Toronto Local Appeal Body 40 Orchard View Blvd, Suite 211 Toronto, Ontario M4R 1B9
Telephone: 416-392-4697 Fax: 416-696-4307 Email: [email protected] Website: www.toronto.ca/tlab
DECISION AND ORDER
Decision Issue Date Friday, June 29, 2018
PROCEEDING COMMENCED UNDER section 45(12), subsection 45(1) of the Planning Act, R.S.O. 1990, c. P.13, as amended (the "Act")
Appellant(s): NHAT HUNG PHAN
Applicant: MAX MERCHASIN
Property Address/Description: 665 SHAW ST
Committee of Adjustment Case File Number: 17 159362 STE 19 MV
TLAB Case File Number: 17 249169 S45 19 TLAB
Hearing date: Tuesday, March 27, 2018
DECISION DELIVERED BY S. Gopikrishna
APPEARANCES
Name Role Representative
Darshan Sahota Applicant/Appellant's Rep.
Nhat Hung Phan Appellant/Owner
City of Toronto Party Matthew Schuman
Mladen Kukic Expert Witness
Fanny Chaggaris Participant
Bruce Burron Participant
Patricia Chaggaris Participant
1 of 12
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
INTRODUCTION AND BACKGROUND
Nhat Phung Phan is the owner of 665 Shaw St. He applied for variances to the COA on May 13, 2017. The Committee of Adjustment refused the application at its meeting on September 27, 2017. The applicant appealed the decision of the Committee of Adjustment on October 17, 2017. The City of Toronto, authorized the City Solicitor, along with appropriate City Staff, to attempt to negotiate a resolution of the appeal with the applicant, in consultation with the Ward Councilor and concerned residents, and to attend the Toronto Local Appeal Body hearing in opposition to the minor variances requested, if a resolution was not reached.
The original application was submitted on 17 October, 2017, it was found to be incomplete through the process of administrative screening. A Notice of Non-Compliance was issued by the staff on 24 October, 2017. When no response was received by 30 October 2017, I issued and signed a Notice of Proposed Dismissal on 30 October, 2017, listing the non-compliance issue as the reason. A revised and updated Notice of Appeal, rectifying the issue in the original application was submitted by the Appellants on 8 November 2017 and was deemed to compliant by staff.
On 21 November 2017, I issued a decision setting aside the decision for a Notice of Dismissal on administrative grounds, allowing the appeal to proceed forward and be scheduled for an oral hearing of evidence.
MATTERS IN ISSUE
The requested variances to the Zoning By-laws are: 1. Chapter 10.10.40.40.(2), By-law 569-2013 Additions to the rear of a semi-detached house erected before October 15, 1953, are permitted provided the floor space index as enlarged does not exceed 0.69 times the area of the lot (207.35 m²). The altered semi-detached house will have a floor space index equal to 0.75 times the area of the lot (225.83 m²). . 3. Chapter 10.5.60.50.(2), By-law 569-2013 The maximum permitted floor area of all ancillary buildings or structures on the lot is 40.0 m². The total floor area of all ancillary buildings on the lot is 47.4 m².
1. Section 6(3) Part VI 1(I), By-law 438-86 Additions to the rear of a semi-detached house erected before October 15, 1953, or to a converted house are permitted provided the residential gross floor area as enlarged does not exceed 0.69 times the area of the lot (207.36 m²). The altered semi-detached house will have a residential gross floor area equal to 0.75 times the
2 of 12
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
area of the lot (225.83 m²).
By way of editorial comment, the unusual numbering of the variances ( with missing numbers) is a consequence of the fact that the variances were changed at the time of the hearing. They are re-numbered in a conventional fashion in the final order.
JURISDICTION
Provincial Policy – S. 3
A decision of the Toronto Local Appeal Body (‘TLAB’) must be consistent with the 2014 Provincial Policy Statement (‘PPS’) and conform to the Growth Plan of the Greater Golden Horseshoe for the subject area (‘Growth Plan’).
Minor Variance – S. 45(1)
In considering the applications for variances form the Zoning By-laws, the TLAB Panel must be satisfied that the applications meet all of the four tests under s. 45(1) of the Act. The tests are whether the variances:
maintain the general intent and purpose of the Official Plan;
maintain the general intent and purpose of the Zoning By-laws;
are desirable for the appropriate development or use of the land; and
are minor.
EVIDENCE
The Appeal respecting 665 Shaw St. was heard on 27 March, 2018. The Appellant was represented by Mr. Darshan Sahota, a designer while the City was represented by Mr. Matt Schuman, Lawyer and Mr. Mladen Kukic, Planner. The hearing was also attended by three witnesses, Ms. Fanny Chaggaris and Ms. Patricia Chaggaris, both of 667 Shaw Street and Mr. Bruce Barron of 671 Shaw Street.
Mr. Schuman stated that the City and the Appellant had reached a settlement, resulting in a revised proposal. The revised proposal, in conjunctions with conditions of approval, would be discussed at the hearing and would be recommended for approval. Mr. Schuman advised that Mr. Sahota, the Appellant’s designer would present a brief outline of the project, and stated that he would object if Mr. Sahota were questioned about planning evidence since the latter wasn’t a planner. In response to a question if new notice was required as a result of the settlement, Mr. Schuman opined that there was no need for new notice.
3 of 12
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
Mr. Sahota provided a very brief introduction in his role as Agent for the Appellant. He described the proposal broadly and said that the proposal aimed to build a larger and higher deck, which was the main issue of concern to the neighbours. However, Mr. Sahota stated that the proposed deck did not trigger any variances. The requested variances were primarily for the Gross Floor Area (GFA) as a result of an addition at the back of the house. He said that a result of the settlement, 2 variances pertaining to soft landscaping ( Variance No 2) and the garage height ( Variance No 4 under 569-2013 and 2 under 438-86) had been dropped.
By way of editorial comment, the 3 variances, that were negated, as a result of the Settlement are reproduced below:
2. Chapter 10.5.50.10.(3)(A), By-law 569-2013 A minimum of 50% (76.5 m²), of the rear yard shall be maintained as soft landscaping. In this case, 42% (63.88 m²), of the rear yard will be maintained as soft landscaping.
4. Chapter 10.5.60.40.(2), By-law 569-2013 The maximum permitted height of an ancillary building or structure is 4.0 m. The height of the ancillary structure will be 4.3 m.
2. Section 4(2)(d), By-law 438-86 The maximum permitted height of an accessory building is 4.0 m. The height of the accessory building will be 4.3 m
The removal of these variances, results in the unusual numbering of from the list of variances to be ruled on by TLAB.
Mr. Schuman then asked Mr. Sahota a few questions of clarification. He wanted to confirm that the existing footprint of the garage would be maintained, to which Mr. Sahota replied in the affirmative. Mr. Schuman then asked Mr. Sahota to confirm that there were no variances for length and depth notwithstanding a new addition at the back of the house, to which Mr. Sahota said that he did not know the answer. Mr. Schuman then asked Mr. Sahota to look at the proposed conditions and confirm that he agreed to the imposition of the same. Mr. Sahota confirmed that the conditions were acceptable to the Appellants.
Mr. Schuman then introduced Mr. Mladen Kukic, assistant planner at the City of Toronto, as the next witness. After reviewing Mr. Kukic’s resume and work history, Mr. Schuman asked that Mr. Kukic be recognized as an Expert Witness.
Mr. Mladen Kukic was introduced as the Expert Witness. His evidence was as follows:
The established study area was bounded by Bloor Street West to the north, Harbord Street to the south, Roxton Road to the west and Crawford Street to the east. This study area was chosen because it encompasses the area near the subject property, as experienced by the local residents on a day-to-day basis as they visit neighbours, retail
4 of 12
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
stores or walk to the closest transit stop. Further, Bloor Street West and Harbord Street were chosen as the north and south boundaries because they function as main streets, as reflected in their zoning, land use designations, densities and vehicular as well as non-vehicular traffic. The Commercial-Residential (CR) zoned properties that front onto Bloor Street West and Harbord Street have been excluded from the study area because these properties have different land use designations and zoning, and therefore should be reviewed using different criteria.
According to Mr. Kukiic, the entire area has the same zoning as the subject site: R in Zoning By-law No. 569-2013, and R2 in Zoning By-law No. 438-86. The entire area is also designated Neighbourhoods under the Official Plan's Land Use Designation map. The study area contains 217 properties, consists generally of single detached, semidetached as well as row houses that are predominantly 2.5 storeys in height located on rectangular lots that have rear access to public laneways. Of the 217 properties, 44 properties have existing rear second or third storey decks while177 properties have existing rear garages (approximately 81%), of which 77 garages have floor areas that are greater than the permitted 40 square metres under Zoning By-law 569-2013.
According to Mr. Kukic, there have been a total of 41 minor variance applications within the study area in the past 17 years. Twenty-four of the aforementioned 41 minor variance applications requested an FSI variance in excess of the permitted 0.69 and were approved- according to Mr. Kukic, they varied from 0.72 to 1.44.
Mr. Kukic then discussed the Provincial Policy Statement (PPS) and how it applied to this proposal. The PPS encourages intensification and efficient development. The City's Official Plan has responded by establishing areas for intensification and policies to encourage intensification – provided this can occur in the context of other applicable policies. According to Mr. Kukic, the manifestation of intensification in the proposal makes it consistent with the PPS.
Mr. Kukic then discussed the Growth Plan and concluded that the Proposal was consistent with the objectives of the Growth Plan, because of the Official Plan to implement the policies of the Growth Plan.
Mr. Kukic then discussed the Official Plan and how it impacted the project. The subject site is designated Neighbourhoods. The plan states that Neighbourhoods designated areas are to be considered physically stable areas made up of residential uses in lower scale buildings such as detached houses, semi-detached houses, duplexes, triplexes and townhouses, as well as interspersed walkup apartments that are no higher than four storeys.
He discussed Policy 4.1.5 from Chapter 4 of the Official Plan and applied it to the proposal. Mr. Kukic pointed out that Policies 4.1.5 a), b), d), e), g) and h) do not apply because the proposal does not require any variances related to the lot size and dimensions, the building type, the setbacks, special landscape or built form features, as well as conservation of heritage buildings, structures of landscapes. Therefore, the
5 of 12
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
application proposes an extension of the ground level. According to him, the majority of the buildings within the study area, including the three properties immediately to the south, and the 12 properties immediately to the north, have first storeys that are similar, or greater, than the proposal, which results in the increase to the GFA.
Mr. Kukic also stated that Policy 4.1 discusses the endurance of the general physical character of Toronto’s neighbourhoods amidst constant social and demographic change. Physical changes to established Neighbourhoods must be sensitive, gradual and generally "fit" the existing physical character. Although many properties within the study area have rear second and third storey decks, the proposed rear second storey deck, which does not provide any privacy screening to mitigate privacy and overlook issues onto the neighbouring backyards, cannot be considered as "sensitive" development. Based on these arguments, Mr. Kukic concluded that the proposal is consistent with the Official Plan.
The purpose of the performance standards in the Zoning By-law for maximum permitted FSI, total floor area and height of ancillary buildings or structures on a lot is to generally maintain a stable built form in the neighborhood, control the massing of buildings and to limit the impact of new development on adjacent residential properties. The proposed application would extend the length of the first storey by approximately 2.5 metres, for a total length of 15.25 metres, which would bring the FSI coverage to 0.75, as opposed to the permitted 0.69. In the past 17 years, there have there have been a total of 41 minor variance applications within the study area, of which 27 requested a variance related to the FSI, the vast majority (over 90%) of which were approved. Coupled with the fact there are no variances related to the depth of the building, this suggests that the proposal will maintain a stable built form. The additional FSI will be located at the rear of the ground floor, which would mitigate the impact of the built form on the surrounding properties because the proposed height of the first floor is less than 3 metres.
The proposed garage requests a ground floor area of 47.4 square metres, as opposed to the maximum permitted 40 square metres. The height is at 4 metres, which is as of right while the side walls of the garage would have a height of 3 metres, well below what is as-of-right.
Based on these observations, Mr. Kukic concluded that the requested variances for FSI, and the height and size of the proposed garage, and the reduction in rear yard soft-landscaping, would not destabilize the established built form in the neighborhood, and would have limited impacts on the adjacent residential properties. Consequently, the test pertaining to conformity with the zoning law was fulfilled.
Regarding the test of appropriateness, and desirable development, Mr. Kukic pointed out that the proposed addition to the house and new garage would be a reinvestment in the neighborhood that is in keeping with the purpose and intent of the Official Plan and Zoning By-law. The rear addition to the main building, and the new garage are sensitive to the neighbourhood in nature and generally fit within the built form character of the
6 of 12
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
area and meet the intent of the Official Plan and Zoning By-laws. Based on this, Mr. Kukic argued that the test of desirable development had been met.
Lastly, addressing the test of variances being “minor”, Mr. Kukic stated that the proposed rear addition to the house would result in an increase of the allowable FSI for the property by 0.06. The impact was restricted to possible overlook over a neighbours backyard, which would be minimized as a result of the conditions suggested by the City.
To ensure that the applicant would not be able to revise plans and build a building to fill the entire zoning envelope, as varied, Mr. Kukic recommend that the Board impose the following conditions:
1) That the second floor of the proposed dwelling have a maximum building depth of 10.65 metres, excluding the rear deck, and 15.3 metres, inclusive of the rear deck, as per the second floor plan received by the Committee of Adjustment on May 13, 2017;
2) That the proposal be constructed and landscaped substantially in accordance with the site plan and elevations dated March 8, 2018 (pages A1, A7, and A8), and January 15, 2018 (pages A12-A15).
3) That permanent opaque screening or fencing be provided along the north and south edges of the rear second storey deck to a minimum height of 1.5 metres from the floor of the deck; and
4) That the garage plans submitted to Toronto Building for building permit are substantially in accordance with garage plans date stamped by Committee of Adjustment Staff May 13, 2017.
Mr. Kukic concluded his evidence by stating that he recommended approval of the proposal as modified and presented to TLAB, along with the suggested conditions.
Ms. Patricia Chaggaris was the first witness to provide evidence. She stated that her opposition was premised on the impact on privacy to herself and her mother, Ms. Fanny Chaggaris, both of whom lived next door at 667 Shaw St. She then proceeded to read from a statement, the highlights of which are reproduced below:
According to Ms. Patricia Chaggaris, the proposed addition, as designed, results in a complete lack of privacy because anyone on the stairs or deck can look directly into the windows of four rooms (that have no other windows) in her house from a distance of less than 5 metres, including the kitchen and living area on the first floor; and a bedroom and the bathroom on the second floor. The bulk of the building causes a significant decrease in light into the kitchen and living area because of the addition being proposed directly in front of it and the stair even extending beyond the addition. Ms Chaggaris quoted the definition of a minor variance as “the process of seeking relief through a Committee of Adjustment when hardship or circumstances do not allow you to
7 of 12
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
meet the standards listed in the by-law” , as quoted in the City of Mississauga website, and asked how this definition was consistent with what the Appellants proposed. She stated that her family would not be able to see the CN tower from their bedroom window, and how much this mattered to them since she and her mother really enjoyed the sight of the CN tower. Based on these reasons, Ms. Chaggaris concluded that the variances were not minor.
Ms. Patricia Chaggaris also said that the proposal did not maintain the intent of the Official Plan and By-laws because the proposed building depth of 15.25 m, exceeded the maximum of 14 m allowed in the by-laws for duplexes. When asked how she concluded that the proposed building was a duplex, Ms. Patricia Chaggaris, pointed to the COA application form in her disclosure statement. She said that the proposed build contradicted policies in the Official Plan, which discussed the need for new developments to respect and reinforce the existing physical character.
Mr. Schuman explained the Site Plans to the Appellants and assured them that there were no windows in the proposal looking at 667 Shaw St. He said that there would be a privacy screen of 1.5 m placed at the back of the house which would protect the privacy of the Chaggaris family. In response to a question from Ms. Chaggaris about the material to be used for the privacy screen, Mr. Schuman also stated that the privacy screen would be made of material that would admit light partially if it was not opaque. I interjected to state that the material being proposed for the screen should be translucent ( i.e. something that partially admits light) and asked Ms. Chaggaris if increasing the height of the fence and ensuring that it was made of translucent material allayed her concerns. Ms. Patricia Chaggaris said that she understood the design but was not confident about the impact. When Ms. Patricia Chaggaris repeated her concern about the stairs, Mr. Schuman asked if she would prefer staring at a wall rather than the stairs. Ms.Chaggaris said that she preferred the stairs to staring at a wall.
The next witness was Mr. Bruce Barron who lives at 671 Shaw Street. Mr. Barron pointed out that on the north side of the property, there was a significant amount of concrete which prevented water from seeping into the ground. He wondered about what the impact of the extension to the house would be given the issue with water pooling as a result of concrete on the ground. Mr. Schuman explained that there would be permeable material, with a honeycomb like structure, on the path between the rear of the staircase and rear of the driveway, which would allow for the water to seep in. Mr. Barron then asked questions about the placement of the stairs and asked if it was possible to move the placement of the stairs such that the stair lines would be obscured? Mr. Sahota said that the obscuring of stair lines wasn’t possible based on the clients’ instructions. He again repeated that the neighbours’ main concern was the deck and that there were no variances for the deck.
At this point in time, I suggested that the height of the proposed fence, set at a maximum of 1.5 metres in the proposed conditions, be increased to 1.8 m to better protect the privacy of the neightbours. Mr. Sahota agreed with my suggestion.
8 of 12
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
9 of 12
In terms of the closing statements, Mr. Sahota stated that the Appellants had made changes to the proposal as a result of the Settlement and reiterated, for the third time, that the objections of the objectors had been about the deck and that there were no variances associated with the deck. Mr. Schuman, in his closing statement, stated that the planning evidence given by the expert witness, Mr. Kukic, was uncontroverted and recommended that the evidence be accepted by the TLAB. He said that he was recommending that the updated variances ( 2 under 569-2013 and 1 under 438-86) be approved by the Board subject to the conditions, as recommended, including the fence’s height being increased to “ a maximum of 1.8 m” as opposed to the originally suggested 1.5 m.
ANALYSIS, FINDINGS, REASONS
In the absence of alternative planning evidence, the uncontroverted evidence of the Expert Witness is accepted and the proposal is approved. However, I would like to observe on the methodology followed regarding the test for desirability; I understand that the conclusion about desirability is a consequence of the proposal’s meeting the tests for consistency with the Official Plan and Zoning. I would have preferred that the conclusion regarding desirability be arrived independently, through means of analyzing the proposal, as opposed to making it dependent on other tests.
I also note the inconvenience stated by the Chaggaris family, which seems to be
the consequence of a lack of communication by the Appellants more than any planning related reason. I ask that the Appellants proceed in a thoughtful manner to communicate with, and address any concerns, brought up by the neighbours.
While I share the concern brought up by the Chaggaris family about the lack of
privacy, I believe that the privacy screen as well as the lack of windows facing their property will result in their concerns being addressed. I note the concern about the lack of loss of view of the CN tower; however, the state of jurisprudence as it exists today is crystal clear about there being no right to a certain view or scenery, especially in dense, urban settings.
While the variances requested are fairly straight forward and the proposal is not
complex, I did detect an undercurrent of nervousness among the neighbours about the lack of communication or concern on the Appellants’ part to their concerns. I share the concern based on the perceived attitude of the Appellants, which comes across as cavalier, when not dismissive or disdainful, of the neighbours’ concerns, as well as conducting business with TLAB. I note that the applications were not accurately filled out in the beginning and were not updated until TLAB undertook to dismiss the application. While no particular weight may be attached to the absence of the Appellant for the TLAB hearing, my concerns about the Appellants’ understanding of their own proposal are strengthened by the confusing evidence heard from their representative, Mr. Sihota, who couldn’t verify information about variances when being examined by Mr. Schuman. The constant refrain of “The neighbours’ main concern was the deck, which
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
10 of 12
does not result in variances” did not assist me in coming to a conclusion, especially since the neighbours complained about privacy and not the size of the deck. I don’t hold Mr. Sihota responsible for not addressing the planning issues because he is not a planner; however, the Appellants’ approach to the project is concerning. Lastly, the Appellants relied on the City to provide planning evidence, leading me to further question how much they appreciate the importance of adhering to a decision of the TLAB. It is this concern that resulted in my suggesting that the privacy screen be increased to 1.8 m, instead of the proposed 1.5 m, which Mr. Sahota agreed to.
The above observations about the Appellant’s ability to understand the
implications of the decision may not be cause for refusing the appeal; however, I find it prudent to inform the Appellants that they should be careful about adhering to the Plans and not making any changes without consulting the City, as well as to communicate closely with the neighbours should there be questions from the latter. The neighbours may judiciously exercise their right to inform the City’s Municipal Licensing and Standards department in case they have concerns about an overbuild, and are not able to obtain a response from the Appellant. I reiterate that while this right exists, it should be used with an abundance of caution and only the Appellants don’t respond to concerns or dismiss the concerns.
The proposal is found to have satisfied Section 45(1) as well as the higher
policies, like the PPS and Growth Plan. The proposal is therefore approved, subject to the conditions listed in Paragraph 3 of the Decision and Order below. Lastly, by way of editorial comment, the 3 variances to be ruled upon are listed in rearranged numerical order below; this order is different from what was stated in the “Matters in Issue” section because of the modified proposal.
DECISION AND ORDER
1. The decision of the Committee of Adjustment dated 27 September, 2017, is set aside. The original Appeal, modified because of the redesign and the consequent removal of some variances, is allowed in part.
2. The following variances to the Zoning By-laws are approved based on the modified application:
1. Chapter 10.10.40.40.(2), By-law 569-2013
Additions to the rear of a semi-detached house erected before October 15, 1953, are permitted provided the floor space index as enlarged does not exceed 0.69 times the area of the lot (207.35 m²). The altered semi-detached house will have a floor space index equal to 0.75 times the area of the lot (225.83 m²). . 2. Chapter 10.5.60.50.(2), By-law 569-2013
The maximum permitted floor area of all ancillary buildings or structures on the lot is 40.0 m².
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
11 of 12
The total floor area of all ancillary buildings on the lot is 47.4 m². 3. Section 6(3) Part VI 1(I), By-law 438-86
Additions to the rear of a semi-detached house erected before October 15, 1953, or to a converted house are permitted provided the residential gross floor area as enlarged does not exceed 0.69 times the area of the lot (207.36 m²). The altered semi-detached house will have a residential gross floor area equal to 0.75 times the area of the lot (225.83 m²).
3. The following conditions are imposed, and have to be adhered to by the Appellant: 1. That the second floor of the proposed dwelling have a maximum building
depth of 10.65 metres, excluding the rear deck, and 15.3 metres, inclusive of the rear deck, as shown on the plans and elevations prepared by Acadia Drafting and dated March 8, 2018.
2. That the proposal be constructed and landscaped substantially in accordance with the site plan and elevations prepared by Acadia Drafting and dated March 8, 2018 (pages A1, A7, and A8), and January 15, 2018 (pages A12-A15).
3. That the path connecting the rear driveway with the rear staircase be comprised of permeable materials as shown on the site plan prepared by Acadia Drafting and dated March 8, 2018 (page A1).
4. That the applicant provide permanent, opaque privacy screens at the northern and southern edges of the rear, second storey deck, at a minimum height of 1.8 metres measured from the floor of the deck. The screen on the northern side to be comprised of frosted glass as shown on the plans and elevations prepared by Acadia Drafting and dated March 8, 2018 (pages A1-A9).
Decision of Toronto Local Appeal Body Panel Member: S. Gopikrishna TLAB Case File Number: 17 249169 S45 19 TLAB
12 of 12
XS. Gopikrishna
Panel Chair, Toronto Local Appeal Body
INDEX SHEET:
A1 COVER PAGE & SITE PLAN
A2 BASEMENT PLAN
A3 UNDERPINNING
A4 GROUND FLOOR PLAN
A5 SECOND FLOOR PLAN
A6 THIRD FLOOR PLAN
A7 BACK ELEVATION
A8 SIDE ELEVATION
A9 SECTION A-A
A10 GARAGE FLOOR PLAN
A11 GARAGE ROOF PLAN
A12 GARAGE FRONT ELEVATION
A13 GARAGE SIDE ELEVATION
A14 GARAGE BACK ELEVATION
A15 GARAGE SIDE ELEVATION
A16 GARAGE SECTION B-B
D1, 2, 3 DETAILS
PROPERTY LINE
GREEN AREA
EXISTING BUILDING
MAIN ENTRANCE
LEGEND :
⅊
SITE STATISTICS:
LOT AREA = 300.50 m² (3234.57 ft²)EXISTING DWELLING FOOT PRINT = 78.71 m² (847.27 ft²) 26.19%EXISTING GARAGE FOOT PRINT = 47.36 m² (509.81 ft²) 15.76%PROPOSED ADDITION FOOT PRINT = 18.30 m² (196.96 ft²) 6.09%PROPOSED ADDITION GROUND FLOOR = 23.79 m² (256.04 ft²) 7.92%PROPOSED DECK SECOND FLOOR = 7.51 m² (80.83 ft²) 2.50%FRONT YARD GREEN AREA = 17.46 m² (187.91 ft²) 57.79%BACK YARD GREEN AREA = 82.89 m² (892.25 ft²) 44.08%
PROPOSED ADDITION
KEY PLAN: 665 Shaw Street, Toronto, ON M6G 3L8
N
SURVEY INFORMATION :
SURVEY INFORMATION TAKEN FROM: VLADIMIR DOSEN SURVEYINGDONE ON: NOVEMBER 3rd, 2016LOT NUMBER: PART OF LOT 14PLAN NUMBER: 430
GENERAL NOTES:
1. WEEPING TILE IS TO DRAIN TO THE STORM SEWER, DITCH, DRYWELL OR INSTALL COVERED SUMP PIT WITH ANAUTOMATIC, PUMP
2. FOOTINGS- 18"x6" (457x152mm) POURED CONC. FOOTING ALL FOOTINGS SHALL REST ON NATURALUNDISTURBED SOIL OR COMPACTED GRANULAR FILL
3. CONCRETE- MIN. COMPRESSIVE STRENGTH OF 25MPa @ 28 DAYS W/ 5% TO 8% AIR ENTRAINMENT
4. INTERIOR STAIRSRISE: 4 7 8" (124mm) MINIMUM 7 7 8" (200mm) MAXIMUMRUN: 8 14" (210mm) MINIMUM 14" (356mm) MAXIMUMTREAD: 9 14" (235mm) MINIMUM 14" (356mm) MAXIMUMNOSING: 1" (25mm) MINIMUMHEADROOM: 80" (2032mm) MINIMUM
5. PRE-ENGINEERED GUARD HEIGHT OF 36" (914mm) IF TOP OF DECK EXCEEDS 24" (610mm) ABOVE GRADE OR 42"(1067mm) IF TOP OF DECK EXCEEDS 5' 11" (1803mm). GUARDS SHALL BE NON-CLIMBABLE AND VERTICAL PICKETSSHALL BE SPACED NO MORE THAN 4" (100mm) APART [AS PER OBC 9.8.8, OBC SB-7]
129'-4 3/8"[39.43m]
129'-5 1/8"
25'-0
"[7
.62m
]
25'-0
"[7
.62m
]
2'-4
3/4
"[0
.73m
]
12'-10"[3.91m]
50'-0 3/4"[15.26m]
66'-5 1/2"[20.26m]
34'-11 1/4"[10.65m]
15'-1 1/2"[4.61m]
24'-8 3/4"[7.54m]
11'-4 1/4"[3.46m]
13'-2 5/8"[4.03m]
50'-0 1/2"[15.25m]
30'-3 5/8"[9.24m]
24'-8 1/4"[7.52m]
11'-2 1/4"[3.41m]
16'-1
1 1/
8"[5
.16m
]2'
-5 1
/2"
[0.7
5m]
9"[0
.23m
]20
'-7 5
/8"
[6.2
9m]
3'-7
1/4
" [1
.10m
]
3'-8
1/2
"[1
.13m
]20
'-7 5
/8"
[6.2
9m]
7 7/
8" [0
.20m
]
EXISTING 2-1/2 STOREYBRICK DWELLING
SCOPE OF WORK:NEW UNIT SECOND & THIRD FLOORALTERATIONUNDERPINNINGADDITION 23.79 m² (256.04 ft²)DECK 2nd FLOOR 7.17 m² (77.15 ft²)GARAGE TO BE RAISED
665 SHAW STREET
SHA
W S
T.
LAN
E
PORCH
GRASS GRASS
PATH
PATH
PATH
DRIVEWAYPART OF LOT 14
⅊ ⅊
⅊ ⅊
⅊
⅊
⅊
⅊
DN
5R
22'-7
1/4
"[6
.89m
]
30'-4 5/8"[9.26m]
7 1/
8" [0
.18m
]
34'-11"[10.64m]
DN
6R
2'-6
5/8
" [0
.78m
]3'
-3"
[0.9
9m]
4'-5 1/2"[1.36m]
66'-2 1/8"[20.17m]
EXISTING GARAGETO BE INCREASED IN HEIGHT
15'-1 1/2"[4.61m]
8'-4 5/8"[2.56m]
4'-8 1/8"[1.43m]
8'-4 1/2"[2.55m]
4'-5 3/8"[1.36m]
7'-2"[2.18m]
7'-2"[2.18m]
7'-11 5/8"[2.43m]
15'-1 1/2"[4.61m]
6'-11"[2.11m]
3'-1
0"[1
.17m
]
1'-2
1/4
" [0
.36m
]
DN 1R
DN
19R
23'-5 5/8"[7.15m]
20'-9
1/8
" [6
.33m
]3'
-7 3
/4"
[1.1
1m]
7'-11 5/8"[2.43m]
PERMEABLE PAVERS
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Cover Page & Site Plan
A11:125
March 08, 2018
Addition
665 Shaw StreetToronto, ON
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
SITE PLAN1:125
[39.45m] M6G 3L8
1A1
0.38
12.
266
2.51
4
N
A9A-A
10.648
4.77
7
4.610
4.610
15.257
A9-A
EXISTING EXTERIOR & INTERIOR WALL
LEGEND:
2.273 2.172 0.889 0.901
0.241
3.583
PROPOSED CONCRETE BLOCK 10" FOUNDATION WALL (TYP):0.
768
1.13
70.
800
UP1
5R
EXISTING STAIRS TO BE REBUILD,SEE NOTE #4
PROPOSED 36" HIGH HANDRAIL,SEE NOTE #5
1 2 3
2"x8" SPF No.1/No.2@16"O/C
UNEXCAVATED
EXISTING STAIRS
SD
MECHANICAL ROOM
ELECTRICAL ROOM
HWT
FURN
ACE
HWT
FURN
ACE
3.48
0
10.642
6.88
9
EXISTING BASEMENT
EXST BEAM TO BE REPLACED WITH W250 x 33
EXST BEAM TO BEREPLACED WITH
W250 x 33
EXST
2"x
10"
@16
"O/C
SD
E
E
UNIT 1
FURN
ACE
HWT
FURN
ACE
HWT
SD
2
3
2.476
0.11
42.
438
0.11
4 0.99
1 0.49
5
1.0921.270
ELECTRICAL ROOM2.362
℄
℄
0.99
1
4.905
4.912
℄
℄
2.21
02.
794
2.79
4
2.21
04.
064
PROPOSED 3-2"X6"ABOVE
PROPOSED 3-2"X6" ABOVE
0.27
9
3.07
33.
200
℄℄℄
℄
5.045℄ ℄
EXST COLUMN TOREMOVE
2.378 0.356
EXST COLUMN TO BEREPLACED W/ 4"Ø
EXST COLUMN TO BEREPLACED W/ 4"Ø,
SEE DETAIL 2/D1
36"x36"x8" FOOTING
36"x36"x8" FOOTING
CONNECTION DETAIL,SEE DETAIL 1/D1
PRO
POSE
D 3
-2X8
CONNECTION DETAIL,SEE 2/D1
EXISTING STAIRS TO BE DEMOLISHED
SMOKE DETECTOR/ CO DETECTOR COMBINATION DEVICEINTERCONNECTED
SD
PROPOSED INTERIOR WALL:2"x 4", 2"x 6" SPF. STUDS @ 16" O.C. WITH BLOCKING AT MIDPOINT, 1/2" GYPSUM BOARD ON BOTH SIDES, TAPED ANDSANDED C/W PAINT FINISH. AROUND FOUNDATION WALL R22RIGID XPS INSULATION CAULKED AND TAPED
1 HR FIRE RATED 2"x4" @16 O/C W/ LAYERS OF 5/8"TYPE X GYPSUM BOARD ON BOTH SIDES
20 MIN. FIRE-RATED DOOR
EXISTING WALL TO BE DEMOLISHED
0.38
10.
180
2"x8
" SP
F N
o.1/
No.
2@
16"O
/C
0.25
44.
907
4.356
0.254
2.085
2.271
℄
DJ
2"x8
" SP
F N
o.1/
No.
2@
16"O
/C
CONNECTING TO PARTY WALL
EXISTING WINDOW TO BE FRAMED INW/ R22 RIGID XPS INSULATION
CAULKED AND TAPED
10"Ø ST. 32 MPa (TYP)
6"x6" POST (TYP)
0.381 1.704 2.271
℄℄
3-2"x10" BEAM
10"Ø ST. 32 MPa (TYP)
6"x6" POST (TYP)
℄
1.53
0
5.15
8
DOOR SCHEDULE
TAG SIZE REMARKS QUANTITY LINTEL SIZE
1 30" x 7'-0" 4 3- 2" x 6"
2 34" x 7'-0" 9 3- 2" x 6"
3 34" x 7'-0" 20 MIN. FIRE-RATED 1 3- 2" x 6"
4 40" x 7'-0" 20 MIN. FIRE-RATED 2 3- 2" x 6"
5 56" x 7'-0" LAUNDRY DOUBLE DOOR 1 3- 2" x 6"
6 64" x 7'-0" EXTERIOR SLIDING DOOR 2 3- 2" x 6"
E EXISTING DOOR
6"x6" POST ABOVE
12Ø ST. 32 MPa (TYP)
6"x6" POST (TYP)
DECK AND STAIRS ABOVE
8Ø ST. 32 MPa (TYP)
4"x4" POST (TYP)
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Basement Floor Plan
A21:60
Feb 24, 2017
Addition
665 Shaw StreetToronto, ONM6G 3L8
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
BASEMENTFLOOR PLAN1A2 1:60
A
0.61
0
EXISTING FOUNDATION WALL
EXISTING SLAB TO BE DEMOLISHED
4" WEEPING TILE
4" OF COMPACTEDGRAVEL
3" HI-40 INSULATIONBY STYROFOAM
4" NEW SLAB4" NEW SLAB2 31
NEW UNDERPINNING
0.10
2
0.387
15.354
0.45
7
1
2
3
3
2
1
3 2
1
1
3
2
3 2 1 3 2 1EQ
11.
134
1.13
41.
134
1.13
41.
134
0.387EQ2
1.1201.120 1.120 1.120 1.120 1.120 1.119 1.120 1.120 0.387
EQ3
1.13
11.
131
1.13
11.
131
1.13
1
EQ11.119
1.119 1.119
3 2 31 2 31 1
EXISTING SLAB TO BE DEMOLISHED
NEW 4" SLAB ON GRADE ON 4" OFCOMPACTED GRAVEL
EXISTING BRICK WALL AND 15 1/4" WIDEFOUNDATION UNDERPIN FOUNDATION
A3S
1.119 1.119 1.119 1.119 1.119 1.119 0.387
1
2
3
1.13
1
4.255
0.254
6.68
5
UNEXCAVATED
1.21
9(m
in)
EXISTING UNDERPINNING.DONE UNDER PARTY WALL BY 663 SHAW UNDERBLDG PERMIT # 03-113955 REVISION # 1(CONTRACTOR TO VERIFY EXISTINGUNDERPINNING DEPTH MATCHES PROPOSED)
1.13
4
10.648
6.70
5
UNDERSIDE @ +/- 10'-0" BELOW FIRST FLOOR
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Underpinning Plan & Section
A31:50
Feb 24, 2017
Addition
665 Shaw StreetToronto, ON
SECTION S2A3 1:50
UNDERPINNING PLAN1A3 1:50
M6G 3L8
1.15
90.
152
10.642
10.648
4.611
LEGEND:
4.611
15.258
15.252
PROPOSED INTERIOR WALL:2"x 4", 2"x 6" SPF. STUDS @ 16" O.C. WITH BLOCKING AT MIDPOINT, 1/2" GYPSUM BOARD ON BOTH SIDES, TAPED ANDSANDED C/W PAINT FINISHEXHAUST
SMOKE DETECTOR/ CO DETECTOR COMBINATION DEVICEINTERCONNECTED
SD
6.69
1
0.91
4
0.44
1
4.385
4.75
2
1.66
40.
813
1.00
3H
=4'-0
"
37.3
3ft²
1.359
0.267
13.7
2ft²
1.27
6
PROPOSED EXTERIOR WALL:FRAME WALL CONSTRUCTIONFINISH AS PER ELEVATIONS1" EXTERIOR STUCCO1" RIGID INSULATION W/ BUILDING PAPER 6" MINIMUM LAP7/8" O.S.B. SHEATHING2X6 WOOD STUDS @ 16" O.C. W/ BLOCKING AT MID POINTC/W R-29 SPRAY FOAM INSULATION IN CONTACT W/SHEATHINGCONTINUOUS VAPOUR/AIR BARRIERDOUBLE TOP PLATE @ BOTTOM PLATE @ SOLE PLATE1/2" GYPSUM BOARD ON INTERIOR SIDE, TAPED AND SANDEDC/W PAINT FINISH
1 HR FIRE RATED 2"x4" @16 O/C W/ LAYERS OF 5/8"TYPE X GYPSUM BOARD ON BOTH SIDES
1 HR FIRE-RATED FLOOR ASSEMBLY BETWEEN GROUND &SECOND FLOORS, W/ STC 50 RATING FLOOR FINISH,1/2" PLYWOOD SHEATHING ABSORPTIVE MATERIAL INCAVITY 2"x8" WOODEN JOIST W/ RESILIENT CHANNELS @16" O.C. TYPE-X GYPSUM BOARD DOUBLE LAYER
20 MIN. FIRE-RATED DOOR
DOOR SCHEDULE
TAG SIZE REMARKS QUANTITY LINTEL SIZE
1 30" x 7'-0" 4 3- 2" x 6"
2 34" x 7'-0" 9 3- 2" x 6"
3 34" x 7'-0" 20 MIN. FIRE-RATED 1 3- 2" x 6"
4 40" x 7'-0" 20 MIN. FIRE-RATED 2 3- 2" x 6"
5 56" x 7'-0" LAUNDRY DOUBLE DOOR 1 3- 2" x 6"
6 64" x 7'-0" EXTERIOR SLIDING DOOR 2 3- 2" x 6"
E EXISTING DOOR
EXISTING EXTERIOR & INTERIOR WALL
EXISTING WALL TO BE DEMOLISHED
2.61
2
1.51
1
10.643
6.88
9
3.1970.114
0.9020.114
0.7110.114
5.045
2.070 1.7271.130
1.025 1.092 1.397 0.864
0.75
63.
169
0.16
52.
134
1.44
4
0.61
71.
374
0.61
7
1.23
11.
231
1.524 1.251
3.81
0
℄ ℄
℄℄
℄
0.52
73.
054
℄
5.045
3.38
03.
137
3.13
73.
388
℄
℄ ℄
0.057
1.68
41.
359
0.99
7
0.81
6
0.18
0
0.225
0.18
4
0.22
5
5.16
00.
103
0.81
61.
626
H=7
'-0"
0.96
5PI
ER S
PAC
ING
0.10
2
℄
℄℄
1.186 3.552 0.864
℄ ℄ ℄
1.185
N
A9A-A
FG
KITCHEN
SD
VAPOUR/AIR BARRIER & SEAL TO JOIST & SUBFLOOR2"x6" WOOD STUDS @ 16" O.C.1 HR EXTERIOR WALL W/ 2x LAYERS OF 5/8" TYPE X GYPSUM BOARD
2"x12" SPF No.1/No.2@16"O/C
EXISTING WINDOW TO BEINCREASED TO OPENING
EXST
WIN
DO
W L
INTE
L
LIVING ROOM
3-2"
-10"
3-2"
-6"
DN
6R
PROPOSED STAIRS, SEE NOTE #4
PROPOSED 36" HIGH HANDRAIL,SEE NOTE #5
BEDROOM1A9A-A
DN
15R
UP
17R
ENTRANCE
DN
5R
PORCH
EXST
2"x
8" @
16"O
/C
W
DWALK INCLOSET
BATHROOM
LAUNDRY
SD
SD
SD
SD
SD
1 HR FIRE RATED 2"x4" @16 O/C W/LAYERS OF 5/8" TYPE X GYPSUM BOARD
ON BOTH SIDES
U/S OF STAIR1 HR FIRE-RATED
4
4
2 1
1
5
E
E
E
UNIT 1
UNIT 2
PROPOSED 3-2"X6"
PROPOSED 3-1 34" x 11 14" LVL
EXST
2"x
8" @
16"O
/CU/S OF STAIR1 HR FIRE-RATED
6
DECK AND STAIRS ABOVE
DJ
8Ø ST. 32 MPa (TYP)
4"x4" POST (TYP)
2-2"
x6"
2-2"
x6"
DJ
DJ
2-2"
x6"
2"x6
"LED
GER 2"x6"@16"O/C 2"x6"@16"O/C
12Ø ST. 32 MPa (TYP)
6"x6" POST (TYP)
6"x6" POST
SEE CONNECTION DETAIL 2, 3/D3
SEE DETAIL 1/D3
SEE DETAIL 4/D3
SEE CONNECTION DETAIL 5/D3
EXISTING OPENINGTO BE FRAMED IN
PROPOSED3-2"X6"
℄
℄
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Ground Floor Plan
A41:65
Feb 24, 2017
Addition
665 Shaw StreetToronto, ONM6G 3L8
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
GROUND FLOOR PLAN1A4 1:65
5.16
0
1.62
6H
=7'-0
"
0.46
40.
603
1.02
2
37.3
3ft²
EXISTING EXTERIOR & INTERIOR WALL
LEGEND:
EXISTING WALL TO BE DEMOLISHED
PROPOSED INTERIOR WALL:2"x 4", 2"x 6" SPF. STUDS @ 16" O.C. WITH BLOCKING AT MIDPOINT, 1/2" GYPSUM BOARD ON BOTH SIDES, TAPED ANDSANDED C/W PAINT FINISH
EXHAUST
SMOKE DETECTOR/ CO DETECTOR COMBINATION DEVICEINTERCONNECTED
SD
0.18
0
4.611
10.648
10.642
6.88
9
3.226 0.5970.165
1.003 1.524 3.454
3.226 0.848 1.425 0.914 0.102
3.289
1.194 1.003 1.092
0.940
0.59
11.
727
0.53
3
1.63
8
0.81
30.
711
1.32
7
℄ ℄
℄℄
℄℄
3.38
93.
137
℄
5.045 0.057
3.454
℄
3.38
03.
137
℄
1.32
91.
003
0.40
0 0.40
00.
416
0.18
0
DOOR SCHEDULE
TAG SIZE REMARKS QUANTITY LINTEL SIZE
1 30" x 7'-0" 4 3- 2" x 6"
2 34" x 7'-0" 9 3- 2" x 6"
3 34" x 7'-0" 20 MIN. FIRE-RATED 1 3- 2" x 6"
4 40" x 7'-0" 20 MIN. FIRE-RATED 2 3- 2" x 6"
5 56" x 7'-0" LAUNDRY DOUBLE DOOR 1 3- 2" x 6"
6 64" x 7'-0" EXTERIOR SLIDING DOOR 2 3- 2" x 6"
E EXISTING DOOR
1.16
80.
362
1.334 3.302 1.067 1.016
0.254
1.91
7
N
A9A-A
PROPOSEDDECK
SLOPE 2% min. TO NEW DRAINAGE
EXISTING ROOF TOBE DEMOLISHED
STEE
L LIN
TEL
2-10
2x89
x7.9
mm
EXISTING WINDOW TO BEINCREASED TO SLIDING DOOR
STAIRS BELOW
PROPOSED 42" HIGH GUARDRAIL,SEE NOTE #5
BEDROOM1A9A-A
DN 17RUP 14R
DINING ROOM
EXISTING SLOPE ROOF
EXST
2"x
8" @
16"O
/C
U/S OF STAIR1 HR FIRE-RATED
FG
KITCHEN
SD
LIVING ROOM
BATHROOM
W/D
CLO
SET
SD
2 1
2
2
UNIT 2
PROPOSED 3-1 34" x 9 14" LVL
PROPOSED 3-2"X6"
FG
EXISTING WINDOW TOBE DECREASED
PROPOSED 3-2"X6"
EXISTING WINDOW OPENING TOBE CLOSED, NEW EXTERIOR WALL
TO MATCH EXISTING FINISH
PROPOSED DRAINAGE
DN 1R
SLOPE
2% m
in. TO
NEW
DRA
INAGE
RUBBER MEMBRANE ROOFING ON SLOPING RIGIDROOFING MIN. 1:50 (SLOPE TO SCUPPER DRAINS)ON 5 8" PLYWOOD SHEATHING ON 2"x12" SPFNo.1/No.2 JOIST @16" O/C FILLED /W CLOSED CELLSPRAY FOAM INSULATION MIN. R50 ON 6 mil. POLYV.B. ON 12" DRYWALL
6
DN
19R
PROPOSED 36" HIGH HANDRAIL,SEE NOTE #5
6.32
8
1.5m OPAQUE PRIVACY SCREEN
1.53
0
PROPOSED MIN 1.5 M HIGHOPAQUE PRIVACY SCREENS
PROPOSED MIN 1.5 M HIGHOPAQUE PRIVACY SCREENS
PROPOSED MIN 1.5 M HIGHOPAQUE PRIVACY SCREENS
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Second Floor Plan
A51:65
March 08, 2018
Addition
665 Shaw StreetToronto, ON
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
SECOND FLOOR PLAN1A5 1:65
M6G 3L8
DECK BELOW
A9A-A
N
10.642
10.648
6.86
9
BEDROOM2
EXISTING EXTERIOR & INTERIOR WALL
LEGEND:
DN 14R
LOPE ROOF BELOW
EXISTING WALL TO BE DEMOLISHED
PROPOSED INTERIOR WALL:2"x 4", 2"x 6" SPF. STUDS @ 16" O.C. WITH BLOCKING AT MIDPOINT, 1/2" GYPSUM BOARD ON BOTH SIDES, TAPED ANDSANDED C/W PAINT FINISH. AROUND FOUNDATION WALL R22RIGID XPS INSULATION CAULKED AND TAPED
EXHAUST
SMOKE DETECTOR/ CO DETECTOR COMBINATION DEVICEINTERCONNECTED
SD
BEDROOM3
WALK INCLOSET
WALK INCLOSET
SDSD SD
3.39
71.
276
0.86
4
3.39
71.
276
0.86
4
2.56
51.
482
0.55
90.
286
1.7403.054 3.505
BATHROOM
CORRIDOR
1.654 1.400 1.753 1.753
℄
℄ ℄
0.432 1.308
℄
℄
1
2 2
2 2
UNIT 2
DOOR SCHEDULE
TAG SIZE REMARKS QUANTITY LINTEL SIZE
1 30" x 7'-0" 4 3- 2" x 6"
2 34" x 7'-0" 9 3- 2" x 6"
3 34" x 7'-0" 20 MIN. FIRE-RATED 1 3- 2" x 6"
4 40" x 7'-0" 20 MIN. FIRE-RATED 2 3- 2" x 6"
5 56" x 7'-0" LAUNDRY DOUBLE DOOR 1 3- 2" x 6"
6 64" x 7'-0" EXTERIOR SLIDING DOOR 2 3- 2" x 6"
E EXISTING DOOR
STAIRS BELOW
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Third Floor Plan
A61:65
Feb 24, 2017
Addition
665 Shaw StreetToronto, ONM6G 3L8
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
LAN FOR REFERENCE
A9A-A
S
6.88
9
THIRD FLOOR P1A6 1:65
BRICK
A9A-A
37.33ft²
2.13
4
1.626
0.19
2
37.33ft²
2.13
4
1.626PROPOSED MIN 1.5M FROSTED
GLASS PRIVACY SCREEN
1.21
9
1.003
13.72ft²
DISTANCE TO PROPERTY LINE 66'-2 1/8" (20.17m)
EXPOSED BUILDING FACADE 61.82 m² (665.40 ft²)EXISTING GLAZED AREA 2.32 m² (24.93 ft²)PROPOSED GLAZED AREA 8.21 m² (88.39 ft²)TOTAL GLAZED AREA 10.53 m² (113.32 ft²) 17.03%
PROPOSED STAIRS, SEE NOTE #4
PROPOSED 36" HIGH HANDRAIL,SEE NOTE #5
PROPOSED DRAINAGE
PROPOSEDSTUCCO
NEIGHBORING GUARDRAIL
6.328PROPOSED ADDITION
EXST. BASEMENT SLAB TOBE DEMOLISHED
AVERAGE GRADE
1.01
4
PROPOSED BASEMENT SLAB
0.61
0
PROPOSED UNDERPINNING
0.10
2
T/O FLAT ROOF
T/O PARAPET
FIN. CEILING GROUND FLOOR
FIN. CEILING GROUND FLOOR
FIN. GROUND FLOOR
1.62
35.
331
2.56
50.
273
2.46
40.
298
0.28
71.
067
T/O GUARDRAIL
EXISTING WINDOW TO BEDECREASED
1.003
1.21
90.
356
1.57
5
13.72ft²
EXISTING WINDOW OPENING TO BECLOSED, NEW EXTERIOR WALL TO
MATCH EXISTING FINISH
EXISTING WINDOW TO BEINCREASED TO SLIDING DOOR
PROPOSED 36" HIGH HANDRAIL,SEE NOTE #5
8"Ø ST. 32 MPa BEHIND
4"x4" POST BEHIND
2-2"x6" BEHIND
0.19
9
PROPOSED MIN 1.5M FROSTEDGLASS PRIVACY SCREEN
1.50
0
1.50
0
1.50
0
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Back (East) Elevation
A71:50
March 08, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
T) ELEVATION
PROPOSED MIN 1.5M FROSTEDGLASS PRIVACY SCREEN
BACK (EAS1A7 1:50
1.50
0
BRICK
BALUSTRADE POST @MAX. 4'-0" O.C.
PROPOSED 42" HIGH GUARDRAIL,SEE NOTE #5
EXST. BASEMENT SLABTO BE DEMOLISHED
AVERAGE GRADE
1.01
4
PROPOSED BASEMENT SLAB
0.61
0
PROPOSED UNDERPINNING
0.10
2
T/O FLAT ROOF
T/O PARAPET
FIN. CEILING GROUND FLOOR
FIN. CEILING GROUND FLOOR
FIN. GROUND FLOOR
1.62
35.
331
2.56
50.
273
2.46
40.
2980.
287
T/O GUARDRAIL
1.06
7
0.19
3
0.267
PROPOSED STAIRS,SEE NOTE #4
PROPOSED 36" HIGH HANDRAIL,SEE NOTE #5
0.15
2(m
in)
PROPOSEDSTUCCO
PROPOSED EXISTING
4.610PROPOSED ADDITION
12"Ø ST. 32 MPa
6"x6" POST
8"Ø ST. 32 MPa
4"x4" POST
2-2"x6"
0.15
2(m
in)
1.22
0(m
in)
0.15
2(m
in)
1.22
0(m
in)
3.21
7
0.49
5
2-6"x6" BEAM
2"x6"@16 O.C.
2"x6"@16 O.C.
SEE DETAIL 1/D3
SEE CONNECTIONDETAIL 2, 3/D3
D34
SEE CONNECTION DETAIL 5/D3
PROPOSED MIN 1.5M FROSTEDGLASS PRIVACY SCREEN
1.50
0
PROPOSED MIN 1.5M FROSTEDGLASS PRIVACY SCREEN
Phone: +1 (647) 478-9
Fax: +1 (877) 347-3
www.acadiadrafting.c
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIPRIOR TO COMMENCEMENT OF THE WODRAWINGS & SPECIFICATIONS ARE PROPACADIA DRAFTING AND MUST BE RETURUPON COMPLETION OF THE WORK. DRAARE NOT TO BE USED FOR OTHER PROJEWITHOUT THE WRITTEN CONSENT OF THDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUE
Proj
ect:
NOTES
DATE DESCRIPTION
Side (North) Elevation
A81:65
March 08, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
SIDE (NORTH) ELEVATION1A8 1:65
292
479
a
a
ONSRK. ALLERTY OF
NEDWINGS
CTSE
S:
1.95
60.
610
EXISTINGWALL
4" WEEPING TILE
4" OF COMPACTED GRAVEL
" HI-40 INSULATION BY STYROFOAM
4" NEW SLAB4" NEW SLAB
NEW UNDERPINNING
0.10
2
0.45
7
EXISTING STAIRS
PROPOSED 36" HIGH HANDRAIL,SEE NOTE #5
EXISTINGBASEMENT
KITCHENBEDROOM1
KITCHENBEDROOM1 CORRIDOR
EXISTING EXTERIOR & INTERIOR WALL
EXISTING WALL TO BE DEMOLISHED
UNIT 1 UNIT 1
UNIT 1
UNIT 2 UNIT 2
0.18
1
12
3
EXST. BASEMENT SLABTO BE DEMOLISHED
AVERAGE GRADE
1.01
4
PROPOSED BASEMENT SLAB
0.61
0
PROPOSED UNDERPINNING
0.10
2
T/O FLAT ROOF
T/O PARAPET
FIN. CEILING GROUND FLOOR
FIN. CEILING GROUND FLOOR
FIN. GROUND FLOOR
1.62
35.
331
2.56
50.
273
2.46
40.
298
0.28
7
EXISTING STAIRS TO BE REBUILD,SEE NOTE #4
UNEXCAVATED
1
3
EXISTING WINDOW TO BEINCREASED TO OPENING
2"x8" SPF No.1/No.2@16"O/C
ALIGN
T/O GUARDRAIL
1.06
7
EXISTING WINDOW TO BEINCREASED TO SLIDING DOOR
STEEL LINTEL2-102x89x7.9mm
LIVING ROOM
2"x12" SPF No.1/No.2@16"O/C
0.15
1
PROPOSED BALCONY
RUBBER MEMBRANE ROOFING ON SLOPING RIGID ROOFINGMIN. 1:50 (SLOPE TO SCUPPER DRAINS) ON 5 8" PLYWOODSHEATHING ON 2"x12" SPF No.1/No.2 JOIST @16" O/CFILLED /W CLOSED CELL SPRAY FOAM INSULATION MIN. R50ON 6 mil. POLY V.B. ON 12" DRYWALL
BALUSTRADE POST @MAX. 4'-0" O.C.
PROPOSED 42" HIGH GUARDRAIL,SEE NOTE #5
0.254
0.19
9
3-2"X10"
PROPOSED CONCRETE BLOCK 10"FOUNDATION WALL (TYP):
PROPOSED 36" HIGH HANDRAIL,SEE NOTE #5
1" EXTERIOR STUCCO1" RIGID INSULATION W/ BUILDING PAPER 6" MINIMUM LAP7/8" O.S.B. SHEATHING2X6 WOOD STUDS @ 16" O.C. W/ BLOCKING AT MID POINTC/W R-29 SPRAY FOAM INSULATION IN CONTACT W/SHEATHINGCONTINUOUS VAPOUR/AIR BARRIERDOUBLE TOP PLATE @ BOTTOM PLATE @ SOLE PLATE1/2" GYPSUM BOARD ON INTERIOR SIDE, TAPED AND SANDEDC/W PAINT FINISH
0.267
2.30
50.
248
2.75
60.
286
PROPOSEDEXISTING
4.610PROPOSED ADDITION
D1
2
D1
3
D2
2
EXISTING 2"x10"@16"O/C
EXISTING 2"x8"@16"O/C
EXISTING 2"x8"@16"O/C
D2
1
0.25
0
PROPOSED INTERIOR WALL:2"x 4", 2"x 6" SPF. STUDS @ 16" O.C. WITHBLOCKING AT MID POINT,1/2" GYPSUM BOARD ON BOTH SIDES, TAPEDAND SANDED C/W PAINT FINISH. AROUNDFOUNDATION WALL R22 RIGID XPS INSULATIONCAULKED AND TAPED
1 HR FIRE-RATED FLOOR ASSEMBLY BETWEENGROUND & SECOND FLOORS, W/ STC 50RATING FLOOR FINISH,1/2" PLYWOOD SHEATHING ABSORPTIVEMATERIAL IN CAVITY 2"x8" WOODEN JOIST W/RESILIENT CHANNELS @ 16" O.C. TYPE-X GYPSUMBOARD DOUBLE LAYER
F1
D1
1
CLO
SET 2
CLO
SET 2
CO
RRID
OR 1
BEDROOM3BEDROOM2 BATHROOM
UNIT 2 UNIT 2 UNIT 2
EXISTING STAIR BEHIND
F1 F1 F1
UNIT 2
PROPOSED 3-1 34" x 9 14" LVL
PROPOSED 3-2"X6"BEHIND THE WALL
PROPOSED 3-2"X6"
CO
RRID
OR
CO
RRID
OR2 1
BATHROOM
U/S OF STAIR1 HR FIRE-RATED
EXISTING STAIRS
PROPOSED 3-1 34" x 11 14" LVL
PROPOSED 3-2"X6"ABOVE 3-2"X8" BEAM
PROPOSED 3-2"X6"
PROPOSED 3-2"X6"BEHIND THE WALL
PROPOSED 3-2"X6"BEHIND THE WALL
EXST BEAM TO BE REPLACED WITH W250 x 33
EXST COLUMN TOREMOVE
EXST COLUMN TO BEREPLACED W/ 4"Ø
36"x36"x8" FOOTING
PROPOSED BASE PLATE10"x10"x1/2" PL
CONNECTION DETAIL,SEE 1/D1
CONNECTION DETAIL,SEE 2/D1
BITUMINOUS DAMP ROOFING ON 12"CEMENT PARGINGAPPROVED DRAINAGE LAYER B.M.C.E.
FLOORING MATERIAL ON 3 4" PLYWOOD T&G SUBFLOOR2"x8" SPF No.1/No.2 @16"O/C JOISTW/ R-29 CLOSED CELL POLYURETHANE INSULATION,VAPOUR/AIR BARRIER & SEAL TO JOIST & SUBFLOOR
WOOD SILL PLATE FASTENED TO EXSTINGFOUNDATION WALL W/ MINIMUM 1/2" DIAMETERANCHOR BOLTS EMBEDDED MIN. 4" IN CONCRETE@7'-10" MAX. & PROVIDE CAULKING OR GASKETBETWEEN PLATE & FOUNDATION WALL
2-2"x6" TOP PLATE
2"x6" WOOD STUDS @ 16" O.C.R29 BATT INSULATION58" SHEATHING WITH VAPOR BARRIER
DJ
PROPOSED STAIRS BEHIND
D3
1
1.50
0
PROPOSED MIN 1.5M FROSTED GLASS PRIVACY SCREEN
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Section A-A
A91:65
March 08, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
TION A-A
3
LEGEND: PROPOSED EXTERIOR WALL:FRAME WALL CONSTRUCTIONFINISH AS PER ELEVATIONS
SEC1A9 1:65
9'-6
1 2"
[2.9
1m]
512"
[0.1
4m]
9'-6
1 2"
[2.9
1m]
N
A16B-B
EXISTING 4"CONCRETE SLAB
EXISTING 2 CARSGARAGE
2"x1
2" S
PF N
o.1/
No.
2@
16"O
/C
LINE OF ROOF ABOVE
EXISTING GARAGE WALLSTO BE REBUILD TO 10'-0"
20'-7
58"
[6.2
9m]
20'-7
58"
[6.2
9m]
24'-834"
[7.54m]
7.525
A16B-B
EXISTING GARAGE DOORTO BE REPLACED
EXISTING GARAGE DOORTO BE REPLACED
934"
[0.2
5m]
9'-0
"[2
.74m
]H
=8'-0
"0.
305
9'-0
"[2
.74m
]H
=8'-0
"
934"
[0.2
5m]
PROPOSED METAL SIDING (PREFER TO ELEVATIONS):1" (25mm) METAL SIDINGSHEATHING PAPER W/ LAYERS TO OVERLAP EACH OTHEREXTERIOR TYPE SHEATHING2"x6" WOOD STUDS @ 16" O.C.DOUBLE PLATE AT TOP, SOLE PLATE AT BOTTOM. INTERIOR FINISH
LEGEND:
0.19
719
'-4"
[5.8
9m]
778"
[0.2
0m]
734"
[0.20m] 23'-434"
[7.13m]
734"
[0.20m] 1'-4"[0.41m]
1'-4
"[0
.41m
]
℄℄
℄℄
6"x6" POST
6"x6" POST
6"x6" POST
3-2"
x10"
BEA
M3-
2"x1
0" B
EAM
0.71
13'
-2"
[0.9
7m]
H=7
'-0"
9'-7
1 2"
[2.9
3m]
3'-2
"[0
.97m
]H
=7'-0
"
10'-458"
[3.17m]1.207
H=2'-1"
10'-458"
[3.16m]
2'-4
"[0
.71m
]
10'-458"
[3.17m]
EXISTING WINDOW
EXISTING DOOR TOBE RELOCATED
EXISTING WINDOW TO BEINCREASED TO DOOR
EXISTING STUDS TO BEREPLACED W/2"x6"
6"[0
.15m
]
1 HR EXTERIOR WALL W/ LAYER OF5/8" TYPE X GYPSUM BOARD
1'-4"[0.41m]
Phone: +1 (647) 478-929
Fax: +1 (877) 347-347
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIOPRIOR TO COMMENCEMENT OF THE WORKDRAWINGS & SPECIFICATIONS ARE PROPERACADIA DRAFTING AND MUST BE RETURNEUPON COMPLETION OF THE WORK. DRAARE NOT TO BE USED FOR OTHER PROJECTWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Garage Floor Plan
A101:50
Jan 15, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
GE FLOOR PLAN
2
9
NS. ALLTY OFD
WINGSS
GARA1A10 1:50
N
A16B-B
EXISTING GARAGE WALLSTO BE REBULD TO 10'-0"
A16B-B
22'-5
58"
[6.8
5m]
22'-5
58"
[6.8
5m]
27'-434"
[8.35m]
27'-414"
[8.34m]
GRAVEL FINISH ON 3 PLY FELT ROOFING 1/2" PLYWOOD SHEATING
2"x1
2"@
16"O
/C R
OO
F RA
FTER
PROPOSED 2%SLOPED ROOF
PROPOSED DRAINAGE
PROPOSED DRAINAGE
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Garage Roof Plan
A111:50
Jan 15, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
GARAGE ROOF PLAN1:50
1A11
A16B-B
METAL SIDING
8'-0
"[2
.44m
]
ADE
ST T/O PLATE
ST T/O ROOF
8'-0
"[2
.44m
]
9'-0"[2.74m]
9'-0"[2.74m]
OPOSED T/O ROOF
EXISTING GARAGE DOORTO BE REPLACED
EXISTING GARAGE DOORTO BE REPLACED
6"[0.15m]
1'-4"[0.41m]
2% SLOPE
Phone:
Fax:
info@a
www.a
*DO NOT SCALE*CONTRACTOR MUPRIOR TO COMMEDRAWINGS & SPEACADIA DRAFTINUPON COMPLETIOARE NOT TO BE UWITHOUT THE WRIDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISI
Proj
ect:
NOTES
DATE
Front (East
A12
Ja
Addition
665 Shaw StrToronto, ONM6G 3L8
T) GARAGE ELEVATION
GR
6'-1
1"[2
.11m
]
EX
EX
4'-8
"[1
.43m
]
PR
13'-1
1/2
"[4
.00m
]
+1 (647) 478-9292
+1 (877) 347-3479
cadiadrafting.ca
cadiadrafting.ca
ST VERIFY ALL DIMENSIONSNCEMENT OF THE WORK. ALLCIFICATIONS ARE PROPERTY OFG AND MUST BE RETURNEDN OF THE WORK. DRAWINGSSED FOR OTHER PROJECTSTTEN CONSENT OF THE
ONS & ISSUES:DESCRIPTION
) Garage Elevation
1:30
n 15, 2018
eet
FRONT (EAS1A12 1:30
GRADE
6'-1
1"[2
.11m
]
EXST T/O PLATE
EXST T/O ROOF
4'-8
"[1
.43m
]
PROPOSED T/O ROOF
METAL SIDING
1'-4"[0.41m]
1'-4"[0.41m]
13'-1
1/2
"[4
.00m
]
PROPOSED 2%SLOPED ROOF
12'-7
"[3
.83m
]
GRADE
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Side (South) Garage Elevation
A131:30
Jan 15, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
SIDE (SOUTH) GARAGE ELEVATION3 1:30
1A1
A16B-B
METAL SIDING
GRADE
6'-1
1"[2
.11m
]
EXST T/O PLATE
EXST T/O ROOF
13'-1
1/2
"[4
.00m
]
PROPOSED T/O ROOF
7'-0
"[2
.13m
]
3'-2"[0.97m]
7'-0
"[2
.13m
]
3'-2"[0.97m]
EXISTING DOOR TO BE RELOCATED EXISTING WINDOW TO BEINCREASED TO DOOR
6"[0.15m]
1'-4"[0.41m]
4'-8
"[1
.43m
]
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Back (West) Garage Elevation
A141:30
Jan 15, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
BACK (WEST) GARAGE ELEVATION4 1:30
1A1
GRADE
6'-1
1"[2
.11m
]
EXST T/O PLATE
EXST T/O ROOF
4'-8
"[1
.43m
]
PROPOSED T/O ROOF
1.207
0.63
5 EXISTING WINDOW
METAL SIDING
1'-4"[0.41m]
1'-4"[0.41m]
12'-7
"[3
.83m
]
13'-1
1/2
"[4
.00m
]
PROPOSED 2%SLOPED ROOF
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Side (North) Garage Elevation
A151:30
Jan 15, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
SIDE (NORTH) GARAGE ELEVATION15 1:30
1A
GRADE
6'-1
1"[2
.11m
]
EXST T/O PLATE
EXST T/O ROOF
4'-8
"[1
.43m
]
PROPOSED T/O ROOF
1'-4"[0.41m]
EXISTING CONCRETESLAB ON GRADE
3-2"x10" BEAM
EXISTING CONCRETESLAB
EXISTINGFOUNDATION
EXISTING GARAGE DOORTO BE REPLACED
OTE:ONCRETE SLAB ANDOOTING ARE EXISTING
3-2"x6" EXISTING GARAGE WALLS TOBE REBUILD TO 10'-0" HIGH
EXISTING STUDS TO BEREPLACED W/2"x6"
EXISTING WINDOW TO BEINCREASED TO DOOR
2"x12" SPF No.1/No.2 @16"O/C
1'-4"[0.41m]
2% SLOPE FOR DRAINAGE
13'-1
1/2
"[4
.00m
]
ASHPALT SHINGLES ON 5/8" PLYWOOD SHEATHING
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Garage Section B-B
A161:30
Jan 15, 2018
Addition
665 Shaw StreetToronto, ONM6G 3L8
GARAGE SECTION B-B1:30
NCF
1A16
ALIGN
EXISTING EXTERIOR BRICK
ADHESIVE MEMBRANE
EXISTING JOIST 2"x10"@16"O/C
EXISTINGBASEMENT
EXISTINGROUND FLOOR
2"x8"
PROPOSEDAREA
FLOORING MATERIAL ON 3 4" PLYWOOD T&G SUBFLOOR2"x8" SPF No.1/No.2 @16"O/C JOISTW/ R-29 CLOSED CELL POLYURETHANE INSULATION,VAPOUR/AIR BARRIER & SEAL TO JOIST & SUBFLOOR
12" STEEL TOPE PLATE WELDED TO BEAM & POST
4"Ø COLUMN
EXISTING JOIST
W250x33mm BEAM
EXISTING COLUMN TO BE DEMOLISHED
PLACE #55 ROOFING PAPER ORSUITABLE SUBSTITUTE UNDERBEAM/GIRDER AND SIDES
12" AIR SPACE ON BEAM/GIRDER
SIDES AND END OF BEAM/GIRDER
NEW W250 x 33 BEAM TO SIT IN EXST.BEAM POCKET IN FOUNDATION WALL
MINIMUM 3 12" BEARING OR 12" THETHICKNESS OF CONCRETE STEM WALL
EXISTING FOUNDATION WALL
EXISTING BEAM POCKET
PROPOSED 3-2"X6" ABOVE 3-2"X8" BEAM
PROPOSED 3-2"x8" BEAM
SIMPSON TOP FLANGE HANGERS WELDED TO W250x33mm BEAM PERMANUFACTURER INSTRUCTIONS
2"x8" SPF No.1/No.2@16"O/C
R29 BATT INSULATION
2-2"x6" TOP PLATE
2"x6" WOOD STUDS @ 16" O.C.
WOOD SILL PLATE FASTENED TO FOUNDATIONWALL W/ MINIMUM 1/2" DIAMETER ANCHORBOLTS EMBEDDED MIN. 4" IN CONCRETE @7'-10"O.C. MAX. & PROVIDE CAULKING OR GASKETBETWEEN PLATE & FOUNDATION WALL
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Details
D11"=1'-0"
Feb. 24, 2017
Addition
665 Shaw StreetToronto, ONM6G 3L8
Feb. 1st, 2017 APPLIED FOR PERMIT
Feb. 7th, 2017 REVISION
CONNECTION DETAIL1"=1'-0"
CONNECTION DETAIL1"=1'-0"
SECTION DETAIL2D1 1"=1'-0"
G
3D1
1D1
6"
FENDERS WASHERS
2-8mm X 152mm OUTSIDE DIAM.
3-2"x10"
RIM BOARD 2"x12" SPF No.1/No.2
2-2"x6" TOP PLATE
2-2"x6"
PREFINISHED ALUMINUMFLASHING AND PARAPET CAP (TYP.)
PROPOSED 1" EXTERIOR STUCCO
RUBBER MEMBRANE ROOFING ON SLOPING RIGID ROOFING MIN.1:50 (SLOPE TO SCUPPER DRAINS) ON 5 8" PLYWOOD SHEATHINGON 2"x10" SPF No.1/No.2 JOIST @16" O/CON 6 mil. POLY V.B. ON 12" DRYWALL
1" RIGID INSULATION
METAL FLASHING
WOOD STRIP
BUILDING PAPER 6" MINIMUM LAP
VAPOUR BARRIER
4"x4" BALUSTRADE POST @4'-0" O.C. MAX.ANCHORED TO RIM BOARD
WATER RESISTIVE BARRIER AND FLASHING
9 7 8"
7/8" O.S.B. SHEATHING
PROPOSED EXTERIOR WALL:FRAME WALL CONSTRUCTIONFINISH AS PER ELEVATIONS1" EXTERIOR STUCCO1" RIGID INSULATION W/ BUILDING PAPER 6" MINIMUM LAP7/8" O.S.B. SHEATHING2X6 WOOD STUDS @ 16" O.C. W/ BLOCKING AT MID POINTC/W R-29 SPRAY FOAM INSULATION IN CONTACT W/SHEATHINGCONTINUOUS VAPOUR/AIR BARRIERDOUBLE TOP PLATE @ BOTTOM PLATE @ SOLE PLATE1/2" GYPSUM BOARD ON INTERIOR SIDE, TAPED AND SANDEDC/W PAINT FINISH
PROPOSED SLOPE 3%
RUBBER MEMBRANEROOFING ON SLOPINGRIGID ROOFING
EXISTING 2"x8"@16"O/C
2"x12"
SIMPSON STRONG TIE
12" GYPSUM BOARD
ADHESIVE MEMBRANE
EXISTING BRICK WALL
3-1 34" x 11 14" LVL BEAMW/ MIN. R-50 INSULATION
2"x12" SPF No.1/No.2@16"O/C
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Details
D21 1/2"=1'-0"
Feb. 24, 2017
Addition
665 Shaw StreetToronto, ONM6G 3L8
CONNECTION DETAIL2 1 1/2"=1'-0"
SECTION DETAIL2D2 1 1/2"=1'-0"
1D
POST ANCHOR CONNECTEDTO CONCRETE PIERTO FASTEN WOODEN POSTW/ 1/2" DIA. ANCHOR BOLT MIN.100mm INTO CONCRETE PIER
12" DIA. ANCHOR BOLT
CONCRETE PIER MIN. 4' BELOWGRADE ON UNDISTURBED SOIL(REFER TO PLAN FOR Ø)
POST (REFER TO PLAN)
DECKING MATERIAL
LEDGER BOARD (REFER TO PLAN AND/ORSECTIONS), GLUED AND BOLTED WITH 12" DIA.
ANCHOR BOLT TO EXISTING STRUCTURALFRAMING TO SUPPORT DECK JOISTS
ADHESIVE MEMBRANE
EXISTING HOUSEBRICK FINISH
LEDGER BOARD (REFER TO PLAN AND/ORSECTIONS), GLUED AND BOLTED TO EXISTINGSTRUCTURAL FRAMING TO SUPPORT DECKJOISTS
WOOD JOISTS (REFER TO PLAN)
SIMPSON STRONG TIE
DECKING MATERIAL
STRUCTURAL FRAMING @24" O.C.
WOOD JOISTS (REFER TO PLAN)
JOIST (REFER TO PLAN)
WOOD BEAM (REFER TOPLAN AND/OR SECTIONS)
WOOD POST (REFER TOPLAN AND/OR SECTIONS)
DECKING MATERIAL
TREAD
NOSING
DROPPED FRAMING MEMBER INTO WHICHEACH STRINGER IS END NAILED USING 76mm
NAILS MAX. 900mm BETWEEN STRINGERS
2"x4" WOOD BLOCKING@ 4'-0" O.C. MINIMUMBETWEEN STRINGERS
2-9.5mm DIAMETER THRU BOLTS C/W 32mm O.D.WASHERS
2-#7x76 CORROSION RESISTANT SPIRAL NAILSOR SCREWS TYPICAL
BALUSTRADE POST @ MAX. 4'-0" O.C.
2"x4" BRIDGING JOIST
FENDERS WASHERS
PROPOSED GUARDRAIL,SEE NOTE #5
4"x4"BALUSTRADE POST@ MAX. 4'-0" O.C.
SPACER/PACKER
X 152mm OUTSIDE DIAM.
DECKING MATERIAL
WOOD BEAM (REFER TOPLAN AND/OR SECTIONS)
JOIST (REFER TO PLAN)
WOOD POST (REFER TOPLAN AND/OR SECTIONS)
Phone: +1 (647) 478-9292
Fax: +1 (877) 347-3479
www.acadiadrafting.ca
*DO NOT SCALE*CONTRACTOR MUST VERIFY ALL DIMENSIONSPRIOR TO COMMENCEMENT OF THE WORK. ALLDRAWINGS & SPECIFICATIONS ARE PROPERTY OFACADIA DRAFTING AND MUST BE RETURNEDUPON COMPLETION OF THE WORK. DRAWINGSARE NOT TO BE USED FOR OTHER PROJECTSWITHOUT THE WRITTEN CONSENT OF THEDESIGNER.
Draw
ing:
Scal
e:Da
te:
GEN
ERAL
NO
TES:
REVISIONS & ISSUES:
Proj
ect:
NOTES
DATE DESCRIPTION
Details
D31 1/2"=1'-0"
Feb. 24, 2017
Addition
665 Shaw StreetToronto, ONM6G 3L8
CONNECTION DETAIL4D3 1 1/2"=1'-0"
CONNECTION DETAIL1D3 1 1/2"=1'-0"
SECTION DETAIL5D3 1 1/2"=1'-0"
CONNECTION DETAIL2D3 1 1/2"=1'-0"
SECTION DETAIL3D3 1 1/2"=1'-0"
12" BOLT GLUED AND BOLTED TO EXISTING
2-8mm