Data sheet 3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07fixed-mounted circuit breaker 3-pole, size I, IEC In=1250A to 690V,AC50/60Hz Icu=66kA at 500V frnt.conn. top/bot. dual-holeOvercurrent release ETU 45 LSIN protection adjustable 0.4-1 in withcubicle bus Opt.: Comm. /measuring func./ground fault/ ZSSMotorized/manual operating mechanism with memory Drive motor24-30 V DC Activation 24 V DC without 1st auxiliary release With 2ndauxiliary release "R", F3 Undervoltage, instant. 24 V DC 2NO+2NCC22= Ready indicator K07= Tripped signaling contact, 1 CO notpossible with option F02 N61= Cage spring connections for auxiliaryS07= Locking device in OFF position w. 4 bracket locks (safeOFF/disconnector functionality) Disconnector condition IEC 60947-2
ModelProduct brand name SENTRONProduct designation ACBDesign of the product IEC 60947-2Design of the auxiliary switch 2 NO + 2 NCDesign of the operating mechanism Pushbutton
3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07 Subject to change without noticePage 1/7 03/20/2019 © Copyright Siemens
Type of the driving mechanism Manual/motorized operating mechanism with mechanical andelectrical closing
Type of the driving mechanism / motor drive YesDesign of the overcurrent release ETU45B
General technical dataNumber of poles 3Size of the circuit-breaker 1Usage category Bcircuit-breaker / Design 3WL1
VoltageRated insulation voltage Ui 1 000 V
Protection classProtection class IP IP20Protection class IP / on the front IP20Protective function of the overcurrent release LSIN
DissipationPower loss [W] / for rated value of the current / at AC/ in hot operating state / per pole
35 W
ElectricityOperating current / at 45 °C / rated value 1 250 AContinuous current / rated value 1 250 AAdjustable pick-up value current
● of the current-dependent overload release /Full-scale value
1 250 A
● of instantaneous short-circuit trip unit / initialvalue
1 875 A
● of instantaneous short-circuit trip unit / Full-scale value
15 000 A
Main circuitOperating frequency
● 1 / rated value 50 Hz
● 2 / rated value 60 Hz
Operating voltage
● at AC / at 50/60 Hz / rated value 690 V
Operating current
● at 40 °C / rated value 1 250 A
● at 50 °C / rated value 1 250 A
● at 55 °C / rated value 1 250 A
● at 60 °C / rated value 1 250 A
● at 65 °C / rated value 1 250 A
● at 70 °C / rated value 1 210 A
3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07 Subject to change without noticePage 2/7 03/20/2019 © Copyright Siemens
Auxiliary circuitNumber of NC contacts / for auxiliary contacts 2Number of NO contacts / for auxiliary contacts 2
SuitabilitySuitability for use Plant / motor protection
Adjustable parametersAdjustable pick-up value current
● of the L-trip / with I4t characteristic / initial value 500 A
● of the L-trip / with I4t characteristic / Full-scalevalue
1 250 A
Adjustable pick-up value current / of the current-dependent overload release / initial value
500 A
Product detailsProduct component
● Trip indicator Yes
● Voltage trigger No
● undervoltage release Yes
Product extension / optional / motor drive No
Product functionProduct function
● Ground fault protection No
● Phase failure detection Yes
Display and operationDisplay version without display
Short circuitOperational short-circuit current breaking capacity(Ics)
● at 415 V / rated value 66 kA
● at 500 V / rated value 66 kA
● at 690 V / rated value 50 kA
Maximum short-circuit current breaking capacity (Icu)
● at 415 V / rated value 66 kA
● at 500 V / rated value 66 kA
● at 690 V / rated value 50 kA
ConnectionsArrangement of electrical connectors / for maincurrent circuit
Main connection top front/bottom double hole
Type of electrical connection / for main current circuit busbar connection
Mechanical DesignHeight 541 mm
3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07 Subject to change without noticePage 3/7 03/20/2019 © Copyright Siemens
Width 320 mmDepth 374 mmMounting type fixed mounting
Environmental conditionsAmbient temperature
● during operation / minimum -20 °C
● during operation / maximum 70 °C
● during storage / minimum -40 °C
● during storage / maximum 70 °C
CertificatesReference code
● acc. to DIN EN 61346-2 Q
● acc. to DIN EN 81346-2 Q
General Product Approval Declaration ofConformity
Test Certificates
Special Test Certi-ficate
Miscellaneous
Shipping Approval
Shipping Ap-proval
other
Environmental Con-firmations
Manufacturer De-claration
Miscellaneous
Further informationIndustry Mall (Online ordering system)https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)https://support.industry.siemens.com/cs/ww/en/ps/3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07
CAx-Online-Generatorhttp://www.siemens.com/cax
Tender specificationshttp://www.siemens.com/specifications
3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07 Subject to change without noticePage 4/7 03/20/2019 © Copyright Siemens
123.
527
5
10
15270
300
440
7632
7.5
401
45
106
127
20
130
150
5.5
8215
47
6
39
551
60 90 90
55
421
14
4040 80
80
58139
320
9
3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07 Subject to change without noticePage 5/7 03/20/2019 © Copyright Siemens
-Q
-Q1
-T1
L1L1
-T2
L2L2
-T3
L3L3
ETU45B-A1
X8.9
X8.1
0
-F5
L
I > S
I >> I
N N
In = 1250AIr = 500A-1250AIsd = 1562.5A-15000AIi = 1875A - 15000A; MAX=0.8*IcsIN = 0.5* In / 1* In / OFF
X8.1
X8.2
X8.3
X8.4
-S24
X7.1
4
X7.1
2
X7.1
3
-Y1
X6.7
X6.8
-S20
X6.6
X6.5
-F3
U <
X5.1
2X5
.11
M
-S11
X5.2
X5.1
X6.1
0X6
.9
-S1
X6.1
2X6
.11
X6.2
X6.1
-S2
X6.4
X6.3
L / L+
N / L-
L (Long Time Delay / Überlastschutz); S (Short Time Delay / Kurzschlussschutz, kurzzeitverzögert); I (Instantaneous / Kurzschlussschutz, unverzögert); N (Neutral Protection / Neutralleiterschutz);
S11 (Internal motor shutdown switch, if spring is tensioned / Interner Motorabstellschalter, wenn Feder gespannt); F3 (Undervoltage release / Unterspannungsauslöser);
F5 (Maglatch for trip unit / Auslösemagnet); S1 - S8 (Auxiliary switch / Hilfsschalter); S20 (Ready to close signalling switch / Einschaltbereitschaftsmeldeschalter);
S24 (1st trip signalling switch K07 (Reset position) / Erster Ausgelöstmeldeschalter K07 (Reset Position)); Y1 (Closing coil / Einschaltmagnet);
3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07 Subject to change without noticePage 6/7 03/20/2019 © Copyright Siemens
last modified: 03/14/2019
3WL1112-3EB34-6AJ2-Z C22+K07+N61+S07 Subject to change without noticePage 7/7 03/20/2019 © Copyright Siemens