Domestic Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE. 2. THIS MANUAL IS USED BY QUALIFIED APPLIANCE TECHNICIANS ONLY. 3. HAIER DOES NOT ASSUME ANY RESPONSIBILITY FOR PROPERTY DAMAGE OR PERSONAL INJURY FOR IMPROPER SERVICE PROCEDURES DONE BY ONE UNQUALIFIED PERSON. CAUTION DC Inverter Console Type
Transcript
Page 1: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

DomesticAir conditioner

HFU-09HA03/R(DB)HFU-12HA03/R(DB)HFU-18HA03/R(DB)

1. READ THIS MANUAL CAREFULLY TO

DIAGNOSE TROUBLE CORRECTLY

BEFORE OFFERING SERVICE.

2. THIS MANUAL IS USED BY QUALIFIED

APPLIANCE TECHNICIANS ONLY.

3. HAIER DOES NOT ASSUME ANY

RESPONSIBILITY FOR PROPERTY

DAMAGE OR PERSONAL INJURY FOR

IMPROPER

SERVICE PROCEDURES DONE BY ONE

UNQUALIFIED PERSON.

CAUTION

DC Inverter

Console Type

Page 2: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

stnetnoCfoelbaT

Table of Contents

1. Features.…………………………...…………………………..…….…….…............ 1

2. Specifications……….……………………………….……………. .….….……….. 2

3. Remote controller lists…….…………..………….….….……….………………... 5

4. Sensors lists…...….….…………………………………………………………........ 5

5. Dimensional drawings…………………………………………………………….....6

6. Operation range……………………………………...…………………………….....8

7. Piping diagrams……………………………………………………………. .…….... 9

8. Wiring diagrams………………………………………………….…………….........10

9. Performance curves diagrams ...............………………………………. ……...13

10. Sound level……………………………………………………… ………………...

11. Accessories……………………………………………………………………….. 38

12. Control systems…………………………………………………………………..

13. Center of gravity…………………………………………………………………..

39

40

14. Installations……………………………………………………………………..… 41

Domestic air conditioner

37

HFU-09,12,18HA03/R2(DB)

9.1 Cooling capacity-temperature curves..................................................................................13

9.2 Heating capacity-temperature curves………………………………………...........................

9.5 Cooling discharge pressure cu rves................................................................................... 259.6 Cooling suction pressure cu rves........................................................................................

9.7 Heating discharge pressure curves.....................................................................................31

9.8 Heating suction pressure curves........................................................................................

9.3 Cooling power consumption value curves..........................................................................19

power consumption value curves..........................................................................9.4 Heating

16

28

34

The end 42…….........................................................................................................

22

Page 3: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Carpet airflow: This setting blows air from upper outlet only or from both upper and lower outlet

Dry function: Make dehumidifying in the room when the unit is working in the "DRY" mode

Child lock: Avoid the child's wrong operation on the remote controller

24 Hour timer: Use the timer function to set on,or off,or from on to off,or from off to on

Auto restart: The function permits automatic return to previous peration conditions

Easy clean design: The panel is easy to wash and the airflow vents can be detached withoutany special tools for quick cleaning of the inside of the air conditioner

Sleep mode: The setting temprature and the indoor noise can be adjusted to a morecomfortable level when you set the "sleep mode"during night sleep

4 Fan setting: Slect the fan speed LO,MED,HI,AUTO

Entire auto mode: You can set a tempreture value,with which the unit can be adjustedtheoperation mode automatically

1

Features

Domestic air conditioner

1. Features

HFU-09,12,18 HA03/R2(DB)

HFU-09,12 HA03/R2(DB) HFU-18 HA03/R2(DB)

Page 4: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Specifications

2 Domestic Air Conditioner

2. Specifications

NOMINALCAPACITY and NOMINAL INPUT

Model HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB)

Cooling(1) min.~norm.~max. w 750.~2600.~3200. 850.~3600.~4200. 1050.~5000.~5800. NORMINAL

CAPACITY(3-4) Heating(2) min.~norm.~max. w 800.~3200.~4000. 1000.~4000.~4500. 1200.~6000.~7000.

Cooling min.~norm.~max. w 300.~760.~1150. 320.~1100.~1450. 420.~1550.~2100. NORMINAL

INPUT Heating min.~norm.~max. w 350.~880.~1200. 380.~1100.~1600. 550.~1650.~2300.

EER Cooling 3.42 3.27 3.23

COP Heating 3.63 3.63 3.63

ANNUAL ENERGY

CONSUMPTION(9) Cooling kwh 400 540 750

TECHNICAL SPECIFICATIONS

INDOOR UNITS HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB)

H mm 640 640 640

W mm 720 720 720 DIMENSIONS Unit

D mm 255 255 255

WEIGHT Unit KG 17 17.5 17.5

COLOR Unit WHITE WHITE WHITE

high dB(A) 42/41 44/43 48/47

medium dB(A) 39/38 41/40 45/43 Sound

pressure(cooling/heating)(5) low dB(A) 37/35 38/36 42/40

SOUND

LEVEL Sound

power(cooling/heating)(6) high dB(A) 52/51 54/53 58/57

high m3 /min 7.5 8.5 11

medium m3 /min 6 7.5 9.5

Air flow

rate(cooling/h

eating) low m3 /min 4.8 6 8.5

steps 4steps,silent and auto 4steps,silent and auto 4steps,silent and auto

high rpm 900 1000 1200

medium rpm 850 975 1125

Speed(cooling

/heating)

low rpm 800 850 1050

Type Cross flow fan Cross flow fan Cross flow fan

FAN

Motor output(upper/lower) 20/11 20/11 20/11

AIR FILTER Removable/washable/

mildew proof

Removable/washable/

mildew proof

Removable/washable/

mildew proof

REMOTE CONTROLLER YR-H05 YR-H05 YR-H05

liquid mm 6.35 6.35 6.35

gas mm 9.52 9.52 12.7

PIPING

CONNECTIONS(external

diameter) drain mm 16 16 16

INSULATION MATERIAL

Heat insulation type

both liquid and gas

pipes

both liquid and gas

pipes

both liquid and gas

pipes

Page 5: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Specifications

3

TECHNICAL SPECIFICATIONS

OUTDOOR UNITS HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB)

H mm 543 543 680

W mm 783 783 813

NET DIMENSIONS(stop

valve, and bottom

supportis not included)

Unit

D mm 255 255 312

WEIGHT Unit KG 31 33 44

COLOR Unit Ivory white Ivory white Ivory white

Sound

pressure(cooling/heating)(5) high dB(A) 55/55 55/55 57/58

SOUND

LEVEL Sound

power(cooling/heating)(6) high dB(A) 65/65 65/65 67/68

high m3 /min 30.2/26.5 30.2/26.5 31.3/27.7 Air flow

rate(cooling/heating) low m3 /min 18.7/15.3 18.7/15.3 20.5/16.8

high rpm 800 800 840 Speed(cooling/heating)

low rpm 500 500 500

Type Propeller fan Propeller fan Propeller fan

FAN

Motor output 20 20 35

Refrigerant type R410A R410A R410A

Refrigerant charge kg 0.65 1.0 1.1

Maximum allowable distance

between indoor and outdoor m 15 15 20

Maximum allowable level difference m 7 7 10

REFRIGERANT

CIRCUIT

Refrigerant control Capillary Capillary Capillary

Type DC Inverter DC Inverter DC Rotary

Model DA89X1C-20FZ DA108X1C-20FZ3 5CS130XCC03

Motor output W 690 855 1405

Oil type ESTER OIL VG74 ESTER OIL VG74 ESTER OIL VG74

COMPRESSOR

Oil charge volume ml 370 480 480

liquid mm 6.35 6.35 6.35

gas mm 9.52 9.52 12.7 PIPING

CONNECTIONS drain mm 16 16 16

INSULATION MATERIAL Heat insulation type both liquid and gas

pipes

both liquid and gas

pipes

both liquid and gas

pipes

Domestic Air Conditioner

Page 6: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Specifications

4

ELECTRICAL SPECIFICATIONS

Model HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB)

Phase 1PH 1PH 1PH

Frequency Hz 50 50 50

NORMINAL

DISTRIBUTION

SYSTIEM

VOLTAGE Voltage V 230V~ 230V~ 230V~

Cooling A 3.5 5.0 6.8 Norminal running

current Heating A 4.0 5.0 7.3

Cooling A 5.8 7.5 10.2 Maximum running

current Heating A 5.3 7.0 10.2

Cooling A 1.1 1.2 1.5

CURRENT

Starting current Heating A 1.1 1.2 1.5

Domestic Air Conditioner

NOTES

1 Nominal cooling capacities are based on: indoor temperature 27°CDB/19°CWB * outdoor temperature 35°CDB * refrigerant piping length:5m * level difference: 0m.

2 Nominal heating capacities are based on: indoor temperature 20°CDB * outdoor temperature 7°CDB/6°CWB * refrigerant piping length5m (horizontal) * level difference 0m.

3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.4 Units should be selected on nominal capacity. Maximum capacity is limited to peak periods.5

6 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.7 Energy label: scale from A (most efficient) to G (less efficient).8 The energy label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European

official Standard.9 Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)

The sound pressure level is measured in an anechoic room at 1m distance from the unit. It is a relative value, depending on the distanceand acoustic environment. For measuring conditions: please refer to item 8 of this chapter.

Page 7: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Specifications

5 Domestic Air Conditioner

3. Remote controller lists

4. Sensors lists

Mode HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB)

YR-H05 Y Y Y

INDOOR UNIT

Description Value Qty

Room sensor It's used for detecting room temperature 1

Pipe sensor It's used for detecting temperature of evaporator 1

OUTDOOR UNIT

Ambient sensor It's used for detecting temperature outdoor side 1

Defrosting sensor It's used for controlling outdoor defrosting at heating mode 1

Descharging sensor It's used for protecting compressor in case of over-heat 1

Page 8: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Dimensional Drawings

6 Domestic Air Conditioner

5. Dimensional Drawings

Indoor

Page 9: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Dimensional drawings

7

Domestic air conditioner

Outdoor unit

HFU-09,12HA03/R2(DB)

HFU-09,12,18HA03/R2(DB)

2-way valve6.35mm(1/4")

6.35mm(1/4")3-way valve

9.52mm(3/8")

HFU-18HA03/R2(DB)

2-way valve6.35mm(1/4")

3-way valve

12.7mm(1/2")

8060

146

680

813

352

583

312

319.

5

837

6.35mm(1/4")

55

783

543

255840

68

74

Page 10: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

8

HFU-09,12,18 HA03/R2(DB) Operation range

Domestic air conditioner

Cooling

50

Out

door

tem

p.D

B

4640 43

nwodllup03

2018

10

0 16 23 3210 20 30

indoor temp WB

25gnitaeH42

20

outd

oort

emp

WB

Out

door

tem

p.

15

10

5

0

-5

-10

-15

10 20 30indoor temp DB

NotesThe graphs are based on the following conditionEquivalent piping length 7.5mLevel difference 0m

hgihetar wolf riA

outd

oort

emp

Page 11: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

F ,12,18 HA 2 (D

9

Page 12: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Wiring Diagrams

10 Domestic Air Conditioner

8. Wiring Diagrams Indoor(for 09/12 unit)

R:RED

B:BLACK

W:WHITE

Y/G:YELLOW/GREEN

Y/G

NOTES:THE DOTTED PARTS ARE OPTIONAL

BL:BLUE

BR:BROWN

Page 13: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Wiring Diagrams

11 Domestic Air Conditioner

Indoor(for 18 unit)

R:RED

B:BLACK

W:WHITE

Y/G:YELLOW/GREEN

Y/G

NOTES:THE DOTTED PARTS ARE OPTIONAL

Page 14: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Wiring Diagrams

12 Domestic Air Conditioner

Outdoor(for 09/12 unit)

0010510022

TO BILATERAL FRESH AIR MOTOR

TO FRESH AIR MOTOR

DC MOTOR AC MOTOR VALVEEXPANSION

FOUR-WAY VALVE

TO INDOOR UNITBLOCK

TERMINAL

REACTOR

B:BLACK

BL:BLUE

R:REDW:WHITE

NOTES:

DISCHARGE TEMP.SENSOR

AMBIENT TEMP.SENSOR

SUCTION TEMP.SENSOR

DEFROST TEMP.SENSOR

WIRING DIAGRAM OF OUTDOOR UNIT

NOTESWARNING

DON'T TOUCH CAPACITOR, EVEN AFTER

PLUG-OFF ( DANGER OF ELECTRIC SHOCK)

The capacitor retains high voltage even after the plug-off. For your safety, be sure to wait at least 5 minutes. after plug off and use a tester to confirm the voltage between connector CN301 and CN302 is less than DC 10V before start servicing.

FUS

E2

CN25

FUSE1

ELC

TRIC

H

EATI

NG

C

AB

LE

CN24

CN23

NOTES:THE DOTTED PARTS ARE OPTIONAL.

T25A/250VAC

CN13

CN10

CN11

(CN7)

(CN6)

AC-NAC-L

W

CN12

CN14 CN8 CN7

CN16

LI

LO W

(CN8)(CN9)

CN11

CN10

POWER MODULE

CN3

CN4

CN5

Outdoor(for 18 unit)

T25A/250VAC

0010562188OUTDOOR UNIT WIRING DIAGRAM

DON'T TOUCH CAPACITOR, EVEN AFTER

PLUG-OFF ( DANGER OF ELECTRIC SHOCK)

The capacitor retains high voltage even after the plug-off. For your safety, be sure to wait at least 5 minutes. after plug off and use a tester to confirm the voltage between connector P and N is less than DC 10V before start servicing.

WARNINGCAUTION

/GREENY/G:YELLOWW: WHITE

OR:ORANGEBL:BLUE

B: BLACKR: RED

TERMINAL BLOCK

Double-way air exchange MOTOR

POWER SUPP

LY

TO INDOOR

REACTORCOMPRESSOR

CAP BOARD

OUTDOOR PCB

(CN3)

(CN4)

AC-NAC-L

NOTES:THE PARTS OF DOTTED ARE OPTIONAL

W

P512

LI

LO W

(CN1)(CN2)

DEFROST TEMP.SENSOR

COMP.TEMP.SENSOR

AMBIENT TEMP.SENSOR

SUCTION.TEMP.SENSOR

EXPANSION VALVEELECTRIC 4-WAY VALVE

FUSE

MODULE BOARD

CN10

CN11

FLITER

R

Single-way air exchange MOTOR

DC FAN MOTOR AC FAN MOTOR

Page 15: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Domestic air conditioner13

9 Performance Curves Diagram9.1 Cooling Capacity-temperature Curves

HFU-09,12,18 HA03/R2(DB) Performance Curves

indoor temp.

DB/WB 18℃ 20℃ 25℃ 32℃ 35℃ 40℃ 43℃ 46℃

18/12℃ 2127 1976 1859 1779 1617 1400 1317 1198

18/14℃ 2254 2095 1910 1828 1700 1475 1367 1248

20/15℃ 2353 2169 2003 1917 1821 1631 1469 1348

22/16℃ 2561 2333 2174 2080 1992 1829 1617 1483

25/18℃ 2688 2547 2412 2308 2247 2075 1842 1662

27/19℃ 2892 2734 2642 2529 2437 2250 2075 1877

30/22℃ 2965 2844 2728 2611 2525 2367 2200 2021

32/23℃ 3080 2956 2847 2724 2650 2550 2375 2216

32/24℃ 3122 2998 2924 2798 2742 2625 2433 2293

outdoor temp.(humidity 46%)

cooling capacity and indoor/outdoor temp.talbeHFU-09HA03/R2(DB) performance curves

Cooling capacity and indoor/outdoor temp.curves

1000

1500

2000

2500

3000

18/12℃

18/14℃

20/15℃

22/16℃

25/18℃

27/19℃

30/22℃

32/23℃

32/24℃

indoor tempe.(DB/WB)

pow

er c

onsu

mpt

ion(

w)

18℃

20℃

25℃

32℃

35℃

40℃

43℃

46℃

Page 16: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18 HA03/R2(DB) Performance Curves

14 Domestic Air Conditioner

indoor temp.

DB/WB 18℃ 20℃ 25℃ 32℃ 35℃ 40℃ 43℃ 46℃

18/12℃ 3130 2910 2720 2524 2377 2200 1940 1577

18/14℃ 3310 3080 2840 2684 2530 2283 2020 1706

20/15℃ 3503 3300 2990 2840 2634 2366 2160 1783

22/16℃ 3750 3440 3210 3020 2770 2541 2310 1990

25/18℃ 3871 3663 3466 3276 3140 2797 2593 2198

27/19℃ 4091 3970 3797 3588 3420 3151 2889 2469

30/22℃ 4250 4070 3920 3740 3550 3330 3110 2804

32/23℃ 4390 4251 4091 3940 3830 3606 3360 3030

32/24℃ 4459 4312 4201 3970 3870 3695 3440 3090

outdoor temp.(humidity 46%)

cooling capacity and indoor/outdoor temp.talbe

HFU-12HA03/R2(DB) performance curves

Cooling capacity and indoor/outdoor temp.curves

1500

2000

2500

3000

3500

4000

4500

18/12℃

18/14℃

20/15℃

22/16℃

25/18℃

27/19℃

30/22℃

32/23℃

32/24℃

indoor tempe.(DB/WB)

pow

er c

onsu

mpt

ion(

w) 18℃

20℃

25℃

32℃

35℃

40℃

43℃

46℃

Page 17: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18 HA03/R2(DB) Performance Curves

15 Domestic Air Conditioner

indoor temp.

DB/WB 18℃ 20℃ 25℃ 32℃ 35℃ 40℃ 43℃ 46℃

18/12℃ 4399 4036 3771 3465 3061 2720 2386 2062

18/14℃ 4571 4144 3905 3571 3110 2780 2524 2231

20/15℃ 4748 4274 4091 3734 3404 3020 2541 2332

22/16℃ 5193 4785 4360 4052 3795 3338 2868 2602

25/18℃ 5451 5038 4825 4558 4315 3850 3262 2873

27/19℃ 5762 5408 5202 5039 4840 4320 3796 3228

30/22℃ 5921 5626 5430 5250 5050 4570 4086 3666

32/23℃ 6214 5847 5605 5410 5250 4770 4482 4039

32/24℃ 6280 5929 5756 5530 5361 4930 4636 4173

outdoor temp.(humidity 46%)

cooling capacity and indoor/outdoor temp.talbe

HFU-18HA03/R2(DB) performance curves

Cooling capacity and indoor/outdoor temp.curves

2000

2500

3000

3500

4000

4500

5000

5500

6000

6500

18/12℃

18/14℃

20/15℃

22/16℃

25/18℃

27/19℃

30/22℃

32/23℃

32/24℃

indoor tempe.(DB/WB)

pow

er c

onsu

mpt

ion(

w) 18℃

20℃

25℃

32℃

35℃

40℃

43℃

46℃

Page 18: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

9.2 Heatling Capacity-temperature Curves

HFU-09,12,18 HA03/R2(DB) Performance Curves

outdoor temp.

DB/WB 15℃ 20℃ 25℃

-10℃ 2488 2116 1745

-5℃ 3010 2293 1816

5℃ 3228 2578 2107

7/6℃ 3626 3027 2481

15℃ 4300 3636 3112

20℃ 3947 3335 2937

25℃ 3782 3316 3053

indoor temp.(humidity 46%)

heating capacity and indoor/outdoor temp.curves

HFU-09HA03/R2(DB) performance curves

Heating capacity and indoor/outdoor temp.curves

1500

2000

2500

3000

3500

4000

4500

1 2 3 4 5 6 7

indoor tempe.(DB/WB)

cono

ling

capa

city

(w)

15℃

20℃

25℃

16Domestic Air Conditioner

Page 19: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.

DB/WB 15℃ 20℃ 25℃

-10℃ 2874 2423 1885

-5℃ 3010 2550 2120

5℃ 3228 2850 2330

7/6℃ 4160 3667 2930

15℃ 4660 4130 3410

20℃ 3900 3650 3150

25℃ 3782 3500 3053

indoor temp.(humidity 46%)

heating capacity and indoor/outdoor temp.curves

HFU-12HA03/R2(DB) performance curves

Heating capacity and indoor/outdoor temp.curves

1500

2000

2500

3000

3500

4000

4500

5000

1 2 3 4 5 6 7

indoor tempe.(DB/WB)

cono

ling

capa

city

(w)

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

17Domestic Air Conditioner

Page 20: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.

DB/WB 15℃ 20℃ 25℃

-10℃ 4426 3780 2884

-5℃ 4635 3978 2953

5℃ 4971 4446 3565

7/6℃ 6406 5721 4483

15℃ 7176 6443 5217

20℃ 6006 5694 4820

25℃ 5824 5460 4671

indoor temp.(humidity 46%)

heating capacity and indoor/outdoor temp.curves

HFU-18HA03/R2(DB) performance curves

Heating capacity and indoor/outdoor temp.curves

2500

3000

3500

4000

4500

5000

5500

6000

6500

7000

7500

1 2 3 4 5 6 7

indoor tempe.(DB/WB)

cono

ling

capa

city

(w)

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

18Domestic Air Conditioner

Page 21: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Domestic air conditioner19

9.3 Cooling Power Consumption Value-temperature Curves

indoor temp.

DB/WB 18℃ 20℃ 25℃ 32℃ 35℃ 40℃ 43℃ 46℃

18/12℃ 387 503 549 616 687 774 823 897

18/14℃ 401 521 581 652 704 802 869 931

20/15℃ 413 537 596 669 722 826 901 969

22/16℃ 427 555 615 691 735 835 922 993

25/18℃ 442 575 629 707 758 868 967 1047

27/19℃ 452 587 653 733 796 919 1012 1103

30/22℃ 488 634 695 797 881 1003 1088 1196

32/23℃ 542 704 777 865 981 1100 1170 1276

32/24℃ 571 743 804 902 1032 1139 1210 1289

outdoor temp.(humidity 46%)

cooling power consumption value-temp.talbe

HFU-09HA03/R2(DB) performance curves

Cooling power consumption value-temp.curves

300

400

500

600

700

800

900

1000

1100

1200

1300

18/12℃

18/14℃

20/15℃

22/16℃

25/18℃

27/19℃

30/22℃

32/23℃

32/24℃

indoor tempe.(DB/WB)

pow

er c

onsu

mpt

ion(

w)

18℃

20℃

25℃

32℃

35℃

40℃

43℃

46℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

Page 22: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

indoor temp.

DB/WB 18℃ 20℃ 25℃ 32℃ 35℃ 40℃ 43℃ 46℃

18/12℃ 497 585 687 760 831 895 987 1108

18/14℃ 512 607 713 787 857 957 1024 1149

20/15℃ 532 632 742 853 930 972 1066 1197

22/16℃ 566 648 760 874 969 1023 1092 1226

25/18℃ 596 683 802 921 996 1068 1152 1293

27/19℃ 648 733 845 971 1083 1125 1213 1362

30/22℃ 697 818 942 1052 1166 1236 1316 1477

32/23℃ 755 905 1027 1159 1263 1336 1404 1576

32/24℃ 779 938 1077 1178 1303 1365 1418 1592

outdoor temp.(humidity 46%)

cooling power consumption value-temp.talbe

HFU-12HA03/R2(DB) performance curves

Cooling power consumption value-temp.curves

400

600

800

1000

1200

1400

1600

18/12℃

18/14℃

20/15℃

22/16℃

25/18℃

27/19℃

30/22℃

32/23℃

32/24℃

indoor tempe.(DB/WB)

pow

er c

onsu

mpt

ion(

w)

18℃

20℃

25℃

32℃

35℃

40℃

43℃

46℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

20Domestic Air Conditioner

Page 23: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

indoor temp.

DB/WB 18℃ 20℃ 25℃ 32℃ 35℃ 40℃ 43℃ 46℃

18/12℃ 619 831 961 1038 1105 1282 1422 1591

18/14℃ 632 863 997 1077 1193 1371 1475 1651

20/15℃ 677 898 1038 1171 1279 1392 1568 1718

22/16℃ 710 920 1064 1201 1365 1465 1626 1761

25/18℃ 800 970 1122 1269 1444 1529 1716 1857

27/19℃ 871 1042 1182 1394 1570 1671 1832 2000

30/22℃ 986 1163 1318 1535 1691 1819 1974 2181

32/23℃ 1068 1286 1437 1660 1865 1981 2122 2310

32/24℃ 1101 1333 1507 1687 1929 2032 2185 2348

outdoor temp.(humidity 46%)

cooling power consumption value-temp.talbe

HFU-18HA03/R2(DB) performance curves

Cooling power consumption value-temp.curves

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

18/12℃

18/14℃

20/15℃

22/16℃

25/18℃

27/19℃

30/22℃

32/23℃

32/24℃

indoor tempe.(DB/WB)

pow

er c

onsu

mpt

ion(

w)

18℃

20℃

25℃

32℃

35℃

40℃

43℃

46℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

21

Domestic Air Conditioner

Page 24: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Domestic air conditioner22

9.4 Heating Power Consumption Value-temperature Curves

outdoor temp.

DB/WB 15℃ 20℃ 25℃

-10℃ 845 984 1176

-5℃ 801 923 1118

5℃ 946 1131 1229

7/6℃ 782 905 1135

15℃ 700 830 1003

20℃ 731 912 1106

25℃ 909 1086 1158

indoor temp.(humidity 46%)

heating power consumption value-temp.talbe

HFU-09HA03/R2(DB) performance curves

Heating power consumption value-temp.curves

600

700

800

900

1000

1100

1200

1300

1400

-10℃ -5℃ 5℃ 7/6℃ 15℃ 20℃ 25℃

indoor tempe.(DB/WB)

conoling capacity(w)

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

Page 25: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.

DB/WB 15℃ 20℃ 25℃

-10℃ 1018 1191 1349

-5℃ 965 1117 1306

5℃ 1064 1306 1472

7/6℃ 909 1075 1415

15℃ 833 1004 1214

20℃ 885 1176 1366

25℃ 1047 1314 1387

indoor temp.(humidity 46%)

heating power consumption value-temp.talbe

HFU-12HA03/R2(DB) performance curves

Heating power consumption value-temp.curves

-10℃ -5℃ 5℃ 7/6℃ 15℃ 20℃ 25℃

indoor tempe.(DB/WB)

conoling capacity(w)

系列1

系列2

系列3

HFU-09,12,18 HA03/R2(DB) Performance Curves

23Domestic Air Conditioner

Page 26: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.

DB/WB 15℃ 20℃ 25℃

-10℃ 1476 1757 1997

-5℃ 1400 1738 1933

5℃ 1543 1931 2179

7/6℃ 1360 1688 2095

15℃ 1324 1577 1797

20℃ 1550 1950 2110

25℃ 1680 2036 2120

indoor temp.(humidity 46%)

heating power consumption value-temp.talbe

HFU-18HA03/R2(DB) performance curves

Heating power consumption value-temp.curves

1000

1200

1400

1600

1800

2000

2200

2400

-10℃ -5℃ 5℃ 7/6℃ 15℃ 20℃ 25℃

indoor tempe.(DB/WB)

conoling capacity(w)

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

24Domestic Air Conditioner

Page 27: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Domestic air conditioner25

9.5 Cooling Discharge Pressure Curves

outdoor temp.(humidity 46%)

DB/WB 16℃ 19℃ 22℃

15℃ 2056 2258 2339

25℃ 2313 2473 2614

30℃ 2454 2626 2697

35℃ 2768 2894 2976

40℃ 3079 3254 3405

45℃ 3344 3545 3646

HFU-09HA03/R2(DB) performance curves

cooling discharge pressure.table

indoor temp.

Cooling discharge pressure

1500

2000

2500

3000

3500

4000

15℃ 25℃ 30℃ 35℃ 40℃ 45℃

Outdoor Temp

discharge pressure

16℃

19℃

22℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

Page 28: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 16℃ 19℃ 22℃

15℃ 2100 2262 2438

25℃ 2316 2477 2618

30℃ 2458 2630 2779

35℃ 2700 2899 2980

40℃ 3083 3200 3411

45℃ 3349 3550 3652

HFU-12HA03/R2(DB) performance curves

cooling discharge pressure.table

indoor temp.

Cooling discharge pressure

1500

2000

2500

3000

3500

4000

15℃ 25℃ 30℃ 35℃ 40℃ 45℃

Outdoor Temp

discharge pressure

16℃

19℃

22℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

26Domestic Air Conditioner

Page 29: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 16℃ 19℃ 22℃

15℃ 2103 2265 2442

25℃ 2319 2481 2691

30℃ 2461 2634 2783

35℃ 2704 2903 3063

40℃ 3088 3300 3500

45℃ 3354 3555 3658

HFU-18HA03/R2(DB) performance curves

cooling discharge pressure.table

indoor temp.

Cooling discharge pressure

1500

2000

2500

3000

3500

4000

15℃ 25℃ 30℃ 35℃ 40℃ 45℃

Outdoor Temp

discharge pressure

16℃

19℃

22℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

27Domestic Air Conditioner

Page 30: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Domestic air conditioner28

9.6 Cooling Suction Pressure Curves

outdoor temp.(humidity 46%)

DB/WB 16℃ 19℃ 22℃

15℃ 665 723 765

25℃ 694 753 795

30℃ 696 778 810

35℃ 707 781 826

40℃ 745 823 868

45℃ 773 855 890

HFU-09HA03/R2(DB) performance curves

cooling suction pressure.table

indoor temp.

Cooling suction pressure

600

700

800

900

1000

15℃ 25℃ 30℃ 35℃ 40℃ 45℃

Outdoor Temp

suction pressure

16℃

19℃

22℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

Page 31: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 16℃ 19℃ 22℃

15℃ 667 726 769

25℃ 697 756 800

30℃ 716 763 815

35℃ 730 785 852

40℃ 747 827 873

45℃ 776 859 895

HFU-12HA03/R2(DB) performance curves

cooling suction pressure.table

indoor temp.

Cooling suction pressure

600

700

800

900

1000

15℃ 25℃ 30℃ 35℃ 40℃ 45℃

Outdoor Temp

suction pressure

16℃

19℃

22℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

29Domestic Air Conditioner

Page 32: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 16℃ 19℃ 22℃

15℃ 658 711 774

25℃ 701 762 804

30℃ 721 784 848

35℃ 735 789 857

40℃ 764 833 891

45℃ 809 852 901

HFU-18HA03/R2(DB) performance curves

cooling suction pressure.table

indoor temp.

Cooling suction pressure

600

700

800

900

1000

15℃ 25℃ 30℃ 35℃ 40℃ 45℃

Outdoor Temp

suction pressure

16℃

19℃

22℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

30Domestic Air Conditioner

Page 33: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 15℃ 20℃ 25℃

-15℃ 2216 2414 2596

-10℃ 2372 2553 2723

-5℃ 2479 2665 2885

0℃ 2624 2837 3033

5℃ 2721 2942 3147

10℃ 2808 3065 3275

15℃ 2750 2970 3210

20℃ 3020 3248 3440

HFU-09HA03/R2(DB) performance curves

Heating discharge pressure.table

indoor temp.

Heating discharge pressure

1500

2000

2500

3000

3500

4000

-15℃ -10℃ -5℃ 0℃ 5℃ 10℃ 15℃ 20℃

Outdoor Temp

discharge pressure

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

Domestic air conditioner31

9.7 Heating Discharge Pressure Curves

Page 34: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 15℃ 20℃ 25℃

-15℃ 2150 2440 2645

-10℃ 2401 2580 2870

-5℃ 2509 2693 2939

0℃ 2656 2866 3090

5℃ 2754 2973 3310

10℃ 2842 3170 3430

15℃ 2820 3070 3250

20℃ 3056 3282 3505

HFU-12HA03/R2(DB) performance curves

Heating discharge pressure.table

indoor temp.

Heating discharge pressure

1500

2000

2500

3000

3500

4000

-15℃ -10℃ -5℃ 0℃ 5℃ 10℃ 15℃ 20℃

Outdoor Temp

discharge pressure

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

32Domestic Air Conditioner

Page 35: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 15℃ 20℃ 25℃

-15℃ 2300 2390 2680

-10℃ 2427 2611 2810

-5℃ 2536 2726 3040

0℃ 2685 2940 3131

5℃ 2784 3009 3353

10℃ 2770 3040 3475

15℃ 2670 2920 3292

20℃ 3090 3321 3550

HFU-18HA03/R2(DB) performance curves

Heating discharge pressure.table

indoor temp.

Heating discharge pressure

1500

2000

2500

3000

3500

4000

-15℃ -10℃ -5℃ 0℃ 5℃ 10℃ 15℃ 20℃

Outdoor Temp

discharge pressure

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

33Domestic Air Conditioner

Page 36: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 15℃ 20℃ 25℃

-15℃ 629 690 757

-10℃ 668 721 791

-5℃ 696 757 826

0℃ 721 795 884

5℃ 741 830 935

10℃ 889 955 1057

15℃ 960 1011 1079

20℃ 952 1015 1062

HFU-09HA03/R2(DB) performance curves

Heating suction pressure.table

indoor temp.

Heating suction pressure

600

700

800

900

1000

1100

1200

-15℃ -10℃ -5℃ 0℃ 5℃ 10℃ 15℃ 20℃

Outdoor Temp

suction pressure

15℃

20℃

25℃

Domestic air conditioner34

9.8 Heating Suction Pressure Curves

HFU-09,12,18 HA03/R2(DB) Performance Curves

Page 37: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 15℃ 20℃ 25℃

-15℃ 636 678 749

-10℃ 675 730 800

-5℃ 704 788 835

0℃ 729 805 894

5℃ 772 856 945

10℃ 899 966 1069

15℃ 987 1023 1091

20℃ 962 1015 1074

HFU-12HA03/R2(DB) performance curves

Heating suction pressure.table

indoor temp.

Heating suction pressure

600

700

800

900

1000

1100

1200

-15℃ -10℃ -5℃ 0℃ 5℃ 10℃ 15℃ 20℃

Outdoor Temp

suction pressure

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

35Domestic Air Conditioner

Page 38: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

outdoor temp.(humidity 46%)

DB/WB 15℃ 20℃ 25℃

-15℃ 643 685 757

-10℃ 683 738 831

-5℃ 711 769 836

0℃ 760 834 904

5℃ 811 865 956

10℃ 909 977 1080

15℃ 998 1034 1103

20℃ 973 1016 1055

HFU-18HA03/R2(DB) performance curves

Heating suction pressure.table

indoor temp.

Heating suction pressure

600

700

800

900

1000

1100

1200

-15℃ -10℃ -5℃ 0℃ 5℃ 10℃ 15℃ 20℃

Outdoor Temp

suction pressure

15℃

20℃

25℃

HFU-09,12,18 HA03/R2(DB) Performance Curves

36Domestic Air Conditioner

Page 39: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Sound level

Domestic air conditioner

Octave band center frequency(Hz)

approximatethresholdhearing forcontinuous noise

heatingcooling

63 125 250 500 1000 2000 4000 8000

20

30

40

50

60

70

80

53 106 212 425 850 1700 3400 6800

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

Octave band center frequency(Hz)

approximatethresholdhearing forcontinuousnoise

63 125 250 500 1000 2000 4000 8000

20

30

40

50

60

70

80

53 106 212 425 850 1700 3400 6800

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

HFU-09HA03/R2(DB) 42/41

44/43

39/38

40/39 38/36

52/51

54/53

37/35

Model

Sound presure level

230V,50Hz

Cooling/heatingMeasuring location sound power level

(cooling/heating)

H L SL

Location of microphone

10 Sound levelHFU-09,12,18HA03/R2(DB)

HFU-12HA03/R2(DB)

HFU-09HA03/R2(DB) HFU-09HA03/R2(DB)

Octave band center frequency(Hz)

approximatethresholdhearing forcontinuous noise

63 125 250 500 1000 2000 4000 8000

20

30

40

50

60

70

80

53 106 212 425 850 1700 3400 6800

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

Octave band center frequency(Hz)

approximatethresholdhearing forcontinuousnoise

63 125 250 500 1000 2000 4000 8000

20

30

40

50

60

70

80

53 106 212 425 850 1700 3400 6800

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

HFU-12HA03/R2(DB) HFU-12HA03/R2(DB)cooling heating

HFU-12HA03/R2(DB)

48/47 45/43 42/40 58/57

IndoorOutdoor

IndoorOutdoor

37

Page 40: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Accessories

38 Domestic Air Conditioner

11. Accessories

Standard accessories Name HFU-09HA03/R2(DB)

Drain hose

Plastic bag 1 1

screw assembly 1 1

Battery 2 2

Remote controller YR-H05 YR-H05

1 1 Operation manual

Octave band center frequency(Hz)

approximatethresholdhearing forcontinuous noise

63 125 250 500 1000 2000 4000 8000

20

30

40

50

60

70

80

53 106 212 425 850 1700 3400 6800

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

Octave band center frequency(Hz)

approximatethresholdhearing forcontinuousnoise

63 125 250 500 1000 2000 4000 8000

20

30

40

50

60

70

80

53 106 212 425 850 1700 3400 6800

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

HFU-18HA03/R2(DB) HFU-18HA03/R2(DB)cooling heatingIndoorOutdoor

2

1

1

HFU-09HA03/R2(DB) HFU-09HA03/R2(DB)

YR-H05

1

1 1 1

Page 41: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

Control systemsHFU-09,12,18 HA 03/ R2(DB)

39 Domestic air conditioner

1.TIMERUsed to select TIMER ON,TIMER OFF, TIMER ON-OFF

2.HOURUsed to set clock and timersetting.

3.CLOCKUsed to set correct time.

Note:1. The following functions and related displays are not available for all models: Display of humidifying and atmosphere humidity.

2. There is health display with the remote controller in this type, but without health function.

4. MODEUsed to select AUTO, COOL, DRY,FAN and HEAT operation.

5. ON/OFFUsed for unit start and stop.

6. SWINGUsed to adjust the up/down air flow direction.

7. TEMP.Used to select your desired temperature.

8. TIMER ON display9. SLEEP display10. FAN SPEED display

Remote controller:

LOW MED HI AUTO

11. SWING UP/DOWN display12. MODE display

AUTO

COOL

DRY

FAN

HEAT

Operationmode

Remotecontroller

13. SIGNAL SENDING display14. TEMP. display

Remote controller: to display the TEMP. setting.15. CLOCK display16. TIMER OFF display17. FAN

Used to select fan speed: LO,MED,HI,AUTO18. SET

Used to confirm timer and clock settings.19. SLEEP

Used to select sleep mode.20. RESET

When the remote controller appears abnormal,use a sharp pointed item to press this buttonto reset the remote controller to normal condition.

21. LOCKUsed to lock buttons and LCD display. Ifpressed, the other buttons will be disabled andthe lock condition display appears.Press it once again, lock will be canceled andlock condition display disappears.

22. LOCK display23. POWER/SOFT

12 Control systems

Page 42: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Center of gravity

40 Domestic Air Conditioner

13 Center of gravity Indoor

Outdoor(for 09/12 unit)

Outdoor(for 18 unit)

543

255

783310

255118

720

305

640

315255

120

680

312

837

275

813

332

145

Page 43: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) Accessories

41 Domestic Air Conditioner

14. Installation

Installation of indoor unitselection of installation placePlace where it is easy to route drainage pipeand outdoor piping.Place, away from heat source and with lessdirect sunlight.Place where cool and warm air could bedelivered evently to every corner of the room.Place near power supply socket.Leave enoughspace around the unit.Place, robust not causing vibration, where thebody can be supported sufficiently.

Installation of outdoor unitselection of installation placePlace strong enough to support the unit and willnot cause vibration and noise.Place where discharged wind and noise does notcause a nuisance to the neighbors.Place where is less affected by rain or direct sunlightand is sufficiently ventilated,or to install a shield.Place with enough space for smooth air flow.

Figure.2

Figure.3

Installation

To prevent interference, place it at least 1maway from other electric machines, such asTV set, radio.

There must be no gap between the indoor unit andwall.

According to the dimension of the Figure 2 shownnail two cement steel nails on the wall keep 2-3mmout, then hang the back of the unit on them.

Remove the front panel,then use two fasteningscrews to fix the unit on the floor. As Figure 3 shown.Once refrigerant piping and drain piping connectionsare complete,fill the gap of the through hole with putty.Attach the front panel and front grille in their orginalpositions once all connections are complete.

Figure.4

more than 60 cm

more than 10 cm

more than 10 cm

more than 10 cm

Figure.1

mc001nahterom

mc01nahterom

mc01

nah tero

m

mc01naht

erom

Page 44: DC Inverter - HAIER€¦ · Air conditioner HFU-09HA03/R(DB) HFU-12HA03/R(DB) HFU-18HA03/R(DB) 1. READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

HFU-09,12,18HA03/R2(DB) The end

42

Domestic air conditioner