Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark Pierre J.C. Vogler-Finck, Henrik Lund Stærmose, Per Dahlgaard Pedersen Smart Energy Systems Conference Copenhagen, 11/09/2019
Transcript
Page 1: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

Data-driven control forefficient and flexible energy use

at building levelField investigations in Denmark

Pierre J.C. Vogler-Finck, Henrik Lund Stærmose, Per Dahlgaard Pedersen

Smart Energy Systems ConferenceCopenhagen, 11/09/2019

Page 2: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

2/

Outline

1- Presentation of Neogrid and its activities

2- PreHEAT: a heating control solution for buildings

3- Presentation of some use cases

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 3: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

3/

Neogrid Technologies ApS

Founded in 2009 in Aalborg (Denmark), currently 8 employees

Collaboration-oriented

Extensive experience in research and demonstration projects in the energy sector

Engaged in both national (Denmark) and international projects

Focus areas

Visualisation and monitoring technology for building heating

Data collection from ‘smart’ meters and IoT sensors

Energy-efficient and energy-flexible controllers

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 4: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

4/

Flexibility ‘in the real world’ in power systems

Annex concept workshop - Copenhagen - 09/09/2019 - (C) Neogrid 2019

Technology developed and demonstrated for heat-pump aggregated control.

Waiting for the flexibility market to take-off(still waiting…)

-> Business needed to look at another direction

Page 5: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

5/

Commercial platform capabilityfor research and demonstrationHardware Gateway supporting direct access for acquisition and control via: BMS systems (Modbus, Bacnet) Local wireless sensor network (Wireless Mbus) Custom box for direct interaction with valves of substation

Supporting online collection of large buildings Demonstrated on >1,100 measurement points per gateway Low latency communication for control (<1 minute)

Software Online visualisation dashboard

Web API for automated data exchange (https://neogrid-technologies.gitlab.io/neogrid-api/ )

Reading historical data Sending control setpoints A toolbox for Matlab and Python is available Demonstrated in research and demonstration environments

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 6: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

6/

Neogrid’s activity in the DH sector

IndicatorsYears of operation in Denmark >3 years

Number of buildings in pool >140Apartment blocks 104

Single family houses 31*Others (schools, offices,

institutions, …)7

Heated area covered >260,000 m2

Measurement points >25,000Entries in timeseries database 2.2 billion

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Technology development:

- Online data acquisition and monitoring

- Data-driven control technology

- Automated analytics

Services:

- Data collection and management

- Optimised control of supply temperature at central level

- Monitoring and reporting on performance

Page 7: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

7/

Control is made at central level with room feedback

: IoT sensing

: Communication

Predicts the heating demand Using models from historical

data weather dependency and

forecast Accounts for temperatures in

critical zones

Dynamically optimises the supply temperature Ensuring comfort in critical

zones Reducing pipe losses

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 8: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

8/

Providing services to different stakeholders For building owner/occupants

Condition monitoring (regular reporting and live view) Energy usage Indoor climate State of the installation and substation

Fault-detection (building operator is contacted) Abnormally high consumption Bad cooling in heat exchangers/loops Defect valves and other components in technical rooms Cost of fault (and ROI of fixing) can be quantified

Remote tuning of controller settings

For DH operators

Delivering demand forecasts (at building and aggregate level) Unlocking demand response from buildings

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 9: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

9/

Improved cooling and energy efficiency in a renovated apartment block

Example: [MA14 – Aalborg]Type Apartment blockConstruction 1960s (renovated)Heated area 1 132 m2

Energy class CTotal heat usage

90 MWh/yr.(80 kWh/m2/yr.)

0 2 4 6 8 10 12 14 16 18 20

Heating degree days per day [K]

4

6

8

10

12

14

Volu

me

cons

umpt

ion

per d

ay -

mai

n [m

3]

Sep-17

Oct-17

Nov-17

Dec-17 Jan-18

Feb-18

Mar-18

Apr-18

May-18 Jun-18

Jul-18

Aug-18

-25 %

-7 %

Baseline

(trend / R2 =87.0%)

With PreHEAT

(trend / R2 =76.0%)

0 2 4 6 8 10 12 14 16 18 20

Heating degree days per day [K]

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Ener

gy u

se p

er d

ay- m

ain

[MW

h]

Sep-17 Oct-17

Nov-17

Dec-17 Jan-18

Feb-18

Mar-18

Apr-18

May-18 Jun-18

Jul-18 Aug-18

-11 %

Baseline

(trend / R2 =89.3%)

With PreHEAT

(trend / R2 =93.7%)

Reduced energy demand

Reduced primary flow

Reduced supply temperature

(Occurred in early training)-15°C

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 10: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

10/

Improved energy efficiency in a pool of apartment blocks

Example: [GD –Taastrup]Type Apartment blocksConstruction 1970-80sHeated area 33 128 m2

Energy class (?)Total heat usage

(?)

Reduced energy demand

Cooling of DH water improved by 2-4 °C

Several malfunctions identified from the data and reported to building operator.

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 11: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

11/

Things aren’t always that simpleExample: [NG19 – Aalborg]

Type Apartment blockConstruction 1920sHeated area 2 003 m2

Energy class FTotal heat usage 152 MWh/yr.

(76 kWh/m2/yr.)

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 12: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

12/

Control of heating in an office buildingwith complex HVAC system

Example: [L21 – Aalborg]Type Office buildingConstruction 2005Heated area 1 851 m2

Energy class (?)Total heat usage

~85 MWh/yr.(46 kWh/m2/yr.)

Ventilation systems

2 (with heat recovery, hydronic heating & cooling)

Heating loops 4 (2 to ventilation, 1 floor, 1 radiator, 1 fan coil)

Gateway- integrated in Bacnet-based BMS - Collecting real time data from 792 points- Updating setpoints in real time control

Currently- Controlling the radiator heating - Investigating multizone control-oriented

modelling- Fault detection implemented

Aim- Integrated multizone model predictive

controller of HVAC system- Automated fault detection

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

IntelByg project with Bravida, and financed by the Danish ministry of energy

Page 13: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

13/

Conclusions

- Commercial technology for robust online cloud-based building data collection is available, including online control technology.

- Supply temperature in building heating can often be optimised for more efficiency.

- Documentation of savings is difficult, for ranges of ~10% savings.

- Energy efficiency is a way to get into the buildings, and cloud-based controllers infrastructure can support demand response at low extra cost.

- Flexibility enabling technology is ready and waiting, but there are major barriers to commercial delivery :- lack of clear quantifications of value of flexibility for system operators- absence of functioning appropriate markets.

SES conference - Copenhagen - 11/09/2019 - (C) Neogrid 2019

Page 14: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

14/

Neogrid Technologies ApSNiels Jernes vej 10, Aalborg Øst, Denmark / www.neogrid.dk

Contact: Pierre J.C. Vogler-Finck (R&D scientist)

+45 4280 0898 / [email protected] / Skype: pvf.neogrid

SES conference - Copenhagen - 09/09/2019 - (C) Neogrid 2019

Page 15: Data-driven control for efficient and flexible energy use · 2019-09-26 · Data-driven control for efficient and flexible energy use at building level Field investigations in Denmark

15/

Selected current projects

HEAT 4.0 – Digitally supported district heating ( https://energiforskning.dk/node/9356 )

Control to support integrated operation of DH systems Optimised heating control at central and zone level in houses and offices

FED – Flexible Energy Denmark ( https://energiforskning.dk/node/9406 )

Data-driven control to provide energy flexibility in Living Labs with a market environment Optimised control of residential building substations and local area supply in a DH system

SmartCE2H – Smart citizen-centered local electricity to heat systems ( https://energiforskning.dk/node/9297 )

Optimised control of large booster heat pumps to local areas in DH systems Collaborative control of building substations in local areas with booster heat pumps Optimised control of booster heat-pumps at building level for DHW production

SES conference - Copenhagen - 09/09/2019 - (C) Neogrid 2019