cooling plant
A cooling plant belongs to the main units of an air conditioning system. Without a cooling plant it will be impossible to meet a comfort inside climate when cooling is needed. A cooling plant consist of four main components “Compressor, condenser, expansion valve and evaporator”. The diagram below shows the complete cooling circuit with all the main component as well the phase of the refrigerant in each stage of the circuit.
The selection of a cooling plant depends on several factors like the required cooling capacity, the refrigerant type and cooling medium.
There are two groups of cooling plants:- Direct expansion (DX) unit: A DX unit is mostly located near by the air handling unit to avoid long refrigerant pipe through the ship. The cooling coil inside the air handling unit operates as evaporator of the cooling plant.- Chilled water unit (CWU): are used for ships where there is a long distance between the air handling unit and the cooling plant or with several air handling units. The chilled water (mostly with a percentage of glycol) will be used as cooling medium between the evaporator and the cooling coil inside the air handling unit. An advantage of this system is that it avoids the long refrigerant pipes filled with Freon on board.
compressor
The compressor is a mechanical device that increase the pressure of the refrigerant gas by reducing the volume. There are four kind of compressors:1. Reciprocating compressor2. Scroll compressor3. Screw compressor4. Centrifugal compressor
Semi hermetic screw compressor Hermetic scroll compressor
Which kind of compressor is needed, depends on the needed capacity. Scroll and vacuum compressors are used for low compressor capacity and screw and centrifugal compressors are used for high compressor capacity. The most compressors are available in hermetic type, semi-hermetic type or open type.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
condenser
A condenser is a heat exchanger that extract the heat of the compressed refrigerant by transferring it to a cooling medium (air/ water).In the condenser the refrigerant transforms from its vapor to its liquid state.
There are two different groups of condensers:• Air cooled condenser• Water cooled condenser
Air cooled condenser Water cooled condenser (shell/tube)
The water condensers can be divided in two types shell/tube or plate heat exchanger.
Plate heat exchanger shell/tube condenser
The size of the condenser depends on the available cooling medium (water or air) and the temperature of the cooling medium.
Expansion valve
The expansion valve removes pressure from the liquid refrigerant to allow expansion (change the state from liquid to a vapor) in the evaporator. The liquid refrigerant under high pressure entering the expansion valve is warm, the liquid refrigerant leaving the expansion valve is quite cold.
The orifice within the valve does not remove heat, but only reduces pres-sure. Heat molecules contained in the liquid refrigerant are thus allowed to spread as the refrigerant moves out of the orifice. Under a greatly reduced pressure the liquid refrigerant is at its coldest as it leaves the expansion valve and enters the evaporator. The expansion valve controls the amount of the refrigerant that flow into the evaporator.There are two kind of expansion valve:
Thermostatic expansion valve Electronic expansion valve
Evaporators
An evaporator is used to vaporize liquid into its vapor state. It is one of the main components in an air conditioning system. The evaporator is used as heat exchanger to allow a compressed refrigerant to evaporate from liquid to gas while absorbing the heat from the surroundings and transfer its cooling capacity to the surrounding medium (air or water).
There are three types of evaporators:• Shell and tube evaporator• Plate heat exchanger• Finned pipe heat exchanger
Shell/tube evaporator DX Cooling coil evaporator
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
condensing units 50Hz
HHSSc - SERiE
*Power supply: 3 ~ 400 V / 50 H *Sea water temperature: 320C *Evaporating temperature (mean): 50C
HHSFc - SERiE
*Power supply: 3 ~ 400 V / 50 H *Fresh water temperature: 380C *Evaporating temperature (mean): 50C
Maximum allowable line length is 10m with a maximum height difference of 3m for each unit. Units are designed according EN 378-2008
and delivered with 1 bar(e) dry-nitrogen transport pressure. Units shall be mounted longitudinal with the vessel. When mounting transversal the optional liquid-manifold shall be installed.
TypeQ0 [kW]
R407C / R134a
Pe [kW]
absorbed
Imax [A] Volume flow
[m3/h]
Dimensions
L x W x H [m]
Weight
[kg]
HHSSC1 30 / 20 9 / 5 20 6 1.22 x 0.52 x 0.75 250
HHSSC2 65 / 45 18 / 12 43 8 1.68 x 0.57 x 0.86 350
HHSSC3 95 / 65 26 / 14 60 12 1.71 x 0.61 x 1.10 550
HHSSC4 135 / 95 39 / 22 90 19 1.71 x 0.61 x 1.10 600
HHSSC5 170 / 115 45 / 26 103 20 1.76 x 0.66 x 1.27 850
HHSSC6 220 / 145 60 / 36 135 27 1.76 x 0.66 x 1.27 870
TypeQ0 [kW]
R407C / R134a
Pe [kW]
absorbed
Imax [A] Volume flow
[m3/h]
Dimensions
L x W x H [m]
Weight
[kg]
HHSFC1 30 / 20 9 / 5 20 10 1.18 x 0.52 x 0.75 250
HHSFC2 65 / 42 18 / 12 43 15 1.64 x 0.57 x 0.86 350
HHSFC3 95 / 63 26 / 15 60 22 1.69 x 0.61 x 1.10 550
HHSFC4 135 / 91 39 / 23 90 33 1.69 x 0.61 x 1.10 600
HHSFC5 170 / 110 45 / 28 103 36 1.76 x 0.66 x 1.27 850
HHSFC6 220 / 140 60 / 38 135 48 1.76 x 0.66 x 1.27 870
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
condensing units 60Hz
HHSSc - SERiE
*Power supply: 3 ~ 400 V / 60 H *Sea water temperature: 320C *Evaporating temperature (mean): 50C
HHSFc - SERiE
*Power supply: 3 ~ 400 V / 60 H *Fresh water temperature: 380C *Evaporating temperature (mean): 50C
Maximum allowable line length is 10m with a maximum height difference of 3m for each unit. Units are designed according EN 378-2008
and delivered with 1 bar(e) dry-nitrogen transport pressure. Units shall be mounted longitudinal with the vessel. When mounting transversal the optional liquid-manifold shall be installed.
TypeQ0 [kW]
R407C / R134a
Pe [kW]
absorbed
Imax [A] Volume flow
[m3/h]
Dimensions
L x W x H [m]
Weight
[kg]
HHSSC1 37 / 25 10 / 6 20 10 1.22 x 0.52 x 0.75 250
HHSSC2 78 / 54 21 / 14 43 19 1.68 x 0.57 x 0.86 350
HHSSC3 114 / 80 31 / 17 60 30 1.71 x 0.61 x 1.10 550
HHSSC4 164 / 116 47 / 26 90 45 1.71 x 0.61 x 1.10 600
HHSSC5 205 / 138 54 / 31 103 45 1.76 x 0.66 x 1.27 850
HHSSC6 265 / 178 71 / 43 135 60 1.76 x 0.66 x 1.27 870
TypeQ0 [kW]
R407C / R134a
Pe [kW]
absorbed
Imax [A] Volume flow
[m3/h]
Dimensions
L x W x H [m]
Weight
[kg]
HHSFC1 37 / 24 10 / 6 20 10 1.18 x 0.52 x 0.75 250
HHSFC2 78 / 51 21 / 14 43 25 1.64 x 0.57 x 0.86 350
HHSFC3 114 / 76 31 / 18 60 38 1.69 x 0.61 x 1.10 550
HHSFC4 164 / 110 47 / 28 90 55 1.69 x 0.61 x 1.10 600
HHSFC5 205 / 132 54 / 33 103 65 1.76 x 0.66 x 1.27 850
HHSFC6 265 / 170 71 / 45 135 90 1.76 x 0.66 x 1.27 870
chilled water units 50Hz
advantages:• High quality assured;• Standard Capacity control 25%, 50%, 75% and 100%;• Refrigerant 134a, [complies with the most ship classifications];• All common power supplies available on request; • Paint color standard RAL6011 other colors available on request;• Easy accessible for maintenance and cleaning;• Fully ventilated electric switch board;• Easy cleanable condensers; • Two fully independent circuit.
optional:• Step less capacity control 25% till 100%;• All other power supplies available on request;• Troubleshooting on distance. HHScHSc - SERiE
*Power supply: 3 ~ 400 V / 50 H *Sea water temperature: 320C *Evaporating temperature (mean): 10C
HHScHFc - SERiE
*Power supply: 3 ~ 400 V / 50 H *Fresh water temperature: 380C *Evaporating temperature (mean): 10C
TypeQ0 [kW]
R134a 50/60 Hz
Pe [kW]
absorbed
Imax [A] Volume flow
[m3/h] condenser
Volume flow
[m3/h] chiller
Dimensions
L x W x H [m]
Weight
[kg]
HHSCHSC1 190 2 x 32 2 x 92 2 x 16,5 27,8 3.20 x 1.00 x 1.66 1960
HHSCHSC2 270 2 x 46,4 2 x 117 2 x 24,9 39,5 3.30 x 1.20 x 1.66 3050
HHSCHSC3 330 2 x 54,5 2 x 147 2 x 25,8 48,3 3.70 x 1.20 x 1.66 3300
HHSCHSC4 420 2 x 67,6 2 x 169 2 x 30,2 61,5 3.70 x 1.25 x 1.76 3690
HHSCHSC5 570 2 x 92,2 2 x 258 2 x 46,6 83,4 3.70 x 1.40 x 2.00 4470
HHSCHSC6 660 2 x 102,6 2 x 288 2 x 50,2 96,6 3.70 x 1.60 x 2.10 4530
HHSCHSC7 880 2 x 138,9 2 x 384 2 x 67,7 128,8 3,75 x 1,65 x 2,20 6300
HHSCHSC8 1100 2 x 172 2 x 465 2 x 93,9 161 4,50 x 1,75 x 2x25 7000
TypeQ0 [kW]
R134a 50/60 Hz
Pe [kW]
absorbed
Imax [A] Volume flow
[m3/h] condenser
Volume flow
[m3/h] chiller
Dimensions
L x W x H [m]
Weight
[kg]
HHSCHFC1 190 2 x 32 2 x 92 2 x 14,5 27,8 3.20 x 1.00 x 1.66 1960
HHSCHFC2 270 2 x 46,4 2 x 117 2 x 20 39,5 3.30 x 1.20 x 1.66 3050
HHSCHFC3 330 2 x 54,5 2 x 147 2 x 22,8 48,3 3.30 x 1.20 x 1.66 3200
HHSCHFC4 420 2 x 67,6 2 x 169 2 x 26,7 61,5 3.48 x 1.25 x 1.76 3600
HHSCHFC5 570 2 x 92,2 2 x 258 2 x 41,2 83,4 3.49 x 1.40 x 2.00 4450
HHSCHFC6 660 2 x 102,6 2 x 288 2 x 44,3 96,6 3.49 x 1.40 x 2.10 4450
HHSCHFC7 880 2 x 138,9 2 x 384 2 x 63,9 128,8 4,06 x 1,60 x 2,20 6210
HHSCHFC8 1100 2 x 172 2 x 465 2 x 82,4 161 4,30 x 1,60 x 2,25 6900
Design note
Chilled water IN/OUTLET temperature 12/6 0CUnits are designed according EN 378-2008 and delivered with complete refrigerant charge.Units can be delivered with 1 Bar(e) dry-nitrogen transport pressure.
chilled water units 50Hz
advantages:• High quality assured;• Standard Capacity control 25%, 50%, 75% and 100%;• Refrigerant 134a, [complies with the most ship classifications];• All common power supplies available on request; • Paint color standard RAL6011 other colors available on request;• Easy accessible for maintenance and cleaning;• Fully ventilated electric switch board;• Easy cleanable condensers; • Two fully independent circuit.
optional:• Step less capacity control 25% till 100%;• All other power supplies available on request;• Troubleshooting on distance. HHScHSc - SERiE
*Power supply: 3 ~ 400 V / 50 H *Sea water temperature: 320C *Evaporating temperature (mean): 10C
HHScHFc - SERiE
*Power supply: 3 ~ 400 V / 50 H *Fresh water temperature: 380C *Evaporating temperature (mean): 10C
chilled water units 60Hz
advantages:• High quality assured;• Standard Capacity control 25%, 50%, 75% and 100%;• Refrigerant 134a, [complies with the most ship classifications];• All common power supplies available on request; • Paint color standard RAL6011 other colors available on request;• Easy accessible for maintenance and cleaning;• Fully ventilated electric switch board;• Easy cleanable condensers; • Two fully independent circuit.
optional:• Step less capacity control 25% till 100%;• All other power supplies available on request;• Troubleshooting on distance. HHScHSc - SERiE
*Power supply: 3 ~ 400 V / 60 H *Sea water temperature: 320C *Evaporating temperature (mean): 10C
HHScHFc - SERiE
*Power supply: 3 ~ 400 V / 60 H *Fresh water temperature: 380C *Evaporating temperature (mean): 10C
Design note
Chilled water IN/OUTLET temperature 12/6 0CUnits are designed according EN 378-2008 and delivered with complete refrigerant charge.Units can be delivered with 1 Bar(e) dry-nitrogen transport pressure.
TypeQ0 [kW]
R134a 50/60 Hz
Pe [kW]
absorbed
Imax [A] Volume flow
[m3/h] condenser
Volume flow
[m3/h] chiller
Dimensions
L x W x H [m]
Weight
[kg]
HHSCHSC1 200 2 x 38,5 2 x 101 2 x 17,4 29,4 3,20 x 1,00 x 1,66 1960
HHSCHSC2 300 2 x 55,8 2 x 128 2 x 29 44 3,30 x 1,20 x 1.66 3050
HHSCHSC3 400 2 x 65,6 2 x 161 2 x 31,3 58,7 3.70 x 1,20 x 1.66 3300
HHSCHSC4 500 2 x 84,4 2 x 202 2 x 35,9 73,4 3,70 x 1,25 x 1,76 3690
HHSCHSC5 650 2 x 110 2 x 282 2 x 53,3 95,4 3,70 x 1,40 x 2,00 4470
HHSCHSC6 800 2 x 123,5 2 x 316 2 x 60,8 117,4 3,70 x 1,60 x 2,10 4530
HHSCHSC7 1000 2 x 167,2 2 x 420 2 x 82,3 146,8 3,75 x 1,65 x 2,20 6300
HHSCHSC8 1200 2 x 206,9 2 x 509 2 x 102,6 176,2 4,50 x 1,75 x 2,25 7000
TypeQ0 [kW]
R134a 50/60 Hz
Pe [kW]
absorbed
Imax [A] Volume flow
[m3/h] condenser
Volume flow
[m3/h] chiller
Dimensions
L x W x H [m]
Weight
[kg]
HHSCHFC1 200 2 x 38,5 2 x 101 2 x 16,3 29,4 3,20 x 1,00 x 1.66 1960
HHSCHFC2 300 2 x 55,8 2 x 128 2 x 22,5 44 3,30 x 1,20 x 1,66 3050
HHSCHFC3 400 2 x 65,6 2 x 161 2 x 27,6 58,7 3,30 x 1,20 x 1.66 3200
HHSCHFC4 500 2 x 84,4 2 x 202 2 x 31,7 73,4 3,48 x 1,25 x 1.76 3600
HHSCHFC5 650 2 x 110 2 x 282 2 x 47,1 95,4 3,49 x 1,40 x 2,00 4450
HHSCHFC6 800 2 x 123,5 2 x 316 2 x 53,7 117,4 3,49 x 1,40 x 2,10 4450
HHSCHFC7 1000 2 x 167,2 2 x 420 2 x 72,6 146,8 4,06 x 1,60 x 2,20 6210
HHSCHFC8 1200 2 x 206,9 2 x 509 2 x 90,5 176,2 4,30 x 1,60 x 2,25 6900
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
50 / 60 Hz HHCHSC Sea water serie*
TypeQ0 [kW]
R410a
Pe [kW]
absorbed
Pe [kW]
Option heating
Imax [A] Volume flow
[m3/h condenser]
Volume flow
[m3/h chiller]
Dimensions
L x W x H [m]
Weight
[kg]
HHCHSC1 90 30 20 72 2 x 10 13,5 1.52 x 0.72 x 1.55 990
HHCHSC2 120 40 30 95 2 x 13 17x5 1.52 x 0.72 x 1.55 1010
HHCHSC3 150 50 40 119 2 x 16 22 1.52 x 0.72 x 1.55 1190
HHCHSC4 180 60 40 145 2 x 20 26,5 1.75 x 0.79 x 1.69 1360
HHCHSC5 240 80 60 190 2 x 23 35,5 1.75 x 0.79 x 1.69 1480
Yacht chilled water units
Design notes:• Sea water temperature: 320C evaporating temperature (dew) 20C - Chilled water IN/OUTLET temperature 6 / 120C; • Power supply: 3 x 400 / 440V 50/60 Hz other voltages on request;• Units are designed according EN 378-2008 and delivered with complete refrigerant charge;• Units can be delivered with 1 Bar(e) dry-nitrogen transport pressure.
Heinen & Hopman standard yacht chillers range 90 - 240 kW
advantages:• High quality assured;• Standard capacity control 25% till 100% [step less];• Low starting current due to the use of frequency controllers;• Refrigerant R410a;• Design based upon Heinen & Hopman successful worldwide deployed Yacht chillers;• All common power supplies available on request;• Paint color fully customizable;• Easy accessible for maintenance and cleaning;• Fully conditioned electric switch board;• Easy cleanable condensers;• Two fully independent cooling circuits;• Troubleshooting on distance.
www.heinenhopman.com
Heinen & Hopman encourages a more
sustainable world. By providing eco-friendly solutions and serviceswe offer our clients
the option of reducing energy consumption
and thus co2 emissions. Visit
greenmanifest.info for more information.
BrazilT: +5521 3587 4241/4244E: [email protected]
France - la ciotatT: +334 4204 8685E: [email protected]
France - grasseT: +336 3090 7786 E: [email protected]
germanyT:+49 4073 1680E: [email protected]
indiaT: +9133 6499 1293E: [email protected]
italyT: +3901 8745 7970E: [email protected]
the netherlands (HQ)T: +313 3299 2500E: [email protected]
the netherlands (Rotterdam)T: +317 8890 8050E: [email protected]
norwayT: +47 6919 0900E: [email protected]
peoples Republic of chinaT: +8621 3253 2896E: [email protected]
peoples Republic of chinaT: +86 510 8528 1763E: [email protected]
polandT: +489 1433 1800E: [email protected]
RomaniaT: +402 3644 8222E: [email protected]
RussiaT: +7 (4012) 308 801E: [email protected]
SingaporeT: +65 6897 7879E: [email protected]
South KoreaT: +8270 4901 0000E: [email protected]
SpainT: +349 3225 9668E: [email protected]
SwedenT: +46 3121 7500E: [email protected]
turkeyT: +9021 6493 8118E: [email protected]
UaE (abu Dhabi) T:+971 2550 4147E: [email protected]
UaE (Dubai)T: +971 4263 5453E: [email protected]
USa - Fort lauderdale, FloridaT: +195 4463 0110E: [email protected]
USa - Houma, louisiana T: +198 5876 7989E: [email protected]