    General Design of Firefighting - Sprinkler System(Description, spacing, flow rate, Pressure Requirements,Applications and Related Standards)

    Parts of a Sprinkler

    The components of a sprinkler head are: . Frame or casting, . Deflector. Fusible element or frangible bulb, . Pip Cap, . Pintle Screw. . Belleville

    SpringSome Sprinklers utilize low zinc content brass to provide a more resilient frameor casting. This low zinc content protects the sprinkler from de zincification.The Bellville Spring seals the water way of the sprinkler. This metal to metalsealing mechanism allows the waterway to clear even when no pressure is onthe inlet of the - Sprinkler head

    Sprinkler Components

  • 7/30/2019 Description & Design of Sprinkler Systems

    2/20

    Laboratory Approvals

    UL & c-UL (ULC) : NFPA & UL RequirementsFM : FM Requirements(NFPA : NFPA minimum)LPC :P LPC StandardVDS : VDS StandardNYC & LA : Specific CityapprovalsTypes of Sprinkler HeadsControl Mode Standard Response and Quick Response

    Standard CoverageUprightPendent

    Sidewall

    Extended CoverageUprightPendentSidewall

    Control Mode Special ApplicationLarge Drop SprinklerSuppression

    ESFR upright and Pendent

    ResidentialControl Mode SprinklersControl Mode Sprinklers are separated in the followingCategories:Standard Coverage - Standard ResponseStandard Coverage - Quick ResponseExtended Coverage Standard ResponseExtended Coverage Quick ResponseDry Barrel Standard Response/Quick ResponseStorage Standard/Quick Response

  • 7/30/2019 Description & Design of Sprinkler Systems

    3/20

    Sprinkler Head Identification

    The Model or SIN (Sprinkler Identification) Number is a number assignedto a sprinkler head. The number is stamped on the sprinkler deflector asa means of identifying the sprinkler

    Sprinkler identifying

    SIN Number

  • 7/30/2019 Description & Design of Sprinkler Systems

    4/20

    SIN Number

    Thermal Response RequirementsTEMPERATURE RATINGS FOR GLASS BULB HEADS

    A - Standard Response Elements mm bulb

    F F or F F F F( C) ( C) ( or C) ( C) ( C) ( C)Ordinary Intermediate High Extra High Ultra High Red Yellow Green Blue Mauve Black

    Max Ceil Max Ceiling Max Ceiing Max Ceiing MaxCeiingTemp Temp Temp Temp TempF F F F F

    ( C) ( C) ( C) ( C) ( C)

  • 7/30/2019 Description & Design of Sprinkler Systems

    5/20

    B - Fast Response Elements mm bulb

    F F or F F( C) ( C) ( or C) ( C)

    Ordinary Intermediate HighMax Ceiling Temp Max Ceiling Temp Max Ceiling Temp

    F F F( C) ( C) ( C)Red Yellow Green Blue

    K FactorsK factors are known as the coefficient of discharge. the larger the K factor innumber, the more water it can discharge at a given pressure. There are ( )current thread sizes used for sprinkler heads, , , and threads.

    Do not just match the thread size when replacing a sprinkler head. Identifywhat orientation, K factor, and temperature prior to replacing a sprinkler.

    Orifice Sizes - Effect of Larger K Factors Develop larger water droplets that penetrate the fire plume

    Discharges same water density at lower pressures Lower starting pressures may save the designer a pipe size in theircalculations, which will lower the cost of the system installation.

  • 7/30/2019 Description & Design of Sprinkler Systems

    6/20

    Calculating (K)

    NOMINAL K FACTORS- NFPA and Factory MutualSprinkler K Factors are as follows

    K of% . Thread. % . . % . % . %

    Baseline. % . % . %

    . %

    . %

    . %

    . %

    . %

    . %

    Sprinkler Sensitivity-Thermal Response Requirements

    SPRINKLER SENSITIVITY

    STANDARD RESPONSE : Min. Sec. Room Fire Test- Sec. Plunge Test

    QUICK RESPONSE : Sec. Room Fire Test Sec. Plunge Test

    RESIDENTIAL : Special Fire Test Sec. Plunge Plunge Oven

  • 7/30/2019 Description & Design of Sprinkler Systems

    7/20

    Response Time Index - RTI RTI - measures the speed of response of the heat sensitive element Traditionally Fast Response sprinklers have a thermal element with an RTI of

    (m/s) or less. ESFRs must have a thermal element with an RTI of m/s)or less

    Standard Response Sprinklers have a thermal element with an RTI of(m/s) or more.Components:Strut m/s, Glass Bulb ( mm) - m/s, Fusible Link m/s, GlassBulb ( mm) - m/s, Glass Bulb ( . mm) - m/sHeat Fin - m/s

    MINIMUM SPRINKLER FLOW

    Q = Area x DensityQ = K x PP = (Q/K)K = Q/ PWere:Q = Water FlowK = Coefficient of dischargeP = Pressure

    Sprinkler Spacing

    -Determining Area/SprinklerA. Along branch lines:

    . Determine distance between sprinklers (or to wall/obstruction)

    . Choose largest - twice distance to wall or distance to next sprinkler.This dimension will be defined as S.

    B. Between branch lines:. Determine distance to adjacent branch line (or to wall//obstruction).. Choose largest - twice distance to wall or distance to adjacent line.

    This dimension will be defined as L.

    Area/Sprinkler = S L

  • 7/30/2019 Description & Design of Sprinkler Systems

    8/20

    Extended Coverage or ResidentialMust use one of the listed coverage areasThe actual area protected per sprinkler must fit within the listed designcoverage area

    Example:ft x ft ( . m X m) room

    Use ft X ft ( . X . )m

  • 7/30/2019 Description & Design of Sprinkler Systems

    9/20

    Determining design area

    . Determining Size- standardUse NFPA Chart

    . Determining Size - Extended CoverageMust use Greater of Coverage of five sprinklers or area required byoccupancy

    Example :Light Hazard w/ x Sprinklers sf x sprinklers = sfLH = sfUse sf

    Example :Light Hazard w/ x Sprinklers sf x sprinklers = sfLH = sfUse sf

  • 7/30/2019 Description & Design of Sprinkler Systems

    10/20

    . Determining Size - Quick Response Sprinklers

    When using Quick ResponseYou can reduce the design area based on ceiling height

    (Remember: NFPA limits the minimum size to sf= m)

    Design Calculations

    Calculating Flow (Q) at sprinkler End HeadQ = Area x DensityExample: . density with sf coverage per sprinkler

    . x = gpm minimum at sprinkler end head

    Calculating Pressure (P) at the sprinkler End HeadP = (Q K)Q = Flow at sprinkler end headK = K Factor of Sprinkler

    Example:Q = gpm

  • 7/30/2019 Description & Design of Sprinkler Systems

    11/20

    K = .So ( . ) = . psi Minimum

    Calculating (K) - Orifice SizesOrifice Sizes are Represented by a K FactorThe K Factor is derived by the following formula:

    K = . CDBasically, the larger the K value the larger the orifice.

    Starting Pressure Comparison for Different Orifice SprinklersK Factor Flow Rate Starting Pressur

    . gpm . psi

    . gpm . psi

    . gpm . psi( . gpm) (min psi)

    K Factor Flow Rate Starting Pressur. gpm . psi

    ( . gpm) (min psi)

  • 7/30/2019 Description & Design of Sprinkler Systems

    12/20

    . gpm per sq. ft x sq. ft. = gpm

    Standard Coverage Sprinklers Pendent or Upright

    Minimum operating pressure is psi. Flow rate per sprinkler is determined by

    area x density or minimum pressure multiplied by square root of minimumpressure (which ever is greater)

    Pendent

  • 7/30/2019 Description & Design of Sprinkler Systems

    13/20

    Upright

    Standard Spray Sprinkler Spacing (Area of Coverage)Light Hazard (as defined by NFPA ) : sq. ft.max Ordinary Hazard (as defined by NFPA ) : sq. ft.Max Extra Hazard (as defined by NFPA ) : sq. ft. max(Note: areas given for hydraulically calculated systems)

    Classification of OccupanciesUpright and pendent spray sprinklers shall be permitted in all occupancy

    hazard classifications and building construction types.

    . * Classification of Occupancies.. . Occupancy classifications for this standard shall relate to sprinkler

    design, installation, and water supply requirements only.. . Occupancy classifications shall not be intended to be a general

    classification of occupancy hazards.

    . * Light Hazard Occupancies.Light hazard occupancies shall be defined as occupancies or portions of other

    occupancies where the quantity and/or combustibility of contents is low andfires with relatively low rates of heat release are expected.EXAMPLES: Churches, Clubs, Hospitals, Museums, Offices,Restaurant Seating Areas

  • 7/30/2019 Description & Design of Sprinkler Systems

    14/20

    NFPA limits maximum area of coverage for Light Hazard tosq. ft. per sprinkler

    O O O

    ft( . m)

    O ft( . m) O O

    Density prescribed for Light Hazard is . gpm per sq. ft.Minimum flow rate for sprinklers spaced sq. ft. isDetermined by area x densityQ = . gpm per sq. ft. x sq. ft. = . gpm

    . . * Ordinary Hazard (Group ).Ordinary hazard (Group ) occupancies shall be defined as occupancies orportions of other occupancies where combustibility is low, quantity ofcombustibles is moderate,stockpiles of combustibles do not exceed - , and fires with moderate rates of

    heat release are expected.Examples: Restaurant Service Areas, Bakeries, Automobile Parking andShowrooms, Laundries

    . . * Ordinary Hazard (Group ). Ordinary hazard (Group )occupancies shall be defined as occupancies or portions of other occupancieswhere the quantity and combustibility of contents are moderate to high,stockpiles do not exceed , and fires with moderate to high rates of heatrelease are expected.Examples: Dry Cleaners, Horse Stables, Machine Shops, LibraryStack Rooms, Mercantile, Confectionary Products, Casino area.

  • 7/30/2019 Description & Design of Sprinkler Systems

    15/20

    NFPA limits maximum area of coverage for Ordinary Hazardto sq. ft. per sprinkler

    O O O

    ft( . m)

    O ft( . m) O O

    Density prescribed for Ordinary Hazard is . gpmper sq. ft.

    Minimum flow rate for sprinklers spaced sq. ft. isDetermined by area x densityQ = . gpm per sq. ft. x sq. ft. = . gpm

    Density prescribed for Ordinary Hazard is . gpmper sq. ft.

    Minimum flow rate for sprinklers spaced sq. ft. isDetermined by area x density = QQ = . gpm per sq. ft. x sq. ft. = gpm

    . . * Extra Hazard (Group ).Extra hazard (Group ) occupancies shall be defined as:occupancies or portions of other occupancies where the quantity andcombustibility of contents are very high and dust, lint, or other materials arepresent, introducing the probability of rapidly developing fires with high rates of

    heat release but with little or no combustible or flammable liquids.Examples: Combustible Hydraulic Fluid Use Areas, Metal Extruding, Saw Mills,Upholstering with Plastic Foams, Rubber Reclaiming

  • 7/30/2019 Description & Design of Sprinkler Systems

    16/20

    . . * Extra Hazard (Group ).Extra hazard (Group ) occupancies shall be defined asoccupancies or portions of other occupancies with moderate to substantialamounts of flammable or combustible liquids or occupancies where shieldingof combustibles is extensive.Examples: Flammable Liquids Spraying, Open Oil Quenching,

    Plastics Processing, Solvent Cleaning, Varnish and Paint Dipping

    NFPA limits maximum area of coverage for ExtraHazard to sq. ft. per sprinkler

    O O O

    ft( . m)

    O ft( . m) O O

    Standard Coverage Sprinklers

    Density prescribed for Extra Hazard is . gpm per sq. ft.Minimum flow rate for sprinklers spaced sq. ft. is Determined by area xdensity = QQ = . gpm per sq. ft. x sq. ft. = gpm

    Density prescribed for Extra Hazard is . gpm per sq. ft.Minimum flow rate for sprinklers spaced sq. ft. is Determined by area xdensity = QQ = . gpm per sq. ft. x sq. ft. = gpm

  • 7/30/2019 Description & Design of Sprinkler Systems

    17/20

    Standard Coverage Sprinklers Sidewall

    Standard Spray Sprinkler Spacing (Area of Coverage) Light Hazard (asdefined by NFPA ) : sq. ft. max ( , sq. m)

    Ordinary Hazard (as defined by NFPA ) : sq. ft. max(Note: Must be listed for Ordinary Hazard) ( , sq. m)

  • 7/30/2019 Description & Design of Sprinkler Systems

    18/20

    SIDEWALL SPRINKLER DISTRIBUTION

    Must meet Average Distribution Requirements over the ft( , m ) area between two sprinklers spaced ft. ( , m) apart for standard/ ( mm) orifice sprinklers: . gpm/ft ( . L/s/m ) or . gpm/ft

    ( . L/s/m ) for large orifice sprinklers / ( mm) : And still provide

    . % against wall in which sprinklers are installed, for both / and L/O.

    Density prescribed for Light Hazard is . gpm per sq. ft.

    ^ ^ ^SidewallSprinklers

    ft( . m) Sp/Sp ft( . m) Sp/Sp

    ft ( . m) Sp/WMaximum Distance

    Minimum flow rate for sprinklers spaced sq. ft. isDetermined by area x density = QQ = . gpm per sq. ft. x sq. ft. = . gpm

    Density prescribed for Ordinary Hazard Group is . gpmper sq. ft.

    ^ ^ ^SidewallSprinklers

    ft( . m)Sp/Sp ft( . m)Sp/Sp

    ft ( . m)Sp/W

    Maximum Distance

  • 7/30/2019 Description & Design of Sprinkler Systems

    19/20

    Minimum flow rate for sprinklers spaced sq. ft. isDetermined by area x density = QQ = . gpm per sq. ft. x sq. ft. = gpm

    Density prescribed for Ordinary Hazard Group is . gpmper sq. ft.

    Minimum flow rate for sprinklers spaced sq. ft. isDetermined by area x density = QQ = . gpm per sq. ft. x sq. ft. = gpm

    Extended Coverage Sprinklers ECLH Sprinkler MinimumDesignHave maximum coverage areas of sq. ft. as mandated by NFPA .Spacing is in increments of - intervals, example: x , x , x ,

    x , and x

    ECLH Sprinkler Minimum Design

    Model M ECLH-ELO Pendent VK type

    Spacing Area of Light Hazard Minimum * % Fewer

    Coverage Density water flow Sprinklers

    x ft . gpm/sq ft. . gpm %

    x ft . gpm/sq ft. . gpm %

    x ft . gpm/sq ft. gpm %

    *Based on a sq. ft. coverage area for standard coverage upright andpendent

  • 7/30/2019 Description & Design of Sprinkler Systems

    20/20

    EC(extended coverage) Sidewall vs. Standard EC has larger protection areas EC has flatter distribution Require greater separation from obstructions Need to be designed and installed per listing

    Extended Coverage Sidewall Spacing Per NFPA : Unobstructed, flat Max. area of coverage = ft (Lt. & Ord.) Light Hazard max. between sprinklers Ordinary Hazard max. between sprinklers


Recommended