1. Only large openings in structural framing members are shown on the structural drawings.
However, all sleeves, embeds, inserts, openings and frames that are necessary for the work
shall be provided. The Contractor shall coordinate with all trades sizes, locations and
placement. All openings and embedded items which have an effect on the structure shall be
submitted to the Engineer for review.
2. Refer to Architectural, Mechanical, Electrical and Plumbing drawings for floor elevations,
location of depressed or elevated floor areas, slopes and drains.
3. Contractor shall coordinate the requirements for building equipment supported on or from
the structure. Submittals identify all equipment including size, dimensions, clearances,
accessibility, weights and reactions. Any deviations from specified equipment shall be noted
on the submittals.
4. Shop drawings shall be prepared for all structural items and submitted for review by the
Engineer. Contract Drawings shall not be reproduced and used as shop drawings. All items
deviating from the Contract Drawings or from previously submitted shop drawings shall be
noted.
5. The details designated as "Typical Details" apply generally to the Drawings in all areas where
conditions are similar to those described in the detail
6. All dimensions and conditions of existing construction shall be verified at the job site.
Differences between existing construction and the Drawings shall be referred to the Architect.
Differences shall also be clouded on the shop drawings.
7. The design and provision of all temporary supports required for the execution of the contract
such as guys, braces, shores, reshores, falsework, supports and anchors are not included in
these drawings and shall be the responsibility of the Contractor. Temporary supports shall not
result in the overstress or damage to the structure.
COORDINATION
1. All requests for substitutions of materials or details shown in the contract documents shall be
submitted for approval during the bidding period. Once bids are accepted, proposed
substitutions will be considered only when they are officially submitted with an identified
savings to be deducted from the contract.
SUBSTITUTIONS
1. IBC 2015 International Building Code with City of Round Rock Amendments.
2. Wind and Earthquake Loads: Minimum Design Loads for Building and Other Structures,
American Society of Civil Engineers, ASCE 7-10.
3. Structural Concrete: Building Code Requirements for Reinforced Concrete, American Concrete
Institute, ACI 318-14.
4. Structural Masonry: Building Code Requirements for Masonry Structures, reported by the
Masonry Standards Joint Committee, ACI 530-13/ASCE 5-13/TMS 402-13.
5. Structural Steel: Steel Construction Manual, American Institute of Steel Construction,
Fourteenth Edition. Specification for Structural Steel Buildings, AISC 360-10.
6. Wood Framing: National Design Specification (NDS) For Wood Construction with 2015
Supplement, American Forest and Paper Association, AF&PA NDS-2015, and Special Design
Provisions for Wind and Seismic, ANSI/AF&PA SDPWS-15.
7. Wood Structural Panels: Panel Design Specification, American Plywood Association, APA
PDS-12, Plywood Design Specification Supplements 1-5, and DOC PS 1 or PS 2.
8. Prefabricated Composite Wood Products: Products shall be proven by testing as
demonstrated either by ICBO and NRB acceptance or through a test program meeting
requirements of ASTM D 5055 for wood I-joists and ASTM D 5456 for Structural Composite
Lumber (SCL).
9. Prefabricated Metal-plate-connected Wood Trusses: National Design Standard for Metal-
plate-connected Wood Truss Construction, TPI 1-2014.
CODES
1. Live Loads
a. Public areas, corridors, lobbies 100 psf
b. Mechanical Rooms 150 psf
c. Storage (minimum) 125 psf
d. Roof 20 psf
e. Bleachers 100 psf
f. Stairs 100 psf
g. Assembly areas and theaters
Auditoriums (fixed seating) 60 psf
Auditoriums (moveable seating) 100 psf
h. Awnings or canopies 5 psf
2. Dead Loads include the self weight of the structural elements and the following superimposed
loads:
a. Ceiling and Mechanical at roof 10 psf
b. Roofing and rigid insulation 5 psf
3. Wind Loads
a. Wind Lateral Load on Structural Frame is based on the following:
i) Ultimate Design Wind Speed (3-sec. gust), Vult 115 mph
Nominal Design Wind Speed, Vasd 89 mph
ii) Risk Category II
iii) Wind Exposure Category C
iv) Internal Pressure Coefficient, GCpi ±0.18
v) Component & Cladding Ultimate Design Pressures:
Effective Area: ≤ 10 ft2 (Overhangs)
Zone 1 +16.0 psf; -33.2 psf +16.0 psf; -47.9 psf
Zone 2 +16.0 psf; -55.7 psf +16.0 psf; -47.9 psf
Zone 3 +16.0 psf; -83.9 psf +16.0 psf; -78.8 psf
Zone 4 +30.4 psf; -32.9 psf
Zone 5 +30.4 psf; -40.5 psf
Effective Area: 50 ft2 (Overhangs)
Zone 1 +16.0 psf; -31.2 psf +16.0 psf; -45.9 psf
Zone 2 +16.0 psf; -42.0 psf +16.0 psf; -45.9 psf
Zone 3 +16.0 psf; -50.4 psf +16.0 psf; -39.5 psf
Zone 4 +27.3 psf; -29.8 psf
Zone 5 +27.3 psf; -34.3 psf
Effective Area: >100 ft2 (Overhangs)
Zone 1 +16.0 psf; -30.4 psf +16.0 psf; -45.0 psf
Zone 2 +16.0 psf; -36.0 psf +16.0 psf; -45.0 psf
Zone 3 +16.0 psf; -36.0 psf +16.0 psf; -45.0 psf
Zone 4 +25.9 psf; -28.5 psf
Zone 5 +25.9 psf; -31.6 psf
NOTE: Zone 1 = Interior roof area not in Zones 2 or 3.
Zone 2 = Perimeter roof area not in Zone 3 (6'-6" strips).
Zone 3 = Corner roof areas where Zone 2 strips intersect.
Zone 4 = Wall areas not in Zone 5.
Zone 5 = Wall corner areas (6'-6" strips).
b. Calculate the effective area for each component & cladding element, as defined by ASCE
7, depending on length and location. Effective area shall be the maximum of the
following:
Effective Area = Length x Tributary Width (OR) Length x (Length/3)
c. Interpolation of uplift pressures is allowed between effective areas.
4. Roof Snow Loads
a. Ground Snow Load 5 psf
5. Earthquake Loads
a. Seismic Lateral Load on Structural Frame is based on the following:
i) Seismic Importance Factor, I 1.0
ii) Risk Category II
iii) Mapped Spectral Response Accelerations
SS 0.063
S1 0.035
iv) Site Class C
v) Spectral Response Coefficients
SDS 0.051
SD1 0.039
vi) Seismic Design Category A
vii) Basic Seismic-Force-Resisting System: 2D -- Ordinary Steel
Concentrically Braced
Frames
2Q -- Ordinary reinforced
masonry sheer walls
viii) Design Base Shear 5 kips
ix) Seismic Response Coefficient, CS 0.01
x) Response Modification Factor, R 5 @ 2D Sys.
3 @ 2Q Sys.
xi) Analysis Procedure Minimum Design
Requirements for Seismic
Design Category A
6. Loading for mechanical rooms and kitchens are based on the weights of equipment and
concrete pads as indicated on the contract documents. Any revisions in equipment type, size,
or quantity shall be reported to the Architect immediately for verification of the structural
design.
7. Floor and roof live loads noted above have been reduced in accordance with the building
code.
DESIGN LOADS
1. The building movements specified herein are anticipated to occur and shall be taken into
account by the Contractor in the design, detailing, and installation of the building elements.
2. Spandrel beam deflections: Provisions shall be made in the building cladding for relative floor
to floor vertical deflections of 3/8".
3. Interior floor/roof deflections: Provisions shall be made in interior partitions and other
elements supported by or attached to the floors or roofs for relative floor to floor vertical
deflections of 3/4".
4. Lateral building drift: Provisions shall be made in building cladding and other architectural
finishes for relative floor to floor lateral deflections of story height/400.
BUILDING MOVEMENTS
1. The structural system is designed and detailed to provide the following fire resistance in
accordance with the building code fire resistance standards:
Floor assembly 0 hours
Roof assembly 0 hours
Structural frame 0 hours
2. The structural frame consists of columns and members framing into columns.
3. For establishment of fire resistance ratings, the structural framing shall be considered
unrestrained.
FIRE RESISTANCE
1. Shop drawings shall be prepared for all structural items and submitted for review by the
Engineer. Contract Drawings shall not be reproduced and used as shop drawings. All items
deviating from the Contract Drawings or from previously submitted shop drawings shall be
clouded.
2. The contractor shall review shop drawings for compliance with the contract documents and
shall certify that he has done so by a stamp noting that the drawings have been "Approved"
and which bears the signature (or initials) of an authorized representative of the contractor
and the date. Submittals which do not reflect the contractor's approval, signature and date
will be returned without review.
3. The contractor shall be responsible for delays caused by rejection of inadequate shop
drawings.
4. Where review and return of shop drawings is required or requested, the engineer will review
each submittal and, where possible, return within 2 weeks of receipt.
5. Corrections or comments on shop drawings or manufacturer's data sheets do not relieve the
contractor from compliance with requirements of the plans and specifications. The engineer's
review is for general conformance with the requirements of the contract documents. The
contractor is responsible for confirming and correcting all quantities and dimensions, selecting
fabrication processes and techniques of construction, and coordinating his work with that of
all other contractors.
6. Refer to individual sections for specific submittal requirements.
SUBMITTALS
1. Work specified herein shall be performed by a qualified independent Testing Laboratory,
selected and paid by the Owner.
2. Pier drilling operation: Make continuous inspections to determine that the proper bearing
stratum is obtained and utilized for bearing and that the shafts are clean and dry before
pouring concrete.
3. Filling and Backfilling operation:
a. Analyze backfill samples delivered by the contractor to determine compliance with
gradation and quality requirements of the geotechnical report.
b. Make in place compaction tests for moisture content, moisture density relationship, and
density of materials in place. Perform test once for each li.
4. Concrete inspection and testing:
a. Secure composite samples of concrete at the jobsite in accordance with ASTM C172.
b. Mold and cure three specimens from each sample in accordance with ASTM C31. Test
specimens in accordance with ASTM C39. Two specimens shall be tested at 28 days for
acceptance and one shall be tested at seven days for information.
c. Perform one strength test (three cylinders) for each pour.
d. Make one slump test for each set of cylinders following the procedural requirements of
ASTM C143 and C172.
e. Determine total air content of air entrained concrete in accordance with ASTM C231.
Perform one test for each strength test.
5. Concrete Reinforcement: Inspect all concrete reinforcing steel and embedded metal
assemblies prior to placement of concrete for compliance with Contract Documents and shop
drawings. All instances of non-compliance shall be immediately brought to the attention of
the contractor for correction, and if uncorrected, reported to the engineer.
6. Structural Masonry: Provide a qualified masonry inspector to inspect all masonry work on a
periodic basis. Inspect work in progress at least once for every 5000 square feet of wall laid,
but not less than once each day.
a. Compressive test for grout: Mold and cure three 3" diameter by 6" tall cylinders from each
sample in accordance with ASTM C31. Test cylinders in accordance with ASTM C39. Two
specimens shall be tested at 28 days for acceptance and one shall be tested at seven days
for information.
b. Inspections: Inspect the placement of reinforcing, mortar and grout mixing operations,
bedding of mortar for each type of unit and placing of units.
7. Expansion Anchors: Provide continuous inspection of expansion bolt installation to ensure
that holes are of the specified size, and that bolts are properly installed including application
of minimum installation torques.
8. Structural steel & steel joists: Field inspection of proper erection of all members, visual
examination of all field welding, visual inspection of all bolts, inspection of all shop fabricated
members upon arrival at the jobsite for conformance with accepted fabrication and erection
drawings, verification of welder's certificates.
TESTING LABORATORY SERVICES
1. If utility trenches or other excavations extend to or below a depth of 5'-0" below construction
grade, the contractor or others shall be required to develop a trench safety plan to protect
personnel entering the trench or trench vicinity, unless the following applies:
a. A steeper slope is allowed by the geotechnical engineer for the particular location and site
conditions in question.
b. A retention system is indicated on the Contract Drawings.
c. An alternative protective system is submitted by the Contractor and allowed by the
Owner.
2. Contractor shall submit Drawings and calculations sealed by a Registered Engineer licensed in
the State of Texas for the design of any alternative protective systems. Alternative protective
systems shall be designed to resist the soil pressures stipulated in the project geotechnical
report prepared by Raba Kistner, dated June 19, 2020. In addition, the design shall consider
surcharges created by construction equipment, excavation spoil, and other surface
encumbrances.
3. Contractor shall comply with all Occupational Safety and Health Administration standards and
all other regulatory agency standards regarding excavation safety.
EXCAVATION PROTECTION
1. Backfill material shall be on-site clays.
2. Backfill shall be placed in loose lifts not to exceed 6 inches.
3. Backfill shall be compacted to at least 90 percent of the maximum dry density as determined
by TxDOT Test Method Tex-114-E at the optimum moisture content to plus 3 percent above
optimum moisture content.
4. Compaction and moisture content of controlled backfill shall be verified by an independent
testing laboratory for each lift.
5. Backfill material shall not be placed against foundation walls until all supporting slabs, beams,
struts, etc., have attained their 28 day design strength unless proper bracing is installed.
6. Where backfill is required on both sides of a structure or building element, backfill shall be
placed simultaneously along both sides so that the backfill height on one side does not exceed
the height on the opposite side by more than 4'-0".
7. Design of basement and retaining walls is based on equivalent hydrostatic pressure of 90 pcf,
assuming free draining backfill and use of perforated drain pipe in accordance with the
geotechnical report prepared by Raba Kistner, dated June 19, 2020.
CONTROLLED BACKFILL AROUND CRAWLSPACE
1. Pier design is based on an allowable loading of 35,000 psf in end bearing and 3,000 psf in side
friction in accordance with the geotechnical report dated Raba Kistner, dated June 19, 2020.
2. Bearing stratum shown on the pier details is hard, intact shale.
3. Piers not specifically located on the plan shall be located on centerline of column above.
Where no column occurs, locate on centerline of wall or beam.
4. Provide dowels from piers into concrete above using same bar size and number as shown for
pilaster above. Where no pilaster occurs, use dowels of same size and number as pier
reinforcing steel. Extend dowels 30 bar diameters into pier and beam, wall, pilaster or column
u.n.o.
5. Elevation of top of piers, unless noted otherwise on the drawings is at the bottom of the
deepest intersecting beam or wall supported by the pier.
6. Reinforcing cage shall be held securely away from earth at sides and bottom by sets of 3
spacers at a maximum spacing of 8-ft. along the length of the cage and 1'-0" from the bottom.
7. Pier reinforcing and concrete shall be placed immediately after drilling operations are
complete; in no case shall a pier be drilled that cannot be poured by the end of the workday.
8. See plans for pier sizes, reinforcing, and depth.
9. The contractor shall verify depths of piers before pier steel is cut. Pier steel may be delivered
to the jobsite in standard lengths and cut as required. Provide 64 bar diameter laps in all
vertical pier reinforcing.
10. Reinforcing steel shop drawings shall include placing drawings for templates to set dowels in
piers.
11. Top of pier shall be of the specified diameter. Form top of pier if required to maintain the
specified diameter. Any concrete extending beyond the specified diameter shall be removed.
12. Temporary steel casing may be required during pier drilling operations. Prior to the placement
of concrete, any seepage water shall be removed from the pier holes. Special construction
procedures in accordance with ACI 336.1-98 and ACI 336.3R-98 and specifications shall be
followed during extraction of the casing and during concrete placement.
13. Contractor shall include in bid documents, unit-costs for casing if required and unit-cost for
greater and lesser depth of drilling for each pier size. Base bids shall be for cased piers.
14. All piers shall be inspected by a representative of Raba Kistner in order to ensure that the
proposed bearing material has been reached in accordance with the recommendations given
in the geotechnical report.
15. The contractor shall make and maintain accurate records of the drilled pier depths, bearing
stratum, depth of penetration into bearing stratum, diameter and location (including off
center eccentricities), and shall submit this information to the Engineer.
DRILLED PIERS
1. Cast in place concrete shall meet the following requirements:
28 Day Aggregate Slump
Class Strength Type Size (at point of Use
placement)
A 4,000 psi C33 3/4" 4"-6" All, u.o.n.
B 4,000 psi C33 3/4" 5"-7" Drilled Piers
In addition, class "A " concrete shall meet the following additional requirements:
a. A maximum water/cement ratio of 0.45.
2. Fly ash shall not be used in architecturally exposed concrete.
3. Provide 5 percent plus or minus 1 1/2 percent of entrained air in concrete permanently
exposed to the weather and elsewhere at the contractors option. Do not use entrained air in
drilled piers.
4. Lightweight concrete shall have a maximum cured density of 115 pounds per cubic foot.
5. Horizontal construction joints in concrete pours shall be permitted only where indicated on
the drawings. All vertical construction joints shall be made in the center of spans in
accordance with the typical details. Contractor shall submit proposed locations for
construction joints not shown on drawings for review by the Architect and Structural
Engineer. Additional construction joints may require additional reinforcing as specified by the
Engineer which shall be provided by the contractor at no additional cost to the owner.
6. Embedded conduits, pipes, and sleeves shall meet the requirements of ACI 318-14, Section
6.3, including the following:
a. Conduits and pipes embedded within a slab, wall, or beam (other than those passing
through) shall not be larger in outside dimension than 1/3 the overall thickness of the
slab, wall or beam in which they are embedded.
b. Conduits, pipes and sleeves shall not be spaced closer than three diameters or widths on
center.
7. Concrete pours shall not exceed 5000 square feet or 100 linear feet on each side without prior
approval by the Architect for each pour.
8. Submittal: Submit proposed mix designs in accordance with ACI 301, chapter 3.9. Each
proposed mix design shall be accompanied by a record of past performance based on at least
30 consecutive strength tests, or by three laboratory trial mixtures with confirmation tests.
CAST IN PLACE CONCRETE
1. Reinforcing steel shall be deformed new billet steel bars in accordance with ASTM A615 Grade
60.
2. Detailing of reinforcing steel shall conform to the American Concrete Institute Detailing
Manual.
3. All hooks and bends in reinforcing bars shall conform to ACI detailing standards unless shown
otherwise.
4. Provide reinforcing bars in accordance with the bar bending diagram if bar types are specified.
In unscheduled beams, slabs, columns and walls detail reinforcing as follows:
a. Lap top reinforcing bars at mid span.
b. Lap bottom reinforcing bars at the supports.
c. Lap vertical bars in columns and walls only at floor lines, unless noted otherwise.
d. Refer to lap splice schedule for splice length requirement.
e. Reinforcement labeled as continuous shall be lap spliced 38 bar diameters as a minimum,
unless otherwise noted.
f. Provide standard hooks in top bars at cantilever and discontinuous ends of beams, walls
and slabs.
g. Provide corner bars for all horizontal bars at the inside and outside faces of intersecting
beams or walls. Corner bars are not required if top, bottom, or horizontal bars are
hooked.
5. Welding of reinforcing steel will not be permitted.
6. Heat shall not be used in the fabrication or installation of reinforcement.
7. Reinforcing steel clear cover shall be as follows:
a. Grade beams - 1 1/2" top, 3" bottom, 2" side (formed),
3" side (placed against earth)
b. Drilled piers - 3" bottom, 3" sides
c. Walls - 2"
d. Columns - 1 1/2"
e. Slabs above grade - 1"
f. Beams above grade - 1 1/2"
8. Submittal: Submit shop drawings for fabrication, bending, and placement of concrete
reinforcement. Comply with ACI 315 "Details and Detailing of Concrete Reinforcement". Do
not reproduce the Contract Drawings for use as shop drawings.
CONCRETE REINFORCING
1. Concrete repair includes removal of deteriorated concrete, cleaning concrete reinforcement
and patching with a concrete restoration material. The applications may include horizontal
surfaces, vertical surfaces or overhead surfaces as required on the drawings by the type of
repair.
2. Repairs shall be performed by workers qualified to perform the work. As a minimum, the
foreman shall have not less than two years experience with structural concrete repairs.
3. Repairs shall be patched with a horizontal, vertical or overhead patching concrete product
from one of the following manufactureres (or an equivalent product submitted to the
engineer for approval):
a. Sto
b. Euclid
c. Master Builders
d. Thoro
e. Dayton Superior
4. Dust caused by sandblasting shall be removed prior to applying concrete patch. Dust screens
shall be installed around the construction area to restrict dust to the immediate area.
5. Concrete repair products shall have a minimum 28 day strength of 6000 psi. The patching
material shall be suitable for the repair applied to regarding thin patches, feather edged
patches, thick patches, vertical patches, overhead patches and all other criteria specified by
the manufacturer.
6. Existing concrete shall be prepared as recommended by the manufacturer including but not
limited to the following:
a. Saw cut edges 1/2 inch deep around the perimeter of the repair area without cutting any
reinforcing steel.
b. Remove loose and unsound concrete by chipping or sandblasting.
c. Remove rust from reinforcing steel by medium sandblasting or wire brush.
d. Dampen concrete surface and apply bonding agent (if recommended or required by
manufacturer).
7. Patching materials shall be prepared in accordance with the manufacturers directions.
8. Apply patch material in thicknesses, layers and within working time limits identified by the
manufacturer.
9. Concrete patches shall be placed to the align with the existing dimensions of the structure.
Beam soffits may be formed. All surfaces shall be struck off to dimensions shown and shall
receive a smooth trowel finish. Any surface to receive traffic (without traffic waterproof and
wearing surface) shall have a broom finish.
10. Concrete patches shall be cured by continuous wetting for seven days (or as recommended by
the manufacturer) at a temperature above 40 degrees Fahrenheit, or by the immediate
application of a membrane curing compound conforming to ASTM C309 applied in accordance
with manufacturer's recommendations.
11. Submit manufacturers product data on repair materials to be used for review.
CONCRETE REPAIR
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
GENERAL NOTES
S101
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO. DESCRIPTION DATE
>AARCHITECTUREBUILDING SCIENCE I IMDESIGN
ztiLI.-
- -~::N
:
- -
1. Concrete joint sealant includes routing, sawcutting, surface preparation and application of
waterproof concrete joint sealant. Sealant used where exposed to pedestrian or vehicle traffic
shall be suited for traffic. Repair deteriorated concrete adjacent to crack or joint as required.
2. Joint sealing shall be performed by workers qualified to perform the work. As a minimum, the
foreman shall have not less than two years experience with structural concrete repairs.
3. Joints shall be sealed with a waterproof concrete joint sealant product from one of the
following manufactureres (or an equivalent product submitted to the engineer for approval):
a. Sto
b. Euclid
c. Master Builders
d. Thoro
e. Dayton Superior
4. Existing concrete shall be prepared as recommended by the manufacturer including but not
limited to the following:
a. Remove any existing joint sealant from crack or joint
b. Saw cut or route if necessary to clean joint,
c. Repair damage concrete as required,
5. Apply joint sealant in accordance with the manufacturers directions.
6. Apply sealant within working time limits and temperatures identified by the manufacturer.
CONCRETE JOINT SEALANT
1. Precast Floor Deck shall be 8 inch deep precast prestressed concrete hollow-core planks
designed and manufactured in accordance with the specifications and requirements of the
Prestressed Concrete Institute and the American Concrete Institute.
2. Precast fabricator shall design the reinforcement in each unit to support the applied service
and erection loads.
3. Calculations must be submitted with the shop drawings. The shop drawings and calculations
shall bear the seal of a Registered Professional Engineer licensed to practice in the State of
Texas.
4. Fabricator shall layouts units (except in areas specifically shown and dimensioned on the
drawings) to cover all areas noted as framed with precast units. Exact width of load bearing
surfaces shall be verified by the contractor.
5. Coordinate openings required in units with Architectural, Mechanical and Electrical drawings.
6. All units shall be designed by the fabricator to satisfy the following criteria:
a. Design for the superimposed live and dead loads listed in the General Notes. Refer to
architectural plans for location of the various areas listed.
b. Limit net design camber due to prestress to as required including maximum allowable
tolerance, creep, and the weight of the topping.
c. Live loads shall not be reduced.
d. The maximum flexural stress resulting from support of total load shall not exceed 6 times
the square root of f'c.
e. Limit differential camber between adjacent units of different spans to 3/4".
7. Powder-Driven anchors shall not be used on hollow-core planks. Drilling and coring of planks
in the field for expansion anchors, conduits, etc., may be done only with prior approval of the
Architect.
8. Hollow-core planks shall bear 3" (nominal) on bearing surfaces. Provide hard plastic shims at
all supports.
9. Design modifications may be made only as necessary to meet field conditions and to ensure
proper fitting of the work and only as acceptable to the Engineer and Architect. Maintain
general design concept shown without increasing or decreasing sizes of members or altering
profiles and alignment shown. Provide complete design calculations and drawings prepared
by a Registered Professional Engineer, licensed to practice in the State of Texas, if design
modifications are anticipated.
PRECAST CONCRETE HOLLOW-CORE SLABS
1. Topping slabs over precast concrete units shall be placed to a nominal minimum thickness of
3" and finished to provide a level floor within the specified tolerances. Topping thickness may
vary away from supports due to deflections of the precast concrete units, deflections of the
supporting beams and girders, and residual camber of precast units and supporting members.
2. Reinforce topping slab with 6x6 - W2.9xW2.9 welded wire mesh placed at mid-depth of slab.
Mesh shall be supported on and tied to chairs.
TOPPING SLAB OVER PRECAST CONCRETE
FLOOR UNITS
1. Concrete masonry units shall be hollow load bearing Type N-1 units which conform to ASTM
C90, with a minimum compressive strength of 1900 psi.
2. Minimum compressive prism strength of the masonry (f'm) shall be 1500 pounds per square
inch when tested at 28 days.
3. Chases shall be built in and not cut in. Chases shall be plumb and shall be minimum one-unit
length from jambs of openings. Anchors, wall plugs, accessories and other items to be built in
shall be installed as the masonry work progresses. All cutting and fitting of masonry, including
that required to accommodate the work of other sections shall be done by masons with
masonry saws.
4. Mortar shall conform to ASTM C270, Type S, by proportion. Masonry cement shall not be
used.
5. Coarse grout shall conform to ASTM C476, with a maximum aggregate size of 1/2" and a
minimum compressive strength of 2500 psi.
6. Coarse grout shall conform to ASTM C476, by proportion, with a maximum aggregate size of
1/2".
7. Reinforce concrete masonry unit joints with ladder type hot dip galvanized cold-drawn steel
conforming to ANSI/ASTM A82, with (no. 9 gauge or 3/16 inch) side rods with no. 9 gauge
cross rods. Space joint reinforcing at 16" o.c. unless noted otherwise. Provide "Trirod" joint
reinforcing where 6" or wider concrete masonry units backup brick masonry veneer. Lap joint
reinforcing 14" at splices. Joint reinforcing shall be discontinuous at control and expansion
joints.
8. Provide reinforced and grouted vertical cells at 48" on center unless noted otherwise on the
drawings. Reinforcing shall consist of #4 bars. Grout and reinforce the first cell at the ends of
walls and at corners.
9. Reinforce each cell of concrete masonry units each side of framed openings with 1-#4 vertical.
Grout cell full height of wall.
10. Lap reinforcing bars in grouted masonry 36 bar diameters minimum at foundations and 48 bar
diameters at all other locations, unless noted otherwise. Except at foundations, splices in
reinforcing shall be staggered so that not more than 1/2 of all bars are spliced at the same
location.
STRUCTURAL MASONRY
1. Expansion anchors shall only be used where specified on the drawings. The contractor shall
obtain approval from the engineer of record prior to using the anchors for missing or
misplaced cast-in-place anchors.
2. Unless otherwise noted, size and depth of the expansion anchors specified in the drawings are
based on the Hilti Fastening System products - Hilti Kwik Bolt 3 for general applications, and
Kwik Bolt TZ for overhead applications.
3. Substitution of expansion anchor products with similar capacities shall be submitted to the
engineer of record for approval.
4. Expansion anchors of the size and embedment shown on the Drawings shall be installed in
accordance with the Contract Documents, the manufacturer's recommendations, and the
manufacturer's current ICBO report for the anchor. If conflicts exist between these referenced
documents, the most stringent requirements shall govern.
5. The Contractor shall locate all existing reinforcing steel and other embedded items contained
in the concrete using non-destructive methods and shall position anchor locations to avoid
conflicts with existing embedded items. Anchor locations can be adjusted by a maximum of 1
1/2" from detailed locations to avoid conflicts, unless noted otherwise.
6. Based on field verified locations of reinforcing steel and embedded items, the Contractor shall
create templates for each anchor group. Submit template dimensions for review prior to
fabrication of connection plates.
7. Holes for anchors shall be drilled in a continuous operation using the bit type and size
recommended by the anchor manufacturer. Holes shall be drilled perpendicular to the
concrete surface and shall not be enlarged or redirected at any point along its length. All
debris shall be blown out of the holes with compressed air after drilling.
8. All abandoned holes shall be filled with non-shrink grout.
9. Holes in connection plates shall be no more than 1/16" larger than the anchor diameter. If
larger holes are required for erection purposes, Contractor shall provide 1/4" x 3" x 3" plate
washers sufficiently welded to the connection plate to transfer the specified load.
10. Installation of expansion anchors shall be continuously inspected by the testing agency to
ensure that holes are of specified size, and that bolts are properly installed including
application of minimum installation torques.
EXPANSION ANCHORS
1. Adhesive anchors shall only be used where specified on the drawings. The contractor shall
obtain approval from the engineer of record prior to using the anchors for missing or
misplaced cast-in-place anchors.
2. Unless otherwise noted, size and depth of the adhesive anchors specified in the drawings are
based on HAS rods epoxy doweled with HY 200 Max or RE 500 SD, Hilti Fastening Systems.
3. Substitution of expansion anchor products with similar capacities shall be submitted to the
engineer of record for approval.
4. Adhesive anchors of the size and embedment shown on the Drawings shall be installed in
accordance with the Contract Documents, the manufacturer's recommendations, and the
manufacturer's current ICBO report for the anchor. If conflicts exist between these referenced
documents, the most stringent requirements shall govern.
5. The Contractor shall locate all existing reinforcing steel and other embedded items contained
in the concrete using non-destructive methods and shall position anchor locations to avoid
conflicts with existing embedded items. Anchor locations can be adjusted by a maximum of 1
inch from detailed locations to avoid conflicts, unless noted otherwise.
6. Based on field verified locations of reinforcing steel and embedded items, the Contractor shall
create templates for each anchor group. Submit template dimensions for review prior to
fabrication of connection plates.
7. Holes for anchors shall be drilled in a continuous operation using the bit type and size
recommended by the anchor manufacturer. Holes shall be drilled perpendicular to the
concrete surface and shall not be enlarged or redirected at any point along its length. All
debris shall be blown out of the holes with compressed air after drilling.
8. All abandoned holes shall be filled with non-shrink grout.
9. Holes in connection plates shall be no more than 1/16" larger than the anchor diameter. If
larger holes are required for erection purposes, Contractor shall provide 1/4" x 3" x 3" plate
washers sufficiently welded to the connection plate to transfer the specified load.
10. Installation of adhesive anchors shall be continuously inspected by the testing agency to
ensure that holes are of specified size, and that bolts are properly installed.
ADHESIVE ANCHORS
1. Adhesive dowelling system shall be one of the following products: Hilti "HY 200 MAX", Hilti
"RE 500 SD". Install dowels in accordance with the manufacturer's instructions.
2. Clean out holes with compressed air after drilling holes.
3. Rebar Size Hole Diameter Embedment Depth
#4 5/8" 4 1/2"
#5 3/4" 6"
4. Prior to drilling holes for dowels, locate existing reinforcing steel with a Pachometer (R-Meter)
or by drilling 1/4" diameter pilot holes. Relocate bolt holes as required to avoid existing
reinforcement.
5. Abandoned holes shall be completely filled with adhesive dowelling compound.
ADHESIVE DOWELS
1. Structural Steel shall conform to ASTM A992 or A572, grade 50 except where A36 is noted on
plan, except that miscellaneous plates, angles, and channels may be A572, grade 50 or A36.
Steel pipe shall conform to ASTM Specification A 501 or ASTM A 53, Type E or S, Grade B.
Steel tube shall conform to ASTM Specification A 500, Grade B, Fy 46 ksi or ASTM A1085.
2. Anchor rods shall conform to ASTM F1554 grade 36 ksi.
3. Column base plates shall be grouted with a non-shrink, high strength nonmetallic grout
conforming to ASTM C827, and shall have a compressive strength at 28 days of 5000 psi. Pre-
grouting of base plates will not be permitted.
4. Studs shall be Nelson studs type S3L (Fu=65 ksi) or acceptable equal. Studs shall be made from
cold drawn steel conforming to ASTM A108.
5. Deformed bar anchors shall be Nelson D2L or KSM deformed bar anchors (or acceptable
equal) and shall be made from cold drawn wire per STM A490 conforming to ASTM A108 with
minimum yield strength of 70 Ksi. Anchors shall be automatically and welded with suitable
welding equipment in the shop or in the field. Welding shall be in accordance with the
recommendations of Nelson Stud Company or KSM Welding Company.
6. Structural steel detailing, fabrication, and erection shall conform to the AISC "Specification for
Steel Buildings" and the AISC "Code of Standard Practice for Steel Buildings and Bridges".
Typical connection details are indicated in the drawings. The fabricator shall prepare drawings
based on these details. If alternate connection designs are used, the fabricator shall have a
registered professional engineer prepare the connection designs. Such connection shall bear
the engineer's seal and shall be submitted with shop drawings.
7. Splicing of structural steel members is prohibited without prior approval of the Engineer as to
location and type of splice to be made. Any member having splice not shown and detailed on
shop drawings will be rejected.
8. All welds denoted as moment connection or full penetration weld shall be ultrasonically or x-
ray certified by an independent testing agency.
9. Contractor shall coordinate structural steel fireproofing requirements. All interior structural
steel, including steel joists, scheduled or indicated to receive spray applied fireproofing shall
be delivered to the project site unprimed. Steel exposed to corrosive conditions after
installation shall be primed with a protective coating which does not diminish the bond
between the spray applied fireproofing, and the steel substrate. Any primer, and/or coating
applied to structural steel shall be approved for use in the applicable U.L. Fire Resistance
Assembly used on the project. Contractor shall protect any unprimed structural steel from
detrimental effects of corrosion, as required, until the steel is enclosed and protected by the
new construction.
10. Shop painting: Paint structural steel with one coat of manufacturer's standard red oxide
primer applied at a rate to provide a uniform dry film thickness of 2.5 mils.
11. Contractor must fabricate and erect steel in accordance with OSHA Safety requirements, 29 CF
part 1926 Safety for Steel Erection, Final Rule.
12. Submittal: Provide drawings showing details for fabrication and shop assembly of members,
erection plans, and details. Include details of connections, camber, weld profiles and sizes and
spacing. Shop and erection drawings shall not be made using reproductions of the contract
drawings.
STRUCTURAL STEEL
1. Welding shall conform to ANSI/AWS D1.1, latest edition.
2. Bolts conform to ASTM A325. Bolts shall be designed using values for bearing type bolts with
thread allowed in the shear plane.
3. Structural steel connections not specifically detailed on the Drawings shall be designed and
detailed by the Contractor under the direct supervision of a registered engineer licensed in
the State of Texas. Sealed calculations for all connections designed by the Contractor shall be
submitted for the Architect's files. Connections that meet the requirements and assumptions
presented in our schematic connection details and table can be used at the discretion of the
Contractor. The Contractor shall take full responsibility in confirming that the connection
tables are used within their limitations and assumptions outlined in the details and notes.
4. Beam connections shall be designed and detailed as follows, unless noted otherwise on the
Drawings:
a. Connections shall be AISC type 2 simple framing connections.
b. In general, shop connections shall be bolted or welded and field connections shall be
bolted.
c. Where indicated, connections shall be designed for the scheduled shear force, the shear
force indicated on the Drawings as "V= ", and the horizontal force indicated as "H= ".
d. If not indicated on the Drawings, connections shall be designed for 55 percent of the total
load capacity for the beam span shown in the beam tables in Section 2 of the AISC
Manual, ninth edition. ((OR, IF USING LRFD)) Part 5 of the AISC Manual, third edition.
((OR, IF USING AISC 360-05)) Part 3 of the AISC Manual, thirteenth edition. ((OR, IF USING
AISC 360-10)) Part 3 of the AISC Manual, fourteenth edition.
e. The minimum number of rows of bolts shall be 1/6 of the beam depth with any fraction
be rounded to the next higher number.
f. Bolts shall be "snug tight", u.o.n.
g. Short slotted holes shall be permitted provided washers are installed in accordance with
AISC requirements. Washers shall be hardened where A325 bolts are utilized. Long slotted
holes are not permitted unless the connection is designed as slip-critical or as specified
otherwise.
5. Wind brace and truss connections shall be designed and detailed as follows, unless noted
otherwise on the Drawings:
a. Connections shall be welded.
b. Connections shall be designed and detailed for the forces shown on the Drawings.
c. If forces are not indicated on the Drawings, connections shall be designed to develop the
full tensile capacity of the members.
6. For connections not specifically addressed by these notes or the Drawings, provide fillet welds
at all contact surfaces sufficient to develop the tensile strength of the smaller member at the
joint.
7. Moment connections indicated on Drawings as " " shall be welded to develop the full
capacity of the member on both sides of supporting member.
8. Roof edges angles shall be continuous and shall be spliced only at supports. Splices shall be
butt-welded to develop full capacity of the member.
9. Fillet welds with no size specified shall be 3/16", or minimum size required by AISC, whichever
is larger.
STRUCTURAL STEEL CONNECTIONS
1. Open Web Steel Joists and Joist Girders shall conform to the Standard Specifications of the
Steel Joist Institute (SJI). Chords of joists and joist girders shall be angles or tees.
2. Provide bridging in accordance with SJI specifications and OSHA Standard
29CFR-1926.751(C)2. However, the number of rows of bridging shall not be less than that
shown on the Drawings. Bridging shall be continuous through structural steel members, and
shall be anchored to spandrel members or walls. Provide additional bridging where required
for uplift.
3. Open web steel joists shall be welded to steel supports with the equivalent of one 1/8" fillet
weld 2" long each side of joist seat. Longspan (LH) series joists shall be welded to steel
supports with the equivalent of one 1/4" fillet weld 1 1/2" long each side of joist seat.
4. Joist manufacturer shall design bottom chords of all open web joists and joist girders to
support a 50 lbs load located anywhere along the length of the chord. Hangers for mechanical
equipment with reactions in excess of 50 lbs must be located at the panel points of the joists.
Provide joist reinforcing in accordance with the typical details where hangers are required to
be located more than 4" from the joist panel points.
5. Roof joists shall be designed by the manufacturer to resist the net uplift loads specified on the
drawings. Provide additional bridging as required to resist net uplift loads.
Gym Weight Room
Wing Wing
Interior of Roof Area 13 psf 13 psf
6'-6" Perimeter Band 16 psf 16 psf
6. Special Loading: Joists and joist girders with labels ending with "SP" shall be designed by joist
manufacturer for non-uniform loading indicated on plans.
7. Shop painting: Joists and joist girders shall receive one coat of fabricator's standard red oxide
primer.
8. Submittals: Submit shop drawings including setting plans and shop tickets indicating standard
designations, bridging, camber, material strengths, spacing, joist seat extensions and
connection details. Submit calculations for all joists and joist girders for which standard load
tables are not applicable. Calculations must be submitted prior to or with shop drawings.
Calculations shall be signed and sealed by a registered professional engineer licensed in the
state of Texas. Calculations will be retained for the Architects file and shall not be approved or
returned.
OPEN WEB JOISTS AND JOIST GIRDERS
1. Steel Roof Deck shall be per the drawings.
2. Roof deck shall be galvanized with a class G60 minimum coating.
3. Roof deck shall be continuous over four or more supports.
4. Roof deck connections shall be as follows:
a. Plug weld deck to supporting steel and adjoining deck sheets with 5/8" diameter puddle
welds in accordance with the recommendations of the American Welding Society
standard D1.3.
b. 30 inch wide deck sheets shall be connected as follows:
i.) Weld at perimeter supports using a 12-6-12 pattern (one weld at each sidelap and
at the third and fourth flutes)
ii.) Weld at intermediate supports using a 12-18 staggered pattern (one at each
sidelap and the third and fourth flutes).
c. 36 inch wide deck sheets shall be connected as follows:
i.) Weld to all deck supports using 4 welds per sheet (a weld at each sidelap and at
every other flute).
d. Within 6'-6" from the building perimeter, the deck sheets shall be welded to all supports
at each flute.
e. At side laps: 2 screws equally spaced at 3 equal spaces between supports.
5. Screws shall be Teks #10 or equal.
6. Power driven fasteners shall be selected by the contractor for the combinations of deck gauge
and deck support member thickness. Submit proposed fasteners with complete
manufacturer's information, including diaphragm shear values for Engineer's review.
7. Puddle welds shall be 5/8" minimum diameter and shall be made through weld washers for 22
gauge and lighter decking.
8. Ceilings, mechanical, electrical, & plumbing systems shall not be supported by the metal roof
deck.
9. Submittal: Submit deck layout plans and details indicating deck type, fastening methods and
layout, support locations, projections, openings and reinforcement, and any other pertinent
details and accessories.
METAL ROOF DECK
1. The following Deferred Submittal items are required:
a. Awnings
b. Canopies
c. Bleachers
d. Noncombustible Metal Carports
e. Guardrails and Handrails
f. Curtain wall systems and storefront systems
g. Hollow core planks and other precast concrete members
DEFERRED SUBMITTALS
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
GENERAL NOTES
S102
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO. DESCRIPTION DATE
>L4ARCHITECTUREBUILDING SCIENCE IIMIODESIGN
4 '
ztiLI.-
- -~::N
:
- -
ADDITIONAL ADD'L.
ADJACENT ADJ.
AGGREGATE AGGR.
ALTERNATE ALT.
ANCHOR ROD A.R.
ARCHITECT(URAL) ARCH('L).
AIR CONDITIONER A/C
AIR HANDLING UNIT AHU
APPROXIMATE(LY) APPROX.
AXIAL LOAD P
BACK FACE B.F.
BEAM BM.
BEARING BRG.
BETWEEN BTWN.
BLOCKING BLKG.
BLOCK-OUT B.O.
BOTTOM BOT.
BOTTOM OF B.O.
BOTTOM OF STEEL B.O.S.
BRICK LEDGE BR. L.
BRIDGING BRDG.
BUILDING BLDG.
BUILDING LINE B.L.
CAST-IN-PLACE C.I.P.
CENTER LINE C.L. OR ℄
CENTER LINE OF STEEL C.L.S.
CENTER OF GRAVITY C.G.
CLEAR(ANCE) CLR.
COLUMN COL.
COMPLETE JOINT PENETRATION C.J.P.
COMPRESSION C OR COMP.
CONCRETE CONC.
CONCRETE MASONRY UNIT CMU
CONNECTIONS CONX(S).
CONTINUOUS CONT.
CONTRACTOR CONTR.
CONTROL JOINT CTL. J.
CONSTRUCTION CONST.
CONSTRUCTION JOINT C.J.
COVER PLATE COV. PL.
DEFORMED BAR ANCHOR(S) DBA('S).
DETAIL DET.
DEAD LOAD D.L.
DIAGONAL DIAG.
DIAMETER DIA.
DIMENSION(S) DIM(S).
DIRECTION DIR.
DRAWING(S) DWG(S).
DOUBLE DBL.
DOUBLE EXTRA STRONG XXS
DOWEL(S) DWL(S).
EACH EA.
EACH FACE E.F.
EACH WAY E.W.
ELECTRICAL ELEC.
ELEVATION EL.
ELEVATOR ELEV.
EMBEDMENT EMBED.
ENGINEER ENGR.
EQUAL EQ.
EQUIPMENT EQUIP.
EXPANSION EXP.
EXPANSION JOINT E.J.
EXISTING EXIST.
EXTERIOR EXT.
EXTRA STRONG XS
FACE TO FACE F. TO F.
FABRICATE(ION)(OR) FAB.
FAR SIDE F.S.
FINISH(ED) FIN('D).
FINISHED FLOOR F.F.
FIREPROOF F.P.
FLANGE FLG.
FLOOR FL.
FLOOR DRAIN F.D.
FOOTING FTG.
FOUNDATION FDN.
GALVANIZED GALV.
GENERAL GEN.
GLUE LAMINATED TIMBER GLULAM
GRADE GR.
GRADE BEAM GR.BM.
HOT DIP(PED) H.D.
HEADED STUD(S) H.S.
HEADER HDR.
HEIGHT HT.
HORIZONTAL HORIZ.
HOOK HK.
INSIDE DIAMETER I.D.
INSIDE FACE I.F.
INTERIOR INT.
INTERMEDIATE INTERM.
JOINT JT.
JOIST(S) JST(S).
LAMINATED VENEER LUMBER LVL
LAMINATED STRAND LUMBER LSL
LIGHTWEIGHT LWT.
LIVE LOAD L.L.
LONGITUDINAL LONG.
LONG LEG HORIZONTAL LLH
LONG LEG VERTICAL LLV
LONG SIDE HORIZONTAL LSH
LONG SIDE VERTICAL LSV
STRUCTURAL ABBREVIATIONS
MANUFACTURE(R) MFR.
MASONRY MAS.
MATERIAL MAT'L.
MECHANICAL MECH('L).
METAL MTL.
MEZZANINE MEZZ.
MIDDLE MID.
MISCELLANEOUS MISC.
MOMENT M.
MOMENT CONNECTION(S) M.C.
NEAR FACE N.F.
NOMINAL NOM.
NON-SHRINK N.S.
NORMAL WEIGHT N.W.
NOT IN CONTRACT N.I.C.
NOT TO SCALE N.T.S.
ON CENTER O.C.
OPENING(S) OPNG(S).
OPPOSITE OPP.
OPPOSITE HAND O.H.
ORIENTED STRAND BOARD OSB
OUTSIDE FACE O.F.
OUTSIDE DIAMETER O.D.
PARALLEL PAR.
PARALLEL STRAND LUMBER PSL
PARTIAL JOINT PENETRATION P.J.P.
PENETRATION PEN.
PERPENDICULAR PERP.
PIECE PC.
PLATE PL. OR ⅊
PLYWOOD PLYWD.
POINT PT.
POST-TENSION(ED) P.T.
POUND(S) X1000 KIP(S)
POUNDS PER LINEAR FOOT PLF
POUNDS PER SQUARE FOOT PSF
POUNDS PER CUBIC FOOT PCF
POUNDS PER CUBIC YARD PCY
PRECAST CONCRETE P/C
PREFABRICATED PREFAB.
PRELIMINARY PRELIM.
PRESSURE PRESS.
PROJECT(ION) PROJ.
RADIUS R
REFER TO / REFERENCE REF.
REINFORCE(ING)(ED)(MENT) REINF.
REMAINDER REM.
REQUIRE REQ.
REQUIRED REQ'D
RETURN RET.
ROOF DRAIN R.D.
ROUGH OPENING R.O.
ROUND RND.
SCHEDULE(D) SCHED.
SECTION SECT.
SHEAR FORCE V
SHEET SHT.
SIMILAR SIM.
SPACE(S)(ING) SPA.
SPECIFICATION(S) SPEC(S).
SPECIFIED SPEC'D
SQUARE SQ.
STAINLESS STEEL S.S.
STANDARD STD.
STEEL STL.
STIFFENER STIFF
STRAIGHT STR.
STIRRUPS STIR.
STRUCTURE OR STRUCTURAL STRUCT.
SUPPORT(S) SUPT(S)
TENSION T
THICK(NESS) THK.
TONGUE AND GROOVE T&G
TOP AND BOTTOM T&B
TOP OF BEAM T.O. BM.
TOP OF FOOTING T.O. FTG.
TOP OF PIER T.O. PIER
TOP OF PIER CAP T.O. P.C.
TOP OF STEEL T.O.S.
TOP OF STRUCTURAL CONCRETE T.O.S.C.
TOP OF WALL T.O.W.
TREATED TRTD.
TYPICAL TYP.
UNLESS OTHERWISE NOTED U.O.N.
VERTICAL VERT.
VOLUME VOL.
WATER STOP W.S.
WELDED WIRE MESH W.W.M.
WIND BRACE WB
WIND LOAD W.L.
WITH W/
WITHOUT W/O
WATER PROOFING W.P.
WORK POINT W.P.
WOOD WD.
MATERIALS LEGEND
EXISTING CONSTRUCTION
CONCRETE
STEEL IN SECTION
PLYWOOD IN SECTION
CMU
BRICK OR STONE IN
SECTION
GROUT/SAND
EARTH
(UNDISTURBED)
EARTH/FILL
(COMPACTED)
ROCK
MECH. UNIT
OR ZONE
DRAFTING SYMBOLS
.
SECTION MARK
ELEVATION MARK
DETAIL MARK
DIRECTION OF VIEW
FOR SECTION CUT
OR ELEVATION
SECTION NUMBER
SHEET NUMBER
DIRECTION OF VIEW
SPECIFIC LOCATION
DESCRIBED BY DETAIL
PLAN/DETAIL DESIGNATION
PLAN NAME/DETAIL TITLE
SCALE:
STRUCTURAL DRAWING TYPESS1 . . . . GENERAL NOTES & PIER PLAN
S2 . . . . PLANS/FOUNDATION CONSTRUCTION
S3 . . . . CONCRETE CONSTRUCTION
S4 . . . . MASONRY CONSTRUCTION
S5 . . . . STEEL CONSTRUCTION
1
S300
1
S300
1
S300
#
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
GENERAL NOTES
S103
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO. DESCRIPTION DATE
aARCHITECTURE
M jo~'w)e N rierngine~rs
ztiLI-A
cK
t~m~uta
- ¾11
P1W- -V/il . ~0
Ii ¾ I.
8.'- '4.Im.1 ----4
½
I F-- -E7 -- ]
EC.1
EC.1
E12
E11
E10
E9
E8
E7
E6
E6
EB.1EA.1
8" H.C.P. w/ 3" TOPPING SLAB
w/ 6X6-W3.5XW3.5 W.W.M.
TYP. U.O.N.
SPAN DIRECTION
OF HOLLOW-CORE
PLANKS, TYP.VOLLEYBALL SLEEVE, TYP. (6) LOC.;
REF. ARCH. FOR LOCATION, COORD. w/
HOLLOW CORE PLANK PROVIDER AND
VOLLEYBALL NET MANUFACTURER
W10X33, BP-2P24, EL. -4'-0"
P30, EL. -3'-0"
P30, EL. -4'-0"EXISTING
T.O.S.C. EL. =
T.O.S.C. EL. =
A.3A.1 A.5 A.7 A.9 B.6 C.2 C.9
HSS5X5X1/4, BP-5A
30' - 0" 15' - 6" 3' - 4"
8" H.C.P. w/ 3" TOPPING
SLAB w/ 6X6-W3.5XW3.5
W.W.M. TYP. U.O.N.
8" CONC. SLAB-ON-VOID REINF. w/
#4 @ 12" O.C. TOP & BOT. E.W.
P24, EL. -4'-0"
P30, EL. -3'-0" P30, EL. -3'-0" P30, EL. -3'-0" P30, EL. -3'-0" P30, EL. -4'-0"
P24, EL. -4'-0" P24, EL. -4'-0" P24, EL. -4'-0" P24, EL. -4'-0" P24, EL. -4'-0"
P24, EL. -4'-0" P24, EL. -4'-0" P24, EL. -4'-0" P24, EL. -4'-0"
P30, EL. -4'-0"
P24, EL. -4'-0"
P30, EL. -4'-0"
P30, EL. -3'-0"
P30, EL. -4'-0"P30, EL. -3'-0"
P30, EL. -4'-0"
P30, EL. -4'-0"
W10X33, BP-1 W10X33, BP-1 W10X33, BP-1 W10X33, BP-1 W10X33, BP-1 W10X33, BP-1
W10X33, BP-1 W10X33, BP-1 W10X33, BP-1 W10X33, BP-1
W10X33, BP-1
W10X33, BP-2
P24, EL. -3'-0"W10X33, BP-1
HSS5X5X1/4, BP-4
HSS5X5X1/4, BP-5
HSS5X5X1/4, BP-4
HSS5X5X1/4, BP-5
HSS5X5X1/4, BP-5A
HSS5X5X1/4, BP-4
HSS5X5X1/4, BP-3
HSS5X5X1/4, BP-3
HSS5X5X1/4, BP-3
HSS5X5X1/4, BP-3
P30, EL. -3'-0"
W10X33, BP-2
W10X33, BP-2
W10X33, BP-1
W10X33, BP-1
P24, EL. -4'-0"
W10X33, BP-1
P30, EL. -4'-0"
P24, EL. -4'-0" P24, EL. -4'-0" P24, EL. -4'-0"
P24, EL. -4'-0"
P24, EL. -4'-0"
P24, EL. -4'-0"
P24, EL. -4'-0"
W10X33, BP-1
P24, EL. -4'-0"
W10X33, BP-1
3.5
1" E.J.
1" E.J.
2' -
0"
5' - 0" 10 1/2"
4' - 4 1/2"
5' - 0"
2' -
0"
TYP
.
11
3/8
"
10 1/2"
5' - 0"
2' -
0"
57' - 1" 24' - 0" 15' - 0"
5' -
0"
9 3
/8"
5' -
0"
4' -
2"
5' -
0"
5' -
10
"1
1"
3.1
4' - 11 3/8"
2' - 0"
2' - 0"
2' - 0"CL CL CL CL
CL
CL
CL
7' -
11
1/4
"2
' - 6
1/8
"
CL
11
"
CL
1' - 11" 2' - 6"
1' - 6" 6"
2' - 6" 12' - 6" 2' - 9"
11
"
9"
3' -
8"
5' -
0"
2' - 0"
16
' - 6
5/8
"2
' - 6
3/8
"5
' - 0
"
2' - 0"
FLOOR HATCH
REF. ARCH.
-0'-2 1/2"
0'-0"
T.O.S.C. EL. = 0'-0" , TYP. @ GRADE BEAM
1
S310
2
S310
3
S310
CANOPY ABOVE
BY OTHERS
5
S310
10' - 0" 2' - 8"
EXISTING VENT PENET.,
TYP.
1
S311
4
S310
S531
1
1
S310
1
S311
3
S310
1
S310
1
S311
1
S310
S531
2
S531
3
S531
47
S530
TYP.
VOLLEYBALL
SLEEVE
VOLLEYBALL
SLEEVE
VOLLEYBALL
SLEEVE
3.7
VOLLEYBALL
SLEEVE
1A
S310
T.O.S.C. EL. VARIES,
REF.-CIVIL
TYP. @ COL.
1A
S310
TYP.
@
COL.
W10X33, BP-1
P24, EL. -4'-0" P24, EL. -4'-0"
P24, EL. -4'-0"TYP. @ (4) LOC.
4
EC.2
3.9
3
7"
64
' - 2
"
22
' - 3
"2
9' -
9"
9' -
8"
15
' - 0
"2
4' -
0"
24
' - 6
"
D
C
C
B
BA
96' - 1"
3.3
1' -
0"
5"
P24, EL. -4'-0"
2
1.9
1
9"
52
' - 0
"9
' - 6
"
1.1
1.3
1.5
B.1 B.4 B.9
3' - 0"
4 3
/8"
5"
9"
11 3/8" 13' - 8 5/8" 13' - 9" 13' - 9" 13' - 9" 12' - 7" 2' - 4" 11' - 8 3/8"
1' - 3"
64
' - 5
"9
' - 3
"5
2' -
0"
12
5' -
8"
4 5
/8"
30
' - 0
"1
0' -
2"
10
' - 5
3/8
"1
' - 0
" 9"
15
' - 6
"1
5' -
8 1
/8"
15
' - 8
1/8
"1
5' -
8"
11
3/8
"
48' - 10"
24' - 0"
9" 7' - 0" 15' - 3"
5' - 3" 9"
12
5' -
2"
WB-1
WB-2
WB
-3
WB
-4
P30, EL. -4'-0"
P30, EL. -3'-0"
ALL GRADE BEAMS
ALONG GRIDS C & 1 TO BE
LATERALLY DOWELED
INTO EXISTING GRADE
BEAM w/ #4 x18" @ 24"
O.C.E.W. EMBED 6" & SET
w/ HILTI HY 200 ADH.
CL
2' -
6" CL
FACE OF EXIST.
MASONRY
FACE OF EXIST.
MASONRY
FACE OF EXIST.
MASONRY
FACE OF EXIST.
MASONRY
1" E.J.
PLAN LEGEND:
INDICATES CONCRETE COLUMN
OR WALL
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLAB STEP
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLOPE CHANGE
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLOPE EXTENTS
FOUNDATION PLAN NOTES:
1. TOP OF STRUCTURAL CONCRETE ELEVATION IS
DENOTED AS FOLLOWS UNLESS OTHERWISE
NOTED:
2. FOR FINISH FLOOR ELEVATIONS (F.F. EL.), REFER TO
ARCHITECTURAL DRAWINGS. ELEVATIONS NOTED ON
PLAN ARE FOR REFERENCE ONLY. T.O.S.C. EL. =0'-0"
REFERS TO 746.9' ABOVE MEAN SEA LEVEL. REFER TO
AND VERIFY ALL DIMENSIONS AND ELEVATIONS w/
ARCHITECTURAL DRAWINGS.
3. REFER TO THE ARCHITECTURAL DRAWINGS FOR
EXACT LOCATIONS OF FLOOR RECESSES, DROPS AND
SLOPES NOT DIMENSIONED ON PLAN.
4. REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING
DRAWINGS FOR LOCATIONS AND DIMENSIONS OF
PENETRATIONS NOT SHOWN OR DIMENSIONED ON
PLAN.
6. REFER TO S501 FOR BASEPLATE SCHEDULE AND
DETAILS
7. COLUMNS AND PIERS ARE NOTED ON PLAN AS
FOLLOWS:
8. REFER TO FOR TYPICAL PIER ELEVATION.
PIER MARK, T.O.PIER EL.
T.O.S.C. EL.=XXX'-XX" T.O.S.C. EL.=XXX'-XX"
COLUMN MARK, BASE PLATE MARK
(AREA ELEVATION) (SPOT ELEVATION)
/1 S303
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
FOUNDATION PLAN
S201
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
SCALE: 1/8" = 1'-0"
FIRST FLOOR LEVEL1
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGNPp 1''`0 011 1
w w
1 17- 9
7
1/0N
I
FFF=71I
%W w
11QN N ftNVV222~ I \-N r%
1 -QV
I I H :1 1 1 I I 111A I I 1 f:-L :lI I U
----
\L 'if( I *--I-
1111
,~ N
- - - (
$ N
N_ -'
N
N V-i--i-
-N
44
IH----JV N_ V
-_ - N_ ---- -
N
'7
-- -
N
-V
N11
-N
K-~ 11 _
.. - I --
7 ~ n--I---~~*7 7~~~_ ~-zJvI _
K _ I_L1 K _ _ I_L~
) ( )04 -r
'2. ol
V)
1"N I N N --NILI '"- ---
m -- nlmm
-. 7
K-N.
I__N
)3NN..
N N11-- -L
ti~i-I------Iii
ztiLI-A
N4%~
-1
N
-- 9-9All---- 9-9
V"I'a
- .~-.........
- q
--- .
-/-
- p.,.~--
-~jLE~ 4$%../~
IIIIII
(N-.
-- 9
)1 N -N- I
-- , -- ll
-1 I
NL -7- -9 -- 9
) -K.)-
-~ ILL'
1) INN
( I N1 N11 - 11
N-.'
4 N
)N
II-( -
N ,'
/
/ /-VI
- 1
I
O0)A
V
.1 II
.1, ,
I
EC.1
EC.1
E12
E11
E10
E9
E8
E7
E6
E6
EB.1EA.1
HSS6X6X1/4 HSS6X6X1/4 HSS6X6X1/4 HSS6X6X1/4 HSS6X6X1/4 HSS6X6X1/4 HSS6X6X1/4
HSS
6X
6X
1/4
HSS
6X
6X
1/4
HSS
6X
6X
1/4
HSS6X6X1/4HSS6X6X1/4HSS6X6X1/4HSS6X6X1/4HSS6X6X1/4HSS6X6X1/4
HSS6X6X1/4
W1
2X
26
W12X26
W12X19
W1
2X
26
W12X26
W12X26
W1
2X
26
OPEN
1.5
B2
0 R
OO
F D
EC
K
A.3A.1 A.5 A.7 A.9 B.6 C.2 C.9
3.5
3.1
12
5' -
8"
48' - 10"
30' - 0" 15' - 6" 3' - 4"
96' - 1"
EXISTING
11
"
24' - 0"
1' - 9"
20' - 0"
14
K3
@ S
PA
. AS
SHO
WN
W1
2X
26
W1
2X
26
W1
2X
26
W1
2X
26
T.O.S. EL. = 10'-6" , TYP.
BUILDING LINE, TYP.
HSS
6X
6X
1/4
HSS
6X
6X
1/4
HSS
6X
6X
1/4
ALTERNATES TO 1.5B20 ROOF DECK:
2" EPICORE ER2RA 20 GA. DECK
2.0DA 20 GA. NUCOR DECK
VERSA-DEK S-ES ACOUSTICAL
S531
1
CANOPY BY OTHERS
1
S510
RTU-10E
1,473#
2
S510
2
S510
2
S510S531
2
S531
3
S531
4
HSS
6X
6X
1/4
3.7
W1
2X
19
W12X14
LOW
T.O.S. EL. = 21'-0". TYP. HIGH
HIGH & LOWHIGH & LOWHIGH & LOWHIGH & LOWHIGH & LOWHIGH & LOWHIGH & LOW
3
S510
3
S510
4
S510
5
S510
HIG
H &
LO
WH
IGH
& L
OW
HIG
H &
LO
WH
IGH
& L
OW
HIGH & LOW
HIGH & LOWHIGH & LOWHIGH & LOWHIGH & LOWHIGH & LOW
HSS
6X
6X
1/4
HIG
H &
LO
WH
IGH
& L
OW
HIG
H &
LO
WH
IGH
& L
OW
4
EC.2
3.9
3
D
C
C
B
BA
3.3
2
1.9
1
1.1
1.3
1.5
B.1 B.4 B.9
11 3/8" 13' - 8 5/8" 13' - 9" 13' - 9" 13' - 9"
24
' - 6
"2
4' -
0"
15
' - 0
"9
' - 8
"2
9' -
9"
22
' - 3
"
12' - 7"
57' - 1" 24' - 0" 15' - 0"
2' - 4" 11' - 8 3/8"
1' - 3"
64
' - 5
"9
' - 3
"5
2' -
0"
30
' - 0
"1
0' -
2"
10
' - 5
3/8
"1
' - 0
"1
5' -
6"
15
' - 8
1/8
"1
5' -
8 1
/8"
15
' - 8
"1
1 3
/8"
9"
9" 7' - 0" 15' - 3"
5' - 3" 9"
12
5' -
2"
WB-1
WB-2
WB
-3
WB
-4
1"
1"
1"
1/4"
HIGH & LOW & @ T.O.S. EL.=16'-6"
L7x4x3/8LLH SHELF
ANGLE WELDED TO
HSS TO SUPPORT
MASONRY VENEER
ABOVE. REF. ARCH.
HSS5X5X1/4,
HANGER
HSS6x6x1/4
BELOW @ T.O.S.
EL = 11'-2"
L7x4x3/8LLH SHELF ANGLE
WELDED TO HSS TO
SUPPORT MASONRY
VENEER ABOVE. REF.-ARCH.
ROOF DRAIN,
TYP.
ROOF
DRAIN,
TYP.
LINK TOPS OF ALL COLS TO
EXIST. STEEL STRUCT. w/
HSS5X5X5/16 HORIZ. @
GRIDS B.9 & 1.1
7
S5051
S502 TYP.
2 E
Q. S
PA
.2
EQ
. SP
A.
6 E
Q. S
PA
.2
EQ
. SP
A
T.O
.S. E
L. =
14
'-9
1/2
"
T.O
.S. E
L. =
14
'-4
"
T.O
.S. E
L. =
14
'-4
"
T.O
.S. E
L. =
14
'-9
1/2
"
PLAN LEGEND:
INDICATES CONCRETE COLUMN
OR WALL
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLAB STEP
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLOPE CHANGE
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLOPE EXTENTS
ROOF PLAN NOTES:
1. TOP OF STRUCTURAL STEEL ELEVATION (BOTTOM OF
DECK) IS DENOTED AS FOLLOWS UNLESS OTHERWISE
NOTED:
2. FOR FINISH FLOOR ELEVATIONS (F.F. EL.), REFER TO
ARCHITECTURAL DRAWINGS. ELEVATIONS NOTED ON
PLAN ARE FOR REFERENCE ONLY. REFER TO AND
VERIFY ALL DIMENSIONS AND ELEVATIONS w/
ARCHITECTURAL DRAWINGS.
3. REFER TO THE ARCHITECTURAL DRAWINGS FOR
EXACT LOCATIONS OF ROOF SLOPES NOT
DIMENSIONED ON PLAN.
4. REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING
DRAWINGS FOR LOCATIONS AND DIMENSIONS OF
ROOF PENETRATIONS NOT SHOWN OR DIMENSIONED
ON PLAN.
5. STEEL BEAMS ARE NOTED ON PLAN AS FOLLOWS:
T.O.S. EL.=XXX'-XX" T.O.S. EL.=XXX'-XX"
(AREA ELEVATION) (SPOT ELEVATION)
W14x22, c=1"
BEAM MARK
CAMBER AT
MID . LENGTH
5K 5K
BEAM END
REACTION
(SERVICE)
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
LOW ROOF FRAMINGPLAN
S202
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
SCALE: 1/8" = 1'-0"
LOW ROOF FRAMING PLAN1
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGNP- I'0 4 4
/
I 4-
I .-o
.-o .4-1 -1 .1 -9
Q - - - - - - - - - - - - - - - - -
I
ON ------------- - -------------L- ~
II
( 4 *--I-N
11
--N
1 I
( 4 1111
-
.,A!, )4 /
V ___
A
- - - - I- 7
- - - - - - - -- 4
03
-----------------------
) M -- lmm-
40' )., N N
ztiLI-A
v
.....................................i
-1 - 0CLN. )N 1 11a 1%
a
\1( 4 N - -N.
N.
//
/ /
2v/
0I I)"oo,
.1lol , ,
EC.1
EC.1
E12
E11
E10
E9
E8
E7
E6E6
EB.1EA.1
W18X35 W18X40 W18X40 W18X40 W18X40 W18X40 W18X35
W18X35 W18X40 W18X40 W18X40 W18X40 W18X40 W18X35
W1
4X
22
W1
4X
22
W1
4X
22
ROOF BELOW
A.3A.1 A.5 A.7 A.9 B.6 C.2 C.9
BUILDING LINE, TYP.
3.5
1.5B20 ROOF DECK
ALTERNATES TO 1.5B20 ROOF DECK:
2" EPICORE ER2RA 20 GA. DECK
2.0DA 20 GA. NUCOR DECK
VERSA-DEK S-ES ACOUSTICAL
3.1
12
5' -
8"
48' - 10"
30' - 0" 15' - 6" 3' - 4"
96' - 1"
40LH08SP @ 4' - 7" O.C.
1' -
11
3/8
"
EXISTING
SLO
PE
DO
WN
TY
P. @
RO
OF
JOIS
TS
W1
4X
22
W1
4X
22
W1
4X
22
W1
4X
22
S531
1
6
S510
T.O.S. EL. = 28'-11"
T.O.S. EL. = 30'-3" T.O.S. EL. = 30'-3"
T.O.S. EL. = 28'-11"
S531
2
S531
3
S531
4
CANOPY BELOW
RTU-9E
2,852#
3.7
W1
4X
22
SUPPLEMENTAL STEEL FRAMING TO
BE PROVIDED BY STEEL FABRICATOR
AND COORD. w/ BASKETBALL GOAL
MANUFACTURER (6 LOCATIONS)
ROOF DRAIN,
TYP.
4
EC.2
3.9
3
D
C
C
B
BA
3.3
2
1.9
1
1.1
1.3
1.5
B.1 B.4 B.9
57' - 1" 24' - 0" 15' - 0"
11 3/8" 13' - 8 5/8" 13' - 9" 13' - 9" 13' - 9" 12' - 7" 2' - 4" 11' - 8 3/8"
1' - 3"
12
5' -
2"
24
' - 6
"2
4' -
0"
15
' - 0
"9
' - 8
"2
9' -
9"
22
' - 3
"
24' - 0"
9" 7' - 0" 15' - 3"
64
' - 5
"9
' - 3
"5
2' -
0"
30
' - 0
"1
0' -
2"
10
' - 5
3/8
"1
' - 0
" 9"
11
3/8
"1
5' -
6"
15
' - 8
1/8
"1
5' -
8 1
/8"
15
' - 8
"1
1 3
/8"
5' - 3" 9"
NO PERMANENT BOTTOM
CHORD OR X-BRIDGING
BETWEEN THESE TWO
JOISTS. ADD X-BRIDGING AS
REQ'D ELSEWHERE.
2
S504
2
S504
WB-1
WB-2
WB
-3
WB
-4
3
S504
7
S505
1
S502
TYP.
REF.-ARCH. FOR LADDER
TYP.
4
S504
TYP.
4
S504
CAMBER FIRST INTERIOR JOIST
1/2 OF STANDARD SJI CAMBERCAMBER FIRST
INTERIOR JOIST 1/2 OF
STANDARD SJI CAMBER
PLAN LEGEND:
INDICATES CONCRETE COLUMN
OR WALL
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLAB STEP
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLOPE CHANGE
INDICATES STRUCTURAL
CONCRETE OR TOPPING
CONCRETE SLOPE EXTENTS
ROOF PLAN NOTES:
1. TOP OF STRUCTURAL STEEL ELEVATION (BOTTOM OF
DECK) IS DENOTED AS FOLLOWS UNLESS OTHERWISE
NOTED:
2. FOR FINISH FLOOR ELEVATIONS (F.F. EL.), REFER TO
ARCHITECTURAL DRAWINGS. ELEVATIONS NOTED ON
PLAN ARE FOR REFERENCE ONLY. REFER TO AND
VERIFY ALL DIMENSIONS AND ELEVATIONS w/
ARCHITECTURAL DRAWINGS.
3. REFER TO THE ARCHITECTURAL DRAWINGS FOR
EXACT LOCATIONS OF ROOF SLOPES NOT
DIMENSIONED ON PLAN.
4. REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING
DRAWINGS FOR LOCATIONS AND DIMENSIONS OF
ROOF PENETRATIONS NOT SHOWN OR DIMENSIONED
ON PLAN.
5. STEEL BEAMS ARE NOTED ON PLAN AS FOLLOWS:
T.O.S. EL.=XXX'-XX" T.O.S. EL.=XXX'-XX"
(AREA ELEVATION) (SPOT ELEVATION)
W14x22, c=1"
BEAM MARK
CAMBER AT
MID . LENGTH
5K 5K
BEAM END
REACTION
(SERVICE)
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
HIGH ROOFFRAMING PLAN
S203
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
SCALE: 1/8" = 1'-0"
HIGH ROOF FRAMING PLAN1
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGN
'0 011 1w1 I I 1
A
II
A
II I
QI I I I
I I I I I I II I -I-- H---I I I~I HW~T~7
~\ (~\/
A,
2%W w
ON ft
_V-NI I
I II I4--- -4---II
//
\\ /
// /
/N
I1( I JL [~~JL~
*--I-11 F. -711
N
N
L. ~~1
AS -
I
7 -
7F 7
-j
7-
II
I IHI I
I
u 0
T
7N
I II I
NV
7--- -1 7-. -17
7 -7N-1 F- -1 F-
C
-- N11N
-. 4
N
//
/0 0 /
/I- /
/ k~~)_ /4
)-L
M--nlmm
ON)- N 11
ztiLI-
- -~-........... A- ~ U- I.~/I- .. II q
-...........-4...........v~. . -
---4 -~jLE~ 4$%.~/~- '~~w.~tttt'.
)N 11
( I 11
n-
I
)/ /
I -~A
IA
0 1 1 1 1 10I
.1 II
.1A A
IA
~ ~
NOTES:
1. SCHEDULED DOWELS ARE MARKED "DWL" ON THE SECTIONS AND DETAILS.
2. DOWEL SPACING TO BE THE SAME AS SLAB OR WALL REINFORCEMENT UNLESS
OTHERWISE NOTED ON DETAILS.
DOWEL SCHEDULE
MARK SIZE A B
DWL A #4 8" 3'-0"
DWL B #4 2'-6" 3'-0"
DWL C #4 - 4'-0"
DWL D #4 8" 6'-0"
DWL E #4 - 6'-0"
B
A
STANDARD HOOK SCHEDULE
BAR SIZE D180° HOOK 90° HOOK
A or G J A or G
#3 2 1/4" 5" 3" 6"
#4 3" 6" 4" 8"
#5 3 3/4" 7" 5" 10"
#6 4 1/2" 8" 6" 12"
#7 5 1/4" 10" 7" 1'-2"
#8 6" 11" 8" 1'-4"
#9 9 1/2" 1'-3" 11 3/4" 1'-7"
J
D
D
A o
r G
12
db
A or G
2 1/2" MIN.
4 db or
db
#10 10 3/4" 1'-5" 1'-1 1/4" 1'-10"
#11 1'-7" 1'-2 3/4" 2'-0"12"
PLAN
RECTANGULAR,
SQUARE OR ROUND
BLOCKOUT IN SLAB-
ON-GRADE
#4 x 2'-6" EA SIDE
OF BLOCKOUT AT
MID DEPTH OF
SLAB (NOT REQ'D
AT BLOCKOUTS
LESS THAN 4" IN
THEIR LONGEST
DIMENSION)
MAX.
.1' - 0"
EDGE OF CONCRETE
SLAB-ON-GRADE
(2)-#4 x 3'-0" @ ALL
RE-ENTRANT CORNERS NOT
ALIGNED WITH CONTROL JOINT.
PLACE MID DEPTH OF SLAB.
PLAN
1 1
/ 2"
3"
PLAN - TWO CURTAINS OF REINFORCEMENT
PLAN - ONE CURTAIN OF REINFORCEMENT
NOTES:
1. WHERE 90 DEGREE HOOKS ARE SCHEDULED OR DETAILED FOR BARS, CORNER BARS MAY BE OMITTED FOR THAT LAYER.
2. MATCH SIZE, LOCATION AND NUMBER OF HORIZONTAL BEAM AND WALL BARS, EXCEPT THAT WHERE THERE ARE
MORE THAN 2 TOP OR BOTTOM BARS, ONLY THE INSIDE AND OUTSIDE BARS MUST BE MATCHED.
(2) CORNER BARS
CORNER BARS EACH FACE TO MATCH
SMALLER BAR AT INTERSECTION.
PROVIDE CORNER BARS SHOWN AT
TOP, BOTTOM, AND INTERMEDIATE
HORIZONTAL BARS
STOP ENDS OF DETAILED
REINFORCEMENT 2"
SHORT OF FORM, TYP.
(3) CORNER BARS
ADD (2) VERTICAL
REBAR TO MATCH
VERT. REINFORCEMENT
ADD VERTICAL REBAR
TO MATCH VERT.
REINFORCEMENT
ADD VERTICAL
CORNER BAR
CORNER BARS EACH FACE
TO MATCH TOP, BOTTOM, AND
INTERMEDIATE HORIZONTAL BARS
IN DISCONTINUOUS MEMBER
INTERSECTIONS CORNERS
INTERSECTIONS CORNERS
EA. LEG TYPICAL
CLASS "A" DIA.
SPACING
TYP. TYP.
1/2 SPACING
EAC
H L
EG T
YPIC
AL
CLA
SS "
A"
DIA
.
EAC
H L
EG T
YPIC
AL
CLA
SS "
A"
LAP
EACH LEG TYPICAL
CLASS "A" LAP
REINFORCEMENT SPLICE LENGTH SCHEDULE
f'c=3000 psi
CONCRETE
BAR SIZE"A" "B"
#3 1'-5" 1'-10"
#4 1'-10" 2'-5"
#5 2'-4" 3'-0"
#6 2'-9" 3'-7"
#7 4'-1" 5'-3"
#8 4'-7" 6'-0"
#9 5'-2" 6'-10"
NOTES:
1. WHERE SPLICE TYPE IS NOT INDICATED, USE CLASS "B" SPLICE.
2. LAP LENGTHS LISTED ABOVE APPLY UNDER THE FOLLOWING CONDITIONS:
A. BEAM & COLUMN BARS ARE SPACED AT LEAST 1 BAR DIAMETERS O.C. WITH CLEAR COVER NOT LESS THAN 1 BAR DIAMETER.
B. WALL & SLAB BARS ARE SPACED AT LEAST 2 BAR DIA. O.C.
C. FOR UNCOATED AND ZINC-COATED (GALVANIZED) REINFORCEMENT.
D. FOR REINFORCEMENT THAT CONFORMS DEFORMED NEW BILLET STEEL BARS IN ACCORDANCE TO ASTM A615 GR. 60.
3. WHERE CLEAR COVER OR CLEAR SPACING FOR MASONRY REINF. IS LESS THAN 5 BAR DIAMETERS, INCREASE SPLICE LENGTHS
SHOWN BY MULTIPLYING LENGTHS BY MAX. RATIO OF 5 BAR DIAMETERS TO CLEAR COVER OR SPACING.
4. FOR HORIZ. TOP BARS w/ 12" OF CONCRETE CAST BELOW, MULTIPLY TABULATIONS BY 1.3.
5. WHERE A LARGER BAR LAPS A SMALLER BAR, THE SMALLER SCHEDULED LAP LENGTH APPLIES U.O.N.
6. REFER TO "CONCRETE REINFORCING" SECTION OF THE GENERAL NOTES FOR FURTHER INFORMATION.
7. FOR MASONRY REINFORCEMENT SPLICE LENGTH SCHEDULE, SEE MASONRY DETAILS.
8. FOR LIGHTWEIGHT CONCRETE, MULTIPLY TABULATIONS BY 1.3.
#10
#11
f'c=4000 psi
CONCRETE
"A" "B"
1'-3" 1'-7"
1'-7" 2'-1"
2'-0" 2'-7"
2'-5" 3'-1"
3'-6" 4'-6"
4'-0" 5'-2"
4'-6" 5'-10"
f'c=5000 psi
CONCRETE
"A" "B"
1'-1" 1'-5"
1'-5" 1'-10"
1'-10" 2'-4"
2'-2" 2'-9"
3'-1" 4'-1"
3'-7" 4'-7"
4'-0" 5'-3"
5'-10" 7'-7" 5'-1" 6'-7" 4'-6" 5'-10"
6'-6" 8'-5" 5'-7" 7'-3" 5'-0" 6'-6"
CLASS
HOOK DEVELOPMENT LENGTH SCHEDULE, Ldh
BAR SIZE 3000 psi
#3 9"
#4 11"
#5 1'-2"
#6 1'-5"
#7 1'-8"
#8 1'-10"
#9 2'-1"
#10
#11
4000 psi
8"
10"
1'-0"
1'-3"
1'-5"
1'-7"
1'-10"
5000 psi
7"
9"
11"
1'-1"
1'-3"
1'-5"
1'-8"
6000 psi
6"
8"
10"
1'-0"
1'-2"
1'-4"
1'-6"
7000 psi
6"
8"
9"
11"
1'-1"
1'-3"
1'-5"
8000 psi
6"
7"
9"
11"
1'-0"
1'-2"
1'-4"
2'-4" 2'-1" 1'-10" 1'-8" 1'-7" 1'-6"
2'-7" 2'-3" 2'-0" 1'-10" 1'-9" 1'-7"MIN. Ldh
MIN. Ldh
90° HOOKS
180° HOOKS
NOTES:
1. TABULATED VALUES ARE BASED ON GRADE 60 REINFORCING BARS AND NORMAL WEIGHT CONCRETE.
2. FOR TABULATED BARS SIZES ONLY:
A. IF CONCRETE COVER PER ACI 318-08, SECTION 12.5.3(a), THEN A MODIFICATION FACTOR
OF 0.7 MAY BE APPLIED BUT THE LENGTH MUST NOT BE LESS THAN 8 x db NOR 6 IN.
B. IF HOOK IS ENCLOSED IN TIES OR STIRRUPS PER ACI 318-08, SECTION 12.5.3(b),(c), THEN A
MODIFICATION FACTOR OF 0.8 MAY BE APPLIES BUT THE LENGTH MUST NOT BE LESS THAN
8 x db NOR 6 IN.
3. FOR EPOXY-COATED HOOKS, MULTIPLY THE TABULATED VALUES BY 1.2.
4. FOR LIGHTWEIGHT CONCRETE, MULTIPLY THE TABULATED VALUES BY 1.3.
C.J. EDGE OF CONC.
1' -0"
INTERMITTENT ABOVE GRADE CONTINUOUS BELOW GRADE
2x4 x 1'-0" SHEAR
KEY @ 2'-0" O.C.
CONT. W.S.
BELOW GRADE
WHERE NOTED
2x4 CONT. SHEAR KEY
1' -0"
1' -0"
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
CONCRETE TYPICALDETAILS
S301
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
STANDARD DOWEL SCHEDULE1
TYPICAL DETAIL
NO SCALE
STANDARD HOOK SCHEDULE6
TYPICAL DETAIL
NO SCALE
ADDITIONAL REINFORCING AT BLOCKOUT2
TYPICAL DETAIL
NO SCALE
RE-ENTRANT CORNER REINF.3
TYPICAL DETAIL
NO SCALE
WALL OR GRADE BEAM REINFORCING5
TYPICAL DETAIL
NO SCALE
LAP SPLICE SCHEDULE4
TYPICAL DETAIL
NO SCALE
GRADE BEAM SHEAR KEY AT HORIZONTAL JOINT7
TYPICAL DETAIL
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGN
'V / /-z4½
'V I
L 11
"I
V 00
I--- --- Vr-ZZ'
0 00
___V,--
'V'V
ol--Ool
II /
/&
00
,---I
I
0
I &00
I W-
'A-Alh
jv-
M -. nY7-
ZiaLI.-A
-..................
.. ... . . . ...... . ... .
C)
ola]C
V2
) -1.
A ' "/
/A ' 1.11
-r /
-Zv 1.
I-
//
vI,
/'N._ 7
v
A
3/4" CHAMFER#3 CONT.
#3 x 6" @ 24" AROUND
PERIMETER OF PAD
ROUGHEN
FLOOR SLAB
#3 @ 24" O.C.
(4)-#3 CONT.
ROUGHEN
FLOOR SLAB
9" MAX.
OR
MEC
H.
REF
. AR
CH
.
3/4" CHAMFER
THAN 9"
MORE
OR
MEC
H.
REF
. AR
CH
.
1 1
/2"
CLR
.
NOTE:
PROVIDE CONSTRUCTION JOINTS @ 20'-0" O.C. MAX. ELEVATION
4 ADD'L STIR.
BEAM REINF. CONT. THROUGH (NOT
SPLICED) CONSTRUCTION JOINT
CONSTRUCTION JOINT SHALL BE LOCATED
WITHIN 2'-0" OF CL. OF MIDSPAN
6" 6" 6" 6"
WIDTH = BEAM WIDTH -6"
3 1/2" DEEP SHEAR KEY
"D"
DEP
TH O
F B
EAM
1/3
"D
"1
/3 "
D"
1/3
"D
"
NOTE:
DO NOT LOCATE WITHIN
4'-0" OF POINT LOAD.
EQUIPMENT PAD
3/4" CHAMFER
#4 @ 12" EA. WAY
#4 x 6" EPOXY @ 24"
AROUND PERIMETER OF
PAD (4" EMBED)
ROUGHEN
FLOOR SLAB
NOTES:
1. PADS PER DETAIL TO BE PROVIDED UNDER EQUIPMENT SUPPORTED ON
SLAB-ON-GRADE OR ELEVATED SLABS.
2. COORDINATE MECHANICAL PAD SIZE, LOCATION AND EMBEDDED ITEMS WITH
MEP DRAWINGS AND EQUIPMENT MANUFACTURER.
OR
MEC
H'L
REF
. AR
CH
'L
1 1
/2"
CLR
.
SUPPORTS, WHICHEVER APPLICABLE
MIN. 6" LARGER ALL AROUND
THAN EQUIP. OR INERTIA PAD
8"
(6"
MA
X.)
ELEVATION
SECTION "A"
HORIZ. REINF. IS CONT.
THROUGH JOINT.
NOTES:
1. THIS DETAIL APPLIES TO GRADE BEAMS DEEPER THAN 4'-0" AND ALL WALLS.
2. HORIZ. REINF. (NOT SHOWN) IS CONT. THRU CONSTRUCTION JOINT.
2 ADD'L STIRRUPS OR VERT. BARS EA.
SIDE OF JOINT IN ADDITION TO SCHED.
OR DETAILED REINF.
KEY WIDTH
T W
≤12"
12"-16"
16"-20"
20"-24"
24"-30"
CONST. JOINT WITHIN
2'-0" OF CL OF SPAN U.O.N.
3 1/2"
5 1/2"
7 1/4"
9 1/4"
11 1/4"
T
EQ.
WEQ
.
SHEAR KEY
1 1/2" DEEP
1' -
0"
1' -
0"
1' -
0"
....
"A"
REINFORCING TO BE
CONTINUOUS THROUGH JOINT
INTERMITTENT 1'-0" LONG
SHEAR KEY @ 2'-0" IF JOINT
IS ABOVE GRADE
CONTINUOUS KEY AND
WATERSTOP IF JOINT IS
BELOW GRADE
KEY WIDTH
"T" "W"
≤12" 3 1/2"12"-16"
16"-20"
20"-24"
24"-30"
1 1
/2"
"T" (WALL THICKNESS)
5 1/2"
7 1/4"
9 1/4"
11 1/4"
1/3 "T"4"4"4"
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
CONCRETE TYPICALDETAILS
S302
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
STRUCTURAL SLAB MECHANICAL CURB1
TYPICAL DETAIL
NO SCALE
BEAM CONSTRUCTION JOINT2
TYPICAL DETAIL
NO SCALE
MECHANICAL PAD5
TYPICAL DETAIL
NO SCALE
DEEP GRADE BEAM AND WALL VERTICAL CONSTRUCTION JOINT3
TYPICAL DETAIL
NO SCALE
HORIZONTAL CONSTRUCTION JOINT IN CONCRETE WALL4
TYPICAL DETAIL
NO. DESCRIPTION DATE
ARCHITECTUREBUILDING SCIENCE INTERIOR DESIGN
IA L y/
L
I
z , ,, ,, , t. , , lw
U
Ut
0
'1~ I 0
7
I I \ \\ \ I I \
/ i K
L
/
VN
I II \ \
N
1 I
V
v1
I N \I I
-7
/ /
-74
F
0 0
%-
IirIS
I IM -- lmm-
ZiaLI-A
ZVIa....... ........... . . ..
.....................
e ;:
e /
ELEVATION
T.O. PIER EL.
INCREASE SHAFT DIAMETER
AS REQUIRED FOR CASED
HOLES TO ALLOW FOR CASING
SPIRAL OR TIES AS SCHEDULED.
PROVIDE ONE COMPLETE FLAT
TURN TOP AND BOTTOM.
BEARING STRATUM
(SEE DRILLED PIER NOTES)
SEE PLAN FOR TOP OF PIER
ELEVATION AND DETAIL REFERENCE.
SEE DRILLED PIER
SCHEDULE FOR SHAFT
DIAMETER AND
REINFORCINGBO
TT
OM
OF
CA
SIN
G
FOR
CA
SED
PIE
RS
.
30
FT.
FO
R E
STIM
ATI
NG
PU
RP
OSE
S
ESTI
MA
TED
AV
ERA
GE
DEP
TH T
O B
EAR
ING
STR
ATU
M
PIT
CH
PEN
ETR
ATI
ON
SEE
SC
HED
ULE
6"
3"
SHAFT DIA.
3" CLR.
NOTE:
1. VERT. REINF. SHALL BE CLASS "A" SPLICED, TYP.
2. VERT. REINF. FOR TENSION "T" PIERS SHALL BE CLASS "B" SPLICED.
3. ROUND TIES THUS: MAY BE USED IN LIEU OF SPIRALS. TIE LAP
SHALL BE 18" MINIMUM.
T.O. PIER EL.
NOTE:
CLASS "A" SPLICE DIM. TO BE
INCREASED TO CLASS "B"
SPLICE AT PIERS NOTED
TENSION "T" ON PLAN.
DWLS TO GRADE BEAM OR WALL
SHALL BE SAME SIZE AND NUMBER
AS VERTICAL BARS IN PIER - HOOK
REINF. w/ STD. HOOK WHERE REQ'D
SPLICE LENGTH EXCEEDS GRADE
BEAM DEPTH.
SPLI
CE
CLA
SS "
A"
SPLI
CE
CLA
SS "
A"
2"
CLR
.
TYP.
3"
T.O. PIER EL.
EXTEND PIER REINF. INTO GRADE
BEAM OR PIER CAP AS SHOWN.- HOOK
REINF. w/ STD. HOOK WHERE REQ'D
SPLICE LENGTH EXCEEDS GRADE
BEAM/PIER CAP DEPTH
NOTE:
CLASS "A" SPLICE DIM. TO BE
INCREASED TO CLASS "B" SPLICE AT
PIERS NOTED TENSION "T" ON PLAN.
SPLI
CE
CLA
SS "
A"
2"
CLR
.
STIRRUP SPA.
AS INDICATED
STIRRUP SPA.
AS INDICATEDTYP. EA.
SPAN
PROVIDE 90° HOOKS FOR TOP
BARS AT END SPAN OR
DISCONTINUOUS ENDS
TOP, BOTTOM, & SIDE
BARS AS DETAILED OR
SCHEDULED
DO NOT SPLICE TOP
BARS IN CANTILEVER
CLASS "A" BAR SPLICE
FOR TOP & SIDE BARS AT
MIDSPAN U.O.N.
CLASS "A" BAR SPLICE
FOR BOTTOM BARS AT
SUPPORT U.N.O.
CONCRETE PIER
SEE PLAN
CL. OF END SUPPORT CL. OF INTERIOR SUPPORT CL. OF INTERIOR SUPPORTEND SPAN INTERIOR SPAN CANTILEVER SPAN
2". .
2"
BEAM STIRRUPS
TOP BARS
2 BARS x 2'-0" SAME SIZE AS
BARS IN DEEPER BEAM
BOTTOM BARS IN
DEEPER BEAM
BOTTOM BARS IN
HIGHER BEAM
3' - 0"
SECTION "A"
2 ADDITIONAL STIRRUPS @ 4" O.C.
(TYP. EACH SIDE OF PIPE SLEEVE(S))
2 ADDITIONAL STIRRUPS (MIN.)
BETWEEN SLEEVES, TYP.
PROVIDE SLEEVES FOR ALL
PIPES I.D. 2" LARGER THAN
PIPE O.D., TYP.
MA
X.
SLE
EVE
O.D
≤ D
/3 O
R 1
2"
6"
MIN
.6
" M
IN.
GR
AD
E B
EAM
DEP
TH "
D"
TUR
ND
OW
N
SLA
B
MIN.
6"
1 1/2"
"A"
NOTE:
DO NOT INSTALL PARALLEL TO GR. BMS.,
INSTALL PERP. TO GR. BMS.
ELEVATION
PROVIDE EXTRA BARS IN EACH FACE,
ON EA. SIDE OF OPENING EQUAL TO
HALF OF THE AREA OF INTERRUPTED
BARS (1-#5 EACH FACE EACH SIDE 3"
MIN. O.C. LARGER OF).
#5 x 4'-0" EACH FACE, EACH
CORNER. PLACE INSIDE OF
TYPICAL WALL REINFORCING.
EXTEND VERTICAL BARS
FULL STORY HEIGHT
TYPICAL WALL
REINFORCING
PROVIDE STD. HOOK
2' - 0" MIN. OR
CLEAR
1 1/2".
BEAM STIRRUPS
BOT. BARS
2 BARS x 2'-0" SAME SIZE AS
BARS IN DEEPER BEAM
TOP BARS IN
DEEPER BEAM
TOP BARS IN
HIGHER BEAM
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
CONCRETE TYPICALDETAILS
S303
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
DRILLED PIER1
TYPICAL DETAIL
NO SCALE
DRILLED PIER SCHEDULE2
TYPICAL DETAIL
NO SCALE
NARROW BEAM OR WALL BEARING ON WIDER PIER3
TYPICAL DETAIL
NO SCALE
WIDE GRADE BEAM OR PIER CAP BEARING ON NARROW PIER4
TYPICAL DETAIL
NO SCALE
GRADE BEAM REINFORCING7
TYPICAL DETAIL
NO SCALE
STEP IN BOTTOM GRADE BEAM5
TYPICAL DETAIL
NO SCALE
HORIZONTAL PIPE PENETRATIONS THROUGH GRADE BEAM8
TYPICAL DETAIL
NO SCALE
REINF. AT CONCRETE WALL OPENING6
TYPICAL DETAIL
DRILLED PIER SCHEDULE
Mark
SHAFT
DIAMETER
VERTICAL
REINFORCING SPIRALS PENETRATION
P24 24"
P30 30"
NO SCALE
STEP IN TOP GRADE BEAM5A
TYPICAL DETAIL
(6) - #6 #3 @ 12" O.C. 2' - 0"
(6) - #7 #3 @ 12" O.C. 2' - 0"
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMIDESIGNof
(KO P P
>4 _
/
__ KN
AI' 1100,(7:)
/
/
ool`0
IV
/p
/ 4\44' 4' 44 44 44 44 44 44 44 44 44 44 44 44 44
I4
4II qp 40 ql 10 44 10 11 10 44 44I' qp IP qp qp Ip 11 '4 IP
N -
_ 7_ _
<V -- x1N
- N/
1N
- N'
ol/ 1\
-............ .... ... .. ... ... .. ... ... io
/ 7
IN
0
A /
ill I
N
N
N
08 -ZZ'-L- 2~
0 a
N 11 v
4 A4of ol-- o 0
T.O. PIER EL.
SEE PLAN
MAX. TORQUE (ft.-lbs)
EMBEDMENT FOR HAS STD.
30 75 150
CLEAN HOLE w/ WATER OR AIR
PER MFR'S INSTRUCTIONS & FILL
w/ SPECIFIED ANCHORING
ADHESIVE
SEE SECTIONS FOR
ANCHOR DIAMETER
EXISTING CONCRETE
OR MASONRY
ADHESIVE ANCHOR NOTES:
1. REFER TO GENERAL NOTES FOR ADHESIVE ANCHOR TYPE.
2. LOCATE EXISTING REINFORCING STEEL IN THE CONCRETE USING
NON-DESTRUCTIVE METHODS & POSITION ANCHOR LOCATIONS TO
AVOID CONFLICTS WITH EXISTING REINFORCING. ANCHOR LOCATIONS
CAN BE ADJUSTED BY A MAXIMUM OF 1 1/2" FROM DETAILED
LOCATIONS TO AVOID CONFLICTS, UNLESS NOTED OTHERWISE.
3. BASED ON FIELD VERIFIED LOCATIONS OF REINFORCING STEEL &
EMBEDDED ITEMS, THE CONTRACTOR SHALL CREATE TEMPLATES FOR
EACH ANCHOR GROUP.
4. ALL ABANDONED HOLES SHALL BE FILLED WITH NONSHRINK GROUT.
5. HOLES IN CONNECTION PLATES SHALL BE NO MORE THAN 1/16"
LARGER THAN THE ANCHOR DIAMETER. IF LARGER HOLES ARE REQUIRED
FOR ERECTION PURPOSES, PROVIDE 1/4"x3x3 PLATE WASHERS
CONTINUOUSLY WELDED TO THE CONNECTION PLATE.
ANCHOR INSTALLATION INFORMATION
ANCHOR DIAMETER
HOLE DIAMETER
4 1/4" 5" 6 5/8"
SEE TABLE
EMBEDMENT
9/16" 11/16" 13/16"
3/4"5/8"1/2"
EXISTING
CONCRETE
ADHESIVE DOWEL NOTES:
1. REF. GENERAL NOTES FOR ADHESIVE DOWELING SYSTEMS.
2. LOCATE EXISTING REINFORCING STEEL IN THE CONCRETE USING NON-DESTRUCTIVE
METHODS & POSITION DOWEL LOCATIONS TO AVOID CONFLICTS WITH EXISTING
REINFORCING.
3. ALL ABANDONED HOLES SHALL BE FILLED WITH NONSHRINK GROUT.
HOLE DIAMETER:
1/2"Ø FOR #3 DWLS.
5/8"Ø FOR #4 DWLS.
3/4"Ø FOR #5 DWLS.
SEE SECTIONS FOR
DWL. SIZE & LENGTH
NEW CONCRETE
CLEAN HOLE w/ WATER OR AIR PER
MFR'S's INSTRUCTIONS FILL w/
SPECIFIED ANCHORING ADHESIVE
6" FOR #5 DWLS
4" FOR #4 DWLS
4 1/2" FOR #4 DWLS
FIN. FLR. EL.
REF. ARCH.
T.O.S.C. EL.
SEE PLAN
RAMP
NOTE:
REF. ARCH. FOR PLAN DIMENSIONS OF BUILT UP
FLOOR AREA. LOCATE RAMPS & STAIRS ACCORDINGLY.
STRUCTURAL FLOOR
6x6xW2.1xW2.1 PLACE
1" FROM TOP OF CONC.
STYROFOAM FILL.
MIN.
8"
4"
MIN
.
OF RAMPS
1-1/2" DEEP x 1' - 0"
WIDE KEY @ BASE #3 NOSING BAR
T.O. PIER EL.
FORM UP BOTTOM OF
BEAM AND REMOVE
FORMS BEFORE
BACKFILLING OR FILL
VOID WITH CARTON
FORMS
MOTZBLOCK HIGH DENSITY
POLYETHYLENE SOIL
RETAINER BY M&M
CONSTRUCTION
SPECIALTIES. EMBED INTO
CLAY TO OBTAIN FIRM
SEATING.
VOID
SPACE
REF.-NOTE 4 AT CRAWL
SPACE
FORM BOTH SIDES OF
GRADE BEAMS, TYP.
VOID FORM & VOID RETAINER NOTES:
1. FORM VOID SPACE WITH SOIL RETAINERS UNDER ALL STRUCTURAL CONCRETE PIER CAPS,
PILASTERS, GRADE BEAMS, AND WALLS BELOW GRADE
2. INSTALL SOIL RETAINERS IN ACCORDANCE WITH MANUFACTURER'S RECOMENDATIONS
AND AS FOLLOWS:
a. PLACE BASE OF SOIL RETAINER IN A 3" DEEP TRENCH CUT IN UNDISTURBED SOIL OR
COMPACTED FILL. TRENCHES SHALL BE LOCATED 4" FROM OUTSIDE AND INSIDE
FACE OF GRADE BEAM OR WALL PANEL
b. STARTING AT END OF BEAM OR WALL PANEL, LAY BOTTOM FLANGE OF SOIL
RETAINER IN TRENCH AND LEAN FLAT SIDE AGAINTS BEAM OR WALL PANEL.
OVERLAP SIDE FLANGES AT LEAST 1" TO PROVIDE A CONTINUOUS SEAL
c. CUT RETAINERS TO FIT ENDS OF BEAMS OR WALL PANELS. MITER CUT OR BEND
RETAINERS AT CORNERS. CUT LENGTHS LESS THAN 1'-0" IN LENGTH SHALL NOT BE USED
d. PLACE BACKFILL AS SPECIFIED AFTER COMPLETION OF SOIL RETAINER INSTALLATION.
TAKE NECESSARY PRECAUTIONS TO PROTECT SOIL RETAINERS FORM DAMAGE FROM
COMPACTION EQUIPMENT.
3. STORE RETAINERS FLAT AND PROTECTED FROM DIRECT SUNLIGHT TO AVOID WARPAGE
4. VOID RETAINER IN CRAWL SPACE MAY BE OMITTED WHERE CRAWL SPACE GRADE IS AT
BOTTOM OF VOID. USE CONCRETE MUDSLAB AT LEAST EQUAL TO GRADE BEAM WIDTH TO
SUPPLEMENT LATERAL RESTRAINT FOR BOTTOM OF RETAINER.
5. DESIGN OF SOIL RETAINERS IS THE RESPONSIBILITY OF THE CONTRACTOR & SHALL RESIST
THE FULL HYDROSTATIC PRESSURES NOTED IN THE STRUCTURAL NOTES. SUBMIT
CALCULATIONS SIGNED & SEALED BY AN ENGINEER LICENSED IN THE STATE OF TEXAS.
4"
"3
1' -
0"
FILL & VOID RETENTION DETAIL
6"6"
MODULAR LENGTH
ELASTROMERIC SHEET
FLASHING - (SECURE
TO FACE OF BEAM -
LOOSE AT TOP OF FILL
SLAB)
ELASTROMERIC SHEET
FLASHING - SECURE
TO FILL-SLAB PRIOR
TO INSTALLATION OF
TOP SLAB
COMPACTED
BACK FILL
CONCRETE GRADE
BEAM
VOID BOX
COMPACTED
BACK FILL
UNDISTURBED EARTH
NOTE:
BOTTOM MUST BE PLACED
IN UNDISTURBED EARTH
1 1/2"
NOTE:
REPLACE CARTON FORMS THAT HAVE BEEN DAMAGED OR IF
THEYBECOME SATURATED AND WEAK. TAKE SPECIAL CARE TO PREVENT
CRUSHING OF CARTON FORMS DURING PLACEMENT OF REINFORCING
AND CONCRETE.
VAPOR BARRIER OVER PROTECTION
BOARD OVER CARTON FORMS
MIN
.
1' -
0"
CARTON FORMS
SEE PLAN FOR SLAB
THICKNESS & REINF.
(4) - #5 x DOWELS
w/ (4) - #4 HORIZ.
SEE PLAN FOR PIER
REFERENCES, TYP.
VOID FORMS
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
CONCRETE TYPICALDETAILS
S304
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
ADHESIVE ANCHOR FOR SOLID & GROUTED MASONRY & CONCRETE4
TYPICAL DETAIL
NO SCALE
ADHESIVE DOWELING5
TYPICAL DETAIL
NO SCALE
BUILT-UP FLOOR CONSTRUCTION6
TYPICAL DETAIL
NO SCALE
FOUNDATIN VOID SPACE2
TYPICAL DETAIL
NO SCALE
FOUNDATIN VOID SPACE1
TYPICAL DETAIL
NO SCALE
FOUNDATION VOID SPACE3
TYPICAL DETAIL
NO SCALE
TOP OF PIER DETAIL7
TYPICAL DETAIL
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMIDESIGN1) N I ?
~jL_ _ _ _
N
N.
I II
N
K~t
e__
/
Ii
I10
/ ~ I
'9
G
................... ......... ......i
K
1 0 0 09 9 9 0
0 0 <>
/'1,"..xx x X.",M l -
Im 9-
-ZI*-%
T.O. PIER EL.
REF. PLAN
T.O. BR. LEDGE EL.
REF. ARCH.
FINAL GRADE
REF. ARCH.
T.O.S.C. EL.
REF. PLAN
T.O.S.C. EL.
REF. PLAN
T.O. PIER EL.
REF. PLAN
T.O. PIER EL.
REF. PLAN
T.O.S.C. EL.
REF. PLAN
T.O.S.C. EL.
REF. PLAN
T.O.S.C. EL.
REF. PLAN
T.O. PIER EL.
REF. PLAN
T.O. PIER EL.
REF. PLAN
T.O.S.C. EL.
REF. PLAN
BM. REINF.
(3) #8 T&B
#4 HORIZ. @ 12" O.C.
#4 STIR. @ 12" O.C.
SOIL RETAINER
BY OTHERS
LAPPED BLDG PAPER
OR POLY. REF.- , TYP.
MUD SLAB FOR
RETAINER KICKER
REF
. AR
CH
.
VA
RIE
S,
#4x CONT
#4
EA. KEYWAY (TYP.) BRG
2'-6"
SLOPE SUBGRADE PER CIVIL. PROVIDE
15mil VAPOR BARRIER ON TOP OF
SUBGRADE PER MANUFACTURER'S
RECOMMENDATIONS FOR CRAWLSPACE
APPLICATIONS. REF.-MEP FOR DRAINAGE
& CIVIL FOR GRADING
#4x HAIRPIN @ 48" O.C.
CENTERED IN CIP
6" PROJECTION
H.C. PLANK
TOPPING SLAB
TYP
.
VO
ID,
1' - 10"
11"3"
MASONRY, REF. GEN.
NOTES FOR REINF.,
NOT SHOWN FOR CLARITY
/1 S304
4" TYP.
REF. ARCH. FOR GYM FLOOR FINISH
T.O.S.C. EL. VARIES
REF. ARCH.
REF. PLAN FOR
SLAB REINF.
DWL "B" @ 12" O.C.
H.C. PLANK
#4
EA. KEYWAY (TYP.) BRG
#4x CONT
#4x HAIRPIN @ 48" O.C.
CENTERED IN CIP
6" PROJECTION
2'-6"
TYP
.
VO
ID
BM. REINF.
(3) #8 T&B
#4 HORIZ. @ 12" O.C.
#4 STIR. @ 12" O.C.
1' - 10" 1' - 10" 1' - 10"
LAPPED BLDG PAPER
OR POLY
SOIL RETAINER
MUD SLAB FOR
RETAINER KICKER
REF. ARCH. FOR GYM FLOOR FINISH
SLOPE TOP OF
EXTERIOR SLAB AS
REQ'D
1" E.J. BTWN.
GRIDS B.3 & C
#4x CONT
3' - 0"
8" H.C. PLANK EA. SIDE
2'-6"
#4x HAIRPIN @ 48" O.C.
CENTERED IN CIP
6" PROJECTION
#4
EA. KEYWAY (TYP.)
TOPPING SLAB
REF. ARCH. FOR GYM
FLOOR FINISH
BM. REINF.
(5) - #9 T&B
#4 STIR. @ 12" O.C.
#4 HORIZ. @ 12" O.C. E.F.
EC.1C.9
MUD SLAB FOR
RETAINER KICKER
REF. ARCH. & MEP FOR
CRAWLSPACE GRADING
& DRAINAGE
V.I
.F.
3' -
6"
NEW PIER BEYOND
1' - 10"
REF. PLAN
/1 S310
REINF. IN BM. NOT SHOWN
FOR CLARITY, REF.
FOR ADD'L INFO NOT SHOWN
D
4"
H.C. PLANK
#4
EA. KEYWAY (TYP.)
BRG
#4x CONT
#4x HAIRPIN @ 48" O.C.
CENTERED IN CIP
6" PROJECTION
2'-6"
SOIL RETAINER
LAPPED BLDG PAPER
OR POLY
MUD SLAB FOR
RETAINER KICKER
SLOPE SUBGRADE
PER CIVIL
VO
ID, T
YP.
NOTE: REF.
FOR INFO NOT SHOWN
/1 S310CMU BTWN. COL.
NOT SHOWN FOR
CLARITY
REF. S501 FOR
BASE PL. &
ANCHORS
PIER BELOW
PER PLAN
PIER REINF. NOT SHOWN FOR CLARITY;
REF. FOR ADD'L INFO/3 S303
4" MIN., TYP.
STEEL COL. PER PLAN
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
CONCRETE DETAILS
S310
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
SCALE: 3/4" = 1'-0"
SECTION - PERIMETER GRADE BEAM AT STONE VENEER1 SCALE: 3/4" = 1'-0"
SECTION - GRADE BEAM AT SLAB-ON-VOID2
SCALE: 3/4" = 1'-0"
SECTION - INTERIOR GRADE BEAM DETAIL3 SCALE: 3/4" = 1'-0"
DETAIL - COLUMN BASE AT EXIST. BLDG.5SCALE: 3/4" = 1'-0"
SECTION - GRADE BEAM AT SLAB ON VOID4
SCALE: 3/4" = 1'-0"
DETAIL - COLUMN BASE1A
NO. DESCRIPTION DATE
00QARCHITECTURE
I NTERIOR DESIt
Z--I
F-YI-I -- ,A--
C
C
d
- -- - iAP;7 -/-- - '00 / - - 'IF-
=111 -'-I-e s
1177- V iK~~
V V V ->
' O.LON .1 1)
II II
(SN
KTh (eNI. 1.~
1( / .' 640
6
FLof
e__ol
I--
6 6of
_If
-A,
0 ej66 6 6
I. ifi- -
'A____-N
I I
e__ I OP.111 .1 d .1
C)-- 0-
ztiLI-A
0
11 r= l I
C
It............... A.V.
.. ..... ..... ...
L-VI ~i Lz1---~ S F--j
I___________( otl I
QQQQQQQQQQQ(K
S
* 0
6
Kr___ol ol
N
~. 6* - 0 -- !.1
-QV,- ---oll
XV I F-- -E7 -- ]XV
.......................................
V
/-- t-\//ft 41 ____
0- 0- 0-
T.O.S.C. EL.
REF. PLAN
T.O. CURB EL.
REF. PLAN
T.O.S.C. EL.
REF. PLAN
BM. REINF.
(3) #8 T&B
#4 HORIZ. @ 12" O.C.
#4 STIR. @ 12" O.C.
#4
EA. KEYWAY (TYP.) BRG
2'-6"
2
S311
1' - 10"
TOPPING SLAB
H.C. PLANK
#4x CONT
#4x HAIRPIN @ 48" O.C.
CENTERED IN CIP
6" PROJECTION
GRATING,
REF. ARCH.
BR. LEDGE,
REF. ARCH.
/2 S311
GALV. L3X3X3/16 x 4'-0"
w/ 1/2"⌀ x 6" H.S. @
16" O.C.
CONC. WALL, REINF.
w/ #4 @ 12" O.C. E.W.
SLEEVE THRU GRADE BM.,
REF. FOR ADD'L.
REINF. AT OPENING 4"
NOTE: REF. MEP &
CIVIL FOR
DRAINAGE PIPING
REF. CIVIL FOR SITE
PAVING
EQ.
1' -
2"
EQ.
11
"
4' - 0"
2"2"
(2) - #6 x 10'-0" T&B
OF OPENING
(2) - #4 x 3'-0"
DIAG. EA. CORNER
(2) STIRRUPS
EA. END
#4 STIR. @ 6" O.C.
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
CONCRETE DETAILS
S311
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
SCALE: 3/4" = 1'-0"
SECTION - CRAWL SPACE VENT1 SCALE: 3/4" = 1'-0"
SECTION - VENT THRU GRADE BEAM2
NO. DESCRIPTION DATE
2 3 4 5 6 8 10 I I 12 13 14 15 16
FAXP P
ARCHITECTURE
y
PRIOR DI
1517 East Palm Valley Blvd.Round Rock, Texas 78664Phone (512) 255-9690
(512) 388-1843FaxO 0C
REF. CIVIL FOR SITEPAVING
Cunningham-Allen, Inc.3103 Bee Caves Road, Suite #202
Austin, Texas 78746(512) 327-2946
-Q/
-I-QU (2) STIRRUPS
EA. ENDN N
--
F, &u-i
N
-1' Studio 16:19, LLC1717 North Interstate 35
Round Rock, Texas 78664(512) 534-8680
CONC. WALL, REINF.. E.W.
v9
%TYTTTT+, II \ 9pw/ #4 @ 12" O.C(2) - #4 x 3'-0"
DIAG. EA. CORNERK.
1
Ilk 7 * * * . . - - N/ N
M M
Architectural Engineers Collaborative3800 North Lamar Blvd., Suite #330
Austin, Texas 78756(512) 472-2111
I.,~ - --[Z
N* * * a * * 2ZSLEEVE THRU GRADE BM.
\j\I%I41111r6
FORADD'L.REF. 0 x6" H.S. @ dLL,0
-i-f
z~. 7)REINF. AT OPENING 6" O.C.
II4 4 41 4
v
"
L L
of
22
(2) - #6 x 10'-0" T&BOF OPENING
#4 STIR. @ 6" O.C.
O'Connell Robertson811 Barton Springs Road, Suite #900
Austin, Texas 78704(512) 478-7286
NOTE: REF. MEP&CIVIL FOR
DRAINAGE PIPING
41-0"IL
K K
True North Consulting Group13284 Pond Springs Road, Suite #304
Austin, Texas 78729(512) 451-5445
SECTION - CRAWL SPACE VENT SECTION- VENT THRU GRADE BEAM~1
2,
SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0"J i
FMWWW
Lamar Central Austin, Tx 787563800 N. Lamar Blvd. P 512.472.2111
www.aecollab.comSuite 330
FIRM REG.#:AECJOB#:
F-198520014H H
NORTH
KEY PLAN
G G
OF
.. ... ...4JOSHUA BEDRE
..................... 100254 .* 0
07/29/2020ONS/SUBMISSIONS
SEAL
F
RENOVATI
E IE
D D
I NO. DESCRIPTION DATE
C c SHEET INFORMATIONKAH-1908KAH NO.
DATE 07/29/2020AS_DRAWN
CHECKED JB_REVIEWED
DRAWINGTITLE
CONCRETE DETAILSB B
SHEET NUMBER
S311A A
I 2 3 4 5 8 10 11 12 13 14 15 16
NEW
PRA
CTIC
E GY
MNAS
IUM
& W
EIGH
T RO
OM A
DDIT
ION
HERN
ANDE
Z MI
DDLE
SCH
OOL
1901
SUN
RISE
ROAD
ROUN
D RO
CK, T
EXAS
NOTES:
1. LAP LENGTHS LISTED ABOVE APPLY UNDER THE FOLLOWING CONDITIONS:
A. REINFORCING BARS ARE GRADE 60 (Fy=60,000 PSI)
B. MASONRY STRENGTH IS AT LEAST 1,500 PSI
C. WALL BARS ARE SPACED AT LEAST 5 BAR DIA. O.C.
D. CLEAR COVER ASSUMED TO BE 2 1/2" FOR BAR SIZES OF #6 AND LESS.
E. CLEAR COVER ASSUMED TO BE 3" FOR #7 BARS AND 4" FOR #8 AND #9 BARS.
2. WHERE CLEAR COVER OR CLEAR SPACING FOR MASONRY REINF. IS LESS,
INCREASE SPLICE LENGTHS SHOWN BY MULTIPLYING LENGTHS BY MAX.
RATIO OF ASSUMED CLEAR COVER TO ACTUAL CLEAR COVER.
3. WHERE A LARGER BAR LAPS A SMALLER BAR, THE SMALLER SCHEDULED
LAP LENGTH APPLIES.
4. SEE CONCRETE TYPICAL DETAILS FOR DOWELS AND HOOK LENGTHS.
REINFORCEMENT SPLICE
LENGTH SCHEDULE
f'm=1500 psi MASONRY
BAR SIZE MASONRY
#3 1'-4"
#4 1'-9"
#5 2'-8"
#6 4'-6"
#7 5'-3"
#8 6'-0"
#9 6'-9"
CORNERS & JAMBSINTERSECTIONS
VERT. STD. HOOK @ END
OF WALL & OPENINGS, TYP.
ADD (2) VERTICAL REBAR TO
MATCH VERT. REINFORCEMENT
ADD
VERTICAL
CORNER BAR
3 CELLS
JAMB BAR,
SEE DETAIL
TYPICAL
LAP PER SCHED.
SPACING
TYP. SPACING
1/2 TYP.
SPA
CIN
G
1/2
TYP
.
TYPICAL ELEVATION
LAPPING DOWEL, TYP.
FOUNDATION
2 TRIM BARS T&B OF OPNG., PROJ.
BEYOND EACH SIDE OF OPNGS. PER
MASONRY REINFORCING LAP SPLICE
SCHEDULE.
2 TRIM BARS EACH SIDE OF OPNGS.,
FULL HEIGHT OF WALL, TYP.
NOTES:
1. TRIM BAR SIZES TO MATCH WALL REINFORCING, #5 MIN.
2. TRIM BARS ARE IN ADDITION TO TYPICAL WALL REINFORCING
3. VERTICAL STEEL SHALL BE FULL HEIGHT EACH SIDE OF OPENINGS.
ROVIDE LAP PLICES TO MATCH VERTICAL STEEL.
4. APPLIED ONLY TO WALLS 2'-0" OR THINNER. FOR OPENINGS THROUGH
THICKER WALLS, SEE STRUCTURAL ENGINEER FOR SPECIAL DETAILS.
REF. TYP.
LINTEL DETAIL
ALTERNATE
COURSES
SASH
BLOCK
SEE NOTE #1
(TYP. BOTH SIDES)
HARD RUBBER PREMOLDED
CONTROL JOINT INSERT
(TYP.)NOTES:
1. USE SEALANT BOTH SIDES FULL HEIGHT OF WALL.
2. MAXIMUM CONTROL JOINT SPACING IS 20'-0" O.C.
3. WHERE POSSIBLE, POSITION CMU WALL CONTROL JOINT TO COINCIDE
WITH SLAB-ON-GRADE CONTROL/CONSTRUCTION JOINTS.
4. SUBMIT A CMU CONTROL JOINT PLAN TO THE ARCHITECT FOR REVIEW
AND APPROVAL.
5. IN LIEU OF HARD RUBBER PREMOLDED CONTROL JOINT INSERT AND
SPECIAL SASH BLOCKS, A CONTROL JOINT SHEAR BAR (12" LONG x 1"
WIDE x 1/4" THICK) MAY BE GROUTED INTO THE WALL AT THE
CONTROL JOINT AT 16" O.C.
CAST-IN-PLACE (STRAIGHT BAR) CAST-IN-PLACE (HOOKED BAR) DRILLED-IN-ADHESIVE ALTERNATE
NOTES:
1. MASONRY DOWEL TO MATCH SIZE & SPACING OF VERTICAL WALL REINF. TYP.
2. REF. TO REINFORCEMENT SPLICE LENGTH SCHEDULE ON S___ FOR ADD'L INFO.
3. REF. TO __/S___ FOR DIMENSION "A".
REF. SCHED. FOR
WALL REINF. TYP U.O.N.
PROVIDE DOWELS TO MATCH SIZE
& NUMBER OF REINFORCING BARS
IN WALL - TYP.#4 CONT.
STD. HOOK
REF. SCHED. FOR
WALL REINF. TYP U.O.N.
DRILL & ADHERE DOWEL INTO
CONCRETE - REF __/S___ FOR
ADHESIVE DOWEL INFO.
SPLI
CE
CLA
SS "
A"
SPLI
CE
MA
SON
RY
6"
SPLI
CE
MA
SON
RY
8" "A
"
SPLI
CE
MA
SON
RY
OPENING < 4'-0" OPENING 4'-0" TO 10'-0"
LINTEL BLOCKS
REINF. w/ (2) - #5
KNOCK OUT WEB
LINTEL BLOCK -
REINF. w/ (2) - #5
VERTICAL REINF. REF.
STRUCTURAL NOTES
NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR OPENING SIZES
AND LOCATIONS.
2. EXTEND BOND BEAM 8" EACH SIDE OF OPENING.
3. PROVIDE GROUTED VERTICAL CELL EACH SIDE OF OPENING -
GROUT TO UNDERSIDE OF BOND BEAM - REINF. w/ #5.
MASONRY LOOSE LINTEL SCHEDULE
OPENING LINTEL SIZE
L4 x 4 x 5/16
L6 x 4 x 5/16 LLV
L6 x 4 x 3/8 LLV7' - 0" TO 8' - 0"
5' - 0" TO 7' - 0"
UP TO 5' - 0"
NOTE:
1. LINTEL ANGLES SHALL BE HOT DIP GALVANIZED.
2. PROVIDE 3/8" GAP IN MORTAR AT ENDS OF ANGLE. FORM
GAP WITH BACKER ROD.
3. PROVIDE 8" BEARING AT EACH END OF LINTEL ANGLE.
CORNER
END OR JAMB
ADDITIONAL VERT. BAR
ADDITIONAL VERT. BAR
VERT. BAR SPACING
VERT. BAR SPACING
MASONRY VENEER
REF. ARCH.
PL. 5/16" x 3" x 0' - 3"
@ EA. ANCHOR, WELD
TO LEDGE ANGLE
5/8"ø ADHESIVE
ANCHORS @ 24" O.C.
MAX., REF.
L6 x 6 x 5/16 (H.D. GALV.)
ABOVE OPENINGS AT VENEER
CONDITIONS, TYP. AT OPENING
WIDTHS > 6' - 0"
NOTE:
PROVIDE LOOSE LINTEL ANGLES PER
FOR VENEER SUPPORT AT OPENINGS EQUAL TO
OR LESS THAN 6' - 0"
REF. FOR
FOR LINTEL INFO.
6"
AR
CH
.
REF
.
/9 S401
/7 S401
/4 S304
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
MASONRY TYPICALDETAILS
S401
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
MASONRY LAP SPLICE SCHEDULE1
TYPICAL DETAIL
NO SCALE
CMU WALL CORNER REINFORCING6
TYPICAL DETAIL
NO SCALE
MINIMUM REINFORCEMENT AROUND CMU WALL OPENINGS3
TYPICAL DETAIL
NO SCALE
WALL CONTROL JOINT5
TYPICAL DETAIL
NO SCALE
WALL ANCHORAGE2
TYPICAL DETAIL
NO SCALE
LINTEL9
TYPICAL DETAIL
NO SCALE
MASONRY LOOSE LINTEL7
TYPICAL DETAIL
NO SCALE
CMU WALL REINFORCING4
TYPICAL DETAIL
NO SCALE
MASONRY VENEER SUPPORT AT CMU BACK-UP8
TYPICAL DETAIL
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMIDESIGN
I
-A'- F-
//
//
//
//
/
~$
U
v---, ///,I I/
p I I
/
z
/ /I I ol
El El F-I F-I M El [il 11
//
//
I2 2TJAI
k r-, Ar--ir- Ar-~- -, A r-..- Ar -I r I
" L-j " L2 --:i L- I I Li L.j I LI
ED'11£11El
£~7L
121'IEDElED
II-LA0ti
VI
El El El El El 6 F--l F-I F-I El ElWL-jI I
ztiLI.-A
El'2 II
oI
-..............v ............... i-
/-I
A, //-
//
/____________ /
~.~.
--------
II 21
PROVIDE BOND BM. @ TOP.
REINFORCE w/ (2) - #4 CONT.
IN GROUTED SOLID CELL
BOND BM. @ 10-0" O.C.
REINFORCED w/ (2) - #4 CONT.
IN GROUTED SOLID CELLS
INT. WALL VERT. REINF. PER SCHED.
GROUT CELLS WHERE OCCURS.
EXT. WALL VERT. REINF. PER SCHED.
GROUT CELLS WHERE OCCURS.
SEE TOP OF CMU
WALL CONNECTIONS
SEE BOT. OF CMU
WALL CONNECTIONS
WALL THICKNESS
CMU NOMINAL
.
BTW
N H
OR
IZ. B
ON
D B
EAM
S
10
' - 0
" TY
P. M
AX
.
REF
. CM
U W
ALL
SC
HED
. FO
R R
EIN
F.
HEI
GH
T, A
S R
EQU
IRED
L5 x 3 x 1/4 x 0' - 8" LLV
EA. BEAM OR 8'-0" O.C.
MAX. - TYP.
CONT. BOND BEAM
REINF. w/ (2) - #4
CONT. TYP.
L3 x 3 x 1/4 @ 8' - 0" O.C.
MAX.
CONCRETE
CONSTRUCTION
2 1/2"ø EXPANSION ANCHORS w/
2" EMBEDMENT @ 6" O.C.
L5 x 3 x 1/4" x 0' - 8" LLV EA.
SIDE @ 8' - 0" O.C. MAX.
TYP
.
2 1
/2"
CLR
.
3/16TYP.
L5 x 3 x 1/4" x 0' - 8"
LLV EA. SIDE @ L 3 x 3
3/16
(2)-#4 CONT. IN
EACH COURSE
ELEVATION
DOUBLE COURSE
KNOCK OUT LINTEL
BLOCK BOND BEAM
- TYPICAL
(2)-#4 CONT. IN
EACH COURSE
1' - 4"
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
MASONRY TYPICALDETAILS
S402
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
WALL SECTION1
TYPICAL DETAIL
NO SCALE
CMU PARTITION WALL BRACE2
TYPICAL DETAIL
NO SCALE
STEP IN BOND BEAM3
TYPICAL DETAIL
NO. DESCRIPTION DATE
ARCHITECTUREBUILDING SCIENCE INTERIOR DESIGN(
)
1V4-j
1-
-if---
0@
-I
C=7
"V
r - --- , I r-- ,--I
~lv4 ,0//
-if---
-IVP-
'11\
-7-7-
-'F---
(S.
/
'I
I v,L L_
-JvI-
ztiLI.-A
...... ........... . . ..
................. iq
MIL
L
ROD PROJECTION AND
GROUT THICKNESS
ROD PROJECTION AND GROUT
THICKNESS SCHEDULE
2 1/4" TO 2 1/2"
1 3/4" TO 2"
1 1/8" TO 1 1/2"
1" OR LESS
ANCHOR ROD
DIAMETER
1 1/2"
3"
2"
SEE PLAN
FOR COLUMN
BASE PLATE,
REF. SCHEDULE
LEVELING NUTS & WASHER PLS.
ANCHOR RODS, REFER TO
BASE PLATE SCHEDULE
GR
OU
T
SCH
ED. N
.S.
TP
RO
JEC
TIO
N
SCH
ED. B
OLT
2 1/2"
BA
SE P
L. T
HIC
KN
ESS
TYPE "A" TYPE "B"
TOP OF
CONCRETE
NOTES:
1. USE TYPE "A" ROD, TYPICAL, UNLESS NOTED OTHERWISE.
2. USE TYPE "B" ROD AT ALL WINDBRACE LOCATIONS.
3. REF. S531 FOR WINDBRACE ELEVATIONS.
LEVELING NUT &
WASHER, OPTIONAL
HEAVY HEX NUT w/
THREADS FULLY ENGAGED.
WELD NUT TO ROD PRIOR
TO INSTALLATION.
(ALT OPTION: HEADED ROD)
EMB
ED. L
ENG
TH
SCH
ED.
PLA
TE D
ETA
IL
SEE
BA
SE
OR 3 x Ø
LARGER OF 3"
REQ
UIR
ED
THR
EAD
S A
S
REQ
UIR
ED
THR
EAD
S A
S
REQ
'D
AS
EMB
ED. L
ENG
TH
SCH
ED.
PLA
TE D
ETA
IL
SEE
BA
SE
DIA. (Ø)
ANCHOR BOLT 1/2" WASHER,
DIMENSION = ROD Ø + 2"LP
COL. CL.
COL. CL.
NOTES:
1. WELD TO BE MINIMUM SIZE REQUIRED BY
A.I.S.C. FOR THICKNESS OF BASE PLATE USED.
2. SEE DETAIL FOR BASE PLATE ELEVATION.
Y Y
V/2 V/2
V
ZZ
W/2
W/2
W
/1 S501
TYP.
ANCHOR ROD HOLES IN BASE PLATE
ANCHOR ROD
DIAMETERHOLE DIAMETER
MIN. WASHER
DIMENSION
MIN. WASHER
THICKNESS
3/4" 2"
7/8"
1" 3"
1 1/4" 3"
1 1/2"
1 3/4" 4"
2" 5"
2 1/2"
1 5/16"
1 9/16"
1 13/16"
2 1/16"
2 5/16"
2 3/4"
3 1/4"
3 1/4"
2 1/2"
3 1/2"
5 1/2"
5/16"
1/2"
7/8"
1/4"
3/8"
1/2"
5/8"
3/4"
EXT. EDGE OF GR. BM.
EXT. EDGE OF BR. LEDGE
5 1
/2"
3 1
/2"
1 1/2"5 1/2" 5 1/2"
1 1/2"
1' -
0"
1' - 2"
CL
CL COL.
COL.
PL. 1"x1'-0"x1'-2" w/
(4) 3/4" DIA. ANCHOR BOLT
w/ 1'-6" MIN. EMBED
EXT. EDGE
OF GR. BM.
EXT. EDGE OF
BR. LEDGE2"7"3"2"
1 1
/2"
5 1
/2"
3 1
/2"
1 1
/2"
1' - 2"
1' -
0"
CL
CL COL.
COL.
PL. 1"x1'-0"x1'-2" w/
(4) 3/4" DIA. ANCHOR BOLT
w/ 1'-6" MIN. EMBED
EXT. EDGE
OF GR. BM.
EXT. EDGE OF
BR. LEDGE
1 1
/2"
4 1
/2"
4 1
/2"
1 1
/2"1 1/2"
4 1/2" 4 1/2"1 1/2"
1' - 0"
CL
CL COL.
COL.
PL. 3/4"x1'-0"x1'-0" w/
(4) 3/4" DIA. ANCHOR BOLT
w/ 1'-6" MIN. EMBED
1' -
0"
EXT. EDGE OF
GR. BM.
EXT. EDGE OF
BR. LEDGE
1 1
/2"
8"
1"
1 1
/2"1 1/2"
4 1/2" 4 1/2"1 1/2"
1' -
0"
1' - 0"
CL
CL COL.
COL.
PL. 3/4"x1'-0"x1'-0" w/
(4) 3/4" DIA. ANCHOR BOLT
w/ 1'-6" MIN. EMBED
EXT. EDGE OF
GR. BM.
EXT. EDGE OF
BR. LEDGE
1 1
/2"
3"
5"
1"
1 1
/2"1 1/2"
1" 5" 3"1 1/2"
1' -
0"
1' - 0"
CL
CL COL.
COL.
PL. 3/4"x1'-0"x1'-0" w/
(4) 3/4" DIA. ANCHOR BOLT
w/ 1'-6" MIN. EMBED
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
STEEL TYPICALDETAILS
S501
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
COLUMN BASE PLATES1
TYPICAL DETAIL
NO SCALE
ANCHOR ROD2
TYPICAL DETAIL
NO SCALE
BASE PLATE SCHEDULE3
TYPICAL DETAIL
SCALE: 1 1/2" = 1'-0"
BASE PLATE - BP-14 SCALE: 1 1/2" = 1'-0"
BASE PLATE - BP-25 SCALE: 1 1/2" = 1'-0"
BASE PLATE - BP-36 SCALE: 1 1/2" = 1'-0"
BASE PLATE - BP-47 SCALE: 1 1/2" = 1'-0"
BASE PLATE - BP-58
NO. DESCRIPTION DATE
ARCHITECTUREBUILDING SCIENCE INTERIOR DESIGN
v
N INNN.
A AI I I I
O o
IfO
N
N\
62
C/ -
'VEZZj-~
N\
N. N.N. N.
-
I
I r,
ofolI'1~ , 10 I, I I 2' ' '2 I I 2, , oo
0 0
I,,77)7
\N. N.N ~N.N.
O - O
D 0v
~oDO
-0O0
VDto jo
jr I0 0
N.
v 0-g -e-
0
0 0N.
N.
A VN.N. N. N.11N N.K N. I' N.
IT 2IT
10
.....................................
SECTION "A"
WELD 1/4" CAP PL.
@ TOP OF COLUMN
3/8" CONN. PLATES,
SLOT COLUMN FOR
PLATE(S) & WELD ALL
SLOTS CLOSED
NOTE:
PLATES AND CONNECTIONS SHALL BE
DESIGNED BY THE CONTRACTOR IN
ACCORDANCE WITH THE GENERAL NOTES.
PL. FOR THIRD
BEAM IF REQ'D.
1/4
"A"
SPLICE IN COLUMN IF
REQUIRED
1/4
BEAM BELOW GIRDER
BEAM AT GIRDER
STIFFENER PL. - SAME OR
GREATER THICKNESS THAN
UPPER BEAM WEB (3/8"
MINIMUM)
END PLATE, WT & BOLTS
DESIGNED BY FABRICATOR PER
"STRUCTURAL STEEL
CONNECTIONS" STRUCTURAL
NOTES (ALIGN FLANGE OF TEE
w/ UPPER BEAM WEB)
NOTCH WT STEM TO
FIT AROUND UPPER
BEAM FLANGE
END PLATE, WT & BOLTS
DESIGNED BY FABRICATOR PER
"STRUCTURAL STEEL CONNECTIONS"
STRUCTURAL NOTES
TO BE DESIGNED BY
FABRICATOR
NOTES:
1. REF. PLAN FOR BEAM SPLICE LOC'N SPLICES NOT NOTED ON PLAN SHALL BE
SUBMITTED TO ARCH. FOR REVIEW
2. SPLICE CONNECTIONS SHALL BE DESIGNED BY THE CONTRACTOR TO
MEET THE REQUIREMENTS SPECIFIED FOR STANDARD CONNECTIONS IN
THE STRUCTURAL NOTES.
3. PROVIDE SHIM PLATES AS REQ'D.
SUPPORTING BEAM
"DROP-IN" BEAM
PROVIDE HORIZ. SHORT SLOTTED HOLES
IN DROP-IN BEAM FOR ADJUSTMENT
COPE BOTTOM FLANGE OF
DROP-IN BEAM FOR
INSTALLATION
PL. EA. SIDE OF BEAM
(3/8" MIN. THICKNESS)
4".
1/2".
2".
PLAN
SECTION "A"
SECTION "B"
TOP FLANGE OF
BEAM OR JOIST
CL. OF ROOF
BEAM OR JOIST
L3 x 3 x 1/4 BETWEEN
BEAMS (OR JOISTS)
L3 x 3 x 1/4 MITERED
& WELDED FRAME
WELD DECK TO
L FRAME @ 12" -
2 WELDS MIN. EA. SIDE
"B"
"A"
3/16
T.O.S. EL.=
SEE PLAN
L3x3x1/4 CONT.
CL. BEAM
3/16 1 1/2-12
1" MIN.PLAN
REF.
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
STEEL TYPICALDETAILS
S502
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
TUBE COLUMN CONNECTION FOR WEB CONNECTIONS TO BEAM4
TYPICAL DETAIL
NO SCALE
OFFSET BEAM TO GIRDER CONX.5
TYPICAL DETAIL
NO SCALE
BOLTED BEAM SPLICE3
TYPICAL DETAIL
NO SCALE
ROOF OPENING1
TYPICAL DETAIL
NO SCALE
EXTERIOR BEAM PARALLEL TO JOISTS2
TYPICAL DETAIL
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGN
x ;x/r.4
-- o
III
o I
CCD
CCD
j II rIIIIIIIIII
I
'Ah I
r/-77-/;'
I
7 7, 77
\\\\ > I
K
I II II II II I
010
I I01 I
0
0 10
I II III
/=IIv
v+
i i
7,qw Fi +
II\ M -. nY7-
V
I II I
ztiLI-A
4-4
-4
-4
+
+
4-4
- -~::N
:
- -
SUPPORTED BEAM
SINGLE PL. AND NO.
OF BOLTS PER SCHED.
NOTES 1 & 2
SUPPORTING
BEAM/GIRDER
TWO-SIDED CONNECTION - BEAMS TO GIRDERB C
BEAM TO COLUMN FLANGE CONNECTION
W.F. COL.
PER PLAN
SUPPORTED
BEAM
SUPPORTED BEAMSUPPORTING
BEAM/GIRDER
EXTENDED PLATE, BEAM TO COLUMN WEB CONNECTION
SUPPORTED BEAM
WELD 1/4 CAP PL. @
TOP OF COLUMN
WHERE OCCURS
W.F. COL.
PER PLAN
3/8" STIFFENERS
D FSINGLE PLATE CONNECTION SCHEDULE
SUPPORTED BEAM
NOTES:
1. PIPE COLUMN CONNECTION IS SIMILAR.
2. SINGLE SHEAR PLATE CONNECTION SHOWN APPLIES
TO RIGHT ANGLE CONNECTIONS AND SKEWED
CONNECTIONS UP TO 30° FROM RIGHT ANGLE.
FOR HSS COLUMN WITH
b/t > 35.1 AND Fy=46 KSI,
PROVIDE THROUGH-PLATE
EXTENDED PLATE BEAM TO COLUMN
WEB CONNECTIONE
STANDARD SINGLE PLATE CONNECTION
BEAM
SIZE
NO. OF ROWS
OF BOLTS(n)
BOLT
DIAMETER
PLATE
THICKNESS
WELD
SIZE A
MAX. BEAM
REACTION
(KIPS)
W8 2 3/4" 12
W10 2 16
W12 3 24
W14 3 30
W16 4 40
W18 5 50
W21 6 73
W24 7 85
W27 8 97
W30 8 97
W33 8 97
W36 10 140
W40 10 140
W44 10 140
WELD 1/4 CAP PL. @
TOP OF COLUMN
WHERE OCCURS
CL. OF BEAM/GIRDER
CL. OF BOLTS
CL. OF BEAM/GIRDER
CL. OF BOLTS, TYP.
CL. OF COLUMN
CL. OF BOLTS
CL. OF COLUMN
CL. OF BOLTS
NOTES:
1. IF SUPPORTED BEAM IS LESS THAN 1/2
OF BOLTS TO CONNECTION AT GIRDER.
2. EXTEND TAB PLATE TO BOTTOM FLANGE
AT PERIMETER CONDITION.
NOTES:
1. ALL OTHER CONNECTIONS DEVIATING FROM TYPICAL
CONNECTIONS SHALL BE DESIGNED AND DETAILED BY A
PROFESSIONAL ENGINEER WORKING UNDER THE
GUIDANCE OF THE CONTRACTOR. REF. GENERAL
NOTES UNDER "STRUCTURAL STEEL CONNECTIONS."
2. NOTED REACTIONS ARE FOR SERVICE LOADS.
3. BOLTS ARE A325N WITH STANDARD HOLES.
4. SCHEDULED SHEAR PLATE CONNECTIONS APPLY TO
RIGHT ANGLE CONNECTIONS AND SKEWED
CONNECTIONS UP TO 30° FROM RIGHT ANGLE.
5. BEAM CONNECTIONS ARE "STANDARD" UNLESS
OTHERWISE NOTED ON PLAN.
6. WORKLINES ARE ON CENTERLINES OF BEAMS AND
COLUMNS, U.O.N.
7. WELD CAPACITY BASED ON Exx = 70 KSI.
8. CONTRACTOR RESPONSIBLE FOR MEETING ALL
O.S.H.A. REQUIREMENTS.
CL. OF COLUMN
CL. OF BOLTS
PLAN
TOP FLANGE SHOWN CUT
AWAY FOR CLARITY
NOTE:
REF. DETAIL "A" FOR INFO NOT SHOWN
NOTE:
REF. DETAIL "A" FOR INFO NOT SHOWN
NOTE:
REF. DETAIL "A" FOR INFO NOT SHOWN
ONE-SIDED CONNECTION - BEAMS TO GIRDERA
MAX.
1/2".
MIN
.
1 1
/2"
n B
OLT
S
@ 3
" O
.C.
MIN
.
1 1
/2"
MAX.
3".
MAX.
1/2"
"A"
WELD SIZE
PER SCHED.
n B
OLT
S
@ 3
" O
.C.
MAX.
1/2"
MAX.
1/2"
n B
OLT
S
@ 3
" O
.C.
"A"
WELD SIZE
PER SCHED.
n B
OLT
S
@ 3
" O
.C.
"b"
MAX.
1/2"
3"
MAX.
"A"
WELD SIZE
PER SCHED.
MIN
.
1 1
/2"
MIN
.
1 1
/2"
n B
OLT
S
@ 3
" O
.C.
1/4" 1/4"
5/16"
7/8" 3/8"
1/2" 5/16"
MAX.
1/2"
"t"
DOUBLE ANGLE AND
NO. OF BOLTS PER
SCHED.
SUPPORTED
BEAM/GIRDER
SUPPORTING
MEMBER
BOLTED/WELDED DOUBLE ANGLE CONNECTION:
ANGLES WELDED TO SUPPORTING MEMBER
CONNECTION TO
SUPPORTING
MEMBER
CONNECTION TO
SUPPORTED
MEMBER
COPING AS
REQ'D, TYP.
DOUBLE ANGLE AND NO.
OF BOLTS PER SCHED.
SUPPORTING
MEMBER
ALL BOLTED CONNECTION BOLTED/WELDED CONNECTION:
ANGLES WELDED TO SUPPORTED BEAM
CONNECTION TO
SUPPORTED MEMBER
CONNECTION TO
SUPPORTING
MEMBER
BEAM TO BEAM CONNECTIONSA BBEAM TO COLUMN FLANGE CONNECTION
SUPPORTED
BEAM
T.O.S. COL. WHERE
OCCURS
W.F. COL.
PER PLAN
CONNECTION TO
SUPPORTED
MEMBER
CONNECTION TO
SUPPORTING MEMBER
SUPPORTING
MEMBER
C
DOUBLE ANGLE AND NO.
OF BOLTS PER SCHED.
SUPPORTING
MEMBER
SUPPORTING
MEMBER
DOUBLE ANGLE CONNECTION SCHEDULED
BOLTED OR WELDED PER
DETAIL "A"
STANDARD DOUBLE ANGLE CONNECTION
BEAM
SIZE
NO. OF
ROWS OF
BOLTS(n)
BOLT
DIAMETER
ANGLE
THICKNESS
WELD
SIZE C
MAX.
BEAM
REACTION
(KIPS)
W8 2 3/4" 12
W10 2 16
W12 3 24
W14 3 30
W16 4 40
W18 5 50
W21 6 73
W24 7 85
W27 8 97
W30 8 97
W33 8 97
W36 10 140
W40 10 140
W44 10 140
CL. OF BEAM/GIRDER CL. OF BOLTS
CL. OF
SUPPORTED
BEAM &
ANGLES
CL. OF BEAM/GIRDER
CL. OF BOLTS CL. OF BOLTS
CL. OF COLUMN
CL. OF BOLTS
NOTES:
1. REFERENCE SCHEMATIC DETAILS OF TYPICAL STEEL
CONNECTIONS FOR ADD'L INFO.
2. ALL OTHER CONNECTIONS DEVIATING FROM TYPICAL
CONNECTIONS SHALL BE DESIGNED AND DETAILED BY A
PROFESSIONAL ENGINEER WORKING UNDER THE
GUIDANCE OF THE CONTRACTOR. REF. GENERAL NOTES
UNDER "STRUCTURAL STEEL CONNECTIONS."
3. NOTED REACTIONS ARE FOR SERVICE LOADS.
4. BOLTS ARE A325N WITH STANDARD HOLES.
5. SCHEDULED SHEAR PLATE CONNECTIONS APPLY TO
RIGHT ANGLE CONNECTIONS AND SKEWED
CONNECTIONS UP TO 30° FROM RIGHT ANGLE.
6. BEAM CONNECTIONS ARE "STANDARD" UNLESS
OTHERWISE NOTED ON PLAN.
7. WORKLINES ARE ON CENTERLINES OF BEAMS AND
COLUMNS, U.O.N.
8. WELD CAPACITY BASED ON Exx = 70 KSI.
9. TABLE BASED ON LL4x31/2, A36 STEEL.
10. CONTRACTOR RESPONSIBLE FOR MEETING ALL O.S.H.A.
REQUIREMENTS.
CL. OF BEAM/GIRDER CL. OF BEAM/GIRDER
CL. OF BOLTS
CL. OF BEAM/GIRDER
NOTE:
REF. DETAIL "A" FOR INFO NOT SHOWN
1 2
MAX.
1/2"
MIN
.
1 1
/2"
MIN
.
1 1
/2"
n B
OLT
S
@ 3
" O
.C.
1 3/4"
3 1/2" 4".
1 3/4"
MIN
.
1 1
/2"
MIN
.
1 1
/2"
n B
OLT
S
@ 3
" O
.C.
MAX.
1/2"
3 1/2"1 3/4"
4".
MAX.
1/2"
EQ EQ
3 1/2"
MIN
.
1 1
/2"
MIN
.
1 1
/2"
n B
OLT
S
@ 3
" O
.C.
MAX.
1/2"
EQ EQ
1/4" 1/4"
7/8" 5/16" 1/4"
"C" 3/4"
SHORT
RETURN"C"
NOTES:
1) DESIGN SKEW CONNECTIONS FOR REQUIRED SHEAR, REF. GEN. NOTES FOR MORE INFORMATION.
2) ACCOUNT FOR ECCENTRICITIES IN CALCULATIONS.
CL. SUPPORTING
BEAM
BENT DOUBLE
ANGLE
BENT DOUBLE
ANGLE
ø ø
ALL BOLTED BOLTED / WELDED
CL. SUPPORTING
BEAM
ø
DOUBLE BENT
PLATE
DOUBLE BENT
PLATE
ALL BOLTED BOLTED / WELDED
ø
ø
CL. SUPPORTING
BEAM
SINGLE BENT
PLATE
SINGLE BENT
PLATE
ø
ALL BOLTED BOLTED / WELDED ø
0° < ø ≤ 30°
CL. SUPPORTING
BEAM
ø
SINGLE SHEAR
PLATE
END PLATE
BENT DOUBLE ANGLE CONNECTION (0° < ø ≤ 5°)A DOUBLE BENT PLATE CONNECTION (5° < ø ≤ 33°)
BSINGLE BENT PLATE CONNECTION (33° < ø ≤ 71°)
CSINGLE SHEAR PLATE
CONNECTION (0° < ø ≤ 30°)D
END PLATE CONNECTION (0° < ø ≤ 30°)E
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
STEEL TYPICALDETAILS
S503
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
SCHEMATIC SINGLE-PLATE FRAMING CONNECTIONS1
TYPICAL DETAIL
NO SCALE
SCHEMATIC DOUBLE-ANGLE FRAMING CONNECTIONS2
TYPICAL DETAIL
NO SCALE
SKEWED SIMPLE FRAMING CONNECTIONS3
TYPICAL DETAIL
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGN
of
I
I II IK'
INI II II ILyL
IIIIII
olloIIII110
7
I V
4-I
V +I
1 11Ivv
V v
v vV
00 0 0 00
I
pq I.
cc go-41
cc go
00~
-/4--00
C- I-o
01ztiLI-A
J19 V U
I\-
.................
ftwwmv -
V v V
00 0 0= 0
C'C -
-C'
K7~L_::: v K
V 14 iv
0 0 a00
/
~I"
T.O.S. EL.
REF. PLAN T.O.S. EL.
REF. PLAN
T.O.S. EL.
REF. PLAN
METAL DECK
PER PLAN
4 x 4 x 1/4 PL
L2 x 2 x 3/16 @
EVERY JOIST
(WELD AFTER DEAD
LOAD IS IN PLACE)
3/16 1 1/2
3/16 2
NOTE:
REF. ARCH. FOR
MISC. STEEL
NOT SHOWN
L5X3 1/2X3/8 LLH
CONT., U.O.N.
REF. ARCH.
FOR ROOFING
REF. ARCH.
FOR VENEER
L6X4X5/16 x 0'-5" @
24" O.C. w/
(1) - 3/4" Ø x 6"
EMBED. ADH.
ANCHOR IN VERT.
LONG SLOTTED HOLE
KNOCK-OUT WEB
BOND BEAM
REINF. w/
(2) - #4 CONT.
VERT. REINF.
CONT. THRU
BOND BEAM
4"
1/4 2
C6X8.2 @
4'-0" O.C.
MAX.
C6X8.2
CONT.
HSS6X5X1/4 LSH
BTWN. JOISTS
(JOIST SPA. -12")
REF. ARCH.
FOR VENEER
4 x 4 x 1/4 PL
L2 x 2 x 3/16 @
EVERY JOIST
(WELD AFTER DEAD
LOAD IS IN PLACE)
C6X8.2 CONT.
L5X3 1/2X3/8 LLV CONT.
REF. ARCH. FOR ROOFING
REF. MEP FOR DUCTWORK TO BE
ROUTED BELOW BEAM BOTTOM
FLANGE BRACING ANGLES
5"
SECTION "A"
PLAN
L2 1/2 x 2 1/2 x 1/4
JOIST
TOP CHORD
L2 1/2 x 2 1/2 x 1/4 x 0'-6"
BOTTOM FLANGE OF
BEAM (TOP BEAM FLANGE
NOT SHOWN)
PL 3/8" x AS REQUIRED
(OFFSET AS REQUIRED TO
AVOID INTERFERENCE WITH
CRIMPED ANGLE WEB MEMBERS)
COLUMN
PER PLAN
4'-0" MAX.
3'-0" MIN.
"A"
TYP.
4'-0" MAX.
3'-0" MIN.
SECTION "A"
PLAN
L2 1/2 x 2 1/2 x 1/4 CLIP VER.
LEG AT EA. END AS REQ'D
AS SHOWN
BOTTOM FLANGE OF
BEAM (TOP BEAM
FLANGE NOT SHOWN)
COLUMN
PER PLANTYP.
"A"
PLAN
SEE
L2X2X3/16 @ 4'-0" O.C.
@ PERIMETER BEAM
(WELD AFTER DEAD
LOAD IS IN PLACE)
4X4X1/4 PL.
4X4X1/4 PL.
T.O.S. EL.=
REF. PLAN
EXTEND TOP CHORD
WHERE REQUIRED FOR
CONTINUOUS DECK
SUPPORT Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
STEEL JOIST TYPICALDETAILS
S504
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
KCS OR K SERIES STEEL JOIST BEARING ON PERIMETER BEAM1
TYPICAL DETAIL
NO SCALE
LH SERIES STEEL JOIST BEARING ON PERIMETER BEAM2
TYPICAL DETAIL
NO SCALE
COLUMN BRACE JOISTS PARALLEL TO BEAM4
TYPICAL DETAIL
NO SCALE
COLUMN BRACE JOISTS PERPENDICULAR TO BEAM5
TYPICAL DETAIL
NO SCALE
EDGE CONDITION @ JOIST PARALLEL TO BEAM3
TYPICAL DETAIL
NO SCALE6EXTENDED TOP CHORD FOR DECK SUPPORT
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGN
F-1
1>LI11
-AL
VA
L - - - - - --.- - - - -
ol14I II-,- - - - I- -
-11:7 - ri - -1-1- - - -7//'I I
44
I IK
K
K-I -I
I II IK, K, V
+.- 0
-I-- 0
-I -II IztiLI-A
I
Kr
I4-.-~ I VI I
I I
LAVA
?t 11 I
... . . .. . . . .. . ..
.. . . .. . . . .. . . .. .. .
Wt ,) ttw%i
-,*-,4 -Z- -
Kv
JL
I-T
T';
-7
NOTE:
THIS DETAIL APPLIES WHEREVER A
CONCENTRATED LOAD GREATER THAN 50
POUNDS OCCURS BETWEEN PANEL POINTS
OF BOTTOM CHORD JOIST.
LOCATION OF
CONCENTRATED LOAD
L2x2x3/16 WT 3x6 CENTERED ON
BOTTOM CHORD OF JOIST
BOTTOM CHORD
OF JOIST
NOTE:
THIS DETAIL APPLIES WHEREVER A
CONCENTRATED LOAD GREATER THAN 50
POUNDS OCCURS BETWEEN PANEL POINTS
OF BOTTOM CHORD JOIST.
3/16 2-12
3/16 4EACH PANEL JOINT
3"3"NOTE:
TOP CHORD SHALL BE REINFORCED WHEREVER A
CONCENTRATED LOAD IN EXCESS OF 50 LBS. OCCURS
BETWEEN PANEL POINTS OF THE JOIST.
L2 x 2 x 3/16 EACH
SIDE OF JOIST
LOCATION OF
CONCENTRATED LOAD
JOISTS BEAR ON BEAM FROM BOTH
SIDES AT AN ANGLE OTHER THAN
90°, SEE PLAN
HSS3 1/2 x 2 1/2 x 3/16
BETWEEN JOISTS
WELD BOTH DECKS TO TUBE
AS SPECIFIED FOR
"PERIMETER WELDS"
2 1
/2"
3/16 2-12
MECHANICAL UNIT SUPPORTED ON JOISTS
JOIST PANEL
POINT - TYP.
NOTE:
WHERE DIMENSION "A" EXCEEDS
1'-0" EXTEND ANGLE TO NEXT JOIST
PANEL POINT
TOP CHORD REINFORCING
PER
SEE MECHANICAL DRAWINGS
FOR SIZE AND LOCATION OF
ROOF TOP UNITS
C6 x 8.2 AT ROOF TOP
MECHANICAL UNIT CURBS -
EXTEND 3" MIN. PAST ø OF
JOIST AT END CONDITIONS
TYP.
6" A
3/16 2
/3 S505
MECHANICAL UNIT SUPPORTED BETWEEN JOISTS
JOIST PANEL
POINT - TYP.
TOP CHORD REINFORCING
PER
SEE MECHANICAL DRAWINGS FOR
SIZE AND LOCATION OF ROOF TOP
UNITS
C6 x 8.2 BETWEEN JOISTS AT ROOF
TOP MECHANICAL UNITS
NOTE:
1'-0" EXTEND ANGLE TO
NEXT JOIST PANEL POINT
6" "A"
3/16 2
/3 S505
HORIZONTAL BRIDGING
WELD TO BEAM AND JOIST
RIGID X-BRIDGING
BOLTED AT INTERSECTION
HORIZONTAL BRIDGING
WELDED TO BEAM AND JOIST
OF JOIST, MOVE X-BRIDGING BACK ONE BAY
WHERE END BAY DIMENSION IS LESS THAN DEPTHTHIS MEMBER MAY BE PLACED BENEATH JOIST CHORD
FOR ADDITIONAL CLEARANCE. EXTEND ONE JOIST
SPACE BEYOND EACH SIDE OF DUCT
OMIT STANDARD CROSS
BRIDGING AT DUCT
L2 x 2 x 1/4 AT EACH
BRIDGING LINE
3/16EACH JOIST
COLUMN
PER PLAN
1/2" CAP PL
SAME AS COL.
1/2"Ø BOLT EA. SIDE AT "K" &
"KCS" SERIES JOISTS, 3/4" PL
BOLT EA. SIDE AT "LH" SERIES
JOISTS.
PL 3/8" x AS REQ'D
PROVIDE EXTENDED TOP CHORD
WHERE JOIST ON ONE SIDE ONLY
AND AT EXTERIOR BEARING
CONDITIONS
EXTENDED JOIST BOTTOM
CHORD
3/16
1/4 2 1/2
3/16
3/16 2
EXTENDED JOIST
BOTTOM CHORD
L3 x 3 x 5/16 x DEPTH OF
COLUMN + 1"
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
STEEL JOIST TYPICALDETAILS
S505
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
JOIST REINFORCEMENT1
TYPICAL DETAIL
NO SCALE
JOIST BOTTOM CHORD REINFORCEMENT2
TYPICAL DETAIL
NO SCALE
TOP CHORD REINFORCEMENT FOR LH-SERIES JOISTS3
TYPICAL DETAIL
NO SCALE
CHANGE IN DIRECTION OF DECK SPAN4
TYPICAL DETAIL
NO SCALE
MECHANICAL UNIT SUPPORT AT KCS & K-SERIES JOIST7
TYPICAL DETAIL
NO SCALE
MECHANICAL UNIT SUPPORT AT KCS & K-SERIES JOIST8
TYPICAL DETAIL
NO SCALE
BEAM PARALLEL TO JOISTS5
TYPICAL DETAIL
NO SCALE
CROSS BRIDGING AT END BAY FOR K & KCS SERIES JOISTS9
TYPICAL DETAIL
NO SCALE10DUCT OPENING AT CROSS BRIDGING
NO SCALE
JOIST TO COLUMN CONNECTION WITH EXTENDED BOTTOM CHORD11
TYPICAL DETAIL
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGN
4/-4- F -7/
LLDP< H'
K
i
I // \\
/ \ H H1 -I r
L
I / / \ \,AL / \ Architectural Engineers
0 000 c Collaborative I
-/- -/-- / /
/
/ / / /
/ ztiLI.-AA
-.................... .. . .. . ...... .... .
/
A\qA AV I
K
I II I
' \ X vZ71 F, ii 71 F_
IIi I I I
I II II II I
I I
IXJL JL 1 -1
K*JL
M.1
'V'V
1-11,
L.,
T.O. PARAPET
REF. ARCH.
T.O.S. EL.
REF. PLAN
T.O. BEAM EL.
REF. PLAN
T.O. BEAM EL.
REF. PLAN
EC.1
T.O.S. EL. EXISTING LOW
14' - 5"
C.9
S510
2
EXISTING BUILDING
FRAMING
DIAGONAL WIND
BRACE, IN LOC.
NOTED ON PLAN
REF. PLAN
NEW COL.
PER PLAN
C.9 D
REF.
FOR PARAPET
FRAMING
/2 S504
STEEL COL. PER PLAN
REF. ARCH. FOR STONE VENEER
STEEL JOIST PER PLAN
REF. ARCH. FOR ROOFING
REF. PLAN
8 3/8"
REF.
FOR BRACING
@ 4'-0" O.C.
MAX.
/3 S504
CL
HSS BEAM,
REF. PLAN
3/4" Ø HEADED STUD
@ 16" O.C.
CMU WALL PER PLAN,
REINF. PER GEN. NOTES
REF. PLAN
CONT. BOND
BEAM, REINF. w/
(2) #4 CONT.
SLOPE PER PLAN
STEEL JOIST
PER PLAN
CONT. BOND
BEAM, REINF. w/
(2) #4 CONT.
STEEL COL. BEYOND
REF..-1/S5044"
EB.1
SLOPE PER PLAN
REF. ARCH. FOR ROOFING
CB.9
CEILING, REF. ARCH.
STEEL JOIST PER PLAN
REF. PLAN
EXISTING BUILDING
FRAMING
TOP CHORD EXTENSION
L3X3X1/4 CONT.
E611.1
REF. ARCH. FOR ROOFING
EXISTING BUILDING
FRAMING
REF. PLAN
CEILING, REF. ARCH.
STEEL JOIST PER PLAN
L3X3X1/4 CONT.
L3X3X1/4 @ 24" O.C.
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
STEEL DETAILS
S510
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
SCALE: 3/4" = 1'-0"
SECTION - GYM LOW ROOF LEVEL AT EXISTING BLDG.1
SCALE: 3/4" = 1'-0"
SECTION - TOP OF FRAMING AT EXISTING BLDG.6
SCALE: 3/4" = 1'-0"
DETAIL - CMU WALL CONNECTION2 SCALE: 3/4" = 1'-0"
SECTION - LOW ROOF3 SCALE: 3/4" = 1'-0"
SECTION - WEIGHT ROOM LOW ROOF AT EXISTING BLDG.4
SCALE: 3/4" = 1'-0"
SECTION - LOW ROOF EDGE AT EXIST. BLDG.5
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I WINMIDESIGN
10 ol
Uol
I
ol11 10
p
I Lr-
II
0
x12,,,E
V1
-i-iL - 0
/ /
/
4 4
/ /G
I I
I I
r--_
-A I
/
KI II I
4
I II I
p
-1L-
VI
AV
61>
- -~::
N:
- -
ELEVATION
3/8" CAP PL. x
AS REQUIRED @
TOP OF COL.
W.P.
DOUBLE ANGLE
CONNECTION
ADD DOUBLE ANGLE CONNECTION
@ GUSSET IF REQUIRED FOR
COMBINED REACTION
GUSSET PL. BY STEEL
FABRICATOR - (3/8"
MIN. THICKNESS) SLOT
TUBE FOR PL.BOTH SIDES SIZE BY STEEL
FABRICATOR, TYP.
SIZE BY STEEL FABRICATOR,
TYP.
ELEVATION
BOTH SIDES SIZE BY STEEL
FABRICATOR, TYP.
SIZE BY STEEL FABRICATOR,
TYP.
3/8" CAP PL. x
AS REQUIRED @
TOP OF COL.
W.P.
DOUBLE ANGLE
CONNECTION
ADD DOUBLE ANGLE CONNECTION
@ GUSSET IF REQUIRED FOR
COMBINED REACTION
GUSSET PL. BY STEEL
FABRICATOR - (3/8"
MIN. THICKNESS) SLOT
TUBE FOR PL.
PLAN
ELEVATION
REF. SCHED. FOR BASE
PL. AND ANCHOR RODS
GUSSET PL. BY STEEL
FABRICATOR - (3/8"
MIN. THICKNESS) SLOT
TUBE FOR PL.
REF. _/S___ FOR SCHED.
GROUT THICKNESS AND
BOLT PROJECTION
W.P.
BOTH SIDES SIZE BY STEEL
FABRICATOR, TYP.
SIZE BY STEEL FABRICATOR,
TYP.
PLAN
ELEVATION
REF. SCHED. FOR BASE
PL. AND ANCHOR RODS
GUSSET PL. BY STEEL
FABRICATOR - (3/8"
MIN. THICKNESS) SLOT
TUBE FOR PL.
REF. _/S___ FOR SCHED.
GROUT THICKNESS AND
BOLT PROJECTION
W.P.
BOTH SIDES SIZE BY STEEL
FABRICATOR, TYP.
SIZE BY STEEL FABRICATOR,
TYP.
WIND BRACE DESIGN NOTES:
1. Design connections for forces shown on wind brace elevations.
2. If no forces are shown on wind brace elevations, design for the full tensile capacity of the braces according to the Manual
of American Institute of Steel Construction. Refer to General Notes for edition.
3. Size welds for forces & eccentricity of C.G. weld & C.G. force.
4. At beam to column connections, size attachment to column for combined gravity load shear plus vertical shear
component due to lateral load.
5. Check for Whitmore section buckling, and block shear rupture of gusset plates.
6. Calculations shall be performed and sealed by a Registered Professional Engineer & shall be submitted to the Architect
per specifications.
7. Design forces noted as H=_K are service forces in axial tension or compression. V=_k are service vertical shear forces.
PLAN
ELEVATION
CMU WALL
BELOW, TYP.
GUSSET PL. BY STEEL FABRICATOR
(3/8" MIN. THICKNESS); SLOT TUBE
FOR PL.
W.P.
BOTH SIDES SIZE BY
STEEL FABRICATOR,
TYP.
SIZE BY STEEL
FABRICATOR, TYP.
CO
L. O
FFSE
T
REF
. PLA
N F
OR
REF. ARCH FOR
COL. CASING
T.O. BM. EL. =
REF. PLAN
HSS6x6x1/4 w/ 3/4"Øx6" HSS @
16" O.C. (E.S. OF COL.)
T.O. WALL
L5x5x5/16 CONT. FROM
BASE PL. TO TOP OF BRACE
CONNX. @ TOP OF CMU w/
3/4"Øx6" H.S.@ 24" O.C.
HSS BRACE
CENTERED ON
HSS6x6
WIND
FRAME
3/4" Ø x 0'-6" HEADED STUD @ 24" O.C.
CMU WALL; PROVIDE
GROUTED REINFORCED
VERTICAL CELLS E.S. OF COL.
PER
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
WINDBRACE TYPICALDETAILS
S530
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
NO SCALE
WIDE FLANGE BEAM AND WIND BRACE CONNECTION TO COLUMN FLANGE1
TYPICAL DETAIL
NO SCALE
WIDE FLANGE BEAM AND WIND BRACE CONNECTION TO COLUMN WEB2
TYPICAL DETAIL
NO SCALE
WIND BRACE CONNECTION TO COLUMN FLANGE AND BASE PLATE4
TYPICAL DETAIL
NO SCALE
WIND BRACE CONNECTION TO COLUMN WEB AND BASE PLATE5
TYPICAL DETAIL
NO SCALE
WINDBRACE DESIGN NOTES6
NO SCALE
WIND BRACE CONNECTION TO COLUMN WEB AND BASE PLATE3
TYPICAL DETAIL
NO SCALE
MASONRY WALL @ WINDFRAME COLUMN7
TYPICAL DETAIL
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE I IMDESIGN
7-7
v
~-u~ **~ij~
v-
--
--kk
~1~ 1+01N.
-I-
-I- \V
I 01__ ~LiIx
I /7,IK-I-
-I-
-I-
1olV K4
4
4
Vo~v I\ w 0
\\U~
\
40~I
II>
\/v K\ ~, V
II II IIIIII
) r-- IjII II
~ II IIKH~
1I 11I1 11 17=0I 11
I II II A
hi-
G
..................
....................
¶ -D9 9
I¶
p
\
//
/ // /
/ //
//
VK 7/ /V
/ // /
//
KV
I K I/
I
'VI I'VI I
A.3A.5
S530
2
T = C = 30 k
HSS6X6X1/4
S530
3
REF.-ARCH.
FOR WINDOW
A.3 A.5
S530
3
S530
2
HSS6X6X1/4
T = C = 30 k
REF.-ARCH.
FOR WINDOW
E10E9 3.1
S530
2
S530
3
HSS6X6X1/4T = C = 30 k
HSS6X6X1/4
T = C = 25 k
S530
2
3 3.3 E10 E93.1
S530
2
S530
3
HSS6X6X1/4 T = C = 25 k
T = C = 20 k
HSS6X6X1/4
S530
2
3
Lamar Central
3800 N. Lamar Blvd.
Suite 330
FIRM REG.#:AEC JOB#:
F-1985
Austin, Tx 78756
P 512.472.2111
www.aecollab.com
100254
ES
SI ONA L E N
GI
NE
ER
LI C E N S E D
PR
OF
JOSHUA BEDRE
ST
AT E
OF T EX
AS
1
A
NORTH
KEY PLAN
SEAL
RENOVATIONS/SUBMISSIONS
SHEET NUMBER
DRAWING TITLE
SHEET INFORMATION
DATE
REVIEWED
CHECKED
DRAWN
KAH NO.
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
1517 East Palm Valley Blvd.
Round Rock, Texas 78664
Phone (512) 255-9690
Fax (512) 388-1843
KAH-1908
20014
07/29/2020
NEW
PRA
CTI
CE
GYM
NA
SIUM
& W
EIG
HT
ROO
M A
DD
ITIO
NH
ERN
AN
DEZ
MID
DLE
SC
HO
OL
1901
SU
NRI
SE R
OA
D
ROU
ND
RO
CK,
TEX
AS
07/29/2020
Cunningham-Allen, Inc.
3103 Bee Caves Road, Suite #202
Austin, Texas 78746
(512) 327-2946
AS
JB
WINDBRACEELEVATIONS
S531
Studio 16:19, LLC
1717 North Interstate 35
Round Rock, Texas 78664
(512) 534-8680
Architectural Engineers Collaborative
3800 North Lamar Blvd., Suite #330
Austin, Texas 78756
(512) 472-2111
O'Connell Robertson
811 Barton Springs Road, Suite #900
Austin, Texas 78704
(512) 478-7286
True North Consulting Group
13284 Pond Springs Road, Suite #304
Austin, Texas 78729
(512) 451-5445
SCALE: 1/4" = 1'-0"
ELEVATION - WINDBRACE 11 SCALE: 1/4" = 1'-0"
ELEVATION - WINDBRACE 22 SCALE: 1/4" = 1'-0"
ELEVATION - WINDBRACE 33 SCALE: 1/4" = 1'-0"
ELEVATION - WINDBRACE 44
NO. DESCRIPTION DATE
>w4~ARCHITECTUREBUILDING SCIENCE IINTERIOR DESIGN
7.7
II
IIK
C-0
r
I
d
II
=4k! I
zl7iLI.-A
I
Li
j.-
..............
Li Li Li, Li-L