Date post: | 10-Feb-2018 |
Category: |
Documents |
Upload: | luis-salinas |
View: | 227 times |
Download: | 0 times |
of 160
7/22/2019 ControlNet Communications Module
1/160
Instruction Manual
ControlNetCommunications Module
M/N RECOMM-CNET
D2-3497
7/22/2019 ControlNet Communications Module
2/160
7/22/2019 ControlNet Communications Module
3/160
Contents I
CONTENTSChapter 1 Introduction
1.1 ControlNet Module Features.......................................... 1-1
1.2 Related Documentation ................................................. 1-2
1.3 Conventions Used in This Manual................................. 1-2
1.4 Getting Assistance from Reliance Electric..................... 1-2
Chapter 2 Getting Started
2.1 ControlNet Module Components ................................... 2-1
2.2 Required Equipment...................................................... 2-2
2.3 Installation Checklist ...................................................... 2-3
Chapter 3 Installing the ControlNet Module
3.1 Preparing for an Installation........................................... 3-1
3.2 Commissioning the Module ........................................... 3-1
3.3 Connecting the Module to the Drive .............................. 3-2
3.4 Connecting the Module to the Network.......................... 3-5
3.5 Applying Power.............................................................. 3-6
Chapter 4 Configuring the ControlNet Module4.1 Configuration Tools........................................................ 4-1
4.2 Using the LCD OIM to Configure the Module ................ 4-2
4.3 Setting the Node Address.............................................. 4-2
4.4 Setting the I/O Configuration ......................................... 4-3
4.5 Selecting Master-Slave.................................................. 4-4
4.6 Selecting Reference Adjust ........................................... 4-5
4.7 Setting a Fault Action..................................................... 4-5
4.7.1 Changing the Fault Action ................................... 4-6
4.7.2 Setting the Fault Configuration Parameters ........ 4-7
4.7.3 Resetting the Module........................................... 4-7
4.8 Viewing the Module Configuration................................. 4-8
Chapter 5 RSNetWorx Configuration for PLC-5C Applications5.1 Configuring a ControlNet Network: An Example............ 5-1
5.1.1 Installing and Registering EDS Files in
RSNetWorx ......................................................... 5-2
5.1.2 Configuring a Network with RSNetWorx.............. 5-7
5.1.3 Verifying Network Properties ............................. 5-18
7/22/2019 ControlNet Communications Module
4/160
II ControlNet Communications Module
Chapter 6 PLC-5C Applications
6.1 About I/O Messaging .....................................................6-1
6.2 Understanding the I/O Image......................................... 6-2
6.3 Using Logic Command/Status ....................................... 6-4
6.4 Using Reference/Feedback ........................................... 6-5
6.5 Using Datalinks.............................................................. 6-5
6.5.1 Rules for Using Datalinks .................................... 6-5
6.5.2 32-Bit Parameters using 16-Bit Datalinks............ 6-6
6.6 Function of the Sample Program ................................... 6-7
6.7 Main Program (PLC-5C) ................................................6-8
6.8 About Explicit Messaging............................................. 6-12
6.8.1 Performing Explicit Messages ........................... 6-12
6.8.2 Explicit Messaging Examples ............................6-13
Chapter 7 ControlLogix Applications
7.1 Configuring a ControlLogix CNB Scanner ..................... 7-2
7.2 Function of the Sample Program ................................. 7-15
7.3 RSLogix 5000 Ladder Logic Program.......................... 7-17
7.4 About Explicit Messaging............................................. 7-19
7.4.1 Performing Explicit Messages ........................... 7-19
7.4.2 Explicit Messaging Examples ............................7-20
Chapter 8 Troubleshooting the ControlNet Module and Network
8.1 Understanding the Status Indicators.............................. 8-18.1.1 DRIVE Status Indicator........................................ 8-2
8.1.2 MS Status Indicator ............................................. 8-3
8.1.3 NET A and B Together ........................................ 8-4
8.1.4 NET A and B Independently ................................ 8-5
8.2 Module Diagnostic Items................................................ 8-6
8.3 Viewing and Clearing Events ......................................... 8-8
Appendix A Technical Specifications...................................................... A-1
Appendix B ControlNet Module Parameters ............................................ B-1
Appendix C ControlNet Objects ............................................................... C-1
Appendix D Logic Command/Status Words............................................. D-1
Glossary ..................................................................................Glossary-1
Index .......................................................................................Index-1
7/22/2019 ControlNet Communications Module
5/160
7/22/2019 ControlNet Communications Module
6/160
7/22/2019 ControlNet Communications Module
7/160
Contents V
List of Tables
Table 2.1 Equipment Shipped with the ControlNet Module ................... 2-2
Table 2.2 Required User-Supplied Equipment ...................................... 2-2
Table 4.1 Configuration Tools................................................................ 4-1
Table 4.2 Selections for Drive Response to Communication Fault........ 4-6
Table 4.3 Fault Configuration Parameters............................................. 4-7
Table 4.4 Module Configuration Status Parameters.............................. 4-8
Table 5.1 Input/Output Table ............................................................... 5-14
Table 6.1 Parameter Settings for the Sample Program......................... 6-7
Table 7.1 Parameter Settings for the Sample Program....................... 7-16
Table 8.1 DRIVE Status Indicator: State Definitions.............................. 8-2
Table 8.2 MS Status Indicator: State Definitions ................................... 8-3
Table 8.3 NET A and B Together: State Definitions .............................. 8-4
Table 8.4 NET A and B Independently: State Definitions ......................8-5
Table 8.5 Module Diagnostic Items........................................................ 8-6
Table 8.6 Event Codes and Descriptions............................................... 8-8
7/22/2019 ControlNet Communications Module
8/160
VI ControlNet Communications Module
7/22/2019 ControlNet Communications Module
9/160
Introduction 1-1
CHAPTER1Introduction
The ControlNetmodule (RECOMM-CNET) is an embedded
communication option for DPI
AC drives, such as the SP600
drive. The module is mounted in the drive and receives its requiredpower from the drive and from the network.
The module can be used with other products that implement DPI, aperipheral communication interface. Refer to the documentation foryour product for specific information about how it works with themodule.
This manual is intended for qualified electrical personnel familiarwith installing, programming, and maintaining AC drives andnetworks.
1.1 ControlNet Module Features
The ControlNet module features the following:
A number of configuration tools that can be used to configure themodule and connected drive. The tools include the LCD OperatorInterface Module (OIM) on the drive and drive-configurationsoftware such as VS Utilities (version 1.01 or later).
Status indicators that report the status of the drivecommunications, module, and network. They are visible bothwhen the cover is opened and when it is closed.
I/O, including Logic Command/Reference and up to four pairs ofDatalinks, that may be configured for your application using aparameter.
Support of explicit messages.
User-defined fault actions that determine how the module and thedrive respond to communication disruptions on the network andcontrollers in idle mode.
7/22/2019 ControlNet Communications Module
10/160
1-2 ControlNet Communications Module
1.2 Related Documentation
Refer to the following related publications as necessary for moreinformation. All of the publications are available fromhttp://www.theautomationbookstore.com.
D2-3485 SP600 AC Drive User Manual
D2-3488 VS Utilities Getting Results ManualOnline help installed with the software
9399-WAB32GR Getting Results with RSLinxOnline help installed with the software
9399-RL53GR RSLogix 5 Getting Results GuideOnline help installed with the software
9399-RL50GR RSLogix 500 Getting Results GuideOnline help installed with the software
9399-RLD300GR RSLogix 5000 Getting Results GuideOnline help installed with the software
9357-CNETL3 RSNetWorx for ControlNet Getting ResultsGuideOnline help installed with the software.
1.3 Conventions Used in This Manual
The following convention is used throughout this manual:
Parameters are referenced as follows:
Parameter Name (Parameter Number)
For example: DPI Port (1)
1.4 Getting Assistance from RelianceElectric
If you have any questions or problems with the products describedin this instruction manual, contact your local Reliance Electric salesoffice.
For technical assistance, call 1-800-726-8112.
7/22/2019 ControlNet Communications Module
11/160
Getting Started 2-1
CHAPTER2Getting Started
This chapter provides:
A description of the ControlNet module components A list of parts shipped with the module
A list of user-supplied parts required for installing the module
An installation checklist
2.1 ControlNet Module Components
Status Indicators Four LEDs that indicate the status of theControlNet channel(s), DPI, and the module. Referto chapter 8 for more information.
DPI Connector A 20-pin, single-row shrouded male header. AnInternal Interface cable is connected to thisconnector and a connector on the drive.
Channel A BNCReceptacleChannel ABNC connection for the ControlNetcable.
Channel B BNCReceptacle
Channel BBNC is an optional connection for theredundnat ControlNet cable.
ControlNet NodeAddress Switches
Switches for setting the node address.
Figure 2.1 Components of the ControlNet Module
7/22/2019 ControlNet Communications Module
12/160
2-2 ControlNet Communications Module
2.2 Required Equipment
Table 2.1 lists the equipment shipped with the ControlNet module.When you unpack the module, verify that the package includes all ofthese items.
Table 2.2 lists user-supplied equipment also required to install andconfigure the ControlNet module.
Table 2.1 Equipment Shipped with the ControlNet Module
Item Description
One RECOMM-CNET ControlNet module
A 2.54 cm (1 in) and a 15.24 cm (6 in) Internal Interface cable(only one cable is needed to connect the module to the drive)
One grounding wrist strap
ControlNet Module User Manual (D2-3497)
Table 2.2 Required User-Supplied Equipment
Item Description
A small flathead or Phillips screwdriver
Configuration tool, such as:
LCD OIM
VS Utilities (version 1.01 or later)
with RECOMM-232 Serial Converter
RSNetWorx for ControlNet (version 3.00.00 or later)
Controller configuration software (for example, RSLogix 5,RSLogix 500, or RSLogix 5000)
A PC connection to the ControlNet network, such as:
1784-PCC
1770-KFC
1784-KTCX
7/22/2019 ControlNet Communications Module
13/160
Getting Started 2-3
2.3 Installation Checklist
This section is designed to help experienced users start using theControlNet module. If you are unsure about how to complete a step,refer to the referenced chapter.
Step Action Refer to 1 Review the safety precautions for the
module.Throughoutthis manual
2 Verify that the drive is properly installed. SP600 ACDrive UserManual
3 Install the module.Verify that the drive is not powered. Then,connect the module to the network using aControlNet cable and to the drive using theInternal Interface cable. Use the captivescrews to secure and ground the module tothe drive.
Chapter 3,Installing theControlNetModule
4 Apply power to the module.The module receives power from the drive.Apply power to the drive. The statusindicators should be green. If they flash red,there is a problem. Refer to chapter 8,
Troubleshooting the ControlNet Module andthe Network.
Chapter 3,Installing theControlNetModule
5 Configure the module for yourapplication.Set the parameters for the following featuresas required by your application:
I/O configuration.
Fault actions.
Chapter 4,ConfiguringtheControlNetModule
6 Apply power to the ControlNet master andother devices on the network.Verify that the master and network areinstalled and functioning in accordance withControlNet standards, and then apply powerto them.
7 Configure the scanner to communicatewith the module.Use a network tool for ControlNet toconfigure the master on the network.
Chapter 5,RSNetWorxConfigurationfor PLC-5CApplications
7/22/2019 ControlNet Communications Module
14/160
2-4 ControlNet Communications Module
8 Create a ladder logic program.Use a programming tool to create a ladderlogic program that enables you to do thefollowing:
Control the module and connected drive.
Monitor or configure the drive using ExplicitMessages.
Chapter 6,PLC-5CApplications
Step Action Refer to
7/22/2019 ControlNet Communications Module
15/160
Installing the ControlNet Module 3-1
CHAPTER3Installing the
ControlNet Module
Chapter 3 provides instructions for installing the module on anSP600 drive.
3.1 Preparing for an Installation
Before installing the ControlNet module, verify that you have allrequirement equipment. Refer to chapter 2, Getting Started, for alist of equipment.
3.2 Commissioning the Module
To commission the module, you must set a unique node address onthe network. (Refer to the Glossary for details about nodeaddresses.)
Important: New settings are recognized only when power isapplied to the module or it is reset. If you change asetting, cycle power or reset the module.
Important: To guard against device malfunction, you must wear agrounding wrist strap when installing the ControlNetmodule.
Step 1. Set the ControlNet modules node address by rotating thenode address switches to the desired value for each digitas shown in figure 3.1.
Important: Each node on the ControlNet network must have aunique address.
!
ATTENTION: The ControlNet module contains ESD-(Electrostatic Discharge) sensitive parts that can bedamaged if you do not follow ESD controlprocedures. Static control precautions are requiredwhen handling the module. Failure to observe theseprecautions could result in damage to equipment.
7/22/2019 ControlNet Communications Module
16/160
3-2 ControlNet Communications Module
Important: The node address must be set before power is appliedbecause the module uses the node address it detectswhen it first receives power. To change a nodeaddress, you must set the new value and then removeand reapply power to or reset the module.
3.3 Connecting the Module to the DriveStep 1. Remove power from the drive.
Step 2. Use static control precautions.
Step 3. Connect the Internal Interface cable to the DPI port on thedrive and then to the DPI connector on the module. See
figure 3.2.
Setting Description
0 to 99 Node address used by the module if switches are enabled.The default switch setting is 02.
Important: If the address switch is set to 00, the modulewill use the setting of CN Addr Cfg (03) for the nodeaddress. Refer to chapter 4, Configuring the ControlNetModule, for more information.
Figure 3.1 Setting the Modules Node Address
2
1
0
9
8
3
4
5
6
7
2
1
0
9
8
3
4
5
6
7
TensDigit
OnesDigit
7/22/2019 ControlNet Communications Module
17/160
7/22/2019 ControlNet Communications Module
18/160
3-4 ControlNet Communications Module
Important: All screws must be tightened since the module isgrounded through a screw.
Figure 3.3 Mounting the Module
Adapter
Drive
SP600 1-20 HP Drive
Internal Interface CableFolded Behind the Moduleand in Front of the Drive
Module
SP600 Drive25-40 HP @ 460 V
7/22/2019 ControlNet Communications Module
19/160
Installing the ControlNet Module 3-5
3.4 Connecting the Module to theNetwork
Step 1. Remove power from the drive.
Step 2. Use static control precautions.
Step 3. Route the ControlNet cable through the bottom of theSP600 drive. (See figure 3.3.)
Step 4. Connect the ControlNet cable to the module.A 1786-TPS (straight tap) is recommended.
See figure 3.4 for typical ControlNet network wiring.
!
ATTENTION: The SP600 drive may contain highvoltages that can cause injury or death. Removepower from the drive, and then verify power hasbeen discharged before installing or removing a
module. Failure to observe this precaution couldresult in severe bodily injury or loss of life.
Figure 3.4 Typical ControlNet Network Wiring
Scanner SP600 Drive SP600 Drive
7/22/2019 ControlNet Communications Module
20/160
3-6 ControlNet Communications Module
3.5 Applying Power
Step 1. Close the door or reinstall the cover on the drive. Thestatus indicators can be viewed on the front of the driveafter power has been applied.
Step 2. Apply power to the drive. The module receives its powerfrom the connected drive. When you apply power to theproduct for the first time, the status indicators should begreen or off after an initialization. If the status indicatorsare red, refer to chapter 8.
Step 3. Apply power to the master device and other devices onthe network.
!
ATTENTION: Unpredictable operation may occurif parameter settings and switch settings are notcompatible with your application. Verify thatsettings are compatible with your applicationbefore applying power to the drive. Failure toobserve these precations could result in severebodily injury of loss of life.
7/22/2019 ControlNet Communications Module
21/160
Configuring the ControlNet Module 4-1
CHAPTER4Configuring the
ControlNet Module
Chapter 4 provides instructions and information for setting theparameters in the module.
For a complete list of parameters, refer to Appendix B, ControlNetModule Parameters. For definitions of terms in this chapter, refer tothe Glossary.
4.1 Configuration Tools
The ControlNet module stores parameters and other information inits own non-volatile memory. Therefore, you must access themodule to view and edit its parameters. Table 4.1 lists the tools that
can be used to access the module parameters.
Table 4.1 Configuration Tools
Tool Refer to:
VS Utilities Software VS Utilities online help
LCD OIM Section 4.2
7/22/2019 ControlNet Communications Module
22/160
7/22/2019 ControlNet Communications Module
23/160
Configuring the ControlNet Module 4-3
4.4 Setting the I/O Configuration
The I/O configuration determines the type of data sent to the drive.This is a two-part process: enabling/disabling the data transmittedbetweeen the module and the drive, and identifying the datatransmitted between the module and the scanner.
Step 1. Enable or disable the data transmitted between themodule and the drive by setting the bits in DPI I/O Config(13). A 1enables the I/O. A 0disables the I/O.
Bit 0 is the right-most bit. In figure 4.3, it is highlighted and equals1.
Step 2. If Logic Command/Reference is enabled (default),configure the parameters in the drive to accept the LogicCommand and Reference from the module. For example,set Speed Ref A Sel (90) in an SP600 drive to Networkso that the drive uses the Reference from the module.Also, verify that Logic Source Sel (89) is configured toreceive the desired logic from the module.
Step 3. If you enabled one or more Datalinks (optional), configureparameters in the drive to determine the source anddestination of data in the Datalink(s). Also, ensure that theControlNet module is the only module using the enabledDatalink(s).
Step 4. Reset the module. Refer to section 4.7.3, Resetting theModule.
The module is ready to receive I/O from the master (i.e., scanner).You must now configure the scanner to recognize and transmit I/Oto the module. Refer to chapter 5, RSNetWorx Configuration forPLC-5C Applications, for more information.
Figure 4.3 I/O Configuration Screen on an LCD OIM
Port 5 Device
RECOMM-CNET
Parameter #: 13DPI I/O Configx x x x x x x x x x x 0 0 0 0 1Cmd/Ref b00
Bit Description
0 Logic Command/Reference (Default)
1 Datalink A
2 Datalink B
3 Datalink C
4 Datalink D
5 - 15 Not Used
7/22/2019 ControlNet Communications Module
24/160
4-4 ControlNet Communications Module
4.5 Selecting Master-Slave
A hierarchy determines the type of device with which the moduleexchanges data. In a Master-Slave hierarchy, a module exchangesdata with a scanner.
To set a Master-Slave hierarchy
Step 1. Enable the desired I/O in DPI I/O Config (13). Refer tofigure 4.3.
Step 2. Set the bits in the M-S Input (25). This parameter
determines the data transmitted from the scanner to thedrive. A 1enables the I/O. A 0disables the I/O.
Bit 0 is the right-most bit. In figure 4.4, it is highlighted and equals1.
Step 3. Set the bits in the M-S Output (26). This parameterdetermines the data transmitted from the drive to thescanner. A 1enables the I/O. A 0disables the I/O.
Bit 0 is the right-most bit. In figure 4.5, it is highlighted and equals1.
Step 4. Reset the module. Refer section 4.7.3 for this procedure.
Figure 4.4 Master-Slave Input Screen on an LCD OIM
Figure 4.5 Master-Slave Input Screen on an LCD OIM
Bit Description
0 Logic Command/Reference (Default)
1 Datalink A Input
2 Datalink B Input
3 Datalink C Input
4 Datalink D Input
5 - 15 Not Used
Port 5 Device
RECOMM-CNET
Parameter #: 25M-S Inputx x x x x x x x x x x 0 0 0 0 1Cmd/Ref b00
Bit Description
0 Status/Feedback (Default)
1 Datalink A Output
2 Datalink B Output
3 Datalink C Output
4 Datalink D Output
5 - 15 Not Used
Port 5 Device
RECOMM-CNET
Parameter #: 26M-S Outputx x x x x x x x x x x 0 0 0 0 1Status/Fdbk b00
7/22/2019 ControlNet Communications Module
25/160
Configuring the ControlNet Module 4-5
The module is ready to receive I/O from the master (i.e., scanner).You must now configure the scanner to recognize and transmit I/Oto the module. Refer to chapter 5, RSNetWorx Configuration forPLC-5C Applications.
4.6 Selecting Reference Adjust
Reference Adjust is the percent scaling factor for the Referencefrom the Network and can be set from 0-200%. This allows thedrives Reference to either match the network Reference (=100%),scale below the network Reference (100%).
4.7 Setting a Fault Action
By default, when communications are disrupted (for example, acable is disconnected) or the master is idle, the drive responds byfaulting if it is using I/O from the network.
You can configure a different response to communicationdisruptions using Comm Flt Action (10) and a different response toan idle scanner using Idle Flt Action (11).
!
ATTENTION: Comm Flt Action (10) and Idle FltAction (11)let you determine the action of the moduleand connected Host product if the controller is idle(for example, in program mode). These parameterscan be used to fault the Host product (default) orperform another function such as allow the Host tocontinue to run. Some ControlNet scanners mayoperate differently when a controller is idle, whichcould limit the Idle Fault Actions operating states.The Idle Flt Action should be verified whencommissioning the drive on the network by testingthe operation with the controller in idle.
7/22/2019 ControlNet Communications Module
26/160
7/22/2019 ControlNet Communications Module
27/160
Configuring the ControlNet Module 4-7
4.7.2 Setting the Fault Configuration Parameters
If you set Comm Flt Action (10) or Idle Flt Action (11) to Send FltCfg,the values in the parameters shown in table 4.3 are sent to thedrive after a communications fault and/or idle fault occurs. You mustset these parameters to values required by your application.
Changes to these parameters take effect immediately. A reset is notrequired.
4.7.3 Resetting the Module
Changes to switch settings or some module parameters require thatyou reset the module before the new settings take effect. You canreset the module by cycling power to the drive or by using ResetModule (9).
Table 4.3 Fault Configuration Parameters
Parameter
Number Name Description
15 Flt Cfg Logic A 16-bit value sent to the drivefor Logic Command.
16 Flt Cfg Ref A 32-bit value (0 to 4294967295)sent to the drive as a Referenceor Datalink.
Important: If the drive uses a16-bit Reference or 16-bitDatalinks, the most significantword of the value must be set tozero (0) or a fault will occur.
17 - 24 Flt Cfg x1 InFlt Cfg x2 In
!
ATTENTION: If the module is transmitting controlI/O to the drive, the drive may fault when you resetthe module. Determine how your drive will respondbefore resetting a connected module. Failure toobserve this precaution could result in bodily injuryor damage to equipment.
7/22/2019 ControlNet Communications Module
28/160
4-8 ControlNet Communications Module
Set Reset Module (9) to Reset Module. See figure 4.7.
When you enter 1 (Reset Module), the module will be immediatelyreset. When you enter 2 (Set Defaults), the module will set allmodule parameters to their factory-default settings. The value of thisparameter will be restored to 0 (Ready)after the module is reset orresetting the defaults. The module should be reset after performinga Set Defaults.
4.8 Viewing the Module Configuration
The parameters in table 4.4 provide information about how themodule is configured. You can view these parameters at any time.
Figure 4.7 Reset Screen on an LCD OIM
Port 5 Device
RECOMM-CNET
Parameter #: 9Reset Module
1Reset Module
Value Description
0 Ready (Default)
1 Reset Module
2 Set Defaults
Table 4.4 Module Configuration Status Parameters
No. Name and Description Details
01 DPI PortPort to which the module is connected. This willusually be port 5.
Default: 5Minimum: 0Maximum: 7Type: Read Only
02 DPI Data RateData rate used by the drive. This data rate is set inthe drive and the module detects it.
Default: 0 = 125 KValues 0 = 125 K 1 = 500 KType: Read Only
04 CN Addr ActThe actual network node address.
Default: 2Minimum: 1Maximum: 99Type: Read Only
06 CN Rate ActThe actual network data rate. Default: 0 = 5 MbpsValues: 0 = 5 MbpsType: Read Only
07 Ref/Fdbk SizeSize of the Reference/Feedback. The drivedetermines the size of the Reference/Feedback.
Default: 0 = 16-bitValues: 0 = 16-bit
1 = 32-bitType: Read Only
08 Datalink SizeSize of each Datalink word. The drive determinesthe size of Datalinks.
Default: 0 = 16-bitValues: 0 = 16-bit
1 = 32-bitType: Read Only
7/22/2019 ControlNet Communications Module
29/160
Configuring the ControlNet Module 4-9
14 DPI I/O ActiveI/O that the module is actively transmitting. Thevalue of this parameter will usually be equal to thevalue of parameter 13 - DPI I/O Config.
Default: xxx0 0001Bit Values: 0 = I/O disabled
1 = I/O enabledType: Read Only
Bit Definitions0 = Cmd/Ref1 = Datalink A2 = Datalink B3 = Datalink C4 = Datalink D
5 = Not Used6 = Not Used7 = Not Used
25 M-S InputConfigures the I/O Data to be transferred from thenetwork to the drive.
Default: xxx0 0001Bit Values: 0 = I/O disabled
1 = I/O enabledType: Read/WriteReset Required: Yes
Bit Definitions0 = Cmd/Ref1 = Datalink A2 = Datalink B3 = Datalink C4 = Datalink D5 = Not Used6 = Not Used7 = Not Used
26 M-S Output
Configures the I/O Data to be transferred from thedrive to the network.
Default: xxx0 0001
Bit Values: 0 = I/O disabled1 = I/O enabledType: Read/WriteReset Required: Yes
Bit Definitions0 = Cmd/Ref1 = Datalink A2 = Datalink B3 = Datalink C4 = Datalink D5 = Not Used6 = Not Used7 = Not Used
27 Ref AdjustPercent scale factor for the Reference from theNetwork.
Default: 100.00Minimum: 0.00Maximum: 200.00Type: Read/WriteReset Required: No
Table 4.4 Module Configuration Status Parameters
No. Name and Description Details
BitDefault 10000x xx
0123457 6
BitDefault 10000x xx
0123457 6
BitDefault 10000x xx
0123457 6
7/22/2019 ControlNet Communications Module
30/160
4-10 ControlNet Communications Module
7/22/2019 ControlNet Communications Module
31/160
RSNetWorx Configuration for PLC-5C Applications 5-1
CHAPTER5RSNetWorx Configuration
for PLC-5C Applications
This chapter provides information for using RSNetWorx forControlNet to configure a PLC-5C controller to communicate withthe RECOMM-CNET ControlNet module.
RSNetWorx for ControlNet is a 32-bit Windows application forconfiguring ControlNet networks. After installing and configuring themodule, RSNetWorx is used to configure the controller to recognizeand communicate with the module.
Before configuring the controller, your PC must be:
Connected to the ControlNet network using a 1784-PCC,1770-KFC, or similar device.
Running RSNetWorx with RSLinx communications.
5.1 Configuring a ControlNet Network:An Example
In this example, we will be configuring two SP600 drives to beNode 2 and Node 3 on a ControlNet network. This chapterdescribes the steps to configure a simple network as shown infigure 5.1.
Figure 5.1 Sample ControlNet Network
SP600 DriveNode 2
SP600 DriveNode 3
Scanner
7/22/2019 ControlNet Communications Module
32/160
5-2 ControlNet Communications Module
5.1.1 Installing and Registering EDS Files inRSNetWorx
This section needs to be performed only if new EDS (ElectronicData Sheet) files need to be added to RSNetWorx. The latest EDSfiles can be obtained at:http://www.reliance.com/prodserv/standriv/networks.
In the Tools menu, select EDS Wizard and click Next (figure 5.2).
Step 1. The EDS Wizard can be used to install (register) newEDS files to the RSNetWorx database, remove(unregister) EDS files from the RSNetWorx database, andchange the graphic icon used to represent the device.Select Register an EDS file(s) and click Next (figure5.3).
Figure 5.2 Rockwell Software EDS Wizard
7/22/2019 ControlNet Communications Module
33/160
RSNetWorx Configuration for PLC-5C Applications 5-3
Step 2. The EDS Wizard allows for registering single or multipleEDS files. Click Browse and locate where your EDS filesare located. In our example (figure 5.4), multiple EDS files
are registered from a directory on the hard drive.
Figure 5.3 EDS Wizard Option Screen
Figure 5.4 EDS Wizard Designation Screen
7/22/2019 ControlNet Communications Module
34/160
7/22/2019 ControlNet Communications Module
35/160
RSNetWorx Configuration for PLC-5C Applications 5-5
Step 4. The graphic images for each EDS file are displayed andcan be changed if desired. Click Next to continue (figure5.6).
Figure 5.6 EDS Wizard Change Graphic Image Screen
SP600
7/22/2019 ControlNet Communications Module
36/160
5-6 ControlNet Communications Module
Step 5. Click Next to register the EDS files (figure 5.7).
Step 6. The EDS files have been installed and registered. ClickFinish to return to the main RSNetWorx screen (figure5.8).
Figure 5.7 EDS Wizard Final Task Summary Screen
You would like to register the following device:
SP600
Figure 5.8 EDS Wizard Completion Screen
7/22/2019 ControlNet Communications Module
37/160
RSNetWorx Configuration for PLC-5C Applications 5-7
Step 7. Click on the DPI to ControlNetfolder in the Hardwarewindow to view the EDS files that have been installed tothe RSNetWorx database (figure 5.9).
5.1.2 Configuring a Network with RSNetWorx
The main screen for RSNetWorx consists of several windows:
The Network Usage View displays current and pending valuesassociated with the ControlNet network configuration.
A Hardware View displays a list of all network hardware currentlyavailable to RSNetWorx software.
The Favorites View displays a list of hardware that is frequentlyused when working with the current RSNetWorx configuration.
The Graph View shows a pictorial representation of all thehardware used in the current RSNetWorx configuration.
The Message View displays a log of messages which are listedfrom top to bottom, newest to oldest. This view may containinformational, warning, and/or error messages.
Figure 5.9 RSNetWorx for ControlNet DPI to ControlNet Folder Example
SP600
7/22/2019 ControlNet Communications Module
38/160
5-8 ControlNet Communications Module
The various views can be displayed or closed by using the Viewmenu. In figure 5.10,the Network Usage, Hardware and Graphicviews are displayed while the Message and Favorites views areclosed.
Step 1. Click the on-line icon to browse the network.
Step 2. Select the ControlNet network access method and clickOK. In this example, RSNetWorx will use the 1784-PCCto access the ControlNet network (figure 5.11).
Figure 5.10 RSNetWorx for ControlNet Screen
7/22/2019 ControlNet Communications Module
39/160
RSNetWorx Configuration for PLC-5C Applications 5-9
.
RSNetWorx starts browsing the ControlNet network for nodes andbuilds the graphic representation of the network (figure 5.12).
Figure 5.11 Sample Browse for Network Dialog Box
Figure 5.12 Sample Network Displayed in RSNetWorx
7/22/2019 ControlNet Communications Module
40/160
5-10 ControlNet Communications Module
Step 3. When the network browse is complete, a graphical view ofthe network is displayed. In this example (figure 5.13), theControlNet network consists of a PLC-5C/40C controller,two SP600 drives, and a PC using a 1784-PCC.
The symbol indicates the device shown on thenetwork does not exist in the configuration file, but it wasfound on the network. Double-click on the PLC-5C/40Cicon.
Step 4. The ControlNet configuration box displays informationabout each node (figure 5.14). Click OK.
Figure 5.13 Sample ControlNet Configuration Screen
SP600 SP600
7/22/2019 ControlNet Communications Module
41/160
7/22/2019 ControlNet Communications Module
42/160
5-12 ControlNet Communications Module
Step 6. If the On-line / Off-line Mismatch dialog box appears, clickOK to use the on-line data (figure 5.16). If prompted tosave, save the data (figure 5.17).
Important: During the save process, RSNetWorx will execute thebrowse function. Allow RSNetWorx to complete thebrowse (1-99 nodes), even if you already see the entirenetwork. Canceling the browse early may cause animproper scheduling of I/O.
Step 7. Right-click on the controllers icon (PLC-5C) and select
SCANlist Configuration. The Scanlist Configurationscreen (figure 5.18), is used to configure the controller tocommunicate with the nodes.
Figure 5.16 Online / Offline Mismatch Dialog Box
Figure 5.17 Save Data Screen
RECOMM-CNET Example.XC
7/22/2019 ControlNet Communications Module
43/160
RSNetWorx Configuration for PLC-5C Applications 5-13
..
Step 8. Enter the Integer files to be used for ControlNetcommunications (figure 5.19). In this example, N9 is theData Input File, N10 is the Data Output File, N11 is theStatus File, and N13 is the Configuration File. Double-click the Node 2 row (SP600 drive).
Figure 5.18 Scanlist Configuration Screen
SP600
SP600
7/22/2019 ControlNet Communications Module
44/160
5-14 ControlNet Communications Module
Step 9. Enter the input and output size for the node on the
network. The number of words selected depends on theI/O to be communicated with the node. In this example,the Node 2 SP600 is set for all I/O enabled which equatesto 10 words of I/O (table 5.1).
Important: The size of the Reference (Ref/Fdbk Size (7)) andDatalinks (Datalink Size (8)) will affect the size youconfigure for the network I/O. For example, 32-bitDatalinks requires twice as many words as 16-bitDatalinks. Depending on your application, theconfigured I/O size may vary.
Figure 5.19 Integer Files for ControlNet Communications Screen
Table 5.1 Input/Output Table
Words Input to PLC-5C Output to PLC-5C
0-1 Logic Command /Reference
Logic Status /Feedback
2-3 Datalinks A1 & A2 Out Datalinks A1 & A2 In
4-5 Datalinks B1 & B2 Out Datalinks B1 & B2 In
6-7 Datalinks C1 & C2 Out Datalinks C1 & C2 In
8-9 Datalinks D1 & D2 Out Datalinks D1 & D2 In
SP600
SP600
7/22/2019 ControlNet Communications Module
45/160
RSNetWorx Configuration for PLC-5C Applications 5-15
Note the values in the Input Address and Output Address fields.These are needed to develop a ladder program.
Step 10. Enter the desired Requested Packet Interval (RPI) andnote the value (figure 5.20). Ensure that this value isequal to or greater than the value that will be set later forNetwork Update Time (NUT). The Actual Packet Interval(API) may vary from the Requested Packet Interval.
Step 11. Click the Electronic Keying tab. Electronic Keying isused to determine the criteria used for the scanner toestablish a connection to a node. Select the settingsaccording to your application needs (figure 5.21).
Figure 5.20 Communicaiton Properties
SP600
7/22/2019 ControlNet Communications Module
46/160
5-16 ControlNet Communications Module
Step 12. Click the Details(figure 5.22)tab. The availability ofchoosing connection options are determined by the EDS
file for the node. Click OK.
Figure 5.21 Connection Properties: Electronic Keying Settings
Figure 5.22 Connection Properties: Details Settings
7/22/2019 ControlNet Communications Module
47/160
RSNetWorx Configuration for PLC-5C Applications 5-17
Step 13. Repeat steps 9-12 for additional nodes. When complete,all of the nodes should be mapped (figure 5.23).
Step 14. Click File/ Save to save the project (figure 5.24). Ifprompted to optimize and re-write schedule for allconnections, click OK.
Figure 5.23 ScanList Configuration: Mapped Nodes
Figure 5.24 Save Configuration Dialog Box
SP600
SP600
7/22/2019 ControlNet Communications Module
48/160
7/22/2019 ControlNet Communications Module
49/160
7/22/2019 ControlNet Communications Module
50/160
5-20 ControlNet Communications Module
Step 17. If desired, select the General tab and enter a name anddescription for the network (figure 5.28). Click OK.
Step 18. In the Network menu, select Save the properties anddownload them to the PLC. The module(s) are nowmapped on the network and the controller willcommunicate with it.
Figure 5.28 ControlNet: General Tab
RECOMM-CNET ControlNet demonstrationprogram using two SP600 demo units.
7/22/2019 ControlNet Communications Module
51/160
7/22/2019 ControlNet Communications Module
52/160
7/22/2019 ControlNet Communications Module
53/160
PLC-5C Applications 6-3
An image that uses 32-bit words for Reference and Datalinks A andD would change the I/O image in figure 6.1 as follows:
Figure 6.1 Sample I/O Image with All I/O Enabled
Controller Scanner Module SP600 DriveControlNet DPI
Output
Image
(Write)
MessageHandler
Input
Image
(Read)
0 Logic Status
1 Feedback
2 Datalink Out A1
3 Datalink Out A2
4 Datalink Out B1
5 Datalink Out B2
6 Datalink Out C1
7 Datalink Out C28 Datalink Out D1
9 Datalink Out D2
0 Logic Command
1 Reference
2 Datalink In A1
3 Datalink In A2
4 Datalink In B1
5 Datalink In B2
6 Datalink In C17 Datalink In C2
8 Datalink In D1
9 Datalink In D2
Logic Status
Feedback
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2Data Out D1
Data Out D2
Word and I/O
MessageHandler
MessageHandler
Message
Buffer
Message
Buffer
MessageHandler
Logic Command
Reference
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1Data In C2
Data In D1
Data In D2
Word I/O Word I/O
0 Logic Command/Status 8 - 11 Datalink B1/B21 Pad Word 12 - 15 Datalink C1/C2
2 - 3 Reference/Feedback 16 - 19 Datalink D1/D2
4 - 7 Datalink A1/A2
7/22/2019 ControlNet Communications Module
54/160
6-4 ControlNet Communications Module
Figure 6.2 illustrates an example of an I/O image that does not useall of the I/O data. Only the Logic Command/Reference andDatalink B are enabled. In this example, the Reference is a 32-bitword, and Datalinks are 16-bit words.
6.3 Using Logic Command/Status
When enabled, the Logic Command/Status word is always word 0 inthe I/O image. The Logic Commandis a 16-bit word of controlproduced by the scanner and consumed by the module. The LogicStatusis a 16-bit word of status produced by the module andconsumed by the scanner.
This manual contains the bit definitions for compatible productsavailable at the time of publication in Appendix D, Logic Command/Status Words. For other products, refer to their documentation.
Figure 6.2 Sample I/O Image with Only Logic/Reference and Datalink BEnabled
Controller Scanner Module SP600 Drive
ControlNet DPI
Output
Image
(Write)
Input
Image
(Read)
0 Logic Status1 Pad Word
2 Feedback (LSW)
3 Feedback (MSW)
4 Datalink Out B1
5 Datalink Out B2
0 Logic Command
1 Pad Word
2 Reference (LSW)
3 Reference (MSW)
4 Datalink In B1
5 Datalink In B2
Word and I/OLogic Command
Reference
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2
Logic Status
Feedback
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Data Out D2
LSW = Least Signicant Word (Bits 15 - 0)MSW = Most Significant Word (Bits 31 - 16)
7/22/2019 ControlNet Communications Module
55/160
PLC-5C Applications 6-5
6.4 Using Reference/Feedback
The Reference(16 bits or 32 bits) is produced by the controller andconsumed by the module. The Feedback(16 bits or 32 bits) isproduced by the module and consumed by the controller. The sizeof the Reference/Feedback is determined by the drive and displayedin Ref/Fdbk Size (07) in the module.
6.5 Using Datalinks
A Datalink is a mechanism used by SP600 drives to transfer data toand from the controller. Datalinks allow a parameter value to bechanged without using an Explicit Message.
When enabled, each Datalink consumes either two 16-bit or 32-bitwords in both the input and output image depending on its size. Thesize of Datalinks (16-bit words or 32-bit words) is determined by thedrive and displayed in Datalink Size (08) in the module.
6.5.1 Rules for Using Datalinks
Each set of Datalink parameters in an SP600 drive can be usedby only one module. If more than one module is connected to asingle drive, multiple modules must not try to use the sameDatalink.
Parameter settings in the drive determine the data passedthrough the Datalink mechanism. Refer to the documentation foryour drive.
When you use a Datalink to change a value, the value is notwritten to the Non-Volatile Storage (NVS). The value is stored involatile memory and lost when the drive loses power.
Size Valid Values In I/O Image Example
16-bit -32768 to 32767 Word 1 Figure 6.1
32-bi t -2147483648 to 2147483647 Word 2 and Word 3 Figure 6.2
7/22/2019 ControlNet Communications Module
56/160
6-6 ControlNet Communications Module
6.5.2 32-Bit Parameters using 16-Bit Datalinks
To read (and/or write) a 32-bit parameter using 16-bit Datalinks,typically both Datalinks (x1 and x2) are set to the 32-bit parameter.
For example, to read Elapsed MWh (9)in an SP600 drive, bothDatalink A1 and A2 are set to 9.Datalink A1 will contain the leastsignificant word (LSW) and Datalink A2 the most significant word(MSW). In this example, the parameter 9 value of 5.8 MWh is readas a 58in Datalink A1.
Regardless of the Datalink combination, x1 will always contain theLSW and x2 will always contain the MSW. In the following examplesPower Up Marker (242) contains a value of 88.4541 hours.
32-bit data is stored in binary as follows:
Example:
Power Up Marker (242) = 88.4541 hours
MSW = 13decimal= 1101binary= 219+ 218+ 216= 851968
LSW = 32573
851968 + 32573 = 884541
DatalinkMost/Least
Significant Word ParameterData
(decimal)
A1 LSW 9 58
A2 MSW 9 0
Datalink
Most/Least
Significant Word Parameter
Data
(decimal)
A1 LSW 242 32573
A2 - Not Used - 0 0
Datalink
Most/Least
Significant Word Parameter
Data
(decimal)
A1 - Not Used - 0 0
A2 MSW 242 13
Datalink
Most/Least
Significant Word Parameter
Data
(decimal)
A2 MSW 242 13
B1 LSW 242 32573
MSW 231through 216
LSW 215through 20
7/22/2019 ControlNet Communications Module
57/160
PLC-5C Applications 6-7
6.6 Function of the Sample Program
The program performs the following actions:
Obtains Logic Status information from the drive.
Uses the Logic Command to control the drive (for example, start,stop).
Sends a Reference to the drive and receives Feedback from thedrive.
Sends/Receives Datalink data to/from the drive.
Module Settings for the Sample Program
Nodes 2 and 3.
See Chapter 5, RSNetWorx Configuration for PLC-5CApplications.
Parameter Settings for the Sample Program
Logic Command/Status Words
These examples use the Logic Command word and Logic Statusword for SP600 drives. Refer to Appendix D, Logic Command/Status Words to view these. The definition of the bits in these wordsmay vary if you are using a different DPI product. Refer to thedocumentation for your drive.
Table 6.1 Parameter Settings for the Sample Program
Device Parameter Name Value Description
SP600 Drive
90 Speed Ref A Sel 22 Network (RECOMM-CNET)
300 Data In A1 140 Points to 140 (Accel Time 1)
301 Data In A2 142 Points to 142 (Decel Time 1)302 Data In B1 100 Points to 100 (Jog Speed)
303 Data In B2 155 Points to 155 (Stop Mode A)
310 Data Out A1 140 Points to 140 (Accel Time 1)
311 Data Out A2 142 Points to 142 (Decel Time 1)
312 Data Out B1 100 Points to 100 (Jog Speed)
313 Data Out B2 155 Points to 155 (Stop Mode A)
13 DPI I/O Cfg xxx1 1111 Enables Cmd/Ref, Datalinks A-D
RECOMM-CNET
25 M-S Input xxx1 1111 Configures the I/O Data to betransferred from the network to thedrive.
26 M-S Output xxx1 1111 Configures the I/O Data to be
transferred from the drive to thenetwork.
7/22/2019 ControlNet Communications Module
58/160
6-8 ControlNet Communications Module
6.7 Main Program (PLC-5C)
Figure 6.3 I/O Messaging
There is an operator station wired into the local rack as follows:I:000/0 Start (Normally Open Pushbutton)I:000/1 Stop (Normally Closed Pushbutton)I:000/2 Clear Faults (Normally Open Pushbutton)I:000/3 Forward / Reverse Selector SwitchI:001 Operator Speed Reference
O:000/0 Drive ReadyO:000/1 Drive ActiveO:000/2 Drive FaultedO:001 Operator Speed FeedbackThe 20-COMM-C on the PowerFlex 70 drive is mapped as follows:N9:0 Logic Status N10:0 Logic CommandN9:1 Feedback N10:1 ReferenceN9:2 Datalink A1 Out N10:2 Datalink A1 InN9:3 Datalink A2Out N10:3 Datalink A2 InN9:4 Datalink B1 Out N10:4 Datalink B1 InN9:5 Datalink B2 Out N10:5 Datalink B2 InN9:6 Datalink C1 Out N10:6 Datalink C1 InN9:7 Datalink C2 Out N10:7 Datalink C2 InN9:8 Datalink D1 Out N10:8 Datalink D1 InN9:9 Datalink D2 Out N10:9 Datalink D2 In
0000I:000
0
Operator
StartPushbutton
N10:0
1
Drive
Logic CommandSTART
0001I:000
1
OperatorStopPushbutton
N10:0
0
DriveLogic CommandSTOP
The RECOMM-CNET on the SP600 drive is mapped as follows:
7/22/2019 ControlNet Communications Module
59/160
PLC-5C Applications 6-9
Figure 6.4 I/O Messaging (Continued)
002I:000
2
OperatorClear FaultsPushbutton
N10:0
3
DriveLogic CommandCLEAR FAULTS
003I:000
3
OperatorFwd / RevSelector Switch
N10:0
4
DriveLogic CommandFORWARD
004I:000
3
OperatorFwd / RevSelector Switch
N10:0
5
DriveLogic CommandREVERSE
005N9:0
0
DriveREADYStatusBit
O:000
0
OperatorDrive ReadyStatusDisplay
006N9:0
1
DriveACTIVE
StatusBit
O:000
1
OperatorDrive Active
StatusDisplay
7/22/2019 ControlNet Communications Module
60/160
6-10 ControlNet Communications Module
Figure 6.5 I/O Messaging (Continued)
007N9:0
7
DriveFAULTEDStatusBit
O:000
2
OperatorDrive FaultedStatusDisplay
This rung moves the Speed Reference from the operator station to thedrive.
008
MOV
MoveSource I:001 0>.
Step 13. The configured node (SP600_02in this example) nowappears under the 1756-CNB module in the I/OConfiguration folder.
Step 14. Repeat the previous steps for each additional node youneed to configure.
Figure 7.13 Module Properties: My ControlNet
Figure 7.14 RSLogix: Configure Additional Nodes Screen
RSLogix 5000 - Example_RECOMM-CNET [1756-L1]
SP600_02
Controller Example_RECOMM-CNET
7/22/2019 ControlNet Communications Module
79/160
ControlLogix Applications 7-11
Step 15. In the Data Types folder, click on the Module-Definedsub-folder. When you create a module, module-defineddata types and tags are automatically created. These tagsallow you to access the Input and Output Data of themodule via the controllers ladder logic.
Step 16. Select Communications / Downloadto download theconfiguration to the controller (figure 7.16). RSLogixautomatically enters on-line mode when complete.
Figure 7.15 RSLogix 5000: Module-Defined Screen
RSLogix 5000 - Example_RECOMM-CNET [1756-L1]
Controller Example_RECOMM-CNET
RE:
RE:
RE:
SP600_02
Figure 7.16 Download to the Controller Dialong Box
Example_RECOMM-CNET
7/22/2019 ControlNet Communications Module
80/160
7-12 ControlNet Communications Module
Step 17. An Attention symbol is located next to the Node 2(SP600_02) icon in figure 7.17, which indicates theControlNet scanner needs to be configured.
Step 18. Start RSNetWorx and perform the following:
a. Click the On-line icon and browse the network.
b. Select Edits Enabled and view the messages in the
Message View for completion (figure 7.18). Theicon should disappear from the nodes in the GraphicalView.
c. Select File / Saveand save the project (figure 7.19).
d. Close RSNetworx.
This schedules the I/O that was configured in
RLSLogix 5000.
Figure 7.17 RSLogix: Attention Symbol
RSLogix 5000 - Example_RECOMM-CNET [1756-L1]
Controller Example - RECOMM-CNET
SP600_02
RE:
RE:
RE:
7/22/2019 ControlNet Communications Module
81/160
7/22/2019 ControlNet Communications Module
82/160
7-14 ControlNet Communications Module
Figure 7.19 RSLogix 5000: Example Without Attention Symbol
SP600
7/22/2019 ControlNet Communications Module
83/160
ControlLogix Applications 7-15
Step 19. The Attention symbol on the RSLogix 5000 connectiontree will disappear if the network has been configuredproperly (figure 7.20). You are now ready to develop yourladder logic program.
7.2 Function of the Sample Program
The program performs the following actions:
Obtains Logic Status information from the drive.
Uses the Logic Command to control the drive (for example, start,stop).
Sends a Reference to the drive and receives Feedback from thedrive.
Sends/Receives Datalink data to/from the drive.
Module Settings For Use With the Example
Nodes 2 and 3.
Figure 7.20 RSLogix 5000: Connection Tree Without Attention Symbol
RSLogix 5000 - Example_RECOMM-CNET [1756-L1]
Controller Example_RECOMM-CNET
SP600
RE:
RE:RE:
7/22/2019 ControlNet Communications Module
84/160
7-16 ControlNet Communications Module
Parameter Settings for the Sample Program
Logic Command/Status Words
These examples use the Logic Command word and Logic Statusword for SP600 dr ives. Refer to Appendix D, Logic Command/Status Words to view these. The definition of the bits in these wordsmay vary if you are using a different DPI product. Refer to thedocumentation for your drive.
Table 7.1 Parameter Settings for the Sample Program
Device Parameter Name Value Description
SP600 Drive
90 Speed Ref A Sel 22 Network(RECOMM-CNET)
300 Data In A1 140 Points to 140 (Accel Time 1)
301 Data In A2 142 Points to 142 (Decel Time 1)
302 Data In B1 100 Points to 100 (Jog Speed)
303 Data In B2 155 Points to 155 (Stop Mode A)
310 Data Out A1 140 Points to 140 (Accel Time 1)
311 Data Out A2 142 Points to 142 (Decel Time 1)
312 Data Out B1 100 Points to 100 (Jog Speed)
313 Data Out B2 155 Points to 155 (Stop Mode A)
13 DPI I/O Cfg xxx1 1111 Enables Cmd/Ref, Datalinks A-D
RECOMM-CNET
25 M-S Input xxx1 1111 Configures the I/O Data to betransferred from the network to thedrive.
26 M-S Output xxx1 1111 Configures the I/O Data to betransferred from the drive to thenetwork.
7/22/2019 ControlNet Communications Module
85/160
ControlLogix Applications 7-17
7.3 RSLogix 5000 Ladder Logic Program
Figure 7.21 I/O Messaging
This rung determines whether the drive is running, and sets the DriveStatusRunning tag appropriately.
DriveInputImage.Data[2].1
DriveStatusRunning
This rung determines whether the drive is running, and sets the DriveStatusRunning tag appropriately.
This rung determines whether the drive is faulted, and sets the DriveStatusFaulted tag appropriately.
DriveInputImage.Data[2].7
DriveStatusFaulted
This rung determines whether the drive is faulted, and sets the DriveStatusFaulted tag appropriately.
This rung moves the drive's frequency feedback to the DriveFeedback tag.
Copy FileSource DriveInputImage.Data[3]
Dest DriveFeedbackLength 1
COP
This rung moves the drive's frequency feedback to the DriveFeedback tag.
When the DriveCommandStart tag is true, this rung sends a start command to the drive.
DriveCommandStart
DriveOutputImage.Data[0].1
When the DriveCommandStart tag is true, this rung sends a start command to the drive.
When the DriveCommandNotStop tag is false, this rung sends a stop command to the dri ve. This rung uses anXIO input instruction because Stop pushbuttons are usually normally closed so that the equipment stops if a wirebreaks.
/DriveCommandNotStop
DriveOutputImage.Data[0].0
When the DriveCommandNotStop tag is false, this rung sends a stop command to the dri ve. This rung uses anXIO input instruction because Stop pushbuttons are usually normally closed so that the equipment stops if a wirebreaks.
When the DriveCommandJog tag is true, this rung sends a jog command to the drive.
DriveCommandJog
DriveOutputImage.Data[0].2
When the DriveCommandJog tag is true, this rung sends a jog command to the drive.
When the DriveCommandClearFault tag is true, this rung sends a clear fault command to the drive.
DriveCommandClearFault
DriveOutputImage.Data[0].3
When the DriveCommandClearFault tag is true, this rung sends a clear fault command to the drive.
7/22/2019 ControlNet Communications Module
86/160
7-18 ControlNet Communications Module
Figure 7.22 I/O Messaging (Continued)
This rung moves data from the DriveReference tag to the drive where it is used as a frequency reference.
7 Copy FileSource DriveReferenceDest DriveOutputImage.Data[1]
Length 1
COP
This rung moves data from the DriveReference tag to the drive where it is used as a frequency reference.
This rung moves Datalink data from the drive.
8 Copy FileSource DriveInputImage.Data[4]
Dest ParameterDataFromDrive[0]Length 8
COP
This rung moves Datalink data from the drive.
This rung moves Datalink data to the drive.
9 Copy FileSource ParameterDataToDrive[0]Dest DriveOutput Image.Data[2]
Length 8
COP
This rung moves Datalink data to the drive.
(End)
7/22/2019 ControlNet Communications Module
87/160
ControlLogix Applications 7-19
7.4 About Explicit Messaging
Explicit Messaging is used to transfer data that does not requirecontinuous updates. With Explicit Messaging, you can configureand monitor a slave devices parameters on the ControlNet network.
7.4.1 Performing Explicit Messages
Important: There are five basic events in the Explicit Messaging
process defined below. The details of each step willvary depending on the controller. Refer to thedocumentation for your controller.
Important:The scanner module may be integrated with thecontroller (e.g., PLC-5C).
Retrieve ParameterMessage Response
Complete ParameterMessage
Set up and sendParameter Message
Format the required data and set up the ladderlogic program to send an Explicit Messagerequest to the scanner module (download).
The scanner module transmits the ExplicitMessage Request to the slave device over theControlNet network.
The slave device transmits the Explicit MessageResponse back to the master.
The controller retrieves the Explicit MessageResponse.
The Explicit Message is complete.
Figure 7.23 Explicit Message Process
7/22/2019 ControlNet Communications Module
88/160
7-20 ControlNet Communications Module
7.4.2 Explicit Messaging Examples
A Get_Attributes_Scattered message allows for reading multipleparameters that may or may not be in sequential order (figure 7.25).
A Service Code of 4Bindicates the Get_Attributes_Scatteredservice (see page C-20, Object Specific Services).
A Class Number of 93indicates accessing the DPI ParameterObject (see page C-16, DPI Parameter Object).
An Instance Number of 0is the Class Attributes for the drive(see page C-16, Instances).
The Source identifies the service data with the request messageto send.
The Destination contains the response message to the request.
Figure 7.24 Explicit Messaging
This rung sends a CIP message to the PowerFlex 70 drive at ControlNet address 2. The data sent is obtainedfrom the MessageSendData tag. The data received is stored in the MessageReplyData tag. This MSG instructioncan be configured to send any CIP message.
0 EnableDriveMessage
ENDNER
Type - CIP GenericMessage Control DriveMessageControl ...
MSG
This rung sends a CIP message to the PowerFlex 70 drive at ControlNet address 2. The data sent is obtainedfrom the MessageSendData tag. The data received is stored in the MessageReplyData tag. This MSG instructioncan be configured to send any CIP message.
(End)
This rung sends a CIP message to the SP600 drive at ControlNet Address 2. The data sent is obtained
7/22/2019 ControlNet Communications Module
89/160
ControlLogix Applications 7-21
Get Attributes Scattered sample request and response data:
(Source) Request Data
Figure 7.25 Get_Attributes_Scattered Message Screen
0 12 Parameter Number = 12
1 0 (Pad Word)
2 0 (Pad Word)
3 11 Parameter Number = 11
4 0 (Pad Word)
5 0 (Pad Word)
6 10 Parameter Number = 10
7 0 (Pad Word)
8 0 (Pad Word)
9 9 Parameter Number = 9
10 0 (Pad Word)11 0 (Pad Word)
7/22/2019 ControlNet Communications Module
90/160
7-22 ControlNet Communications Module
(Destination) Response Data
A Set _Attributes_Scattered message is used to write multipleparameters that may or may not be in sequential order (figure 7.26).
A Service Code of 4Cindicates the Set_Attributes_Scattered
service (see page C-20, Object Specific Services).
0 12 Parameter Number = 12
1 3333 Value = 333.3VDC
2 0 (Pad Word)
3 11 Parameter Number = 11
4 0 Value = 0.0Hz
5 0 (Pad Word)
6 10 Parameter Number = 10
7 148 Value = 14.8Hrs
8
9 9 Parameter Number = 9
10 23 Value = 2.3MWh
11
Figure 7.26 Set_Attributes_Scattered Message Screen
7/22/2019 ControlNet Communications Module
91/160
ControlLogix Applications 7-23
Set_Attributes_Scattered sample request and response data:
(Source) Request Data
(Destination) Response Data
A Set_Attribute_Single message is used to write a single parameter(figure 7.27).
A Service Code of 10indicates the Set_Attribute_Single service(see page C-8, Services).
A Class Name of Findicates the Parameter Object (see pageC-6, Parameter Object).
An Instance of 45indicates the Drive Parameter 45 Attributes(see page C-6, Instances).
An Attribute of 1indicates the Parameter Value (see page C-7,Instance Attributes).
N13:0 45 Parameter Number = 45
N13:1 50 Value = 0.50HP
N13:2 0 (Pad Word)
N13:3 44 Parameter Number = 44
N13:4 1740 Value = 1740RPM
N13:5 0 (Pad Word)
N13:6 43 Parameter Number = 43N13:7 600 Value = 60.0Hz
N13:8 0 (Pad Word)
N13:9 42 Parameter Number = 42
N13:10 16 Value = 1.6Amps
N13:11 0 (Pad Word)
N14:0 45 Parameter Number = 45
N14:1 0 (Pad Word)
N14:2 0 (Pad Word)
N14:3 44 Parameter Number = 44
N14:4 0 (Pad Word)N14:5 0 (Pad Word)
N14:6 43 Parameter Number = 43
N14:7 0 (Pad Word)
N14:8 0 (Pad Word)
N14:9 42 Parameter Number = 42
N14:10 0 (Pad Word)
N14:11 0 (Pad Word)
7/22/2019 ControlNet Communications Module
92/160
7-24 ControlNet Communications Module
.
Set_Attribute_Single example (writing SP600 Parameter 45 in figure7.27 ):
Send Data
A Get_Attribute_Single message is used to read a single parameter(figure 7.28).
A Service Code of Eindicates the Get_Attribute_Single service(see page C-8, Services).
A Class Name of Findicates the Parameter Object (see pageC-6, Parameter Object).
An Instance of 45indicates the Drive Parameter 45 Attributes(see page C-6, Instances).
An Attribute of 1indicates the Parameter Value (see page C-7,Instance Attributes).
Figure 7.27 Set_Attribute_Single Message Screen
0 50 Value = 0.50HP
7/22/2019 ControlNet Communications Module
93/160
ControlLogix Applications 7-25
Get Attributes Single example (reading S600 Parameter 45 in figure7.28):
Reply Data
Figure 7.28 Get_Attributes_Single Message Screen
0 50 Value = 0.50HP
7/22/2019 ControlNet Communications Module
94/160
ControlLogix Applications 7-26
7/22/2019 ControlNet Communications Module
95/160
Troubleshooting the ControlNet Module and Network 8-1
CHAPTER8Troubleshooting the
ControlNet Module
and NetworkChapter 8 contains information for troubleshooting the ControlNetmodule and the network.
8.1 Understanding the Status Indicators
The ControlNet module has four status indicators. They can beviewed on the module or through the drive cover. (See figure 8.1.)
Number
Status
Indicator Description Refer to...
DRIVE DPI Connection Status Section 8.1.1
MS Module Status Section 8.1.2
NET A ControlNet A Status Sections 8.1.3and 8.1.4
NET B ControlNet B Status Sections 8.1.3and 8.1.4
Figure 8.1 Status Indicators (Location on Drive May Vary)
7/22/2019 ControlNet Communications Module
96/160
8-2 ControlNet Communications Module
8.1.1 DRIVE Status Indicator
Table 8.1 DRIVE Status Indicator: State Definitions
Status Cause Corrective Action
Off The module is notpowered or is notconnected properly tothe drive.
Securely connect the moduleto the drive using the ribboncable.
Apply power to the drive.FlashingRed
The module is notreceiving a pingmessage from thedrive.
Verify that cables aresecurely connected.
Cycle power to the drive.
SolidRed
The drive has refusedan I/O connection fromthe module.
Another DPI peripheralis using the same DPIport as the module.
Important:Cycle power to theproduct after making any of thefollowing corrections:
Verify that all DPI cables aresecurely connected and notdamaged. Replace cables ifnecessary.
Verify that the DPI Hostsupports Datalinks.
Configure the module andDPI Host to use a Datalink
that is not already beingused by another peripheral.
Orange The module isconnected to a productthat does not supportReliance Electric DPIcommunications.
Connect the module to aproduct that supportsReliance Electric DPIcommunications (forexample, SP600 drives).
FlashingGreen
The module isestablishing an I/Oconnection to the drive.
No action. Normal behavior ifno DPI I/O is enabled.
SolidGreen
The module is properlyconnected and iscommunicating with thedrive.
No action.
7/22/2019 ControlNet Communications Module
97/160
Troubleshooting the ControlNet Module and Network 8-3
8.1.2 MS Status Indicator
Table 8.2 MS Status Indicator: State Definitions
Status Cause Corrective Action
Off The module is notpowered.
Securely connect the moduleto the SP600 drive using theribbon cable.
Apply power to the drive andnetwork.
FlashingRed
The module hasfailed the firmwaretest.
Cycle power to the drive.Parameter settings may havebeen changed.
Clear faults in the module.
If cycling power does notcorrect the problem, theparameter settings may havebeen corrupted. Reset defaultsand reconfigure the module.
If resetting defaults does notcorrect the problem, flash themodule with the latest firmwarerelease.
Solid
Red
The module has
failed the hardwaretest.
Cycle power to the drive.
Replace the module.
FlashingGreen
The module isoperational but is nottransferring I/O data.
Place the scanner in RUNmode.
Program the controller torecognize and transmit I/O tothe module.
Configure the module for theprogram in the controller.
Normal behavior if no DPI I/Ois enabled.
SolidGreen
The module isoperational and
transferring I/O data.
No action.
7/22/2019 ControlNet Communications Module
98/160
8-4 ControlNet Communications Module
8.1.3 NET A and B Together
Table 8.3 NET A and B Together: State Definitions
Status Cause Corrective Actions
Both LEDsare off
A reset occurred orthere is no power.
Apply power to the module.
Both LEDsare steadyred
A link interfacefailed.
Check media for broken cables,loose connectors, missingterminators, etc.
Power cycle or reset themodule. If the problem persists,contact Rockwell Automationsupport.
LEDs arealternatingred/green
The module is inself-test mode.
No action required. The modulewill exit this mode when theself-test is completed.
LEDs arealternatingred/off
There is a badconfiguration.
Verify that all node addressesare unique.
Check the modulesconfiguration.
Check media for broken cables,loose connectors, missingterminators, etc.
Power cycle or reset themodule.
7/22/2019 ControlNet Communications Module
99/160
Troubleshooting the ControlNet Module and Network 8-5
8.1.4 NET A and B Independently
Table 8.4 NET A and B Independently: State Definitions
Status Cause Corrective Actions
OnechannelLED issteady off
That channel isdisabled or notsupported.
Program the network forredundant media, if required.
Onechannel
LED isflashingred/green
There is an invalidlink configuration
for that channel.
Power cycle or reset themodule.
Reset the controller.
If the problem persists, contactRockwell Automation support.
OnechannelLED isflashingred/off
The channel is notreceiving networkactivity.
Check media for broken calbes,loose connectors, missingterminators, etc.
OnechannelLED isflashinggreen/off
A temporarychannel error hasoccurred, or thechannel is in listen-only mode.
Verify the controller is presenton the network and working.
One
channelLED issteadygreen
Normal operation
for that channel.
No action required.
7/22/2019 ControlNet Communications Module
100/160
8-6 ControlNet Communications Module
8.2 Module Diagnostic Items
Table 8.5 lists diagnostic items that can be accessed usingVS Utilities software or the LCD OIM.
Table 8.5 Module Diagnostic Items
No. Event Description
1 Common LogicCmd
The current value of the Common LogicCommand being transmitted to the host.
2 Prod Logic Cmd The current value of the Product-Specific LogicCommand being transmitted to the host.
3 Reference The current value of the Product-SpecificReference being transmitted to the host.
4 Common Logic Sts The current value of the Common Logic Statusbeing received from the host.
5 Prod Logic Sts The current value of the Product-Specific Statusbeing received from the host.
6 Feedback The current value of the Product-SpecificFeedback being received from the host.
7 Datalink A1 In The current value of Datalink A1 beingtransmitted to the host. (Value of 0 if datalink isnot used).
8 Datalink A2 In The current value of Datalink A2 beingtransmitted to the host. (Value of 0 if datalink isnot used).
9 Datalink B1 In The current value of Datalink B1 beingtransmitted to the host. (Value of 0 if Datalink isnot used).
10 Datalink B2 In The current value of Datalink B2 beingtransmitted to the host. (Value of 0 if Datalink isnot used).
11 Datalink C1 In The current value of Datalink C1 beingtransmitted to the host. (Value of 0 if Datalink notused).
12 Datalink C2 In The current value of Datalink C2 beingtransmitted to the host. (Value of 0 if Datalink isnot used).
13 Datalink D1 In The current value of Datalink D1 being
transmitted to the host. (Value of 0 if Datalink isnot used).
14 Datalink D2 In The current value of Datalink D2 beingtransmitted to the host. (Value of 0 if Datalink isnot used).
15 Datalink A1 Out The current value of Datalink A1 being receivedfrom the host.
16 Datalink A2 Out The current value of Datalink A2 being receivedfrom the host.
7/22/2019 ControlNet Communications Module
101/160
Troubleshooting the ControlNet Module and Network 8-7
17 Datalink B1 Out The current value of Datalink B1 being receivedfrom the host.
18 Datalink B2 Out The current value of Datalink B2 being receivedfrom the host.
19 Datalink C1 Out The current value of Datalink C1 being receivedfrom the host.
20 Datalink C2 Out The current value of Datalink C2 being receivedfrom the host.
21 Datalink D1 Out The current value of Datalink D1 being receivedfrom the host.
22 Datalink D2 Out The current value of Datalink D2 being receivedfrom the host.
23 DPI Rx Errors The current value of the DPI Receive errorcounter.
24 DPI Rx Err Max The maximum value (since reset) of the DPIReceive error counter.
25 DPI Tx Errors The current value of the DPI Transmit errorcounter.
26 DPI Tx Err Max The maximum value (since reset) of the DPITransmit error counter.
27 Node Address SW The current value set on the Node AddressSwitches.
28 Boot Flash Count The number of times the Boot flash segment hasbeen updated in the field.
29 App Flash Count The number of tmes the Application flashsegment has been updated in the field.
30 M-S Input Size The size of data transferred from the network tothe drive.
31 M-S Output Size The size of data transferred from the drive to thenetwork.
Table 8.5 Module Diagnostic Items (Continued)
No. Event Description
7/22/2019 ControlNet Communications Module
102/160
8-8 ControlNet Communications Module
8.3 Viewing and Clearing Events
The module maintains an event queue that reports the history of itsactions. You can view the event queue using an LCD OIM orVS Utilities software.
To View and Clear Events Using an LCD OIM
Use the procedure shown in figure 8.2 to access the event queueusing the LCD OIM. Note that you must have the RECOMM-CNETmodule as the selected device to access the event queue.
Events
Many events in the event queue occur under normal operation. Ifyou encounter unexpected communications problems, the eventsmay help you or Reliance Electric personnel troubleshoot theproblem. Table 8.6 lists events that may appear in the event queue.
Figure 8.2 VIewing and Clearing Events Using an LCD OIM
Diagnostics:
Device VersionOIM Version
View Event Queue
P0: RECOMM-CNET
Stopped Auto
Main Menu
Diagnostics
EvtQ# : E# xxxxxOnline @ 500kbps
1
Clrqu
Highl ight Diagnostics icon
Highl ight i temMoni to r Lang
>>
Press F2 key toclear event queue
Table 8.6 Event Codes and Descriptions
Code Event Description
1 No Event Empty event queue entry.
2 DPI Bus Off Flt A bus-off condition was detected on DPI. Thisevent may be caused by loose or brokencables or by noise.
3 Ping Time Flt A ping message was not received on DPIwithin the specified time.
4 Port ID Flt The module is not connected to a correct porton a DPI product.
5 Port Change Flt The DPI port changed.
6 Host Sent Reset The DPI product issued this because it wasreset.
7 EEPROM Sum Flt The EEPROM in the module is corrupt.
8 Online @ 125kbps The module and DPI product arecommunicating at 125 kbps.
7/22/2019 ControlNet Communications Module
103/160
Troubleshooting the ControlNet Module and Network 8-9
9 Online @ 500kbps The module and DPI product arecommunicating at 500 kbps.
10 Bad Host Flt The module was connected to an incompatibleproduct.
11 Dup. Port Flt Another peripheral with the same port numberis already in use.
12 Type 0 Login The module has logged in for type 0 control.
13 Type 0 Time Flt The module has not received a type 0 status
message within the specified time.14 DL Login The module has logged into a datalink.
15 DL Reject Flt The host rejected an attempt to log in to adatalink because the datalink is not supportedor is used by another peripheral.
16 DL Time Flt The module has not received a datalinkmessage within the specified time.
17 Reserved Not used.
18 Control Disabled The module has sent a Soft Control Disablecommand to the DPI product.
19 Control Enabled The module has sent a Soft Control Enablecommand to the DPI product.
20 Message Timeout A Client-Server message sent by theperipheral was not completed.
21 Flt Cfg Error Flt Cfg for the Reference or Data links is set toa value greater than 65535 and the drive is setfor 16-bit.
22 App CRC Flt Start-up sequence detected corruptapplication firmware.
23 App Updated Start-up sequence detected new applicationfirmware in candidate area.
24 CN Comm Flt The module detected a fault condition on theControlNet network.
25 CN Sent Reset The peripheral received a reset from thenetwork.
26 CN Close Fit An I/O connection from the network to theperipheral was closed.
27 CN Idle Flt The peripheral is receiving idlepackets fromthe network.
28 CN Open An I/O connection to the peripheral from thenetwork has been opened.
29 Net Timeout Flt An I/O connection from the network to theperipheral has timed out.
30 PCCC IO Close The device sending PCCC Control messagesto the peripheral has sent the PCCC ControlTimeout to a value of zero.
Table 8.6 Event Codes and Descriptions
Code Event Description
7/22/2019 ControlNet Communications Module
104/160
Troubleshooting the ControlNet Module and Network 8-10
31 PCCC IO Open The per ipheral has begun receiving PCCCControl messages (the PCCC Control Timeoutwas previously set to a non-zero value).
32 PCCC IO Time Flt The peripheral has not received a PCCCControl Message for longer than the PCCCControl Timeout.
33 Watchdog T/O Flt The software watchdog detects a failure.
34 EEPROM Init Start-up sequence detected a blank EEPROM
map revision. Intended to happen in factorytest.
35 DPI Fault Clear The user cleared a fault in the Host.
36 Normal Startup Peripheral completes a normal start up.
37 Manual Reset The user reset the module.
Table 8.6 Event Codes and Descriptions
Code Event Description
7/22/2019 ControlNet Communications Module
105/160
Technical Specifications A-1
APPENDIXATechnical
Specifications
Communications
Electrical
Mechanical
Environmental
Regulatory Compliance
Network
Protocol
Data Rates
ControlNet
5M baud
Drive
Protocol
Data Rates
DPI
125 Kbps or 500 Kbps
Consumption
Drive
Network
275 mA at 5 VDC supplied through the drive
Dimensions
Height
Length
Width
16 mm (0.624 in)
103 mm (4 in)
80 mm (3.125 in)
Weight 85 g (3 oz)
Temperature
Operating
Storage
-10 to +50C (14 to 149F)
-40 to +85C (-40 to 185F)
Relative Humidity 5 to 95% non-condensing
UL 508C and CUL
CE EN61800-3
7/22/2019 ControlNet Communications Module
106/160
A-2 ControlNet Communications Module
7/22/2019 ControlNet Communications Module
107/160
ControlNet Module Parameters B-1
APPENDIXBControlNet Module
Parameters
The following information is provided for each ControlNet moduleparameter along with its description:
About Parameter Numbers
The parameters in the ControlNet module are numberedsequentially. However, depending on the configuration tool used,they may have different numbers.
Parameter Number: Unique number assigned to eachparameter.
Parameter Name: Unique name assigned to eachparameter.
Range: Predefined parameter limits orselections.
Default: Factory default setting.
Type: Read Only or Read/Write
Reset Required: Module must be reset before parametervalue is recognized.
Configuration Tool Numbering Schemes
VS Utilities
OIM
The module parameters begin with
parameter 1. For example, parameter 01
(DPI Port) is parameter 1 as indicated by
the manual. Explicit Messaging The module parameters are appended to
the list of drive parameters. For example,
with a drive with 300 parameters,
parameter 01 (DPI Port) is parameter 301.
7/22/2019 ControlNet Communications Module
108/160
B-2 ControlNet Communications Module
Port to which the module is connected. This will usually be port 5.
Data rate used by the drive. This data rate is set in the drive and themodule detects it.
Configures the network if the Node Address Switches are set to00.Updates CN Addr Act (4) after reset.
The actual network node address.
1 DPI Port
Range: 0 to 7
Default: 5
Type: Read Only
Reset Required: N/A
2 DPI Data RateRange: 0 = 125 Kbps
1 = 500 Kbps
Default: 0 = 125 Kbps
Type: Read Only
Reset Required: N/A
3 CN Addr Cfg
Range: 1 to 99
Default: 2
Type: Read/Write
Reset Required: Yes
4 CN Addr Actual
Range: 1 to 99
Default: 2
Type: Read Only
Reset Required: N/A
7/22/2019 ControlNet Communications Module
109/160
ControlNet Module Parameters B-3
Configures the Network Data Rate. Updates CN Rate Act (6) after areset.
The actual Network Data Rate.
The size of the Reference/Feedback. The drive determines the sizeof the Reference/Feedback.
The size of each Datalink word. The drive determines the size ofDatalinks.
5 CN Rate Cfg
Range: 0 = 5 Mbps
Default: 0 = 5 Mbps
Type: Read/Write
Reset Required: Yes
6 CN Rate Act
Range: 0 = 5 Mbps
Default: 0 = 5 Mbps
Type: Read Only
Reset Required: N/A
7 Ref/Fdbk Size
Range: 0 = 16-bit1 = 32-bit
Default: 0 = 16-bit
Type: Read Only
Reset Required: N/A
8 Datalink Size
Range: 0 = 16-bit1 = 32-bit
Default: 0 = 16-bit
Type: Read Only
Reset Required: N/A
7/22/2019 ControlNet Communications Module
110/160
B-4 ControlNet Communications Module
No action if set to Ready.Resets the module if set to ResetModule.Restores the module to factory default settings if set toSet Defaults.This parameter is a command. It will be reset to0 = Readyafter the command has been performed.
Sets the action that the module takes if the module detects anetwork failure. This setting is effective only if I/O that controls thedrive is transmitted though the module.
9 Reset Module
Range: 0 = Ready (No action)1 = Reset Module2 = Set Defaults (Restores module to factory-default
settings)
Default: 0 = Ready
Type: Read/Write
Reset Required: No
!
ATTENTION: If the module is transmitting I/O thatcontrols the drive, the drive may fault when you resetthe module. Determine how your drive will respondbefore resetting a connected module. Failure toobserve this precaution could result in bodily injuryor damage to equipment.
10 Comm Flt Action
Range: 0 = Fault
1 = Stop2 = Zero Data3 = Hold Last4 = Send Flt Cfg
Default: 0 = Fault
Type: Read/Write
Reset Required: No
!
ATTENTION: Comm Flt Action (10) lets youdetermine the action the module and connected
drive if communications are disrupted. By default,this parameter faults the drive. You can set thisparameter so that the drive continues to run. Takeprecautions to ensure that the setting of thisparameter does not create a hazard of injury orequipment damage. Failure to observe thisprecaution could result in bodily injury or damage toequipment.
7/22/2019 ControlNet Communications Module
111/160
ControlNet Module Parameters B-5
Sets the action that the module takes if the module detects that thePLC is set to program mode. This setting is effective only if the I/Othat controls the drive is transmitted through the module.
Indicates either the Node Address Switches or CN Addr Cfg (03) inthe module are controlling the node address.
11 Idle Flt Action
Range: 0 = Fault1 = Stop2 = Zero Data3 = Hold Last4 = Send Flt Cfg
Default: 0 = Fault
Type: Read/Write
Reset Required: No
!
ATTENTION: Idle Flt Action (11) lets you determinethe action of the module and connected Host productif the controller is idle (e.g., in program mode). Thisparameter can be used to fault the Host product(default) or to perform another function such as allowthe Host to continue to run. Ensure that the settingof this parameter does not create a hazard of injuryor equipment damage. Failure to observe thisprecaution could result in bodily injury or damage toequipment.
12 CN Active Cfg
Range: 0 = Switches1 = EEPROM
Default: 0 = Switches
Type: Read Only
Reset Required: N/A
7/22/2019 ControlNet Communications Module
112/160
B-6 ControlNet Communications Module
Configures the I/O that is transferred through the module.
I/O that the module is actively transmitting. The value of thisparameter will usually be equal to the value of DPI I/O Cfg (13).
13 DPI I/O Cfg
Range: See figure B.1.
Default: xxx0 0001
Type: Read/Write
Reset Required: Yes
Figure B.1 DPI I/O Config (13)
000 10xxx01234567
1= I/O Enabled0= I/O Disabledx =Not Used
Cmd/R
ef
DatalinkA
DatalinkB