+ All Categories
Home > Documents > CURRENT TRANSDUCERS - Flex-Core® · sales@flex-core.com 92 CURRENT TRANSDUCERS AC CURRENT...

CURRENT TRANSDUCERS - Flex-Core® · sales@flex-core.com 92 CURRENT TRANSDUCERS AC CURRENT...

Date post: 18-Jan-2019
Category:
Upload: ngothu
View: 224 times
Download: 0 times
Share this document with a friend
1
CURRENT TRANSDUCERS PHONE (614) 889-6152 TECH. ASSISTANCE (614) 876-8308 FAX # (614) 876-8538 4970 Scioto Darby Rd. Hilliard, Ohio 43026 Div. Morlan & Associates, Inc. WWW.FLEX-CORE.COM sales@flex-core.com 92 CURRENT TRANSDUCERS AC CURRENT TRANSDUCER/TRANSFORMER MODELS AT, ATR (0,1,2) 3.50 2.4 2.18 0.74 The AT & ATR (0,1,2) series of AC Current Transducers provide a proportional analog output. Average responding (AT) and true RMS (ATR) designs are available. Jumper selectable input ranges Magnetically isolated output Available in solid or split-core designs UL/CE Approved Current Range ......................................... See Table Frequency ATx-005 or 010....................................... 50-60Hz ATx-420 ................................................ 20-100Hz ATRx-420 ............................................. 10-400Hz Isolation Voltage .............. 1270Vac (Tested to 5kV) Temp. Range..................................-20 O C to +50 O C Humidity Range ......... 0-95% RH, Non-Condensing Accuracy ...................................................1.0% F.S. Response Time ATx-005 or 010.......................................... 100ms ATx-420 ..................................................... 300ms ATRx-420 .................................................. 600ms Supply Voltage ATx-005 or 010............................... Self-Powered ATx-420 ........................ 12-40Vdc Loop Powered ATRx-420 ..................... 12-40Vdc Loop Powered Weight .......................................................... 0.5 Lb. FEATURES SPECIFICATIONS DIMENSIONS CONNECTIONS All Dimensions In Inches 3.53 2.40 0.85 0.85 2.25 3.04 1.19 0.19 (-) (+) POWER SUPPLY 12-40Vdc (+) (-) 4-20mA (-) (+) R L 3.03 0.93 0.19 FT (Solid Core) SP (Split Core) 5V & 10V Models Direct Connection 4-20mA Models Loop-Powered Connection *4-20mA Models are Loop-Powered (12-40Vdc) **0-5V & 0-10V Output Models are Self-Powered E310017 (+) (-) (-) (+) 0-5Vdc (or) 0-10Vdc AVERAGE RMS RESPONDING SPLIT CORE (SP) AC INPUT (AMP) (JUMPER SELECTED) *4-20mA OUTPUT **0-5V OUTPUT **0-10V OUTPUT 0-2 0-5 AT0-420-24L-SP N/A N/A 0-10 0-20 0-50 AT1-420-24L-SP AT1-005-000-SP AT1-010-000-SP 0-100 0-150 0-200 AT2-420-24L-SP AT2-005-000-SP AT2-010-000-SP SOLID CORE (FT) 0-2 0-5 AT0-420-24L-FT N/A N/A 0-10 0-20 0-50 AT1-420-24L-FT AT1-005-000-FT AT1-010-000-FT 0-100 0-150 0-200 AT2-420-24L-FT AT2-005-000-FT AT2-010-000-FT TRUE RMS 4-20mA OUTPUT SPLIT CORE (SP) SOLID CORE (FT) AC INPUT (AMP) (JUMPER SELECTED) *4-20mA OUTPUT AC INPUT (AMP) (JUMPER SELECTED) *4-20mA OUTPUT 0-2 0-5 ATR0-420-24L-SP 0-2 0-5 ATR0-420-24L-FT 0-10 0-20 0-50 ATR1-420-24L-SP 0-10 0-20 0-50 ATR1-420-24L-FT 0-100 0-150 0-200 ATR2-420-24L-SP 0-100 0-150 0-200 ATR2-420-24L-FT
Transcript

CURRENT TRANSDUCERS

PHONE (614) 889-6152TECH. ASSISTANCE (614) 876-8308

FAX # (614) 876-85384970 Scioto Darby Rd. Hilliard, Ohio 43026Div. Morlan & Associates, Inc.

[email protected]

92

CU

RR

EN

T T

RA

NS

DU

CE

RS

AC CURRENT TRANSDUCER/TRANSFORMERMODELS AT, ATR (0,1,2)

3.50

2.4

3.03

2.18

0.93

0.74

0.19

• The AT & ATR (0,1,2) series of AC Current Transducers provide a proportional analog output.Average responding (AT) and true RMS (ATR)designs are available.

• Jumper selectable input ranges• Magnetically isolated output• Available in solid or split-core designs• UL/CE Approved

Current Range .........................................See TableFrequency

ATx-005 or 010 .......................................50-60HzATx-420 ................................................20-100HzATRx-420 .............................................10-400Hz

Isolation Voltage .............. 1270Vac (Tested to 5kV)Temp. Range..................................-20O C to +50O CHumidity Range .........0-95% RH, Non-CondensingAccuracy ...................................................1.0% F.S.Response Time

ATx-005 or 010 ..........................................100msATx-420 .....................................................300msATRx-420 ..................................................600ms

Supply VoltageATx-005 or 010 ............................... Self-PoweredATx-420 ........................ 12-40Vdc Loop PoweredATRx-420 ..................... 12-40Vdc Loop Powered

Weight ..........................................................0.5 Lb.

FEATURES

SPECIFICATIONS

DIMENSIONS

CONNECTIONS

All Dimensions In Inches

3.53

3.04

2.40

0.85

0.852.25

1.19

0.19

3.53

3.04

2.40

0.85

0.852.25

1.19

0.19

(-)

(+)

POWERSUPPLY12-40Vdc

(+) (-)

4-20mA(-)

(+)

RL

3.50

2.4

3.03

2.18

0.93

0.74

0.19

FT (Solid Core) SP (Split Core)

5V & 10V ModelsDirect Connection

4-20mA ModelsLoop-Powered Connection

*4-20mA Models are Loop-Powered (12-40Vdc)**0-5V & 0-10V Output Models are Self-Powered

E310017

(+) (-)

(-)

(+)0-5Vdc (or)0-10Vdc

AVERAGE RMS RESPONDINGSPLIT CORE (SP)

AC INPUT (AMP)(JUMPER SELECTED)

*4-20mAOUTPUT

**0-5VOUTPUT

**0-10VOUTPUT

0-20-5

AT0-420-24L-SP N/A N/A

0-100-200-50

AT1-420-24L-SP AT1-005-000-SP AT1-010-000-SP

0-1000-1500-200

AT2-420-24L-SP AT2-005-000-SP AT2-010-000-SP

SOLID CORE (FT)0-20-5

AT0-420-24L-FT N/A N/A

0-100-200-50

AT1-420-24L-FT AT1-005-000-FT AT1-010-000-FT

0-1000-1500-200

AT2-420-24L-FT AT2-005-000-FT AT2-010-000-FT

TRUE RMS 4-20mA OUTPUT

SPLIT CORE (SP) SOLID CORE (FT)

AC INPUT (AMP)(JUMPER SELECTED)

*4-20mAOUTPUT

AC INPUT (AMP)(JUMPER SELECTED)

*4-20mAOUTPUT

0-20-5

ATR0-420-24L-SP0-20-5

ATR0-420-24L-FT

0-100-200-50

ATR1-420-24L-SP0-100-200-50

ATR1-420-24L-FT

0-1000-1500-200

ATR2-420-24L-SP0-1000-1500-200

ATR2-420-24L-FT

Recommended