+ All Categories
Home > Documents > Dehumidification at Part Load_ASHRAE_April2004

Dehumidification at Part Load_ASHRAE_April2004

Date post: 07-Apr-2018
Category:
Upload: mross0355
View: 230 times
Download: 0 times
Share this document with a friend
6
B y Don B . Shirey III, Member ASHRAE, and Hugh I. Henderson Jr., P.E., Member ASHRAE ngineers and equipment manufacturers need a bet er understanding of de- humidification performance at part-load conditions to evaluate the impacts of their design choices on indoor humidity levels. occupant comfort. and indoor air quality. Data from previous field test studies"? show that the moisture removal capacity of a cooling coil degrades at part-load conditions - especially when the su pply air fan ope rates continuously. Figure 1 illustrates this concept with transient data from a laboratory test. Degradation occurs because a portion of the moisture that condenses on the coil surfaces during the cooling on cycle (blue data) evaporates back into the airstream when the coil is off (green data). The data in the plot shows that the transient off-cycle perfor- mance of the coil IS essentially adiabatic with sensible cooling (red data) provided in conjunc- tion with evaporation of moisture (green data) back nto the irstream, The off-cycle sensible cooling diminishes with time as the amount of available moi ture on the coil surfaces decreases, As a result, a cooling coil that cyc es on and off in response to a control or thermostat signal will provide a smaller fraction of its total cooling capacity as moisture removal when the system spends relatively more time with the coil off. Conversely, the full latent removal capability of the system is only realized when the coil oper- ates continuously, The net impact of this latent degradation phe- nomenon is that dehumidification per ormance depends on the runtime fraction 0(' t he co oli ng coil (load divided by steady-state capacity), Fig- About the Authors Don B. Shirey III is principal resear h engineer at the Florida Solar Energy Center In Cocoa, Fla. Hugh I. Henderson IS Wth Caz enovia , N, Y . April 2004
Transcript
Page 1: Dehumidification at Part Load_ASHRAE_April2004

8/6/2019 Dehumidification at Part Load_ASHRAE_April2004

http://slidepdf.com/reader/full/dehumidification-at-part-loadashraeapril2004 1/6

B y Don B . Shirey III, Member A S H R A E , and Hugh I.Henderson Jr., P.E., Member A S H R A E

ngineers and equipment manufacturers need a better understanding of de-

humidification performance at part-load conditions to evaluate the impacts

of their design choices on indoor humidity levels. occupant comfort. and indoor

air quality. Data from previous field test studies"? show that the moisture removal

capacity of a cooling coil degrades at part-load conditions - especially when the

supply air fan operates continuously.

Figure 1 illustrates this concept with transient

data from a laboratory test. Degradation occurs

because a portion of the moisture that condenses

on the coil surfaces during the cooling on cycle

(blue data) evaporates back into the airstreamwhen the coil is off (green data). The data in the

plot shows that the transient off-cycle perfor-

mance of the coil IS essentially adiabatic with

sensible cooling (red data) provided in conjunc-

tion with evaporation of moisture (green data)

back into the airstream, The off-cycle sensible

cooling diminishes with time as the amount of

available moisture on the coil surfaces decreases,

As a result, a cooling coil that cycles on and off

in response to a control or thermostat signal will

provide a smaller fraction of its total cooling

capacity as moisture removal when the system

spends relatively more time with the coil off.

Conversely, the full latent removal capability of

the system is only realized when the coil oper-ates continuously,

The net impact of this latent degradation phe-

nomenon is that dehumidification performance

depends on the runtime fraction 0(' the cooling

coil (load divided by steady-state capacity), Fig-

About the Authors

Don B. Shirey III is principal research engineer at the

Florida Solar Energy Center In Cocoa, Fla. Hugh I.

Henderson [r ., P.E., IS a principal Wth CDH Energy in

Cazenovia , N, Y .

April 2004

Page 2: Dehumidification at Part Load_ASHRAE_April2004

8/6/2019 Dehumidification at Part Load_ASHRAE_April2004

http://slidepdf.com/reader/full/dehumidification-at-part-loadashraeapril2004 2/6

ure 2 shows the field-measured impact of pal i -load operation on

the sensible heat ratio (SIIR) of a residential water-to-air heat

pump with continuous supply air fan operarion.i When the cool-

ing system operates at steady-state conditions (i.e., at a runtime

fraction of one), the effective SHR of the system is 0.76. How-ever, as the compressor runs less often, the effective SHR of the

cooling coil increases. meaning that less moisture removal is

provided. I n this case, the cooling system provided no latent

removal for compressor runtime fractions less than 40%. Most

cooling coils spend a large number of hours at part-load condi-

tions. As a result, there is considerable degradation in the mois-

ture removal capacity for a system across the cooling season.

This part-load degradation causes space humidity levels to drift

upwards, especially on days when cooling loads arc modest.

Henderson and Rengarajan' developed a mathematicalmodel to predict the degradation of latent (dehumidification)

capacity of single-stage cooling equipment at part-load con-

ditions. This model, shown as a line on Figure 2, demonstrates

agreement with these measured data. The model parameters

and y were derived from on-site measurements for this

system to be 720 seconds (12 minutes) and 1.07 respectively?

Figure 3 shows the meaning of the model parameters

and y . An amount of moisture (;\:/) must build up on the coil

before condensate falls from the coil. After this time (to)' all the

latent capacity provided by the coil is "useful" moisture re-

April 2004

moval since this condensate leaves the system through the

drain. When the coil cycles off and the supply air tim contin-

ues to operate, the initial mass of moisture buildup on the coil

(A-~) evaporates back into the airstream. If the cooling coil

cycles back on before all the moisture has evaporated, then thetime until the first condensate removal is reduced for this next

cooling cycle since the coil starts out partially wetted.

The parameter is the ratio of the coil's moisture holding

capacity (Af) and steady-state latent capacity (QL)' is the

nominal time for moisture to fall from the coil (starting from a

dry coi I and ignoring transient effects at startup). The other

parameter y is defined as the ratio of the initial evaporation

rate (Q,J and the steady-state latent capacity (QL)' The latent

degradation model requires two additional parameters that also

arc associated with engineering models for part-load cffi-

ciency' These additional parameters include 1, the time con-

stant associated with latent capacity at startup (for the systemin figure 2 it was assumed to be 75 seconds). The other pararn-

eter is the maximum cycling rate of the thermostat as

defined in the NFM A thermostat test standard."

A project was initiated in 20U 1 to collect additionallabora-

tory and field measurements of part-load cooling coil perfor-

mance. These data arc used to verify the existing latent

degradation mathematical model and to refine or extend the

model to predict latent degradation for a wider range of cool-

ing systems (c.g., multistage cooling equipment and constant

air volume chilled water systems),

ASHRAE Journal 43

Page 3: Dehumidification at Part Load_ASHRAE_April2004

8/6/2019 Dehumidification at Part Load_ASHRAE_April2004

http://slidepdf.com/reader/full/dehumidification-at-part-loadashraeapril2004 3/6

.c

~ 20iii"CC

III

! 1 l 10

e.cl-

i- 0'uIIIC.III

(J-10

Off·Cycle Evaporation

Is Adiabatic Process;

Sensible = latent

-20

o 20 60 800

Minutes

Figure 1; Transient sensible & 0 latent capacity of cooling coil

over an operating cycle (supply air Ian operates continuously}.

For this project, a psychrometric testingfacility was set up

for evaluating air conditioner cooling coils with cooling ca-

pacities up to 3 tons (10.5 kW). The facility includes indoor

and outdoor test chambers capable of maintaining constant

temperature and humidity conditions as specified in ANSl/

ASHRAE Standard 37, Methods of Testingfor Rating Unitary

Air-Conditioning and Ifeat Pump Equipment= The facility is

able to hold the desired conditions, even for transient testing,

where the cooling equipment is cycled on and off.

Laboratory testing has been completed fix several coils. Each

coil is tested at various entering air temperature/humidity con-

ditions. airflow rates, and coil refrigerant temperatures. Over-

all. the test results from the laboratory tend to confirm the

following trends:

• The off-cycle evaporation process becomes adiabatic after

refrigerant migration inside the coil and system has subsided

one or two minutes after the compressor stops operating. The

type of refrigerant expansion device has some impact on the

length of this transition.

o The mass of moisture retained on the coil surface is mostly a

function of coil surface geometry with some secondary depen-

dence on dew-point temperature and velocity of entering air.

o The calculated values of the mode I parameter are

generally in line with the measured condensate delay time

(t). The delay time is a strong function of the entering airconditions. As entering conditions arc more humid. moisture

builds up faster on the coil. so the time to first condensate

removal is shorter. For example, the delay time for Coil 2

varies from 40 to 10 minutes as the entering clew point goes

from 50°F to 70°F (I O~C to 21°(').

• The moisture evaporation rate during the off cycle is a

function of the wet-bulb depression (i.e., the difference be-

tween the wet-bulb and dry-bulb temperatures) of the entering

air, as would be expected for an evaporative cooler. The re-

tained moisture on the cooling coil evaporates more quickly

44 ASHRAE Journal ashrae.org April 2004

100

1.10Continuous Supply Air

Fan Operation

720 sec... / v = 107 ...~.' .

Nma

, = 3.6 cyc/h

T = 75 sec

Measured Data:

• Entering RH: 57% to 63%

• Entering Air Temp.: 68"F to 72°F

o Loop Temps. : 65cF to gO°F

0.70

0.0 0.2 0.6 1.0.4

Runtime Fraction H

Figure 2; Field data showing the net impact of part-load op-

eration on sensible heat ratio':

twet = MolQL

y = QelQL

. . . .

c:41

j

Falls From Drain Pan

M o ~ Evaporation

4020 60

Minutes ~ ~ __

Figure 3: Concepts of moisture buildup and evaporation .

with drier inlet air conditions.

• The off-cycle evaporation trend implies that the wetted

surface area of the coil decreases ill proportion to the remain-

ing moisture mass. So the wet coil acts as an evaporative cooler

with progressively less surface area as moisture is evaporated

from the coil.

Table 1compares the latent performance model parameters

determined for the five coils that have been tested in the labo-

ratory to date. The tested coils ranged in size from 1.5 to 3 tons

(5.3-10.5 kW). with the total fin surface area varying by nearlya factor of two from the largest to the smallest coil. The mois-

ture-holding capacity per total finned surface area has been

very similar for most of the lab-tested coils at 8 to 9 lbs per

1.000 ft 2 (39 to 44 g/m-) of fin area. Less accurate field mea-

surements of moisture-holding capacity also have resulted in

a similar range of values: typically 6 to 10 lb per 1,000 ft2 (30

to 50 g/m"), The one exception observed thus far is lab Coil4.

This vertical slab coil with wavy fins retained stYli; ' to 60'%

more moisture per unit surface area than the other coils. Through

continued lab testing, we intend to quantify how fin spacing,

Page 4: Dehumidification at Part Load_ASHRAE_April2004

8/6/2019 Dehumidification at Part Load_ASHRAE_April2004

http://slidepdf.com/reader/full/dehumidification-at-part-loadashraeapril2004 4/6

o

ia:

() 1s tCycle

2nd Cycle

A 3rd Cycle

. . . .

t 'I lQ)

J:

Q)

: a' C i j 0.8eQ)

til

= 17.3. gamma = 1.50, expo

Steady State SHR = 0.755 (Based on Condensate)

0.0 0.2 0.4 0.6 0.8 1.0

Runtime Fraction (-)

Figure 4: Comparing measured latent degradation to LHR

model at nominal conditions (Coil 2).

fin type, and coil orientation affect the moisture-holding ca-

pacity of the coil.

The time for condensate to first fall from the coil ( I , , ) varied

from 12 minutes to 33 minutes for the lab test coils at nominal

conditions. Similar variations were observed for the model

parameter lweI' The results from field testing have generally

confirmed these parameter values for other cooling coils.

As part of the test program, we have completed a series of

quasi-steady cyclic tests in the laboratory with differing lengths

of compressor on and off times to simulate real-world cycling

performance. The lengths of the on and off times were selected

to correspond with the NEMA thermostat curve with a maxi-

mum cycle rate of three cycles/hour." The quasi-steady lab

testing showed the same degradation trends observed in the

1l3rd Cycle0:;::t 'I la:. . .

t 'I lQ)

J:

Q)

: a' C i j

0.8Q)

til

o ¢Steady State SHR = 0.730

(Based on Condensate)

0.2 0.8.0 0.4 0.6 1.0

Runtime Fraction -

Figure 5:Measured latent degradation with cycling fan at

nominal conditions.

field (e.g., in Figure 2) and confirmed that the model by

Henderson and Rengarajan' could reasonably predict part-

load dehumidification performance. The data points shown in

Figure 4 for Coil 2 correspond to the first, second, and third

operating cycles at the same inlet air conditions and discrete

runtime fractions. Typically, the results for the second and third

cycles for a given runtime fraction are in close agreement,

implying that at least two cycles arc necessary to achieve quasi-

steady conditions. The triangles from the third cycle match the

latent degradation model, which is shown as a line on the plot.

The parameters for the model include a of 17.3 minutes

and gamma of 1.5 for Coil 2. Similar tests have been C0111-

pleted at other operating conditions that also show agreement

between the model and the measured data.

Cooling Fin Surface Moisture-Holding Condo «:Capacity Area Capacity, M Delay Time, t

tons (kW) ft' (m') Ib (kg)Ib/1,000 ft·

Min Min(g/m2)

3.0 (10.5) 243.8 (22.7) 2.1 (0.95) 8.6 (42.1) 13.5 16.5

2.4 (8.4) 237.8 (22.1) 2.0 (0.91) 8.4 (41.1) 16.3 17.0

1.5 (5.3) 237.8 (22.1) 2.0 (0.91) 8.4 (41.1) 32.5 29.0

1.8 (6.3) 138.3 (12.8) 1.9 (0.86) 13.7 (67.0) 23.5 18.5

2.3 (8.1) 162.7 (15.1) 1.4 (0.64) 8.6 (42.1) 11.5 9.0

Coil 1

(Slanted Slab, Three Rows, 13 fpi,

Plain Fins, Orifice)

Coil 2 - Normal Air Flow Rate

(A-coil, Three Rows, 15.5 fpi, Lanced

Sine-Wave Fins, TXV)

Coil 3 - Coil 2 with low Airflow

(A-Coil, Three rows, 15.5 fpi, Lanced

Sine-Wave Fins, TXV)

Coil 4

(Vert. Slab, Two rows, 14 fpi,

Wavy Fins, Orif ice)

ceu s(Slanted Slab, Four Rows, 12 fpi,

Wavy Fins, Ori fice)

Notes: 1. Cooling capacity includes sensible and latent cooling at nominal conditions with airflow rate of 400 elm/ton (54 Lis per kW).

Nominal conditions correspond to ASH RAE Test A test point.

2. Fin surface area is gross fin area (coif face area x coil depth x fin spacing x 2).

3. Condensate delay time and are at nominal conditions.

46 ASH RAE Journal

Table I: Comparing measured performance p arsuneters for lab-tested cooling coils.

April 2004shrae.org

Page 5: Dehumidification at Part Load_ASHRAE_April2004

8/6/2019 Dehumidification at Part Load_ASHRAE_April2004

http://slidepdf.com/reader/full/dehumidification-at-part-loadashraeapril2004 5/6

Page 6: Dehumidification at Part Load_ASHRAE_April2004

8/6/2019 Dehumidification at Part Load_ASHRAE_April2004

http://slidepdf.com/reader/full/dehumidification-at-part-loadashraeapril2004 6/6

mate the moisture removal capacity of

cooling equipment and predict that space The latent capacity of a cooling coil

humidity levels are maintained at lower degrades at part-load conditions. This

levels than are observed in practice. Kosar degradation is most significant when the

et al.6 showed that ignoring latent degra- supply air fan operates continuously with

dation causes hourly building simulation a single-stage cooling coil. However,somemodels to underpredict space humidity degradation also occurs with modulated

levels by 5% to 10% RI [ under typical and staged cooling systems as well. Con-

conditions in a small office application. tinuous supply air fan operation is used

The latent degradation model from in nearly all commercial buildings to pro-

Henderson and Rengarajan has already vide the outdoor air ventilation require-

been incorporated into some whole build- mcnts prescribed by ANSliASHRAE

ing hourly simulation models7,~,9 and Standard 62, Ventilationfor Acceptable

will be available soon in other models.l? Indo or A ir Q ualit_v 1 1 and to provide air

This research project has confirmed the circulation for occupant comfort. The im-

validity of the latent degradation model pact of latent degradation must be con-

for single-capacity systems and is work- sidered in these circumstances,

ing to refine the model to consider more A recent utility research project indi-

applications. We are also working to UI1- cated that 2(%of Florida homeowners op-

derstand the moisture-related character- crated the supply air fan continuously. 12

istics of cooling coils so we can develop This fan operation mode may become

guidelines for selecting model parameters more prevalent in residential applications

for an array of cooling coil and equip- if its use is recommended for central air

ment configurations. filtration systems (e.g., uve lamps or

; : : :===============::; ! high-efficiency air filters), ventilation rc-

quiremcnts.l' or occupant comfort. How-

ever, most residential air conditioners

cycle the supply air fan on and off with

the cooling coil in response to the ther-

mostat signal (AUTO fan control), Most

homeowners in humid regions inherently

know this operating mode is preferable

since it provides reasonable moisture re-

moval, However, laboratory data have

confirmed that evenAUTO fan control can

result in significant degradation in dehu-

midification performance at part load.

This study is working to quantity the

equipment characteristics, control

modes, and operating conditions where

latent degradation is a concern. Algo-

rithms to predict latent degradation are

being incorporated into hourly wholebuilding energy analysis tools to allow

building designers and equipment manu-

facturcrs to quantity thc impact as well.

rAir Condit ioning, Inc.

is an Air Conditioning

Equipment provider/manufacturerseeking to expand into the US

market with their new line of

Portable Air Conditioners (PAC's),

Room Air Conditioners (RAC's)

and Ductless Mini-Split Systems.

We are seeking Dealers,

Distributors, Regional Sales

Managers and Service

Engineers. Experience in

HVAC products preferred,

Phone: 604-276-7641

Fax 604-276-8681

E-mail: [email protected]

Web: www.EnStar-HVAC.com

WV vW .I nf o im s ca/3216-16 o r C irc le 1 6

48 ASH RAE Journal

This article was prepared with the sup-

port of the U.S, Department of Energy.

under Award No. DE-FC26-0 INT41253.

However, any opinions, findings. conclu-

sions, or recommendations expressed

a s h r ae io r q

herein are those of the authors and do no

necessarily reflect the views of the DOE.

1. Khattar, M., N. Ramanan. and M. Swami.

1985. "Fan cycl ing effects on air conditioner

moisture removal performance in warm, hu-

mid climates." Presented at the International

Symposium on Moisture and Humidity April.

Washington, D.C.

2. Henderson, H. 1998. "The impact o f part -

load air-conditioner operation on dehumidifi-

cation performance: Validating a latent capacity

degradation model." Presented at ASH RAE's

TAQ & Energy '98 conference.

3. Henderson, H .. and K . Rengarajan. 1996.

"A model to predict the latent capacity of air

conditioners and heat pumps at part- load con-

ditions with constant fan operation." A SllR A 1 :'

Transactions I02( I): 266-274.

4. J\ ,E?vlA. 1990. Residential Controls-

Electric Wall-Mounted Room Thermostats,

NEMA Standards Publication No. DC 3. Na-

t ional Electrical Manufacturers Association.

Washington, D.C.

5. ANSJlASHRAE Standard 37-1988,

Methods ojTestingfor Rating Unitarv Air-Con-

ditioning and Heat Pump Equipment.

6. Kosar, D.R., M.J. Witte, D.B. Shirey, and

R.L. Hedrick. 1998. "Dehumidi fication issues

of Standard 62-1 Y89." ASHRAE Journal 40(3 ).

7. EPRI. 2000. Supermarket Simulation

Too] Version 3: Installation and User Guide,

Electric Power Research Institute, Customer

Solutions Group, Palo Alto, Calif. CM-

111112-R4.8. Shirey, O.B. and K. Rengarajan. "Impacts

of ASHRAE Standard 62-1989 on small

Florida officcs." A S1 fR A F T ra ns ac tio ns

102(l):153-165

9. EPA. 2001. Indoor J lumiditv Assessment

Tool -- Reference Manual. Available at

www.epa.govliaq!schooldesign/saves.html.

10. EncrgyPlus. 2003. Engineering Refer-

ence Manual for Energy PIllS. Available at

www.cncrgyplus.gov

II. ANSUASHRAE Standard 62-2001.

Ventilat ionfor Acceptable indoor Air Quality.

12. Personal correspondence with D. Parker

regarding a large scale utility study: Parker,

D.S., "Research highlights from a large scale

residential moni toring study in a hot climate."

Proceedings of International Svmposium on

Highly Efficien: Use ot Energyand Reduction

Environmental lmpact, pp. 108116, Ja-

pan Society fix the Promotion of Science Re-

search for the Future Program,

JPS-RFTF97P01002, Osaka, Japan. January

2002. (Also published as FSEC-PF369-02.

Florida Solar Energy Center. Cocoa, Fla.)

13. ASIIRAE Standard 62.2-20()3, Ventila-

tion for Acceptable Indoor Air Quality in row-

Rise Residential Buildings .•

April 2004


Recommended