampling, higher sampling

    rate), processingand storage capability

    (doubling every18 months as per

    Moores Law) will allowfurther upgrade

    of protection functionsandseamless

    monitoring and recording of load,

    fault events and switchgear state.Wide-

    bandcommunication LANs and Internet

    technology(relay integrated servers and

    browserbased dialogue) will make the

    informationavailable at any place of the

    enterprise.Theproblem will however be

    to select the usefulinformation from the

    large amount of indicatedand stored

    data. Expert systems willhave to take on

    this task.Functionality, performance, and

    operationcomfort of substation control

    will beenhanced corresponding to the

    current stateof media (colour graphics,

    images, video,voice recognition,

    etc.).Wireless hand helddevices may be

    used for local operation andservices.

    There will be cross-links throughfast

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    15/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 15

    WAN to system control and there will

    bea development towards totally

    integratedover-all controlsystems.Access

    for operationand diagnosis will be

    possible from any place,even world wide

    via mobile communication.Substation

    automation and remote controlwill

    increasingly extend to the distribution

    level. The much discussed distribution

    automation should become reality inthe

    foreseeable future.The further fast

    proceeding system integrationimplicates

    however application issuesin particular

    with reduced technical staffafter utility

    privatisation and deregulation.Users

    already complain about the complexityof

    presently offered systems and ask

    foreasy and vendor independent

    configuration,parameterisation and

    setting procedures.It remains to be seen

    if applicable standardsand tools will be

    available in the nearfuture and if the

    promised plug and playcompatibility

    can be achieved.Anyway, nomadic

    knowledge workerswill be around to

    provide adequate services.

    6. Literature:

    [1] Mackey, M.: Summary report on

    surveyto establish protection

    performance duringmajor disturbances,

    ELECTRA No. 196,June/July 2001, pp.

    19-29.

    [2] Gale, P.F. et al: Travelling wave fault

    locator experience in ESKOMs

    transmissionnetwork. IEE DPSP

    Conference, 9-12 April2001 in

    Amsterdam, Conference manual

    pp. 327-330.

    [3] CIGRE Brochure.No. 187: System

    protection schemes in Power Networks.

    [4] CIGRE Brochure No. 200: Isolation

    and restoration policies against power

    systemcollapse.

    [5] Lehtonen,M. et al: Automatic fault

    management in distribution networks.,

    CIRED 2001, Report 3.9.

    [6] Roman H. und Hylla, H.: Fast fault

    locating in rural MV distribution

    networks.CIRED 2001, Report 3.6.

    [7] Roth, P.D.: Communication

    architecturein modern distribution

    systems,CIRED 2001, Report 3.8.

    [8] Redfern, M.A.: A review of

    techniquesto detect downed conductors

    in overheaddistribution systems. IEE

    DPSP Conference,9-12 April 2001 in

    Amsterdam,Conference manual pp. 169-

    172.

    [9] Shephard, B.; Janssen, M:C:;

    Schubert,H.: Standardised

    PDF created with pdfFactory Pro trial version www.software-partners.co.uk

    http://www.software-partners.co.uk/http://www.software-partners.co.uk/http://www.software-partners.co.uk/
  • 8/7/2019 controllingmonitoringsubstationautomationnbkrinst

    16/16

    PROTECTION AND SUBSTATION AUTOMATION

    N.B.K.R.I.S.T VIDYANAGAR 16

    communication insubstations. IEE DPSP

    Conference, 9-12April 2001 in

    Amsterdam,Conference manual

    pp. 270-274.