R Y M C H N C R E G I S T E R E D S T V I R G I S I O N A L E N 13460 STATE OF A I N W E R E E N I G P R O F E S G A Y E . A LIGHTING FIXTURE SCHEDULE MOUNTING TYPE MFR. CATALOG NO. DESCRIPTION LAMPS WATTS SYMBOL VOLTS NOTES B (2) A 2'X2' LED TROFFER WITH DIMMING DRIVER CEILING RECESSED 120 CEILING RECESSED AE CEILING RECESSED X EXIT LIGHT; SHADED AREA INDICATES EXIT FACE; ARROW INDICATES DIRECTION OF EGRESS 120 CEILING OR WALL 7'-0" XR EXIT LIGHT; SHADED AREA INDICATES EXIT FACE; REMOTE CAPACITY 120 D BE CEILING RECESSED 4' LED NARROW WRAPAROUND CEILING SURFACE K EE 4' LED WIDE WRAPAROUND SURFACE 120 120 120 120 120 120 FE SURFACE 120 G 2' FLUORESCENT VANITY WALL BRACKET WALL 6'-6" DE 120 SAME AS FIXTURE TYPE 'D', EXCEPT FIXTURE TO HAVE EMERGENCY BATTERY BACKUP V EXTERIOR LED SCONCE WALL 5'-0" W EXTERIOR LED WALL PACK 120 120 120 WALL 10'-0" 6" OPEN REFLECTOR LED DOWNLIGHT WITH DIMMING DRIVER 35 CEILING RECESSED 35 CEILING RECESSED 40 40 1 LED 4 LED LQM S W 3 R 120/277 ELN LHQM S W 3 R HO RO WL4 25L D24 LP835 NX 24 KENALL OLW 23 FS824T-2TB-PIA BR-27L40K-1-DV 30 35 SAME AS FIXTURE TYPE 'A', EXCEPT FIXTURE TO HAVE EMERGENCY BATTERY BACKUP SAME AS FIXTURE TYPE 'B', EXCEPT FIXTURE TO HAVE EMERGENCY BATTERY BACKUP SAME AS FIXTURE TYPE 'E', EXCEPT FIXTURE TO HAVE EMERGENCY BATTERY BACKUP METALUX 22EN-LD1-34-UNV L835-CD1 3400 LM 3500K LED 35 55 55 (3) (4) R H ELA DDB OMC H1006 1-H1006 MR11 6 10 EXTERIOR REMOTE EMERGENCY LIGHT LITHONIA WALL 7'-0" NARROW LINEAR LED PENDANT WITH DIMMING DRIVER PENDANT 8'-0" 120 (5) (3) (5) 40 (5) 5400 LM 3500K LED 2'X4' LED TROFFER WITH DIMMING DRIVER 5400 LM 3500K LED LITHONIA 2500 LM 3500K LED LITHONIA LITHONIA STL4 48L D50 LP835 NX 4800 LM 3500K LED STL4 48L D50 LP835 NX EL14L 4800 LM 3500K LED GOTHAM GOTHAM EVO 35/22 6AR MVOLT TRW 2200 LM 3500K LED EVO 35/22 6AR MVOLT TRW ELR 2200 LM 3500K LED 2700 LM 4000K LED LITHONIA LITHONIA CEILING OR WALL 7'-0" LITHONIA 2700 LM 5000K LED METALUX 22EN-LD1-34-UNV EL10W-L835-CD1 3400 LM 3500K LED 35 METALUX 24EN-LD1-54-UNV L835-CD1 C CEILING RECESSED 120 35 (5) 4000 LM 3500K LED 2'X4' LED TROFFER WITH DIMMING DRIVER LITHONIA 2TL4 40L FW A12 EZ1 LP835 TECH LIGHTING 700BCSLC26W-C-CF 2-24W T5/835 55 TECH LIGHTING 700LSVAN-W-S-LED830 2400 LM 3000K LED METALUX 24EN-LD1-54-UNV EL10W-L835-CD1 (3) (5) (3) (5) (5) (3) (3) (3) (1) (5) ELECTRICAL SYMBOL LEGEND DESCRIPTION WIRING AND RACEWAY CONCEALED IN WALLS AND/OR ABOVE CEILING, UNLESS NOTED OTHERWISE SYMBOL NOTE: ALL SYMBOLS MAY NOT BE REPRESENTED ON PLANS. J 3 4 a D E A-2 HOMERUN; TEXT INDICATES PANEL DESIGNATION AND CIRCUIT NUMBER UNSWITCHED PHASE CONDUCTOR TOWARDS HOME RUN TO DISTINQUISH LIGHTING CONTROL JUNCTION BOX PER N.E.C. SINGLE POLE SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F. INDICATES CONDUIT STUBBED INTO SPACE; PROVIDE CONDUIT BUSHING THREE-WAY SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F. FOUR-WAY SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F. LIGHT SWITCH; LOWER CASE LETTER DENOTES LIGHT FIXTURE BEING CONTROLLED DIMMER SWITCH; 1500W, LOW VOLTAGE, MOUNT AT 48" O.C. A.F.F. WIRING AND RACEWAY CONCEALED IN/OR UNDER FLOOR OR UNDERGROUND OS F M OS R G E C GC R RECEPTACLE; NEMA 5-20R DUPLEX; 18" O.C. A.F.F. OR AS NOTED RECEPTACLE; NEMA 5-20R DUPLEX; 18" O.C. A.F.F. OR AS NOTED; GFCI; NON FEED THRU FAN CONTROL SWITCH; 120/277V, MOUNT AT 48" O.C. A.F.F. MANUAL MOTOR STARTER SWITCH; 20A, 1 HP, 120/277V, MOUNT AT 48" O.C. A.F.F. OCCUPANCY SENSOR WALL SWITCH; DUAL TECH.; MANUAL ON, AUTO OFF; (2) RELAYS FOR CONTROL OF (2) LOADS; 1200W, LOW VOLTAGE, MOUNT AT 48" O.C. A.F.F. EXISTING SWITCH TO BE REMOVED RECEPTACLE; NEMA 5-20R DUPLEX; 44" O.C. A.F.F. RECEPTACLE; NEMA 5-20R DUPLEX; 44" O.C. A.F.F.; GFCI; NON FEED THRU EXISTING RECEPTACLE TO BE REMOVED OCCUPANCY SENSOR; CEILING MOUNTED, DUAL TECHNOLOGY; LOW VOLTAGE R E INDICATES ELECTRICAL CONNECTION BY ELECTRICAL CONTRACTOR TO EQUIPMENT PROVIDED AND INSTALLED BY OTHERS. SAFETY DISCONNECT SWITCH; SEE DISCONNECT SCHEDULE FOR RATINGS SURFACE MOUNTED DISTRIBUTION PANEL; SEE RESPECTIVE PANEL SCHEDULE FLUSH MOUNTED DISTRIBUTION PANEL; SEE RESPECTIVE PANEL SCHEDULE (2) RECEPTACLES; NEMA 5-20R DUPLEX; MOUNT IN 2-GANG BOX; 18" O.C. A.F.F. OR AS NOTED SPECIAL POWER OUTLET; NEMA DESIGNATION AS SHOWN ON PLANS; MOUNT IN 2-GANG BOX; 18" O.C. A.F.F. OR AS NOTED VOICE/DATA OUTLET; 18" O.C. A.F.F. OR AS NOTED; 1-GANG BOX WITH 3/4" EMT TO ACCESSIBLE AREA ABOVE GRID CEILING EXISTING VOICE/DATA OUTLET TO BE REMOVED CR CARD READER; 48" O.C. A.F.F.; 2-GANG BOX WITH 1" EMT TO ACCESSIBLE AREA ABOVE GRID CEILING TV T THERMOSTAT; EC TO PROVIDE SINGLE GANG BOX WITH 1/2" EMT TO ACCESSIBLE AREA ABOVE GRID CEILING EXISTING TO BE REPLACED EXISTING TO BE REMOVED E R EXISTING RELOCATED AS SHOWN RL RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED 18" O.C. A.F.F. OR AS NOTED; GFCI; NON FEED THRU; WEATHERPROOF COVER. W RECEPTACLE; NEMA 5-20R DUPLEX; CONCEALED BEHIND WATER COOLER ENCLOSURE; COORDINATE LOCATION WITH WC SHOP DRAWINGS. WC F FLOOR BOX WITH (2) DUPLEX RECEPTACLES AND (4) RJ45 DATA JACKS TV RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED 60" O.C. A.F.F.; FOR FLAT SCREEN TV TELEVISION OUTLET; MOUNTED 60" O.C. A.F.F. OR AS NOTED; 1-GANG BOX WITH 3/4" EMT TO ACCESSIBLE AREA ABOVE CEILING FIRE ALARM CONTROL PANEL FIRE ALARM MANUAL PULL STATION; MOUNTED 48" O.C. A.F.F. FIRE ALARM STROBE; MOUNTED 80" O.C. A.F.F. FIRE ALARM HORN & STROBE; MOUNTED 80" O.C. A.F.F. SMOKE DETECTOR; CEILING MOUNTED FIRE ALARM HORN & STROBE; WEATHERPROOF; MOUNTED 80" O.C. A.F.F. SPRINKLER FLOW SWITCH; EXISTING SWITCH WIRED TO FIRE ALARM SYSTEM BY EC SPRINKLER TAMPER SWITCH; EXISTING SWITCH WIRED TO FIRE ALARM SYSTEM BY EC W DUCT MOUNTED SMOKE DETECTOR; FURNISHED BY EC AND INSTALLED BY MC. FIRE ALARM ANNUNCIATOR PANEL. HEAT DETECTOR; CEILING MOUNTED SMOKE DETECTOR; CEILING MOUNTED; FOR ELEVATOR RECALL EL D FACP FAAP F S FS TS S S S S S H LIGHT SWITCH; 20A, 120/277V, MOUNTED IN EXISTING RECESSED BOX; PROVIDE NEW WALL PLATE RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED IN EXISTING RECESSED BOX; PROVIDE NEW WALL PLATE VOICE/DATA OUTLET; MOUNTED IN EXISTING RECESSED BOX FIRE ALARM MANUAL PULL STATION; MOUNTED IN EXISTING RECESSED BOX F E FIRE ALARM HORN & STROBE; MOUNTED IN EXISTING RECESSED BOX S E ENCLOSED CIRCUIT BREAKER; 240V, 90A, 3-POLE, SHUNT TRIP, NEMA 1 ENCLOSURE; PROVIDE AUXILIARY CONTACTS REQUIRED FOR ELEVATOR CONTROL CB ABBREVIATIONS ABOVE GRID CEILING AGC COOLING TOWER CT EXHAUST FAN EF FAN COIL UNIT FC ELECTRIC HEATER EH AIR CONDITIONING CONDENSING UNIT CU ON CENTER OC ROOF TOP UNIT RTU NOTE: ALL ABBREVIATIONS MAY NOT BE REPRESENTED ON PLANS. WATER SOURCE HEAT PUMP WSHP MOTORIZED DAMPER MD WATER HEATER WH ABOVE FINISHED FLOOR AFF SANITARY PUMP SP SPLIT SYSTEM INDOOR UNIT SSI SPLIT SYSTEM OUTDOOR UNIT SSO NF 2 240 30 B NEMA 1 NF 2 240 30 A DISCONNECT SCHEDULE MARK AMP RATING VOLTS POLES FUSE ENCLOSURE NEMA 3R NF 2 240 60 D NEMA 3R NF 3 30 C NEMA 3R NF 3 F NEMA 1 NF 3 E NEMA 3R 60 60 240 240 240 NF 3 G 100 240 NEMA 1 NF 2 240 200 H NEMA 3R Owner / Client: Project Number Date: Drawing Title: Scale: Drawing Number: © Desmone Architects 2015 Revisions: Seal: For O N E D O U G H B O Y S Q U A R E 3 4 0 0 B U T L E R S T R E E T P I T T S B U R G H, P A 1 5 2 0 1 T E L : 4 1 2. 6 8 3. 3 2 3 0 F A X : 4 1 2. 6 8 3. 3 5 6 3 w w w . d e s m o n e . c o m 1/8" = 1'-0" Z:\MEP CURRENT PROJECTS\Desmone Architects - Jobs\DESMONE-MEP15-03 - Morgantown Enterprise Center- Phase II\Revit & CAD\Electrical - Details - 2014.rvt E-100 Electrical Legends & Notes Monongalia County Development Authority Morgantown Enterprise Center Office Building 3942 08.26.2015 955 H artman Run Road Morga ntown, WV 26505 Interior & Exterior Renovations 08.26.2015 LIGHTING FIXTURE SCHEDULE NOTES 1. EQUAL LIGHT FIXTURES MANUFACTURED BY ACUITY BRANDS, COOPER LIGHTING, DAYBRITE, AND HUBBELL LIGHTING SHALL BE ACCEPTABLE. OTHER MANUFACTURERS MUST FOLLOW THE GUIDELINES IN ACCORDANCE WITH THE PRODUCT SUBSTITUTION SECTION OF THE SPECIFICATIONS FOR APPROVAL BEFORE BID DATE. ENGINEER SHALL HAVE FINAL APPROVAL OF ALL LIGHT FIXTURE SUBSTITUTIONS. 2. MOUNTING HEIGHT SHALL BE MEASURED FROM THE FINISHED FLOOR LEVEL TO THE BOTTOM OF THE FIXTURE. 3. PROVIDE BATTERY TO SUPPLY EMERGENCY LIGHTING FOR 90 MINUTES AS REQUIRED BY NFPA 101 - LIFE SAFETY CODE. 4. PROVIDE INTEGRAL BUTTON-TYPE PHOTOELECTRIC CONTROLLER. 5. LED DRIVER CAPABLE OF DIMMING USING 0-10V DIMMER SWITCH. GENERAL ELECTRICAL NOTES 25. LAMPS AND LIGHTING FIXTURES SHALL BE AS DESCRIBED IN LIGHT FIXTURE SCHEDULE ON THE DRAWINGS. PROVIDE LAMPS IN ALL LIGHT FIXTURES. 26. ALL LINEAR FLUORESCENT LAMPS SHALL BE T-8, LOW-MERCURY BASED ON TCLP TESTING, A COLOR TEMPERATURE OF 3500°K, AND A COLOR RENDERING INDEX (CRI) OF 82, AS MANUFACTURED BY PHILIPS, GE, OR OSCRAM SYLVANIA. 27. ALL LINEAR FLUORESCENT LIGHT FIXTURES SHALL HAVE ELECTRONIC BALLASTS AS MANUFACTURED BY ADVANCE, UNIVERSAL, OR OSCRAM SYLVANIA. COMPACT FLUORESCENT BALLASTS SHALL BE ELECTRONIC AS MANUFACTURED BY ADVANCE, MAGNETEK, OR OSCRAM SYLVANIA. 28. LABEL EACH PANELBOARD, DISCONNECT SWITCH AND ENDS OF WIRING AND CABLES AS SPECIFIED. 29. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS. 30. GIVE RIGHT-OF-WAY TO SYSTEMS REQUIRED TO BE INSTALLED AT A REQUIRED SLOPE. 31. FURNISH AND INSTALL ANY MISCELLANEOUS METAL OR WOOD SUPPORTS, FASTENERS, MOUNTS HANGERS, SIDE BRACES, ETC., WHICH MAY BE REQUIRED TO SECURELY ANCHOR AND SUPPORT ELECTRICAL EQUIPMENT FURNISHED UNDER THIS CONTRACT. 32. APPLY FIRESTOPPING TO RACEWAY PENETRATIONS OF FIRE-RATED FLOOR AND WALL ASSEMBLIES TO ACHIEVE FIRE-RESISTANCE RATING OF THE ASSEMBLY. 33. MAKE PROVISION AND PROVIDE POWER WIRING INCLUDING FINAL EQUIPMENT CONNECTION TO ALL EQUIPMENT FURNISHED AND INSTALLED BY OTHERS. VERIFY THE EXACT REQUIREMENT OF EQUIPMENT BEFORE INSTALLATION OF ELECTRICAL WORK. 34. ALL REQUIRED BUILDING PERMITS FOR THE ELECTRICAL PORTION OF THE WORK SHALL BE INCLUDED. A FINAL INSPECTION BY THE OWNER, ARCHITECT, ENGINEER, AND ALL INVOLVED AGENCIES WILL BE CONDUCTED UPON COMPLETION OF THE WORK TO DETERMINE ACCEPTABILITY OF THE WORK. IN ADDITION, AN INSPECTION BY THE ELECTRICAL INSPECTOR AND CERTIFICATE OF APPROVAL WILL BE REQUIRED PRIOR TO FINAL PAYMENT FOR THE WORK. ALL FEES FOR BUILDING PERMITS AND ELECTRICAL INSPECTIONS SHALL BE INCLUDED. 35. TESTING: ON COMPLETION OF THE WORK, THE INSTALLATION SHALL BE FREE FROM GROUNDS AND SHORT CIRCUITS. ALL CIRCUITS SHALL BE TESTED AND LABELED. ALL MOTOR CIRCUITS, CONTROL CIRCUITS, SIGNAL SYSTEMS, INTERLOCKING AND ELECTRIC HEAT CIRCUITS SHALL BE TESTED FOR PROPER OPERATION. 36. GUARANTEE: THE CONTRACTOR SHALL GIVE THE OWNER A WRITTEN GUARANTEE THAT HE WILL MAKE GOOD, AT HIS OWN EXPENSE, ANY DEFECTS IN MATERIALS OR WORKMANSHIP WHICH MAY DEVELOP IN ONE YEAR FROM THE FINAL ACCEPTANCE OF THE WORK. GENERAL ELECTRICAL NOTES 17. BEFORE INSTALLING OUTLETS, THE ELECTRICAL CONTRACTOR SHALL CONFER WITH THE ARCHITECT TO DETERMINE IF THE OUTLETS ARE TO BE INSTALLED AT HEIGHTS OTHER THAN THOSE GIVEN HEREIN. IN GENERAL, UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL THE OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHT FROM THE FLOOR: A.SWITCHES: 48" O.C. B. RECEPTACLE OUTLETS: 18" O.C. C.VOICE/DATA OUTLETS: 18" O.C. D. WALL MOUNTED TELEPHONE OUTLETS: 54" O.C. RECEPTACLE OUTLETS AT COUNTERTOPS: 6" O.C. ABOVE BACKSPLASH. 18. A TYPEWRITTEN LABEL SHALL BE INSTALLED ON THE WALL PLATE OF EACH RECEPTACLE OUTLET INDICATING THE CONNECTED PANEL AND CIRCUIT NUMBER. 19. ALL GROUNDING SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC AND AS REQUIRED BY THE DRAWINGS. 20. PANELBOARDS SHALL BE DEAD FRONT WITH RATINGS AS SCHEDULED ON DRAWINGS. PROVIDE CIRCUIT BREAKERS AS RECOMMENDED BY PANEL MANUFACTURER. PROVIDE BRANCH BREAKERS IN QUANTITIES AND RATINGS AS INDICATED ON DRAWINGS. PROVIDE TYPED DIRECTORIES REFLECTING CONNECTED LOADS. 21. BRANCH CIRCUIT BREAKERS SHALL BE OF INDIVIDUAL UNIT CONSTRUCTION COMPLETE WITH QUICK-MAKE, QUICK-BREAK MECHANISM; THERMAL MAGNETIC TRIP; AMBIENT COMPENSATION; AND SHALL BE INTERCHANGEABLE IN THE PANELBOARD ASSEMBLY IN RATINGS FROM 15 TO 100 AMPERES WITHOUT NECESSITATING BUS, LINK OR ASSEMBLY REARRANGEMENT. CIRCUIT BREAKERS SHALL HAVE SUITABLE SCREW TYPE LINE TERMINALS SO THAT THEY WILL BE HELD IN POSITIVE CONTACT WITH THEIR RESPECTIVE LINKS OR BUSSES. 22. SAFETY SWITCHES SHALL BE HEAVY DUTY, QUICK-MAKE, QUICK-BREAK, TYPES OF THE SIZE AND FUSE AMPACITY AS NOTED ON THE DRAWINGS. PROVIDE GROUND BUS, SOLID NEUTRAL, CLASS RK-5 DUAL ELEMENT, TIME DELAY FUSES, AND NEMA RELATED ENCLOSURE. 23. MOTOR STARTERS FOR THREE PHASE MOTORS SHALL BE FULL VOLTAGE NON-REVERSING MAGNETIC TYPES WITH PROPERLY SIZED OVERLOAD HEATERS, LONG LIFE PILOT LIGHTS, HAND-OFF-AUTO SELECTOR SWITCH, PUSHBUTTONS, AND 120V CONTROL TRANSFORMER. MANUAL MOTOR STARTERS FOR SINGLE PHASE MOTORS SHALL BE SENTINEL TYPE WITH PROPERLY SIZED OVERLOAD HEATERS AND TOGGLE TYPE DISCONNECT SWITCH MOUNTED IN A NEMA RATED ENCLOSURE. 24. EACH PANELBOARD, DISCONNECT SWITCH, MOTOR STARTER AND CABINET SHALL BE IDENTIFIED BY PHENOLIC LAMINATED PLASTIC ENGRAVED PLATES ATTACHED WITH POP RIVETS OR SHEET METAL SCREWS. GENERAL ELECTRICAL NOTES 10. ALL CONDUIT AND EQUIPMENT SHALL BE LEVEL, PLUMB, AND PARALLEL AND PERPENDICULAR TO OTHER BUILDING SYSTEMS AND COMPONENTS, UNLESS OTHERWISE NOTED. 11. CONDUIT AND CABLES SHALL BE INSTALLED AT LEAST 6" AWAY FROM PARALLEL RUNS OF FLUES AND HOT-WATER PIPES. LOCATE HORIZONTAL CONDUIT AND CABLE RUNS ABOVE WATER PIPING. 12. PROVIDE PULL WIRES IN ALL EMPTY CONDUITS. USE NO. 14 AWG ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN 200-LB TENSILE STRENGTH. LEAVE AT LEAST 12" OF SLACK AT EACH END OF THE PULL WIRE. 13. OUTLET AND JUNCTION BOXES SHALL BE 4" SQUARE MINIMUM SIZE, GALVANIZED, STAMPED STEEL, EXCEPT AS NOTED. OUTLET BOXES SHALL BE EQUIPPED WITH PLASTER RINGS OF APPROPRIATE DEPTH TO FINISH FLUSH WITH FINISHED WALL. MULTIGANG BOXES SHALL BE OF SINGLE PIECE CONSTRUCTION WITH WALL PLATES MATCHING RESPECTIVE DEVICE. OUTLET BOXES IN CONCRETE OR MASONRY WALLS SHALL BE MASONRY TYPE. OUTLET BOXES FOR EXPOSED EXTERIOR WALLS SHALL BE WEATHERPROOF WITH THREADED CONDUIT HUBS. JUNCTION AND PULL BOXES SHALL HAVE STEEL, SCREW-TYPE COVER PLATES. 14. WIRES AND CABLES SHALL BE COPPER CONDUCTORS AND HAVE APPROVED INSULATION FOR THE SPACES WHERE THEY ARE TO BE USED AND SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NEC. THE MINIMUM TEMPERATURE RATING SHALL BE 75°C WITH TYPE THHN/THWN INSULATION AND 600 VOLT RATING. 15. NO WIRE SMALLER THAN #12 SHALL BE USED FOR LIGHTING, RECEPTACLES, AND MOTOR CIRCUITS. ALL WIRE #10 AND SMALLER MAY BE SOLID OR STRANDED CONDUCTOR. FOR SIZE #8 AND LARGER STRANDED CABLE SHALL BE USED. ALL WIRES SHALL BE INSTALLED IN CONDUIT UNLESS OTHERWISE NOTED. ALL SPLICES SHALL BE MADE WITH INSULATED SOLDERLESS TYPE CONNECTORS. WIRING INSTALLATION SHALL COMPLY WITH NEC 310.15(B)(3)(a). ALL FEEDER AND BRANCH CIRCUIT CONDUCTOR AMPACITIES SHALL BE PROPERLY INCREASED FOR VOLTAGE DROP IN ACCORDANCE WITH THE NEC. 16. WIRING DEVICES SHALL BE THREE-WIRE, SPECIFICATION GRADE, 20 AMPERE MINIMUM; DUAL VOLTAGE SWITCHES, DUPLEX RECEPTACLES, AND GROUND-FAULT CIRCUIT INTERRUPTING RECEPTACLES. PROVIDE IVORY NYLON WALL PLATES FOR FINISHED AREAS. PROVIDE GASKETED WEATHERPROOF WALL PLATES FOR EXTERIOR AREAS. WALL PLATES SHALL BE INSTALLED ON ALL SWITCHES, RECEPTACLES, VOICE/DATA OUTLETS, TV OUTLETS, AND EMPTY BOXES. DUPLEX RECEPTACLES SHALL BE HUBBELL #5362; SINGLE POLE SWITCHES SHALL BE HUBBELL #1221; THREE-WAY SWITCHES SHALL BE HUBBELL #1223; FOUR-WAY SWITCHES SHALL BE HUBBELL #1224 OR ENGINEER APPROVED EQUAL. GENERAL ELECTRICAL NOTES 1. SCOPE: FURNISH ALL LABOR AND MATERIALS AND INSTALL ALL EQUIPMENT; INCLUDING, BUT NOT LIMITED TO WIRING, CONDUIT, ELECTRICAL DISTRIBUTION EQUIPMENT, LIGHTING, AND MISCELLANEOUS EQUIPMENT DETAILED ON THE DRAWINGS OR REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION. 2. ALL ELECTRICAL WORK SHALL BE COMPLIANT WITH THE STATE ADOPTED EDITION OF NFPA 70: NATIONAL ELECTRICAL CODE (NEC) AND OTHER APPLICABLE STATE AND LOCAL CODES. 3. COORDINATE ELECTRICAL SERVICE ENTRANCE WORK WITH MON POWER COMPANY. ELECTRICAL SERVICE WORK SHALL COMPLY WITH MON POWER SPECIFICATIONS. 4. ALL MATERIAL SHALL BE NEW AND SHALL BE LISTED BY UNDERWRITERS LABORATORIES. 5. CONDUITS SHALL BE 1/2" MINIMUM SIZE, RIGID GALVANIZED STEEL, INTERMEDIATE METAL CONDUIT, LIQUID-TIGHT FLEXIBLE CONDUIT, ELECTRICAL METALLIC TUBING, FLEXIBLE METAL CONDUIT. CONDUITS SHALL BE SIZED AND APPLIED IN ACCORDANCE WITH THE NEC. CONDUIT FITTINGS SHALL BE ALL PLATED STEEL: SET-SCREW, THREADED OR COMPRESSION TYPE. METAL CLAD CABLE SHALL BE PERMITTED FOR INSTALLATION. 6. ALL WIRING SHALL BE INSTALLED IN CONDUIT. BRANCH CIRCUIT WIRING SHALL BE MC CABLE AS PERMITTED BY THE NEC. IN GENERAL, CONCEAL CONDUIT IN WALLS AND ABOVE CEILNGS. MC CABLE SHALL BE USED WHERE OUTLETS ARE INSTALLED THROUGH CONTINUOUS METAL STUD WALLS. IN UNFINISHED AREAS OF THE BUILDING, CONDUIT SHALL BE EXPOSED AND ROUTED ON SURFACE OF THE CEILING AND/OR WALLS AS HIGH AS POSSIBLE AND ROUTED SO AS TO NOT INTERFERE WITH OTHER TRADES. CONDUIT AND CABLES SHALL BE SECURED WITH APPROVED SUPPORTING DEVICES AND RUN PARALLEL AND PERPENDICULAR TO SURROUNDING STRUCTURE. 7. CONDUITS INSTALLED UNDERGROUND SHALL BE A MINIMUM OF 18" BELOW FINISHED GRADE TO THE TOP OF THE CONDUIT, UNLESS OTHERWISE NOTED. PROVIDE ROCK-FREE BACKFILL MATERIAL AND TAMP IN 8" LAYERS. PROVIDE UNDERGROUND WARNING TAPE IN TRENCH 3" BELOW FINISHED GRADE. 8. RGS CONDUIT SHALL BE USED IN ALL AREAS SUBJECTED TO PHYSICAL DAMAGE. EMT MAY BE INSTALLED ONLY IN CONCEALED INTERIOR SPACES ABOVE CEILINGS OR IN WALLS. OUTDOOR WIRING ABOVE GRADE SHALL BE ENCLOSED IN RGS CONDUIT. OUTDOOR WIRING BELOW GRADE SHALL BE ENCLOSED IN SCHEDULE 40 PVC CONDUIT UNLESS OTHERWISE NOTED. 9. CONNECT MOTORS AND EQUIPMENT SUBJECT TO VIBRATION, NOISE TRANSMISSION OR MOVEMENT WITH A MAXIMUM OF 72" FLEXIBLE CONDUIT. PROVIDE LIQUID-TIGHT FLEXIBLE CONDUIT IN WET OR DAMP LOCATIONS. INSTALL SEPARATE GROUND CONDUCTOR ACROSS FLEXIBLE CONNECTIONS.
Transcript
Page 1: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

LIGHTING FIXTURE SCHEDULE

MOUNTINGTYPE MFR. CATALOG NO.DESCRIPTION LAMPS WATTSSYMBOL VOLTS NOTES

B

(2)

A 2'X2' LED TROFFER WITH DIMMING DRIVERCEILING

RECESSED120

CEILINGRECESSED

AECEILING

RECESSED

XEXIT LIGHT; SHADED AREA INDICATES EXITFACE; ARROW INDICATES DIRECTION OFEGRESS

120CEILING ORWALL 7'-0"

XREXIT LIGHT; SHADED AREA INDICATES EXITFACE; REMOTE CAPACITY

120

D

BECEILING

RECESSED

4' LED NARROW WRAPAROUNDCEILING

SURFACEK

EE 4' LED WIDE WRAPAROUND SURFACE

120

120

120

120

120

120

FE SURFACE 120

G 2' FLUORESCENT VANITY WALL BRACKETWALL6'-6"

DE 120SAME AS FIXTURE TYPE 'D', EXCEPTFIXTURE TO HAVE EMERGENCY BATTERYBACKUP

V EXTERIOR LED SCONCEWALL5'-0"

W EXTERIOR LED WALL PACK

120

120

120WALL10'-0"

6" OPEN REFLECTOR LED DOWNLIGHT WITHDIMMING DRIVER

35CEILING

RECESSED

35CEILING

RECESSED

40

40

1LED

4LED

LQM S W 3 R 120/277 ELN

LHQM S W 3 R HO RO

WL4 25L D24 LP835 NX 24

KENALL

OLW 23

FS824T-2TB-PIABR-27L40K-1-DV

30

35

SAME AS FIXTURE TYPE 'A', EXCEPTFIXTURE TO HAVE EMERGENCY BATTERYBACKUP

SAME AS FIXTURE TYPE 'B', EXCEPTFIXTURE TO HAVE EMERGENCY BATTERYBACKUP

SAME AS FIXTURE TYPE 'E', EXCEPTFIXTURE TO HAVE EMERGENCY BATTERYBACKUP

METALUX22EN-LD1-34-UNV

L835-CD13400 LM

3500K LED35

55

55

(3)

(4)

R

H

ELA DDB OMC H1006 1-H1006 MR11 6 10EXTERIOR REMOTE EMERGENCY LIGHT LITHONIAWALL7'-0"

NARROW LINEAR LED PENDANT WITHDIMMING DRIVER

PENDANT8'-0"

120

(5)

(3) (5)

40

(5)5400 LM

3500K LED2'X4' LED TROFFER WITH DIMMING DRIVER

5400 LM3500K LED

LITHONIA2500 LM

3500K LED

LITHONIA

LITHONIA

STL4 48L D50 LP835 NX4800 LM

3500K LED

STL4 48L D50 LP835 NXEL14L

4800 LM3500K LED

GOTHAM

GOTHAM

EVO 35/22 6AR MVOLTTRW

2200 LM3500K LED

EVO 35/22 6AR MVOLTTRW ELR

2200 LM3500K LED

2700 LM4000K LED

LITHONIA

LITHONIACEILING ORWALL 7'-0"

LITHONIA2700 LM

5000K LED

METALUX22EN-LD1-34-UNVEL10W-L835-CD1

3400 LM3500K LED

35

METALUX24EN-LD1-54-UNV

L835-CD1

CCEILING

RECESSED120 35 (5)

4000 LM3500K LED

2'X4' LED TROFFER WITH DIMMING DRIVER LITHONIA2TL4 40L FW A12

EZ1 LP835

TECHLIGHTING

700BCSLC26W-C-CF 2-24W T5/835 55

TECHLIGHTING

700LSVAN-W-S-LED8302400 LM

3000K LED

METALUX24EN-LD1-54-UNVEL10W-L835-CD1

(3) (5)

(3) (5)

(5)

(3)

(3)

(3)

(1)

(5)

ELECTRICAL SYMBOL LEGEND

DESCRIPTION

WIRING AND RACEWAY CONCEALED IN WALLS AND/OR ABOVE CEILING, UNLESS NOTEDOTHERWISE

SYMBOL

NOTE: ALL SYMBOLS MAY NOT BE REPRESENTED ON PLANS.

J

3

4

a

D

E

A-2HOMERUN; TEXT INDICATES PANEL DESIGNATION AND CIRCUIT NUMBER

UNSWITCHED PHASE CONDUCTOR TOWARDS HOME RUN TO DISTINQUISH LIGHTING CONTROL

JUNCTION BOX PER N.E.C.

SINGLE POLE SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F.

INDICATES CONDUIT STUBBED INTO SPACE; PROVIDE CONDUIT BUSHING

THREE-WAY SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F.

FOUR-WAY SWITCH; 20A, 120/277V, MOUNT AT 48" O.C. A.F.F.

LIGHT SWITCH; LOWER CASE LETTER DENOTES LIGHT FIXTURE BEING CONTROLLED

DIMMER SWITCH; 1500W, LOW VOLTAGE, MOUNT AT 48" O.C. A.F.F.

WIRING AND RACEWAY CONCEALED IN/OR UNDER FLOOR OR UNDERGROUND

OS

F

M

OS

R

G

E

C

GC

R

RECEPTACLE; NEMA 5-20R DUPLEX; 18" O.C. A.F.F. OR AS NOTED

RECEPTACLE; NEMA 5-20R DUPLEX; 18" O.C. A.F.F. OR AS NOTED; GFCI; NON FEED THRU

FAN CONTROL SWITCH; 120/277V, MOUNT AT 48" O.C. A.F.F.

MANUAL MOTOR STARTER SWITCH; 20A, 1 HP, 120/277V, MOUNT AT 48" O.C. A.F.F.

OCCUPANCY SENSOR WALL SWITCH; DUAL TECH.; MANUAL ON, AUTO OFF; (2) RELAYS FORCONTROL OF (2) LOADS; 1200W, LOW VOLTAGE, MOUNT AT 48" O.C. A.F.F.

EXISTING SWITCH TO BE REMOVED

RECEPTACLE; NEMA 5-20R DUPLEX; 44" O.C. A.F.F.

RECEPTACLE; NEMA 5-20R DUPLEX; 44" O.C. A.F.F.; GFCI; NON FEED THRU

EXISTING RECEPTACLE TO BE REMOVED

OCCUPANCY SENSOR; CEILING MOUNTED, DUAL TECHNOLOGY; LOW VOLTAGE

R

E

INDICATES ELECTRICAL CONNECTION BY ELECTRICAL CONTRACTOR TO EQUIPMENTPROVIDED AND INSTALLED BY OTHERS.

SAFETY DISCONNECT SWITCH; SEE DISCONNECT SCHEDULE FOR RATINGS

SURFACE MOUNTED DISTRIBUTION PANEL; SEE RESPECTIVE PANEL SCHEDULE

FLUSH MOUNTED DISTRIBUTION PANEL; SEE RESPECTIVE PANEL SCHEDULE

(2) RECEPTACLES; NEMA 5-20R DUPLEX; MOUNT IN 2-GANG BOX; 18" O.C. A.F.F. OR AS NOTED

SPECIAL POWER OUTLET; NEMA DESIGNATION AS SHOWN ON PLANS; MOUNT IN 2-GANG BOX;18" O.C. A.F.F. OR AS NOTED

VOICE/DATA OUTLET; 18" O.C. A.F.F. OR AS NOTED; 1-GANG BOX WITH 3/4" EMT TO ACCESSIBLEAREA ABOVE GRID CEILING

EXISTING VOICE/DATA OUTLET TO BE REMOVED

CRCARD READER; 48" O.C. A.F.F.; 2-GANG BOX WITH 1" EMT TO ACCESSIBLE AREA ABOVE GRIDCEILING

TV

TTHERMOSTAT; EC TO PROVIDE SINGLE GANG BOX WITH 1/2" EMT TO ACCESSIBLE AREA ABOVEGRID CEILING

EXISTING TO BE REPLACED

EXISTING TO BE REMOVED

E

R

EXISTING RELOCATED AS SHOWNRL

RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED 18" O.C. A.F.F. OR AS NOTED; GFCI; NON FEEDTHRU; WEATHERPROOF COVER.

W

RECEPTACLE; NEMA 5-20R DUPLEX; CONCEALED BEHIND WATER COOLER ENCLOSURE;COORDINATE LOCATION WITH WC SHOP DRAWINGS.

WC

F FLOOR BOX WITH (2) DUPLEX RECEPTACLES AND (4) RJ45 DATA JACKS

TV RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED 60" O.C. A.F.F.; FOR FLAT SCREEN TV

TELEVISION OUTLET; MOUNTED 60" O.C. A.F.F. OR AS NOTED; 1-GANG BOX WITH 3/4" EMT TOACCESSIBLE AREA ABOVE CEILING

FIRE ALARM CONTROL PANEL

FIRE ALARM MANUAL PULL STATION; MOUNTED 48" O.C. A.F.F.

FIRE ALARM STROBE; MOUNTED 80" O.C. A.F.F.

FIRE ALARM HORN & STROBE; MOUNTED 80" O.C. A.F.F.

SMOKE DETECTOR; CEILING MOUNTED

FIRE ALARM HORN & STROBE; WEATHERPROOF; MOUNTED 80" O.C. A.F.F.

SPRINKLER FLOW SWITCH; EXISTING SWITCH WIRED TO FIRE ALARM SYSTEM BY EC

SPRINKLER TAMPER SWITCH; EXISTING SWITCH WIRED TO FIRE ALARM SYSTEM BY EC

W

DUCT MOUNTED SMOKE DETECTOR; FURNISHED BY EC AND INSTALLED BY MC.

FIRE ALARM ANNUNCIATOR PANEL.

HEAT DETECTOR; CEILING MOUNTED

SMOKE DETECTOR; CEILING MOUNTED; FOR ELEVATOR RECALLEL

D

FACP

FAAP

F

S

FS

TS

S

S

S

S

S

H

LIGHT SWITCH; 20A, 120/277V, MOUNTED IN EXISTING RECESSED BOX; PROVIDE NEW WALL PLATE

RECEPTACLE; NEMA 5-20R DUPLEX; MOUNTED IN EXISTING RECESSED BOX; PROVIDE NEWWALL PLATE

VOICE/DATA OUTLET; MOUNTED IN EXISTING RECESSED BOX

FIRE ALARM MANUAL PULL STATION; MOUNTED IN EXISTING RECESSED BOXF E

FIRE ALARM HORN & STROBE; MOUNTED IN EXISTING RECESSED BOXS E

ENCLOSED CIRCUIT BREAKER; 240V, 90A, 3-POLE, SHUNT TRIP, NEMA 1 ENCLOSURE;PROVIDE AUXILIARY CONTACTS REQUIRED FOR ELEVATOR CONTROL

CB

ABBREVIATIONS

ABOVE GRID CEILINGAGC

COOLING TOWERCT

EXHAUST FANEF

FAN COIL UNITFC

ELECTRIC HEATEREH

AIR CONDITIONING CONDENSING UNITCU

ON CENTEROC

ROOF TOP UNITRTU

NOTE: ALL ABBREVIATIONS MAY NOT BE REPRESENTEDON PLANS.

WATER SOURCE HEAT PUMPWSHP

MOTORIZED DAMPERMD

WATER HEATERWH

ABOVE FINISHED FLOORAFF

SANITARY PUMPSP

SPLIT SYSTEM INDOOR UNITSSI

SPLIT SYSTEM OUTDOOR UNITSSO

NF224030B

NEMA 1NF224030A

DISCONNECT SCHEDULE

MARK AMP RATING VOLTS POLES FUSE ENCLOSURE

NEMA 3R

NF224060D

NEMA 3RNF330C

NEMA 3R

NF3F

NEMA 1NF3E

NEMA 3R

60

60

240

240

240

NF3G 100 240 NEMA 1

NF2240200H NEMA 3R

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

1/8" = 1'-0"

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\Ele

ctr

ical -

Deta

ils -

2014.r

vt

E-100

Electrical Legends& Notes

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

LIGHTING FIXTURE SCHEDULE NOTES1. EQUAL LIGHT FIXTURES MANUFACTURED BY ACUITY BRANDS,

COOPER LIGHTING, DAYBRITE, AND HUBBELL LIGHTING SHALLBE ACCEPTABLE. OTHER MANUFACTURERS MUST FOLLOWTHE GUIDELINES IN ACCORDANCE WITH THE PRODUCTSUBSTITUTION SECTION OF THE SPECIFICATIONS FORAPPROVAL BEFORE BID DATE. ENGINEER SHALL HAVE FINALAPPROVAL OF ALL LIGHT FIXTURE SUBSTITUTIONS.

2. MOUNTING HEIGHT SHALL BE MEASURED FROM THEFINISHED FLOOR LEVEL TO THE BOTTOM OF THE FIXTURE.

3. PROVIDE BATTERY TO SUPPLY EMERGENCY LIGHTING FOR 90MINUTES AS REQUIRED BY NFPA 101 - LIFE SAFETY CODE.

4. PROVIDE INTEGRAL BUTTON-TYPE PHOTOELECTRICCONTROLLER.

5. LED DRIVER CAPABLE OF DIMMING USING 0-10V DIMMERSWITCH.

GENERAL ELECTRICAL NOTES25. LAMPS AND LIGHTING FIXTURES SHALL BE AS DESCRIBED IN

LIGHT FIXTURE SCHEDULE ON THE DRAWINGS. PROVIDELAMPS IN ALL LIGHT FIXTURES.

26. ALL LINEAR FLUORESCENT LAMPS SHALL BE T-8,LOW-MERCURY BASED ON TCLP TESTING, A COLORTEMPERATURE OF 3500°K, AND A COLOR RENDERING INDEX(CRI) OF 82, AS MANUFACTURED BY PHILIPS, GE, OR OSCRAMSYLVANIA.

27. ALL LINEAR FLUORESCENT LIGHT FIXTURES SHALL HAVEELECTRONIC BALLASTS AS MANUFACTURED BY ADVANCE,UNIVERSAL, OR OSCRAM SYLVANIA. COMPACTFLUORESCENT BALLASTS SHALL BE ELECTRONIC ASMANUFACTURED BY ADVANCE, MAGNETEK, OR OSCRAMSYLVANIA.

28. LABEL EACH PANELBOARD, DISCONNECT SWITCH AND ENDSOF WIRING AND CABLES AS SPECIFIED.

29. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS.

30. GIVE RIGHT-OF-WAY TO SYSTEMS REQUIRED TO BEINSTALLED AT A REQUIRED SLOPE.

31. FURNISH AND INSTALL ANY MISCELLANEOUS METAL ORWOOD SUPPORTS, FASTENERS, MOUNTS HANGERS, SIDEBRACES, ETC., WHICH MAY BE REQUIRED TO SECURELYANCHOR AND SUPPORT ELECTRICAL EQUIPMENT FURNISHEDUNDER THIS CONTRACT.

32. APPLY FIRESTOPPING TO RACEWAY PENETRATIONS OFFIRE-RATED FLOOR AND WALL ASSEMBLIES TO ACHIEVEFIRE-RESISTANCE RATING OF THE ASSEMBLY.

33. MAKE PROVISION AND PROVIDE POWER WIRING INCLUDINGFINAL EQUIPMENT CONNECTION TO ALL EQUIPMENTFURNISHED AND INSTALLED BY OTHERS. VERIFY THE EXACTREQUIREMENT OF EQUIPMENT BEFORE INSTALLATION OFELECTRICAL WORK.

34. ALL REQUIRED BUILDING PERMITS FOR THE ELECTRICALPORTION OF THE WORK SHALL BE INCLUDED. A FINALINSPECTION BY THE OWNER, ARCHITECT, ENGINEER, AND ALLINVOLVED AGENCIES WILL BE CONDUCTED UPONCOMPLETION OF THE WORK TO DETERMINE ACCEPTABILITYOF THE WORK. IN ADDITION, AN INSPECTION BY THEELECTRICAL INSPECTOR AND CERTIFICATE OF APPROVALWILL BE REQUIRED PRIOR TO FINAL PAYMENT FOR THEWORK. ALL FEES FOR BUILDING PERMITS AND ELECTRICALINSPECTIONS SHALL BE INCLUDED.

35. TESTING: ON COMPLETION OF THE WORK, THE INSTALLATIONSHALL BE FREE FROM GROUNDS AND SHORT CIRCUITS. ALLCIRCUITS SHALL BE TESTED AND LABELED. ALL MOTORCIRCUITS, CONTROL CIRCUITS, SIGNAL SYSTEMS,INTERLOCKING AND ELECTRIC HEAT CIRCUITS SHALL BETESTED FOR PROPER OPERATION.

36. GUARANTEE: THE CONTRACTOR SHALL GIVE THE OWNER AWRITTEN GUARANTEE THAT HE WILL MAKE GOOD, AT HISOWN EXPENSE, ANY DEFECTS IN MATERIALS ORWORKMANSHIP WHICH MAY DEVELOP IN ONE YEAR FROMTHE FINAL ACCEPTANCE OF THE WORK.

GENERAL ELECTRICAL NOTES17. BEFORE INSTALLING OUTLETS, THE ELECTRICAL

CONTRACTOR SHALL CONFER WITH THE ARCHITECT TODETERMINE IF THE OUTLETS ARE TO BE INSTALLED ATHEIGHTS OTHER THAN THOSE GIVEN HEREIN. IN GENERAL,UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL THEOUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTFROM THE FLOOR: A.SWITCHES: 48" O.C. B. RECEPTACLE

OUTLETS: 18" O.C. C.VOICE/DATA OUTLETS: 18" O.C. D. WALLMOUNTED TELEPHONE OUTLETS: 54" O.C. RECEPTACLEOUTLETS AT COUNTERTOPS: 6" O.C. ABOVE BACKSPLASH.

18. A TYPEWRITTEN LABEL SHALL BE INSTALLED ON THE WALLPLATE OF EACH RECEPTACLE OUTLET INDICATING THECONNECTED PANEL AND CIRCUIT NUMBER.

19. ALL GROUNDING SHALL BE IN ACCORDANCE WITH THEREQUIREMENTS OF THE NEC AND AS REQUIRED BY THEDRAWINGS.

20. PANELBOARDS SHALL BE DEAD FRONT WITH RATINGS ASSCHEDULED ON DRAWINGS. PROVIDE CIRCUIT BREAKERS ASRECOMMENDED BY PANEL MANUFACTURER. PROVIDEBRANCH BREAKERS IN QUANTITIES AND RATINGS ASINDICATED ON DRAWINGS. PROVIDE TYPED DIRECTORIESREFLECTING CONNECTED LOADS.

21. BRANCH CIRCUIT BREAKERS SHALL BE OF INDIVIDUAL UNITCONSTRUCTION COMPLETE WITH QUICK-MAKE, QUICK-BREAKMECHANISM; THERMAL MAGNETIC TRIP; AMBIENTCOMPENSATION; AND SHALL BE INTERCHANGEABLE IN THEPANELBOARD ASSEMBLY IN RATINGS FROM 15 TO 100AMPERES WITHOUT NECESSITATING BUS, LINK OR ASSEMBLYREARRANGEMENT. CIRCUIT BREAKERS SHALL HAVESUITABLE SCREW TYPE LINE TERMINALS SO THAT THEY WILLBE HELD IN POSITIVE CONTACT WITH THEIR RESPECTIVELINKS OR BUSSES.

22. SAFETY SWITCHES SHALL BE HEAVY DUTY, QUICK-MAKE,QUICK-BREAK, TYPES OF THE SIZE AND FUSE AMPACITY ASNOTED ON THE DRAWINGS. PROVIDE GROUND BUS, SOLIDNEUTRAL, CLASS RK-5 DUAL ELEMENT, TIME DELAY FUSES,AND NEMA RELATED ENCLOSURE.

23. MOTOR STARTERS FOR THREE PHASE MOTORS SHALL BEFULL VOLTAGE NON-REVERSING MAGNETIC TYPES WITHPROPERLY SIZED OVERLOAD HEATERS, LONG LIFE PILOTLIGHTS, HAND-OFF-AUTO SELECTOR SWITCH, PUSHBUTTONS,AND 120V CONTROL TRANSFORMER. MANUAL MOTORSTARTERS FOR SINGLE PHASE MOTORS SHALL BE SENTINELTYPE WITH PROPERLY SIZED OVERLOAD HEATERS ANDTOGGLE TYPE DISCONNECT SWITCH MOUNTED IN A NEMARATED ENCLOSURE.

24. EACH PANELBOARD, DISCONNECT SWITCH, MOTOR STARTERAND CABINET SHALL BE IDENTIFIED BY PHENOLIC LAMINATEDPLASTIC ENGRAVED PLATES ATTACHED WITH POP RIVETS ORSHEET METAL SCREWS.

GENERAL ELECTRICAL NOTES10. ALL CONDUIT AND EQUIPMENT SHALL BE LEVEL, PLUMB, AND

PARALLEL AND PERPENDICULAR TO OTHER BUILDINGSYSTEMS AND COMPONENTS, UNLESS OTHERWISE NOTED.

11. CONDUIT AND CABLES SHALL BE INSTALLED AT LEAST 6"AWAY FROM PARALLEL RUNS OF FLUES AND HOT-WATERPIPES. LOCATE HORIZONTAL CONDUIT AND CABLE RUNSABOVE WATER PIPING.

12. PROVIDE PULL WIRES IN ALL EMPTY CONDUITS. USE NO. 14AWG ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINEWITH NOT LESS THAN 200-LB TENSILE STRENGTH. LEAVE ATLEAST 12" OF SLACK AT EACH END OF THE PULL WIRE.

13. OUTLET AND JUNCTION BOXES SHALL BE 4" SQUAREMINIMUM SIZE, GALVANIZED, STAMPED STEEL, EXCEPT ASNOTED. OUTLET BOXES SHALL BE EQUIPPED WITH PLASTERRINGS OF APPROPRIATE DEPTH TO FINISH FLUSH WITHFINISHED WALL. MULTIGANG BOXES SHALL BE OF SINGLEPIECE CONSTRUCTION WITH WALL PLATES MATCHINGRESPECTIVE DEVICE. OUTLET BOXES IN CONCRETE ORMASONRY WALLS SHALL BE MASONRY TYPE. OUTLET BOXESFOR EXPOSED EXTERIOR WALLS SHALL BE WEATHERPROOFWITH THREADED CONDUIT HUBS. JUNCTION AND PULLBOXES SHALL HAVE STEEL, SCREW-TYPE COVER PLATES.

14. WIRES AND CABLES SHALL BE COPPER CONDUCTORS ANDHAVE APPROVED INSULATION FOR THE SPACES WHERE THEYARE TO BE USED AND SHALL CONFORM TO THE LATESTREQUIREMENTS OF THE NEC. THE MINIMUM TEMPERATURERATING SHALL BE 75°C WITH TYPE THHN/THWN INSULATIONAND 600 VOLT RATING.

15. NO WIRE SMALLER THAN #12 SHALL BE USED FOR LIGHTING,RECEPTACLES, AND MOTOR CIRCUITS. ALL WIRE #10 ANDSMALLER MAY BE SOLID OR STRANDED CONDUCTOR. FORSIZE #8 AND LARGER STRANDED CABLE SHALL BE USED. ALLWIRES SHALL BE INSTALLED IN CONDUIT UNLESS OTHERWISENOTED. ALL SPLICES SHALL BE MADE WITH INSULATEDSOLDERLESS TYPE CONNECTORS. WIRING INSTALLATIONSHALL COMPLY WITH NEC 310.15(B)(3)(a). ALL FEEDER ANDBRANCH CIRCUIT CONDUCTOR AMPACITIES SHALL BEPROPERLY INCREASED FOR VOLTAGE DROP IN ACCORDANCEWITH THE NEC.

16. WIRING DEVICES SHALL BE THREE-WIRE, SPECIFICATIONGRADE, 20 AMPERE MINIMUM; DUAL VOLTAGE SWITCHES,DUPLEX RECEPTACLES, AND GROUND-FAULT CIRCUITINTERRUPTING RECEPTACLES. PROVIDE IVORY NYLON WALLPLATES FOR FINISHED AREAS. PROVIDE GASKETEDWEATHERPROOF WALL PLATES FOR EXTERIOR AREAS. WALLPLATES SHALL BE INSTALLED ON ALL SWITCHES,RECEPTACLES, VOICE/DATA OUTLETS, TV OUTLETS, ANDEMPTY BOXES. DUPLEX RECEPTACLES SHALL BE HUBBELL#5362; SINGLE POLE SWITCHES SHALL BE HUBBELL #1221;THREE-WAY SWITCHES SHALL BE HUBBELL #1223; FOUR-WAYSWITCHES SHALL BE HUBBELL #1224 OR ENGINEERAPPROVED EQUAL.

GENERAL ELECTRICAL NOTES1. SCOPE: FURNISH ALL LABOR AND MATERIALS AND INSTALL

ALL EQUIPMENT; INCLUDING, BUT NOT LIMITED TO WIRING,CONDUIT, ELECTRICAL DISTRIBUTION EQUIPMENT, LIGHTING,AND MISCELLANEOUS EQUIPMENT DETAILED ON THEDRAWINGS OR REQUIRED FOR A COMPLETE AND OPERABLEINSTALLATION.

2. ALL ELECTRICAL WORK SHALL BE COMPLIANT WITH THESTATE ADOPTED EDITION OF NFPA 70: NATIONAL ELECTRICALCODE (NEC) AND OTHER APPLICABLE STATE AND LOCALCODES.

3. COORDINATE ELECTRICAL SERVICE ENTRANCE WORK WITHMON POWER COMPANY. ELECTRICAL SERVICE WORK SHALLCOMPLY WITH MON POWER SPECIFICATIONS.

4. ALL MATERIAL SHALL BE NEW AND SHALL BE LISTED BYUNDERWRITERS LABORATORIES.

5. CONDUITS SHALL BE 1/2" MINIMUM SIZE, RIGID GALVANIZEDSTEEL, INTERMEDIATE METAL CONDUIT, LIQUID-TIGHTFLEXIBLE CONDUIT, ELECTRICAL METALLIC TUBING, FLEXIBLEMETAL CONDUIT. CONDUITS SHALL BE SIZED AND APPLIED INACCORDANCE WITH THE NEC. CONDUIT FITTINGS SHALL BEALL PLATED STEEL: SET-SCREW, THREADED ORCOMPRESSION TYPE. METAL CLAD CABLE SHALL BEPERMITTED FOR INSTALLATION.

6. ALL WIRING SHALL BE INSTALLED IN CONDUIT. BRANCHCIRCUIT WIRING SHALL BE MC CABLE AS PERMITTED BY THENEC. IN GENERAL, CONCEAL CONDUIT IN WALLS AND ABOVECEILNGS. MC CABLE SHALL BE USED WHERE OUTLETS AREINSTALLED THROUGH CONTINUOUS METAL STUD WALLS. INUNFINISHED AREAS OF THE BUILDING, CONDUIT SHALL BEEXPOSED AND ROUTED ON SURFACE OF THE CEILINGAND/OR WALLS AS HIGH AS POSSIBLE AND ROUTED SO AS TONOT INTERFERE WITH OTHER TRADES. CONDUIT ANDCABLES SHALL BE SECURED WITH APPROVED SUPPORTINGDEVICES AND RUN PARALLEL AND PERPENDICULAR TOSURROUNDING STRUCTURE.

7. CONDUITS INSTALLED UNDERGROUND SHALL BE A MINIMUMOF 18" BELOW FINISHED GRADE TO THE TOP OF THECONDUIT, UNLESS OTHERWISE NOTED. PROVIDE ROCK-FREEBACKFILL MATERIAL AND TAMP IN 8" LAYERS. PROVIDEUNDERGROUND WARNING TAPE IN TRENCH 3" BELOWFINISHED GRADE.

8. RGS CONDUIT SHALL BE USED IN ALL AREAS SUBJECTED TOPHYSICAL DAMAGE. EMT MAY BE INSTALLED ONLY INCONCEALED INTERIOR SPACES ABOVE CEILINGS OR INWALLS. OUTDOOR WIRING ABOVE GRADE SHALL BEENCLOSED IN RGS CONDUIT. OUTDOOR WIRING BELOWGRADE SHALL BE ENCLOSED IN SCHEDULE 40 PVC CONDUITUNLESS OTHERWISE NOTED.

9. CONNECT MOTORS AND EQUIPMENT SUBJECT TO VIBRATION,NOISE TRANSMISSION OR MOVEMENT WITH A MAXIMUM OF72" FLEXIBLE CONDUIT. PROVIDE LIQUID-TIGHT FLEXIBLECONDUIT IN WET OR DAMP LOCATIONS. INSTALL SEPARATEGROUND CONDUCTOR ACROSS FLEXIBLE CONNECTIONS.

Page 2: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

UP

OS

OS

3 4

3

3

OS OS OS

OS OS

RE

F.

3

D DD

OS OSOS

33

D

InformationPamphlets

Mail

Copy/Print

AE

A

A

A

A

A

EEEE

A

FE

W

EE

XR

B B B

BBB

B

B

B

B

C

C

XAE

DE

DE

DD

D D

GG

X

DE

DE

D

D

D

D

D DD

D

R

Stairs

S2.0

Men'sRestroom

007

Women'sRestroom

009

Office

002

Office

001

MechanicalRoom

005

Corridor

000

Office

003

Storage

004

KK

K

V V

2

1

1 1

1

1 1 1

1

1

1 1

1

3 3

1

A AE

A

A

A

A AA

A A AAE

E EE

A

B

B B B

BB

AE

X XR

R

FE

EE

X

W

X

D D D

D

D D D

D

Stairs

S1.0

Kitchenette

012

Boardroom

010

2

1

1

111

1 1

E-200

1

E-200

2

KEY NOTES LIGHTING PLAN

1 CONNECT TO EXISTING BRANCH LIGHTING CIRCUIT INROOM/AREA USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT OFREMOVED LIGHT FIXTURE.

CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT USING (2) #12 CONDUCTORS AND (1) #12 EQUIPMENT GROUNDINGCONDUCTOR IN 1/2" CONDUIT.

2

3

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

E-200

Ground FloorLighting Plan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/4" = 1'-0"1

ENLARGED GROUND FLOOR LIGHTING PLAN - NORTH

1/4" = 1'-0"2

ENLARGED GROUND FLOOR LIGHTING PLAN - SOUTH 1/16" = 1'-0"3

GROUND FLOOR LIGHTING PLAN

GENERAL LIGHTING NOTES1. FIXTURES: SET LEVEL, PLUMB, AND SQUARE WITH CEILING

AND WALLS. SECURE ACCORDING TO MANUFACTURER'SWRITTEN INSTRUCTIONS AND APPROVED SUBMITTALMATERIALS. INSTALL LAMPS IN EACH FIXTURE.

2. CONNECT EXIT LIGHTS AND EMERGENCY BATTERY BALLASTSIN NOTED FIXTURES TO THE NEAREST UNSWITCHEDLIGHTING CIRCUIT IN THE AREA BEING SERVED.

3. EXTERIOR LIGHTING FIXTURES SHALL BE OPERATED BY ANEXISTING TIME CLOCK AND A PHOTOELECTRIC CONTROLLER.

4. PROVIDE LOW VOLTAGE WIRING FROM THE EXIT LIGHTS WITHEXTRA BATTERY CAPACITY TO THE REMOTE EMERGENCYLIGHTS INDICATED. LOW VOLTAGE WIRING SHALL BE ASRECOMMENDED BY THE EMERGENCY LIGHTING UNITMANUFACTURER.

5. SEE GENERAL ELECTRICAL NOTES ON SHEET E100 FORWIRING METHODS.

Page 3: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

DN

3

4

DD

OS OSOS

J

J

OS

OS

3

J

J

OS

OS

OS OS

OS

E

E

FE

EE

X

DE D D

B

B B

B B

B BEB

B B

C

BB

A

A

DE DE DED DD

K

G G

DDDE

DDD

D D D

H

H

H

H

H

H

H

H

H

H

X

1

1 1 1

1

1

1

1

11

1

1

1

111

1

SharedSuite

104

SharedSuite

105

SharedSuite

106

Stairs

S2.1

Corridor

119

Kitchenette

108

Storage

110

Server

110A

Storage

111

Elevator

E1.1

Women'sRestroom

109

Men'sRestroom

107

MeetingRoom

112

PhoneRoom

102

MeetingRoom

103

Co-WorkingOpenOffice

101

A

A

H

H

H

H

H

H

H

H

H

H

B

B B

B B

B

DEX

DEDEX

D D D D

FE

EE

1

111

1

1

1 1 1

PhoneRoom

114

MeetingRoom

115

DedicatedOpenOffice

113

Corridor

119

PrivateOffice

116

PrivateOffice

117

PrivateOffice

118

Stairs

S1.1

E-201

1

E-201

2

KEY NOTES LIGHTING PLAN

1 CONNECT TO EXISTING BRANCH LIGHTING CIRCUIT INROOM/AREA USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT OFREMOVED LIGHT FIXTURE.

CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT USING (2) #12 CONDUCTORS AND (1) #12 EQUIPMENT GROUNDINGCONDUCTOR IN 1/2" CONDUIT.

2

3

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

E-201

First Floor LightingPlan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/4" = 1'-0"1

ENLARGED FIRST FLOOR LIGHTING PLAN - NORTH

1/4" = 1'-0"2

ENLARGED FIRST FLOOR LIGHTING PLAN - SOUTH 1/16" = 1'-0"

3FIRST FLOOR POWER PLAN

GENERAL LIGHTING NOTES1. FIXTURES: SET LEVEL, PLUMB, AND SQUARE WITH CEILING

AND WALLS. SECURE ACCORDING TO MANUFACTURER'SWRITTEN INSTRUCTIONS AND APPROVED SUBMITTALMATERIALS. INSTALL LAMPS IN EACH FIXTURE.

2. CONNECT EXIT LIGHTS AND EMERGENCY BATTERY BALLASTSIN NOTED FIXTURES TO THE NEAREST UNSWITCHEDLIGHTING CIRCUIT IN THE AREA BEING SERVED.

3. EXTERIOR LIGHTING FIXTURES SHALL BE OPERATED BY ANEXISTING TIME CLOCK AND A PHOTOELECTRIC CONTROLLER.

4. PROVIDE LOW VOLTAGE WIRING FROM THE EXIT LIGHTS WITHEXTRA BATTERY CAPACITY TO THE REMOTE EMERGENCYLIGHTS INDICATED. LOW VOLTAGE WIRING SHALL BE ASRECOMMENDED BY THE EMERGENCY LIGHTING UNITMANUFACTURER.

5. SEE GENERAL ELECTRICAL NOTES ON SHEET E100 FORWIRING METHODS.

Page 4: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

OS OS

3

3

4

D

DDJ J J

OS OS OS

OS OS OS

3

JJJ

OS OS OS

OS OS OS

BeverageCenter

WW

E

FE

EE

XDE D DED D D D DEDE

H

H H H

H

H

HH

H

H

H

H

B

B

B

B

B

B

X

G G

D D DE

D

D

D

D

D

D

BB

DE

DE

D

DDD

D

D

K

Stairs

S2.2

Storage

210

Women'sRestroom

209

Men'sRestroom

207

MeetingRoom

211

PrivateOffice

201

PrivateOffice

205

PrivateOffice

203

PrivateOffice

202

PrivateOffice

204

PrivateOffice

206

Elevator

E1.2

Lounge

208

Corridor

200

1

1 1 1

1

1 1 1

1 1

1

1

1

2 2

Stairs

S1.2Chamberof

CommercePrivateOffice

213

Chamberof

CommercePrivateOffice

217

Chamberof

CommercePrivateOffice

215

Chamberof

CommercePrivateOffice

212

Chamberof

CommercePrivateOffice

214

Chamberof

CommercePrivateOffice

216

B

B

B

B

B

B

DEDE DDD D

H

H

H

H

H

H

H

H

H

H

H

H

FE

EE

X

1 1 1

1 1 1

1

E-202

1

E-202

2

KEY NOTES LIGHTING PLAN

1 CONNECT TO EXISTING BRANCH LIGHTING CIRCUIT INROOM/AREA USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT OFREMOVED LIGHT FIXTURE.

CONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT USING (2) #12 CONDUCTORS AND (1) #12 EQUIPMENT GROUNDINGCONDUCTOR IN 1/2" CONDUIT.

2

3

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

E-202

Second FloorLighting Plan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/4" = 1'-0"1

ENLARGED SECOND FLOOR LIGHTING PLAN - NORTH

1/4" = 1'-0"2

ENLARGED SECOND FLOOR LIGHTING PLAN - SOUTH 1/16" = 1'-0"3

SECOND FLOOR LIGHTING PLAN

GENERAL LIGHTING NOTES1. FIXTURES: SET LEVEL, PLUMB, AND SQUARE WITH CEILING

AND WALLS. SECURE ACCORDING TO MANUFACTURER'SWRITTEN INSTRUCTIONS AND APPROVED SUBMITTALMATERIALS. INSTALL LAMPS IN EACH FIXTURE.

2. CONNECT EXIT LIGHTS AND EMERGENCY BATTERY BALLASTSIN NOTED FIXTURES TO THE NEAREST UNSWITCHEDLIGHTING CIRCUIT IN THE AREA BEING SERVED.

3. EXTERIOR LIGHTING FIXTURES SHALL BE OPERATED BY ANEXISTING TIME CLOCK AND A PHOTOELECTRIC CONTROLLER.

4. PROVIDE LOW VOLTAGE WIRING FROM THE EXIT LIGHTS WITHEXTRA BATTERY CAPACITY TO THE REMOTE EMERGENCYLIGHTS INDICATED. LOW VOLTAGE WIRING SHALL BE ASRECOMMENDED BY THE EMERGENCY LIGHTING UNITMANUFACTURER.

5. SEE GENERAL ELECTRICAL NOTES ON SHEET E100 FORWIRING METHODS.

Page 5: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

UP

W

F

S

GC GC GC

W

GC

F S

J J

TV

JJ

S

H

S H

S

MS

GC

GC

W

FS

J J

TV TV

W

J J

FF

GC

InformationPamphlets

Mail

Copy/Print

E

E E E E E E

E

E

E

E

E E E

E

E E

E

CT

E

AGC AGC

Stairs

S2.0

Men'sRestroom

007

Women'sRestroom

009

Office

002

Office

001

MechanicalRoom

005

Corridor

000

Office

003

Storage

004

E E

C C C

AGCAGC

FA

CP

WC

E

ELEV

CB

A ABE A

FIRE ALARMDISCONNECT

2

2 2

DATA DATA

2 2

1

1 AA

AA2

WH

B1P1 P2

B2

4

44

1

1

1

2

2

1

1

E E E EE E E

EE

E

E E EEE EE E

E

E E E E E EEE E

60"AFF

60"AFF

60"

F F

Stairs

S1.0

Kitchenette

012

Boardroom

010

AGC AGC

AGC AGC

E E

TV

1" COMM

3/4" POWER

TV

1" COMM

3/4" POWER

DATADATA

33

1

3

3

3

3

3

3

WH1

E-300

1

E-300

2

KEY NOTES POWER PLAN

1 CONNECT TO EXISTING BRANCH CIRCUIT TO DEVICES SHOWNUSING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER INPANEL AA USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER INPANEL AB USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING BRANCH CIRCUIT WIRING FROMREMOVED EQUIPMENT.

2

3

4

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

E-300

Ground Floor PowerPlan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/4" = 1'-0"1

ENLARGED GROUND FLOOR POWER PLAN - NORTH

1/4" = 1'-0"2

ENLARGED GROUND FLOOR POWER PLAN - SOUTH 1/16" = 1'-0"3

GROUND FLOOR ELECTRICAL PLAN

GENERAL POWER NOTES1. EXISTING RECEPTACLES INDICATED TO BE REPLACED SHALL

BE CONNECTED TO THE EXISTING BRANCH CIRCUIT WIRINGIN DEVICE BOX. PROVIDE A NEW MATCHING WALL PLATE.

2. EXTEND EXISTING BRANCH WIRING TO RELOCATED WATERSOURCE HEAT PUMPS.

Page 6: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

DN

GC

GC

GC

G

F

S

S

J J

J

J

TV

S

J J

J

J

FS

S

J J

J

J

J

J

J J

E

E EE E E E EE E E E EE E E EEEEEEEEE

E

E

E

E

E E E E E E E E E E E E E E E EEEEEEEEE

E

E

E E E E EEEE EE

E

E

E

E

E

E E E E EEEE

E

AGC AGC

AGC

AGC

F F F F

F

WC

E

E

E

TV

1" COMM

3/4" POWER

AGC AGC

E E

AGC

AGC

B

B1

E E

HE

DATA DATA

2

22 DATA

DATA

2

1

1

2

60"

2

2

2

2

Cop

y/P

rint

E E E E E EE E E

EE

EEEEEE EEEEEE EEE

E

EEEE EEEEEE E E EEEEEEE E E E E

E

AGC AGC

AGC

AGC

F F F FStairs

S1.1

PrivateOffice

116

PrivateOffice

118

PrivateOffice

117

PhoneRoom

114

DedicatedOpenOffice

113

MeetingRoom

115

EEEE EEEE EEEE

AGC

AGC

AGC

DATA DATA

AGC

3

3 3DATA

DATA

3

1

E-301

1

E-301

2

KEY NOTES POWER PLAN

1 CONNECT TO EXISTING BRANCH CIRCUIT TO DEVICES SHOWNUSING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER IN PANELB1 USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER IN PANELB USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING BRANCH CIRCUIT WIRING FROMREMOVED EQUIPMENT.

2

3

4

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

E-301

First Floor PowerPlan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/4" = 1'-0"1

ENLARGED FIRST FLOOR POWER PLAN - NORTH

1/4" = 1'-0"2

ENLARGED FIRST FLOOR POWER PLAN - SOUTH

1/16" = 1'-0"3

FIRST FLOOR ELECTRICAL PLAN

GENERAL POWER NOTES1. EXISTING RECEPTACLES INDICATED TO BE REPLACED SHALL

BE CONNECTED TO THE EXISTING BRANCH CIRCUIT WIRINGIN DEVICE BOX. PROVIDE A NEW MATCHING WALL PLATE.

2. EXTEND EXISTING BRANCH WIRING TO RELOCATED WATERSOURCE HEAT PUMPS.

Page 7: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

GC

GC GC

F

S

GC

S

S

F

TV

J

J

J

J

J

J

J

J

J J J

FS

J J J

J

J J

J

BeverageCenter

E E E E E E E E E E E E E E E E E EE

E

E E E E EEEE EEEE EEEEEE EEE

E

E E E E E EE E

WC

60"

FTV

Stairs

S2.2

Storage

210

Women'sRestroom

209

Men'sRestroom

207

MeetingRoom

211

PrivateOffice

201

PrivateOffice

205

PrivateOffice

203

PrivateOffice

202

PrivateOffice

204

PrivateOffice

206

Elevator

E1.2

Lounge

208

Corridor

200

E E E FAAP

E

AGC

AGC

AGC

AGC

AGC

AGC

AGC

AGC

AGC AGC AGC

E E

E

1" COMM

3/4" POWER

E

E

E

E E

E

DATA DATA

2 2 2

2

1

2

DATA DATA

2

C

C2

C1

GEN PANEL& ATS

2 1

2

2

2

EEE E E E E E E E E E EEE E EE E E E EEE E

E E E E E EEE

EEEEEEEEEEEE E E E

E

Stairs

S1.2

Chamber of Commerce PrivateOffice

213

Chamber of Commerce PrivateOffice

217

Chamber of Commerce PrivateOffice

215

Chamber of Commerce PrivateOffice

212

Chamber of Commerce PrivateOffice

214

Chamber of Commerce PrivateOffice

216

AGC AGC AGC

AGC

AGC AGC

AGC

E E

1

3

DATA DATA

1

33

3

WSHP

E-302

1

E-302

2

KEY NOTES POWER PLAN

1 CONNECT TO EXISTING BRANCH CIRCUIT TO DEVICES SHOWNUSING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER INPANEL C1 USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING SPARE 20A, 1-POLE BREAKER INPANEL C2 USING #12/2 MC CABLE WITH GROUND.

CONNECT TO EXISTING BRANCH CIRCUIT WIRING FROMREMOVED EQUIPMENT.

2

3

4

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

E-302

Second Floor PowerPlan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/4" = 1'-0"1

ENLARGED SECOND FLOOR POWER PLAN - NORTH

1/4" = 1'-0"2

ENLARGED SECOND FLOOR POWER PLAN - SOUTH 1/16" = 1'-0"3

SECOND FLOOR ELECTRICAL PLAN

GENERAL POWER NOTES1. EXISTING RECEPTACLES INDICATED TO BE REPLACED SHALL

BE CONNECTED TO THE EXISTING BRANCH CIRCUIT WIRINGIN DEVICE BOX. PROVIDE A NEW MATCHING WALL PLATE.

2. EXTEND EXISTING BRANCH WIRING TO RELOCATED WATERSOURCE HEAT PUMPS.

Page 8: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

EF1

1

KEY NOTES POWER PLAN

1 CONNECT TO EXISTING BRANCH CIRCUIT WIRING FROMREMOVED EQUIPMENT.

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

1/8" = 1'-0"

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

E-303

Roof Power Plan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/8" = 1'-0"1

Roof Floor Power Plan

GENERAL POWER NOTES1. EXISTING RECEPTACLES INDICATED TO BE REPLACED SHALL

BE CONNECTED TO THE EXISTING BRANCH CIRCUIT WIRINGIN DEVICE BOX. PROVIDE A NEW MATCHING WALL PLATE.

2. EXTEND EXISTING BRANCH WIRING TO RELOCATED WATERSOURCE HEAT PUMPS.

Page 9: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

LOCATION: ELECTRICAL ROOM EXISTING PANEL: MS PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED

FROM:SERVICE

MODEL: CCB - STYLE 2

MTG: SURFACE VOLTS Ph W

240 / 120 3 4 22,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA

7205 1 ELEVATOR E - E E 100E * 100E E E E E COOLING TOWER & PUMPS 1 & 2 2 0

7205 3 - E - - - 3P * 3P E - - - - 4 0

7205 5 - E - - - - * - E - - - - 6 0

0 7 PANEL C E E E E 225E * 225E E E E E PANEL B 8 0

0 9 - E - - - 3P * 3P E - - - - 10 0

0 11 - E - - - - * - E - - - - 12 0

0 13 GENERATOR & PANEL C2 E E E E 225E * 225E E E E E PANEL A 14 0

0 15 - E - - - 3P * 3P E - - - - 16 0

0 17 - E - - - - * - E - - - - 18 0

7205 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0

7205 SUBTOTAL Ph B MAIN LUGS - 600 AMPS SUBTOTAL Ph B 0

7205 SUBTOTAL Ph C BUS AMPACITY = 600 AMPS SUBTOTAL Ph C 0

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 7,205

A/C 0 100 0 VA ph B 7,205

HEATING 0 100 0 VA ph C 7,205NON-VENT MOTORS 21615 100 21615 TOTAL 22 kVAVENTILATION 0 100 0 NOTES:KITCHEN, #EQ = 0 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

RECEPTACLES 0 100 0MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 21615 21615

AMPS 52 52

LOCATION: ELECTRICAL ROOM EXISTING PANEL: A PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED

FROM:PANELMS

MODEL: AQF3422MBX

MTG: SURFACE VOLTS Ph W

208 / 120 3 4 22,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA

0 1 HEAT PUMP 108 #12 - #12 1/2" 20E * 20E #12 - #12 1/2" HEAT PUMP 107 2 0

0 3 - #12 - - - 3P * 3P #12 - - - - 4 0

0 5 - #12 - - - - * - #12 - - - - 6 0

0 7 EXISTING LOAD E E E E 20E * 20E E E E E EXTERIOR LIGHTING 8 0

0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXTERIOR LIGHTING 10 0

0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0

0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0

0 15 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 16 0

0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0

0 19 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 20 0

0 21 HVAC CLOCK E E E E 20E * 20E E E E E EXISTING LOAD 22 0

0 23 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 24 0

0 25 ELEVATOR LIGHTS E E E E 20E * 20E E E E E EXISTING LOAD 26 0

0 27 HEAT PUMP #10 - #10 1/2" 30E * 20E #12 - #12 1/2" HEAT PUMP 28 0

0 29 - #10 - - - 2P * 2P #12 - - - - 30 0

0 31 HEAT PUMP #10 - #10 1/2" 30E * 20E #12 - #12 1/2" HEAT PUMP 32 0

0 33 - #10 - - - 2P * 2P #12 - - - - 34 0

0 35 HEAT PUMP #10 - #10 1/2" 30E * 20E E E E E SUMP PUMP 36 0

0 37 - #10 - - - 2P * 70E E E E E PANEL AA 38 0

0 39 PANEL AB E E E E 100E * 3P E - - - ROOM 108 40 0

0 41 - E - - - 2P * - E - - - - 42 0

0 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0

0 SUBTOTAL Ph B MAIN LUGS - 225 AMPS SUBTOTAL Ph B 0

0 SUBTOTAL Ph C BUS AMPACITY = 225 AMPS SUBTOTAL Ph C 0

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 0

A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:

RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 0 0

AMPS 0 0

LOCATION: ELECTRICAL ROOM EXISTINGPANEL: AB PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC SUPPLY: PANEL A

MODEL: TM2010CCU

MTG: SURFACE VOLTS Ph W

208 / 120 1 3 10,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B BKR Ph N G C LOAD # VA

0 1 EXISTING 208 REC E - E E 20E * 20E E - E E EXISTING 208 REC 2 0

0 3 - E - - - 2P * 2P E - - - - 4 0

0 5 EXISTING 208 REC E - E E 20E * 20E E - E E EXISTING 208 REC 6 0

0 7 - E - - - 2P * 2P E - - - - 8 0

0 9 EXISTING 208 REC E - E E 20E * 20E E - E E EXISTING 208 REC 10 0

0 11 - E - - - 2P * 2P E - - - - 12 0

0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0

0 15 SPARE E E E E 20E * 20E E E E E SPARE 16 0

0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0

0 19 EXISTING LOAD E E E E 20E * 30E E E E E EXISTING LOAD 20 0

0 SUBTOTAL Ph A MAIN BREAKER - 100 AMPS SUBTOTAL Ph A 0

0 SUBTOTAL Ph B MAIN LUGS - - AMPS SUBTOTAL Ph B 0BUS AMPACITY = 100 AMPS

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 0

A/C 0 100 0 VA ph B 0HEATING 0 100 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0 NOTESKITCHEN, #EQ = 0 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

RECEPTACLES 0 100 0MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 0 0

AMPS 0 0

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

12" = 1'-0"

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\Ele

ctr

ical -

Deta

ils -

2014.r

vt

E-600

Panel Schedules

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

Page 10: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

LOCATION: ELECTRICAL ROOM EXISTING PANEL: B PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED

FROM:PANELMS

MODEL: AQF3422MBX

MTG: SURFACE VOLTS Ph W

208 / 120 3 4 10,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA

0 1 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 2 0

0 3 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 4 0

0 5 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 6 0

0 7 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 8 0

0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 10 0

0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0

0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0

0 15 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 16 0

0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0

0 19 EXISTING LOAD E E E E 20E * 30E #10 - #10 1/2" HEAT PUMP 20 0

0 21 EXISTING LOAD E E E E 20E * 3P #10 - - - - 22 0

0 23 EXISTING LOAD E E E E 20E * - #10 - - - - 24 0

0 25 HEAT PUMP #10 - #10 1/2" 30E * 100E PANEL B1 26 0

0 27 - #10 - - - 2P * 3P - - - - 28 0

0 29 REC E E E E 20E * - - - - - 30 0

0 31 HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" 115 HEAT PUMP 32 0

0 33 - #10 - - - 3P * 3P #10 - - - - 34 0

0 35 - #10 - - - - * - #10 - - - - 36 0

0 37 CONF. ROOM HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" RESOURCE ROOM HEAT PUMP 38 0

0 39 - #10 - - - 2P * 2P #10 - - - - 40 0

0 41 TIME CLOCK E E E E 20E * 20E E E E E EXISTING LOAD 42 0

0 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0

0 SUBTOTAL Ph B MAIN LUGS - 225 AMPS SUBTOTAL Ph B 0

0 SUBTOTAL Ph C BUS AMPACITY = 225 AMPS SUBTOTAL Ph C 0

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 0

A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:

RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 0 0

AMPS 0 0

E

E

E

E E E

LOCATION: ELECTRICAL ROOM EXISTING PANEL: B1 PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED

FROM:PANEL B

MODEL: TL42422C

MTG: SURFACE VOLTS Ph W

208 / 120 3 4 10,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA

0 1 EXISTING LOAD E E E E 20E * 30E E E E E EXISTING LOAD 2 0

0 3 EXISTING LOAD E E E E 20E * 30E E E E E EXISTING LOAD 4 0

0 5 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 6 0

0 7 EXISTING LOAD E E E E 30E * 20E E E E E EXISTING LOAD 8 0

0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 10 0

0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0

0 13 EXISTING 208 REC E - E E 30E * 20E E E E E EXISTING LOAD 14 0

0 15 - E - - - 2P * 20E E E E E EXISTING LOAD 16 0

0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0

0 19 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 20 0

0 21 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 22 0

0 23 EXISTING LOAD E E E E 20E * 20E E - E E EXISTING LOAD 24 0

0 25 EXISTING LOAD E - E E 30E * 2P E - - - - 26 0

0 27 - E - - - 2P * 20E E - E E EXISTING LOAD 28 0

0 29 EXISTING LOAD E - E E 20E * 2P E - - - - 30 0

0 31 - E - - - 2P * 20E E - E E EXISTING LOAD 32 0

0 33 EXISTING LOAD E - E E 20E * 2P E - - - - 34 0

0 35 - E - - - 2P * 20E E E E E EXISTING LOAD 36 0

0 37 EXISTING LOAD E E E E 20E * 20E #12 - #12 1/2" SERVER AHU 38 0

0 39 SERVER A/C #10 - #10 1/2" 20E * 2P #12 - - - - 40 0

0 41 - #10 - - - 2P * 20E E E E E EXISTING LOAD 42 0

0 SUBTOTAL Ph A MAIN BREAKER - 100 AMPS SUBTOTAL Ph A 0

0 SUBTOTAL Ph B MAIN LUGS - - AMPS SUBTOTAL Ph B 0

0 SUBTOTAL Ph C BUS AMPACITY = 100 AMPS SUBTOTAL Ph C 0

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 0

A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:

RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 0 0

AMPS 0 0

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

12" = 1'-0"

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\Ele

ctr

ical -

Deta

ils -

2014.r

vt

E-601

Panel Schedules

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

Page 11: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

LOCATION: ELECTRICAL ROOM EXISTING PANEL: C PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED

FROM:PANELMS

MODEL: AQF3422MBX

MTG: SURFACE VOLTS Ph W

208 / 120 3 4 10,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA

0 1 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 2 0

0 3 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 4 0

0 5 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 6 0

0 7 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 8 0

0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 10 0

0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0

0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0

0 15 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 16 0

0 17 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 18 0

0 19 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 20 0

0 21 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 22 0

0 23 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 24 0

0 25 PANEL C1 100E * 20E E E E E EXISTING LOAD 26 0

0 27 - 3P * 60E #6 - #10 3/4" GENERATOR TRANSFER SW 28 0

0 29 - - * 2P #6 - - - - 30 0

0 31 HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" HEAT PUMP 32 0

0 33 - #10 - - - 2P * 2P #10 - - - - 34 0

0 35 HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" HEAT PUMP 36 0

0 37 - #10 - - - 2P * 2P #10 - - - - 38 0

0 39 HEAT PUMP #10 - #10 1/2" 30E * 30E #10 - #10 1/2" HEAT PUMP LOBBY 40 0

0 41 - #10 - - - 2P * 2P #10 - - - - 42 0

0 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0

0 SUBTOTAL Ph B MAIN LUGS - 225 AMPS SUBTOTAL Ph B 0

0 SUBTOTAL Ph C BUS AMPACITY = 225 AMPS SUBTOTAL Ph C 0

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 0

A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:

RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 0 0

AMPS 0 0

E

E

E

E E E

-

-

- -

- -

LOCATION: ELECTRICAL ROOM EXISTING PANEL: C1 PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED

FROM:PANEL C

MODEL: TL24-415C

MTG: SURFACE VOLTS Ph W

208 / 120 3 4 10,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B C BKR Ph N G C LOAD # VA

0 1 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 2 0

0 3 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 4 0

0 5 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 6 0

0 7 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 8 0

0 9 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 10 0

0 11 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 12 0

0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0

0 15 EXISTING LOAD E E E E 30E * 20E E E E E EXISTING LOAD 16 0

0 17 EXISTING LOAD E E E E 30E * 20E E E E E EXISTING LOAD 18 0

0 19 EXISTING LOAD E - E E 30E * 20E E E E E EXISTING LOAD 20 0

0 21 - E - - - 2P * 20E E - E E EXISTING LOAD 22 0

0 23 EXISTING LOAD E E E E 20E * 2P E - - - - 24 0

0 SUBTOTAL Ph A MAIN BREAKER - - AMPS SUBTOTAL Ph A 0

0 SUBTOTAL Ph B MAIN LUGS - 100 AMPS SUBTOTAL Ph B 0

0 SUBTOTAL Ph C BUS AMPACITY = 100 AMPS SUBTOTAL Ph C 0

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 0

A/C 0 100 0 VA ph B 0HEATING 0 100 0 VA ph C 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0KITCHEN, #EQ = 0 0 100 0 NOTES:

RECEPTACLES 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 0 0

AMPS 0 0

LOCATION: ELECTRICAL ROOM EXISTINGPANEL: C2 PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: CUTLER-HAMMER FED

FROM:PANELMS

MODEL: PRL1a

MTG: SURFACE VOLTS Ph W

208 / 120 1 3 10,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B BKR Ph N G C LOAD # VA

0 1 SPACE * SPACE 2 0

0 3 EXISTING REC E E E E 20E * 40E SPARE (EXISTING RTU) 4 0

0 5 SPARE (EXISTING 208 REC) 30E * 3P - 6 0

0 7 - 2P * - - 8 0

0 9 EXISTING REC 20E * 40E SPARE (EXISTING RTU) 10 0

0 11 EXISTING REC 30E * 3P - 12 0

0 13 SPACE * - - 14 0

0 15 SPARE 20E * SPACE 16 0

0 17 SPACE * 15E SPARE (EXISTING 208 REC) 18 0

0 19 SPACE * 2P - 20 0

0 21 SPACE * 15E SPARE (EXISTING 208 REC) 22 0

0 23 SPACE * 2P - 24 0

0 25 SPACE * SPACE 26 0

0 27 SPACE * SPACE 28 0

0 29 SPACE * SPACE 30 0

0 31 SPACE * SPACE 32 0

0 33 SPACE * SPACE 34 0

0 35 SPACE * SPACE 36 0

0 37 SPACE * SPACE 38 0

0 39 SPACE * SPACE 40 0

0 41 SPACE * SPACE 42 0

0 SUBTOTAL Ph A MAIN BREAKER - 200 AMPS SUBTOTAL Ph A 0

0 SUBTOTAL Ph B MAIN LUGS - - AMPS SUBTOTAL Ph B 0BUS AMPACITY = 225 AMPS

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 0

A/C 0 100 0 VA ph B 0HEATING 0 100 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0 NOTESKITCHEN, #EQ = 0 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

RECEPTACLES 0 100 0MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 0 0

AMPS 0 0

E E E E

E E E E

LOCATION: ELECTRICAL ROOM EXISTINGPANEL: GEN PROJECT: MORGANTOWN ENTERPRISECENTERMANUFAC: GENERAL ELECTRIC FED

FROM:PANELMS

MODEL: TLM3220CCU

MTG: SURFACE VOLTS Ph W

208 / 120 1 3 10,000 AIC

CONN CONN

VA # LOAD Ph N G C BKR A B BKR Ph N G C LOAD # VA

0 1 EXISTING LOAD E E E E 20E * 30E E - E E EXISTING LOAD 2 0

0 3 EXISTING LOAD E E E E 20E * 2P E - - - - 4 0

0 5 EXISTING LOAD E - E E 20E * 20E E - E E EXISTING LOAD 6 0

0 7 - E - - - 2P * 2P E - - - - 8 0

0 9 EXISTING LOAD E - E E 30E * 20E E E E E EXISTING LOAD 10 0

0 11 - E - - - 2P * 20E E E E E EXISTING LOAD 12 0

0 13 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 14 0

0 15 EXISTING LOAD E E E E 15E * 50E SPARE 16 0

0 17 EXISTING LOAD E E E E 20E * 2P - 18 0

0 19 EXISTING LOAD E E E E 20E * 20E E E E E EXISTING LOAD 20 0

0 21 EXISTING LOAD E E E E 20E * 50E E - E E EXISTING LOAD 22 0

0 23 EXISTING LOAD E E E E 20E * 2P E - - - - 24 0

0 25 EXISTING LOAD E E E E 20T/E * 20T/E E E E E EXISTING LOAD 26 0

0 27 EXISTING LOAD E E E E 20T/E * 20T/E E E E E EXISTING LOAD 28 0

0 29 EXISTING LOAD E E E E 20T/E * 30T/E E E E E EXISTING LOAD 30 0

0 31 EXISTING LOAD E E E E 20T/E * 30T/E E E E E EXISTING LOAD 32 0

0 SUBTOTAL Ph A MAIN BREAKER - 200 AMPS SUBTOTAL Ph A 0

0 SUBTOTAL Ph B MAIN LUGS - - AMPS SUBTOTAL Ph B 0BUS AMPACITY = 200 AMPS

LOAD CONN DF DEM

LIGHTING 0 125 0 VA ph A 0

A/C 0 100 0 VA ph B 0HEATING 0 100 0NON-VENT MOTORS 0 100 0 TOTAL 0 kVAVENTILATION 0 100 0 NOTESKITCHEN, #EQ = 0 0 100 0 1. "E" INDICATES EXISTING TO REMAIN.

RECEPTACLES 0 100 0 2. "T" INDICATES TANDEM BREAKER.

MISCELLANEOUS 0 100 0

FUTURE 0 100 0

TOTAL VA 0 0

AMPS 0 0

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

12" = 1'-0"

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\Ele

ctr

ical -

Deta

ils -

2014.r

vt

E-602

Panel Schedules

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

Page 12: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

EXISTINGMAIN PANEL

MS600A

208/120V3PH, 4W

MLO

EXISTINGPADMOUNTED

TRANSFORMERTO REMAIN

TO EXISTINGPRIMARY

COMPARTMENT

EXISTING UNDERGROUND SERVICELATERAL IN (2) 6'' CONDUITS TO REMAIN

EXISTING UNDERGROUNDPRIMARY TO REMAIN

EXISTINGGENERATOR

60KW208/120V

1PH

EXISTING GROUNDING ELECTRODECONDUCTOR TO REMAIN

90A SH3-POLE

208VENCLOSED

CIRCUITBREAKERWITH AUX.CONTACTS

EXISTINGPASSENGERELEVATOR

20HP208V3PH

EXISTINGPANEL

A225A

208/120V3PH, 4W

MLO

EXISTINGPANEL

AB100A

208/120V1PH, 3W

100A MCB

REMOVEEXISTING

PANELAA

225A208/120V3PH, 4W

MLO

REMOVEEXISTING

PANELAA2100A

208/120V3PH, 4W

MLO

EXISTINGPANEL

B225A

208/120V3PH, 4W

MLO

EXISTINGPANEL

B1100A

208/120V3PH, 4W

100A MCB

EXISTINGPANEL

C225A

208/120V3PH, 4W

MLO

EXISTINGPANEL

C1100A

208/120V3PH, 4W

MLO

EXISTINGPANEL

C2225A

208/120V1PH, 3W

200A MCB

EXISTINGPANELGEN200A

208/120V1PH, 3W

200A MCB

EXISTINGATS200A

208/120V2-POLE

200AMCB

EXISTINGCT

CABINETTO REMAIN

EXISTING SERVICE CONDUCTORSTO REMAIN

EXISTING FEEDER TO REMAIN

(3) #3, (1) #8EG, 1-1/4"C

EXISTING FEEDER TO REMAIN EXISTING FEEDER TO REMAIN

REMOVE EXISTING FEEDER

REMOVE EXISTING FEEDER

EXISTING FEEDER TO REMAIN

EXISTING FEEDER TO REMAIN

EXISTING FEEDER TO REMAIN

EXISTING FEEDER TO REMAIN

EXISTING FEEDERTO REMAIN

EXISTING200A208V

2-POLE3R

EXISTING FEEDERTO REMAIN

EXISTING FEEDER TO REMAIN

EXISTING FEEDER TO REMAIN

EXISTING FEEDER TO REMAIN

EXISTING FEEDER TO REMAIN

PROVIDE NEW 4"X4"X4'WIREWAY TO SERVECOOLING TOWER LOADS

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

1/8" = 1'-0"

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\Ele

ctr

ical -

Deta

ils -

2014.r

vt

E-800

Diagrams & Details

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

Not to Scale1

Power Riser Diagram

Page 13: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

(TYP)

3/4" C

6" MIN.

SUSPENDEDCEILING

18"

FLOOR ABOVEOR ROOF

TELECOM RISER NOTES:

1. (2) EXISTING 4" CONDUITS WITH EXISTING INCOMING SERVICE.

NOTE 1GND FLOOR

1ST FLOOR

2ND FLOOR

ROOF

(1) EX. 4" C

TO EXISTINGSERVICECONNECTION

ELECTRICALCLOSET

ELECTRICALCLOSET

MECHANICALROOM

(1) EX. 4" C

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

1/8" = 1'-0"

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\Ele

ctr

ical -

Deta

ils -

2014.r

vt

E-801

Diagrams & Details

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

Not to Scale2

Voice/Data Outlet Detail

COMMUNICATIONS NOTES1. VOICE/DATA CABLING: PROVIDE (1) 4 PAIR, 24

AWG, UTP, CAT.5e, CMP RATED CABLE WITHBLUE JACKET FROM EACH OUTLET BOXINDICATED TO A PATCH PANEL LOCATED INTELECOM ROOM ON RESPECTIVE FLOOR.CABLES SHALL BE INSTALLED IN 3/4" EMT MIN.WHERE CONCEALED WITHIN WALLS, ABOVEINACCESSIBLE CEILINGS, AND EXPOSEDCEILING AREAS. PROVIDE (1) RJ-45 JACK IN ASINGLE WALL PLATE FOR EACH OUTLETSHOWN. TERMINATE EACH CAT. 5e CABLE TORJ-45 JACK AND PATCH PANEL. PROPERLYLABEL EACH END OF CABLE.

2. PATCH PANEL: PROVIDE A 19-INCH WALLMOUNTED RACK IN EACH ELECTRICALCLOSET. COORDINATE LOCATION OF RACKWITH OWNER. PROVIDE CAT. 5e PATCHPANEL WITH PORTS FOR CONNECTINGOUTLETS SHOWN PLUS 25% ADDITIONALCAPACITY FOR FUTURE OUTLETS.

3. TELEVISION CABLING: WHERE TV FACILITIESARE INDICATED, PROVIDE (1) RG6/U SOLIDCOPPER QUAD SHIELD COAXIAL,PLENUM-RATED CABLE FROM EACH OUTLETBOX INDICATED TO MECHANICAL ROOM 005.CABLES SHALL BE INSTALLED IN 3/4" EMT MIN.WHERE CONCEALED WITHIN WALLS, ABOVEINACCESSIBLE CEILINGS, AND EXPOSEDCEILING AREAS. PROVIDE A 75 OHM, F-TYPECONNECTOR IN A SINGLE WALL PLATE FOREACH OUTLET SHOWN. PROVIDE ALL CABLETERMINATIONS. PROPERLY LABEL EACH ENDOF CABLE. PROVIDE TV DISTRIBUTIONEQUIPMENT; INCLUDING BUT NOT LIMITED TO,DISTRIBUTION AMPLIFIERS, DIRECTIONALMULTI-TAPS, AND SPLITTERS.

4. CABLE INSTALLATION: CABLES SHALL BEENCLOSED IN RACEWAY WHERE INSTALLEDWITHIN FINISHED WALLS AND ABOVEINACCESSIBLE CEILINGS AREAS. PROVIDEJ-HOOKS, SECURED TO THE BUILDINGSTRUCTURE AT 4'-0" MAXIMUM INTERVALS, TOSUPPORT CABLES ABOVE ACCESSIBLECEILINGS.

5. IDENTIFICATION: LABEL EACH END OF ALLCABLE RUNS.

FIRE ALARM SYSTEM NOTES14. PROVIDE A TEST KEY SWITCH IN THE ELEVATOR MACHINE

ROOM TO SIMULATE THE ACTIVATION OF A HEAT DETECTORTO TEST THE POWER SHUT DOWN OPERATION OF THEELEVATOR.

15. WHEN ACTIVATED, THE SMOKE DETECTORS IN THEELEVATOR SHAFT, THE ELEVATOR LOBBIES, AND IN THEELEVATOR MACHINE ROOM SHALL SOUND A GENERAL FIREALARM AND RECALL THE ELEVATOR TO THE LEVEL OF THEEXIT DISCHARGE.

16. PROVIDE DUCT-TYPE SMOKE DETECTORS IN THE RETURN AIRDUCT OF THE HVAC UNITS INDICATED. WHEN ACTIVATED, THEDUCT-TYPE SMOKE DETECTORS SHALL AUTOMATICALLYSHUT DOWN THE HVAC UNIT, CLOSE THE MAIN FAN DAMPERS,AND SOUND A GENERAL FIRE ALARM.

17. PROVIDE WIRING AND CONNECTION TO ALL FLOW, TAMPER,AND PIV TAMPER SWITCHES. COORDINATE LOCATION WITHTHE SPRINKLER CONTRACTOR. EACH FLOW SWITCH SHALLBE ANNUNCIATED SEPARATELY. TAMPER AND PIV TAMPERSWITCHES SHALL BE ELECTRICALLY-SUPERVISED ANDANNUNCIATED AS A TROUBLE ON THE FACP.

18. PROVIDE REMOTE ALARM INDICATOR AND TEST STATION FOREACH DUCT-TYPE SMOKE DETECTOR AND SPRINKLERSYSTEM FLOW SWITCH. MOUNT STATION IN RECESSEDDEVICE BOX LOCATED 6'-0'' ABOVE FINISHED FLOOR. WIRINGSHALL BE ENCLOSED WITHIN RACEWAY AND CONCEALEDWITHIN WALL.

19. ALL EXTINGUISHING SYSTEMS SHALL BE CONNECTED TO THEFIRE ALARM SYSTEM PER CODE.

20. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

21. IDENTIFY SYSTEM COMPONENTS, WIRING, CABLING, ANDTERMINALS ACCORDING TO DIVISION 28 SPECIFICATIONS.

22. FIRE ALARM WIRING SHALL BE ENCLOSED IN METALRACEWAY SEPARATE FROM OTHER DATA AND POWERWIRING WHERE CONCEALED WITHIN WALLS AND EXPOSEDON WALLS OF UNFINISHED SPACES OR UNLESS OTHERWISEINDICATED. PLENUM-RATED FIRE ALARM CABLE SHALL BEPERMITTED WHERE CONCEALED ABOVE GRID CEILINGS INFINISHED AREAS. SECURE CABLES TO BUILDING STRUCTUREUSING APPROVED SUPPORTING DEVICES MOUNTED AT 4'-0"MAXIMUM INTERVALS. BOXES SHALL BE PAINTED RED FORIDENTIFICATION.

FIRE ALARM SYSTEM NOTES1. ALL WORK SHALL COMPLY WITH THE WEST VIRGINIA STATE

FIRE CODE. ALL WORK SHALL COMPLY WITH THE NFPA CODEADOPTED BY THE WEST VIRGINIA STATE FIRE CODE.

2. THE FIRE ALARM INSTALLER SHALL SUBMIT REQUIREDINFORMATION TO THE WEST VIRGINIA STATE FIRE MARSHALFOR APPROVAL. THE FIRE ALARM INSTALLER SHALL SUBMITFIRE ALARM DRAWINGS, COMPLETE WITH EQUIPMENTLOCATIONS, DIMENSIONS BETWEEN LIKE DEVICES TO VERIFYPROPER SPACING, AND FIRE ALARM RISER DIAGRAM

3. REPLACE THE EXISTING NONCODED, ZONED FIRE ALARMSYSTEM WITH A NEW ADDRESSABLE FIRE ALARM SYSTEMWITH MANUAL AND AUTOMATIC ALARM INITIATION; ANDHARDWIRED FOR SIGNAL TRANSMISSION DEDICATED TO FIREALARM SERVICE ONLY, USING A UNIQUE ADDRESS FOR EACHALARM INITIATION DEVICE.

4. PROVIDE A DEDICATED 20 AMP, 120 VOLT BRANCH CIRCUITFOR FACP POWER.

5. PROVIDE A DEDICATED TELEPHONE LINE TO FACP FORTRANSMITTING MEANS TO REMOTE SUPERVISING STATIONFROM DIGITAL ALARM COMMUNICATOR TRANSMITTER.

6. PROVIDE A FIRE ALARM ANNUNCIATOR PANEL IN MAINVESTIBULE.

7. SMOKE DETECTORS SHALL BE PLACED A MAXIMUM OF 15FEET FROM THE ENDS OF CORRIDORS OR WALLS AND 30FEET ON CENTER AND IN ROOMS OPEN TO THE CORRIDORS.EXCEEDING THE SPACING REQUIREMENTS WILL REQUIRESUBMISSION OF TECHNICAL DATA FOR APPROVAL BY THEFIRE MARSHAL.

8. IN CORRIDORS, VISIBLE NOTIFICATION APPLIANCES SHALL BELOCATED NOT MORE THAN 15 FEET FROM THE END OF THECORRIDOR WITH A SEPARATION NOT GREATER THAN 100FEET BETWEEN APPLIANCES.

9. VISIBLE NOTIFICATION APPLIANCES SHALL BE LOCATED INALL PUBLIC TOILETS.

10. PULL STATIONS SHALL BE LOCATED NO GREATER THAN 200FEET FROM EACH OTHER AND AT ALL EXITS.

11. WHERE EXISTING DEVICE BOXES ARE BEING USED FOR NEWCONSTRUCTION, VERIFY PROPER MOUNTING HEIGHT. IFMOUNTING HEIGHT OF PROPOSED DEVICE IS NOT PER CODE,REPLACE CONCEALED BOX AND RACEWAY AT PROPERHEIGHT.

12. PROVIDE ELEVATOR EMERGENCY OPERATION PER CURRENTEDITION OF ASME A17.1.

13. HEAT DETECTORS IN THE ELEVATOR SHAFT AND IN THEELEVATOR MACHINE ROOM SHALL BE MOUNTED WITHIN 2FEET OF EACH SPRINKLER HEAD. SPRINKLER HEAD SHALLHAVE A HIGHER RESPONSE TIME INDEX (RTI) THAN THE HEATDETECTOR. WHEN ACTIVATED, THE HEAT DETECTORS IN THEELEVATOR SHAFT AND IN THE ELEVATOR MACHINE ROOMSHALL SOUND A GENERAL FIRE ALARM, RECALL THEELEVATOR TO THE LEVEL OF EXIT DISCHARGE ANDAUTOMATICALLY SHUT DOWN POWER TO THE ELEVATORUSING A SHUNT-TRIP CIRCUIT BREAKER.

Not to Scale1

Telecom Riser Diagram

Page 14: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

F

OS OSOS

SS

FEC

S

GC GC GC

W

S

CR

GC

F S

MS

FEC

R

R

R

E E E EE E E

EE

E

E E EEE EE E

E EE

R

E E

R

R

R

R

RRRR

R

RRRR

E

E E E E E EEE E

R

RR R

R

R

CT

WSHP

R

1

E

E E

R RR

RR

R

R

R R R R

E E E E

R

E

E

R

R

R R RRR

E

R

R

R

E

R

R

R

R

R

R

R

R

R

E E

E

EE

E

E

E E E

EEE

E

EER

R

FA

CP

E

E

R

WSHP

WSHP

WH

BOILER

AIRCOMP

AIRCOMP

PUMPPUMP

AA

AA2

ELEV

G

R

R R

R

RR

A AB

CT E

E

R R E

FIRE ALARMDISCONNECT

ED-100

2

ED-100

3

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

ED-100

Ground FloorElectrical DemolitionPlan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/4" = 1'-0"2

ENLARGED GROUND FLOOR ELECTRICAL DEMOLITION PLAN -SOUTH

1/4" = 1'-0"3

ENLARGED GROUND FLOOR ELECTRICAL DEMOLITION PLAN -NORTH

1/16" = 1'-0"1

DEMO - GROUND FLOOR ELECTRICAL PLAN

GENERAL DEMOLITION NOTES1. ALL DEVICES AND EQUIPMENT SHOWN ON THE ELECTRICAL

DEMOLITION PLAN ARE FOR REFERENCE ONLY AND SHALL BEFIELD VERIFIED BEFORE STARTING WORK. NOTIFY A/E IFDEVICES AND EQUIPMENT NOT SHOWN ON THE PLAN AREFOUND DURING DEMOLITION WORK.

2. REMOVE EXISTING BRANCH CIRCUIT WIRING FROM FIXTURESAND DEVICES BEING REMOVED BACK TO SOURCE CIRCUITBREAKER. VERIFY POWER CONTINUATION OF EXISTINGFIXTURES AND DEVICES INDICATED TO REMAIN.

3. REMOVE EXISTING LIGHT FIXTURES, EXIT LIGHTS, ANDEMERGENCY BATTERY LIGHTS WITHIN THE AREA OFCONSTRUCTION, UNLESS OTHERWISE NOTED.

4. REMOVE EXISTING LIGHT SWITCHES, WALL PLATES, ANDASSOCIATED WIRING WITHIN THE AREA OF CONSTRUCTION,UNLESS OTHERWISE NOTED.

5. EXISTING LIGHT SWITCHES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECT LIGHTSWITCH TO EXISTING WIRING AS INDICATED. REPLACE WALLPLATE TO MATCH.

6. EXISTING RECESSED DEVICE BOXES FOR NOTED LIGHTSWITCHES AND RECEPTACLES AND ASSOCIATED CONCEALEDRACEWAY SHALL REMAIN FOR USE WITH NEWCONSTRUCTION.

7. PROVIDE A BLANK WALL PLATE FOR ALL EXISTING RECESSEDDEVICE BOXES NOT USED FOR NEW CONSTRUCTION.PROVIDE GANGING OF WALL PLATE AS REQUIRED TO COVEREXISTING DEVICE BOX.

8. REMOVE EXISTING RECEPTACLES AS INDICATED. REMOVEASSOCIATED BRANCH CIRCUIT WIRING BACK TO SOURCECIRCUIT BREAKER. VERIFY POWER CONTINUATION OFEXISTING RECEPTACLES INDICATED TO REMAIN.

9. EXISTING RECEPTACLES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECTRECEPTACLE TO EXISTING WIRING AS INDICATED. REPLACEWALL PLATE TO MATCH.

10. REMOVE EXISTING VOICE/DATA OUTLETS AS INDICATED.REMOVE VOICE/DATA CABLES BACK TO PATCH PANEL.EXISTING RECESSED BOXES AND CONCEALED RACEWAYSHALL REMAIN FOR FUTURE USE. PROVIDE BLANK WALLPLATES TO COVER EXISTING DEVICE BOXES.

11. REPLACE EXISTING BLANK WALL PLATES WITH WALL PLATESMATCHING PLATES OF DEVICES USED IN NEWCONSTRUCTION.

12. REMOVE EXISTING EXPOSED CONDUIT AND SURFACERACEWAY ON FINISHED WALLS, UNLESS USED FOR NEWCONSTRUCTION.

13. REMOVE EXISTING ACCESS CONTROL SYSTEM DEVICES ANDASSOCIATED WIRING.

14. SEAL FIRE RATED WALLS, FLOORS AND STRUCTURAL CEILINGFROM REMOVED RACEWAY AND SLEEVES MATCHING FIRERATING OF EXISTING ASSEMBLY.

15. REMOVE ALL EXISTING ACCESSIBLE POWER WIRING, DATACABLES, AND ASSOCIATED RACEWAYS NOT BEING USED FORNEW CONSTRUCTION.

17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.

17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.

16. REMOVE EXISTING SURFACE MOUNTED RECEPTACLES ANDASSOCIATED SURFACE RACEWAY. VERIFY POWERCONTINUATION AND TERMINATE BRANCH CIRCUIT WIRING INNEAREST ACCESSIBLE JUNCTION BOX. REMOVE EXISTINGBRANCH CIRCUIT WIRING BACK TO SOURCE CIRCUITBREAKER FOR DEDICATED RECEPTACLES.

17. REMOVE EXISTING SURFACE MOUNTED VOICE/DATA OUTLETSAND ASSOCIATED SURFACE RACEWAY. REMOVE VOICE/DATACABLES BACK TO PATCH PANEL.

18. REMOVE EXISTING FIRE ALARM SYSTEM AND ASSOCIATEDCABLING. EXISTING RECESSED DEVICE BOXES ANDCONCEALED RACEWAY SHALL REMAIN AND BE USED FORNEW CONSTRUCTION IF MOUNTING HEIGHT IS PER NFPAGUIDELINES. EXISTING FIRE ALARM SYSTEM SHALL REMAININ OPERATION UNTIL NEW SYSTEM IS INSTALLED.

Page 15: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

GC

F

3

4

S

GC

G

TV

GC

CR

S

S

S

F

3

CR

CR

SSCR

ED-101

2

ED-101

3

E

E EE E E E EE E E E EE E E EEEEEEEEE

RR R R R R R R R RRRR

R R

R

EE

R

R R R

E

E

E

E

E E

E

R

E E E E E E E E E E E E E E E EEEEEEEEE

E

E

E E E E EEEE EE

E

R

RR

R

RR

R RR

E

E

ER

R

E

E

E E E E EEEE

E

E

R

E

R

E E

E E

E E

R R

E

WSHP WSHP

WSHPWSHP

B1

BE

E

R R

R

E E E E E EE E E

E

E

EEEEEE EEEEEE EEE

E

EEEE EEEEEE E E EEEEEEE E E E E

E

R

EEEEE E E EE E E E

RRR

R

RR

R R RRRR R R R RRRRR

R

RRR

R

FC

WSHP WSHP

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

ED-101

First Floor ElectricalDemolition Plan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/16" = 1'-0"1

DEMO - FIRST FLOOR ELECTRICAL PLAN

1/4" = 1'-0"2

ENLARGED FIRST FLOOR ELECTRICAL DEMOLITION PLAN - NORTH

1/4" = 1'-0"3

ENLARGED FIRST FLOOR ELECTRICAL DEMOLITION PLAN - SOUTH

GENERAL DEMOLITION NOTES1. ALL DEVICES AND EQUIPMENT SHOWN ON THE ELECTRICAL

DEMOLITION PLAN ARE FOR REFERENCE ONLY AND SHALL BEFIELD VERIFIED BEFORE STARTING WORK. NOTIFY A/E IFDEVICES AND EQUIPMENT NOT SHOWN ON THE PLAN AREFOUND DURING DEMOLITION WORK.

2. REMOVE EXISTING BRANCH CIRCUIT WIRING FROM FIXTURESAND DEVICES BEING REMOVED BACK TO SOURCE CIRCUITBREAKER. VERIFY POWER CONTINUATION OF EXISTINGFIXTURES AND DEVICES INDICATED TO REMAIN.

3. REMOVE EXISTING LIGHT FIXTURES, EXIT LIGHTS, ANDEMERGENCY BATTERY LIGHTS WITHIN THE AREA OFCONSTRUCTION, UNLESS OTHERWISE NOTED.

4. REMOVE EXISTING LIGHT SWITCHES, WALL PLATES, ANDASSOCIATED WIRING WITHIN THE AREA OF CONSTRUCTION,UNLESS OTHERWISE NOTED.

5. EXISTING LIGHT SWITCHES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECT LIGHTSWITCH TO EXISTING WIRING AS INDICATED. REPLACE WALLPLATE TO MATCH.

6. EXISTING RECESSED DEVICE BOXES FOR NOTED LIGHTSWITCHES AND RECEPTACLES AND ASSOCIATED CONCEALEDRACEWAY SHALL REMAIN FOR USE WITH NEWCONSTRUCTION.

7. PROVIDE A BLANK WALL PLATE FOR ALL EXISTING RECESSEDDEVICE BOXES NOT USED FOR NEW CONSTRUCTION.PROVIDE GANGING OF WALL PLATE AS REQUIRED TO COVEREXISTING DEVICE BOX.

8. REMOVE EXISTING RECEPTACLES AS INDICATED. REMOVEASSOCIATED BRANCH CIRCUIT WIRING BACK TO SOURCECIRCUIT BREAKER. VERIFY POWER CONTINUATION OFEXISTING RECEPTACLES INDICATED TO REMAIN.

9. EXISTING RECEPTACLES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECTRECEPTACLE TO EXISTING WIRING AS INDICATED. REPLACEWALL PLATE TO MATCH.

10. REMOVE EXISTING VOICE/DATA OUTLETS AS INDICATED.REMOVE VOICE/DATA CABLES BACK TO PATCH PANEL.EXISTING RECESSED BOXES AND CONCEALED RACEWAYSHALL REMAIN FOR FUTURE USE. PROVIDE BLANK WALLPLATES TO COVER EXISTING DEVICE BOXES.

11. REPLACE EXISTING BLANK WALL PLATES WITH WALL PLATESMATCHING PLATES OF DEVICES USED IN NEWCONSTRUCTION.

12. REMOVE EXISTING EXPOSED CONDUIT AND SURFACERACEWAY ON FINISHED WALLS, UNLESS USED FOR NEWCONSTRUCTION.

13. REMOVE EXISTING ACCESS CONTROL SYSTEM DEVICES ANDASSOCIATED WIRING.

14. SEAL FIRE RATED WALLS, FLOORS AND STRUCTURAL CEILINGFROM REMOVED RACEWAY AND SLEEVES MATCHING FIRERATING OF EXISTING ASSEMBLY.

15. REMOVE ALL EXISTING ACCESSIBLE POWER WIRING, DATACABLES, AND ASSOCIATED RACEWAYS NOT BEING USED FORNEW CONSTRUCTION.

17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.

17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.

16. REMOVE EXISTING SURFACE MOUNTED RECEPTACLES ANDASSOCIATED SURFACE RACEWAY. VERIFY POWERCONTINUATION AND TERMINATE BRANCH CIRCUIT WIRING INNEAREST ACCESSIBLE JUNCTION BOX. REMOVE EXISTINGBRANCH CIRCUIT WIRING BACK TO SOURCE CIRCUITBREAKER FOR DEDICATED RECEPTACLES.

17. REMOVE EXISTING SURFACE MOUNTED VOICE/DATA OUTLETSAND ASSOCIATED SURFACE RACEWAY. REMOVE VOICE/DATACABLES BACK TO PATCH PANEL.

18. REMOVE EXISTING FIRE ALARM SYSTEM AND ASSOCIATEDCABLING. EXISTING RECESSED DEVICE BOXES ANDCONCEALED RACEWAY SHALL REMAIN AND BE USED FORNEW CONSTRUCTION IF MOUNTING HEIGHT IS PER NFPAGUIDELINES. EXISTING FIRE ALARM SYSTEM SHALL REMAININ OPERATION UNTIL NEW SYSTEM IS INSTALLED.

Page 16: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

FEC

FEC

OS OS

C

GC GC

GC

FS

STV

TV

FDD

S

FS

S

ED-102

2

ED-102

3

EE

R

E E E E E E E E E E E E E E E E E EE

E

E E E E EEEE EEEE EEEEEE EEE

E

E E E E E EE E

R

R

R R

RR

RR R

R

R RR

R

RRRRRR

R

RRR R R R

E

R

R

R

R

R E RER

E E R

R

RR K

B

PB

E

RRR

FACP

E

R

WSHP

WSHP

WSHP

WSHP

CE

GEN/ATSE

C1/C2

E

E

E

E

E E

E

EEE E E E E E E E E E EEE E EE E E E EEE E

E E E E E EEE

EEEEEEEEEEEE E E E

E

R R R

R R R

R

R R

RRRRRRRRRR

WSHP

WSHP

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

As indicated

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

ED-102

Second FloorElectrical DemolitionPlan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/16" = 1'-0"1

DEMO - SECOND FLOOR ELECTRICAL PLAN

1/4" = 1'-0"2

ENLARGED SECOND FLOOR ELECTRICAL DEMOLITION PLAN -NORTH

1/4" = 1'-0"3

ENLARGED SECOND FLOOR ELECTRICAL DEMOLITION PLAN -SOUTH

GENERAL DEMOLITION NOTES1. ALL DEVICES AND EQUIPMENT SHOWN ON THE ELECTRICAL

DEMOLITION PLAN ARE FOR REFERENCE ONLY AND SHALL BEFIELD VERIFIED BEFORE STARTING WORK. NOTIFY A/E IFDEVICES AND EQUIPMENT NOT SHOWN ON THE PLAN AREFOUND DURING DEMOLITION WORK.

2. REMOVE EXISTING BRANCH CIRCUIT WIRING FROM FIXTURESAND DEVICES BEING REMOVED BACK TO SOURCE CIRCUITBREAKER. VERIFY POWER CONTINUATION OF EXISTINGFIXTURES AND DEVICES INDICATED TO REMAIN.

3. REMOVE EXISTING LIGHT FIXTURES, EXIT LIGHTS, ANDEMERGENCY BATTERY LIGHTS WITHIN THE AREA OFCONSTRUCTION, UNLESS OTHERWISE NOTED.

4. REMOVE EXISTING LIGHT SWITCHES, WALL PLATES, ANDASSOCIATED WIRING WITHIN THE AREA OF CONSTRUCTION,UNLESS OTHERWISE NOTED.

5. EXISTING LIGHT SWITCHES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECT LIGHTSWITCH TO EXISTING WIRING AS INDICATED. REPLACE WALLPLATE TO MATCH.

6. EXISTING RECESSED DEVICE BOXES FOR NOTED LIGHTSWITCHES AND RECEPTACLES AND ASSOCIATED CONCEALEDRACEWAY SHALL REMAIN FOR USE WITH NEWCONSTRUCTION.

7. PROVIDE A BLANK WALL PLATE FOR ALL EXISTING RECESSEDDEVICE BOXES NOT USED FOR NEW CONSTRUCTION.PROVIDE GANGING OF WALL PLATE AS REQUIRED TO COVEREXISTING DEVICE BOX.

8. REMOVE EXISTING RECEPTACLES AS INDICATED. REMOVEASSOCIATED BRANCH CIRCUIT WIRING BACK TO SOURCECIRCUIT BREAKER. VERIFY POWER CONTINUATION OFEXISTING RECEPTACLES INDICATED TO REMAIN.

9. EXISTING RECEPTACLES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECTRECEPTACLE TO EXISTING WIRING AS INDICATED. REPLACEWALL PLATE TO MATCH.

10. REMOVE EXISTING VOICE/DATA OUTLETS AS INDICATED.REMOVE VOICE/DATA CABLES BACK TO PATCH PANEL.EXISTING RECESSED BOXES AND CONCEALED RACEWAYSHALL REMAIN FOR FUTURE USE. PROVIDE BLANK WALLPLATES TO COVER EXISTING DEVICE BOXES.

11. REPLACE EXISTING BLANK WALL PLATES WITH WALL PLATESMATCHING PLATES OF DEVICES USED IN NEWCONSTRUCTION.

12. REMOVE EXISTING EXPOSED CONDUIT AND SURFACERACEWAY ON FINISHED WALLS, UNLESS USED FOR NEWCONSTRUCTION.

13. REMOVE EXISTING ACCESS CONTROL SYSTEM DEVICES ANDASSOCIATED WIRING.

14. SEAL FIRE RATED WALLS, FLOORS AND STRUCTURAL CEILINGFROM REMOVED RACEWAY AND SLEEVES MATCHING FIRERATING OF EXISTING ASSEMBLY.

15. REMOVE ALL EXISTING ACCESSIBLE POWER WIRING, DATACABLES, AND ASSOCIATED RACEWAYS NOT BEING USED FORNEW CONSTRUCTION.

17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.

17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.

16. REMOVE EXISTING SURFACE MOUNTED RECEPTACLES ANDASSOCIATED SURFACE RACEWAY. VERIFY POWERCONTINUATION AND TERMINATE BRANCH CIRCUIT WIRING INNEAREST ACCESSIBLE JUNCTION BOX. REMOVE EXISTINGBRANCH CIRCUIT WIRING BACK TO SOURCE CIRCUITBREAKER FOR DEDICATED RECEPTACLES.

17. REMOVE EXISTING SURFACE MOUNTED VOICE/DATA OUTLETSAND ASSOCIATED SURFACE RACEWAY. REMOVE VOICE/DATACABLES BACK TO PATCH PANEL.

18. REMOVE EXISTING FIRE ALARM SYSTEM AND ASSOCIATEDCABLING. EXISTING RECESSED DEVICE BOXES ANDCONCEALED RACEWAY SHALL REMAIN AND BE USED FORNEW CONSTRUCTION IF MOUNTING HEIGHT IS PER NFPAGUIDELINES. EXISTING FIRE ALARM SYSTEM SHALL REMAININ OPERATION UNTIL NEW SYSTEM IS INSTALLED.

Page 17: C:UserschanceyDocumentsElectrical - Details - 2014 - Sheet ... Drawings_MEC.pdf · 25. lamps and lighting fixtures shall be as described in light fixture schedule on the drawings.

RY

M CHNC

R

EGIS TERE

D

ST

V I R GI

SIONAL EN

13460

STATE OF

AI

N

WE R

EE

NIG

PROF

ES

GA Y

E

. A

RTU

RTU

EF

R

R

E

Owner / Client:

Project Number

Date:

Drawing Title:

Scale:

Drawing Number:

© Desmone Architects 2015

Revisions:

Seal:

Fo

r

O N E D O U G H B O Y S Q U A R E3 4 0 0 B U T L E R S T R E E T

P I T T S B U R G H, P A 1 5 2 0 1T E L : 4 1 2. 6 8 3. 3 2 3 0F A X : 4 1 2. 6 8 3. 3 5 6 3w w w . d e s m o n e . c o m

1/8" = 1'-0"

Z:\

ME

P C

UR

RE

NT

PR

OJE

CT

S\D

esm

on

e A

rch

itects

- J

ob

s\D

ES

MO

NE

-ME

P15-0

3 -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter-

Ph

ase II\R

evit

& C

AD

\E -

Mo

rgan

tow

n E

nte

rpri

se C

en

ter

Off

ice.r

vt

ED-103

Roof DemolitionPlan

Monongalia County DevelopmentAuthority

Morg

anto

wn E

nte

rprise C

ente

r O

ffic

e B

uild

ing

3942

08.26.2015

955 H

art

man

Ru

n R

oad

Mo

rgan

tow

n, W

V 2

6505

Inte

rio

r &

Exte

rio

r R

en

ovati

on

s

08.2

6.2

015

1/8" = 1'-0"1

DEMO - Roof Floor Power Plan

GENERAL DEMOLITION NOTES1. ALL DEVICES AND EQUIPMENT SHOWN ON THE ELECTRICAL

DEMOLITION PLAN ARE FOR REFERENCE ONLY AND SHALL BEFIELD VERIFIED BEFORE STARTING WORK. NOTIFY A/E IFDEVICES AND EQUIPMENT NOT SHOWN ON THE PLAN AREFOUND DURING DEMOLITION WORK.

2. REMOVE EXISTING BRANCH CIRCUIT WIRING FROM FIXTURESAND DEVICES BEING REMOVED BACK TO SOURCE CIRCUITBREAKER. VERIFY POWER CONTINUATION OF EXISTINGFIXTURES AND DEVICES INDICATED TO REMAIN.

3. REMOVE EXISTING LIGHT FIXTURES, EXIT LIGHTS, ANDEMERGENCY BATTERY LIGHTS WITHIN THE AREA OFCONSTRUCTION, UNLESS OTHERWISE NOTED.

4. REMOVE EXISTING LIGHT SWITCHES, WALL PLATES, ANDASSOCIATED WIRING WITHIN THE AREA OF CONSTRUCTION,UNLESS OTHERWISE NOTED.

5. EXISTING LIGHT SWITCHES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECT LIGHTSWITCH TO EXISTING WIRING AS INDICATED. REPLACE WALLPLATE TO MATCH.

6. EXISTING RECESSED DEVICE BOXES FOR NOTED LIGHTSWITCHES AND RECEPTACLES AND ASSOCIATED CONCEALEDRACEWAY SHALL REMAIN FOR USE WITH NEWCONSTRUCTION.

7. PROVIDE A BLANK WALL PLATE FOR ALL EXISTING RECESSEDDEVICE BOXES NOT USED FOR NEW CONSTRUCTION.PROVIDE GANGING OF WALL PLATE AS REQUIRED TO COVEREXISTING DEVICE BOX.

8. REMOVE EXISTING RECEPTACLES AS INDICATED. REMOVEASSOCIATED BRANCH CIRCUIT WIRING BACK TO SOURCECIRCUIT BREAKER. VERIFY POWER CONTINUATION OFEXISTING RECEPTACLES INDICATED TO REMAIN.

9. EXISTING RECEPTACLES INDICATED TO REMAIN SHALL BEREPLACED TO MATCH NEW CONSTRUCTION. CONNECTRECEPTACLE TO EXISTING WIRING AS INDICATED. REPLACEWALL PLATE TO MATCH.

10. REMOVE EXISTING VOICE/DATA OUTLETS AS INDICATED.REMOVE VOICE/DATA CABLES BACK TO PATCH PANEL.EXISTING RECESSED BOXES AND CONCEALED RACEWAYSHALL REMAIN FOR FUTURE USE. PROVIDE BLANK WALLPLATES TO COVER EXISTING DEVICE BOXES.

11. REPLACE EXISTING BLANK WALL PLATES WITH WALL PLATESMATCHING PLATES OF DEVICES USED IN NEWCONSTRUCTION.

12. REMOVE EXISTING EXPOSED CONDUIT AND SURFACERACEWAY ON FINISHED WALLS, UNLESS USED FOR NEWCONSTRUCTION.

13. REMOVE EXISTING ACCESS CONTROL SYSTEM DEVICES ANDASSOCIATED WIRING.

14. SEAL FIRE RATED WALLS, FLOORS AND STRUCTURAL CEILINGFROM REMOVED RACEWAY AND SLEEVES MATCHING FIRERATING OF EXISTING ASSEMBLY.

15. REMOVE ALL EXISTING ACCESSIBLE POWER WIRING, DATACABLES, AND ASSOCIATED RACEWAYS NOT BEING USED FORNEW CONSTRUCTION.

17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.

17.REMOVE EXISTING TYPE NM (ROMEX) CABLE IN AREA OFCONSTRUCTION. WHERE EXISTING ROMEX SUPPLIES POWERTO DEVICES ON FLOOR ABOVE, PROVIDE JUNCTION BOXWHERE ROMEX PENETRATES FLOOR AND INSTALL MC CABLEFROM JUNCTION BOX TO EXISTING PANEL. ROMEX CABLE ISNOT PERMITTED ABOVE ANY GRID CEILINGS.

16. REMOVE EXISTING SURFACE MOUNTED RECEPTACLES ANDASSOCIATED SURFACE RACEWAY. VERIFY POWERCONTINUATION AND TERMINATE BRANCH CIRCUIT WIRING INNEAREST ACCESSIBLE JUNCTION BOX. REMOVE EXISTINGBRANCH CIRCUIT WIRING BACK TO SOURCE CIRCUITBREAKER FOR DEDICATED RECEPTACLES.

17. REMOVE EXISTING SURFACE MOUNTED VOICE/DATA OUTLETSAND ASSOCIATED SURFACE RACEWAY. REMOVE VOICE/DATACABLES BACK TO PATCH PANEL.

18. REMOVE EXISTING FIRE ALARM SYSTEM AND ASSOCIATEDCABLING. EXISTING RECESSED DEVICE BOXES ANDCONCEALED RACEWAY SHALL REMAIN AND BE USED FORNEW CONSTRUCTION IF MOUNTING HEIGHT IS PER NFPAGUIDELINES. EXISTING FIRE ALARM SYSTEM SHALL REMAININ OPERATION UNTIL NEW SYSTEM IS INSTALLED.