Design Change Notice (DCN-17-0824-3608) 1 Page 1 of 53 DCN Number: DCN-17-0824-3608 Project Name: LGWO 3608 Phase 1 DM/GAC Systems Install DCN Title: LGWO Building 3608 DM/GAC System Phase 1 Electrical Isolations Reference FCR Number: NA Description of Change: This DCN isolates power from the existing air stripper and blower, air scour system, backwash pumps, dewatering screw conveyor, GAC sumps, and heat trace panels. It also isolates control power within the bailey control cabinet for the above-mentioned equipment and all instrumentation associated with the Dual Media Filters and GAC Columns. It is the intention of this DCN to isolate hazardous voltages and allow an outside contractor to perform the work in DCN-17-0825-3608 in safely isolated systems. . Documents Affected by This Design Change (include applicable documents, add additional sheets as required) Document Number Rev. No. Document Title Drawing Yes/No Issue Date E3E021180D089 0 NRWTP Control Panel UCP-12 Layout Details Yes 10/89 E3E021180D126 0 Heat Trace Circuits & Loading Yes 7/19/16 E3E21180D003 D NRWTP One Line Diagram - MCC1 Yes 11/96 E3E21180D004 2 NRWTP One Line Diagram - MCC2 Yes 9/8/94 E3E21180D005 B NRWTP One Line Diagram – MCC3 Yes 9/8/94 E3E21180D019 A NRWTP Building 3608 and Process Area Power Plan Yes 9/89 E3E21180D020 B NRWTP Control and Instrument Conduit Plan Yes 3/17/89 E3E21180D024 B NRWTP Conduit & Wire Schedule - I Yes 7/90 E3E21180D029 3 NRWTP Electrical Schematics - IV Yes 5/94 E3E21180D038 4 Interconnection Diagram - X Yes 9/8/94 E3E21180D041 E NRWTP Electrical Plan and Details Piping Heat Trace Circuits Yes 9/5/94 I3B211802003 0 NRWPT Air Strip pH Adjustment Yes 5/89 I3B211802008 0 GAC Column Feed Sump Level Alarm and Stop to Filter Pumps Yes 1/26/87
Transcript
Page 1: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

1

Page 1 of 53

DCN Number: DCN-17-0824-3608 Project Name: LGWO 3608 Phase 1 DM/GAC Systems Install

DCN Title: LGWO Building 3608 DM/GAC System Phase 1 Electrical Isolations

Reference FCR Number: NA

Description of Change:

This DCN isolates power from the existing air stripper and blower, air scour system, backwash pumps, dewatering screw conveyor, GAC sumps, and heat trace panels. It also isolates control power within the bailey control cabinet for the above-mentioned equipment and all instrumentation associated with the Dual Media Filters and GAC Columns.

It is the intention of this DCN to isolate hazardous voltages and allow an outside contractor to perform the work in DCN-17-0825-3608 in safely isolated systems.

.

Documents Affected by This Design Change (include applicable documents, add additional sheets as required)

Document Number Rev. No. Document Title Drawing Yes/No

Issue Date

E3E021180D089 0 NRWTP Control Panel UCP-12 Layout Details Yes 10/89

E3E021180D126 0 Heat Trace Circuits & Loading Yes 7/19/16

E3E21180D003 D NRWTP One Line Diagram - MCC1 Yes 11/96

E3E21180D004 2 NRWTP One Line Diagram - MCC2 Yes 9/8/94

E3E21180D005 B NRWTP One Line Diagram – MCC3 Yes 9/8/94

E3E21180D019 A NRWTP Building 3608 and Process Area Power Plan Yes 9/89

E3E21180D020 B NRWTP Control and Instrument Conduit Plan Yes 3/17/89

E3E21180D024 B NRWTP Conduit & Wire Schedule - I Yes 7/90

E3E21180D029 3 NRWTP Electrical Schematics - IV Yes 5/94

E3E21180D038 4 Interconnection Diagram - X Yes 9/8/94

E3E21180D041 E NRWTP Electrical Plan and Details Piping Heat Trace Circuits Yes

9/5/94

I3B211802003 0 NRWPT Air Strip pH Adjustment Yes 5/89

I3B211802008 0 GAC Column Feed Sump Level Alarm and Stop to Filter Pumps Yes

1/26/87

Page 2: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

2

I3B211802019 0 GAC Column Feed Sump Level Control Yes 1/26/87

I3B0211802031 A NRWPT FLT F1009 Differential Pressure Yes 5/89

I3B0211802032 A NRWPT FLT F1010 Differential Pressure Yes 5/89

I3B0211802033 A NRWPT Air Stripper Air Flow Yes 5/89

I3B0211802034 A NRWPT Air Stripper Differential Pressure Yes 5/89

I3B211802035 0 GAC Column F-1018 Differential Pressure Yes 1/26/87

I3B211802036 0 GAC Column F1019 Differential Pressure Yes 1/26/87

I3B211802037 0 GAC Column F-1020 Differential Pressure Yes 1/26/87

I3B211802038 0 GAC Column F-1018 Valve Control Yes 1/26/87

I3B211802039 0 GAC Column F-1019 Valve Control Yes 1/26/87

I3B211802040 0 GAC Column F-1020 Valve Control Yes 1/26/87

I3B211802041 A NRWTP DM F-1009 Valve Control Yes 5/89

I3B211802042 A NRWTP DM F-1010 Valve Control Yes 5/89

I3B0211802124 0 NRWTP Clarifier Drives and Pump Status Yes 4/88

I3B0211802125 0 NRWTP Filter Feed, Air Stripper, Feed Pump Status Yes 4/88

I3B0211802129 0 NRWTP Polymer Feed, Scour Blower, Sump Pump Status Yes 4/88

I3B0211802131 0 NRWTP Acid Load Pump, Dewaterer Status Yes 4/88

I3B0211802159 0 NRWTP Dual Media Filter Feed Valve Yes 4/88

I3B0211802160 0 NRWTP Dual Media Filter Effluent Feed Valve Yes 4/88

I3B0211802161 0 NRWTP Dual Media Air Scour Valve Yes 4/88

I3B0211802162 0 NRWTP Dual Media Filter Backwash Valve Yes 4/88

I3B0211802173 0 NRWTP Dual Media Filter Spent Backwash Valve Yes 4/88

I3B0211802174 0 NRWTP Dual Media Filter Drain Down Valve Yes 4/88

I3B0211802175 0 NRWTP Dual Media Filter Feed Valve Yes 4/88

I3B0211802176 0 NRWTP Dual Media Filter Effluent Feed Valve Yes 4/88

I3B0211802177 0 NRWTP Dual Media Air Scour Valve Yes 4/88

Page 3: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of
Page 4: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

4

TABLE OF CONTENTS

Scope of Work……………..……………………….…………………….…………………..………..Page 5

1) Isolation of Dual Media Filters...……………………………………………………….…….....Page 6

a) Dual Media Filter DM F-1009…………………………………………….…………………….Page 6

b) Dual Media Filter DM F-1010……………………………………………….………………….Page 15

2) Isolation of GAC Columns…......…………………………………………………………..…...Page 24

a) GAC Column F-1018………………………………………………………….…………...…...Page 24

b) GAC Column F-1019, F1020 …………………………………………………………..……..Page 27

3) Isolation of Air Stripper and Recirculation Pump…...………………………………..…....Page 32

4) Isolation of Air Scour Blower ………………………………….……..………………....….…Page 39

5) Isolation of Dewatering Screw Conveyor ……………………….…………………….…….Page 43

6) Isolation of Backwash Pumps ……………………………………………….………....….….Page 46

7) Isolation of GAC Feed Sumps...…………………………………………………..…...………Page 49

8) Isolation Heat Trace Panels..………………………………………………………....………..Page 53

Page 5: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

5

SCOPE OF WORK:

Provide air gap as described below.

All control circuits shall have continuity tested to verify terminal block designations are as identified within sketches.

Provide labels for all air gap/isolation points indicating power/control and equipment served. This will aid the outside contractor who will be completeting the demolition and installation work assoiciated with DCN-17-0824-3608.

Special Notes:

1) PB No. 3 denoted on the sketches in this DCN is physically labelled Pull Box No. 1 in the field.

2) The notes under the main heading for each section apply to all sketches within section.

Page 6: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

6

1) Isolation of Dual Media Filters:

a) Dual Media Filter DM F-1009

1. Air gap UCP No. 9 by removing power feed IPP circuit 7 back to Panel IPP. (The attached sketch

indicates circuit 17; however, the field conditions indicate circuit 7). 2. Air gap instrument air supply (A/S) valve 3608-SVC-1 and permanently cap. 3. Remove conduit and conductors between UCP No. 9 and Terminal Cabinet 1. 4. Air gap PB No. 3 from IPP circuit 17, back to nearest junction box. 5. Air gap conduit and conductors at UCP No. 9 back to nearest junction box between UCP No. 9 and PB

No. 3.

Page 7: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

7

Page 8: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

8

Page 9: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

9

Page 10: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

10

Page 11: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

11

Page 12: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

12

Page 13: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

13

Page 14: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

14

Page 15: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

15

b) Dual Media Filter DM F-1010

1. Verify air gap for UCP No. 9. 2. Verify air gap for instrument air supply (A/S) valve 3608-SVC-1. 3. Remove conduit and conductors between UCP No. 9 and Terminal Cabinet 1. 4. Verify air gap for PB No. 3. 5. Air gap conduit and conductors at UCP No. 9 back to nearest junction box between UCP No. 9 and PB

No. 3.

Page 16: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

16

Page 17: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

17

Page 18: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

18

Page 19: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

19

Page 20: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

20

Page 21: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

21

Page 22: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

22

Page 23: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

23

Page 24: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

24

2) Isolation of GAC Columns: a) GAC Column F-1018

1. Air gap UCP No. 12 by removing power IPP circuit 11 back to Panel IPP. 2. Air gap instrument air supply (A/S) valve 3608-SVC-2 and permanently cap. 3. Remove conduit and conductors from Terminal Cabinet 1 to first junction box between Terminal Cabinet 1

and UCP No. 12.

Page 25: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

25

Page 26: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

26

Page 27: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

27

b) GAC Column F-1019, F-1020

1. Verify air gap of UCP No. 12. 2. Verify air gap of instrument air supply (A/S) valve 3608-SVC-2. 3. Remove conduit and conductors from Terminal Cabinet 1 to first junction box between Terminal Cabinet 1

and UCP No. 12.

Page 28: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

28

Page 29: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

29

Page 30: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

30

Page 31: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

31

Page 32: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

32

3) Isolation of Air Stripper and Recirculation Pump: a) Air Stripper Fan AJ-1014 and Recirculation Pump NJ-1014

1. Air gap power and control conductors by disconnecting from the MCC and coiling back to the cable tray.

Bundle and label both power conductors and control conductors. 2. Remove conduit and conductors from Terminal Cabinet 1 to first junction box. 3. Verify air gap of UCP No. 12. 4. Verify air gap of PB No 3.

Page 33: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

33

Page 34: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

34

Page 35: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

35

Page 36: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

36

Page 37: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

37

Page 38: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

38

Page 39: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

39

4) Isolation of Air Scour Blower: a) Air Scour Blower AJ-1029

1. Air gap power and control conductors by disconnecting from the MCC and coiling back to the cable tray.

Bundle and label both power conductors and control conductors. 2. Disconnect conductors from Terminal Cabinet 1 and remove to first junction box. 3. Verify air gap of UCP No. 9.

Page 40: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

40

Page 41: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

41

Page 42: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

42

Page 43: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

43

5) Isolation of Dewatering Screw Conveyor: a) Dewatering Screw Conveyor NL-1036

1. Air gap power and control conductors by disconnecting from the MCC and coiling back to the cable tray.

Bundle and label both power conductors and control conductors. 2. Disconnect conductors from Terminal Cabinet 1 and remove back to first junction box.

Page 44: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

44

Page 45: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

45

Page 46: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

46

6) Isolation of Backwash Pumps: a) Backwash Pumps NJ-1021-A and NJ-1021-B

1. Air gap UCP No. 11 by removing power feed IPP circuit 9 back to Panel IPP. 2. Air gap power and control conductors by disconnecting from the MCC and coiling back to the cable tray.

Bundle and label both power conductors and control conductors. 3. Verify air gap for UCP No. 9. 4. Remove conduit and conductors between UCP No. 9 and Terminal Cabinet 1. 5. Remove conduit and conductors at UCP No. 11 back to nearest junction box between UCP No. 11 and

Terminal Cabinet 1.

Page 47: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

47

Page 48: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

48

Page 49: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

49

7) Isolation of GAC Feed Pumps a) Demo GAC Feed Sumps NJ-1017-A and NJ-1017-B

1. Air gap power and control conductors by disconnecting from the MCC and coiling back to the cable tray.

Bundle and label both power conductors and control conductors. 2. Verify air gap for UCP No. 12. 3. Disconnect and remove conductors from Terminal Cabinet 1 to first junction box. 4. Air gap instrument air supply valve for 3608-LVC-675 and permanently cap.

Page 50: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

50

Page 51: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

51

Page 52: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

52

Page 53: Design Change Notice (DCN-17-0824-3608) - UCOR LLC - …info.ettp.energy.gov/rfp/mr-18-051079/attachments/DCN-17-0824-3608… · Design Change Notice (DCN-17-0824-3608) 1 Page 1 of

Design Change Notice (DCN-17-0824-3608)

53

8) Isolation of Heat Trace Panels

a) Air gap Heat Trace Panel HTCP-1 (HT1) power conductors by disconnecting from the MCC3 Section 8K and

coiling back to the cable tray. Bundle and label power conductors.