NEWEA–2018AnnualConference&Exhibit
January22,2018
DesignandOperaAonofAdvancedAeraAonControlSystems
Session10
MaureenD.Neville
NEWEA–2018AnnualConference&Exhibit
WhatisAdvancedAeraAonControl?
Useofprocesssensors,automatedcontrolvalves,andflowmeterstocontrolbloweroutputinanaera7onsystem
2
Blowers
PIT
DO NH3
Aera7onTanks
MFIT
NEWEA–2018AnnualConference&Exhibit
WhyAdvancedAeraAonControl?
§ WhenpermitlimitsdictateaccuratecontrolforopAmalBNRoperaAon
§ WhenenergyandothercostsavingsofadvancedcontrolcanjusAfycostofcontrolequipment
3
Source:StenstromandRosso(2010)www.seas.ucla.edu/stenstro/Aera7on.pdf
NEWEA–2018AnnualConference&Exhibit
OutcomesfromaWell-DesignedAeraAonControlSystem
4
1. Achieveprocesssetpoint(DOtypically)quicklyandmaintainsetpointundervariableloadingcondiAons
2. Maintainsetpointswithasfewactuatorstarts/stopsaspossible
3. OpAmizeenergyusebyminimizingairflowneededforprocessneedsandbyreducingpressureloss
NEWEA–2018AnnualConference&Exhibit
BuXerflyValves(BFVs)
6
§ ThestandardchoiceforMOVcontrolinU.S.
§ NotallBFVsarecreatedequal….
§ AWWATypevs.HighPerformanceType
NEWEA–2018AnnualConference&Exhibit
DiaphragmControlValves
§ IrisDiaphragmControlValve§ Sixsegmentsformcentralaperture,
creaAngcentralflowaxis§ HundredsofinstallaAonsworldwide§ 5installaAonsintheU.S.
§ SquareDiaphragmControlValve(SDCV)§ Slidinggatewithsquare-
shapedaperture§ Fallingflowaxis§ InstallaAonsworldwide
daAngbacktoearly2000s§ 1installaAonintheU.S.
7
Source:EggerTuroPumpsSource:BinderGroup
NEWEA–2018AnnualConference&Exhibit
JetControlValves
8
Source:BinderGroup
§ Engineeredforpreciseairflowcontrol§ Venturi-shapedvalvebody§ Centralcontrolelement(“bullet”)moves
paralleltotheflow§ Annularorificearoundcontrolelement
§ 16installaAonsworldwide
§ NoneinstalledtodateintheU.S.
NEWEA–2018AnnualConference&Exhibit
Motor-OperatedActuatorsforMOVApplicaAons
§ ModulaAngduty=capableofupto1,200start/stopsperhour
§ SomevalvemanufacturersrequireaminimumposiAoningaccuracy(±0.2%),whichonlysomedigitalstyleactuatorscanachieve
9
Source:Limitorque
Source:Rotork
Source:Auma
NEWEA–2018AnnualConference&Exhibit
FactorstoConsiderforValveComparison
§ StableRangeforControl§ ValveSizeSelecAon+FlowMeterInstallaAonàInstalledCost§ PressureLossàOperaAonalCost
10
NEWEA–2018AnnualConference&Exhibit
Source:TheBinderGroup
StableRangeforControl
11
BFVs:50-80%
Diaphragm:20-90%
JetValve:0-95%
%stroke
%flow
NEWEA–2018AnnualConference&Exhibit
ValveSizeSelecAonsforUpperBlackstoneUpgrade(28Valves)
12
Exis7ngPipe
Size
DeZurikHighPerformance
BFVs
EggerIrisDiaphragmValves
BinderSquare
DiaphragmValves
BinderJetControlValves
FirstGrid 12-inch 10-inch 10-inch 12-inch 12-inch
Middle4Grids 8-inch 5-inch 4-inch 6-inch 10-inch
SixthGrid 8-inch 5-inch 5-inch 6-inch 10-inch
SeventhGrid 8-inch 5-inch 5-inch 8-inch 10-inch
Es7matedInstalledCost:$1.3M$1.5M$1.7M$1.9M
NEWEA–2018AnnualConference&Exhibit
FlowMeterInstallaAonRequirements
§ Ideally…..§ 10straightpipediametersupstream§ 5straightpipediametersdownstreambeforecontrolvalve
13
NEWEA–2018AnnualConference&Exhibit
FlowMeterInstallaAonRequirements
§ IrisDiaphragmValve§ Canbeinstalledonly1pipediameter
downstreamofthermalmassflowmeter
14
§ JetControlValve§ Canbeinstalledonly0.5pipediameter
downstreamofthermalmassflowmeter
NEWEA–2018AnnualConference&Exhibit
PressureLossComparisonatVariousValveStrokes
15
0.00 0.20 0.40 0.60 0.80 1.00 1.20
BFV
IrisValve
SDCV
JetValve
psig
Qavg,h50 Qavg,h70 Qmax,hmax Est.AnnualCostSavings:
$34,000$34,000$26,000$16,000
$47,000$34,000$17,000$8,000
$87,000$31,000$9,000$9,000
NEWEA–2018AnnualConference&Exhibit17
Pressure-basedMOVControlwithDOPIDLoops
1. DOPIDàairflowSP2. Flow/valvePIDàvalveposi7onSP3. BlowerpressurePIDàblowermodulatestomeetfloa7ngpressureSP
NEWEA–2018AnnualConference&Exhibit
DisadvantagesofPIDLoops
P=Propor7onalTermPointssystemintherightdirecAontomeetDOsetpoint,assumingairflowislinearlyrelatedtoDOconcentraAonI=IntegralTermForcessystemtobalanceAmeoverversusundersetpointD=Deriva7veTermAppliessomefricAontotheresponse,butinmanycasesnotused
18
Source:BioChemTechnology
COMMONRESULTS:à Oscilla7onaroundsetpoint
à Poorresponsetodiurnalrangeà Seasonalre-tuningneeded
NEWEA–2018AnnualConference&Exhibit
Flow-basedMOVStrategiesthatDon’tUsePIDs
Floa7ngDOControl§ Usesaproprietary,nonlinear
alternaAvetoPIDloopsforvalveandairflowcontrol
§ Operator-adjustable“responsedelays”tominimizeoscillaAons
Predic7veDOControl§ DOandvalvecontrolbasedona
wastewaterprocessalgorithm
§ Calculatesairflowbasedonreal-Ameoxygenuptakerates(OUR)
19
GenerallytheblowersarealsomodulatedtotargetairFLOWsetpoint,althoughPRESSUREcontrolcouldbeused
NEWEA–2018AnnualConference&Exhibit
AmmoniaInstrumentTypes
Type IonSelec7veElectrodeProbes WetChemistryAnalyzers
Range Nominally0–1,000mg/LNTypcalibratedaround1–20mg/LN
Nominally0.02–1,000mg/LNTypcalibratedaround0.05–20mg/LN
Accuracy ±5%ofmVsignal+0.2mg/L ±3%+0.05mg/L
21
Source:HachCompanySource:UpperBlackstone
NEWEA–2018AnnualConference&Exhibit
AmmoniaInstrumentsforABAC:LessonsLearned
22
IonSelec7veElectrodeProbes WetChemistryAnalyzers
LowAmmonia
Openstrugglesinlowammoniaenvironments(<1mg/LNH4-N)
BeXerchoiceforlocaAonswith<1mg/LNH4-N
Loca7on
Mostcommoninfirsthalfoftank(anaerobic/anoxicorheadofaerobic)Mixedsuccessforprimaryeffluent(due
togrease)
Mostcommonatendofaerobiczone,secondaryeffluent,finaleffluent
MixedsuccessinupstreamlocaAons(smalltubingturnsblack)
AccuracyChecks
Requirefrequentaccuracychecksandre-calibraAon
AccuracychecksrecommendedtoidenAfywhenmaintenancerequiredontubingorflow
cells
O&M ReplacementcartridgeheadscanbecostlyifrequiredmulApleAmes/year
ReagentcostcanbereducedbyincreasingAmeinterval(balancedwithprocesscontrol
needs)
NEWEA–2018AnnualConference&Exhibit
ABACExample1:NansemondWRRF(114ML/d5-stgBardenpho) Suffolk,VA
ABACControlScheme
AmmoniaSetPoint
AmmoniaResult
AmmoniaPIDcontrollersoutputAutoDOsetpointsforeach
controlzone
@effluent=3.5mg/L
Typically2.8–4.0mg/L
23
à 12%reducedenergyà 47%reducedsupplemental
carbonà Reducedsupplemental
ammoniaforchloraminaAon
Formorereading:Upretyetal,WEFTEC2015
AerobicAnoxicAnaerobic
NH3ISE
ABACControllers(x5)
M M M
Blowers
PIT
Anoxic Re-Aera7on
NH3WCADO DODO
AutoDOSetPoint(x15)
NEWEA–2018AnnualConference&Exhibit
ABACExample2: SouthPlant(87ML/dA/O)GrandRapids,MI
ControlScheme AmmoniaSetPoint AmmoniaResult
ProprietarycontrolleroutputsAutoDOsetpoint
foreachtrain
@effluent=4-5mg/L
<1mg/Lduetoblowerturndown
limitaAons
24
à 15%reducedenergy
Formorereading:Lunnetal,WEFTEC2014
AerobicAnaerobicBlowers
NH3ISE
PIT
ABACController
M
DONH3WCAMLSS
AutoDOSetPoint(x3)
NEWEA–2018AnnualConference&Exhibit
ABACEx3:RobertW.HiteTreatmentFacility(300ML/dMLE)Denver,CO
25 Formorereading:Grayetal,WEFTEC2012
ControlSchemeAmmoniaSetPoint
AmmoniaResult
ProprietarycontrolleroutputsAutoDOSetPoint
foreachdropleg
@effluent:1.0–1.5mg/L
~1mg/L à 13%reducedenergy
AerobicAnoxicBlowers
NH3ISE
PIT
ABACController
M M MDO DO DO
Disinfec7on
NH3WCAMLSS
AutoDOSetPoint(x36)
NEWEA–2018AnnualConference&Exhibit
ABACExample4:J.D.PhillipsWRF(75ML/dA2/O)ColoradoSprings,CO
26 Formorereading:Lagrangeetal,WEFEnergyandWaterConference2011
ControlSchemeAmmoniaSetPoint
EffluentAmmonia
AmmoniacontrollerdirectlymodifiesvalveposiAon(no
DOcontrolloops)
@secondaerobicgrid:3-4mg/L
~1mg/LduringthedayAme
à 20%reducedenergyà ImproveddetecAonof
nitrificaAonupsetsà Lowershearonbiofloc
AerobicAnoxicAnaerobic Blowers
NH3ISE
PIT
ABACController
M M M
NEWEA–2018AnnualConference&Exhibit
RecommendaAonsforDesignersandOperators
1. Definethedesiredoutcomes(COSTSAVINGS,TIGHTERPROCESSCONTROL)
2. Carefullydefinedesigncriteriaforvalvesandactuators
3. Pilotprocesssensorsonatrialbasis
4. Partnerwithexperiencedblowermanufacturersand/orintegratorswhocandeliver:§ Tightcontrolthatmaintainssetpointswithminimalwearandtearonequipment§ HighlevelofserviceoverAme
28
NEWEA–2018AnnualConference&Exhibit
Contactus!
29