Date post: | 28-Feb-2018 |
Category: |
Documents |
Upload: | athul-tuttu |
View: | 316 times |
Download: | 5 times |
of 72
7/25/2019 CS4000 Service and Maintenance manual.pdf
1/72
Fire Alarm SystemSalwico CS4000
Service & Maintenance manual
Consilium
7/25/2019 CS4000 Service and Maintenance manual.pdf
2/72
The contents of this document are subject to revision without notice due to continued progress inmethodology, design and manufacturing. Consilium assumes no legal responsibility for any erroror damage resulting from the usage of this document.
Edition 5, 081 E, April2008.Document no. S-4-010.968Part no: 465002
2005-2008, Consilium Fire & Gas AB
Consilium Marine AB
P.O. Box 8763SE-402 76 GTEBORGSWEDENTel: +46-31-710 77 00, Fax: +46-31-710 78 00E-mail: [email protected]: www.consilium.se
7/25/2019 CS4000 Service and Maintenance manual.pdf
3/72
Service & Maintenance manual Chapter1: CS4000 block diagramSalwico CS4000
Contents
Chapter 1: CS4000 block diagram ......................................................................................... 2
Chapter 2: Testing.................................................................................................................... 3
TEST A FIRE-DETECTING ZONE................................................................................................. 3Heat detectors .................................................................................................................... 3
Smoke detectors.................................................................................................................. 4
Flame detectors..................................................................................................................4
TEST FAULT CONDITIONS ........................................................................................................ 4
Removed detector fault....................................................................................................... 4
Fuse fault............................................................................................................................ 4
Battery fault........................................................................................................................ 5
Earth fault .......................................................................................................................... 5
Loop cable break................................................................................................................5
Power supply...................................................................................................................... 5
RESET TEST MODE ................................................................................................................... 6
TEST THE CONTROL UNIT DISPLAY...........................................................................................6
Chapter 3: Cleaning of fire detectors ..................................................................................... 7
SMOKE DETECTORS .................................................................................................................7
HEAT DETECTORS.................................................................................................................... 7
FLAME DETECTORS..................................................................................................................7
Chapter 4: Replacing/Adding/Deleting fire detectors........................................................... 8
REPLACING FIRE DETECTORS................................................................................................... 8
Instruction .......................................................................................................................... 8
ID address on DIP switches............................................................................................... 8
HOT PLUG&PLAY (ADDING/DELETING LOOP UNITS)................................................................ 9
Change configuration file from the fault list ...................................................................... 9
Change configuration file from the service menu............................................................ 11
Chapter 5: Replacing battery................................................................................................ 13
INSTRUCTION......................................................................................................................... 13
Chapter 6: Software ............................................................................................................... 14
CONFIGURATION PROGRAM ................................................................................................... 14
TO UPLOAD A CONFIGURATION FILE FROM CS4000............................................................... 14
Upload configuration file to a PC.................................................................................... 14
Upload configuration file to Salwico Memory StickTM
.................................................... 14
TO DOWNLOAD A CONFIGURATION FILE TO CS4000..............................................................15
Download configuration file from a PC........................................................................... 15
Download configuration file from the Salwico Memory StickTM
..................................... 16
UPDATE THE BASE BOARD SOFTWARE ................................................................................... 17
Update the software version in the base board................................................................ 17
Possible errors during update of base board...................................................................18
Chapter 7: Service menu in CS4000 (access level 4)........................................................... 19
1SYSTEM DETAILS................................................................................................................202SYSTEM BOARDS ................................................................................................................21
7/25/2019 CS4000 Service and Maintenance manual.pdf
4/72
Service & Maintenance manual Chapter1: CS4000 block diagramSalwico CS4000
1
3DISPLAY UNITS .................................................................................................................. 25
4ZONES ................................................................................................................................ 26
5LOOPS................................................................................................................................. 28
6RELOAD CONFIGURATION .................................................................................................. 32
7LOAD CONFIG FROM MEMORY STICK................................................................................. 33
8UPLOAD CONFIG TO MEMORY STICK.................................................................................. 349SAVE CHANGES TO CONFIGURATION................................................................................... 35
10UPLOAD SYSLOG TO MEMORY STICK............................................................................... 36
Appendix A: Fault codes & Fuses.........................................................................................37
FAULT LIST............................................................................................................................ 37
FUSES ....................................................................................................................................41
Fuse list ............................................................................................................................ 41
Fuse locations on base board, BB.................................................................................... 41
Fuse locations on rectifier board, RB. ............................................................................. 41
Appendix B: Connections for loop units .............................................................................. 42
Appendix C: System modules................................................................................................ 45
7/25/2019 CS4000 Service and Maintenance manual.pdf
5/72
Service & Maintenance manual Chapter1: CS4000 block diagramSalwico CS4000
2
Chapter 1: CS4000 block diagram
7PQRS
WXYZ
9
TUV
8
4GHI
MNO
6
JKL
5
1''
DEF
3
ABC
OK
Mute
Next
DISC.
FAULT
FIRE
Reset
Menu
SALWICO
SG-6728
Pre-Alarm
OK
Warning
2
Zone/Unit
AlarmDelay
AlarmTransfer
Power
AlarmDevice
Test
Disc.
Home
SystemFault
0
7/25/2019 CS4000 Service and Maintenance manual.pdf
6/72
Service & Maintenance manual Chapter1: CS4000 block diagramSalwico CS4000
3
Chapter 2: Testing
Consilium recommends that the fire alarm system is tested at least
once a year to assure correct function.
The CS4000 has a special test mode, which makes the testing easier.
Characteristics for a zone in test mode:
It will not activate any external alarm devices or controls incase of a fire (this function can be turned off).
The alarm level is lowered to give quick response to test gas.
Detectors and manual call points in the zone will blink.
Each tested detector and manual call point will indicateactivation with a red LED.
The units in alarm are automatically reset when the heat orsmoke concentration is under the alarm level or if the manual
call point is reset.
Fire alarms from zones not in test mode will be handled normally by
the system.
Note: The tested zone will automatically return to normal operation
after two hours.
Test a fire-detecting zone
Put the zone into test mode:Menu/ 3 Disconnections/ 1 New
disconn./ 5 Test Mode. Enter the zone number and confirm with OKbutton
The indications DISC., TEST and ZONE/UNIT will be lit to confirm
the test mode.
It is now safe to test each detector, manual call point etc in this fire
zone during two hours. Use suitable testing equipment, available
from Consilium.
All alarms will be listed under:Menu/ 7 History/ 1 Fire History List
Heat detectors
Heat detectors are preferably tested with heat detector tester VDT-1,part. no. 9300, available from Consilium.
Apply heat to the sensing element until alarm is indicated bya red indication.
Important:
If other test equipments are used, for example cigarette lighter or
heating gun, make sure not to over-heat the detector by holding the
heat-source to close to the detector. This will damage the detectors,
for example causing the plastic to melt.
7/25/2019 CS4000 Service and Maintenance manual.pdf
7/72
Service & Maintenance manual Chapter1: CS4000 block diagramSalwico CS4000
4
Smoke detectors
Smoke detectors are preferably tested with test gas equipment Solo
330, available from Consilium.
Spray test gas on to the detector during 0.5 second. Wait 10seconds until new gas is sprayed during 1 second. Repeat this
procedure until the detector indicates alarm with a red
indication.
If other test methods are used, make sure not to damage the detector.
Flame detectors
Flame detectors may be tested with an ordinary cigarette lighter.
Turn up the flame to a height of approximately 5 cm. Hold itin front of the detector at a distance of about 2-5 meters.
Move the lighter slowly during the test to obtain a flickering
flame until alarm is indicated with a red indication.
Test Fault conditions
The fire alarm central continuously monitors the
system components and will report any fault
condition on the control panel with both optical and
audible indication.
It is possible to test fault indications by following the
below procedures:Please note that a fault condition is only possible to
reset when the cause is remedied.
Removed detector fault
1. Remove a detector.2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. Reinsert the detector4. Reset the fault condition on the control panel.
Fuse faultNote: Before a fuse is removed, make sure which functions
that will be affected by the removal.
1. Remove a fuse.2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. Reinsert the fuse.4. Reset the fault condition on the control panel.
7/25/2019 CS4000 Service and Maintenance manual.pdf
8/72
Service & Maintenance manual Chapter1: CS4000 block diagramSalwico CS4000
5
Battery fault
1. Remove a battery fuse.2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. Reinsert the fuse.4. Reset the fault condition on the control panel.
Earth fault
1. Connect one of the loop cables to earth via a2,7kOhm resistor.
2. Verify that the fault is indicated on the controlunit (this may take up to 1 minute).
3. Remove the earth connection.4. Reset the fault condition on the control panel.
Loop cable break
1. Open up the loop cable.2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. If the detector loop is double fed: Verify thateach of the two branches can detect fire alarms
by testing a detector on each branch.
4. Close the loop cable.5. Reset the fault condition on the control panel.
Power supply
Test the back up power supply (emergency 230VAC
or batteries).
1. Removing the mains power supply.2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute), and that
the system remains operational.
3. If there is an emergency power supply inaddition to the batteries, remove this also. The
system should now operate on the batteries
only.
4. Connect all disconnected power supplies.5. Reset the fault condition(s) on the control
panel.
7/25/2019 CS4000 Service and Maintenance manual.pdf
9/72
Service & Maintenance manual Chapter1: CS4000 block diagramSalwico CS4000
6
Reset test mode
After testing it is important to return the tested zone into normal
condition again. Make sure that there are no detectors or manual call
points still in alarm before leaving test mode.
The zones in test mode are listed in the disconnection list, found
under:Menu/3 Disconnections /2 Disconnection list.
Choose the zone in the disconnection list and then press RESET.
Test the control unit display
It is possible to test the alphanumerical display, all indications on the
control panel and the local buzzer with the function Test display,
found under:Menu/ 5 Settings/ 4 Test display.
7/25/2019 CS4000 Service and Maintenance manual.pdf
10/72
Service & Maintenance manual Chapter3: Cleaning of fire detectorsSalwico CS4000
7
Chapter 3: Cleaning of fi re detectors
The CS4000 fire alarm system continuously monitors the
detectors and will give early warnings if they are polluted ormalfunctioning in other ways. The methods for cleaning
detectors depends of the type of detector, see below.
If the cleaning is initiated by a dirty sensor fault in the
control panel, then try to reset this fault after cleaning. If this
does not succeed, replace the detector.
Smoke detectors
Clean the detector with a vacuum cleaner or by blowing
high-pressure instrument air on it.The detector house is cleaned with a damp cloth.
Note: The high-pressure air must be of instrument type
(clean, not containing oil etc.)
Heat detectors
The sensor part does normally not need to be cleaned.
The detector house is cleaned with a damp cloth.
Flame detectors
Clean the protective glass over the sensor by a grease solventsuch as soap or alcohol.
The detector house is cleaned with a damp cloth.
7/25/2019 CS4000 Service and Maintenance manual.pdf
11/72
Service & Maintenance manual Chapter4: Replacing/Adding/Deleting fire detectorsSalwico CS4000
8
Chapter 4: Replacing/Adding/Deleting fire detectors
Replacing f ire detectors
Instruction
1.Disconnect the faulty detector and remove it from thebase plate.
Note: Some bases have a lock mechanism on the side.
This lock shall either be pulled or pressed (depends on
base model).
2.Check the ID settings on the address switch for the faultydetector. See section ID address on DIP switches for
explanation of the ID address.
3.Set the corresponding ID on the address switch for thenew detector.4.Seal the address switch on the detectors with the attached
label after the address has been set.
5.Connect and mount the new detector.6.Check and reset any fault codes generated by the
replaced faulty detector.
7.Perform a function test of the detector according to thechapter Testing.
ID address on DIP switches
All addressable loop units must be given an address between1-254 to be operational. The loop units located on the same
physical loop must all have unique addresses. The address is
set either by a 8 pole DIP switch located on each addressable
unit, or (for units without physical address switch) with the
address programming tool EV-AD. (See separate instruction)
The DIP switch values follow the binary system.
1 2 3 4 5 6 7 8
O
N
1 2 4 8 16 32 64 128
The value of the address is set according to the switches set
to ON position. For example:
1 2 3 4 5 6 7 8
O
N
=47
The switches numbered 1,2,3,4 and 6 are set to ON position.
The values for these switches are 1+2+4+8+32=47.
Important:Seal the address switch on the detectors with theattached label after the address has been set.
7/25/2019 CS4000 Service and Maintenance manual.pdf
12/72
Service & Maintenance manual Chapter4: Replacing/Adding/Deleting fire detectorsSalwico CS4000
9
Hot Plug&Play (adding/deleting loop units)
The CS4000 system is equipped with a Hot Plug&Play
function enabling the user to add or delete detectors during
normal operation without the need to change the
configuration file with a PC and restarting the system.The configuration file may be updated during normal
operation from service menu 6:5 or direct from the fault list,
menu 1.1.
This function is very useful, especially during installation. If
the CS4000 central detects additional or missing loop units,
they are simply added to/deleted from the configuration file
during normal operation.
Note: The changes to the configuration file is updated in the
RAM memory, but will not saved permanently until it has
been saved under:Menu/ 6 Service menu/ 9 Save changes toconfiguration. If the configuration file is not changed
permanently, any changes done will be lost if the system is
re-started.
Change configuration file from the fault lis t
Adding a loop unit from the fault list
If the CS4000 detects additional or missing loop units
compared to the configuration file, they are added to the fault
list.
1. Open the fault list:Menu/ 1 Fault alarms/ 1 Fault list2. Select the detector to add from the list (fault no. 3 is
selected in the below example).
Loop Units generating fault no 152 (present not
configured) can be added to the systems
configuration.
FAULT ALARM 4(5)
________________________________________
3 LOOP 603 SMOKE HEAT 2 PRESENT NOT
CONFIGURED, FAULT(152) .
Unit not found .
4 ZONE 111 UNKNOWN LOOP DEVICE 3 NO
ANSWER, FAULT(128)
txt
5 LOOP ANALOGUE 601 CABLE BREAK
POSITIVE, FAULT(141)
Loop 1 on LB3 6
________________________________________
0=Add Loop Unit to configuration
OK=Details, 1=Print item, 2=Print all3. Press 0=Add Loop Unit to configuration
7/25/2019 CS4000 Service and Maintenance manual.pdf
13/72
Service & Maintenance manual Chapter4: Replacing/Adding/Deleting fire detectorsSalwico CS4000
10
4. Enter the data required for the new loop unit in dialogbox Add loop unit.
Central, Board, Loop and Zone must exist in the
Systems Configuration to be valid.
Physical Unit Address may NOT exist on the physical
loop already.Logical Zone number may NOT exist on the chosen
Zone.
T1 and T2 are supplementary Text 1 and 2, and are
entered as on a Mobile Telephone.
ADD LOOP UNIT
________________________________________
Physical Central addr.: 1 (valid) .
Physical Board address: 6 (valid)
Physical Loop address : 2 (valid)
Physical Unit address : 0 (invalid)
Logical Zone number : 0 (invalid)
Logical Unit address : 0 (invalid)
Type: 202 (invalid)
T1:
T2:
________________________________________
Enter value with numeric keyboard.
UP/DOWN=New field,OK=Add Unit,'
7/25/2019 CS4000 Service and Maintenance manual.pdf
14/72
Service & Maintenance manual Chapter4: Replacing/Adding/Deleting fire detectorsSalwico CS4000
11
Change configuration file from the servicemenu
Adding a loop unit from the service menu
1. Open the service menu:Menu/ 6 Service menu/ 5Loops
2. Select an analogue loop from the loop list (loop no. 2is selected in the below example). Press 3=Add Unit.
LOOP 2(19)________________________________________
1 LOOP ANALOGUE 601Loop 1 on LB3 624 Loop Units Expected
2 LOOP ANALOGUE 602 .Loop 2 on LB3 6 .
11 loop Units Expected .
3 LOOP ANALOGUE 603Loop 3 on LB3 60 Loop Units Expected
________________________________________
OK=Details, 0=Disconnect, 1=Print List2=Loops Units,3=Add Unit,4=Scan loop
3. Enter the data required for the new loop unit in dialogboxAdd loop unit.
Central, Board, Loop and Zone must exist in theSystems Configuration to be valid.
Physical Unit Address may NOT exist on the physical
loop already.
Logical Zone number may NOT exist on the chosen
Zone.
T1 and T2 are supplementary Text 1 and 2, and are
entered in the same way as on a Mobile Telephone
with the alpha-numerical keyboard.ADD LOOP UNIT________________________________________
Physical Central addr.: 1 (valid) .Physical Board address: 6 (valid)Physical Loop address : 2 (valid)
Physical Unit address : 0 (invalid)Logical Zone number : 0 (invalid)Logical Unit address : 0 (invalid)Type: 202 (invalid)T1:
T2:________________________________________Enter value with numeric keyboard.UP/DOWN=New field,OK=Add Unit,'
7/25/2019 CS4000 Service and Maintenance manual.pdf
15/72
Service & Maintenance manual Chapter4: Replacing/Adding/Deleting fire detectorsSalwico CS4000
12
Deleting a loop unit from the service menu
1. Open the service menu:Menu/ 6 Service menu/ 5Loops.
2. Select an analogue loop from the loop list (loop no. 2is selected in the below example). Press 2=Loop
Units.
LOOP 2(19)
________________________________________1 LOOP ANALOGUE 601
Loop 1 on LB3 624 Loop Units Expected
2 LOOP ANALOGUE 602 .
Loop 2 on LB3 6 .
11 loop Units Expected .
3 LOOP ANALOGUE 603Loop 3 on LB3 60 Loop Units Expected
________________________________________OK=Details, 0=Disconnect, 1=Print List2=Loops Units,3=Add Unit,4=Scan loop
3. Select a loop unit to delete from the listLoop units.Press 3=Erase Loop Unit
LOOP UNITS 1(11)
_________________________________1 LOOP 602 MCP 1 (A/B)2 LOOP 602 SCI 2 (A/B)3 LOOP 602 MCP 3 (A/B)4 LOOP 602 SCI 4 (A/B)
5 LOOP 602 MCP 5 (A/B) .6 LOOP 602 MCP 7 (A/B)7 LOOP 602 SCI 8 (A/B)8 LOOP 602 MCP 9 (A/B)9 LOOP 602 SCI 10 (A/B)10 LOOP 602 MCP 11 (A/B)
11 LOOP 602 SMOKE 201 (A/B)________________________________________
OK=Details, 0=Disconnect, 1=Print List2=Set In Fire, 3=Erase Loop Unit
4. The configuration file is now updated in the RAMmemory.
7/25/2019 CS4000 Service and Maintenance manual.pdf
16/72
Service & Maintenance manual Chapter5: Replacing batterySalwico CS4000
13
Chapter 5: Replacing battery
When replacing the batteries, make sure to use batteries with
the same specification as the original.
Instruction
1. Remove both battery fuses at the rectifier board.See Appendix Afor fuse locations.
2. Remove the battery cables from the battery.3. Exchange the battery.4. Verify the correct polarity and connect the battery
cables to the new battery.
5. Verify that the voltage is approx. 24VDC at thebattery terminals on the rectifier board.
6. Reinsert the battery fuses.7. Reset the battery fault at the control unit.
7/25/2019 CS4000 Service and Maintenance manual.pdf
17/72
Service & Maintenance manual Chapter6: SoftwareSalwico CS4000
14
Chapter 6: Software
Configuration program
The CS4000 central is delivered pre-programmed with a
standard configuration file. See the separate manual
CS4000 Configuration program manualfor information on
how to create and update a configuration file.
To upload a configuration f ile from CS4000
When you want to view or make changes in an existing
configuration file you can get it from the CS4000 central.
The configuration file can be uploaded in two ways:
Direct to PC via USB cable To Salwico Memory StickTM
(the system must be equipped with an USB
Expansion Board)
Upload configuration fi le to a PC
1. Connect a PC via an USB cable to the USBport on the Base Board (not the USB
Expansion Board, if present).
2. The CS4000 will now present itself as anextra drive in your PC. Open the extra
drive.
3. You will find a file with the file extension.c4d, which is the configuration file used by
the CS4000 system.
Example of file name: SG12345.C4D
4. Copy the .c4d file to your local disc beforeworking with it.
Upload configuration file to Salwico Memory
StickTM
1. Connect the Salwico Memory StickTMto one of theUSB ports on the USB expansion board (piggyback
board located on the BaseBoard).
2. ChooseMenu/ 6 Service/ 8 upload config to MemoryStick
3. Choose the current .c4d configuration file from thelist and press OK.
4. The system will now upload the configuration file.5. When the upload is complete, disconnect the Salwico
Memory StickTMand copy the configuration file to a
PC.
7/25/2019 CS4000 Service and Maintenance manual.pdf
18/72
Service & Maintenance manual Chapter6: SoftwareSalwico CS4000
15
To download a configuration file to CS4000
When the configuration file is finished it is time to download
it to the CS4000 system. The configuration file must have the
file extension .c4d.
If only supplementary texts has been updated in the .c4dfile it is possible download them separately, see below
instructions.
The configuration file can be downloaded in two ways:
Direct from PC via USB cable
From Salwico Memory StickTM(the system must be equipped with an USB
Expansion Board)
Note:Make sure to work with the latest .c4d file when making
changes. The latest .c4d file may be uploaded from the
CS4000 system, see instruction above.
In Base Board software versions before 1.0.18 the definition
file must be named current.c4d
Download configuration fi le from a PC
1. Connect a PC via an USB cable to the USB port onthe Base Board (not the USB Expansion Board, if
present).
2. The CS4000 will now be displayed as an extradrive in your PC. Open the extra drive.
3. Change the file extension on the current configurationfile to .old and save it as a back-up file.
4. Copy the new configuration file with the fileextension .c4d from the PC to the extra drive.
5. When the file copy is completed, remove the USBcable from the Base Board.
6. Use the CS4000 control panel to update the systemwith the new configuration file by choosing:
-Menu/ 6 Service menu/ 6 Reload Configuration/
1 Load entire configurationor
-Menu/ 6 Service menu/ 6 Reload Configuration/
2 Load supplementary texts only
7. If 1 Load entire configurationis selected above, theBase Board will re-start and load the new
configuration file.
If 2 Load supplementary texts onlyare selected, the
system will use the new texts without having to re-
start. Any other changes made to the .c4d file will
be ignored, but will come into effect the next time thesystem is re-started.
7/25/2019 CS4000 Service and Maintenance manual.pdf
19/72
Service & Maintenance manual Chapter6: SoftwareSalwico CS4000
16
Download configuration file from the Salwico
Memory StickTM
1. Connect the Salwico Memory StickTMto one of theUSB ports on the USB expansion board (piggyback
board located on the Base Board).
2. ChooseMenu/ 6 Service/ 7 load config from MemoryStick
3. A list of the available .c4d files on the SalwicoMemory StickTMwill be presented. Choose the
appropriate .c4d configuration file from the list and
press OK.
4. The new configuration file is downloaded to theCS4000.
The old configuration file is automatically renamedby the system and saved on the Salwico Memory
StickTM.
5. Disconnect the Salwico Memory StickTM6. Use the CS4000 control panel to update the system
with the new configuration file by choosing:
-Menu/ 6 Service menu/ 6 Reload Configuration/
1 Load entire configurationor
-Menu/ 6 Service menu/ 6 Reload Configuration/
2 Load supplementary texts only
7. If 1 Load entire configurationis selected above, theBase Board will re-start and load the new
configuration file.
If 2 Load supplementary texts onlyis selected, the
system will use the new texts without having to re-
start. Any other changes made to the .c4d file will
be ignored, but will come into effect the next time the
system is re-started.
7/25/2019 CS4000 Service and Maintenance manual.pdf
20/72
Service & Maintenance manual Chapter6: SoftwareSalwico CS4000
17
Update the base board software
There are two flash memories in the base board:
flash1containing bootloader and the software for the
base board (flash1.img). flash2containing the definition file (current.c4d)
Update the software version in the base board
Follow the below instructions to update the software version
in the base board by using an USB cable.
1. Please note how the DIP switch on the base board(see figure below) is set, since this setting shall be
restored after the update of the software.
2. Set the base board in bootloader mode by setting
the DIP switch address to 0 (all switches in OFFposition).
3. Reboot the base board with the reset button.LED1 will indicate that the base board is in
bootloader mode by flashing light.
4. Connect the PC to the base board via an USB cable.The base board will appear in Windows Explorer as
an extra USB drive.
5. Copy the new software file named flash1.img fromthe PC to the USB drive (drag & drop).
6. Close the extra USB drive in Windows Explorer. Thebase board will now start to download the new fileinto flash1. LED2 will indicate this by flashing light.
The download process is finished when LED2 turns
into steady light.
7. Restore the original address on the DIP switch.8. Reset the base board with the reset button. The base
board will now re-start, using the new updated
software.
Description of the LEDs during update of software:
Flashing LED on LED offLed1,
Yellow
Bootloader
mode
Led2,
Yellow
Writing to flash Writing to flash
completed
Writing to flash has not started
Led3, Red Checksum error Checksum OK
Led1Led2Led3
DIP switch
Reset buttonCP
Illustration base board
7/25/2019 CS4000 Service and Maintenance manual.pdf
21/72
Service & Maintenance manual Chapter6: SoftwareSalwico CS4000
18
Possible errors dur ing update of base board
Error
LED1 do not flash after reboot when the DIP switch on the
base board is set to 0.
Cause
The base board is defect.
Error
LED2 is on before flash1.img has been downloaded.
Cause
Under certain circumstances (i.e. remove and reattach USB
cable during bootloader operation) may cause the bootloader
routine to malfunction.
Re-boot the base board and retry the operation.
7/25/2019 CS4000 Service and Maintenance manual.pdf
22/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
19
Chapter 7: Service menu in CS4000 (access level 4)
TheService menu is used for configuration of the system in thecommissioning phase, as well as for troubleshooting and small
updates when the system is in operation. The menu has functions for
downloading and uploading information from/to the Salwico
Memory Stick.
The service menu screen displays a list of the 10 service menu
alternatives, described on the following pages. The alternatives are
reached by pressing the corresponding number on the numerical
keypad, or by selecting the desired alternative with the arrow
buttons and pressing the OK button.
Service menu screen
SERVICE 12 361 System Details >
2 System Boards >
3 Display Units >
4 Zones >
5 Loops >
6 Reload Configuration >
7 Load config from Memory Stick >
8 Upload config from Memory Stick >
9 Save changes to configuration >
10 Upload syslog to Memory Stick > _______________________________________________
Select a menu with 0-9 (or arrows + OK)
7/25/2019 CS4000 Service and Maintenance manual.pdf
23/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
20
1 System Details
The System Details screen gives basic information about the
system.
System details screen
The first four lines display basic data about the installation.
The data originates from the configuration file (Options
module):
SG/SOA Number
Name of shipyard + number of build
IMO Number
Ship name
The remaining information also concerns the configuration
Created: The time the configuration was createdCreated by: The person who created the configuration
Build: Number of times that the configuration file has been
changed
File Name: Name of the configuration file
Program: The definition program version used to create the
file
- Press 1to print the system details
- Press 2to see the software and hardware versions of the
system boards.
SYSTEM DETAILS 12 36
CS4000ConsiliumSalwicoM/S HolidayCONFIGURATION
Created : 2006-08-29 14:34:41Created by : BARBuild : 53File Name : test37.c4d
Program : CS4000CONF.EXE.1.1.0.13
_______________________________________________
1=Print, 2=Program Versions
7/25/2019 CS4000 Service and Maintenance manual.pdf
24/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
21
2 System Boards
The System Boards screen lists the boards in the system.
System boards screen
CENTRALx:xis the number of the central where the boardis placed
BOARDXBx:XBis the board type (BB = Base Board, RB
= Rectifier Board, etc.) andxis the address of the board
(BOARD OK / BOOTING / CONFIG NOT FOUND):
Board status
- Press OKto monitor details about the selected board
- Press 0to disconnect the selected board; all I/O on the
board will be disconnected and fault associated with the
board will disappear from the fault list
- Press 1to print the board list- Press 2to monitor and manipulate the inputs of the selected
board
- Press 3to monitor and manipulate the outputs of the
selected board
- Press 4to monitor the loops of the selected board
(if the board is a loop board)
BOARD 1(2) 12 36
1 CENTRAL 1 BOARD BB 1 (BOARD OK)XX XXXXXXXXXXXXXXXXXXXXXXXXXXXX
2 CENTRAL 1 BOARD RB 4 (BOARD OK)
3 CENTRAL 1 BOARD LB3 11 (BOARD OK)
__________________________________________OK=Details, 0=Disconnect, 1=Print List2=Inputs, 3=Outputs, 4=Loops
7/25/2019 CS4000 Service and Maintenance manual.pdf
25/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
22
Details about system board (press OK at System Boards
screen)
System board, details
HW: Hardware version
SW: Software version
Timestamp Config: Time and date of configuration
No of loops: Number of loops on the board
No of inputs/outputs: Number of inputs and outputs on the
board
Communication errors: Number of reported
communication errors in the last 65 535 tries
- Press OKto return to the board list
- Press 1to print the details
BOARD 1(2) 12 36
1 CENTRAL 1 BOARD BB 1
HW: BASE BOARD VER. 1.0SW: BBP ver. 1.0.37Timestamp Config: 2006-08-29 14:34:42
No of loops: 0No of inputs/outputs: 6/11Communication errors: 0/65535
_______________________________________________
OK=List view, 1=Print details
7/25/2019 CS4000 Service and Maintenance manual.pdf
26/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
23
Inputs of system board (press 2 at System Boards screen)
System board input
BOARDx:xis the board address where the input is placed.
INPUTx:xis the input number
SET / CLEAR:Indicates if the input is active (SET) or
inactive (CLEAR)
- Press 0to disconnect the selected input; inputs must be
disconnected before simulation of inputs can be done
- Press 1to print the input list
- Press 2to simulate activation of the selected input
- Press 3to simulate inactivation of the selected input
INPUT 1(6) 12 36
1 BOARD 1 INPUT 1 CLEAR l XX XXXXXXXXXXXXXXXXXXXXXXXXXXXX
2 BOARD 1 INPUT 2 SET
3 BOARD 1 INPUT 3 CLEAR
_______________________________________________
0=Disconnect, 1=Print List
2=Set Input, 3=Clear Input
7/25/2019 CS4000 Service and Maintenance manual.pdf
27/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
24
Outputs of system board (press 3 at System Boards screen)
System board output
BOARDx:xis the address of the board that the output
belongs to
OUTPUT GRPx/XOUTPUTx:Xis the Output category
(OUTPUT GRP = General output,Xcould be FIRE, FAULT,
DOOR etc.) andxis the output number
SET / CLEAR:Indicates if the output is active (SET) or
inactive (CLEAR)
- Press 0to disconnect the selected output; outputs must be
disconnected before simulation of outputs can be done
- Press 1to print the output list
- Press 2to simulate activation of the selected output
- Press 3to simulate inactivation of the selected output
OUTPUT 1(6) 12 36
1 BOARD 1 OUTPUT GRP 1 CLEAR XXXXXXXXXXXXXXXXXXXXXXXXXX XXXk
2 BOARD 1 OUTPUT GRP 2 CLEAR
3 BOARD 1 FIRE OUTPUT 3 CLEAR
_______________________________________________
0=Disconnect, 1=Print List2=Set Output, 3=Clear Output
7/25/2019 CS4000 Service and Maintenance manual.pdf
28/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
25
3 Display Units
The Display Units screen lists the panel boards.
Panel boards screen
CENTRALx:xis central number where the board is placed
BOARD PBx:xis the address of the panel board
- Press OKto monitor details about the selected panel board
- Press 0to disconnect the selected panel board; all I/O on
the board will be disconnected and fault associated with the
board will disappear from the fault list
- Press 1to print the panel board list
- Press 2to monitor and manipulate the inputs of the selected
panel board (similar to Inputs of System Board screen)
- Press 3to monitor and manipulate the outputs of the
selected panel board (similar to Outputs of System Board
screen)
Details about panel board (press OK at Display Units screen)
Panel boards, details
Greeting text: Text that appears when the system is started;
Ship name and SG/SOA Number originating from the
Options module in the configuration file
Function: Currently not used
- Press OK to return to the panel board list- Press 1 to print the details
DISPLAY UNIT 1(6) 12 36
1 CENTRAL 1 BOARD PB 3xxxx xxxxxxxxxxXXXXXXXXXXXXXXXXXXXXXXllkXXXXXl
2 CENTRAL 1 BOARD PB 5
3 CENTRAL 1 BOARD PB 7
_______________________________________________
OK=Details, 0=Disconnect, 1=Print List2=Inputs, 3=Outputs
DISPLAY UNIT 1(6) 12 36
1 CENTRAL 1 BOARD PB 3
Greeting text:M/S HolidayCS4000
Function:NOT_USED
_______________________________________________
OK=List view, 1=Print details
7/25/2019 CS4000 Service and Maintenance manual.pdf
29/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
26
4 Zones
The Zones screen lists the zones in the system.
Zones screen
ZONEx:xis the zone numberXXX (first row): Any text describing the zone, entered in the
Zone module in the configuration program as Text 1
XXX (second row): Any text describing the zone, entered in
the Zone module in the configuration program as Text 2
- Press OKto monitor details about the selected zone
- Press 1to print the zone list
- Press 2to monitor and manipulate the loop units in the
selected zone
Details about zones (press OK at Zones screen)
Zones, details
Units defined: Number of loop units in the zone
Units located on Loop: The logical loop/loops where the loop
units are placed
- Press OK to return to the zone list
- Press 1 to print the details
ZONE 1(40) 12 36
1 ZONE 1xxxx xxxxxxxxxXMFZ 1XXXXXXX XXXXHHXXXXXXmlXDeck 1XXXXXXX XXXXHHXXXXXXml
2 ZONE 2MFZ 2Deck 1
3 ZONE 3MFZ 1Deck 2
_______________________________________________
OK=Details, 1=Print List, 2=Loop Units
ZONE 1(40) 12 36
1 ZONE 1
Units defined: 2
Units located on Loop: 1
_______________________________________________
OK=List view, 1=Print details
7/25/2019 CS4000 Service and Maintenance manual.pdf
30/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
27
Loop units of Zones (press 2 at Zones screen)
Zones, loop units
LOOP x: x is the logical loop number
SMOKE / MCP / SCI x: Detector type (MCP = Manual call
point, SCI = Short Circuit Interruption) and logical address x
- Press OK to monitor details about the selected loop unit
- Press 0 to disconnect the selected loop unit
- Press 1 to print the loop unit list
- Press 2 to simulate a fire alarm in the system
- Press 3 to remove the loop unit from the configuration
- Press 4 to change the supplementary text of the loop, which
is shown in the display in case of an alarm (also visible in the
Details list, reached via the OK button)
LOOP UNITS 1(10) 12.36________________________________________1 LOOP 2 SMOKE 12 LOOP 2 SMOKE 3
3 LOOP 2 SCI 44 LOOP 2 SMOKE 55 LOOP 2 MCP 76 LOOP 2 SMOKE 87 LOOP 2 SMOKE 98 LOOP 2 SMOKE 109 LOOP 2 MCP 1110 LOOP 2 SMOKE 201_______________________________________OK=Details, 0=Disconnect, 1=Print List2=Set In Fire, 3=Erase, 4=Change text
7/25/2019 CS4000 Service and Maintenance manual.pdf
31/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
28
5 Loops
The Loops screen lists the loops in the system.
Loops screen
LOOP ANALOGUEx:xis the logical loop numberXXX (first row): Any text describing the loop, entered in the
Loop board in the configuration program as Text 1
XXX (second row): Any text describing the loop, entered in
the Loop board in the configuration program as Text 2
- Press OKto monitor details about the selected loop
- Press 0to disconnect the logical loop; the loop will be
disconnect galvanically
- Press 1to print the loop list
- Press 2to monitor and manipulate the logical loop
- Press 3to add a logical loop
- Press 4to scan for new or changed loop units, for example
detectors
LOOP 1(35) 12 36
1 LOOP ANALOGUE 1 f xxxxxxxxXXDeck 3XXXXXXXXXXXXXXXXXXXXXXl
Starboard sideTypisk text XXXXXXXXXXmk
2 LOOP ANALOGUE 2Deck 3Starboard side
_______________________________________________
OK=Details, 0=Disconnect, 1=Print List2=Loo s Units 3=Add Unit 4=Scanloo
7/25/2019 CS4000 Service and Maintenance manual.pdf
32/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
29
Details about loops (press OK at Loops screen)
Loops, details
System Address (crd.subCrd): Address of the loop; crd =
Board address, subCrd = number of physical loop
Loop Units (found/expected): Number of found/expected
loops
Communication errors: Number of reported communication
errors in the last 1 000 tries
Current consumption: Current consumption of the loop
Fire Alarms: Number of active fire alarms at the moment
Fault Alarms: Number of active fault alarms at the moment
Disconnections: Number of disconnections at the moment
- Press OK to return to the loop list
- Press 1 to print the details
LOOP 1(35) 12 36
LOOP ANALOGUE 2
System Address (crd.subCrd): 11.1Loop Units (found/expected): 17/17
Communication errors: 625/1000Current consumption: 17 mAFire Alarms : 0Fault Alarms : 1Disconnections : 0_______________________________________
OK=List view, 1=Print details
7/25/2019 CS4000 Service and Maintenance manual.pdf
33/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
30
Loop units (press 2 at Loops screen)
Loop units
LOOP x: x is the logical loop number
SMOKE HEAT x: Detector type and logical address x
(A/B): The unit answers on side A (primary) and side B
(secondary); when looking for a short circuit or a cable break
this information is useful for locating the break or short
circuit
- Press OK to monitor details about the selected loop unit
- Press 0 to disconnect the selected loop unit
- Press 1 to print the loop unit list
- Press 2 to simulate a fire alarm in the system
- Press 3 to remove the loop unit from the configuration
LOOP UNITS 1(17)________________________________________1 LOOP 1 SMOKE HEAT 1 (A/B)2 LOOP 1 SMOKE HEAT 2 (A/B)3 LOOP 1 SMOKE HEAT 3 (A/B)
4 LOOP 1 SMOKE HEAT 4 (A/B)5 LOOP 1 SMOKE HEAT 5 (A/B)6 LOOP 1 SMOKE HEAT 6 (A/B)7 LOOP 1 SMOKE HEAT 7 (A/B)8 LOOP 1 SMOKE HEAT 8 (A/B)9 LOOP 1 SMOKE HEAT 9 (A/B)10 LOOP 1 SMOKE HEAT 10 (A/B)11 LOOP 1 SMOKE HEAT 11 (A/B)________________________________________OK=Details, 0=Disconnect, 1=Print List2=Set In Fire, 3=Erase
7/25/2019 CS4000 Service and Maintenance manual.pdf
34/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
31
Add loop units (press 3 at Loops screen)
Add loop units
- Press UP/DOWN navigate among the rows- Use the numerical keypad to give the selected loop unit an
address
- Press OK to add the selected loop unit with the specified
address, note that all the entered information must be valid
before a loop unit can be added
- Press < to return to the Loops screen
Scan loop (press 4 at Loops screen)
Add loop units
- Press OK perform the scanning
- Press < to regret
ADD LOOP UNIT________________________________________Physical Central addr.: 1 (valid)Physical Board address: 6 (valid)
Physical Loop address : 1 (valid)Physical Unit address : 0 (invalid)NNNNNNNNLogical Zone number : 0 (invalid)Logical Unit address : 0 (invalid)Type: 4 (ALL_LOOP_DEVICES)T1:T2:
________________________________________Enter value with numeric keyboard.
UP/DOWN=New field, OK=Add Unit,'
7/25/2019 CS4000 Service and Maintenance manual.pdf
35/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
32
6 Reload Configuration
The screen is used when a new updated configuration file or
supplementary text file has been downloaded to the CS4000
system.
Reload configuration screen
- Press 1to reload the entire configuration. The system will
re-start and then use the new configuration file.
- Press 2to update the supplementary text files (no re-start
needed). Before updating the texts, a new configuration file
should be downloaded (see Service menu 7Load config from
Memory Stick). The file should be identical with the previous
configuration file, except for the texts.
RELOAD CONFIGURATION 12 36
1 Load entire configuration2 Load Supplementary Texts only
_______________________________________Select a menu with 1-2 (or arrows + OK)
7/25/2019 CS4000 Service and Maintenance manual.pdf
36/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
33
7 Load config f rom Memory Stick
The screen is used to download a new configuration file from
the Salwico Memory Stick.
Load config from Memory Stick screen
- Press OKto download the selected file
- Press
7/25/2019 CS4000 Service and Maintenance manual.pdf
37/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
34
8 Upload config to Memory Stick
The screen is used copy the existing CS4000 configuration
file to the Salwico Memory Stick.
Upload config to Memory Stick screen
- Press OKto upload the configuration
- Press
7/25/2019 CS4000 Service and Maintenance manual.pdf
38/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
35
9 Save changes to configuration
The screen is used to save all changes made to the system
configuration from the control panel. Note that the changes
are not permanently saved in the configuration file until thiscommand is performed. A backup of the old configuration
file should be saved on a Memory Stick (menu 6.8) before
saving changes to the configuration.
Save changes to configuration screen
- Press OKto save the changes
- Press
7/25/2019 CS4000 Service and Maintenance manual.pdf
39/72
Service & Maintenance manual Chapter7: Service menu in CS4000 (access level 4)Salwico CS4000
36
10 Upload syslog to Memory Stick
The screen is used to upload a system log with service
information to the Salwico Memory Stick. This service log
can then be sent to Consilium for further technical assistance.
Upload syslog to Memory Stick screen
- Press OKto upload the system log
- Press
7/25/2019 CS4000 Service and Maintenance manual.pdf
40/72
Service & Maintenance manual AppendixA: Fault codes & FusesSalwico CS4000
37
Appendix A: Fault codes & Fuses
Fault lis t
Listed below are all fault codes, their causes and how anoperator with some knowledge of the system can solve the
problem.
Fault code Cause Remedy
Wrong type of loop
unitExchange to the correct loop unit
Two loop units have
the same addressCheck the units
Hardware fault Exchange the unit
A fuse is blown (a
secondary fault
appears)
Exchange the fuse128
NO ANSWER
Lost communication. Thesystem has recognized a
unit but lost contact with it
due to some interference.Cable break in a
detector or system loop
(a secondary fault
appears)
Mend the cable
The detector has a
faulty sensor element.Exchange unit
129 SENSOR FAULTThe smoke detector is
exposed to wind
Take care of wind problem
Try to clean the detector with a
vacuum cleaner or by blowing high-
pressure air on it. If this does not
help, exchange the detector.130 DIRTY SENSOR
The detector has a dirty
sensor element
Ion smoke detector: Exchange the
detector
Fewer loop units found
than configured
Check the specification and re-
define the system
Loop units not
correctly installedConnect the unit correctly
131 TOO FEW FOUND
Missing answer from a
unit
Check address (possible doubleaddress). Otherwise exchange the
unit.
132 TOO MANY FOUNDMore loop units found
than configured
Check the specification and re-
define the system
133 IN1 CABLE BREAKThere is a cable break
on input 1Mend the cable break
134 IN2 CABLE BREAKThere is a cable break
on input 2Mend the cable break
135 EXT 24V FAILExternal 24V power
source missing.The local power supply is defect.
7/25/2019 CS4000 Service and Maintenance manual.pdf
41/72
Service & Maintenance manual AppendixA: Fault codes & FusesSalwico CS4000
38
136 FEEDBACK FAULTExternal load is
missing.
Check the cable and the external
load.
137 POSITION FAULT
A supervised unit (for
example a door or
damper) is in the wrongposition.
Check for obstructions.
138 LOOP CABLE SHORTA short circuit in the
detector loop cable.Locate the short circuit and fix it.
139 LOOP CABLE A SHORTShort circuit on the A-
side of a detector loop.Locate the short circuit and fix it.
140 LOOP CABLE B SHORTShort circuit on the B-
side of a detector loopLocate the short circuit and fix it.
141CABLE BREAK
POSITIVE
A cable break on the
positive conductor has
been detected.
Locate the cable break and mend it.
142CABLE BREAK
NEGATIVE
A cable break on the
negative conductor has
been detected.
Locate the cable break and mend it.
Two units have the
same address.Check the loop unit addresses
Loop unit faulty. Exchange the unit.143
COMMUNICATION
ERROR
The communication with
a unit is deficient. Interference Locate interference and deal with it.
144WRONG TYPE OF
UNIT
The type of unit
specified is different
from the type found or
configured.
Check the specification and change
definition or the unit.
Unit faulty Exchange the unit
145
UNKNOWN TYPE OF
UNIT
The type of unit specified
is unknown to the system.
Wrong type of detector
has been installed
Install the correct type and restart
the loop.
146 TIMER STUCKThe timer has been
activated too long.Check the unit.
148 DOUBLE ADDRESSTwo units sharing the
same addressChange one of the addresses.
149 CABLE SHORT Short circuit on cable. Locate the short circuit and fix it.
150 VALVE CLOSED The valve is closed. Open the valve
151CONFIGURED NOT
PRESENT
Unit is configured but
not present.
Add the unit or change the system
configuration.
152PRESENT NOT
CONFIGURED
Unit is present but not
configured.
Remove the unit or change the
system configuration.
153HIGH CURRENT ON
LOOP
There is high current in
the loop cable.
Check if there is to many units
connected to the loop. Compare
with the loop limitations.
7/25/2019 CS4000 Service and Maintenance manual.pdf
42/72
Service & Maintenance manual AppendixA: Fault codes & FusesSalwico CS4000
39
154 LOOP POWER LOSSThe loop voltage is
missing.Exchange the loop board.
155EARTH FAULT
POSITIVE
Too low impedance on
positive conductor.Locate the earth fault and fix it.
156EARTH FAULT
NEGATIVEToo low impedance onnegative conductor.
Locate the earth fault and fix it.
157 FUSE FAULT A fuse is defective. Replace the fuse.
158BATTERY FUSE
FAULT
A battery fuse has
blown or a cable break.Replace fuse or mend the cable.
159 CABLE BREAKA cable break has been
detected.Mend the cable.
160 CABLE OVERLOADToo high current on an
output.Check external loads.
161 POWER FAULTThe main power supply
is lost.
Check the main power supply.
162EMERGENCY POWER
FAULT
Emergency power is
lost.Check the emergency power supply.
163 BATTERY FAULTA bad battery is
detected.
Charge the battery. If the fault
remains then replace the battery.
164 CHARGING LOSS
The battery charger is
unable to charge the
battery.
Replace the battery charger.
165 EXTERNAL FAULTExternal equipment has
indicated fault.Check the external equipment.
166
EARTH DETECTION
FAULT
Unable to detect earth
fault. Replace the earth fault circuit.
167 CHECKSUM EEPIncorrect EPROM
checksum.Contact our service department.
168 RESTARTEDSomething has
restarted.
If it happens repeatedly, contact our
service department.
169 TOO LONG BOOTExceeded the maximal
allowed boot time.
If it happens repeatedly, contact our
service department.
170EXTERNAL LOAD ON
LINE
There is a too high
external load on a
conventional zone.
Locate the load and deal with it.
171 EXTERNAL SOURCEON LINE
Feeding voltage
detected on a
conventional zone.
Locate the source and remove it.
7/25/2019 CS4000 Service and Maintenance manual.pdf
43/72
Service & Maintenance manual AppendixA: Fault codes & FusesSalwico CS4000
40
172LOW POWER SUPPLY
IN1
Low voltage on the
primary 24VDC power
supply to the internal
PCBS.
Check the power supply.
173LOW POWER SUPPLY
IN2
Low voltage on thesecondary 24VDC
power supply to the
internal PCBS.
Check the power supply.
174LOW POWER SUPPLY
LOCAL
Too low voltage on the
3.3V/5V feeding to the
internal circuit boards.
Contact our service department.
175 LOW POWER SUPPLY
Too low incoming
24VDC supply to the
internal circuit boards.
Check the power supply
The configuration fileis corrupt. Check the configuration file and re-configure the system.
176 SYSTEM CONF FAULT An error has occurred
during downloading of
the configuration file.
Re-configure the system. If the fault
remains, contact our service dept.
177 LOW PRESSUREExternal equipment
indicates low pressure.
Check the pressure on the
supervised unit.
178 ACTUATOR 1Missing feedback from
actuator 1
Check cables to actuator 1. If the
cables are OK, change the actuator.
179 ACTUATOR 2Missing feedback from
actuator 2.
Check cables to actuator 2. If the
cables are OK, change the actuator.
180 MAINS POWER The main power supplyis lost
Check the main power supply
181 INTERNAL FAULT Internal system fault Contact our service department
209WRONG TYPE OF
UNIT DEFINED
The type of unit found
is different from the
type configured.
Change the unit or the system
configuration.
210Error in cause&effect
definitions
Fault detected in the
configuration.Check the configuration.
255 ILLEGAL Internal system error. Contact our service department.
7/25/2019 CS4000 Service and Maintenance manual.pdf
44/72
Service & Maintenance manual AppendixA: Fault codes & FusesSalwico CS4000
41
Fuses
If a fuse is defective in the system a fault will be displayed at
the control units. Locate and replace the fuse with the
information below.
Fuse list
Location Fuse Fuse rating
Base board F1: Alarm bell output 1AT
Base board F2: Alarm bell output 1AT
Base board F3: Alarm bell output 1AT
Base board F4: Alarm bell output 1AT
Rectifier board F3: To transformer 3.15AF
Rectifier board F4: To transformer 3.15AF
Rectifier board F5: To external 230VAC 3.15AF
Rectifier board F6: To external 230VAC 3.15AFRectifier board F8: Battery 4 AF
Rectifier board F9: Battery 4 AF
Rectifier board F10: From transformer 6 AF
Rectifier board F11: From transformer 6 AF
Fuse type: 5 x 20 mm
Fuse locations on base board, BB.
Fuse locations on rectifier board, RB.
7/25/2019 CS4000 Service and Maintenance manual.pdf
45/72
Service & Maintenance manual AppendixB: Connections for loop unitsSalwico CS4000
42
Appendix B: Connections for loop units
7/25/2019 CS4000 Service and Maintenance manual.pdf
46/72
Consilium Marine
Connection of loop units 1/2
Detectors Manual call points
NS-AOS NS-ACPNS-AIS NS-ACP IP55NS-AH/AIS NS-ACPWPNS-AOHSNS-AH/CSNS-AIHSNS-AUV
Short circuit isolator Timer
NS-SCI NS-TIMAC
+1
-2+3-4
Loop IN
Loop OUT
Address units
Addressable IS units
NS-AOS-ISNS-AOHS-IS
ACP-IS
5 (+)
7 (+)8 (-)
6 (-)
2
1
Loop OUT
Loop IN
NS-AIN1/ID2
2 (-)3 (+)4 (-)
1 (+)
2
1 11 (+)12 (-) 2
1
2 (-)1 (+)
NS-ISOLATOR
Safe area Hazardous area, IS units
+ 11 +2 2
IS unit
+ +ELR-33
1
2
Last IS unit
1 (+)2 (-)
3 (+)4 (-)
Loop IN
Loop OUT
6 (-)
8 (-)7 (+)
5 (+) +12 2
1
2
1
2
1ELR-33
NS-AIN1/ID3
Detector Last detector
Conventional detectors
+ ++
Loop OUT
Loop IN
3 (+)
6 (-)
8 (-)7 (+)
5 (+)4 (-)
NS-AIN2/ID7
1 (+)2 (-)
ELR-4.7
ELR-4.7
Sprinkler station
Flow switch (no flow position)
Sprinkler valve (open position)
Loop OUT
Loop IN
3 (+)
6 (-)
8 (-)7 (+)
5 (+)4 (-)
NS-AIN2/ID8
1 (+)2 (-)
ELR-4.7 Input
Hazardous areaSafe area
NS-AOS-IS
1(+)2(-)
21(+)22(-)
24(-)23(+)
Loop in
Loop out
NS-ISOLATOR-A
1(+)2(-)
To next IS unit
(max 20)
Call point circuits
Black (-) Red (+)
ACP-ISNS-AOHS-IS
7/25/2019 CS4000 Service and Maintenance manual.pdf
47/72
Consilium Marine
Connection of loop units 2/2
Address units
AE-2AE-2K
AE-2K/IAE-2E
ID Switch
Detectors Manual call points
RDJ-2, RDJ-2T LKA01LKA05RDO-2TDT-2HA100-HA110OA100-140IA100-140
WITH BASES:UB-1, UB-2SPB-ADAPT
Loop units
KS-2, KS-2KVE-1, VE-2LK-2, LK-2KSID-38SID-38TTDT-2KUR-2KUR-2KNVL-2, VL-2K
Black
Loop in
Red
Call point circuits
Loop out+
-
7/25/2019 CS4000 Service and Maintenance manual.pdf
48/72
Service & Maintenance manual AppendixC: System modulesSalwico CS4000
45
Appendix C: System modules
The system modules are building blocks in the fire alarm
system. The system can be designed according to customers
needs. All functions in the modules, including the control
unit, are performed by circuit boards. By combining these
modules, a system can be built which performs the function
desired by the customer. The circuit boards available are:
Panel Board, PB
Base Board, BB
Rectifier Board, RB Loop Board, LB3
Zone Board, ZB
Output Board, OB
Ethernet Board
USB expansion Board
MUX Board, MB
See following pages for detailed information about each
circuit board.
7/25/2019 CS4000 Service and Maintenance manual.pdf
49/72
CS4000 System boards
PB, Panel Board
Part no. 462002
System: Salwico CS4000 fire alarm
Description
The printed circuit board Panel Board, PB, is a system
module in the Salwico CS4000 fire alarm system.
The Panel Board together with the alphanumericaldisplay, keyboard, terminal board and a cabinet forms thecontrol/repeater panel in the CS4000 system.
The Panel Board is equipped with some basic in- andoutputs and a RS232 serial interface.
For more information about how to connect the differentCS4000 system boards together, please refer to CS4000
Service & Maintenance manual.
Specifications may be subject to change for improvement without prior notice Data sheet no: 462002 PB panel board 06 2 EPage 1 of 3
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
DIP switch
The 8-pole DIP switch has two functions:1. Switch 1-7
Set the address for the Panel Board (1-127).2. Switch 8
Set if the Power LED shall be affected by thedimmer function or not (from vers. 4).
Switch 8 on = Power LED affected by dimmerSwitch 8 off = Power LED fully lit.
Data
Nominal voltage 27 VDCWorking voltage 19-30 VDCWorking current 65-85 mA
(excl. buzzer output)Temperature range 0C to +55CWeight panel board ~150 g
Weight display ~200 gWeight terminal board ~60 g
Dimensions PB 180x120x27Dimensions display 145x104x15Dimensions terminal board 127x45x30Art. No. terminal board 057860
Art. No. keyboard, control 461001Art. No. keyboard, repeater 461004
Example address switch setting:
1 2 3 4 5 6 7 8
O
N
1 2 4 8 16 32 64 D im mer funct io n on
Board adress no.
1+4+64=69
Block diagram
PB, Panel Board
Alphanumerical display
External system channel B out :
To next Panel Board (if any)
External system channel A out:
To next Panel Board (if any)
External system channel A in:
From Base Board
External system channel B in:From Base Board
Terminal board
0SystemFault
H om e D is c.
Test
AlarmDevice
Power
AlarmTransfer
AlarmDelay
Zone/Unit
2
Warning
OK
Pre-Alarm
Menu
Reset
FIREF AULT DISC.
NextMute
OK
ABC3
DEF' '1
5JKL 6MNOGHI4
8TUV
9WXYZPQRS
7
F1
F2
F3
Keyboard
7/25/2019 CS4000 Service and Maintenance manual.pdf
50/72
CS4000 System boards
PB, Panel Board
Component layout
Jumpers
Specifications may be subject to change for improvement without prior notice Data sheet no: 462002 PB panel board 06 2 EPage 2 of 3
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
JP1
Run. Fitted during normal operation.
Move to JP4 during programming of PB.
JP2-3
RS485 termination port 1, normally open
(mounted on last board on external system channel)JP4
Prog. Fitted during programming of PB.
Move back to JP1 after programming.
JP5-6
RS485 termination port 2, normally open(mounted on last board on the external systemchannel).
LEDs
D1 Power RS232D9 Local powerD20 RS485 Ch.1 RXD21 RS485 Ch.1 TXD22 RS485 Ch.2 RX
D25 RS485 Ch.2 TXD26 RS232 TXD27 RS232 RX
Connectors
J1 To keyboard.J2 To terminal board.J3 Buzzer.J4 To display.J5 To terminal board.
J7 Backlight display.J8 To keyboard.J9 Door switch.J10 RS232 (printer).J11 External system channel A.J12 External system channel B.
J13 Contact for download of software to PB.(fitted on version R1D and later)
Potentiometer
R139 Adjust contrast on display
7/25/2019 CS4000 Service and Maintenance manual.pdf
51/72
CS4000 System boards
PB, Panel Board
Terminals
Terminal board layout
Terminal data
DESCRIPTION TERMINAL NO. FUNCTION DATA
1 Power +
2 Power -
24VDC, 65-85mA total on A+Bchannel, (excl. buzzer output)
3 Communication, a
External system channel A,IN
4 Communication, bRS485
5 Power +
6 Power -
24VDC, 65-85mA total on A+Bchannel, (excl. buzzer output)
7 Communication, a
External system channel B,IN
8 Communication, bRS485
11 Power +
12 Power -
24VDC, 50mA total on A+B
channel13 Communication, a
External system channel A,OUT
14 Communication, bRS485
15 Power +
16 Power -
24VDC, 50mA total on A+Bchannel
17 Communication, a
External system channel B,OUT
18 Communication, bRS485
19 +External buzzer out
20 -24VDC, max 100mA
21 TX out
22 RX in
23 RTS out
24 CTS in
Interface output, RS232
25 GND
RS232, isolated
Internal FA signal 26 Input Active low
31 +Output 1
32 -
33 +Output 2
34 -
35 +Output 3
36 -
24VDC, max 80mA
37 +Input 1
38 IN
39 +Input 2
40 IN
Not isolated. Active whenshorted.
Specifications may be subject to change for improvement without prior notice Data sheet no: 462002 PB panel board 06 2 EPage 3 of 3
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
7/25/2019 CS4000 Service and Maintenance manual.pdf
52/72
CS4000 System boards
BB, Base Board
Part no. 462001
System: Salwico CS4000 fire alarm
Description
The printed circuit board BB, Base Board is a systemmodule in the Salwico CS4000 fire alarm system.
The Base Board is the motherboard in the system,
containing all the basic in- and outputs and controlling thesystem communication.
For more information about how to connect the different
CS4000 system boards together, please refer to CS4000Service & Maintenance manual.
Data
Nominal voltage 27 VDCWorking voltage 19-30 VDC
Working current 110 mACable terminals 2.5 mm2
Temperature range 0C to +55CWeight ~380 g
Dimensions (bxhxd) 248x127x37
Specifications may be subject to change for improvement without prior notice Data sheet no: 462001 base board 08 1 EPage 1 of 4
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
Address switch
The 8-pole DIP switch is used to set the central and baseboard address.Switch 1-4 is dedicated for the board address, and switch5-8 to the central address.The address number can be set from 1 to 15.
Example:
Block diagram
24 VDC from RB
Basic inputs Basic outputs
Base Board, BB
Panel Boards
Loop/Zone Boards
USBEthernet
Relay boards
1 2 3 4 5 6 7 8
O
N
1 2 4 8 1 2 4 8
Board no. Central no.
5 4
7/25/2019 CS4000 Service and Maintenance manual.pdf
53/72
CS4000 System boards
BB, Base Board
Component layout
Jumpers
JP1-4
If fitted, relay 4-7 follows the GA input.
JP5
Internal function.Should always be mounted towards reset button
Specifications may be subject to change for improvement without prior notice Data sheet no: 462001 base board 08 1 EPage 2 of 4
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
JP6-7
RS485 termination port 1, should normally be open(mounted away from terminal P12)
JP8-9RS485 termination port 2, should normally be open(mounted away from terminal P12)
JP 10-11
RS485 termination port 3, should normally be open
(mounted away from terminal P12)
JP12-13
RS485 termination port 4, should normally be open(mounted away from terminal P12)
JP14
0 or 24VDC on terminal 27-28.
For more info, see Terminals.
ConnectorsP1 Internal system channel and rectifier board, RBP5 Background debug monitor, BDM
P6 Ethernet expansionP7 USB expansionP9 USB DeviceP10 External buzzerP13 To relay board, OBP14 To panel board, channel A
P15 To panel board, channel BP16 Back up power
LEDs
D4 Relay 4D5 Relay 1
D9 Relay 5D10 Relay 2D14 Relay 6D15 Relay 3D17 Relay 7D21 Fire indication
D19 Input 4 activeD22 Input 3 activeD23 Input 2 activeD24 Fault indicationD25 Input 1 activeD27 fault base board
D31 Relay 8, Bell output 1D36 Relay 9, Bell output 2
D44 TX port 1D45 RX port 1D48 TX port 2D49 RX port 2
D52 Power OK port 2
D53 RX port 3D54 TX port 3D57 TX port 4D58 RX port 4D72 Power to base board
Fuses
F1 Alarm bell outputF2 Alarm bell outputF3 Alarm bell outputF4 Alarm bell output
All fuses are 5x20mm, 1AT.
7/25/2019 CS4000 Service and Maintenance manual.pdf
54/72
CS4000 System boards
BB, Base Board
Terminals
Terminal layout
Terminal data
DESCRIPTION TERMINAL FUNCTION DATA
1 Power +
2 Power -24VDC, max 350mA
3 Communication, a
External system channel AControl & repeater panel
4 Communication, bRS485
5 Power +
6 Power -24VDC, max 350mA
7 Communication, a
External system channel BControl & repeater panel
8 Communication, bRS485
9 TX
10 RX
11 RTS
12 CTS
13 GND
RS232, isolated.
14 A
15 B
16 GND17 A
Interface output(RS232 or RS485)
18 B
RS485, isolated
19 +Input 1
20
21 +Input 2
22
23 +Input 3
24
25 +Input 4
26
Not isolated. Activated when terminals areshorted.For example GA auto input.
Specifications may be subject to change for improvement without prior notice Data sheet no: 462001 base board 08 1 EPage 3 of 4
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
7/25/2019 CS4000 Service and Maintenance manual.pdf
55/72
CS4000 System boards
BB, Base Board
Specifications may be subject to change for improvement without prior notice Data sheet no: 462001 base board 08 1 EPage 4 of 4
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
27 +
Programmable DC out
28 -
27VDC, max 500mA (max 900mA on version R2C orlater).JP14 mounted away from terminals= inactive 0V, active
24VDC.JP14 mounted towards terminals= inactive 24VDC,active 0V
29 +24VDC out
30 -
31 +24VDC out
32 -
27VDC, max 500mAVmin=18.5VDCVmax=27.5VDC
33 +Alarm transfer
34 -Must be terminated with end of line resistor 10k
35 NC
36 CProgrammable output 1
37 NO
38 NC39 CProgrammable output 2
40 NO
41 NC
42 CProgrammable output 3
43 NO
44 NC
45 C
Programmable output 4(follows GA if jumper JP1 ismounted) 46 NO
47 NC
48 C
Programmable output 5(follows GA if jumper JP2 ismounted) 49 NO
50 NC51 C
Programmable output 6(follows GA if jumper JP3 ismounted) 52 NO
27VDC, max 1A
53 +Bell output 1
54 -
55 +Bell output 2
56 -
24VDC, max 800mAVmin=19.5VDCVmax=27.5VDCEnd of line resistor 33k
57 +Input GA morse
58
Not isolated.Active when shorted
59 +PA mute
60
Not isolatedActive when shorted
Internal FA signal output61 Open
collector
Active low
62 NC
63 C
Programmable output 7(follows GA if jumper JP4 ismounted) 64 NO
27VDC, max 1A
7/25/2019 CS4000 Service and Maintenance manual.pdf
56/72
CS4000 System boards
RB, Rectifier Board
Part no. 462005e1
System: Salwico CS4000 fire alarm
Specifications may be subject to change for improvement without prior notice Data sheet no: 462005e1 RB rectifier board 08 1 EPage 1 of 3
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
Description
The printed circuit board RB, Rectifier Board, is a
system module in the Salwico CS4000 fire alarmsystem.
The Rectifier Board together with the transformerforms the power supply unit for the CS4000 central,including battery-charging function for the internal
batteries.
There are three types of transformers available:100VAC, 115/230VAC and 115/230VAC with anauto-reset thermal switch. For older revisions (R1A-D)an obsolete 115/230VAC transformer were used.
For more information about how to connect thedifferent CS4000 system boards together, please refer
to the CS4000 Service & Maintenance manual.
Address switch
The 8-pole DIP switch is used to set the address for RB
Rectifier Board. Each board in a system has its ownunique address.The address no. can be set from 1 to 255.
Data
Input voltage 100, 115 or 230 VAC
Output voltage 28 VDCWorking current 70 mAMax output 28 VDC, 3 ACable terminals P1-P2 4 mm2
Cable terminals P5-P7 2.5 mm2
Temperature range +5C to +55C
Weight RB ~475 g
Dimensions RB 175x100x72 mmWeight transformer ~1850 gDimensions transformer 95, height 45 mmPart no. transformer:
-Rev. R1A, B, C, D: -53052 (115/230VAC)-Later revisions: -53053 (115/230VAC)
-53054 (115/230VAC withheat fuse)
-53055 (100VAC)Charge capacity 0.25A (battery size 2.3-10Ah)
For more data, see under Terminals.
Example address switch setting:
Block diagram
1 2 3 4 5 6 7 8
O
N
1 2 4 8 16 32 64 128
Board adress no.
1+ 4+ 64= 69
7/25/2019 CS4000 Service and Maintenance manual.pdf
57/72
CS4000 System boards
RB, Rectifier Board
Specifications may be subject to change for improvement without prior notice Data sheet no: 462005e1 RB rectifier board 08 1 EPage 2 of 3
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
Component & Terminal layout
Jumpers
JP1
Programming mode. Fitted during programming of RB.Move to JP4 when programming is completed.
JP2-JP3
Not used
JP4
Run mode, fitted during normal operation. Move to JP1during programming of RB.
JP5
Battery charge boost. Fit jumper to increase battery
charge current from 0.25A to 1A. Note: Max outputcurrent (P3+P4) will then be decreased to max 2.25A.
Connectors
P1 Power in- and output.P2 To transformerP3 Internal system channel A to LB3/ZB.P4 Internal system channel A to Base Boards + separate
power to bell outputs on Base Board.
P5 From transformer.P6 Programmable relay output 1.P7 Programmable relay output 2.
P8 BatteriesP9 Contact for download of software to RB.P12 Internal system channel B
Change over funct ion
The rectifier board has an in-built change over functionbetween the two 110/115/230VAC inputs (main andemergency). If there is only one 115/230VAC power
supply available, it shall always be connected toemergency.
Note: The rectifier board will not start up if100/115/230VAC is connected to mains unless
the batteries are connected first.
LEDs
D7 Relay 1. Green.D10 System fault. Yellow.D11 Relay 2. Green.D23 TX data port 1. Green.D24 RX data port 1. Green.
D27 TX data port 2. Green.D28 RX data port 2. Green.D31 Power to board OK. Green.D33 Battery fault. Yellow.D34 Forced battery charge. Green.
D35 Battery circuit OK. Green.D36 Indicates battery test. Yellow.
Fuses
F3-F4 3.15AT To transformerF5-F6 3.15AT To external mainsF8-F9 4 AF BatteryF10-F11 6.3AF From transformer
Fuse type: 5x20 mm
7/25/2019 CS4000 Service and Maintenance manual.pdf
58/72
CS4000 System boards
RB, Rectifier Board
Specifications may be subject to change for improvement without prior notice Data sheet no: 462005e1 RB rectifier board 08 1 EPage 3 of 3
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
Terminals Transformer connection
Terminal layout
Terminal data
DESCRIPTION TERMINAL NO. FUNCTION DATA
1 ~From transformer
2 ~
32 VACImin=0.1A, Imax=5A
3 aInternal system channel A
4 b
RS485
11 C
12 NC
Programmable output 1
14 NO
21 C
22 NC
Programmable output 2
24 NO
Max 230 VAC, 5A
101 ~Power in, main
102 ~
100 / 115 / 230 VAC +10%/-15%,50-60 Hz
103 ~Power in, emergency
104 ~
100 / 115 / 230 VAC +10%/-15%,50-60 Hz
105 ~Power out
106 ~
Output 100 / 115 /230 VDCImax=1A
107 ~
108
To transformer
109 ~
Output 100 / 115 / 230 VDCImin=0.1A Imax=1.0A
P8 +BatteryP8 -
24 VDC.Max charging current to battery is0.25 / 1A*
P3 +Power to LB3/ZB (c.i.e)
P3 -
P4 +Power to base board(c.i.e) P4 -
Vmin=18.5VDCVmax=28VDCVripple=200mV RMSImax=3A / 2.25A*. Total P3+P4
Notes
If only one 100/115/220VAC power supply is provided, it shall be connected to Power in, emergency.
When replacing the batteries, make sure to use batteries with the same specification as the original.
*If battery charger boost (jumper 5) is fitted.
7/25/2019 CS4000 Service and Maintenance manual.pdf
59/72
CS4000 System boards
LB3, Loop Board
Part no. 462003
System: Salwico CS4000 fire alarm
Description
The printed circuit board LB3, Loop Board is a system
module in the Salwico CS4000 fire alarm system.
The Loop Board is a connection board for 3 analogueaddressable detector loops. Each analogue addressableloop can have up to 254 loop units.
For more information about how to connect the differentCS4000 system boards together, please refer to the
CS4000 Service & Maintenance manual.
Specifications may be subject to change for improvement without prior notice Data sheet no: 462003 LB3 loop board 06 2 EPage 1 of 2
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
Address switch
The 8-pole DIP switch is used to set the address for LB3Loop Board. Each board in a system has its own uniqueaddress. The address no. can be set from 1 to 255.
Data
Nominal voltage 27 VDC
Working voltage 19-30 VDCWorking current 340 mACable terminals 2.5 mm
2
Temperature range 0C to +55C
Weight ~300 gDimensions (bxhxd) 247x127x25
Example address switch setting:
1 2 3 4 5 6 7 8
O
N
1 2 4 8 16 32 64 128Board adress no.
1+4+64=69
Block diagram
7/25/2019 CS4000 Service and Maintenance manual.pdf
60/72
CS4000 System boards
LB3, Loop Board
Component layout
Jumpers
JP1Run mode. Fitted during normal operation.Move to JP2 during programming.
JP2Programming mode. Fitted during programming.
Move to JP1 after programming is completed.
JP3Not used
Connectors
P1 Internal system channel A, incl. power supply fromRB, rectifier board.
P2 Contact for download of software to LB3P3 Connection of detector loop 1
P4 Connection of detector loop 2P5 Connection of detector loop 3P6 Internal system channel B. Only used if redundancy
of the internal system channel is required.
LEDs
D1 Indication for processor, Green.D2 System fault. Yellow.D16 Fire indication, loop 1. Red.D17 Fault indication, loop 1. Yellow.D18 Communication, loop 1. Green.
D27 Fire indication, loop 2. Red.D28 Fault indication, loop 2. Yellow.D29 Communication, loop 2. Green.D38 Fire indication, loop 3. Red.D39 Fault indication, loop 3. Yellow.D40 Communication, loop 3. Green.
Terminals
DESCRIPTION CONNECTOR TERMINAL NO. FUNCTION DATA
P3 11 +Fire loop 1 A side
P3 12 -P3 13 +Fire loop 1 B side
P3 14 -
P4 21 +Fire loop 2 A side
P4 22 -
P4 23 +Fire loop 2 B side
P4 24 -
P5 31 +Fire loop 3 A side
P5 32 -
P5 33 +Fire loop 3 B side
P5 34 -
28VDC,
max 300mA/loop
Specifications may be subject to change for improvement without prior notice Data sheet no: 462003 LB3 loop board 06 2 EPage 2 of 2
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
7/25/2019 CS4000 Service and Maintenance manual.pdf
61/72
CS4000 System boards
ZB, Zone Board
Part no. 462006
System: Salwico CS4000 fire alarm
Description
The printed circuit board ZB, Zone Board, is a system
module in the Salwico CS4000 fire alarm system.
The Zone Board is a connection board for16 conventional detector zones or 16 digital inputs*.
Each conventional zone can accommodate up toapproximately 50 detectors, depending on the totalpower consumption on the zone.
For more information about how to connect the
different CS4000 system boards together, please referto the CS4000 Service & Maintenance manual.
Specifications may be subject to change for improvement without prior notice Data sheet no: 462006 ZB zone board 06 4 EPage 1 of 3
ConsiliumConsilium Marine ABP.O. Box 8763, SE-402 76 GteborgPhone +46 31 7107700 Fax +46 31 7107800www.consilium.se
Address switch
The 8-pole DIP switch is used to set the address forZB Zone Board. Each board in a system has its ownunique address.
The address no. can be set from 1 to 255.
Data
Nominal voltage 27 VDC
Working voltage 19-30 VDCWorking current 140 mAMax current/zone