Wim de Boer, Univ. Karlsruhe 1 Jan.2009 Design considerations for a CMS CO2 cooling system CMS specials: 50 kW cooling system at -40 0 C (see below) Difficulties: membrane pumps to -25 0 C, condensors at low pressure No high pressure allowed (max. 70 bar, preferred <35 bar) Difficulties: have to separate room temperature storage cylinders (70 bar) from operating system (extra pump or cooled storage cylinders)
Transcript
Page 1: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 1Jan.2009

Design considerations for a CMS CO2 cooling system

CMS specials:

50 kW cooling system at -40 0C (see below)Difficulties: membrane pumps to -250C, condensors at low pressure

No high pressure allowed (max. 70 bar, preferred <35 bar)

Difficulties: have to separate room temperature storage cylinders (70 bar)from operating system (extra pump or cooled storage cylinders)

Page 2: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 2Jan.2009

25 W/10x10 cm sensor at -25 0C, factor 1.5 reduction/5 0CHybrids for strixel design of 2.2 cm: 2 WWant to reduce by factor 8: from -25 to -40 0C -> x3.4Additionally: reduce V by factor 1.5-> factor 2.3 in power=VxI

Why -40 0C?

Page 3: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 3Jan.2009

Temperature profile for 25W in 10x10 Si sensor

Cooling: 240 K at edge-> 40 K increase towards middle for 25 W (Si = SEMI-conductor!)

High risk of thermal run away for such high gradients !Have to run at lower voltage or still lower temperature.

Page 4: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 4Jan.2009

Page 5: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 5Jan.2009

Page 6: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 6Jan.2009

Choices for evaporative cooling systems

Compressor (gas)Condensor

Evaporator

Pressureregulator

Condensor at high pressure,Do not need external chiller.Have to avoid that liquidenters compressor, so needheaters in case heat load dropsor TEV (Thermal expansion valve)which regulates flow.

Condensor at low pressure,Need external chillerHave to avoid evaporation inor before pump, so need subcooledliquid, which need to be heated beforeevaporator to have well defined temp.

Liquid pump

Evaporator

Condensor

Pressureregulator

Chiller

Page 7: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Need pressure reductionbetween condensor and evaporator

3 methods: a) capillaryb) expansion valvec) pressure reducer

a) Capillary pressure drop flow dependent, so needadditional pressure control (accumulator in LHC-b) b) Expansion valve usual method in commercial cooling systems, but different for different fluids.Not available for CO2 (as far as we know)

c) Simple pressure reducer used on bottles work excellent(but not used as such, as far as we know)

Page 8: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Pressure reduction by temperaturecontrolled expansion valve

Page 9: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 9Jan.2009

Pressure reduction by pressure sensitive valve (used on bottles)

Tested to work very well for controlling temperature of CO2 two phase mixture.

Can avoid complicated accumulator used in LHC-b

Page 10: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 10Jan.2009

Choices from ATLAS and LHCbFrom B. Verlaat, NIKHEF

Liquid Vapor

2-phase

Pres

sure

Enthalpy

Liquid Vapor

2-phase

Pres

sure

Enthalpy

Vapor compression system•Always vapor needed•Dummy heat load when switched off•Oil free compressor, hard to find

Pumped liquid system•Liquid overflow, no vapor needed•No actuators in detector•Oil free pump, easy to find•Standard commercial chiller

Detector

Cooling plant

Warm transfer over distance

Detector

Cooling plant

Chiller Liquid circulation

Cold transfer over distance

Direct expansion into detector with C3F8 compressorWarm transfer linesBoil-off heater and in detectorTemperature control by back-pressure regulator

CO2 liquid pumpingCold concentric transfer lineNo components in detectorTemperature control by 2-phase accumulator

LHCb method:

Atlas method:

Hea

ter

Compressor

Pump

Compressor

BP. Regulator

Page 11: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

LHCb-VTCS Overview (B. Verlaat)A 2-Phase Accumulator Controlled Loop

2-phase

gas

R404a chiller

22

33

6677

11

88

44

2-phase2-phase

liquid liquid liquid

2-phaseCon

den

ser Evaporators

Concentric tubePump

Rest

rict

ion

Accumulator Cooling plant areaTransfer lines

(~50m) VELO area

55

liquid

Evaporator :• VTCS temperature ≈ -25ºC• Evaporator load ≈ 0-1600 Watt• Complete passive

Cooling plant:• Sub cooled liquid CO2 pumping• CO2 condensing to a R507a

chiller• CO2 loop pressure control using

a 2-phase accumulator

Accessible and a friendly environment

Inaccessible and a hostile environment

R507aChiller

Page 12: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

LHCb-VTCS Overview (B. Verlaat)A 2-Phase Accumulator Controlled Loop

2-phase

gas

R404a chiller

22

33

6677

11

88

44

2-phase2-phase

liquid liquid liquid

2-phaseCon

den

ser Evaporators

Concentric tubePump

Rest

rict

ion

Accumulator Cooling plant areaTransfer lines

(~50m) VELO area

55

liquid

Evaporator :• VTCS temperature ≈ -25ºC• Evaporator load ≈ 0-1600 Watt• Complete passive

Cooling plant:• Sub cooled liquid CO2 pumping• CO2 condensing to a R507a

chiller• CO2 loop pressure control using

a 2-phase accumulator

Accessible and a friendly environment

Inaccessible and a hostile environment

R507aChiller

Page 13: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 13Jan.2009

CO2 bottle in household freezer

Advantage:Initial pressure reduced by cooling of CO2 to 12 bar(instead of 70 bar at room temp)

No heat exchanger needed

Whole system <500 EuroStandard Swagelock connectorsFast cooldown since liquidhas already detector temperature

The simplest CO2 cooling system you can imageAND IT WORKS!

Flowmeterregulates flow, i.e.cooling power

Pressure reducerregulates temperature long nylon

tube to air

nylon tubeto see boilingof CO2

Relief valve

Page 14: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 14Jan.2009

Flowmeters

hybrid withheater andT-sensor

Some pictures

Cold liquid sent through ladder.Blue temperature curve shows position of liquid.

Page 15: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 15Jan.2009

-70

-60

-50

-40

-30

-20

-10

0

10

20

30

0 10 20 30 40 50 60

time [min]

tem

pera

ture

[°C

]

sensor1sensor2sensor4

Regulating temperature with pressure

11,5bar 8bar 6,5 5,5

very easy to set and hold temperature: just keep pressure constant

CO2 pressurein [bar]

Page 16: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 16Jan.2009

beginning dry-out

050

100150200250300

0 0,5 1 1,5 2 2,5 3

flow in kg/hour (both tubes)to

tal h

eatin

g po

wer

[W]

Test results

easy to cool large powers with little flow of CO2,

flow was tested up to 3,7 kg/hour (max. of flowmeters) with negligible pressure drop

Even much bigger flow seems possible with tolerable pressure drop

Page 17: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Why CMS cannot use any of these systems

CMS cannot use high pressure CO2 closed system, since 1 mm Cu coolingpipes should have max. 70 bar.

CMS has large varying heat loads (detectors cannot be switched onduring cooldown) and 50 kW heaters are a nightmare in cooling circuit

Possible solution: try liquid pump down to -40Cand design low pressure CO2 system.

For sLHC we would like to cool down to -40C to avoid risk of thermalrun away.

Page 18: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 18Jan.2009

scale

A recirculating CO2 system

Com

mer

cial

con

dens

or

Pressure reducer

regulates temperature

to 10 bar=-40C

Detector=evaporator

9 bar

<25 bar fill line

Vacuumpump for leaktests

Chiller -50 C

Pump for subcooledCO2

Transferline 60m asconcentric heat exchangerto heat up subcooled liquid

and reduce pressure in outlet

70 bar shut down line withhigh pressurepump

10 bar

25 bar

Page 19: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 19Jan.2009

Heat exchangers: www.geawtt.com.

Double WallFor extra protection against leakage a special double wall system is developed. This systemconsists of two stainless steel plates instead of one. In case of internal damage, due to strongpressure variations for example, the chance of fluid contamination is prevented

Page 20: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 20Jan.2009

GEAWTT Condensors

Page 21: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 21Jan.2009

Safety Chamber™The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrialstandard for GEA WTT heat exchanger types 7, 8, 9 and 10. The contact points (brazing points), whichare responsible to take off the stress in the port area, are separated. Overloading of these contact pointsand cracking of the material do not lead to a mix with the other side - a maximum of safety for the userThe Full-Flow-System™special developed for GEA WTT nickel brazed heat exchangers. To avoid freezing problems in the portarea when using nickel brazed heat exchangers as an evaporator GEA WTT has developed the Full-Flow-System™. Continuous flow without stagnation around the port avoids "Port Freezing".XCRthe plates consist of high grade corrosion resistant stainless steel, named SMO 254. XCR series has beendeveloped for special applications, such as pool heating, ground water heat pumps, etc. Depend on theparticular application we offer XCR models either copper brazed or nickel brazedDelta-Injektion™...Distribution SystemThe Delta-Injektion™ distribution system on Advanced Evaporator AE models is made from AISI 316Lstainless steel and provides precise allocation of refrigerant to the channelsDouble WallFor extra protection against leakage a special double wall system is developed. This system consists oftwo stainless steel plates instead of one. In case of internal damage, due to strong pressure variations forexample, the chance of fluid contamination is prevented.

Page 22: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 22Jan.2009

Choice of liquid pump

Pressure firm pump characteristic

22

flow

rate

pressure

membrane displacement pumps

rotary positive displacement pumps

centrifugal pumps

Page 23: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 23Jan.2009

LEWA diaphragm pumps (ECOFLOW)

Page 24: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 24Jan.2009

Diaphragm exchange simple

Page 25: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 25Jan.2009

Output pressure limited

Page 26: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 26Jan.2009

Flow adjustment

Page 27: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 27Jan.2009

CMS: Control and Monitoring System

Page 28: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 28Jan.2009

frequency n

fow

rate

Q

Q = k1*n

stroke length hflo

wra

te Q

Q = k2*(h-h0)

h0

limiting stroke length h0

Adjusting the flowrate

Page 29: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 29Jan.2009

Vh Vh Vh

time t

Flow

rate

Q

Pulsating flowrate

Need either: a) 3 phase-shifted pump headsb) pulsation damperc) maybe pressure reducer does the job to prevent temperature variations

Page 30: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 30Jan.2009

1mm diameter, 0.5 mm thick pmax 550 bar

2mm diameter, 0.5 mm thick pmax 367 bar

Flow regimes in small tubes

0.0002 kg/s=66W

rho flow velocity diameter viscosity Surface tension Reynold SuratmanREG/RE

Lkg/m3 kg/s m/s m mPas=cP N/m (x10^6)

1138 0,0002 0,22 0,001 0,15 0,012 1697,70 0,61 CO2 liq -4422 0,0002 11,58 0,001 0,011 0,012 23150,49 CO2 gas -44 13,64

1138 0,0002 0,06 0,002 0,15 0,012 848,85 1,21 CO2 liq -4422 0,0002 2,89 0,002 0,011 0,012 11575,25 CO2 gas -44 13,64

1138 0,0002 0,22 0,001 0,15 0,012 1697,70 0,61 CO2 liq -4422 0,00002 1,16 0,001 0,011 0,012 2315,05 CO2 gas -44 1,36

1138 0,0002 0,06 0,002 0,15 0,012 848,85 1,21 CO2 liq -4422 0,00002 0,29 0,002 0,011 0,012 1157,52 CO2 gas -44 1,36

Pressure drop in 1 mm tube still small enough, especially with heat exchange betweenin- and output by the electrical connections pads, so almost no T-gradient on ladder

To be verifiedfor CO2 atlow temp.

annular

bubble

slug

Page 31: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 31Jan.2009

Questions to be resolved

Diaphragm pump to be tested at -400CStarted collaboration with LEWA.

They will give us a pump and we will testdifferent diaphragms

Heat exchanger at low temperature and low pressure:Started collaboration with GEA.

Their design program says it is possible for high flow of primary liquid

Accumulator:Can one use large volume of return tubes as accumulator?(It would act as pulsation damper! No need for triple, phase shifted pumps,one pump with CMS control preferred? Price tag: 20 kEuro/pump, 20 kEuro/CMS)Do we need accumulator above tracker to guarantee always liquidin upper part of tracker?

Page 32: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 32Jan.2009

Summary • low pressure CO2 system with STANDARD commercial pumps,

heat exchangers and pressure reducers seems feasible.

• Require cooling of sensors below -40 0C to get leakage current noise down and limit risk of thermal runaway#(main difficulty: find membrane material for low temp.)

• Strixels of 2.2 cm could then yield S/N similar as for LHC(signal down by ¼, so capacitance down by ¼)

• All connections outside volume possibleby CO2 cooling, which allows 6m long cooling pipes

• Reduction of material budget possible by powering viacooling pipes, since pure Al cold pipes have VERY low resistivity.No need for DC/DC converters inside tracker

Page 33: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 33Jan.2009

Backup slides

Page 34: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 34Jan.2009

Summary of cooling liquids at LHC

Notes:Single phase cooling simplest, but large pumps neededTwo-phase evaporation in principle much better, because

heat of evaporation much larger than specific heat, butany pressure changes means a temperature change, so be careful about tube bending, tube sizes etc.

CO2 has largest heat of evaporation, is non-toxic, non-flammable, industrial standard, liquid at room temperature, but high pressure (73 bar at 31 0C)

300

Page 35: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 35Jan.2009

Supermarkets start to use CO2

Page 36: deBoer CMS cooling system design considerations ... Documents...The patented Safety Chamber™, the Non-Plus-Ultra for big brazed heat exchangers is the industrial standard for GEA

Wim de Boer, Univ. Karlsruhe 36Jan.2009

CO2 phase diagram


Recommended