LIGHTING FIXTURE SCHEDULE
MOUNTINGTYPE MFR. CATALOG NO.DESCRIPTION LAMPS WATTSSYMBOL VOLTS NOTES
B
(2)
A 2'X2' LED TROFFER WITH DIMMING DRIVERCEILING
RECESSED120
CEILINGRECESSED
AECEILING
RECESSED
XEXIT LIGHT; SHADED AREA INDICATES EXITFACE; ARROW INDICATES DIRECTION OFEGRESS
120CEILING ORWALL 7'-0"
XREXIT LIGHT; SHADED AREA INDICATES EXITFACE; REMOTE CAPACITY
120
D
BECEILING
RECESSED
4' LED NARROW WRAPAROUNDCEILING
SURFACEK
EE 4' LED WIDE WRAPAROUND SURFACE
120
120
120
120
120
120
FE SURFACE 120
G 2' FLUORESCENT VANITY WALL BRACKETWALL6'-6"
DE 120SAME AS FIXTURE TYPE 'D', EXCEPTFIXTURE TO HAVE EMERGENCY BATTERYBACKUP
V EXTERIOR LED SCONCEWALL5'-0"
W EXTERIOR LED WALL PACK
120
120
120WALL10'-0"
6" OPEN REFLECTOR LED DOWNLIGHT WITHDIMMING DRIVER
35CEILING
RECESSED
35CEILING
RECESSED
40
40
1LED
4LED
LQM S W 3 R 120/277 ELN
LHQM S W 3 R HO RO
WL4 25L D24 LP835 NX 24
KENALL
OLW 23
FS824T-2TB-PIABR-27L40K-1-DV
30
35
SAME AS FIXTURE TYPE 'A', EXCEPTFIXTURE TO HAVE EMERGENCY BATTERYBACKUP
SAME AS FIXTURE TYPE 'B', EXCEPTFIXTURE TO HAVE EMERGENCY BATTERYBACKUP
SAME AS FIXTURE TYPE 'E', EXCEPTFIXTURE TO HAVE EMERGENCY BATTERYBACKUP
METALUX22EN-LD1-34-UNV
L835-CD13400 LM
3500K LED35
55
55
(3)
(4)
R
H
ELA DDB OMC H1006 1-H1006 MR11 6 10EXTERIOR REMOTE EMERGENCY LIGHT LITHONIAWALL7'-0"
NARROW LINEAR LED PENDANT WITHDIMMING DRIVER
PENDANT8'-0"
120
(5)
(3) (5)
40
(5)5400 LM
3500K LED2'X4' LED TROFFER WITH DIMMING DRIVER
5400 LM3500K LED
LITHONIA2500 LM
3500K LED
LITHONIA
LITHONIA
STL4 48L D50 LP835 NX4800 LM
3500K LED
STL4 48L D50 LP835 NXEL14L
4800 LM3500K LED
GOTHAM
GOTHAM
EVO 35/22 6AR MVOLTTRW
2200 LM3500K LED
EVO 35/22 6AR MVOLTTRW ELR
2200 LM3500K LED
2700 LM4000K LED
LITHONIA
LITHONIACEILING ORWALL 7'-0"
LITHONIA2700 LM
5000K LED
METALUX22EN-LD1-34-UNVEL10W-L835-CD1
3400 LM3500K LED
35
METALUX24EN-LD1-54-UNV
L835-CD1
CCEILING
RECESSED120 35 (5)
4000 LM3500K LED
2'X4' LED TROFFER WITH DIMMING DRIVER LITHONIA2TL4 40L FW A12
EZ1 LP835
TECHLIGHTING
700BCSLC26W-C-CF 2-24W T5/835 55
TECHLIGHTING
700LSVAN-W-S-LED8302400 LM
3000K LED
METALUX24EN-LD1-54-UNVEL10W-L835-CD1
(3) (5)
(3) (5)
(5)
(3)
(3)
(3)
(1)
(5)
ELECTRICAL SYMBOL LEGEND
DESCRIPTION
WIRING AND RACEWAY CONCEALED IN WALLS AND/OR ABOVE CEILING, UNLESS NOTEDOTHERWISE
SYMBOL
NOTE: ALL SYMBOLS MAY NOT BE REPRESENTED ON PLANS.
J
3
4
a
D
E
A-2HOMERUN; TEXT INDICATES PANEL DESIGNATION AND CIRCUIT NUMBER
UNSWITCHED PHASE CONDUCTOR TOWARDS HOME RUN TO DISTINQUISH LIGHTING CONTROL
JUNCTION BOX PER N.E.C.
SINGLE POLE SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F.
INDICATES CONDUIT STUBBED INTO SPACE; PROVIDE CONDUIT BUSHING
THREE-WAY SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F.
FOUR-WAY SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F.
LIGHT SWITCH; LOWER CASE LETTER DENOTES LIGHT FIXTURE BEING CONTROLLED
DIMMER SWITCH; 1500W, LOW VOLTAGE, MOUNT AT 48" O.C. A.F.F.
WIRING AND RACEWAY CONCEALED IN/OR UNDER FLOOR OR UNDERGROUND
OS
F
M
OS
R
G
E
C
GC
R
RECEPTACLE; NEMA 5-20R DUPLEX; 18" O.C. A.F.F. OR AS NOTED
RECEPTACLE; NEMA 5-20R DUPLEX; 18" O.C. A.F.F. OR AS NOTED; GFCI; NON FEED THRU
FAN CONTROL SWITCH; 120/277V, MOUNT AT 48" O.C. A.F.F.
MANUAL MOTOR STARTER SWITCH; 20A, 1 HP, 120/277V, MOUNT AT 48" O.C. A.F.F.
OCCUPANCY SENSOR WALL SWITCH; DUAL TECH.; MANUAL ON, AUTO OFF; (2) RELAYS FORCONTROL OF (2) LOADS; 1200W, LOW VOLTAGE, MOUNT AT 48" O.C. A.F.F.
EXISTING SWITCH TO BE REMOVED
RECEPTACLE; NEMA 5-20R DUPLEX; 44" O.C. A.F.F.
RECEPTACLE; NEMA 5-20R DUPLEX; 44" O.C. A.F.F.; GFCI; NON FEED THRU
EXISTING RECEPTACLE TO BE REMOVED
OCCUPANCY SENSOR; CEILING MOUNTED, DUAL TECHNOLOGY; LOW VOLTAGE
R
E
INDICATES ELECTRICAL CONNECTION BY ELECTRICAL CONTRACTOR TO EQUIPMENTPROVIDED AND INSTALLED BY OTHERS.
SAFETY DISCONNECT SWITCH; SEE DISCONNECT SCHEDULE FOR RATINGS
SURFACE MOUNTED DISTRIBUTION PANEL; SEE RESPECTIVE PANEL SCHEDULE
FLUSH MOUNTED DISTRIBUTION PANEL; SEE RESPECTIVE PANEL SCHEDULE
(2) RECEPTACLES; NEMA 5-20R DUPLEX; MOUNT IN 2-GANG BOX; 18" O.C. A.F.F. OR AS NOTED
SPECIAL POWER OUTLET; NEMA DESIGNATION AS SHOWN ON PLANS; MOUNT IN 2-GANG BOX;18" O.C. A.F.F. OR AS NOTED
VOICE/DATA OUTLET; 18" O.C. A.F.F. OR AS NOTED; 1-GANG BOX WITH 3/4" EMT TO ACCESSIBLEAREA ABOVE GRID CEILING
EXISTING VOICE/DATA OUTLET TO BE REMOVED
CRCARD READER; 48" O.C. A.F.F.; 2-GANG BOX WITH 1" EMT TO ACCESSIBLE AREA ABOVE GRIDCEILING
TV
TTHERMOSTAT; EC TO PROVIDE SINGLE GANG BOX WITH 1/2" EMT TO ACCESSIBLE AREA ABOVEGRID CEILING
EXISTING TO BE REPLACED
EXISTING TO BE REMOVED
E
R
EXISTING RELOCATED AS SHOWNRL
RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED 18" O.C. A.F.F. OR AS NOTED; GFCI; NON FEEDTHRU; WEATHERPROOF COVER.
W
RECEPTACLE; NEMA 5-20R DUPLEX; CONCEALED BEHIND WATER COOLER ENCLOSURE;COORDINATE LOCATION WITH WC SHOP DRAWINGS.
WC
F FLOOR BOX WITH (2) DUPLEX RECEPTACLES AND (4) RJ45 DATA JACKS
TV RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED 60" O.C. A.F.F.; FOR FLAT SCREEN TV
TELEVISION OUTLET; MOUNTED 60" O.C. A.F.F. OR AS NOTED; 1-GANG BOX WITH 3/4" EMT TOACCESSIBLE AREA ABOVE CEILING
FIRE ALARM CONTROL PANEL
FIRE ALARM MANUAL PULL STATION; MOUNTED 48" O.C. A.F.F.
FIRE ALARM STROBE; MOUNTED 80" O.C. A.F.F.
FIRE ALARM HORN & STROBE; MOUNTED 80" O.C. A.F.F.
SMOKE DETECTOR; CEILING MOUNTED
FIRE ALARM HORN & STROBE; WEATHERPROOF; MOUNTED 80" O.C. A.F.F.
SPRINKLER FLOW SWITCH; EXISTING SWITCH WIRED TO FIRE ALARM SYSTEM BY EC
SPRINKLER TAMPER SWITCH; EXISTING SWITCH WIRED TO FIRE ALARM SYSTEM BY EC
W
DUCT MOUNTED SMOKE DETECTOR; FURNISHED BY EC AND INSTALLED BY MC.
FIRE ALARM ANNUNCIATOR PANEL.
HEAT DETECTOR; CEILING MOUNTED
SMOKE DETECTOR; CEILING MOUNTED; FOR ELEVATOR RECALLEL
D
FACP
FAAP
F
S
FS
TS
S
S
S
S
S
H
LIGHT SWITCH; 20A, 120/277V, MOUNTED IN EXISTING RECESSED BOX; PROVIDE NEW WALL PLATE
RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED IN EXISTING RECESSED BOX; PROVIDE NEWWALL PLATE
VOICE/DATA OUTLET; MOUNTED IN EXISTING RECESSED BOX
FIRE ALARM MANUAL PULL STATION; MOUNTED IN EXISTING RECESSED BOXF E
FIRE ALARM HORN & STROBE; MOUNTED IN EXISTING RECESSED BOXS E
ENCLOSED CIRCUIT BREAKER; 240V, 90A, 3-POLE, SHUNT TRIP, NEMA 1 ENCLOSURE;PROVIDE AUXILIARY CONTACTS REQUIRED FOR ELEVATOR CONTROL
CB
ABBREVIATIONS
ABOVE GRID CEILINGAGC
COOLING TOWERCT
EXHAUST FANEF
FAN COIL UNITFC
ELECTRIC HEATEREH
AIR CONDITIONING CONDENSING UNITCU
ON CENTEROC
ROOF TOP UNITRTU
NOTE: ALL ABBREVIATIONS MAY NOT BE REPRESENTEDON PLANS.
WATER SOURCE HEAT PUMPWSHP
MOTORIZED DAMPERMD
WATER HEATERWH
ABOVE FINISHED FLOORAFF
SANITARY PUMPSP
SPLIT SYSTEM INDOOR UNITSSI
SPLIT SYSTEM OUTDOOR UNITSSO
NF224030B
NEMA 1NF224030A
DISCONNECT SCHEDULE
MARK AMP RATING VOLTS POLES FUSE ENCLOSURE
NEMA 3R
NF224060D
NEMA 3RNF330C
NEMA 3R
NF3F
NEMA 1NF3E
NEMA 3R
60
60
240
240
240
NF3G 100 240 NEMA 1
NF2240200H NEMA 3R
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
1/8" = 1'-0"
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\Ele
ctr
ical -
Deta
ils -
2014.r
vt
E-100
Electrical Legends& Notes
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
LIGHTING FIXTURE SCHEDULE NOTES1. EQUAL LIGHT FIXTURES MANUFACTURED BY ACUITY BRANDS,
COOPER LIGHTING, DAYBRITE, AND HUBBELL LIGHTING SHALLBE ACCEPTABLE. OTHER MANUFACTURERS MUST FOLLOWTHE GUIDELINES IN ACCORDANCE WITH THE PRODUCTSUBSTITUTION SECTION OF THE SPECIFICATIONS FORAPPROVAL BEFORE BID DATE. ENGINEER SHALL HAVE FINALAPPROVAL OF ALL LIGHT FIXTURE SUBSTITUTIONS.
2. MOUNTING HEIGHT SHALL BE MEASURED FROM THEFINISHED FLOOR LEVEL TO THE BOTTOM OF THE FIXTURE.
3. PROVIDE BATTERY TO SUPPLY EMERGENCY LIGHTING FOR 90MINUTES AS REQUIRED BY NFPA 101 - LIFE SAFETY CODE.
4. PROVIDE INTEGRAL BUTTON-TYPE PHOTOELECTRICCONTROLLER.
5. LED DRIVER CAPABLE OF DIMMING USING 0-10V DIMMERSWITCH.
GENERAL ELECTRICAL NOTES25. LAMPS AND LIGHTING FIXTURES SHALL BE AS DESCRIBED IN
LIGHT FIXTURE SCHEDULE ON THE DRAWINGS. PROVIDELAMPS IN ALL LIGHT FIXTURES.
26. ALL LINEAR FLUORESCENT LAMPS SHALL BE T-8,LOW-MERCURY BASED ON TCLP TESTING, A COLORTEMPERATURE OF 3500°K, AND A COLOR RENDERING INDEX(CRI) OF 82, AS MANUFACTURED BY PHILIPS, GE, OR OSCRAMSYLVANIA.
27. ALL LINEAR FLUORESCENT LIGHT FIXTURES SHALL HAVEELECTRONIC BALLASTS AS MANUFACTURED BY ADVANCE,UNIVERSAL, OR OSCRAM SYLVANIA. COMPACTFLUORESCENT BALLASTS SHALL BE ELECTRONIC ASMANUFACTURED BY ADVANCE, MAGNETEK, OR OSCRAMSYLVANIA.
28. LABEL EACH PANELBOARD, DISCONNECT SWITCH AND ENDSOF WIRING AND CABLES AS SPECIFIED.
29. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS.
30. GIVE RIGHT-OF-WAY TO SYSTEMS REQUIRED TO BEINSTALLED AT A REQUIRED SLOPE.
31. FURNISH AND INSTALL ANY MISCELLANEOUS METAL ORWOOD SUPPORTS, FASTENERS, MOUNTS HANGERS, SIDEBRACES, ETC., WHICH MAY BE REQUIRED TO SECURELYANCHOR AND SUPPORT ELECTRICAL EQUIPMENT FURNISHEDUNDER THIS CONTRACT.
32. APPLY FIRESTOPPING TO RACEWAY PENETRATIONS OFFIRE-RATED FLOOR AND WALL ASSEMBLIES TO ACHIEVEFIRE-RESISTANCE RATING OF THE ASSEMBLY.
33. MAKE PROVISION AND PROVIDE POWER WIRING INCLUDINGFINAL EQUIPMENT CONNECTION TO ALL EQUIPMENTFURNISHED AND INSTALLED BY OTHERS. VERIFY THE EXACTREQUIREMENT OF EQUIPMENT BEFORE INSTALLATION OFELECTRICAL WORK.
34. ALL REQUIRED BUILDING PERMITS FOR THE ELECTRICALPORTION OF THE WORK SHALL BE INCLUDED. A FINALINSPECTION BY THE OWNER, ARCHITECT, ENGINEER, AND ALLINVOLVED AGENCIES WILL BE CONDUCTED UPONCOMPLETION OF THE WORK TO DETERMINE ACCEPTABILITYOF THE WORK. IN ADDITION, AN INSPECTION BY THEELECTRICAL INSPECTOR AND CERTIFICATE OF APPROVALWILL BE REQUIRED PRIOR TO FINAL PAYMENT FOR THEWORK. ALL FEES FOR BUILDING PERMITS AND ELECTRICALINSPECTIONS SHALL BE INCLUDED.
35. TESTING: ON COMPLETION OF THE WORK, THE INSTALLATIONSHALL BE FREE FROM GROUNDS AND SHORT CIRCUITS. ALLCIRCUITS SHALL BE TESTED AND LABELED. ALL MOTORCIRCUITS, CONTROL CIRCUITS, SIGNAL SYSTEMS,INTERLOCKING AND ELECTRIC HEAT CIRCUITS SHALL BETESTED FOR PROPER OPERATION.
36. GUARANTEE: THE CONTRACTOR SHALL GIVE THE OWNER AWRITTEN GUARANTEE THAT HE WILL MAKE GOOD, AT HISOWN EXPENSE, ANY DEFECTS IN MATERIALS ORWORKMANSHIP WHICH MAY DEVELOP IN ONE YEAR FROMTHE FINAL ACCEPTANCE OF THE WORK.
GENERAL ELECTRICAL NOTES17. BEFORE INSTALLING OUTLETS, THE ELECTRICAL
CONTRACTOR SHALL CONFER WITH THE ARCHITECT TODETERMINE IF THE OUTLETS ARE TO BE INSTALLED ATHEIGHTS OTHER THAN THOSE GIVEN HEREIN. IN GENERAL,UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL THEOUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTFROM THE FLOOR: A.SWITCHES: 48" O.C. B. RECEPTACLE
OUTLETS: 18" O.C. C.VOICE/DATA OUTLETS: 18" O.C. D. WALLMOUNTED TELEPHONE OUTLETS: 54" O.C. RECEPTACLEOUTLETS AT COUNTERTOPS: 6" O.C. ABOVE BACKSPLASH.
18. A TYPEWRITTEN LABEL SHALL BE INSTALLED ON THE WALLPLATE OF EACH RECEPTACLE OUTLET INDICATING THECONNECTED PANEL AND CIRCUIT NUMBER.
19. ALL GROUNDING SHALL BE IN ACCORDANCE WITH THEREQUIREMENTS OF THE NEC AND AS REQUIRED BY THEDRAWINGS.
20. PANELBOARDS SHALL BE DEAD FRONT WITH RATINGS ASSCHEDULED ON DRAWINGS. PROVIDE CIRCUIT BREAKERS ASRECOMMENDED BY PANEL MANUFACTURER. PROVIDEBRANCH BREAKERS IN QUANTITIES AND RATINGS ASINDICATED ON DRAWINGS. PROVIDE TYPED DIRECTORIESREFLECTING CONNECTED LOADS.
21. BRANCH CIRCUIT BREAKERS SHALL BE OF INDIVIDUAL UNITCONSTRUCTION COMPLETE WITH QUICK-MAKE, QUICK-BREAKMECHANISM; THERMAL MAGNETIC TRIP; AMBIENTCOMPENSATION; AND SHALL BE INTERCHANGEABLE IN THEPANELBOARD ASSEMBLY IN RATINGS FROM 15 TO 100AMPERES WITHOUT NECESSITATING BUS, LINK OR ASSEMBLYREARRANGEMENT. CIRCUIT BREAKERS SHALL HAVESUITABLE SCREW TYPE LINE TERMINALS SO THAT THEY WILLBE HELD IN POSITIVE CONTACT WITH THEIR RESPECTIVELINKS OR BUSSES.
22. SAFETY SWITCHES SHALL BE HEAVY DUTY, QUICK-MAKE,QUICK-BREAK, TYPES OF THE SIZE AND FUSE AMPACITY ASNOTED ON THE DRAWINGS. PROVIDE GROUND BUS, SOLIDNEUTRAL, CLASS RK-5 DUAL ELEMENT, TIME DELAY FUSES,AND NEMA RELATED ENCLOSURE.
23. MOTOR STARTERS FOR THREE PHASE MOTORS SHALL BEFULL VOLTAGE NON-REVERSING MAGNETIC TYPES WITHPROPERLY SIZED OVERLOAD HEATERS, LONG LIFE PILOTLIGHTS, HAND-OFF-AUTO SELECTOR SWITCH, PUSHBUTTONS,AND 120V CONTROL TRANSFORMER. MANUAL MOTORSTARTERS FOR SINGLE PHASE MOTORS SHALL BE SENTINELTYPE WITH PROPERLY SIZED OVERLOAD HEATERS ANDTOGGLE TYPE DISCONNECT SWITCH MOUNTED IN A NEMARATED ENCLOSURE.
24. EACH PANELBOARD, DISCONNECT SWITCH, MOTOR STARTERAND CABINET SHALL BE IDENTIFIED BY PHENOLIC LAMINATEDPLASTIC ENGRAVED PLATES ATTACHED WITH POP RIVETS ORSHEET METAL SCREWS.
GENERAL ELECTRICAL NOTES10. ALL CONDUIT AND EQUIPMENT SHALL BE LEVEL, PLUMB, AND
PARALLEL AND PERPENDICULAR TO OTHER BUILDINGSYSTEMS AND COMPONENTS, UNLESS OTHERWISE NOTED.
11. CONDUIT AND CABLES SHALL BE INSTALLED AT LEAST 6"AWAY FROM PARALLEL RUNS OF FLUES AND HOT-WATERPIPES. LOCATE HORIZONTAL CONDUIT AND CABLE RUNSABOVE WATER PIPING.
12. PROVIDE PULL WIRES IN ALL EMPTY CONDUITS. USE NO. 14AWG ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINEWITH NOT LESS THAN 200-LB TENSILE STRENGTH. LEAVE ATLEAST 12" OF SLACK AT EACH END OF THE PULL WIRE.
13. OUTLET AND JUNCTION BOXES SHALL BE 4" SQUAREMINIMUM SIZE, GALVANIZED, STAMPED STEEL, EXCEPT ASNOTED. OUTLET BOXES SHALL BE EQUIPPED WITH PLASTERRINGS OF APPROPRIATE DEPTH TO FINISH FLUSH WITHFINISHED WALL. MULTIGANG BOXES SHALL BE OF SINGLEPIECE CONSTRUCTION WITH WALL PLATES MATCHINGRESPECTIVE DEVICE. OUTLET BOXES IN CONCRETE ORMASONRY WALLS SHALL BE MASONRY TYPE. OUTLET BOXESFOR EXPOSED EXTERIOR WALLS SHALL BE WEATHERPROOFWITH THREADED CONDUIT HUBS. JUNCTION AND PULLBOXES SHALL HAVE STEEL, SCREW-TYPE COVER PLATES.
14. WIRES AND CABLES SHALL BE COPPER CONDUCTORS ANDHAVE APPROVED INSULATION FOR THE SPACES WHERE THEYARE TO BE USED AND SHALL CONFORM TO THE LATESTREQUIREMENTS OF THE NEC. THE MINIMUM TEMPERATURERATING SHALL BE 75°C WITH TYPE THHN/THWN INSULATIONAND 600 VOLT RATING.
15. NO WIRE SMALLER THAN #12 SHALL BE USED FOR LIGHTING,RECEPTACLES, AND MOTOR CIRCUITS. ALL WIRE #10 ANDSMALLER MAY BE SOLID OR STRANDED CONDUCTOR. FORSIZE #8 AND LARGER STRANDED CABLE SHALL BE USED. ALLWIRES SHALL BE INSTALLED IN CONDUIT UNLESS OTHERWISENOTED. ALL SPLICES SHALL BE MADE WITH INSULATEDSOLDERLESS TYPE CONNECTORS. WIRING INSTALLATIONSHALL COMPLY WITH NEC 310.15(B)(3)(a). ALL FEEDER ANDBRANCH CIRCUIT CONDUCTOR AMPACITIES SHALL BEPROPERLY INCREASED FOR VOLTAGE DROP IN ACCORDANCEWITH THE NEC.
16. WIRING DEVICES SHALL BE THREE-WIRE, SPECIFICATIONGRADE, 20 AMPERE MINIMUM; DUAL VOLTAGE SWITCHES,DUPLEX RECEPTACLES, AND GROUND-FAULT CIRCUITINTERRUPTING RECEPTACLES. PROVIDE IVORY NYLON WALLPLATES FOR FINISHED AREAS. PROVIDE GASKETEDWEATHERPROOF WALL PLATES FOR EXTERIOR AREAS. WALLPLATES SHALL BE INSTALLED ON ALL SWITCHES,RECEPTACLES, VOICE/DATA OUTLETS, TV OUTLETS, ANDEMPTY BOXES. DUPLEX RECEPTACLES SHALL BE HUBBELL#5362; SINGLE POLE SWITCHES SHALL BE HUBBELL #1221;THREE-WAY SWITCHES SHALL BE HUBBELL #1223; FOUR-WAYSWITCHES SHALL BE HUBBELL #1224 OR ENGINEERAPPROVED EQUAL.
GENERAL ELECTRICAL NOTES1. SCOPE: FURNISH ALL LABOR AND MATERIALS AND INSTALL
ALL EQUIPMENT; INCLUDING, BUT NOT LIMITED TO WIRING,CONDUIT, ELECTRICAL DISTRIBUTION EQUIPMENT, LIGHTING,AND MISCELLANEOUS EQUIPMENT DETAILED ON THEDRAWINGS OR REQUIRED FOR A COMPLETE AND OPERABLEINSTALLATION.
2. ALL ELECTRICAL WORK SHALL BE COMPLIANT WITH THESTATE ADOPTED EDITION OF NFPA 70: NATIONAL ELECTRICALCODE (NEC) AND OTHER APPLICABLE STATE AND LOCALCODES.
3. COORDINATE ELECTRICAL SERVICE ENTRANCE WORK WITHMON POWER COMPANY. ELECTRICAL SERVICE WORK SHALLCOMPLY WITH MON POWER SPECIFICATIONS.
4. ALL MATERIAL SHALL BE NEW AND SHALL BE LISTED BYUNDERWRITERS LABORATORIES.
5. CONDUITS SHALL BE 1/2" MINIMUM SIZE, RIGID GALVANIZEDSTEEL, INTERMEDIATE METAL CONDUIT, LIQUID-TIGHTFLEXIBLE CONDUIT, ELECTRICAL METALLIC TUBING, FLEXIBLEMETAL CONDUIT. CONDUITS SHALL BE SIZED AND APPLIED INACCORDANCE WITH THE NEC. CONDUIT FITTINGS SHALL BEALL PLATED STEEL: SET-SCREW, THREADED ORCOMPRESSION TYPE. METAL CLAD CABLE SHALL BEPERMITTED FOR INSTALLATION.
6. ALL WIRING SHALL BE INSTALLED IN CONDUIT. BRANCHCIRCUIT WIRING SHALL BE MC CABLE AS PERMITTED BY THENEC. IN GENERAL, CONCEAL CONDUIT IN WALLS AND ABOVECEILNGS. MC CABLE SHALL BE USED WHERE OUTLETS AREINSTALLED THROUGH CONTINUOUS METAL STUD WALLS. INUNFINISHED AREAS OF THE BUILDING, CONDUIT SHALL BEEXPOSED AND ROUTED ON SURFACE OF THE CEILINGAND/OR WALLS AS HIGH AS POSSIBLE AND ROUTED SO AS TONOT INTERFERE WITH OTHER TRADES. CONDUIT ANDCABLES SHALL BE SECURED WITH APPROVED SUPPORTINGDEVICES AND RUN PARALLEL AND PERPENDICULAR TOSURROUNDING STRUCTURE.
7. CONDUITS INSTALLED UNDERGROUND SHALL BE A MINIMUMOF 18" BELOW FINISHED GRADE TO THE TOP OF THECONDUIT, UNLESS OTHERWISE NOTED. PROVIDE ROCK-FREEBACKFILL MATERIAL AND TAMP IN 8" LAYERS. PROVIDEUNDERGROUND WARNING TAPE IN TRENCH 3" BELOWFINISHED GRADE.
8. RGS CONDUIT SHALL BE USED IN ALL AREAS SUBJECTED TOPHYSICAL DAMAGE. EMT MAY BE INSTALLED ONLY INCONCEALED INTERIOR SPACES ABOVE CEILINGS OR INWALLS. OUTDOOR WIRING ABOVE GRADE SHALL BEENCLOSED IN RGS CONDUIT. OUTDOOR WIRING BELOWGRADE SHALL BE ENCLOSED IN SCHEDULE 40 PVC CONDUITUNLESS OTHERWISE NOTED.
9. CONNECT MOTORS AND EQUIPMENT SUBJECT TO VIBRATION,NOISE TRANSMISSION OR MOVEMENT WITH A MAXIMUM OF72" FLEXIBLE CONDUIT. PROVIDE LIQUID-TIGHT FLEXIBLECONDUIT IN WET OR DAMP LOCATIONS. INSTALL SEPARATEGROUND CONDUCTOR ACROSS FLEXIBLE CONNECTIONS.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
UP
OS
OS
3 4
3
3
OS OS OS
OS OS
RE
F.
3
D DD
OS OSOS
33
D
InformationPamphlets
Copy/Print
AE
A
A
A
A
A
EEEE
A
FE
W
EE
XR
B B B
BBB
B
B
B
B
C
C
XAE
DE
DE
DD
D D
GG
X
DE
DE
D
D
D
D
D DD
D
R
Stairs
S2.0
Men'sRestroom
007
Women'sRestroom
009
Office
002
Office
001
MechanicalRoom
005
Corridor
000
Office
003
Storage
004
KK
K
V V
2
1
1 1
1
1 1 1
1
1
1 1
1
3 3
1
A AE
A
A
A
A AA
A A AAE
E EE
A
B
B B B
BB
AE
X XR
R
FE
EE
X
W
X
D D D
D
D D D
D
Stairs
S1.0
Kitchenette
012
Boardroom
010
2
1
1
111
1 1
E-200
1
E-200
2
KEY NOTES LIGHTING PLAN
1 CONNECT TO EXISTING BRANCH LIGHTING CIRCUIT INROOM/AREA USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT OFREMOVED LIGHT FIXTURE.
CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT USING (2) #12 CONDUCTORS AND (1) #12 EQUIPMENT GROUNDINGCONDUCTOR IN 1/2" CONDUIT.
2
3
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
E-200
Ground FloorLighting Plan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/4" = 1'-0"1
ENLARGED GROUND FLOOR LIGHTING PLAN - NORTH
1/4" = 1'-0"2
ENLARGED GROUND FLOOR LIGHTING PLAN - SOUTH 1/16" = 1'-0"3
GROUND FLOOR LIGHTING PLAN
GENERAL LIGHTING NOTES1. FIXTURES: SET LEVEL, PLUMB, AND SQUARE WITH CEILING
AND WALLS. SECURE ACCORDING TO MANUFACTURER'SWRITTEN INSTRUCTIONS AND APPROVED SUBMITTALMATERIALS. INSTALL LAMPS IN EACH FIXTURE.
2. CONNECT EXIT LIGHTS AND EMERGENCY BATTERY BALLASTSIN NOTED FIXTURES TO THE NEAREST UNSWITCHEDLIGHTING CIRCUIT IN THE AREA BEING SERVED.
3. EXTERIOR LIGHTING FIXTURES SHALL BE OPERATED BY ANEXISTING TIME CLOCK AND A PHOTOELECTRIC CONTROLLER.
4. PROVIDE LOW VOLTAGE WIRING FROM THE EXIT LIGHTS WITHEXTRA BATTERY CAPACITY TO THE REMOTE EMERGENCYLIGHTS INDICATED. LOW VOLTAGE WIRING SHALL BE ASRECOMMENDED BY THE EMERGENCY LIGHTING UNITMANUFACTURER.
5. SEE GENERAL ELECTRICAL NOTES ON SHEET E100 FORWIRING METHODS.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
DN
3
4
DD
OS OSOS
J
J
OS
OS
3
J
J
OS
OS
OS OS
OS
E
E
FE
EE
X
DE D D
B
B B
B B
B BEB
B B
C
BB
A
A
DE DE DED DD
K
G G
DDDE
DDD
D D D
H
H
H
H
H
H
H
H
H
H
X
1
1 1 1
1
1
1
1
11
1
1
1
111
1
SharedSuite
104
SharedSuite
105
SharedSuite
106
Stairs
S2.1
Corridor
119
Kitchenette
108
Storage
110
Server
110A
Storage
111
Elevator
E1.1
Women'sRestroom
109
Men'sRestroom
107
MeetingRoom
112
PhoneRoom
102
MeetingRoom
103
Co-WorkingOpenOffice
101
A
A
H
H
H
H
H
H
H
H
H
H
B
B B
B B
B
DEX
DEDEX
D D D D
FE
EE
1
111
1
1
1 1 1
PhoneRoom
114
MeetingRoom
115
DedicatedOpenOffice
113
Corridor
119
PrivateOffice
116
PrivateOffice
117
PrivateOffice
118
Stairs
S1.1
E-201
1
E-201
2
KEY NOTES LIGHTING PLAN
1 CONNECT TO EXISTING BRANCH LIGHTING CIRCUIT INROOM/AREA USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT OFREMOVED LIGHT FIXTURE.
CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT USING (2) #12 CONDUCTORS AND (1) #12 EQUIPMENT GROUNDINGCONDUCTOR IN 1/2" CONDUIT.
2
3
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
E-201
First Floor LightingPlan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/4" = 1'-0"1
ENLARGED FIRST FLOOR LIGHTING PLAN - NORTH
1/4" = 1'-0"2
ENLARGED FIRST FLOOR LIGHTING PLAN - SOUTH 1/16" = 1'-0"
3FIRST FLOOR POWER PLAN
GENERAL LIGHTING NOTES1. FIXTURES: SET LEVEL, PLUMB, AND SQUARE WITH CEILING
AND WALLS. SECURE ACCORDING TO MANUFACTURER'SWRITTEN INSTRUCTIONS AND APPROVED SUBMITTALMATERIALS. INSTALL LAMPS IN EACH FIXTURE.
2. CONNECT EXIT LIGHTS AND EMERGENCY BATTERY BALLASTSIN NOTED FIXTURES TO THE NEAREST UNSWITCHEDLIGHTING CIRCUIT IN THE AREA BEING SERVED.
3. EXTERIOR LIGHTING FIXTURES SHALL BE OPERATED BY ANEXISTING TIME CLOCK AND A PHOTOELECTRIC CONTROLLER.
4. PROVIDE LOW VOLTAGE WIRING FROM THE EXIT LIGHTS WITHEXTRA BATTERY CAPACITY TO THE REMOTE EMERGENCYLIGHTS INDICATED. LOW VOLTAGE WIRING SHALL BE ASRECOMMENDED BY THE EMERGENCY LIGHTING UNITMANUFACTURER.
5. SEE GENERAL ELECTRICAL NOTES ON SHEET E100 FORWIRING METHODS.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
OS OS
3
3
4
D
DDJ J J
OS OS OS
OS OS OS
3
JJJ
OS OS OS
OS OS OS
BeverageCenter
WW
E
FE
EE
XDE D DED D D D DEDE
H
H H H
H
H
HH
H
H
H
H
B
B
B
B
B
B
X
G G
D D DE
D
D
D
D
D
D
BB
DE
DE
D
DDD
D
D
K
Stairs
S2.2
Storage
210
Women'sRestroom
209
Men'sRestroom
207
MeetingRoom
211
PrivateOffice
201
PrivateOffice
205
PrivateOffice
203
PrivateOffice
202
PrivateOffice
204
PrivateOffice
206
Elevator
E1.2
Lounge
208
Corridor
200
1
1 1 1
1
1 1 1
1 1
1
1
1
2 2
Stairs
S1.2Chamberof
CommercePrivateOffice
213
Chamberof
CommercePrivateOffice
217
Chamberof
CommercePrivateOffice
215
Chamberof
CommercePrivateOffice
212
Chamberof
CommercePrivateOffice
214
Chamberof
CommercePrivateOffice
216
B
B
B
B
B
B
DEDE DDD D
H
H
H
H
H
H
H
H
H
H
H
H
FE
EE
X
1 1 1
1 1 1
1
E-202
1
E-202
2
KEY NOTES LIGHTING PLAN
1 CONNECT TO EXISTING BRANCH LIGHTING CIRCUIT INROOM/AREA USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT OFREMOVED LIGHT FIXTURE.
CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT USING (2) #12 CONDUCTORS AND (1) #12 EQUIPMENT GROUNDINGCONDUCTOR IN 1/2" CONDUIT.
2
3
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
E-202
Second FloorLighting Plan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/4" = 1'-0"1
ENLARGED SECOND FLOOR LIGHTING PLAN - NORTH
1/4" = 1'-0"2
ENLARGED SECOND FLOOR LIGHTING PLAN - SOUTH 1/16" = 1'-0"3
SECOND FLOOR LIGHTING PLAN
GENERAL LIGHTING NOTES1. FIXTURES: SET LEVEL, PLUMB, AND SQUARE WITH CEILING
AND WALLS. SECURE ACCORDING TO MANUFACTURER'SWRITTEN INSTRUCTIONS AND APPROVED SUBMITTALMATERIALS. INSTALL LAMPS IN EACH FIXTURE.
2. CONNECT EXIT LIGHTS AND EMERGENCY BATTERY BALLASTSIN NOTED FIXTURES TO THE NEAREST UNSWITCHEDLIGHTING CIRCUIT IN THE AREA BEING SERVED.
3. EXTERIOR LIGHTING FIXTURES SHALL BE OPERATED BY ANEXISTING TIME CLOCK AND A PHOTOELECTRIC CONTROLLER.
4. PROVIDE LOW VOLTAGE WIRING FROM THE EXIT LIGHTS WITHEXTRA BATTERY CAPACITY TO THE REMOTE EMERGENCYLIGHTS INDICATED. LOW VOLTAGE WIRING SHALL BE ASRECOMMENDED BY THE EMERGENCY LIGHTING UNITMANUFACTURER.
5. SEE GENERAL ELECTRICAL NOTES ON SHEET E100 FORWIRING METHODS.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
UP
W
F
S
GC GC GC
W
GC
F S
J J
TV
JJ
S
H
S H
S
MS
GC
GC
W
FS
J J
TV TV
W
J J
FF
GC
InformationPamphlets
Copy/Print
E
E E E E E E
E
E
E
E
E E E
E
E E
E
CT
E
AGC AGC
Stairs
S2.0
Men'sRestroom
007
Women'sRestroom
009
Office
002
Office
001
MechanicalRoom
005
Corridor
000
Office
003
Storage
004
E E
C C C
AGCAGC
FA
CP
WC
E
ELEV
CB
A ABE A
FIRE ALARMDISCONNECT
2
2 2
DATA DATA
2 2
1
1 AA
AA2
WH
B1P1 P2
B2
4
44
1
1
1
2
2
1
1
E E E EE E E
EE
E
E E EEE EE E
E
E E E E E EEE E
60"AFF
60"AFF
60"
F F
Stairs
S1.0
Kitchenette
012
Boardroom
010
AGC AGC
AGC AGC
E E
TV
1" COMM
3/4" POWER
TV
1" COMM
3/4" POWER
DATADATA
33
1
3
3
3
3
3
3
WH1
E-300
1
E-300
2
KEY NOTES POWER PLAN
1 CONNECT TO EXISTING BRANCH CIRCUIT TO DEVICES SHOWNUSING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER INPANEL AA USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER INPANEL AB USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING BRANCH CIRCUIT WIRING FROMREMOVED EQUIPMENT.
2
3
4
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
E-300
Ground Floor PowerPlan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/4" = 1'-0"1
ENLARGED GROUND FLOOR POWER PLAN - NORTH
1/4" = 1'-0"2
ENLARGED GROUND FLOOR POWER PLAN - SOUTH 1/16" = 1'-0"3
GROUND FLOOR ELECTRICAL PLAN
GENERAL POWER NOTES1. EXISTING RECEPTACLES INDICATED TO BE REPLACED SHALL
BE CONNECTED TO THE EXISTING BRANCH CIRCUIT WIRINGIN DEVICE BOX. PROVIDE A NEW MATCHING WALL PLATE.
2. EXTEND EXISTING BRANCH WIRING TO RELOCATED WATERSOURCE HEAT PUMPS.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
DN
GC
GC
GC
G
F
S
S
J J
J
J
TV
S
J J
J
J
FS
S
J J
J
J
J
J
J J
E
E EE E E E EE E E E EE E E EEEEEEEEE
E
E
E
E
E E E E E E E E E E E E E E E EEEEEEEEE
E
E
E E E E EEEE EE
E
E
E
E
E
E E E E EEEE
E
AGC AGC
AGC
AGC
F F F F
F
WC
E
E
E
TV
1" COMM
3/4" POWER
AGC AGC
E E
AGC
AGC
B
B1
E E
HE
DATA DATA
2
22 DATA
DATA
2
1
1
2
60"
2
2
2
2
Cop
y/P
rint
E E E E E EE E E
EE
EEEEEE EEEEEE EEE
E
EEEE EEEEEE E E EEEEEEE E E E E
E
AGC AGC
AGC
AGC
F F F FStairs
S1.1
PrivateOffice
116
PrivateOffice
118
PrivateOffice
117
PhoneRoom
114
DedicatedOpenOffice
113
MeetingRoom
115
EEEE EEEE EEEE
AGC
AGC
AGC
DATA DATA
AGC
3
3 3DATA
DATA
3
1
E-301
1
E-301
2
KEY NOTES POWER PLAN
1 CONNECT TO EXISTING BRANCH CIRCUIT TO DEVICES SHOWNUSING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER IN PANELB1 USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER IN PANELB USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING BRANCH CIRCUIT WIRING FROMREMOVED EQUIPMENT.
2
3
4
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
E-301
First Floor PowerPlan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/4" = 1'-0"1
ENLARGED FIRST FLOOR POWER PLAN - NORTH
1/4" = 1'-0"2
ENLARGED FIRST FLOOR POWER PLAN - SOUTH
1/16" = 1'-0"3
FIRST FLOOR ELECTRICAL PLAN
GENERAL POWER NOTES1. EXISTING RECEPTACLES INDICATED TO BE REPLACED SHALL
BE CONNECTED TO THE EXISTING BRANCH CIRCUIT WIRINGIN DEVICE BOX. PROVIDE A NEW MATCHING WALL PLATE.
2. EXTEND EXISTING BRANCH WIRING TO RELOCATED WATERSOURCE HEAT PUMPS.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
GC
GC GC
F
S
GC
S
S
F
TV
J
J
J
J
J
J
J
J
J J J
FS
J J J
J
J J
J
BeverageCenter
E E E E E E E E E E E E E E E E E EE
E
E E E E EEEE EEEE EEEEEE EEE
E
E E E E E EE E
WC
60"
FTV
Stairs
S2.2
Storage
210
Women'sRestroom
209
Men'sRestroom
207
MeetingRoom
211
PrivateOffice
201
PrivateOffice
205
PrivateOffice
203
PrivateOffice
202
PrivateOffice
204
PrivateOffice
206
Elevator
E1.2
Lounge
208
Corridor
200
E E E FAAP
E
AGC
AGC
AGC
AGC
AGC
AGC
AGC
AGC
AGC AGC AGC
E E
E
1" COMM
3/4" POWER
E
E
E
E E
E
DATA DATA
2 2 2
2
1
2
DATA DATA
2
C
C2
C1
GEN PANEL& ATS
2 1
2
2
2
EEE E E E E E E E E E EEE E EE E E E EEE E
E E E E E EEE
EEEEEEEEEEEE E E E
E
Stairs
S1.2
Chamber of Commerce PrivateOffice
213
Chamber of Commerce PrivateOffice
217
Chamber of Commerce PrivateOffice
215
Chamber of Commerce PrivateOffice
212
Chamber of Commerce PrivateOffice
214
Chamber of Commerce PrivateOffice
216
AGC AGC AGC
AGC
AGC AGC
AGC
E E
1
3
DATA DATA
1
33
3
WSHP
E-302
1
E-302
2
KEY NOTES POWER PLAN
1 CONNECT TO EXISTING BRANCH CIRCUIT TO DEVICES SHOWNUSING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER INPANEL C1 USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER INPANEL C2 USING #12/2 MC CABLE WITH GROUND.
CONNECT TO EXISTING BRANCH CIRCUIT WIRING FROMREMOVED EQUIPMENT.
2
3
4
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
E-302
Second Floor PowerPlan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/4" = 1'-0"1
ENLARGED SECOND FLOOR POWER PLAN - NORTH
1/4" = 1'-0"2
ENLARGED SECOND FLOOR POWER PLAN - SOUTH 1/16" = 1'-0"3
SECOND FLOOR ELECTRICAL PLAN
GENERAL POWER NOTES1. EXISTING RECEPTACLES INDICATED TO BE REPLACED SHALL
BE CONNECTED TO THE EXISTING BRANCH CIRCUIT WIRINGIN DEVICE BOX. PROVIDE A NEW MATCHING WALL PLATE.
2. EXTEND EXISTING BRANCH WIRING TO RELOCATED WATERSOURCE HEAT PUMPS.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
EF1
1
KEY NOTES POWER PLAN
1 CONNECT TO EXISTING BRANCH CIRCUIT WIRING FROMREMOVED EQUIPMENT.
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
1/8" = 1'-0"
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
E-303
Roof Power Plan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/8" = 1'-0"1
Roof Floor Power Plan
GENERAL POWER NOTES1. EXISTING RECEPTACLES INDICATED TO BE REPLACED SHALL
BE CONNECTED TO THE EXISTING BRANCH CIRCUIT WIRINGIN DEVICE BOX. PROVIDE A NEW MATCHING WALL PLATE.
2. EXTEND EXISTING BRANCH WIRING TO RELOCATED WATERSOURCE HEAT PUMPS.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
LOCATION: ELECTRICAL ROOM EXISTING PANEL: MS PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED
FROM:SERVICE
MODEL: CCB - STYLE 2
MTG: SURFACE VOLTS Ph W
240 / 120 3 4 22,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA
7205 1 ELEVATOR E - E E 100E * 100E E E E E COOLING TOWER & PUMPS 1 & 2 2 0
7205 3 - E - - - 3P * 3P E - - - - 4 0
7205 5 - E - - - - * - E - - - - 6 0
0 7 PANEL C E E E E 225E * 225E E E E E PANEL B 8 0
0 9 - E - - - 3P * 3P E - - - - 10 0
0 11 - E - - - - * - E - - - - 12 0
0 13 GENERATOR & PANEL C2 E E E E 225E * 225E E E E E PANEL A 14 0
0 15 - E - - - 3P * 3P E - - - - 16 0
0 17 - E - - - - * - E - - - - 18 0
7205 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0
7205 SUBTOTAL Ph B MAIN LUGS - 600 AMPS SUBTOTAL Ph B 0
7205 SUBTOTAL Ph C BUS AMPACITY = 600 AMPS SUBTOTAL Ph C 0
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 7,205
A/C 0 100 0 VA ph B 7,205
HEATING 0 100 0 VA ph C 7,205NON-VENT MOTORS 21615 100 21615 TOTAL 22 kVAVENTILATION 0 100 0 NOTES:KITCHEN, #EQ = 0 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
RECEPTACLES 0 100 0MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 21615 21615
AMPS 52 52
LOCATION: ELECTRICAL ROOM EXISTING PANEL: A PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED
FROM:PANELMS
MODEL: AQF3422MBX
MTG: SURFACE VOLTS Ph W
208 / 120 3 4 22,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA
0 1 HEAT PUMP 108 #12 - #12 1/2" 20E * 20E #12 - #12 1/2" HEAT PUMP 107 2 0
0 3 - #12 - - - 3P * 3P #12 - - - - 4 0
0 5 - #12 - - - - * - #12 - - - - 6 0
0 7 EXISTING LOAD E E E E 20E * 20E E E E E EXTERIOR LIGHTING 8 0
0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXTERIOR LIGHTING 10 0
0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0
0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0
0 15 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 16 0
0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0
0 19 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 20 0
0 21 HVAC CLOCK E E E E 20E * 20E E E E E EXISTING LOAD 22 0
0 23 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 24 0
0 25 ELEVATOR LIGHTS E E E E 20E * 20E E E E E EXISTING LOAD 26 0
0 27 HEAT PUMP #10 - #10 1/2" 30E * 20E #12 - #12 1/2" HEAT PUMP 28 0
0 29 - #10 - - - 2P * 2P #12 - - - - 30 0
0 31 HEAT PUMP #10 - #10 1/2" 30E * 20E #12 - #12 1/2" HEAT PUMP 32 0
0 33 - #10 - - - 2P * 2P #12 - - - - 34 0
0 35 HEAT PUMP #10 - #10 1/2" 30E * 20E E E E E SUMP PUMP 36 0
0 37 - #10 - - - 2P * 70E E E E E PANEL AA 38 0
0 39 PANEL AB E E E E 100E * 3P E - - - ROOM 108 40 0
0 41 - E - - - 2P * - E - - - - 42 0
0 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0
0 SUBTOTAL Ph B MAIN LUGS - 225 AMPS SUBTOTAL Ph B 0
0 SUBTOTAL Ph C BUS AMPACITY = 225 AMPS SUBTOTAL Ph C 0
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 0
A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:
RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 0 0
AMPS 0 0
LOCATION: ELECTRICAL ROOM EXISTINGPANEL: AB PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC SUPPLY: PANEL A
MODEL: TM2010CCU
MTG: SURFACE VOLTS Ph W
208 / 120 1 3 10,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B BKR Ph N G C LOAD # VA
0 1 EXISTING 208 REC E - E E 20E * 20E E - E E EXISTING 208 REC 2 0
0 3 - E - - - 2P * 2P E - - - - 4 0
0 5 EXISTING 208 REC E - E E 20E * 20E E - E E EXISTING 208 REC 6 0
0 7 - E - - - 2P * 2P E - - - - 8 0
0 9 EXISTING 208 REC E - E E 20E * 20E E - E E EXISTING 208 REC 10 0
0 11 - E - - - 2P * 2P E - - - - 12 0
0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0
0 15 SPARE E E E E 20E * 20E E E E E SPARE 16 0
0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0
0 19 EXISTING LOAD E E E E 20E * 30E E E E E EXISTING LOAD 20 0
0 SUBTOTAL Ph A MAIN BREAKER - 100 AMPS SUBTOTAL Ph A 0
0 SUBTOTAL Ph B MAIN LUGS - - AMPS SUBTOTAL Ph B 0BUS AMPACITY = 100 AMPS
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 0
A/C 0 100 0 VA ph B 0HEATING 0 100 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0 NOTESKITCHEN, #EQ = 0 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
RECEPTACLES 0 100 0MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 0 0
AMPS 0 0
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
12" = 1'-0"
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\Ele
ctr
ical -
Deta
ils -
2014.r
vt
E-600
Panel Schedules
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
LOCATION: ELECTRICAL ROOM EXISTING PANEL: B PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED
FROM:PANELMS
MODEL: AQF3422MBX
MTG: SURFACE VOLTS Ph W
208 / 120 3 4 10,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA
0 1 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 2 0
0 3 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 4 0
0 5 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 6 0
0 7 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 8 0
0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 10 0
0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0
0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0
0 15 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 16 0
0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0
0 19 EXISTING LOAD E E E E 20E * 30E #10 - #10 1/2" HEAT PUMP 20 0
0 21 EXISTING LOAD E E E E 20E * 3P #10 - - - - 22 0
0 23 EXISTING LOAD E E E E 20E * - #10 - - - - 24 0
0 25 HEAT PUMP #10 - #10 1/2" 30E * 100E PANEL B1 26 0
0 27 - #10 - - - 2P * 3P - - - - 28 0
0 29 REC E E E E 20E * - - - - - 30 0
0 31 HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" 115 HEAT PUMP 32 0
0 33 - #10 - - - 3P * 3P #10 - - - - 34 0
0 35 - #10 - - - - * - #10 - - - - 36 0
0 37 CONF. ROOM HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" RESOURCE ROOM HEAT PUMP 38 0
0 39 - #10 - - - 2P * 2P #10 - - - - 40 0
0 41 TIME CLOCK E E E E 20E * 20E E E E E EXISTING LOAD 42 0
0 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0
0 SUBTOTAL Ph B MAIN LUGS - 225 AMPS SUBTOTAL Ph B 0
0 SUBTOTAL Ph C BUS AMPACITY = 225 AMPS SUBTOTAL Ph C 0
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 0
A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:
RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 0 0
AMPS 0 0
E
E
E
E E E
LOCATION: ELECTRICAL ROOM EXISTING PANEL: B1 PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED
FROM:PANEL B
MODEL: TL42422C
MTG: SURFACE VOLTS Ph W
208 / 120 3 4 10,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA
0 1 EXISTING LOAD E E E E 20E * 30E E E E E EXISTING LOAD 2 0
0 3 EXISTING LOAD E E E E 20E * 30E E E E E EXISTING LOAD 4 0
0 5 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 6 0
0 7 EXISTING LOAD E E E E 30E * 20E E E E E EXISTING LOAD 8 0
0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 10 0
0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0
0 13 EXISTING 208 REC E - E E 30E * 20E E E E E EXISTING LOAD 14 0
0 15 - E - - - 2P * 20E E E E E EXISTING LOAD 16 0
0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0
0 19 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 20 0
0 21 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 22 0
0 23 EXISTING LOAD E E E E 20E * 20E E - E E EXISTING LOAD 24 0
0 25 EXISTING LOAD E - E E 30E * 2P E - - - - 26 0
0 27 - E - - - 2P * 20E E - E E EXISTING LOAD 28 0
0 29 EXISTING LOAD E - E E 20E * 2P E - - - - 30 0
0 31 - E - - - 2P * 20E E - E E EXISTING LOAD 32 0
0 33 EXISTING LOAD E - E E 20E * 2P E - - - - 34 0
0 35 - E - - - 2P * 20E E E E E EXISTING LOAD 36 0
0 37 EXISTING LOAD E E E E 20E * 20E #12 - #12 1/2" SERVER AHU 38 0
0 39 SERVER A/C #10 - #10 1/2" 20E * 2P #12 - - - - 40 0
0 41 - #10 - - - 2P * 20E E E E E EXISTING LOAD 42 0
0 SUBTOTAL Ph A MAIN BREAKER - 100 AMPS SUBTOTAL Ph A 0
0 SUBTOTAL Ph B MAIN LUGS - - AMPS SUBTOTAL Ph B 0
0 SUBTOTAL Ph C BUS AMPACITY = 100 AMPS SUBTOTAL Ph C 0
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 0
A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:
RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 0 0
AMPS 0 0
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
12" = 1'-0"
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\Ele
ctr
ical -
Deta
ils -
2014.r
vt
E-601
Panel Schedules
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
LOCATION: ELECTRICAL ROOM EXISTING PANEL: C PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED
FROM:PANELMS
MODEL: AQF3422MBX
MTG: SURFACE VOLTS Ph W
208 / 120 3 4 10,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA
0 1 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 2 0
0 3 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 4 0
0 5 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 6 0
0 7 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 8 0
0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 10 0
0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0
0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0
0 15 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 16 0
0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0
0 19 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 20 0
0 21 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 22 0
0 23 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 24 0
0 25 PANEL C1 100E * 20E E E E E EXISTING LOAD 26 0
0 27 - 3P * 60E #6 - #10 3/4" GENERATOR TRANSFER SW 28 0
0 29 - - * 2P #6 - - - - 30 0
0 31 HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" HEAT PUMP 32 0
0 33 - #10 - - - 2P * 2P #10 - - - - 34 0
0 35 HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" HEAT PUMP 36 0
0 37 - #10 - - - 2P * 2P #10 - - - - 38 0
0 39 HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" HEAT PUMP LOBBY 40 0
0 41 - #10 - - - 2P * 2P #10 - - - - 42 0
0 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0
0 SUBTOTAL Ph B MAIN LUGS - 225 AMPS SUBTOTAL Ph B 0
0 SUBTOTAL Ph C BUS AMPACITY = 225 AMPS SUBTOTAL Ph C 0
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 0
A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:
RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 0 0
AMPS 0 0
E
E
E
E E E
-
-
- -
- -
LOCATION: ELECTRICAL ROOM EXISTING PANEL: C1 PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED
FROM:PANEL C
MODEL: TL24-415C
MTG: SURFACE VOLTS Ph W
208 / 120 3 4 10,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA
0 1 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 2 0
0 3 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 4 0
0 5 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 6 0
0 7 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 8 0
0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 10 0
0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0
0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0
0 15 EXISTING LOAD E E E E 30E * 20E E E E E EXISTING LOAD 16 0
0 17 EXISTING LOAD E E E E 30E * 20E E E E E EXISTING LOAD 18 0
0 19 EXISTING LOAD E - E E 30E * 20E E E E E EXISTING LOAD 20 0
0 21 - E - - - 2P * 20E E - E E EXISTING LOAD 22 0
0 23 EXISTING LOAD E E E E 20E * 2P E - - - - 24 0
0 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0
0 SUBTOTAL Ph B MAIN LUGS - 100 AMPS SUBTOTAL Ph B 0
0 SUBTOTAL Ph C BUS AMPACITY = 100 AMPS SUBTOTAL Ph C 0
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 0
A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:
RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 0 0
AMPS 0 0
LOCATION: ELECTRICAL ROOM EXISTINGPANEL: C2 PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: CUTLER-HAMMER FED
FROM:PANELMS
MODEL: PRL1a
MTG: SURFACE VOLTS Ph W
208 / 120 1 3 10,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B BKR Ph N G C LOAD # VA
0 1 SPACE * SPACE 2 0
0 3 EXISTING REC E E E E 20E * 40E SPARE (EXISTING RTU) 4 0
0 5 SPARE (EXISTING 208 REC) 30E * 3P - 6 0
0 7 - 2P * - - 8 0
0 9 EXISTING REC 20E * 40E SPARE (EXISTING RTU) 10 0
0 11 EXISTING REC 30E * 3P - 12 0
0 13 SPACE * - - 14 0
0 15 SPARE 20E * SPACE 16 0
0 17 SPACE * 15E SPARE (EXISTING 208 REC) 18 0
0 19 SPACE * 2P - 20 0
0 21 SPACE * 15E SPARE (EXISTING 208 REC) 22 0
0 23 SPACE * 2P - 24 0
0 25 SPACE * SPACE 26 0
0 27 SPACE * SPACE 28 0
0 29 SPACE * SPACE 30 0
0 31 SPACE * SPACE 32 0
0 33 SPACE * SPACE 34 0
0 35 SPACE * SPACE 36 0
0 37 SPACE * SPACE 38 0
0 39 SPACE * SPACE 40 0
0 41 SPACE * SPACE 42 0
0 SUBTOTAL Ph A MAIN BREAKER - 200 AMPS SUBTOTAL Ph A 0
0 SUBTOTAL Ph B MAIN LUGS - - AMPS SUBTOTAL Ph B 0BUS AMPACITY = 225 AMPS
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 0
A/C 0 100 0 VA ph B 0HEATING 0 100 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0 NOTESKITCHEN, #EQ = 0 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
RECEPTACLES 0 100 0MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 0 0
AMPS 0 0
E E E E
E E E E
LOCATION: ELECTRICAL ROOM EXISTINGPANEL: GEN PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED
FROM:PANELMS
MODEL: TLM3220CCU
MTG: SURFACE VOLTS Ph W
208 / 120 1 3 10,000 AIC
CONN CONN
VA # LOAD Ph N G C BKR A B BKR Ph N G C LOAD # VA
0 1 EXISTING LOAD E E E E 20E * 30E E - E E EXISTING LOAD 2 0
0 3 EXISTING LOAD E E E E 20E * 2P E - - - - 4 0
0 5 EXISTING LOAD E - E E 20E * 20E E - E E EXISTING LOAD 6 0
0 7 - E - - - 2P * 2P E - - - - 8 0
0 9 EXISTING LOAD E - E E 30E * 20E E E E E EXISTING LOAD 10 0
0 11 - E - - - 2P * 20E E E E E EXISTING LOAD 12 0
0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0
0 15 EXISTING LOAD E E E E 15E * 50E SPARE 16 0
0 17 EXISTING LOAD E E E E 20E * 2P - 18 0
0 19 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 20 0
0 21 EXISTING LOAD E E E E 20E * 50E E - E E EXISTING LOAD 22 0
0 23 EXISTING LOAD E E E E 20E * 2P E - - - - 24 0
0 25 EXISTING LOAD E E E E 20T/E * 20T/E E E E E EXISTING LOAD 26 0
0 27 EXISTING LOAD E E E E 20T/E * 20T/E E E E E EXISTING LOAD 28 0
0 29 EXISTING LOAD E E E E 20T/E * 30T/E E E E E EXISTING LOAD 30 0
0 31 EXISTING LOAD E E E E 20T/E * 30T/E E E E E EXISTING LOAD 32 0
0 SUBTOTAL Ph A MAIN BREAKER - 200 AMPS SUBTOTAL Ph A 0
0 SUBTOTAL Ph B MAIN LUGS - - AMPS SUBTOTAL Ph B 0BUS AMPACITY = 200 AMPS
LOAD CONN DF DEM
LIGHTING 0 125 0 VA ph A 0
A/C 0 100 0 VA ph B 0HEATING 0 100 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0 NOTESKITCHEN, #EQ = 0 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.
RECEPTACLES 0 100 0 2. "T" INDICATES TANDEM BREAKER.
MISCELLANEOUS 0 100 0
FUTURE 0 100 0
TOTAL VA 0 0
AMPS 0 0
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
12" = 1'-0"
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\Ele
ctr
ical -
Deta
ils -
2014.r
vt
E-602
Panel Schedules
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
EXISTINGMAIN PANEL
MS600A
208/120V3PH, 4W
MLO
EXISTINGPADMOUNTED
TRANSFORMERTO REMAIN
TO EXISTINGPRIMARY
COMPARTMENT
EXISTING UNDERGROUND SERVICELATERAL IN (2) 6'' CONDUITS TO REMAIN
EXISTING UNDERGROUNDPRIMARY TO REMAIN
EXISTINGGENERATOR
60KW208/120V
1PH
EXISTING GROUNDING ELECTRODECONDUCTOR TO REMAIN
90A SH3-POLE
208VENCLOSED
CIRCUITBREAKERWITH AUX.CONTACTS
EXISTINGPASSENGERELEVATOR
20HP208V3PH
EXISTINGPANEL
A225A
208/120V3PH, 4W
MLO
EXISTINGPANEL
AB100A
208/120V1PH, 3W
100A MCB
REMOVEEXISTING
PANELAA
225A208/120V3PH, 4W
MLO
REMOVEEXISTING
PANELAA2100A
208/120V3PH, 4W
MLO
EXISTINGPANEL
B225A
208/120V3PH, 4W
MLO
EXISTINGPANEL
B1100A
208/120V3PH, 4W
100A MCB
EXISTINGPANEL
C225A
208/120V3PH, 4W
MLO
EXISTINGPANEL
C1100A
208/120V3PH, 4W
MLO
EXISTINGPANEL
C2225A
208/120V1PH, 3W
200A MCB
EXISTINGPANELGEN200A
208/120V1PH, 3W
200A MCB
EXISTINGATS200A
208/120V2-POLE
200AMCB
EXISTINGCT
CABINETTO REMAIN
EXISTING SERVICE CONDUCTORSTO REMAIN
EXISTING FEEDER TO REMAIN
(3) #3, (1) #8EG, 1-1/4"C
EXISTING FEEDER TO REMAIN EXISTING FEEDER TO REMAIN
REMOVE EXISTING FEEDER
REMOVE EXISTING FEEDER
EXISTING FEEDER TO REMAIN
EXISTING FEEDER TO REMAIN
EXISTING FEEDER TO REMAIN
EXISTING FEEDER TO REMAIN
EXISTING FEEDERTO REMAIN
EXISTING200A208V
2-POLE3R
EXISTING FEEDERTO REMAIN
EXISTING FEEDER TO REMAIN
EXISTING FEEDER TO REMAIN
EXISTING FEEDER TO REMAIN
EXISTING FEEDER TO REMAIN
PROVIDE NEW 4"X4"X4'WIREWAY TO SERVECOOLING TOWER LOADS
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
1/8" = 1'-0"
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\Ele
ctr
ical -
Deta
ils -
2014.r
vt
E-800
Diagrams & Details
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
Not to Scale1
Power Riser Diagram
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
(TYP)
3/4" C
6" MIN.
SUSPENDEDCEILING
18"
FLOOR ABOVEOR ROOF
TELECOM RISER NOTES:
1. (2) EXISTING 4" CONDUITS WITH EXISTING INCOMING SERVICE.
NOTE 1GND FLOOR
1ST FLOOR
2ND FLOOR
ROOF
(1) EX. 4" C
TO EXISTINGSERVICECONNECTION
ELECTRICALCLOSET
ELECTRICALCLOSET
MECHANICALROOM
(1) EX. 4" C
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
1/8" = 1'-0"
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\Ele
ctr
ical -
Deta
ils -
2014.r
vt
E-801
Diagrams & Details
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
Not to Scale2
Voice/Data Outlet Detail
COMMUNICATIONS NOTES1. VOICE/DATA CABLING: PROVIDE (1) 4 PAIR, 24
AWG, UTP, CAT.5e, CMP RATED CABLE WITHBLUE JACKET FROM EACH OUTLET BOXINDICATED TO A PATCH PANEL LOCATED INTELECOM ROOM ON RESPECTIVE FLOOR.CABLES SHALL BE INSTALLED IN 3/4" EMT MIN.WHERE CONCEALED WITHIN WALLS, ABOVEINACCESSIBLE CEILINGS, AND EXPOSEDCEILING AREAS. PROVIDE (1) RJ-45 JACK IN ASINGLE WALL PLATE FOR EACH OUTLETSHOWN. TERMINATE EACH CAT. 5e CABLE TORJ-45 JACK AND PATCH PANEL. PROPERLYLABEL EACH END OF CABLE.
2. PATCH PANEL: PROVIDE A 19-INCH WALLMOUNTED RACK IN EACH ELECTRICALCLOSET. COORDINATE LOCATION OF RACKWITH OWNER. PROVIDE CAT. 5e PATCHPANEL WITH PORTS FOR CONNECTINGOUTLETS SHOWN PLUS 25% ADDITIONALCAPACITY FOR FUTURE OUTLETS.
3. TELEVISION CABLING: WHERE TV FACILITIESARE INDICATED, PROVIDE (1) RG6/U SOLIDCOPPER QUAD SHIELD COAXIAL,PLENUM-RATED CABLE FROM EACH OUTLETBOX INDICATED TO MECHANICAL ROOM 005.CABLES SHALL BE INSTALLED IN 3/4" EMT MIN.WHERE CONCEALED WITHIN WALLS, ABOVEINACCESSIBLE CEILINGS, AND EXPOSEDCEILING AREAS. PROVIDE A 75 OHM, F-TYPECONNECTOR IN A SINGLE WALL PLATE FOREACH OUTLET SHOWN. PROVIDE ALL CABLETERMINATIONS. PROPERLY LABEL EACH ENDOF CABLE. PROVIDE TV DISTRIBUTIONEQUIPMENT; INCLUDING BUT NOT LIMITED TO,DISTRIBUTION AMPLIFIERS, DIRECTIONALMULTI-TAPS, AND SPLITTERS.
4. CABLE INSTALLATION: CABLES SHALL BEENCLOSED IN RACEWAY WHERE INSTALLEDWITHIN FINISHED WALLS AND ABOVEINACCESSIBLE CEILINGS AREAS. PROVIDEJ-HOOKS, SECURED TO THE BUILDINGSTRUCTURE AT 4'-0" MAXIMUM INTERVALS, TOSUPPORT CABLES ABOVE ACCESSIBLECEILINGS.
5. IDENTIFICATION: LABEL EACH END OF ALLCABLE RUNS.
FIRE ALARM SYSTEM NOTES14. PROVIDE A TEST KEY SWITCH IN THE ELEVATOR MACHINE
ROOM TO SIMULATE THE ACTIVATION OF A HEAT DETECTORTO TEST THE POWER SHUT DOWN OPERATION OF THEELEVATOR.
15. WHEN ACTIVATED, THE SMOKE DETECTORS IN THEELEVATOR SHAFT, THE ELEVATOR LOBBIES, AND IN THEELEVATOR MACHINE ROOM SHALL SOUND A GENERAL FIREALARM AND RECALL THE ELEVATOR TO THE LEVEL OF THEEXIT DISCHARGE.
16. PROVIDE DUCT-TYPE SMOKE DETECTORS IN THE RETURN AIRDUCT OF THE HVAC UNITS INDICATED. WHEN ACTIVATED, THEDUCT-TYPE SMOKE DETECTORS SHALL AUTOMATICALLYSHUT DOWN THE HVAC UNIT, CLOSE THE MAIN FAN DAMPERS,AND SOUND A GENERAL FIRE ALARM.
17. PROVIDE WIRING AND CONNECTION TO ALL FLOW, TAMPER,AND PIV TAMPER SWITCHES. COORDINATE LOCATION WITHTHE SPRINKLER CONTRACTOR. EACH FLOW SWITCH SHALLBE ANNUNCIATED SEPARATELY. TAMPER AND PIV TAMPERSWITCHES SHALL BE ELECTRICALLY-SUPERVISED ANDANNUNCIATED AS A TROUBLE ON THE FACP.
18. PROVIDE REMOTE ALARM INDICATOR AND TEST STATION FOREACH DUCT-TYPE SMOKE DETECTOR AND SPRINKLERSYSTEM FLOW SWITCH. MOUNT STATION IN RECESSEDDEVICE BOX LOCATED 6'-0'' ABOVE FINISHED FLOOR. WIRINGSHALL BE ENCLOSED WITHIN RACEWAY AND CONCEALEDWITHIN WALL.
19. ALL EXTINGUISHING SYSTEMS SHALL BE CONNECTED TO THEFIRE ALARM SYSTEM PER CODE.
20. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
21. IDENTIFY SYSTEM COMPONENTS, WIRING, CABLING, ANDTERMINALS ACCORDING TO DIVISION 28 SPECIFICATIONS.
22. FIRE ALARM WIRING SHALL BE ENCLOSED IN METALRACEWAY SEPARATE FROM OTHER DATA AND POWERWIRING WHERE CONCEALED WITHIN WALLS AND EXPOSEDON WALLS OF UNFINISHED SPACES OR UNLESS OTHERWISEINDICATED. PLENUM-RATED FIRE ALARM CABLE SHALL BEPERMITTED WHERE CONCEALED ABOVE GRID CEILINGS INFINISHED AREAS. SECURE CABLES TO BUILDING STRUCTUREUSING APPROVED SUPPORTING DEVICES MOUNTED AT 4'-0"MAXIMUM INTERVALS. BOXES SHALL BE PAINTED RED FORIDENTIFICATION.
FIRE ALARM SYSTEM NOTES1. ALL WORK SHALL COMPLY WITH THE WEST VIRGINIA STATE
FIRE CODE. ALL WORK SHALL COMPLY WITH THE NFPA CODEADOPTED BY THE WEST VIRGINIA STATE FIRE CODE.
2. THE FIRE ALARM INSTALLER SHALL SUBMIT REQUIREDINFORMATION TO THE WEST VIRGINIA STATE FIRE MARSHALFOR APPROVAL. THE FIRE ALARM INSTALLER SHALL SUBMITFIRE ALARM DRAWINGS, COMPLETE WITH EQUIPMENTLOCATIONS, DIMENSIONS BETWEEN LIKE DEVICES TO VERIFYPROPER SPACING, AND FIRE ALARM RISER DIAGRAM
3. REPLACE THE EXISTING NONCODED, ZONED FIRE ALARMSYSTEM WITH A NEW ADDRESSABLE FIRE ALARM SYSTEMWITH MANUAL AND AUTOMATIC ALARM INITIATION; ANDHARDWIRED FOR SIGNAL TRANSMISSION DEDICATED TO FIREALARM SERVICE ONLY, USING A UNIQUE ADDRESS FOR EACHALARM INITIATION DEVICE.
4. PROVIDE A DEDICATED 20 AMP, 120 VOLT BRANCH CIRCUITFOR FACP POWER.
5. PROVIDE A DEDICATED TELEPHONE LINE TO FACP FORTRANSMITTING MEANS TO REMOTE SUPERVISING STATIONFROM DIGITAL ALARM COMMUNICATOR TRANSMITTER.
6. PROVIDE A FIRE ALARM ANNUNCIATOR PANEL IN MAINVESTIBULE.
7. SMOKE DETECTORS SHALL BE PLACED A MAXIMUM OF 15FEET FROM THE ENDS OF CORRIDORS OR WALLS AND 30FEET ON CENTER AND IN ROOMS OPEN TO THE CORRIDORS.EXCEEDING THE SPACING REQUIREMENTS WILL REQUIRESUBMISSION OF TECHNICAL DATA FOR APPROVAL BY THEFIRE MARSHAL.
8. IN CORRIDORS, VISIBLE NOTIFICATION APPLIANCES SHALL BELOCATED NOT MORE THAN 15 FEET FROM THE END OF THECORRIDOR WITH A SEPARATION NOT GREATER THAN 100FEET BETWEEN APPLIANCES.
9. VISIBLE NOTIFICATION APPLIANCES SHALL BE LOCATED INALL PUBLIC TOILETS.
10. PULL STATIONS SHALL BE LOCATED NO GREATER THAN 200FEET FROM EACH OTHER AND AT ALL EXITS.
11. WHERE EXISTING DEVICE BOXES ARE BEING USED FOR NEWCONSTRUCTION, VERIFY PROPER MOUNTING HEIGHT. IFMOUNTING HEIGHT OF PROPOSED DEVICE IS NOT PER CODE,REPLACE CONCEALED BOX AND RACEWAY AT PROPERHEIGHT.
12. PROVIDE ELEVATOR EMERGENCY OPERATION PER CURRENTEDITION OF ASME A17.1.
13. HEAT DETECTORS IN THE ELEVATOR SHAFT AND IN THEELEVATOR MACHINE ROOM SHALL BE MOUNTED WITHIN 2FEET OF EACH SPRINKLER HEAD. SPRINKLER HEAD SHALLHAVE A HIGHER RESPONSE TIME INDEX (RTI) THAN THE HEATDETECTOR. WHEN ACTIVATED, THE HEAT DETECTORS IN THEELEVATOR SHAFT AND IN THE ELEVATOR MACHINE ROOMSHALL SOUND A GENERAL FIRE ALARM, RECALL THEELEVATOR TO THE LEVEL OF EXIT DISCHARGE ANDAUTOMATICALLY SHUT DOWN POWER TO THE ELEVATORUSING A SHUNT-TRIP CIRCUIT BREAKER.
Not to Scale1
Telecom Riser Diagram
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
F
OS OSOS
SS
FEC
S
GC GC GC
W
S
CR
GC
F S
MS
FEC
R
R
R
E E E EE E E
EE
E
E E EEE EE E
E EE
R
E E
R
R
R
R
RRRR
R
RRRR
E
E E E E E EEE E
R
RR R
R
R
CT
WSHP
R
1
E
E E
R RR
RR
R
R
R R R R
E E E E
R
E
E
R
R
R R RRR
E
R
R
R
E
R
R
R
R
R
R
R
R
R
E E
E
EE
E
E
E E E
EEE
E
EER
R
FA
CP
E
E
R
WSHP
WSHP
WH
BOILER
AIRCOMP
AIRCOMP
PUMPPUMP
AA
AA2
ELEV
G
R
R R
R
RR
A AB
CT E
E
R R E
FIRE ALARMDISCONNECT
ED-100
2
ED-100
3
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
ED-100
Ground FloorElectrical DemolitionPlan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/4" = 1'-0"2
ENLARGED GROUND FLOOR ELECTRICAL DEMOLITION PLAN -SOUTH
1/4" = 1'-0"3
ENLARGED GROUND FLOOR ELECTRICAL DEMOLITION PLAN -NORTH
1/16" = 1'-0"1
DEMO - GROUND FLOOR ELECTRICAL PLAN
GENERAL DEMOLITION NOTES1. ALL DEVICES AND EQUIPMENT SHOWN ON THE ELECTRICAL
DEMOLITION PLAN ARE FOR REFERENCE ONLY AND SHALL BEFIELD VERIFIED BEFORE STARTING WORK. NOTIFY A/E IFDEVICES AND EQUIPMENT NOT SHOWN ON THE PLAN AREFOUND DURING DEMOLITION WORK.
2. REMOVE EXISTING BRANCH CIRCUIT WIRING FROM FIXTURESAND DEVICES BEING REMOVED BACK TO SOURCE CIRCUITBREAKER. VERIFY POWER CONTINUATION OF EXISTINGFIXTURES AND DEVICES INDICATED TO REMAIN.
3. REMOVE EXISTING LIGHT FIXTURES, EXIT LIGHTS, ANDEMERGENCY BATTERY LIGHTS WITHIN THE AREA OFCONSTRUCTION, UNLESS OTHERWISE NOTED.
4. REMOVE EXISTING LIGHT SWITCHES, WALL PLATES, ANDASSOCIATED WIRING WITHIN THE AREA OF CONSTRUCTION,UNLESS OTHERWISE NOTED.
5. EXISTING LIGHT SWITCHES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECT LIGHTSWITCH TO EXISTING WIRING AS INDICATED. REPLACE WALLPLATE TO MATCH.
6. EXISTING RECESSED DEVICE BOXES FOR NOTED LIGHTSWITCHES AND RECEPTACLES AND ASSOCIATED CONCEALEDRACEWAY SHALL REMAIN FOR USE WITH NEWCONSTRUCTION.
7. PROVIDE A BLANK WALL PLATE FOR ALL EXISTING RECESSEDDEVICE BOXES NOT USED FOR NEW CONSTRUCTION.PROVIDE GANGING OF WALL PLATE AS REQUIRED TO COVEREXISTING DEVICE BOX.
8. REMOVE EXISTING RECEPTACLES AS INDICATED. REMOVEASSOCIATED BRANCH CIRCUIT WIRING BACK TO SOURCECIRCUIT BREAKER. VERIFY POWER CONTINUATION OFEXISTING RECEPTACLES INDICATED TO REMAIN.
9. EXISTING RECEPTACLES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECTRECEPTACLE TO EXISTING WIRING AS INDICATED. REPLACEWALL PLATE TO MATCH.
10. REMOVE EXISTING VOICE/DATA OUTLETS AS INDICATED.REMOVE VOICE/DATA CABLES BACK TO PATCH PANEL.EXISTING RECESSED BOXES AND CONCEALED RACEWAYSHALL REMAIN FOR FUTURE USE. PROVIDE BLANK WALLPLATES TO COVER EXISTING DEVICE BOXES.
11. REPLACE EXISTING BLANK WALL PLATES WITH WALL PLATESMATCHING PLATES OF DEVICES USED IN NEWCONSTRUCTION.
12. REMOVE EXISTING EXPOSED CONDUIT AND SURFACERACEWAY ON FINISHED WALLS, UNLESS USED FOR NEWCONSTRUCTION.
13. REMOVE EXISTING ACCESS CONTROL SYSTEM DEVICES ANDASSOCIATED WIRING.
14. SEAL FIRE RATED WALLS, FLOORS AND STRUCTURAL CEILINGFROM REMOVED RACEWAY AND SLEEVES MATCHING FIRERATING OF EXISTING ASSEMBLY.
15. REMOVE ALL EXISTING ACCESSIBLE POWER WIRING, DATACABLES, AND ASSOCIATED RACEWAYS NOT BEING USED FORNEW CONSTRUCTION.
17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.
17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.
16. REMOVE EXISTING SURFACE MOUNTED RECEPTACLES ANDASSOCIATED SURFACE RACEWAY. VERIFY POWERCONTINUATION AND TERMINATE BRANCH CIRCUIT WIRING INNEAREST ACCESSIBLE JUNCTION BOX. REMOVE EXISTINGBRANCH CIRCUIT WIRING BACK TO SOURCE CIRCUITBREAKER FOR DEDICATED RECEPTACLES.
17. REMOVE EXISTING SURFACE MOUNTED VOICE/DATA OUTLETSAND ASSOCIATED SURFACE RACEWAY. REMOVE VOICE/DATACABLES BACK TO PATCH PANEL.
18. REMOVE EXISTING FIRE ALARM SYSTEM AND ASSOCIATEDCABLING. EXISTING RECESSED DEVICE BOXES ANDCONCEALED RACEWAY SHALL REMAIN AND BE USED FORNEW CONSTRUCTION IF MOUNTING HEIGHT IS PER NFPAGUIDELINES. EXISTING FIRE ALARM SYSTEM SHALL REMAININ OPERATION UNTIL NEW SYSTEM IS INSTALLED.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
GC
F
3
4
S
GC
G
TV
GC
CR
S
S
S
F
3
CR
CR
SSCR
ED-101
2
ED-101
3
E
E EE E E E EE E E E EE E E EEEEEEEEE
RR R R R R R R R RRRR
R R
R
EE
R
R R R
E
E
E
E
E E
E
R
E E E E E E E E E E E E E E E EEEEEEEEE
E
E
E E E E EEEE EE
E
R
RR
R
RR
R RR
E
E
ER
R
E
E
E E E E EEEE
E
E
R
E
R
E E
E E
E E
R R
E
WSHP WSHP
WSHPWSHP
B1
BE
E
R R
R
E E E E E EE E E
E
E
EEEEEE EEEEEE EEE
E
EEEE EEEEEE E E EEEEEEE E E E E
E
R
EEEEE E E EE E E E
RRR
R
RR
R R RRRR R R R RRRRR
R
RRR
R
FC
WSHP WSHP
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
ED-101
First Floor ElectricalDemolition Plan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/16" = 1'-0"1
DEMO - FIRST FLOOR ELECTRICAL PLAN
1/4" = 1'-0"2
ENLARGED FIRST FLOOR ELECTRICAL DEMOLITION PLAN - NORTH
1/4" = 1'-0"3
ENLARGED FIRST FLOOR ELECTRICAL DEMOLITION PLAN - SOUTH
GENERAL DEMOLITION NOTES1. ALL DEVICES AND EQUIPMENT SHOWN ON THE ELECTRICAL
DEMOLITION PLAN ARE FOR REFERENCE ONLY AND SHALL BEFIELD VERIFIED BEFORE STARTING WORK. NOTIFY A/E IFDEVICES AND EQUIPMENT NOT SHOWN ON THE PLAN AREFOUND DURING DEMOLITION WORK.
2. REMOVE EXISTING BRANCH CIRCUIT WIRING FROM FIXTURESAND DEVICES BEING REMOVED BACK TO SOURCE CIRCUITBREAKER. VERIFY POWER CONTINUATION OF EXISTINGFIXTURES AND DEVICES INDICATED TO REMAIN.
3. REMOVE EXISTING LIGHT FIXTURES, EXIT LIGHTS, ANDEMERGENCY BATTERY LIGHTS WITHIN THE AREA OFCONSTRUCTION, UNLESS OTHERWISE NOTED.
4. REMOVE EXISTING LIGHT SWITCHES, WALL PLATES, ANDASSOCIATED WIRING WITHIN THE AREA OF CONSTRUCTION,UNLESS OTHERWISE NOTED.
5. EXISTING LIGHT SWITCHES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECT LIGHTSWITCH TO EXISTING WIRING AS INDICATED. REPLACE WALLPLATE TO MATCH.
6. EXISTING RECESSED DEVICE BOXES FOR NOTED LIGHTSWITCHES AND RECEPTACLES AND ASSOCIATED CONCEALEDRACEWAY SHALL REMAIN FOR USE WITH NEWCONSTRUCTION.
7. PROVIDE A BLANK WALL PLATE FOR ALL EXISTING RECESSEDDEVICE BOXES NOT USED FOR NEW CONSTRUCTION.PROVIDE GANGING OF WALL PLATE AS REQUIRED TO COVEREXISTING DEVICE BOX.
8. REMOVE EXISTING RECEPTACLES AS INDICATED. REMOVEASSOCIATED BRANCH CIRCUIT WIRING BACK TO SOURCECIRCUIT BREAKER. VERIFY POWER CONTINUATION OFEXISTING RECEPTACLES INDICATED TO REMAIN.
9. EXISTING RECEPTACLES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECTRECEPTACLE TO EXISTING WIRING AS INDICATED. REPLACEWALL PLATE TO MATCH.
10. REMOVE EXISTING VOICE/DATA OUTLETS AS INDICATED.REMOVE VOICE/DATA CABLES BACK TO PATCH PANEL.EXISTING RECESSED BOXES AND CONCEALED RACEWAYSHALL REMAIN FOR FUTURE USE. PROVIDE BLANK WALLPLATES TO COVER EXISTING DEVICE BOXES.
11. REPLACE EXISTING BLANK WALL PLATES WITH WALL PLATESMATCHING PLATES OF DEVICES USED IN NEWCONSTRUCTION.
12. REMOVE EXISTING EXPOSED CONDUIT AND SURFACERACEWAY ON FINISHED WALLS, UNLESS USED FOR NEWCONSTRUCTION.
13. REMOVE EXISTING ACCESS CONTROL SYSTEM DEVICES ANDASSOCIATED WIRING.
14. SEAL FIRE RATED WALLS, FLOORS AND STRUCTURAL CEILINGFROM REMOVED RACEWAY AND SLEEVES MATCHING FIRERATING OF EXISTING ASSEMBLY.
15. REMOVE ALL EXISTING ACCESSIBLE POWER WIRING, DATACABLES, AND ASSOCIATED RACEWAYS NOT BEING USED FORNEW CONSTRUCTION.
17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.
17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.
16. REMOVE EXISTING SURFACE MOUNTED RECEPTACLES ANDASSOCIATED SURFACE RACEWAY. VERIFY POWERCONTINUATION AND TERMINATE BRANCH CIRCUIT WIRING INNEAREST ACCESSIBLE JUNCTION BOX. REMOVE EXISTINGBRANCH CIRCUIT WIRING BACK TO SOURCE CIRCUITBREAKER FOR DEDICATED RECEPTACLES.
17. REMOVE EXISTING SURFACE MOUNTED VOICE/DATA OUTLETSAND ASSOCIATED SURFACE RACEWAY. REMOVE VOICE/DATACABLES BACK TO PATCH PANEL.
18. REMOVE EXISTING FIRE ALARM SYSTEM AND ASSOCIATEDCABLING. EXISTING RECESSED DEVICE BOXES ANDCONCEALED RACEWAY SHALL REMAIN AND BE USED FORNEW CONSTRUCTION IF MOUNTING HEIGHT IS PER NFPAGUIDELINES. EXISTING FIRE ALARM SYSTEM SHALL REMAININ OPERATION UNTIL NEW SYSTEM IS INSTALLED.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
FEC
FEC
OS OS
C
GC GC
GC
FS
STV
TV
FDD
S
FS
S
ED-102
2
ED-102
3
EE
R
E E E E E E E E E E E E E E E E E EE
E
E E E E EEEE EEEE EEEEEE EEE
E
E E E E E EE E
R
R
R R
RR
RR R
R
R RR
R
RRRRRR
R
RRR R R R
E
R
R
R
R
R E RER
E E R
R
RR K
B
PB
E
RRR
FACP
E
R
WSHP
WSHP
WSHP
WSHP
CE
GEN/ATSE
C1/C2
E
E
E
E
E E
E
EEE E E E E E E E E E EEE E EE E E E EEE E
E E E E E EEE
EEEEEEEEEEEE E E E
E
R R R
R R R
R
R R
RRRRRRRRRR
WSHP
WSHP
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
As indicated
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
ED-102
Second FloorElectrical DemolitionPlan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/16" = 1'-0"1
DEMO - SECOND FLOOR ELECTRICAL PLAN
1/4" = 1'-0"2
ENLARGED SECOND FLOOR ELECTRICAL DEMOLITION PLAN -NORTH
1/4" = 1'-0"3
ENLARGED SECOND FLOOR ELECTRICAL DEMOLITION PLAN -SOUTH
GENERAL DEMOLITION NOTES1. ALL DEVICES AND EQUIPMENT SHOWN ON THE ELECTRICAL
DEMOLITION PLAN ARE FOR REFERENCE ONLY AND SHALL BEFIELD VERIFIED BEFORE STARTING WORK. NOTIFY A/E IFDEVICES AND EQUIPMENT NOT SHOWN ON THE PLAN AREFOUND DURING DEMOLITION WORK.
2. REMOVE EXISTING BRANCH CIRCUIT WIRING FROM FIXTURESAND DEVICES BEING REMOVED BACK TO SOURCE CIRCUITBREAKER. VERIFY POWER CONTINUATION OF EXISTINGFIXTURES AND DEVICES INDICATED TO REMAIN.
3. REMOVE EXISTING LIGHT FIXTURES, EXIT LIGHTS, ANDEMERGENCY BATTERY LIGHTS WITHIN THE AREA OFCONSTRUCTION, UNLESS OTHERWISE NOTED.
4. REMOVE EXISTING LIGHT SWITCHES, WALL PLATES, ANDASSOCIATED WIRING WITHIN THE AREA OF CONSTRUCTION,UNLESS OTHERWISE NOTED.
5. EXISTING LIGHT SWITCHES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECT LIGHTSWITCH TO EXISTING WIRING AS INDICATED. REPLACE WALLPLATE TO MATCH.
6. EXISTING RECESSED DEVICE BOXES FOR NOTED LIGHTSWITCHES AND RECEPTACLES AND ASSOCIATED CONCEALEDRACEWAY SHALL REMAIN FOR USE WITH NEWCONSTRUCTION.
7. PROVIDE A BLANK WALL PLATE FOR ALL EXISTING RECESSEDDEVICE BOXES NOT USED FOR NEW CONSTRUCTION.PROVIDE GANGING OF WALL PLATE AS REQUIRED TO COVEREXISTING DEVICE BOX.
8. REMOVE EXISTING RECEPTACLES AS INDICATED. REMOVEASSOCIATED BRANCH CIRCUIT WIRING BACK TO SOURCECIRCUIT BREAKER. VERIFY POWER CONTINUATION OFEXISTING RECEPTACLES INDICATED TO REMAIN.
9. EXISTING RECEPTACLES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECTRECEPTACLE TO EXISTING WIRING AS INDICATED. REPLACEWALL PLATE TO MATCH.
10. REMOVE EXISTING VOICE/DATA OUTLETS AS INDICATED.REMOVE VOICE/DATA CABLES BACK TO PATCH PANEL.EXISTING RECESSED BOXES AND CONCEALED RACEWAYSHALL REMAIN FOR FUTURE USE. PROVIDE BLANK WALLPLATES TO COVER EXISTING DEVICE BOXES.
11. REPLACE EXISTING BLANK WALL PLATES WITH WALL PLATESMATCHING PLATES OF DEVICES USED IN NEWCONSTRUCTION.
12. REMOVE EXISTING EXPOSED CONDUIT AND SURFACERACEWAY ON FINISHED WALLS, UNLESS USED FOR NEWCONSTRUCTION.
13. REMOVE EXISTING ACCESS CONTROL SYSTEM DEVICES ANDASSOCIATED WIRING.
14. SEAL FIRE RATED WALLS, FLOORS AND STRUCTURAL CEILINGFROM REMOVED RACEWAY AND SLEEVES MATCHING FIRERATING OF EXISTING ASSEMBLY.
15. REMOVE ALL EXISTING ACCESSIBLE POWER WIRING, DATACABLES, AND ASSOCIATED RACEWAYS NOT BEING USED FORNEW CONSTRUCTION.
17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.
17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.
16. REMOVE EXISTING SURFACE MOUNTED RECEPTACLES ANDASSOCIATED SURFACE RACEWAY. VERIFY POWERCONTINUATION AND TERMINATE BRANCH CIRCUIT WIRING INNEAREST ACCESSIBLE JUNCTION BOX. REMOVE EXISTINGBRANCH CIRCUIT WIRING BACK TO SOURCE CIRCUITBREAKER FOR DEDICATED RECEPTACLES.
17. REMOVE EXISTING SURFACE MOUNTED VOICE/DATA OUTLETSAND ASSOCIATED SURFACE RACEWAY. REMOVE VOICE/DATACABLES BACK TO PATCH PANEL.
18. REMOVE EXISTING FIRE ALARM SYSTEM AND ASSOCIATEDCABLING. EXISTING RECESSED DEVICE BOXES ANDCONCEALED RACEWAY SHALL REMAIN AND BE USED FORNEW CONSTRUCTION IF MOUNTING HEIGHT IS PER NFPAGUIDELINES. EXISTING FIRE ALARM SYSTEM SHALL REMAININ OPERATION UNTIL NEW SYSTEM IS INSTALLED.
RY
M CHNC
R
EGIS TERE
D
ST
V I R GI
SIONAL EN
13460
STATE OF
AI
N
WE R
EE
NIG
PROF
ES
GA Y
E
. A
RTU
RTU
EF
R
R
E
Owner / Client:
Project Number
Date:
Drawing Title:
Scale:
Drawing Number:
© Desmone Architects 2015
Revisions:
Seal:
Fo
r
O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T
P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m
1/8" = 1'-0"
Z:\
ME
P C
UR
RE
NT
PR
OJE
CT
S\D
esm
on
e A
rch
itects
- J
ob
s\D
ES
MO
NE
-ME
P15-0
3 -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter-
Ph
ase II\R
evit
& C
AD
\E -
Mo
rgan
tow
n E
nte
rpri
se C
en
ter
Off
ice.r
vt
ED-103
Roof DemolitionPlan
Monongalia County DevelopmentAuthority
Morg
anto
wn E
nte
rprise C
ente
r O
ffic
e B
uild
ing
3942
08.26.2015
955 H
art
man
Ru
n R
oad
Mo
rgan
tow
n, W
V 2
6505
Inte
rio
r &
Exte
rio
r R
en
ovati
on
s
08.2
6.2
015
1/8" = 1'-0"1
DEMO - Roof Floor Power Plan
GENERAL DEMOLITION NOTES1. ALL DEVICES AND EQUIPMENT SHOWN ON THE ELECTRICAL
DEMOLITION PLAN ARE FOR REFERENCE ONLY AND SHALL BEFIELD VERIFIED BEFORE STARTING WORK. NOTIFY A/E IFDEVICES AND EQUIPMENT NOT SHOWN ON THE PLAN AREFOUND DURING DEMOLITION WORK.
2. REMOVE EXISTING BRANCH CIRCUIT WIRING FROM FIXTURESAND DEVICES BEING REMOVED BACK TO SOURCE CIRCUITBREAKER. VERIFY POWER CONTINUATION OF EXISTINGFIXTURES AND DEVICES INDICATED TO REMAIN.
3. REMOVE EXISTING LIGHT FIXTURES, EXIT LIGHTS, ANDEMERGENCY BATTERY LIGHTS WITHIN THE AREA OFCONSTRUCTION, UNLESS OTHERWISE NOTED.
4. REMOVE EXISTING LIGHT SWITCHES, WALL PLATES, ANDASSOCIATED WIRING WITHIN THE AREA OF CONSTRUCTION,UNLESS OTHERWISE NOTED.
5. EXISTING LIGHT SWITCHES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECT LIGHTSWITCH TO EXISTING WIRING AS INDICATED. REPLACE WALLPLATE TO MATCH.
6. EXISTING RECESSED DEVICE BOXES FOR NOTED LIGHTSWITCHES AND RECEPTACLES AND ASSOCIATED CONCEALEDRACEWAY SHALL REMAIN FOR USE WITH NEWCONSTRUCTION.
7. PROVIDE A BLANK WALL PLATE FOR ALL EXISTING RECESSEDDEVICE BOXES NOT USED FOR NEW CONSTRUCTION.PROVIDE GANGING OF WALL PLATE AS REQUIRED TO COVEREXISTING DEVICE BOX.
8. REMOVE EXISTING RECEPTACLES AS INDICATED. REMOVEASSOCIATED BRANCH CIRCUIT WIRING BACK TO SOURCECIRCUIT BREAKER. VERIFY POWER CONTINUATION OFEXISTING RECEPTACLES INDICATED TO REMAIN.
9. EXISTING RECEPTACLES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECTRECEPTACLE TO EXISTING WIRING AS INDICATED. REPLACEWALL PLATE TO MATCH.
10. REMOVE EXISTING VOICE/DATA OUTLETS AS INDICATED.REMOVE VOICE/DATA CABLES BACK TO PATCH PANEL.EXISTING RECESSED BOXES AND CONCEALED RACEWAYSHALL REMAIN FOR FUTURE USE. PROVIDE BLANK WALLPLATES TO COVER EXISTING DEVICE BOXES.
11. REPLACE EXISTING BLANK WALL PLATES WITH WALL PLATESMATCHING PLATES OF DEVICES USED IN NEWCONSTRUCTION.
12. REMOVE EXISTING EXPOSED CONDUIT AND SURFACERACEWAY ON FINISHED WALLS, UNLESS USED FOR NEWCONSTRUCTION.
13. REMOVE EXISTING ACCESS CONTROL SYSTEM DEVICES ANDASSOCIATED WIRING.
14. SEAL FIRE RATED WALLS, FLOORS AND STRUCTURAL CEILINGFROM REMOVED RACEWAY AND SLEEVES MATCHING FIRERATING OF EXISTING ASSEMBLY.
15. REMOVE ALL EXISTING ACCESSIBLE POWER WIRING, DATACABLES, AND ASSOCIATED RACEWAYS NOT BEING USED FORNEW CONSTRUCTION.
17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.
17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.
16. REMOVE EXISTING SURFACE MOUNTED RECEPTACLES ANDASSOCIATED SURFACE RACEWAY. VERIFY POWERCONTINUATION AND TERMINATE BRANCH CIRCUIT WIRING INNEAREST ACCESSIBLE JUNCTION BOX. REMOVE EXISTINGBRANCH CIRCUIT WIRING BACK TO SOURCE CIRCUITBREAKER FOR DEDICATED RECEPTACLES.
17. REMOVE EXISTING SURFACE MOUNTED VOICE/DATA OUTLETSAND ASSOCIATED SURFACE RACEWAY. REMOVE VOICE/DATACABLES BACK TO PATCH PANEL.
18. REMOVE EXISTING FIRE ALARM SYSTEM AND ASSOCIATEDCABLING. EXISTING RECESSED DEVICE BOXES ANDCONCEALED RACEWAY SHALL REMAIN AND BE USED FORNEW CONSTRUCTION IF MOUNTING HEIGHT IS PER NFPAGUIDELINES. EXISTING FIRE ALARM SYSTEM SHALL REMAININ OPERATION UNTIL NEW SYSTEM IS INSTALLED.