further informationwebcode: GW-9428
GEMÜ 9428Motorized quarter turn actuator
Features• Low weight• Integrated manual override• Standard integral optical position indicator• Robust and low-wear because of the mechanically stable
design
DescriptionThe product is a motorized quarter turn actuator. The actuator is designed for DC or AC operating voltages. A manual overrideand an optical position indicator are integrated as standard. The torque in the end positions is increased. This enables a closingcurve matched to the valves.
Technical specifications• Torques: 6 to 35 Nm• Ambient temperature: -10 to 60 °C• Supply voltages: 12 V DC | 230 V AC, 50 Hz | 24 V DC
www.gemu-group.com2 / 22GEMÜ 9428
Product description1
3
4
56
2
Item Name Materials
1 Housing cover Actuator versions 1006, 1015, 2006, 2015: PPE + 30 % glassfibre reinforcedActuator version 3035: PP + 20 % glass bead reinforced
2 CONEXO RFID label (available upon request) Polyester (PET)
3 Optical position indicator PP-R natural
4 Housing base Actuator versions 1006, 1015, 2006, 2015: PP + 30 % glassfibre reinforcedActuator version 3035: PP + 20 % glass bead reinforced
5 Actuator flange
6 Connection for manual override
Product description
GEMÜ 9428www.gemu-group.com 3 / 22
Range overview
Voltage/FrequencyAvailability - GEMÜ 9428
Actuator versionCode 1)
Control moduleCode 2)
Voltage/Frequency
12 V DC(code B1)
12 V AC(code B4)
24 V DC(code C1)
24 V AC(code C4)
100-250 V AC(code O4)
1006 A0, AE X X X X -
1015 A0, AE X - X - -
2006 A0, AE - - - - X
2015 A0, AE - X - X X
3035 A0, AE - - X - X
1) Actuator versionCode 1006: Torque 6 Nm, operating time 4 s, actuator size 1, supply voltage B1, C1, B4, C4Code 1015: Torque 15 Nm, operating time 11 s, actuator size 1, supply voltage B1, C1Code 2006: Torque 6 Nm, operating time 4 s, actuator size 2, supply voltage O4Code 2015: Torque 15 Nm, operating time 11 s, actuator size 2, supply voltage B4, C4, O4Code 3035: Torque 35 Nm, operating time 15 s, actuator size 3, supply voltage C1, O4
2) Control moduleCode A0: On/Off actuatorCode AE: On/Off actuator with 2 additional, potential-free limit switches, Class A (EN15714-2)
Connection sizeActuatorversionCode
Connection size Code
G05 F03 F04 F05
1006 S08 S09 S09 S09/S11
1015 S08 S09 S09 S09/S11
2006 S08 S09 S09 S09/S11
2015 S08 S09 S09 S09/S11
3035 - - - S09/S11/S14
S08, S09, S11, S14 - square drive (code)
Range overview
Order dataThe order data provide an overview of standard configurations.
Please check the availability before ordering. Other configurations available on request.
Products ordered with bold marked ordering options are so-called preferred series.
Order codes1 Type Code
Motorized quarter turn actuator,optical position indicator,manual override
9428
2 Fieldbus Code
Without 000
3 Actuator use Code
Accessory Z
4 Actuator connection Code
Flange type DIN EN ISO 5211, F03 F03
Flange type DIN EN ISO 5211, F04 F04
Flange type DIN EN ISO 5211, F05 F05
Flange type G05 G05
5 Location spigot Code
Without location spigot N
With location spigot Y
6 Coupling and wrench size Code
Star, WAF = 8 mm S08
Star, WAF = 9 mm S09
Star, WAF = 11 mm S11
Star, WAF = 14 mm S14
7 Voltage/Frequency Code
12 V DC B1
12 V/50 - 60 Hz B4
24 V DC C1
24 V/50 - 60 Hz C4
100 - 250 V/50 - 60 Hz O4
8 Control module Code
On/Off actuator A0
On/Off actuator with 2 additional,potential-free limit switches,Class A (EN15714-2)
AE
9 Actuator version Code
Torque 6 Nm, operating time 4 s,actuator size 1,supply voltage B1, C1, B4, C4
1006
Torque 15 Nm, operating time 11 s,actuator size 1,supply voltage B1, C1
1015
Torque 6 Nm, operating time 4 s,actuator size 2,supply voltage O4
2006
Torque 15 Nm, operating time 11 s,actuator size 2,supply voltage B4, C4, O4
2015
Torque 35 Nm, operating time 15 s,actuator size 3,supply voltage C1, O4
3035
10 Type of design Code
1 Hirschmann connector N6R 6598
Parallel operation of several actuators 6410
2 Harting connectors Han 7D 6722
11 CONEXO Code
without
Integrated RFID chip for electronic identificationand traceability
C
Order exampleOrder option Code Description
1 Type 9428 Motorized quarter turn actuator,optical position indicator,manual override
2 Fieldbus 000 Without
Order data
www.gemu-group.com4 / 22GEMÜ 9428
Order option Code Description
3 Actuator use Z Accessory
4 Actuator connection G05 Flange type G05
5 Location spigot Y With location spigot
6 Coupling and wrench size S08 Star, WAF = 8 mm
7 Voltage/Frequency C1 24 V DC
8 Control module A0 On/Off actuator
9 Actuator version 1006 Torque 6 Nm, operating time 4 s,actuator size 1,supply voltage B1, C1, B4, C4
10 Type of design 6598 1 Hirschmann connector N6R
11 CONEXO without
Order data
GEMÜ 9428www.gemu-group.com 5 / 22
www.gemu-group.com6 / 22GEMÜ 9428
Technical data
TemperatureAmbient temperature: -10 to 60 °C
Storage temperature: 0 to 40 °C
Product complianceMachinery Directive: 2006/42/EC
EMC Directive: 2014/30/EU
Low VoltageDirective:
2014/35/EU
Electrical dataDuty cycle: Supply voltage 12 V / 24 V: Continuous duty
Supply voltage 100 - 250 V: 40 % duty
Electrical protection: Supply voltage 12 V / 24 V:Motor protective system by customerSupply voltage 100 - 250 V:Integrated stall and overload protectionplus excess current release T 1A 5x20 mm
Electrical protectionclass:
I (DIN EN 61140)
Electrical connectionCable diameter: Supply voltage 12 V / 24 V: 7.5 to 12.5 mm
Supply voltage 100 - 250 V: 7.0 to 9.0 mm
Max. cross section of wire: 1.5 mm²
Recommended motorprotection:
Voltage 12 V DC 24 V DC 120 V AC 230 V AC
Motor protectionswitch type
Siemens 3RV1011-1CA10
Siemens 3RV1011-1BA10
Siemens 3RV1011-OGA10
Siemens 3RV1011-OGA10
Set current 2.20 1.70 0.60 0.45
Current data in A
Rated voltage: 12 V / 24 V AC or DC (± 10 %)100 – 250 V AC (± 10 %)
Rated frequency: 50/60 Hz (at AC rated voltage)
Power consumption: Actuator ver-sion (code)
12 V DC 12 V AC 24 V DC 24 V AC 100-250 V AC
Code B1 Code B4 Code C1 Code C4 Code O4
1006 30 30 30 30 -
1015 30 - 30 - -
2006 - - - - 60
2015 - 30 - 30 50
3035 - - 30 - 50
Power consumption in W
Technical data
GEMÜ 9428www.gemu-group.com 7 / 22
Current consumption: Actuator ver-sion (code)
12 V DC 12 V AC 24 V DC 24 V AC 100-250 V AC
Code B1 Code B4 Code C1 Code C4 Code O4
1006 2.2 2 1.2 1.5 -
1015 2.2 - 1.2 - -
2006 - - - - 0.25
2015 - 2 - 1.2 0.2
3035 - - 1.3 - 0.2
Current data in A
Max. current at start up: Actuator ver-sion (code)
12 V DC 12 V AC 24 V DC 24 V AC 100-250 V AC
Code B1 Code B4 Code C1 Code C4 Code O4
1006 6.3 2.4 4.0 1.8 -
1015 9.2 - 3.8 - -
2006 - - - - 0.3
2015 - 2.3 - 1.8 0.4
3035 - - 3.3 - 0.2
Current data in A
Mechanical dataInstallation position: Optional
Protection class: IP 65 acc. to EN 60529
Weight: Supply voltage 12 V / 24 V: 1.0 kgSupply voltage 100-250 V: 1.2 kgSupply voltage 24 V / 100-250 V, actuator version 3035: 2.4 kg
Manual override: with Allen key SW3
Torques: Actuator version 1006, 2006: 6 NmActuator version 1015, 2015: 15 NmActuator version 3035: 35 Nm
Operating time: Actuator version 1006, 2006: approx. 4 sActuator version 1015, 2015: approx. 11 sActuator version 3035: approx. 15 s
Nominal travel: 90°
Max. travel: 93°
Setting range: 0 to 20° (limit switch Min.)70 to 93° (limit switch Max.)
Technical data
www.gemu-group.com8 / 22GEMÜ 9428
Dimensions
Actuator version 1006, 1015, 2006, 2015
AB
14540
8055C62*
* Standard with supply voltage code O4
Actuator ver-sion
A B C
1006, 1015 69 94 49
2006, 2015 96 122 53
Dimensions in mm
Actuator version 3035
66 76172 208
94B
Voltages B
24 V 100.5
100 V - 250 V 124.5
Dimensions in mm
Dimensions
GEMÜ 9428www.gemu-group.com 9 / 22
Connection dimensions actuator version (10XX, 20XX, 3035)
LK
G
SW
TDIN ISO 5211
Actuator version(code)
Connection size(code)
Location spigot(code)
SW G LK T
10XX / 20XX G05 Y S08 Ø5.5 48 15
10XX / 20XX F03 N S09 M5 36 16
10XX / 20XX F04 N S09 M5 42 16
10XX / 20XX F05 N S09 M6 50 16
10XX / 20XX F05 N S11 M6 50 16
3035 F05 Y S14 M6 50 22
Dimensions in mm
Dimensions
www.gemu-group.com10 / 22GEMÜ 9428
Electrical connection
Connection/wiring diagramON/OFF actuator (code A0)
12 V AC (code B4) / 24 V AC (code C4)
Assignment of the terminal strips
12345
Item Description
1 L1, supply voltage
2 N, supply voltage
3 L1, change-over (OPEN/CLOSE)
4 N, change-over (OPEN/CLOSE)
5 PE, protective earth conductor
Preferred direction -OPEN- when all signals are present
Connection diagram
Externalwiring
Term
inal
stri
p
Limit switch OPEN
Limit switch CLOSED
MotorUv L1
NPE
S1 S212345
S1 Actuator
0 OFF
1 ON
S2 Direction of travel
0 CLOSED
1 OPEN
Electrical connection
GEMÜ 9428www.gemu-group.com 11 / 22
100 - 250 V AC (code 04)
Position of the connectors
X1
Electrical connection
21
34
65
Plug assignment X1
Pin Description
1 L1, supply voltage
2 N, supply voltage
3 L1, direction of travel CLOSED
4 N, direction of travel CLOSED
5 L1, direction of travel OPEN
6 N, direction of travel OPEN
PE, protective earth conductor
The potential must be assigned by the user.
Connection diagram
1 26
53
4
L1
PEN
External wiring
OPENCLOSED
Electrical connection
www.gemu-group.com12 / 22GEMÜ 9428
12 V DC (code B1) / 24 V DC (code C1) / K-no. 6598
Position of the connectors
X1
Electrical connection
21
34
65
Plug assignment X1
Pin Description
1 Uv+, direction of travel CLOSED
2 Uv-, direction of travel CLOSED
3 Uv+, direction of travel OPEN
4 Uv-, direction of travel OPEN
5 n. c.
6 n. c.
PE, protective earth conductor
Connection diagram
S3Uv
1 26
53
4
CLOSED-0-OPEN
Externalwiring
S3 Actuator
CLOSED Direction of travel CLOSED
0 OFF
OPEN Direction of travel OPEN
Electrical connection
GEMÜ 9428www.gemu-group.com 13 / 22
12 V AC (code B4) / 24 V AC (code C4) / K-no. 6598
Position of the connectors
X1
Electrical connection
21
34
65
Plug assignment X2
Pin Description
1 L1, supply voltage
2 N, supply voltage
3 L1, change-over (OPEN/CLOSE)
4 N, change-over (OPEN/CLOSE)
5 n. c.
6 n. c.
PE, protective earth conductor
Preferred direction -OPEN- when all signals are present
Connection diagram
S2
S1
Uv
1 26
53
4
L1 N
0 1
0 1Externalwiring
S1 Actuator
0 OFF
1 ON
S2 Direction of travel
0 CLOSED
1 OPEN
Electrical connection
www.gemu-group.com14 / 22GEMÜ 9428
12 V DC (code B1) / 24 V DC (code C1) / K-no. 6410
Assignment of the terminal strips
12345
Item Description
1 Uv+, direction of travel CLOSED
2 Uv-, direction of travel CLOSED
3 Uv+, direction of travel OPEN
4 Uv-, direction of travel OPEN
5 PE, protective earth conductor
Connection diagram
PE
12345 S3
Uv
12345
Actuator
Actuator
(Actuator)
(Actuator)
Motor
Motor
S3 Actuator
CLOSED Direction of travel CLOSED
0 OFF
OPEN Direction of travel OPEN
12 V DC (code B1) / 24 V DC (code C1)
Assignment of the terminal strips
12345
Item Description
1 Uv+, direction of travel CLOSED
2 Uv-, direction of travel CLOSED
3 Uv+, direction of travel OPEN
4 Uv-, direction of travel OPEN
5 PE, protective earth conductor
Electrical connection
GEMÜ 9428www.gemu-group.com 15 / 22
Connection diagram
+ − PE
12345
0
S3
Limit switch OPEN
Limit switch CLOSED
Term
inal
stri
p
CLO
SED
OPE
N
Motor
Externalwiring
S3 Actuator
CLOSED Direction of travel CLOSED
0 OFF
OPEN Direction of travel OPEN
Electrical connection
www.gemu-group.com16 / 22GEMÜ 9428
ON/OFF actuator with 2 potential-free limit switches (code AE)
12 V DC (code B1) / 24 V DC (code C1)
Position of the connectors
X1 X2
S1/S2 UV
Actuator version 3035 Actuator version 1006, 1015
Electrical connection
21
34
65
21
34
65
Plug assignment X1, UV Plug assignment X2, S1/S2
Pin Description Pin Description
1 Uv+, direction of travel CLOSED 1 Change-over contact limit switch CLOSED
2 Uv-, direction of travel CLOSED 2 Make contact limit switch CLOSED
3 Uv+, direction of travel OPEN 3 Break contact limit switch CLOSED
4 Uv-, direction of travel OPEN 4 Break contact limit switch OPEN
5 n. c. 5 Make contact limit switch OPEN
6 n. c. 6 Change-over contact limit switch OPENPE, protective earth conductor PE, protective earth conductor
Connection diagram
S3Uv
1 26
53
4
CLOSED-0-OPEN
Externalwiring
1 4 2
61 2
35 4
142
OPEN CLOSED
Additional limit switches
Connection assignment X1, UV Connection assignment X2, S1/S2
S3 Actuator
CLOSED Direction of travel CLOSED
0 OFF
OPEN Direction of travel OPEN
Electrical connection
GEMÜ 9428www.gemu-group.com 17 / 22
12 V AC (code B4) / 24 V AC (code C4)
Position of the connectors
S1/S2UVS1/S2 UV
Actuator version 1006 Actuator version 2015
Electrical connection
21
34
65
21
34
65
Plug assignment X1, UV Plug assignment X2, S1/S2
Pin Description Pin Description
1 L1, supply voltage 1 Change-over contact limit switch CLOSED
2 N, supply voltage 2 Make contact limit switch CLOSED
3 L1, change-over (OPEN/CLOSE) 3 Break contact limit switch CLOSED
4 N, change-over (OPEN/CLOSE) 4 Break contact limit switch OPEN
5 n. c. 5 Make contact limit switch OPEN
6 n. c. 6 Change-over contact limit switch OPENPE, protective earth conductor PE, protective earth conductor
Preferred direction -OPEN- when all signals are present
Connection diagram
S2
S1
Uv
1 26
53
4
L1 N
0 1
0 1Externalwiring
1 4 2
61 2
35 4
142
OPEN CLOSED
Additional limit switches
Connection diagram X1, UV Connection diagram X2, S1/S2
S1 Actuator
0 OFF
1 ON
S2 Direction of travel
0 CLOSED
1 OPEN
Electrical connection
www.gemu-group.com18 / 22GEMÜ 9428
100-250 V AC (code 04)
Position of the connectors
S1/S2UVX1 X2
Actuator version 3035 Actuator version 2006, 2015
Electrical connection
21
34
65
21
34
65
Plug assignment X1, UV Plug assignment X2, S1/S2
Pin Description Pin Description
1 L1, supply voltage 1 Change-over contact limit switch CLOSED
2 N, supply voltage 2 Make contact limit switch CLOSED
3 L1, direction of travel CLOSED 3 Break contact limit switch CLOSED
4 N, direction of travel CLOSED 4 Break contact limit switch OPEN
5 L1, direction of travel OPEN 5 Make contact limit switch OPEN
6 N, direction of travel OPEN 6 Change-over contact limit switch OPENPE, protective earth conductor PE, protective earth conductor
The potential must be assigned by the user.
Connection diagram
1 26
53
4
L1
PEN
External wiring
OPENCLOSED 1 4 2
61 2
35 4
142
OPEN CLOSED
Additional limit switches
Connection diagram X1, UV Connection diagram X2, S1/S2
Electrical connection
GEMÜ 9428www.gemu-group.com 19 / 22
12 V DC (code B1) / 24 V DC (code C1) / K-no. 6722
Position of the connectors
X1 X2
Electrical connection
12
6
5
3 4
7
12
6
5
3 4
7
Plug assignment X1 Plug assignment X2
Pin Description Pin Description
1 Uv+, direction of travel CLOSED 1 Change-over contact limit switch CLOSED
2 Uv-, direction of travel CLOSED 2 Make contact limit switch CLOSED
3 Uv+, direction of travel OPEN 3 Break contact limit switch CLOSED
4 Uv-, direction of travel OPEN 4 Break contact limit switch OPEN
5 n. c. 5 Make contact limit switch OPEN
6 n. c. 6 Change-over contact limit switch OPEN
7 n. c. 7 n. c.PE, protective earth conductor PE, protective earth conductor
Connection diagram
S3
1265
3 4
7
Uv
External wiringCLOSED-0 - OPEN
1 4 2 142
1265
3 4
7
OPEN CLOSEDAdditional limit switches
Connection diagram X1 Connection diagram X2
S3 Actuator
CLOSED Direction of travel CLOSED
0 OFF
OPEN Direction of travel OPEN
Electrical connection
www.gemu-group.com20 / 22GEMÜ 9428
12 V AC (code B4) / 24 V AC (code C4) / K-no. 6722
Position of the connectors
X1 X2
Electrical connection
12
6
5
3 4
7
12
6
5
3 4
7
Plug assignment X1 Plug assignment X2
Pin Description Pin Description
1 L1, supply voltage 1 Change-over contact limit switch CLOSED
2 N, supply voltage 2 Make contact limit switch CLOSED
3 L1, change-over (OPEN/CLOSE) 3 Break contact limit switch CLOSED
4 N, change-over (OPEN/CLOSE) 4 Break contact limit switch OPEN
5 n. c. 5 Make contact limit switch OPEN
6 n. c. 6 Change-over contact limit switch OPEN
7 n. c. 7 n. c.PE, protective earth conductor PE, protective earth conductor
Preferred direction -OPEN- when all signals are present
Connection diagram
S2
S1L1 N
Uv
01
01
1265
3 4
7
Externalwiring
1 4 2 142
1265
3 4
7
OPEN CLOSEDAdditional limit switches
Connection diagram X1 Connection diagram X2
S1 Actuator
0 OFF
1 ON
S2 Direction of travel
0 CLOSED
1 OPEN
Electrical connection
GEMÜ 9428www.gemu-group.com 21 / 22
100-250 V AC (Code O4) / K-no. 6722
Position of the connectors
X1 X2
Electrical connection
12
6
5
3 4
7
12
6
5
3 4
7
Plug assignment X1 Plug assignment X2
Pin Description Pin Description
1 L1, supply voltage 1 Change-over contact limit switch CLOSED
2 N, supply voltage 2 Make contact limit switch CLOSED
3 L1, direction of travel CLOSED 3 Break contact limit switch CLOSED
4 N, direction of travel CLOSED 4 Break contact limit switch OPEN
5 L1, direction of travel OPEN 5 Make contact limit switch OPEN
6 N, direction of travel OPEN 6 Change-over contact limit switch OPEN
7 n. c. 7 n. c.PE, protective earth conductor PE, protective earth conductor
The potential must be assigned by the user.
Connection diagram
1265
3 4
7
L1
PEN
OPEN CLOSED
External wiring
1 4 2 142
1265
3 4
7
OPEN CLOSEDAdditional limit switches
Connection diagram X1 Connection diagram X2
Electrical connection
GEMÜ Gebr. Müller Apparatebau GmbH & Co. KGFritz-Müller-Straße 6-8, 74653 Ingelfingen-Criesbach, GermanyPhone +49 (0)7940 123-0 · [email protected]
Subj
ect t
o al
tera
tion
| 12.
2019
| 88
0486
88