POOL PROBLEMS
EvaporationEvaporation HumidityHumidity
ChlorineChlorine
TEMPERATURE & RELATIVE HUMIDITY
+2oC / 60% RH
26oC
The room air temperature and relative humidity is depending on the water temperature and the building structure of the swimming pool hall.
Normally the swimming pool air temperature is maintained at 2°C over the water temperature for comfort reasons.
The lower the air temperature the lower the evaporation from the pool surface. The higher the relative humidity the lower the evaporation from the pool surface.
TEMPERATURE & RELATIVE HUMIDITY
+2oC / 48% RH
30oC
The maximum absolute water contents in the air is according to VDI 2086 14.3 g/kg. Therefore the relative humidity in this example should not be higher then 48 % rh.
TEMPERATURE & RELATIVE HUMIDITY
-8oC / 50% RH
36oC
A special case are therapy pools where very often a water temperature of 36°C should be maintained.
Here the air temperature should be under the pool temperature because of comfort reasons for the personal.
CALCULATION AFTER VDI 2089
W =e x A x (Pb - Pl)
W = Evaporated water (g/h)
e = Faktor
Pb = Saturated vapour pressure pool water (mbar)
Pl = Partial vapour pressure air (mbar)
6 m
3 m
28°C
30°C / 53% 22,5 mbar
37,8 mbar
A = 6 x 3 = 18 m
Pb = 37,8 mbar
Pl = 22,5 mbar
e = 15 for privat pool
W= 15 x 18 x (37,8 – 22,5) = 4,13 l/h
CALCULATION AFTER VDI 2089
The amount of fresh air which is needed to dehumidify the swimming pool can be calculated as follows:
V = W / (Xi x Xu) x 1.2
V = Air volume (m3/h)
W = Evaporated water (g/h)
Xi = absolute water contents, inside air (g/kg)
Xu = absolute water contents, outside air (g/kg)
In practice this value is set to 9 g/kg in northern Europe.
1.2 = Density of the air (kg/m3)
V = 4130 / (14,3 – 9) x 1.2 = 650 m3/h
It is important that the air volume of the unit is about 3 – 5 times the volume of the swimming pool hall.
PROBLEM SOLUTIONS
1) Dehumidification and ventilation with a heat pump dehumidifier.
Cheap and simple solution but today normally only used in small private or hotel swimming pools because of high temperatures in the pool hall.
HEAT PUMP DEHUMIDIFIER
DanX AF
7 types with dehumidification capacities from 15 to 100 l/h
From pool
To the pool
Fresh air
PROBLEM SOLUTIONS
2) Dehumidification and ventilation with fresh air.
The first type of pool dehumidification, but today with
heat recovery. (Cross flow heat exchanger and /or a heat pump).
FRESH AIR VENTILATION
DanX XK
7 types with dehumidification capacities depending on air volume
To the pool
Fresh air From pool
Exhaust air
FRESH AIR VENTILATION
DanX XWP
18 types with dehumidification capacities from 10 to 140 l/h
To the pool
Fresh air From pool
Exhaust air
UNIT CONSTRUCTION
Cold bridge free painted construction
Specially protected heat exchanger and coils
Swimming Pool Hall VentilationXWPDAY TIME
15oC/95%19oC 22oC
28oC/55%13,1g/kg
34oC/22%6,9g/kg
9oC/80%5,7 g/kg
13oC
15oC
70%
34oC
34oC
20oC 23oC
28oC/55%13,1g/kg
35oC/28%10,3g/kg
35oC
15oC
Swimming Pool Hall VentilationXWPNIGHT TIME
20oC35oC
32oC/35%
30oC
30oC/60%15,9g/kg
18oC/80%10,5g/kg
40oC20oC
Swimming Pool Hall VentilationXWPCOOLING MODE
42oC/30%
26oC/50%10,5g/kg
26oC30oC/60%
OLD SYSTEM – NO HEAT RECOVERY
Euro
ENERGY CONSUMPTION
9/18 WP 9/18 XK 9/18Energy consumption total: Heating coil 36792 313864 481800 kwh/year
Power consumption total: Compressor 84717 0 0 kwh/yearFans 115880 88768 70664 kwh/year
Total kwh/year: Electicity 200597 88768 70664 kwh/yearFuel 36792 313864 481800 kwh/yearSurplus energy from the heat pump 84717 0 0 kwh/year
Cost: Price electricity 0,04 0,04 0,04 /kwhPrice fuel 0,28 0,28 0,28 /L
Cost electricity 8525 3773 3003 Euro/yearCost fuel 1010 8616 13226 Euro/year
Cost total 9535 12389 16229 Euro/year
Cost saving through surplus energy 2326 Euro/year
DanX CALCULATION PROGRAM