Cooling Tower Improvement Study Using PEPSE EPRI Heat Rate Improvement Conference February 5-7, 2013 Justin Strupp Scientech, a business unit of Curtiss-Wright Flow Control Scott Prokopetz SaskPower
Transcript
Page 1: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Cooling Tower Improvement Study Using PEPSE

EPRI Heat Rate Improvement ConferenceFebruary 5-7, 2013

Justin StruppScientech, a business unit of Curtiss-Wright Flow Control

Scott ProkopetzSaskPower

Page 2: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Shand Power Station

Single-Unit Lignite Coal PlantEstevan, Saskatchewan, CanadaCommissioned in 1992 305 MW GrossB&W BoilerHitachi Steam Turbine

Page 3: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Cooling System

Page 4: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Main Cooling Towers

OEM – Ceramic Cooling Tower, installed in 1992 Induced Draft, Counterflow, Clay Tile Fill

Page 5: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Auxiliary Cooling Towers

OEM – Psychrometric Systems Inc, installed 2000 Induced Draft, Counterflow, PVC Fill

Page 6: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Problem

Since construction, Shand Power Station has had historically higher than design condenser backpressure Auxiliary towers were added in 2000 but the

problem remainedCauses

– Cooling Water (CW) flow slightly lower than design 92 – 95% design flow to condenser

– Cooling Towers performing lower than design 70 – 80% capability

– Condenser cleanliness slightly lower than design average 80% (design 90%)

Page 7: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Effects of Problem

Forced Plant De-rates– In the summer, back pressure increases to a point near

the maximum allowable for the turbine– MW output must be lowered to stay within the back

pressure limits of the turbine– De-rates cost $800,000 per year in replacement energy

costs

Increased Heat Rate– As back pressure increases, the boiler must fire harder– Heat rate effect has not been quantified

Page 8: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Possible Improvement Areas

Increase cooling water flow Increase air flow to the main cooling towersAdditional cooling tower cellsUpgrade water distribution system in main towersUpgrade fill in main towers

First three can be modeled with PEPSE

Page 9: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Modeling of Possible Improvement Areas

CW Flow– 15% under design flow– 30% over design flow

Main Cooling Tower Air Flow– 15% under design flow– 25% over design flow

Adding cooling tower cells– One cell to auxiliary cooling tower– Two cells to auxiliary cooling tower– One cell to main cooling tower– Two cells to main cooling tower

Page 10: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Turbine Cycle Modeling

Turbine Cycle– Heat Balance Tuned– Plant Data– Design mode Condenser

Page 11: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Cooling Tower Modeling

Cooling Towers – Main and AuxiliaryCooling Tower Performance CurvesCooling Tower Tuning

Page 12: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Merged Model

Page 13: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Turbine Cycle Assumptions

MCR Main Steam and Reheat Conditions Feedwater Heater TTD and DCA ConstantOther ConditionsDesign Condenser Cleanliness FactorDe-rate Conditions

– LP Turbine Exhaust above 50°C– Main steam flow reduced

Page 14: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Cooling Tower Assumptions

Five wet-bulb temperatures – 24°C, 23°C, 21°C, 18°C, and 17°C– 50% Humidity– 94.5 kPa Pressure

Cooling Tower ConditionsCCCW System

Page 15: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

CW Flow Calculations

Change the CW flow from 85% to 130% of design CW Flow

Page 16: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

CW Flow Results - MW

265

270

275

280

285

290

295

300

85 90 95 100 105 110 115 120 125 130

Gro

ss O

utpu

t (M

W)

CW Flow (%)

Gross MW Output for CW Flow Change

24°C21°C17°C

Page 17: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

CW Flow Results - HR

1019010200102101022010230102401025010260102701028010290

85 90 95 100 105 110 115 120 125 130

GU

HR

(kJ/

kWh)

CW Flow (%)

Gross Unit HR for CW Flow Change

24°C21°C17°C

Page 18: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Fan Air Flow Calculations

Main Cooling Tower Only Fan Affinity Law

100150200250300350400450500

1.5E+07

1.7E+07

1.9E+07

2.1E+07

2.3E+07

2.5E+07

85 95 105 115 125

Fan

Pow

er (k

W)

Air

Flow

Rat

e (k

g/hr

)

Air Flow of Design (%)

Fan Air Flow Rate and Power

Air Flow Rate (kg/hr) Fan Power (kW)

Page 19: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Fan Air Flow Results - MW

265

270

275

280

285

290

295

300

85 90 95 100 105 110 115 120 125

Gro

ss O

utpu

t (M

W)

Air Flow (%)

Gross MW Output for Air Flow Change

24°C21°C17°C

Page 20: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Fan Air Flow Results - HR

1019010200102101022010230102401025010260102701028010290

85 90 95 100 105 110 115 120 125

GU

HR

(kJ/

kWh)

Air Flow (%)

Gross Unit HR for Air Flow Change

24°C21°C17°C

Page 21: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Additional Cells Calculations

Flow Split to each cooling towerNumber of CellsSource Air FlowCTI CW Flows

Page 22: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Adding Cooling Tower Cells Results - MW

280

282

284

286

288

290

292

294

296

Base 1 Aux. 2 Aux. 1 Main 2 Main

Gro

ss O

utpu

t (M

W)

Gross MW Output for Adding Cells

24°C21°C17°C

Page 23: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Adding Cooling Tower Cells Results - HR

10170

10190

10210

10230

10250

10270

10290

Base 1 Aux. 2 Aux. 1 Main 2 Main

GU

HR

(kJ/

klW

h)

Gross Unit HR for Adding Cells

24°C21°C17°C

Page 24: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

The use of the PEPSE Data

Review which options were worth exploring further:– Feasibility of implementation– Cost of implementation– Effects on other parts of the system

Provide benefits found to the second part of the study:– Potential benefits– Cost justification

Page 25: Cooling Tower Improvement Study Using PEPSE - …famos.scientech.us/PDFs/2013 EPRI Papers/Cooling_Tower_Improveme… · Cooling Tower Improvement Study Using PEPSE ... Single-Unit

Conclusion

Study to choose best improvement option(s) is still ongoingSo far, indications are that a distribution system /

fill upgrade in the main towers will offer the greatest improvementStudy will provide which option or combination of

options is best suited to improve the back pressure issue