Denver Fire Alarm Technician Practice Number 1

Date post: 22-Feb-2016
Category:
Upload: thuong
View: 50 times
Download: 3 times
Share this document with a friend
Description:
Ted “ Smitty ” Smith. Denver Fire Alarm Technician Practice Number 1. Instructions. This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National Fire Alarm and Signaling Code and the Denver Building Amendments. - PowerPoint PPT Presentation
83
Denver Fire Alarm Technician Practice Number 1 Ted “Smitty” Smith
Transcript
Page 1: Denver Fire Alarm Technician Practice Number 1

Denver Fire Alarm Technician Practice Number 1

Ted “Smitty” Smith

Page 2: Denver Fire Alarm Technician Practice Number 1

Instructions This slide show contains multiple timed questions. All

questions can be answered using the International Fire Code, The National Fire Alarm and Signaling Code and the Denver Building Amendments.

If you put the slide show into slide show mode, the slides will transition automatically and allow you 3 minutes for each question. The answers will stay up for only 15 seconds. When you reach the end of the practice test there will be a slide that reads STOP.

You can then click on the slide and the questions will be repeated without the timer so that you can write down questions and answers and take notes.

During the timed section, do not worry about writing down the correct answer. Proceed through the timed section then review the questions and answer again without the timer.

Page 3: Denver Fire Alarm Technician Practice Number 1

In the absence of a specific performance based design criteria, smooth ceiling smoke detector spacing shall be a nominal _________ feet.

Page 4: Denver Fire Alarm Technician Practice Number 1

30 feet 17.7.3.2.3.1

Page 5: Denver Fire Alarm Technician Practice Number 1

Signals with carbon monoxide detectors transmitted to a fire alarm system shall be permitted to be _____________________________ signals.

Page 6: Denver Fire Alarm Technician Practice Number 1

Supervisory 23.8.4.7

Page 7: Denver Fire Alarm Technician Practice Number 1

When a supervising station receives a trouble signal they must dispatch personnel with in ________ hours to initiate maintenance, if necessary.

Page 8: Denver Fire Alarm Technician Practice Number 1

4 hours 26.3.7.4

Page 9: Denver Fire Alarm Technician Practice Number 1

Complete records of all signals received by a supervising station shall be kept for a period of ________________.

Page 10: Denver Fire Alarm Technician Practice Number 1

1 year 26.4.6.1

Page 11: Denver Fire Alarm Technician Practice Number 1

A type public alarm system shall be required where the number of all alarms required to be retransmitted exceeds _____________ per year.

Page 12: Denver Fire Alarm Technician Practice Number 1

2500 27.5.2.1.2

Page 13: Denver Fire Alarm Technician Practice Number 1

A fire alarm system installed in an occupancy that does not require a fire alarm system shall ____________________________.

A. comply with NFPA 72 B. not be required to comply with NFPA

72 C. comply with chapters 17 and 18 of

NFPA 72 only D. comply with the NEC only

Page 14: Denver Fire Alarm Technician Practice Number 1

A. comply with NFPA 72 (23.2.3.1)

Page 15: Denver Fire Alarm Technician Practice Number 1

A class A circuit in a protected premises using physical conductors shall be installed so that the outgoing and return conductors are routed separately unless for a distance not to exceed __________ feet where the conductors enter or exit the initiating device, notification appliance, or control unit enclosures. 3 6 10 15

Page 16: Denver Fire Alarm Technician Practice Number 1

10 (23.4.2.2 List item 1)

Page 17: Denver Fire Alarm Technician Practice Number 1

A class B circuit in protected premises shall be designed and installed in a manner to ensure so that a _____________________ signal shall annunciate in the condition of an open or ground condition in the wiring. Supervisory Alarm Trouble None of the above

Page 18: Denver Fire Alarm Technician Practice Number 1

Trouble (23.5.2)

Page 19: Denver Fire Alarm Technician Practice Number 1

Actuation of alarm notification appliances or emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ____________ after the activation of an initiating device. 5 seconds 10 seconds 30 seconds 1 minute

Page 20: Denver Fire Alarm Technician Practice Number 1

10 seconds (23.8.1.1)

Page 21: Denver Fire Alarm Technician Practice Number 1

Signals from a carbon monoxide detectors and carbon monoxide detection systems transmitted to a fire alarm system shall be permitted to be ______________________ signals. Alarm Trouble Supervisory Indicative

Page 22: Denver Fire Alarm Technician Practice Number 1

Supervisory (23.8.4.7)

Page 23: Denver Fire Alarm Technician Practice Number 1

Visible notification signals _______________________ be required in exit stair enclosures and exit passageways. Shall Shall not

Page 24: Denver Fire Alarm Technician Practice Number 1

Shall not (23.8.6.2.1)

Page 25: Denver Fire Alarm Technician Practice Number 1

The evacuation signal ____________________ be required to operate in elevator cars. Shall Shall not

Page 26: Denver Fire Alarm Technician Practice Number 1

Shall not (23.8.6.2.4)

Page 27: Denver Fire Alarm Technician Practice Number 1

As applies to guard’s tour supervisory service, the system shall automatically transmit a delinquency signal within ________________ after the predetermined actuation time if the guard fails to actuate a tour station as scheduled. 10 seconds 30 seconds 5 minutes 15 minutes

Page 28: Denver Fire Alarm Technician Practice Number 1

15 minutes (23.16.4)

Page 29: Denver Fire Alarm Technician Practice Number 1

The occurrence of any single fault at the protected premises that disables transmission between any low-power radio transmitter and the receiver/ fire alarm control unit shall cause a latching trouble signal within ____________. 10 seconds 30 seconds 60 seconds 200 seconds

Page 30: Denver Fire Alarm Technician Practice Number 1

200 seconds (23.18.4.2)

Page 31: Denver Fire Alarm Technician Practice Number 1

A fire alarm system must be supplied by a minimum of __________ independent and reliable power supplies. One Two Three Four

Page 32: Denver Fire Alarm Technician Practice Number 1

Two (10.5.3.2)

Page 33: Denver Fire Alarm Technician Practice Number 1

A coded alarm signal shall consist of not less than__________ complete rounds of the number transmitted. One Two Three Four

Page 34: Denver Fire Alarm Technician Practice Number 1

Three (10.9.3)

Page 35: Denver Fire Alarm Technician Practice Number 1

A coded supervisory signal shall be permitted to consist of ___________ rounds of the number transmitted to indicate a supervisory off-normal condition. One Two Three Four

Page 36: Denver Fire Alarm Technician Practice Number 1

Two (10.11.1.1)

Page 37: Denver Fire Alarm Technician Practice Number 1

Two way telephone communications circuit installation conductors shall be monitored for ______________ fault conditions that would cause the telephone communications circuit to become fully or partially inoperative. Ground fault Open fault Both ground fault and open fault None of the above

Page 38: Denver Fire Alarm Technician Practice Number 1

Open fault (10.17.2.2.1)

Page 39: Denver Fire Alarm Technician Practice Number 1

Spot type smoke detectors shall be located on the ceiling, or if on a side wall, between the ceiling and ___________ inches down from the ceiling to the top of the detector. 6 inches 12 inches 18 inches 24 inches

Page 40: Denver Fire Alarm Technician Practice Number 1

12 inches ( 17.7.3.2.1)

Page 41: Denver Fire Alarm Technician Practice Number 1

The lamps and LED’s for the control equipment of a Mass Notification System shall be visually inspected ________________________________. Monthly Quarterly Semi-annually Annually

Page 42: Denver Fire Alarm Technician Practice Number 1

Semi-Annually (Table 14.3.1 Page 57)

Page 43: Denver Fire Alarm Technician Practice Number 1

STOP> End of Timed Questions

STOP

STOP

STOP

STOP

STOP

Page 44: Denver Fire Alarm Technician Practice Number 1

In the absence of a specific performance based design criteria, smooth ceiling smoke detector spacing shall be a nominal _________ feet.

Page 45: Denver Fire Alarm Technician Practice Number 1

30 feet 17.7.3.2.3.1

Page 46: Denver Fire Alarm Technician Practice Number 1

Signals with carbon monoxide detectors transmitted to a fire alarm system shall be permitted to be _____________________________ signals.

Page 47: Denver Fire Alarm Technician Practice Number 1

Supervisory 23.8.4.7

Page 48: Denver Fire Alarm Technician Practice Number 1

When a supervising station receives a trouble signal they must dispatch personnel with in ________ hours to initiate maintenance, if necessary.

Page 49: Denver Fire Alarm Technician Practice Number 1

4 hours 26.3.7.4

Page 50: Denver Fire Alarm Technician Practice Number 1

Complete records of all signals received by a supervising station shall be kept for a period of ________________.

Page 51: Denver Fire Alarm Technician Practice Number 1

1 year 26.4.6.1

Page 52: Denver Fire Alarm Technician Practice Number 1

A type public alarm system shall be required where the number of all alarms required to be retransmitted exceeds _____________ per year.

Page 53: Denver Fire Alarm Technician Practice Number 1

2500 27.5.2.1.2

Page 54: Denver Fire Alarm Technician Practice Number 1

A fire alarm system installed in an occupancy that does not require a fire alarm system shall ____________________________.

A. comply with NFPA 72 B. not be required to comply with NFPA

72 C. comply with chapters 17 and 18 of

NFPA 72 only D. comply with the NEC only

Page 55: Denver Fire Alarm Technician Practice Number 1

A. comply with NFPA 72 (23.2.3.1)

Page 56: Denver Fire Alarm Technician Practice Number 1

A class A circuit in a protected premises using physical conductors shall be installed so that the outgoing and return conductors are routed separately unless for a distance not to exceed __________ feet where the conductors enter or exit the initiating device, notification appliance, or control unit enclosures. 3 6 10 15

Page 57: Denver Fire Alarm Technician Practice Number 1

10 (23.4.2.2 List item 1)

Page 58: Denver Fire Alarm Technician Practice Number 1

A class B circuit in protected premises shall be designed and installed in a manner to ensure so that a _____________________ signal shall annunciate in the condition of an open or ground condition in the wiring. Supervisory Alarm Trouble None of the above

Page 59: Denver Fire Alarm Technician Practice Number 1

Trouble (23.5.2)

Page 60: Denver Fire Alarm Technician Practice Number 1

Actuation of alarm notification appliances or emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ____________ after the activation of an initiating device. 5 seconds 10 seconds 30 seconds 1 minute

Page 61: Denver Fire Alarm Technician Practice Number 1

10 seconds (23.8.1.1)

Page 62: Denver Fire Alarm Technician Practice Number 1

Signals from a carbon monoxide detectors and carbon monoxide detection systems transmitted to a fire alarm system shall be permitted to be ______________________ signals. Alarm Trouble Supervisory Indicative

Page 63: Denver Fire Alarm Technician Practice Number 1

Supervisory (23.8.4.7)

Page 64: Denver Fire Alarm Technician Practice Number 1

Visible notification signals _______________________ be required in exit stair enclosures and exit passageways. Shall Shall not

Page 65: Denver Fire Alarm Technician Practice Number 1

Shall not (23.8.6.2.1)

Page 66: Denver Fire Alarm Technician Practice Number 1

The evacuation signal ____________________ be required to operate in elevator cars. Shall Shall not

Page 67: Denver Fire Alarm Technician Practice Number 1

Shall not (23.8.6.2.4)

Page 68: Denver Fire Alarm Technician Practice Number 1

As applies to guard’s tour supervisory service, the system shall automatically transmit a delinquency signal within ________________ after the predetermined actuation time if the guard fails to actuate a tour station as scheduled. 10 seconds 30 seconds 5 minutes 15 minutes

Page 69: Denver Fire Alarm Technician Practice Number 1

15 minutes (23.16.4)

Page 70: Denver Fire Alarm Technician Practice Number 1

The occurrence of any single fault at the protected premises that disables transmission between any low-power radio transmitter and the receiver/ fire alarm control unit shall cause a latching trouble signal within ____________. 10 seconds 30 seconds 60 seconds 200 seconds

Page 71: Denver Fire Alarm Technician Practice Number 1

200 seconds (23.18.4.2)

Page 72: Denver Fire Alarm Technician Practice Number 1

A fire alarm system must be supplied by a minimum of __________ independent and reliable power supplies. One Two Three Four

Page 73: Denver Fire Alarm Technician Practice Number 1

Two (10.5.3.2)

Page 74: Denver Fire Alarm Technician Practice Number 1

A coded alarm signal shall consist of not less than__________ complete rounds of the number transmitted. One Two Three Four

Page 75: Denver Fire Alarm Technician Practice Number 1

Three (10.9.3)

Page 76: Denver Fire Alarm Technician Practice Number 1

A coded supervisory signal shall be permitted to consist of ___________ rounds of the number transmitted to indicate a supervisory off-normal condition. One Two Three Four

Page 77: Denver Fire Alarm Technician Practice Number 1

Two (10.11.1.1)

Page 78: Denver Fire Alarm Technician Practice Number 1

Two way telephone communications circuit installation conductors shall be monitored for ______________ fault conditions that would cause the telephone communications circuit to become fully or partially inoperative. Ground fault Open fault Both ground fault and open fault None of the above

Page 79: Denver Fire Alarm Technician Practice Number 1

Open fault (10.17.2.2.1)

Page 80: Denver Fire Alarm Technician Practice Number 1

Spot type smoke detectors shall be located on the ceiling, or if on a side wall, between the ceiling and ___________ inches down from the ceiling to the top of the detector. 6 inches 12 inches 18 inches 24 inches

Page 81: Denver Fire Alarm Technician Practice Number 1

12 inches ( 17.7.3.2.1)

Page 82: Denver Fire Alarm Technician Practice Number 1

The lamps and LED’s for the control equipment of a Mass Notification System shall be visually inspected ________________________________. Monthly Quarterly Semi-annually Annually

Page 83: Denver Fire Alarm Technician Practice Number 1

Semi-Annually (Table 14.3.1 Page 57)


Recommended