+ All Categories
Home > Documents > Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach....

Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach....

Date post: 28-Sep-2020
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
8
Demand-controlled ventilation through a decentralized mechanical ventilation unit for office buildings Bonato Paolo 1 , D’Antoni Matteo 2 and Fedrizzi Roberto 3 1 Eurac Research, Institute for Renewable Energy Bolzano, Italy [email protected] 2 Eurac Research, Institute for Renewable Energy Bolzano, Italy [email protected] 3 Eurac Research, Institute for Renewable Energy Bolzano, Italy [email protected] ABSTRACT The paper focuses on the energetic and economic profitability of demand-controlled ventilation (DCV) strategies implemented in a decentralized ventilation application for tertiary office buildings.DCV consents to modulate the ventilation rate over time and meet the ventilation demand of the zone minimizing the energy- penalty of overventilation. Its cost-effectiveness is however not always guaranteed, since it depends on buildings use, climate, HVAC features and it should be assessed for each application [1].Numerical simulations are carried out for a set of representative European climates to compare the effectiveness of three sensor- based demand-controlled ventilation strategies with a baseline control strategy. To this end, numerical models of the reference zone and the ventilation unit are developed in TRNSYS and the occupancy profile is defined with a stochastic approach to provide a more realistic user behavior.It is found that the energy savings (heating, cooling and fan energy consumption) achieved with sensor-based demand-controlled ventilation are very limited for the selected application in all scenarios. Energy efficiency measures – such as the use of a high- efficiency heat recovery unit, the exploitation of free cooling or the installation of an high-performance ventilation unit – can significantly limit the energy savings achieved with DCV. Author Keywords Decentralized ventilation; Ventilation strategies; Product development; TRNSYS; Multifunctional facades. ACM Classification Keywords Design; Experimentation; Performance 1 INTRODUCTION The design of modern buildings pursue energy efficiency by improving thermal insulation and air-tightness of the envelope. As the heat losses across the building envelope decrease, the adoption of effective ventilation technological solutions and control strategies is crucial to further lower the building energy demand while satisfying thermal and IAQ comfort standards. In this regard, decentralized ventilation has recently gained the attention of the market and technological solutions are commercially available for both residential and tertiary building sectors. The air exchange is realized across the building envelope and multiple devices are installed to satisfy the ventilation demand of individual spaces. Decentralized ventilation benefits from several advantages over traditional centralized installations, such as lower power consumption (up to 50% lower average specific fan power [2]) and reduced technical spaces (from 30 cm [3] to 60 cm [4] lower floor-to-floor height). In addition, the downsizing of the ductwork can lead a higher degree of compartmentalization of the spaces with a consequent better control over the spread of pests, noise, odors, fire and smoke [5]. Decentralized ventilation systems are however typically more expensive to maintain because of the high number of installed devices [6] and complementary solutions have to be found to ventilate the core of the building. In addition, the noise emission and the regulation of indoor humidity may be relevant issues. With respect to control strategies, demand-controlled ventilation (DCV) reduces the energy penalty due overventilation by controlling the outdoor airflow rate intake based on occupancy level [7]. DCV has already been studied in literature [1,8] and is widely recognized as a viable ventilation strategy in standards and norms, e.g. ASHRAE 62.1 [9], EN 15251 [10]. In addition, DCV is valorized as an energy efficiency measure in different building standards, including LEED [11] and WELL [12] certification programs. Demand-controlled ventilation can be operated based on the input of sensors, such as CO2 tracers or passive infrared (PIR) sensors. CO2 tracers measure the concentration of carbon dioxide, which is considered a predictable indicator SimAUD 2018 June 05-07 Delft, the Netherlands © 2018 Society for Modeling & Simulation International (SCS)
Transcript
Page 1: Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach. The effectiveness of the HRU is defined as a function of the volumetric air flow

Demand-controlled ventilation through a decentralized mechanical ventilation unit for office buildings

Bonato Paolo1, D’Antoni Matteo2 and Fedrizzi Roberto3

1Eurac Research, Institute for

Renewable Energy

Bolzano, Italy

[email protected]

2Eurac Research, Institute for

Renewable Energy

Bolzano, Italy

[email protected]

3Eurac Research, Institute for

Renewable Energy

Bolzano, Italy

[email protected]

ABSTRACT

The paper focuses on the energetic and economic

profitability of demand-controlled ventilation (DCV)

strategies implemented in a decentralized ventilation

application for tertiary office buildings.DCV consents to

modulate the ventilation rate over time and meet the

ventilation demand of the zone minimizing the energy-

penalty of overventilation. Its cost-effectiveness is

however not always guaranteed, since it depends on

buildings use, climate, HVAC features and it should be

assessed for each application [1].Numerical simulations

are carried out for a set of representative European

climates to compare the effectiveness of three sensor-

based demand-controlled ventilation strategies with a

baseline control strategy. To this end, numerical models

of the reference zone and the ventilation unit are

developed in TRNSYS and the occupancy profile is

defined with a stochastic approach to provide a more

realistic user behavior.It is found that the energy savings

(heating, cooling and fan energy consumption) achieved

with sensor-based demand-controlled ventilation are very

limited for the selected application in all scenarios.

Energy efficiency measures – such as the use of a high-

efficiency heat recovery unit, the exploitation of free

cooling or the installation of an high-performance

ventilation unit – can significantly limit the energy

savings achieved with DCV.

Author Keywords

Decentralized ventilation; Ventilation strategies; Product

development; TRNSYS; Multifunctional facades.

ACM Classification Keywords

Design; Experimentation; Performance

1 INTRODUCTION

The design of modern buildings pursue energy efficiency by

improving thermal insulation and air-tightness of the

envelope. As the heat losses across the building envelope

decrease, the adoption of effective ventilation technological

solutions and control strategies is crucial to further lower the

building energy demand while satisfying thermal and IAQ

comfort standards.

In this regard, decentralized ventilation has recently gained

the attention of the market and technological solutions are

commercially available for both residential and tertiary

building sectors. The air exchange is realized across the

building envelope and multiple devices are installed to

satisfy the ventilation demand of individual spaces.

Decentralized ventilation benefits from several advantages

over traditional centralized installations, such as lower

power consumption (up to 50% lower average specific fan

power [2]) and reduced technical spaces (from 30 cm [3] to

60 cm [4] lower floor-to-floor height). In addition, the

downsizing of the ductwork can lead a higher degree of

compartmentalization of the spaces with a consequent better

control over the spread of pests, noise, odors, fire and smoke

[5]. Decentralized ventilation systems are however typically

more expensive to maintain because of the high number of

installed devices [6] and complementary solutions have to be

found to ventilate the core of the building. In addition, the

noise emission and the regulation of indoor humidity may be

relevant issues.

With respect to control strategies, demand-controlled

ventilation (DCV) reduces the energy penalty due

overventilation by controlling the outdoor airflow rate intake

based on occupancy level [7]. DCV has already been studied

in literature [1,8] and is widely recognized as a viable

ventilation strategy in standards and norms, e.g. ASHRAE

62.1 [9], EN 15251 [10]. In addition, DCV is valorized as an

energy efficiency measure in different building standards,

including LEED [11] and WELL [12] certification

programs.

Demand-controlled ventilation can be operated based on the

input of sensors, such as CO2 tracers or passive infrared

(PIR) sensors. CO2 tracers measure the concentration of

carbon dioxide, which is considered a predictable indicator

SimAUD 2018 June 05-07 Delft, the Netherlands © 2018 Society for Modeling & Simulation International (SCS)

Page 2: Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach. The effectiveness of the HRU is defined as a function of the volumetric air flow

of human occupancy. They should be located at the normal

breathing zone height [13] and away from doorways, heat

sources, people and air inlet devices [14] or, in alternative,

in the ventilation system return ductwork [15]. Different CO2

control strategies have been studied in the last decades, from

the simple on/off and proportional control strategies to the

more sophisticated PID algorithms [16] and fuzzy logic. PIR

sensors detect infrared light radiation from objects in the

field of view (typically 6-10 m distance, up to 360° angle).

They are typically inexpensive and easily integrated into

artificial lighting, heating and alarm systems. Other options

may be the interaction with light switches or with the radio

frequency identification systems that provide access to

locked building doors.

Concerning energy-related issues, demand-controlled

ventilation is likely to reduce the energy demand (heating,

cooling or fan energy use) in nearly all buildings and

climates [8], but most authors report that the cost-

effectiveness of the solution largely depends on climate,

occupancy, building thermal load, energy prices and HVAC

system features [1,8,17]. The International Energy Agency

in EBC Annex 18 [18] reported that the highest energy

savings are achieved in buildings where the occupancy is

highly variable and unpredictable such as sport centers (up

to 60%), assembly halls (up to 50%) and department stores

(up to 70%). The potential energy savings are instead lower

in office buildings (20-30% for 40% average presence and

3-5% for 90% average presence). In other works, the

implementation of DCV in office spaces allowed to reduce

the gas consumption of 30% for different locations [17] or

the total annual energy load (heating and cooling) of roughly

20% [19].

These topics are faced within the framework of an R&D

collaboration with a building façade manufacturer (Stahlbau

Pichler Srl) and an HVAC manufacturer (Bini Clima Srl).

The project aims to develop new concepts of unitized

curtain-wall façade modules for tertiary office buildings. In

this context, a decentralized ventilation unit is conceived and

a mock-up is assembled and tested in laboratory.

At this stage of the project, the optimization of control

strategies is a key step to enhance the performance of the

ventilation unit and improve the management of the

airflows: DCV can be embedded in decentralized ventilation

units with limited efforts, as no extra investment for VAV

boxes is required.

Nevertheless, the energy savings achieved with DCV in

decentralized ventilation concepts in office buildings are not

clear-cut:

• Decentralized ventilation units typically operate at lower

air pressure drops and specific fan power with respect to

centralized solutions. As consequence, the maximum

electricity savings achievable with DCV are limited.

• The installation of a high-efficiency heat recovery unit in

the ventilation unit in compliance with ErP Directive

2009/125/EC [20] is expected to reduce the energy penalty

of overventilation and thus also the maximum space

heating energy savings achievable with DCV.

• In literature, it is reported that the savings achievable with

DCV in office buildings are lower with respect to other

building typologies because the occupancy schedule is not

as unpredictable and variable.

As discussed above, DCV is an interesting solution but the

energy benefits need to be accurately quantified to

understand at which extent DCV is profitable for this

specific application. For this purpose, system simulation can

effectively assist the product design process. As seen, a

variety of sensors with different degrees of accuracy can be

used to detect the level of occupancy. In order to define the

range of profitability, three DCV strategies based on an

occupancy sensor, a people counter and a CO2 tracer are

developed and expected energy and cost savings for a typical

office cell are evaluated in comparison to a baseline scenario.

2 FAÇADE CONCEPT

The façade module is a pre-fabricated unitized curtain-wall

façade module that integrates a ventilation unit designed to

provide ventilation (up to 300 m3/h fresh air) and space

heating/cooling to typical office cells (Figure 1). The

ventilation unit is hosted in the parapet of a façade module

and is connected to the exterior by two apertures realized on

the side and on the bottom of the lower infill element. The

ventilation unit is wrapped in a layer of thermal insulation

material to reduce the thermal transmittance of the façade

module.

Figure 1. View of the reference office zone.

A simplified layout of the ventilation unit is presented in

Figure 2. The combined electrical consumption of the two

EC fans (M1 and M2 in Figure 2) ranges between 0.09

Wh/m3 to 0.4 Wh/m3 depending on the operation mode. The

ventilation unit is equipped with a counter-flow heat

recovery unit (HRU) with an effectiveness ranging between

83% and 89% in compliance with ErP Directive

2009/125/EC that can be entirely bypassed when convenient.

A F5 class filter and a G4 class filter (F1a, F1b and F2) are

mounted respectively in the fresh and return air ducts. A two-

way valve (V1) controls the water flow in the air-water heat

Page 3: Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach. The effectiveness of the HRU is defined as a function of the volumetric air flow

exchanger, whereas three dampers outline the air circuits in

the ventilation unit. More specifically, damper S1 and S3

control the bypass of the HRU, whereas damper S4 regulates

the recirculation of indoor air.

Figure 2. Simplified layout of the ventilation unit.

3 NUMERICAL MODELLING

A numerical model of the energy concept is developed in the

TRNSYS simulation environment [21]. Yearly simulations

are carried out by using a simulation time-step of 5 minutes.

The modelling activities can be summarized as follows:

• definition of reference thermal zone and climates;

• development of a numerical model of the ventilation unit

and calibration with laboratory measurements;

• definition of stochastic occupancy profiles reproducing the

fluctuation of the time of arrivals, departures etc.;

• development and implementation of three sensor-based

DCV strategies and a baseline ventilation strategy.

3.1 Ventilation unit

The ventilation unit is conceived as a grey-box numerical

model where each component is modelled by Types from the

standard or TESS [22] TRNSYS libraries.

The supply and return fans are modelled as variable speed

fans (Type 111b) that can maintain any outlet volumetric

flow rate between zero and a rated value. As the Type cannot

directly handle pressure drop effects, the power consumption

of the fans is calculated separately using polynomials that

describe the dependence of the electrical consumption on the

volumetric flow rate for each aeraulic circuit.

The HRU is modelled as an air-to-air heat exchanger by Type

760, which implements a “constant effectiveness - minimum

capacitance” calculation approach. The effectiveness of the

HRU is defined as a function of the volumetric air flow rates.

The sensible and latent heat transfer rates in the water coil

(Type 987) are defined according to a performance map

where water and air flow inlet conditions are used as

independent variables.

Airflow diverters (Type 11e) direct the air stream to different

outlets depending on the control signal and tee pieces (Type

11g) mix two inlet streams at different temperature or

humidity. Their combination consents to arrange the aeraulic

circuits defined by the active working scheme. Leakages and

thermal bridges across the air ducts are not accounted in the

current model.

Laboratory tests are carried out on a first prototype of

ventilation unit and the thermal and electrical performances

of individual components are measured to tune the TRNSYS

model. In particular, the following tests are conducted:

• The electricity absorbed by the supply and return fans is

measured with the use of energy meters for a set of fan

speeds in all possible system configurations. A map of the

electrical consumption is then drawn for the design

working conditions of the ventilation unit and provided to

the TRNSYS model.

• The performance maps of HRU and water coil provided by

the manufacturers are counter-checked for a number of

points in heating and cooling working modes. More

specifically, it was verified that the experimental measures

of the heat transfer between the fluid streams (air-to-water

or air-to-air) correspond to the expected values. The

thermal behavior of HRU and water coil is modelled in

TRNSYS with the use of the validated performance maps

of the installed components.

• As the ventilation unit is integrated in the building

envelope, it is important to characterize its performance as

passive thermal “layer”. To this end, the lumped thermal

resistance of the ventilation unit is evaluated under

stationary conditions in a climatic chamber with the “hot

box” method. The thermal resistance amounts to 0.53

(m2K)/W and is accounted in the current TRNSYS model

as a resistive layer in the spandrel panel stratigraphy.

3.2 Reference thermal zone

Because of the potentially high computational efforts, the

energy analysis of high-rise office buildings by means of

transient simulations needs adequate simplifications in the

development of a numerical model. To this end, common

praxis is to use a reference office cell for the assessment of

the energy demand of office buildings [23,24].

The reference zone is identified as a typical office cell

(Figure 1) that is 4.5 m wide, 6 m deep and 3 m high,

resulting in 27 m2 floor surface and 81 m3 gross air volume.

The façade wall has south exposure and is composed of three

1.5 m wide façade modules, of which one integrates the

decentralized ventilation unit. Each façade module

delimiting the thermal zone has a 60% window-to-wall ratio

and consists of a non-openable window and a lower infill

element. It is assumed that internal walls, floor and ceiling

do not exchange heat with adjacent zones (adiabatic

conditions), whereas the exterior surface of the façade is

exposed to the external environment.

The thermal behavior of the office room is modelled with

Type 56. Thermal characteristics of the building envelope

Page 4: Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach. The effectiveness of the HRU is defined as a function of the volumetric air flow

(opaque and transparent structures), internal gains,

ventilation and infiltration rates, shading factor and energy

generation and distribution efficiencies are listed in Table 1.

A setback strategy allows thermostat temperature variations

equal to -2 K (heating) and +1 K (cooling) during the closing

hours of the building.

Building assemblies – Glazing

g-value (glass)

Stockholm 0.63 -

Stuttgart 0.59 -

Rome 0.33 -

U-value (glass)

Stockholm 0.81 W/(m2K)

Stuttgart 1.40 W/(m2K)

Rome 1.29 W/(m2K)

U-value (window frame) 1.18 W/(m2K)

Building assemblies – Opaque surface

U-value

Stockholm 0.26 W/(m2K)

Stuttgart 0.33 W/(m2K)

Rome 0.57 W/(m2K)

Ventilation and infiltrations

Design vent. rate 11 L/s/pers

Night cooling vent. rate 1.5 1/h

Infiltration rate 0.15 1/h

Solar shadings

Shading factor (when closed) 70 %

Beam radiation limit for activ. 150 W/m2

Internal gains [26]

Persons – Latent gains 0.08 kg/h/pers

Persons – Sensible gains 70 W/pers

Appliances 7 W/m2

Artificial lighting 15.9 W/m2

Occupancy

Full occupancy 3 people

Crowding index 0.11 people/m2

Setpoint temperatures

Heating 20 °C

Cooling 26 °C

Energy generation and distribution

Avg. efficiency (gas boiler) 90 %

SEER (compression chiller ) 3.5 -

Thermal losses in pipework 10 %

Table 1. Office zone boundary conditions.

Three reference climatic conditions are selected for

simulation purposes. Stockholm (Sweden), Stuttgart

(Germany) and Rome (Italy) are chosen as they portray a

significant range of European climatic conditions and

represent relevant markets for the product under

development. The climate datasets used in the simulations

are generated using the database Meteonorm 7. They contain

hourly values of ambient air temperature, humidity,

pressure, solar radiation, cloudiness and other

meteorological parameters for a one-year period. For

comparison purposes, Table 2 shows average climatic

parameters for the selected locations, including:

• Ig,h and Ib,h are the annual global and beam solar irradiation

on horizontal surface;

• ϑamb,min and ϑamb,max are the annual minimum and maximum

dry-bulb ambient temperature;

• HDD12/20°C are the Heating Degree Days;

• CDD18°C are the Cooling Degree Days.

Parameter Unit Sto

ckh

olm

Stu

ttg

art

Ro

me

Ig,h kWh/(m2y) 953 1104 1637

Ib,h kWh/(m2y) 478 524 1013

ϑamb,min °C -16.3 -12.4 -1.4

ϑamb,max °C 29.6 32.3 33.1

HDD Kd 3998 3220 1355

CDD Kd 92 163 639

Table 2. Annual climatic parameters.

The indoor air quality is evaluated by calculating the CO2

concentration with a single-node model based on equation

(1) [1]. A number of assumptions is made:

• The measure of the CO2 concentration is accurate enough

to neglect the inaccuracy of the sensor (typically ±75 ppm

[26]);

• The indoor air volume is well-mixed;

• The outdoor CO2 concentration Cout and emission rate E

are fixed to 400 ppm and 0.31 L/min/person [8,9],

respectively.

e

V

EpCeCC out 11061 4 (1)

where:

C(τ) := indoor CO2 concentration at time-step τ [ppm];

Δτ := length of the time-step [h];

E := CO2 emission rate [L/min/person];

Cout := outdoor CO2 concentration [ppm];

p := number of occupants [person];

λ := air change rate (ventilation and infiltration) [1/h];

V:= room volume [m3].

3.3 Occupancy profile

Occupants can actively influence the surrounding

environment with interactions such as window opening,

Page 5: Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach. The effectiveness of the HRU is defined as a function of the volumetric air flow

shading control, lighting control and use of electrical

appliances.

One of the most common ways of modelling occupancy in

buildings is by repeating one or more daily occupancy

profiles, which may be specific to the building use or to the

occupant type. In this case, the variability of the occupancy

patterns of all users is replaced with an averaged behavior,

with the underlying assumption that simulation outcomes are

not significantly affected by this simplification.

As the presence of occupants directly affects the ventilation

unit operations, a more realistic characterization of the room

occupancy is required. To this end, a stochastic approach is

used to model the fluctuation in time of arrivals, departures

and breaks, so that a more natural spread of occupancy

patterns is composed around the reference average daily

occupancy profile.

In this work, the office room occupancy pattern is defined

through the stochastic approach formulated by Page et al.

[27] based on an inhomogeneous Markov chain interrupted

by periods of absence (weekends and holidays). During

regular working days, the state of presence (1-present or 0-

absent) at a given time-step (τ) only depends on the state of

presence at the previous time-step (τ-1). The probability of

transition (i.e. present to absent or vice versa) is time

dependent and is calculated according to a probability

presence profile and a “mobility parameter”. Average

occupancy profiles are commonly provided in energy codes

or standards for most building types. The mobility parameter

describes instead the probability of a change of state over

that of no change.

Figure 3. Average occupancy profile during working days.

In this work, the reference occupancy profile shown in

Figure 3 [25] and a constant parameter of mobility equal to

0.5 are used to generate a time series of the state of presence

for each user. The presence of multiple occupants sharing the

same zone is simulated by simply adding their presence

patterns, disregarding any possible interdependence. During

weekends and holidays (weeks number 1, 33, 34 and 52) the

office room is assumed to be empty.

3.4 Ventilation control strategy

The control logic of the ventilation unit is designed to

guarantee thermal comfort and a ventilation rate of 11

L/s/person, as prescribed for office spaces in UNI 10339 [28]

in compliance with UNI EN 15251 [10].

The fresh air intake is kept at the hygienic ventilation rate

(120 m3/h at full occupancy), unless the free cooling

potential is exploited. The supply ventilation rate can be

increased up to 300 m3/h recirculating indoor air to enhance

the heat transfer from the water coil to the office room.

The HRU is used to transfer heat between the fresh and

return air streams, but is by-passed when its use is not

convenient, typically summertime. The formation of ice in

the HRU during wintertime is prevented by mixing

recirculated indoor air with the fresh airflow before the inlet

of the HRU so that condensation does not occur in the return

air section of the HRU.

The control logic of the ventilation unit requires three inputs

that are (1) ambient air temperature, (2) indoor air

temperature and (3) occupancy level. The control logic is

formalized with a clear hierarchical approach, as shown in

Figure 4. Controllers elaborate feedback signals acquired by

temperature and presence sensors in Boolean format. The

operation schemes of the ventilation unit are defined as an

algebraic calculation of such Boolean variables. The control

signals are elaborated as combination of operation schemes

and modulation coefficients, which in turn can be constant

values or function of the measured variables.

Figure 4. Structure of the control logic.

Three advanced ventilation strategies (St2, St3 and St4) are

compared to a baseline strategy (St1), as described below:

• Fixed time schedule (St1, baseline). The ventilation unit

logic solely relies on a fixed time schedule that records the

opening hours of the building. The ventilation unit cannot

detect whether the room is occupied or not and thus

operates providing the design hygienic ventilation rate for

full occupancy (120 m3/h) during the opening hours of the

building;

• Occupancy sensor (St2). The ventilation unit detects

whether a zone is occupied or not (i.e. motion detectors,

light switch), but is unable to distinguish the occupancy

level. Consequently, the design hygienic ventilation rate

Page 6: Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach. The effectiveness of the HRU is defined as a function of the volumetric air flow

for full occupancy is provided whenever the presence of

one or more users is detected;

• People counter (St3). The ventilation unit detects the

number of people in the room (e.g. thermal counters) and

the hygienic ventilation rate for the full room is scaled

proportionally to the occupancy level;

• CO2 tracer (St4). A gas tracer measures the indoor

concentration of CO2, which is considered a predictable

indicator of occupancy. The hygienic ventilation rate is

adapted to the actual ventilation demand, which is

determined comparing the CO2 concentration in the office

room to a threshold. A multistage control is implemented

and the hygienic ventilation rate is varied between 0 and

120 m3/h in a discreet number of steps according to the

stage level.

In all scenarios, a purge cycle equivalent to 2 1/h air change

rates is performed before the opening hours of the building

as recommended in UNI EN 15251 [10] to reduce any

appreciable buildup of non-occupant-related contaminants.

4 RESULTS

Table 3 shows the simulation results for the three

representative locations and the four ventilation strategies

(St1, St2, St3 and St4). Annual space heating and cooling

energy demand and fans electrical consumption are

provided.

Location Strategy Qheat Qcool Wel

[kWh/(m2y)]

Stockholm

St1 19.9 10.8 4.6

St2 19.0 10.8 4.5

St3 17.7 10.8 4.4

St4 17.0 10.8 4.3

Stuttgart

St1 17.5 14.8 4.8

St2 16.6 14.8 4.7

St3 15.6 14.7 4.6

St4 15.0 14.7 4.5

Rome

St1 4.5 30.2 5.5

St2 4.1 30.0 5.5

St3 3.9 29.7 5.3

St4 3.8 29.7 5.3

Table 3. Annual space heating (Qheat) and cooling (Qcool) energy

demand and fans electrical consumption (Wel).

As expected, space heating and cooling demand respectively

increase and decrease with latitude. The space heating

demand of the office zone ranges from 4.5 kWh/(m2y) in

Rome to 19.9 kWh/(m2y) in Stockholm, whereas the space

cooling demand ranges from 30.2 kWh/(m2y) in Rome to

10.8 kWh/(m2y) in Stockholm. The space heating energy

savings achieved with DCV are largely dependent on the

climate, with decreasing savings from colder climates (up to

2.9 kWh/(m2y) in Stockholm) to warmer climates (up to 0.7

kWh/(m2y) in Rome). Space cooling energy savings are

instead visible only in Rome (around 0.5 kWh/(m2y)), where

DCV allows to reduce the fresh air intake during hot days in

summertime. The fans electrical consumption is rather

constant among climates (4.5-5.5 kWh/(m2y)) and savings

up to 0.3 kWh/(m2y) can be achieved with DCV. Comparing

the three different DCV strategies, ventilation strategies St4

and St2 achieve respectively the highest and the lowest

energy savings in all locations.

Figure 5. Fresh air intake and CO2 concentration (strategy St1).

Figure 6. Fresh air intake and CO2 concentration (strategy St2).

Figure 7. Fresh air intake and CO2 concentration (strategy St3).

Figure 8. Fresh air intake and CO2 concentration (strategy St4).

Page 7: Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach. The effectiveness of the HRU is defined as a function of the volumetric air flow

Concerning IAQ, the indoor air quality falls within class

IDA2 or better during all occupation hours in all scenarios,

according to the classification provided in EN 13779 [29].

Figures 5 to 8 show the fresh air intake and the CO2

concentration in the office room during the same working

day for all ventilation strategies.

5 DISCUSSION

Overall, the energy savings achieved with the sensor-based

DCV strategies are modest and in general lower than the

results seen in literature. The reasons of such deviation can

be motivated by three factors.

Firstly, the electricity savings that can be achieved are

limited. As already mentioned, decentralized ventilation

units typically profit from modest pressure drops and low

fans power and thus the margin to reduce the electrical

consumption is limited. In addition, the ventilation unit is

sized for a design air rate of 300 m3/h that is needed to deliver

enough space heating and cooling power to the office cell.

As consequence, the electricity savings achieved adjusting

the ventilation rate in the range 0..120 m3/h are low.

Furthermore, the efficiency of the EC fans is not constant but

tend to decrease at low-very low airflows. Such an effect can

be hardly accounted with simpler models based on the use of

constant specific fan power values, but it can be appreciated

when the fans electrical consumption is tuned to the

performance of real components, as in this case.

Secondly, an intensive exploitation of free cooling during

occupancy hours is observed in all locations. When free

cooling is exploited, DCV is not fruitful as the fresh air

intake is increased over the minimum hygienic ventilation

rate to maximize the valuable cooling effect of ventilation.

This aspect is especially relevant for modern office

buildings, where the good thermal insulation reduces the

heat losses through the building envelope and the high

internal gains might cause overheating over peak hours also

during mid-seasons.

Thirdly, the use of a high-efficiency HRU has a significant

impact on the success of DCV. In order to support this thesis,

an additional set of simulations is performed assuming a

lower heat recovery efficiency equal to 50%. Table 4 shows

the energy results for ventilation strategies St1 and St4.

Location Strategy Qheat Qcool Wel

[kWh/(m2y)]

Stockholm St1 28.3 10.6 4.4

St4 22.3 10.7 4.2

Stuttgart St1 24.0 14.6 4.5

St4 19.1 14.6 4.3

Rome St1 6.5 29.9 5.2

St4 4.9 29.5 5.1

Table 4. Annual space heating (Qheat) and cooling (Qcool) energy

demand and fans electrical consumption (Wel). (HRU eff: 50%).

The annual space heating energy savings achieved by St4 are

much more significant when the sensible efficiency of the

HRU is lower. Comparing the low-efficiency scenario to the

high-efficiency scenario, the space heating energy savings

achieved by St4 double in all the analyzed climates and

increase from 2.9 to 6.1 kWh/(m2y) in Stockholm, from 2.4

to 4.9 kWh/(m2y) in Stuttgart and from 0.7 to 1.6 kWh/(m2y)

in Rome. A modest reduction of fans electrical consumption

and space cooling energy demand can be observed with

respect to the data shown in Table 3. This is due to a slightly

lower average temperature in the office cell that reduces the

use of the cooling coil and of the free cooling operation

mode.

To conclude, an economic analysis is conducted to evaluate

the profitability of DCV in the analyzed scenarios, assuming

a purchase cost of energy equal to 0.20 €/kWh for electricity

and 0.10 €/kWh for gas. Table 5 shows the energy-related

operation costs and savings for all scenarios.

Location Strategy Cost [€/y] Saving [€/y]

Stockholm

St1 109.7 -

St2 106.3 3.3

St3 101.2 8.5

St4 98.4 11.2

Stuttgart

St1 109.4 -

St2 106.1 3.3

St3 102.0 7.4

St4 99.9 9.6

Rome

St1 96.8 -

St2 94.5 2.3

St3 92.9 3.9

St4 92.3 4.5

Table 5. Annual energy-related operation costs and savings.

The cost savings are low in scenarios, especially in Rome

where they remain under 4.5 €/y. Savings up to 9.6 €/y and

11.2 €/y are achieved in Stuttgart and Stockholm. It is also

observed that ventilation strategy St4 achieves the highest

cost savings with respect to the other strategies in all the

considered climates.

6 CONCLUSIONS

Based on the analyzed building and weather file, one of the

preliminary conclusion is that the implementation of a

demand-controlled ventilation (DCV) strategy in a

decentralized ventilation unit such as the one developed does

not lead to significant energy or cost savings. With respect

to the baseline scenario, the highest cost savings are

achieved with the use of a CO2 tracer (strategy St4). In this

case, the energy bill can be reduced of 4.5 €/y in Rome, 9.6

€/y in Stuttgart and 11.2 €/y in Stockholm.

The simulation work allowed to verify how energy

efficiency measures such as the use of high-efficiency

HRUs, the exploitation of free cooling or the installation of

ventilation units with low specific fan power are not synergic

to the use of DCV and may reduce its cost-effectiveness.

Page 8: Demand-controlled ventilation through a decentralized ... · capacitance” calculation approach. The effectiveness of the HRU is defined as a function of the volumetric air flow

Future studies could investigate the link between average

occupancy level and energy savings and define at which

conditions the implementation of DCV in the developed

decentralized ventilation unit is profitable. Moreover, a

sensitivity analysis could be carried out to understand how

design choices such as thermostat temperatures, façade

assemblies or building use affect the overall effectiveness of

DCV.

REFERENCES

1. Fisk, W. J., De Almeida, A. T. Sensor-based demand

controlled ventilation: a review. Energy and buildings

29 (1998), 35-45.

2. Merzkirch, A., Maas, S., Scholzen, F., Waldmann, D.

Field tests of centralized and decentralized ventilation

units in residential buildings – Specific fan power,

heat recovery efficiency, shortcuts and volume flow

unbalances, Energy and Buildings 116 (2016), 376-

383.

3. Mahler, B. Himmler, R. Results of the evaluation

study DeAL, Decentralized façade integrated

ventilation systems, Proc. 8th ICEBO (2008).

4. Franzke, U. Heidenreich, R., Ehle, A., Ziller, F.

Comparison between Decentralized and Centralized

Air Conditioning Systems, ILK Dresden (2003).

5. CMHC. Assessment of Suite Compartmentalizing and

Depressurization in new High-Rise Residential

Buildings, Technical Series 05-112 (2005).

6. Berkel, S. Residential ventilation: a review of

established systems and preliminary laboratory

investigation of an innovative fire wire heat recovery

ventilator, Proc. 14th conference of building science

and technology.

7. Schell, B., Turner, S.C., Shim, R.O., Application of

CO2-based demand-controlled ventilation using

ASHRAE standard 62: Optimizing Energy Use and

Ventilation, ASHRAE Transactions 104 (1998),

1213-1225

8. Emmerich, S. J., Persily, A. K. State-of-the-Art

Review of Cow Demand Controlled Ventilation

Technology and Application, NISTIR 6729 (2001).

9. ASHRAE. ASHRAE Standard 62.1-2016: Ventilation

for Acceptable Indoor Air Quality.

10. European Commission. EN 15251:2008 Indoor

environmental input parameters for design and

assessment of energy performance of buildings

addressing indoor air quality, thermal environment,

lighting and acoustics.

11. U.S. Green Building Council. LEED Reference Guide

for Green Building Design and Construction, (2009).

12. International WELL Building Institute. WELL

Building Standard, Version 1.0 (2014).

13. Stymne, H., Sandberg, M., Mattsson, M., Dispersion

pattern of contaminants in a displacement ventilated

room – implications for demand control, Proc. 12th

AIVC (1991).

14. Stymne, H., Sandberg, M., Dispersion pattern of

carbon dioxide from human sources - a factor to

consider in demand controlled ventilation systems,

Demand Controlled Ventilating Systems – Case

Studies, IEA Annex 18 (1992).

15. Reardon, J. T., Shaw, C. Y., Vaculik, F., Air change

rates and carbon dioxide concentrations in a high-rise

office buildings, ASHRAE Transactions 100 (1993),

pp. 1251-1263.

16. Chao, C.Y.H., Hu J.S, Development of a dual-mode

demand control ventilation strategy for indoor air

quality control and energy savings, Building and

Environments 39 (2003), 385-397.

17. Brandemuehl, M. J., Braun, J. E. The impact of

Demand-Controlled and Economizer Ventilation

Strategies on Energy Use in Buildings. ASHRAE

Transaction 105(2), Annual meeting 1999, USA.

18. International Energy Agency (IEA). A summary of

IEA Annex 18 - Demand Controlled Ventilating

Systems (1997).

19. Persily, A., Musser, A., Emmerich, S., Taylor, M.,

Simulation of Indoor Air Quality and Ventilation

Impacts of Demand Controlled Ventilation in

Commercial and Institutional Buildings, NISTIR 7042

(2003).

20. EU Commission Regulation No 1253/2014 of 07 July

2014 implementing Directive 2009/125/EC.

21. Klein, S.A., Beckman, W.A., Mitchell, J.W., Duffie,

J.A., Duffie, N.A. et al., TRNSYS 17, transient

system simulation program. University of Wisconsin,

Madison, WI, USA (1979), www.trnsys.com.

22. TESS. TESS Component Libraries: General

Descriptions, http://www.trnsys.com/tesslibraries/

TESSLibs17_General_Descriptions.pdf.

23. Erhorn, H., et al., BESTFACADE, WP 4 Report

“Simple calculation method”, (2007).

24. CISBE, TM35: Environmental Performance Tooling

for Glazed Facades, (2004).

25. SIA. SIA 2024:2015: Raumnutzungsdaten für die

Energie- und Gebäudetechnik.

26. ASHRAE, ASHRAE User’s Manual. Standard 62.1-

2004: Ventilation for Acceptable Indoor Air Quality,

(2005).

27. Page, J., Robinson, D., Morel, N., Scartezzini, J. L. A

generalized stochastic model for the simulation of

occupant presence. Energy and buildings 40 (2008),

8398.

28. Italian National Unification Body (UNI). UNI

10339:1995 Impianti aeraulici a fini di benessere.

29. European Commission, EN 13779:2007 Ventilation

for non-residential buildings – Performance

requirements for ventilation and room-conditioning.


Recommended