Kirk Mescher, PE, LEED ® AP Design of Commercial Ground Source Heat Pumps 1 - and - Lisa Meline, PE, LEED ® AP
Transcript
Page 1: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Kirk Mescher, PE, LEED® AP

Design of Commercial Ground Source Heat Pumps

1

- and - Lisa Meline, PE, LEED® AP

Page 2: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Kirk Mescher, PE, LEED® AP

Steps to Improving Ground Source Design

Page 3: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Learning Objectives

• What documents are required to effectively communicate a ground source system design?

• Energy simulations • Ground Loop 101 • What makes water source heat pump installations

unique? • What makes a good ground source installation?

3

Page 4: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Seminar Scope Limitation • Today’s Seminar will concentrate on:

– Design considerations for vertical ground loop heat exchanger systems

– The design will be applicable to horizontal bore systems, surface water systems and open loop systems

– We will not discuss, other than to introduce, the concept of a standing column system

4 4

Page 5: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Some Background

• Vocabulary • Codes and Standards • References

5 5

Page 6: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

ASHRAE HVAC Applications Handbook Chapter 34 Geothermal resources classification by temperature: High Temperature t > 150 C (300 F) Intermediate Temperature 90 C (195 F) < t < 150C (300 F) Low Temperature t < 90 C (195 F) • Direct Use • Ground-Coupling

6

Page 7: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Vocabulary

• Ground Source, Geo-Exchange, Ground Coupled – A heating and cooling system that uses the ground as a moderator. The ground acts as a heat sink for heating and cooling energy.

• Geothermal – A heating system that typically uses “hot rocks” or a high temperature aquifer for direct heating or energy production.

• Central Plant – A heating and/or cooling system where multiple facilities are tied together such that the single plant can produce the necessary energy or resource.

7

Page 8: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Vocabulary

• Well – A water-producing bore typically with a submersible pump.

• Bore – An approximately 15 cm (6 in.) hole drilled into the geological formation.

• Borehole, U-loop Heat Exchanger, etc. – A typically vertical u-loop pipe (or ground probe) placed into a bore and grouted into position.

• Bore Field – Accumulation bores designed to be connected with header piping to support a ground source heating and cooling system.

8

Page 9: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Vocabulary

• GCHP – Ground Coupled Heat Pump • EER – Energy Efficiency Ratio • SEER – Seasonal Energy Efficiency Ratio

– Does NOT apply to GCHP

• COP – Coefficient of Performance

9

When making comparisons, be sure you are comparing equal terms. These terms can be applied to equipment or SYSTEMS. It is best to compare SYSTEM performance.

WARNING>>>>>>>WARNING>>>>>>WARNING>>>>>>WARNING>>>>>>

9

Page 10: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Codes and Standards (US) • International Mechanical Code

– Chapter 12

• IGSHPA - Closed-Loop/Geothermal Heat Pump Systems - Design and Installation Standards

• ASHRAE Standard 90.1 – Variable flow requirements – Isolation valves

• CSA C448 - Design and Installation of Earth Energy Systems

10 10

Page 11: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Getting Started:

• References – ASHRAE CHAPTER 34 – HVAC

Applications Volume – ASHRAE TC 6.8 Geothermal Heat Pump

and Energy Recovery Applications – Various Journal articles

• Attend seminars like this

11

Page 12: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

12

Recommended ASHRAE Design Guide for Commercial and Institutional Buildings

Page 13: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Ground Source

• What is it? – Efficient system connected with the

ground? • Heat recovery system?

– Recover energy from season to season?

13 13

Page 14: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Are Ground Source Systems a Renewable Energy Source?

14

Page 15: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

The earth absorbs nearly half of the sun’s energy.

Ground Source Energy

15

Page 16: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Energy Efficient Heating: Coefficient of Performance

or building

16

Page 17: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

What is a Geo-Exchange Heating and Cooling System?

17

KEY: Ground Coupled heat exchanger Piping Network Pumps Water source heat pumps Controls

VFD

PD

T

17

Page 18: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

18

How Geo-Exchange Works

Thermal Conductivity

Bore field acts as a battery, storing heating energy in the summer and releasing it in the winter

Geothermal Bore Field

18

Page 19: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

19

Real-World Loading

Heat in bore field is likely to increase

Cooling Energy >> Heating Energy

Geothermal Bore Field

19

Page 20: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

20

Hybrid Geo-Exchange Systems

Cooling Dominated

FLUID COOLER

Excess Heat

20

Page 21: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Ever see this?

Is this sufficient to define the System requirements?

21

Page 22: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

System Definition Requirements • Design parameters

– Flow – Pressure loss – Water quality and

volume – Antifreeze solution and

volume, if required

• Header pipe definition – Material – Diameter – Pressure class rating – Circuit isolation

requirements – Flush/purge provisions

22

Page 23: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

System Definition Requirements • Vertical bore definition

– Drilling technique if available – Casing requirements, if any – Bore depth and approximate bore

diameter – Grout Definition

• Thermal Conductivity • Placement method

• Equipment specification – Airflow and pressure drop – Heating and cooling capacity – EER and COP – Water flow and pressure drop – Electrical characteristics – Air filtration specification

23

Page 24: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

System Definition Requirements • Inside Building

– Piping specification – Pumping system – Control Specification – System diagram

• Air separation • Compression • Make-up

• Commissioning – Piping installation

inspections and testing

– Purge volume and flow

– Purge procedure – System start-up

procedure – Start-up

documentation

24

Page 25: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Key to Good System Design

A. Is ground source a proper selection?

B. Interior Design C. Physical Constraints of the Ground D. System Integration

25

Page 26: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Developing 12-Steps

A. Proper selection 1. Calculate peak and OFF-peak loads 2. Estimate energy to and from the bore field

B. Interior Design 3. Select operating temperatures 4. Correct heat pump operation for actual conditions 5. Select HPs for peak load (heating or cooling) and

minimize duct runs 6. Arrange HPs into building circuits

26

Page 27: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Developing 12-Steps C. Physical Constraints of the Ground

7. Conduct investigation for thermal properties and drilling conditions

8. Determine ground heat exchanger arrangement 9. Calculate optimum ground heat exchanger

dimensions

D. System Integration 10. Iterate to determine optimum operating

temperatures, flows, materials 11. Layout Interior piping for minimum head loss 12. Select pumps and control methodology

Page 28: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Is Ground Source A Proper Selection?

A 28

Page 29: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Ground Source “The Efficiency Silver Bullet”

• The most efficient HVAC system there is!!!

• It works everywhere!!! • XXX m/kW (xx ft/ton) is adequate

everywhere!!!

29

Page 30: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Applicability • Depends on:

– Building energy balance – Undisturbed ground temps – Site characteristics

• Is there a hybrid design opportunity? – High heating and low cooling demand – High cooling with low heating demand

30

A

Page 31: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Preliminary Ground Source Sizing

• Building energy estimate • Idea of how the building will operate • Drilling requirements • Some reference of ground thermal

conductivity and thermal diffusivity

31

A

31

Page 32: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Preliminary Estimates

• Don’t use ‘Rules of Dumb’ • Perform the Calculations!

– Bin data or 8760 hour simulation to understand the energy coming into the facility and going out

32

A

Page 33: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Energy Estimates

Building Name Winnebago School Location Rockford IL 10 MonthBuilding Area 40,000 SQ. FT. Occupancy 400 Persons

COOLING 91 TONS Minimum Ventilation 0.05 cfm/sq. ft.HEAT 800.9 MBTUH min vent 2000 cfm

Occupancy Ventilation 12 CFM/personSummer design temp 75 F Setback 78 F occupant vent 4800 cfm

Wetbulb 63 F Total Ventilation 6800 cfmRel Humidity 51.6 % RH

Specific Humidity 66.8 Grains Lighting 1 W/ft 2̂Summer Design enthalpy 28.4 BTU/# Power 0.3 w/ft 2̂

Days /Week 5WinterDesign Temp 70 F Setback 68 F Occupied 55 Hrs/week

Wet Bulb 54 F Building UA 4739 Btuh/FRel Humidity 33.6 % RH

Specific Humidity 36.5 Grains FUEL COST 5.42 $/mcfWinter Design enthalpy 22.5 BTU/# 154.1140142 Fuel Efficiency 0.8

Ele rate 0.1 $/kwhEconomizer 0 (1-yes, 0-no)

Humidification 0 (1-yes, 0-no) CALCULATION OF BUILDING UAERU 0 (1-yes, 0-no) # of Floors 1

ERU Efficiency 0.7 (0-1.00) Roof Area 40000 2667

33

A

Page 34: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Calculate Peak and Off-Peak Loads

1

34

Page 35: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Building Name Winnebago School Location Rockford IL 10 MonthBuilding Area 40000 SQ. FT.

COOLING 91 TONSHEAT 800.9 MBTUH

COOLING LOAD 995.2 MBTUH HEATING LOAD -717.0 MBTUHCOOLING ENERGY 349528 KBTU HEATING ENERGY -1073139 KBTU

FLCH 319 FLHH 1340 539-12 930 9-12 -8011-4 1095 1-4 -7365-8 371 5-8 -6688-8 221 8-8 -658

tons 91 438 sq ft/ton BTUH/FT^2 20.02ton hours 29127 ton hours 71543

Calculation of Peak and Off-Peak Loads

35

1

Page 36: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Annual Energy Usage Building Name Belvidere Washington Scho Location Chicago DataBuilding Area 96370 SQ. FT.

COOLING 138 TONSHEAT 1531.7 MBTUH

Base Electrical Usage

Lights and Other Electrical Usage 427208.21 KwhAnnual Energy $ 27768.534

$0.29 $/ft^2

Geothermal One Pipe System Output Kbtu/sq. ft./yr24.53

HVAC Energy Use 265435.6 KWH $17,253.32

$0.18 $/ft^2Other Energy Use $0.29 $/ft^2 System EER 13.89

$0.47 $/ft^2 System COP 3.84

SYSTEM HEATING AND COOLING EFFICIENCY AFFECTS PERFORMANCE, DESIGN AND SIZING

36

1

Page 37: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Estimate Energy To and From the Bore Field

2

37

Page 38: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Remember from the Introduction…

Thermal Conductivity

Bore field acts as a battery, storing heating energy in the summer and releasing it in the winter

Ground Source Bore Field

2

38

Page 39: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Building uses more energy for cooling than for heating

Seasonal Energy Usage

Seasonally Stored Energy for Cooling

Seasonally Stored Energy for Heating

2

39

Page 40: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

10-Month School In Colder Climate

2

40

Page 41: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Loop Sizing Inputs

Energy Pulses Building Name Winnebago School Location Rockford IL 10 MonthBuilding Area 40000 SQ. FT.

COOLING 91 TONSHEAT 800.9 MBTUH

COOLING LOAD 995.2 MBTUH HEATING LOAD -717.0 MBTUHCOOLING ENERGY 349528 KBTU HEATING ENERGY -1073139 KBTU

FLCH 319 FLHH 1340 539-12 930 9-12 -8011-4 1095 1-4 -7365-8 371 5-8 -6688-8 221 8-8 -658

tons 91 438 sq ft/ton BTUH/FT^2 20.02ton hours 29127 ton hours 71543

41

2

Page 42: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Interior Design

B 42

Page 43: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Heat Pumps

43

Page 44: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Effect of Temperature Control on Performance

44

VFD

PD

T T

System EER

0

5

10

15

20

25

30

30 40 50 60 70 80 90 100 110 120 TEMP (F)

EER

2

2.5

3

3.5

4

4.5

5

5.5

6

6.5

7

CO

P

UNIT EER Variable Flow EER UNIT COP Variable Flow COP

Page 45: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Water Source Heat Pumps (Self-Contained Approach)

• Many consider: Traditional Equipment • Horizontal Units • Vertical Units • Water to Water • Console Units

45

Page 46: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Water Source HP’s, Traditionally

– “100’s of noisy boxes” above the ceiling – “Require” cooling towers or boilers “to work right” – 2-pipe controlled water distribution

• Water flow control • Motorized isolation valves • Variable speed drives

– Have maintenance issues • Low flow at the end of the distribution • Low temp difference

46

Page 47: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

New Paradigm • Many different heat pump systems

• When properly designed and implemented, ground loops can provide all system heat rejection and heat addition

• Water distribution – Traditional 2-pipe variable capacity – Individual circulations – Circulators with central pumps – One pipe

• Lower maintenance costs – Simpler distribution – Managing flow to the units

47

Page 48: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Heat Exchanger Configurations

Courtesy Water Furnace

Open Loop Surface Water

Horizontal Bore Vertical Bore

48

Page 49: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Improving System Design: Simplicity

49

Everything should be made as simple as possible, but not simpler. ~Albert Einstein

Page 50: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Why Simple?

• Complexity adds $; does it add value?

– How many control points do we need? – Does variable speed pumping add enough

value? – Do we require digital control?

• Why ask the question – It’s $ – Maintenance – Operation – Installation

Page 51: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Select Preliminary Loop Operating Temperatures

and Flow Rate

3

51

Page 52: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Selecting Operating Temperatures • A good starting point

– Undisturbed ground temp • Cooling 10-20ºC (20-35ºF) Above • Heating 5-10ºC (10-15ºF) Below

• Generally, max cooling inlet temps should be below 32.2ºC (90ºF)

• Generally, min heating above 0ºC (Use 7-8ºC to start)

• Final selection based on energy balance • It’s ALL about SYSTEM EER and COP

3

52

Page 53: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Correct Heat Pump Operation for

Actual Conditions

4

53

Page 54: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

HP Performance Ratings

• AHRI/ISO/ASHRAE/ANSI 13256-1 - Water-source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps

• EN 14825 - Air Conditioners, Liquid chilling packages and heat pumps, with electrically driven compressors, for space heating and cooling – Testing and rating at part-load conditions and calculations of seasonal performance

54

Page 55: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

55

Why Adjust Unit Capacity?

• Under ISO 13256-1 – What is the system fan static pressure for

rating? – What is the pumping energy based upon?

• What are the entering water and air conditions?

4

55

Page 56: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

56

Adjusting Unit Capacity • ISO 13256-1

– 0 kPa static pressure – 25ºC (77ºF EWTc) / 0ºC (32ºF) EWTh – 19ºC (66.2ºF) EWB Cooling – 20ºC (68ºF) EDB Heating – Pumping power is included

Some manufacturer’s programs properly adjust the capacity based on your operating conditions, some do not. The point is, capacity adjustment is required to properly select the required equipment.

4

56

Page 57: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

57

1 3 2

Heat Pump Ratings

Page 58: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Select HPs for Peak Load (Heating or Cooling) and

Minimize Duct Runs

5

58

Page 59: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Schedule HP Equipment

59

5

59

HEAT PUMP UNIT SCHEDULCOOLING HEATING WATER H.P. PUMP

S.A. ESP CAPACITY (BTH) EWT EER CAP. TOTAL EWT COP FLOW WPD HEAD (CFM) (IN W.C.) TOTAL SENSIBLE (° F) (BTH) (°F) (GPM) (FT) (FT)

1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 900 0.55 25.7 16.7 90 14.1 22.7 40 3.6 7.4 14.7 22.7 900 0.55 25.7 16.7 90 14.1 22.7 40 3.6 7.4 14.7 22.7 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,830 0.80 62.6 46.1 90 16.1 54.1 40 3.8 12.5 7.4 15.4 1,830 0.80 62.6 46.1 90 16.1 54.1 40 3.8 12.5 7.4 15.4 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 3,440 0.50 113.6 79.1 90 13.3 109.3 40 3.8 25.0 15.0 23.0 3,440 0.50 113.6 79.1 90 13.3 109.3 40 3.8 25.0 15.0 23.0

Page 60: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Arrange HPs into Building Circuits

6

60

Page 61: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Physical Constraints of the Ground

C 61

Page 62: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Conduct Investigation for Thermal Properties and

Drilling Conditions

7

62

Page 63: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

• Thermal Conductivity • Deep Earth Temperature • Thermal Diffusivity

Thermal Properties for Design

Page 64: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Thermal Conductivity Testing

y = 5.1007Ln(x) + 64.27R2 = 0.9806

0

10

20

30

40

50

60

70

80

90

0 5 10 15 20 25 30 35 40 45 50

GPMtemp intemp outaverage TempLog. (average Temp)

Time Period Slope Average He (Btu/hr-ft) at Input (W/ft) Thermal Conductivity (Btu/hr-ft-°F)

10—44 4.3 72.5 21.25 1.34

The purpose of the test is to determine the physical properties of the ground surrounding the bore hole. This will be explained in further detail in Module 2.

7

64

Page 65: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Determine Ground Heat Exchanger (GLHX)

Arrangement

8

65

Page 66: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Heat Exchanger Configurations

Courtesy Water Furnace

Open Loop Surface Water

Horizontal Bore Vertical Bore

66

Page 67: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Typical Bore Detail 9

67

100m

1.2m

(1) U PE100 PN 16

1.9

Page 68: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Calculate GLHX Requirements

9

68

Page 69: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Output from Loop Sizing Routine

9

69

Page 70: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Headers

Page 71: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Basic Header Types • None

– Loop connected directly to equipment

• Close Coupled – U-loops connected to end of the pipe

• Vaults – Reverse return circuits connected to headers in valve vaults

• Reverse Return – Header piping connected to circuits with reverse return piping

and underground valves

• Direct Return – Header piping connected to circuits with direct return piping and

underground valves

71

Page 72: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Close Coupled

72

Page 73: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Vaults

Page 74: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Inexperienced design keys

74

Trenching shown on both sides of the string of bores

Balance is affected by lack of reverse return

Cross trenching, direct supply and return Fix the balance issue by adding valves

Page 75: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Reverse Return

• Circuits are generally pressure balanced throughout the system

• First supplied is last returned

• Each bore sees the same length of piping material

Reverse Return

75

Page 76: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Direct Return

• The U-loops are in control of the pressure loss throughout the system

• The valve authority of the U-loop control flow

Direct Return

76

Page 77: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Vault

Header Configurations Reverse Return

Direct Return

77

Page 78: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Header Configurations

Circuit pressure loss >80% of overall PD = balanced flow

78

Page 79: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Bore Field Don’ts PVC or Copper

Bentonite Grout

•---- use vaults •---- require cross-trenching •---- use pure Bentonite grout •---- put bores any closer than 20 ft (6.1m) OC. •---- put flow controls on loops

79

Page 80: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Ground Loop Supplement

HDPE SDR 11 UNI-LOOP

Thermally enhanced grout

Total Field Pressure Loss 20 ft H20 (60 kPa)

20 ft (6.1m) MIN Connecting Piping DR 15.5 HDPE

Bore Field and Building Purge Assembly

Use good design practices for header design Close coupled Reverse return Direct return with knowledge of U-loop flow control

80

Page 81: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

System Integration

D 81

Page 82: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Iterate to Optimize GLHX 1- Balancing length with operating Temperatures 2- Changing to Different Equipment 3- Balancing with Different Equipment

10

82

Page 83: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Layout Interior Piping for Minimum Head Loss

11

83

Page 84: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

System Layouts

• Direct Flow – With 3-way control – With 3-way control and VFD – With secondary geo pump – Without loop temp control

• Reverse Return – With 3-way valve control – With secondary geo pump – Without loop temp control

84

Page 85: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Direct Flow with 3-Way Control

Attributes Control of water temp Summer and Winter 30/7 Demand Fluid Control Flow Balance managed by

Regulator Valves Challenges System changes with each device added or subtracted from duty Pipe Length/pressure loss Control valve pressure loss/authority Heat/cool energy exchange at

bore field Central pump must be sized

for connected load Last Heat Pump can be short of water flow

T T

85

Page 86: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

86

Please do your own pump

pressure drop calculations!!!

Page 87: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Select Pumps and Control Method,

Determine System Efficiency

12

87

But more about this in Module 3…

Page 88: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Direct Flow without Loop Temp Control

Attributes Heat Pump flow managed by regulator valves Demand Fluid Control Flow Regulator volume control

Challenges System changes manages with flow regulators Pipe Length/ pressure loss Heat/cool energy exchange at bore field Last heat pump can be short of water flow Central pump must be sized for connected load

VFD

PD

88

Page 89: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Reverse Return without Loop Temp Control

Attributes Demand Fluid Control Flow regulator volume control Equal pipe length to each heat pump

Challenges System changes managed with flow regulator valves Pipe Length/ pressure loss Heat/cool energy exchange at bore field Central Pump must be sized for connected load

VFD

PD

89

Page 90: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

One-Pipe Loop Distributed Primary Secondary Loop

Attributes Demand Fluid Control Secondary pump flow control Little loop temp control Unit by unit diversity No flow regulators Low system pump head Primary pump can be sized for BLOCK load conditions No drive/pump/static control head inefficiency

Challenges Temperature control Pipe Length/pressure loss Last heat pump will have warmer/cooler water

sequencer

T

90

Page 91: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

“Heat Recovery, Anyone????”

sequencer

T

Attribute

One-pipe loop allows heat pumps to recover energy from the other units in the system.

Cooling units add heat to the loop, heating units extract heat…

It doesn’t take VRF to have heat recovery.

91

Page 92: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Piping Diagrams

Heat pump

M

FCV

GEO HEAT PUMPTraditional 2-pipe arrangement

1-pipe arrangement

92

Page 93: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Parallel Pump Curve Parallel pump operating point 2.3 kW (8.1 Wm/kWt)

Individual pump operating point 1.3 kW (4.5 Wm/kWt)

Single pump and parallel pump operation allow for greatly reduced pump horsepower usage during normal operation. No speed control is required.

757 lpm @ 12.2m Parallel pumps 625 lpm @ 8.2m Single pump

93

Page 94: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Case Study:

MEM Independence

94

Page 95: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Case Study: MEM Independence

• Missouri Employers Mutual • Independence, Missouri • 557 m2 office facility renovated from

rooftop A/C to Ground Source • First 2 years of results – Less than

impressive $600 per year in additional operating cost.

95

Page 96: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

96

Page 97: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Original Pumping Strategy • Continuous pumping through all heat

pumps

97

Page 98: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Building Energy Consumption

y = -8.214ln(x) + 66.64

0

5

10

15

20

25

30

35

40

0 100 200 300 400 500 600 700 800 900 1000

BEFORE NOVEMBER 2011

98

Page 99: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

As Designed

IHCL-1

6400/12100 BTU/H2.5 GPM

39.9°F94.7°F

45°F85°F

IHCL-2

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-3

50000/93900 BTU/H16 GPM

38.8°F96.8°F

45°F85°F

IHCL-4

17100/32200 BTU/H5 GPM

38.2°F97.9°F

45°F85°F

IHCL-5

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-6

34300/64400 BTU/H12 GPM

39.3°F95.8°F

45°F85°F

IHCL-7

30000/56300 BTU/H9 GPM

38.4°F97.6°F

45°F85°F

P-1

62.5 GPM71.1/70.5 FT

P-2

62.5 GPM71.1/70.5 FT

AS-1

AV-1

HSS-1

189300/355400 BTU/H62.5 GPM

39°F96.4°F

45°F85°F

ET-1

7.3 GAL

V-1

BV-IHCL -1

STR-1V-2

V-3

BV-IHCL -2

STR-2V-4

V-5

BV-IHCL -3

STR-3V-6

V-7

BV-IHCL-4

STR-4V-8

V-9

BV-IHCL-5

STR-5V-10

V-11

BV-IHCL -6

STR-6V-12

V-13

BV-IHCL-7

ST R-7V-14

2.5"

2.5"2.5"

2.5"

1.25"1.25"

2.5"

2"1"1"

1"

2"1.25"

1.25"1.25"

1.25"

2"

2.5"

99

Page 100: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Solutions?

• What will make the system operate more efficiently? – Distributed pumping? – ASHRAE 90.1 variable flow solution? – One-pipe solution? – Something different?

IHCL-1

6400/12100 BTU/H2.5 GPM

39.9°F94.7°F

45°F85°F

IHCL-2

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-3

50000/93900 BTU/H16 GPM

38.8°F96.8°F

45°F85°F

IHCL-4

17100/32200 BTU/H5 GPM

38.2°F97.9°F

45°F85°F

IHCL-5

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-6

34300/64400 BTU/H12 GPM

39.3°F95.8°F

45°F85°F

IHCL-7

30000/56300 BTU/H9 GPM

38.4°F97.6°F

45°F85°F

P-1

62.5 GPM71.1/70.5 FT

P-2

62.5 GPM71.1/70.5 FT

AS-1

AV-1

HSS-1

189300/355400 BTU/H62.5 GPM

39°F96.4°F

45°F85°F

ET-1

7.3 GAL

V-1

BV-IHCL -1

STR-1V-2

V-3

BV-IHCL -2

STR-2V-4

V-5

BV-IHCL -3

STR-3V-6

V-7

BV-IHCL-4

STR-4V-8

V-9

BV-IHCL-5

STR-5V-10

V-11

BV-IHCL -6

STR-6V-12

V-13

BV-IHCL-7

ST R-7V-14

2.5"

2.5"2.5"

2.5"

1.25"1.25"

2.5"

2"1"1"

1"

2"1.25"

1.25"1.25"

1.25"

2"

2.5"

100

Page 101: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Solution Considerations: Distributed Pumping

IHCL-8

6400/12100 BTU/H2.5 GPM

39.9°F94.7°F

45°F85°F

IHCL-9

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-10

50000/93900 BTU/H16 GPM

38.8°F96.8°F

45°F85°F

IHCL-11

17100/32200 BTU/H5 GPM

38.2°F97.9°F

45°F85°F

IHCL-12

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-13

34300/64400 BTU/H12 GPM

39.3°F95.8°F

45°F85°F

IHCL-14

30000/56300 BTU/H9 GPM

38.4°F97.6°F

45°F85°F

AS-2

AV-2

HSS-2

189300/355400 BTU/H62.5 GPM

39°F96.4°F

45°F85°F

ET-2

8 GAL

V-15

STR-8V-16

V-17

STR-9V-18

V-19

ST R-10V-20

V-21

STR-11

STR-12V-22

V-23

STR-13V-24

V-25

STR-14V-26

2.5 GPM13.3 FTP-3

9 GPM12.4 FT

P-4

16 GPM20.9 FTP-5

5 GPM10.5 FTP-6

9 GPM12.4 FTP-7

12 GPM16.2 FT

P-8

9 GPM11.7 FTP-9

2.5 GPM33.9/33.3 FT

P-10

9 GPM33.9/33.3 FTP-11

16 GPM33.9/33.3 FT

P-12

5 GPM33.9/33.3 FT

P-13

9 GPM33.9/33.3 FT

P-14

12 GPM33.9/33.3 FTP-15

9 GPM33.9/33.3 FT

P-16

V-27

V-28

2.5"

2.5"

2.5"

2"

2"

1.25"

2"

2.5"

101

Page 102: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Solution Considerations: ASHRAE 90.1

IHCL-1

6400/12100 BTU/H2.5 GPM

39.9°F94.7°F

45°F85°F

IHCL-2

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-3

50000/93900 BTU/H16 GPM

38.8°F96.8°F

45°F85°F

IHCL-4

17100/32200 BTU/H5 GPM

38.2°F97.9°F

45°F85°F

IHCL-5

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-6

34300/64400 BTU/H12 GPM

39.3°F95.8°F

45°F85°F

IHCL-7

30000/56300 BTU/H9 GPM

38.4°F97.6°F

45°F85°F

P-1

62.5 GPM71.1/70.5 FT

P-2

62.5 GPM71.1/70.5 FT

AS-1

AV-1

HSS-1

189300/355400 BTU/H62.5 GPM

39°F96.4°F

45°F85°F

ET-1

7.3 GAL

V-1

BV-IHCL -1

STR-1V-2

V-3

BV-IHCL -2

STR-2V-4

V-5

BV-IHCL -3

STR-3V-6

V-7

BV-IHCL-4

STR-4V-8

V-9

BV-IHCL-5

STR-5V-10

V-11

BV-IHCL -6

STR-6V-12

V-13

BV-IHCL-7

ST R-7V-14

2.5"

2.5"2.5"

2.5"

1.25"1.25"

2.5"

2"1"1"

1"

2"1.25"

1.25"1.25"

1.25"

2"

2.5"

Install motorized isolation valves and variable speed primary pumps

102

Page 103: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Solution Considerations: One-Pipe Solution

IHCL-22

6400/12100 BTU/H2.5 GPM

39.9°F94.7°F

45°F85°F

IHCL-23

25700/48300 BTU/H9 GPM

39.1°F96.2°F

44.8°F85.4°F

IHCL-24

50000/93900 BTU/H16 GPM

37.8°F98.7°F

44°F86.9°F

IHCL-25

17100/32200 BTU/H5 GPM

35.6°F102.9°F

42.4°F90°F

IHCL-26

25700/48300 BTU/H9 GPM

36.2°F101.8°F

41.8°F91°F

IHCL-27

34300/64400 BTU/H12 GPM

35.3°F103.3°F

41°F92.5°F

IHCL-28

30000/56300 BTU/H9 GPM

33.3°F107.2°F

39.9°F94.6°F

P-26

62.5 GPM30 FT

P-27

62.5 GPM30 FT

AS-4

AV-4

HSS-4

189300/355400 BTU/H62.5 GPM

39°F96.4°F

45°F85°F

ET-4

7.1 GAL2.5 GPM14.2/14.1 FTP-IHCL-22

TT -1

9 GPM13.1/13 FTP-IHCL-23

TT -2

16 GPM21.9/21.7 FTP-IHCL-24

TT -3

5 GPM11.5/11.3 FTP-IHCL-25

TT -4

9 GPM13.1/13 FTP-IHCL-26

TT -5

12 GPM17.4/17.3 FTP-IHCL-27

TT -6

9 GPM12.4/12.3 FTP-IHCL-28

TT -7

V-43

V-44

V-45

V-46

V-47

V-48

V-49

BV-IHCL-22

BV-IHCL-23

BV-IHCL-24

BV-IHCL-25

BV-IHCL-26

BV-IHCL-27

BV-IHCL-28

2.5"

2.5"

Required re-piping of the building

103

Page 104: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Ultimate Solution

IHCL-15

6400/12100 BTU/H2.5 GPM

39.9°F94.7°F

45°F85°F

IHCL-16

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-17

50000/93900 BTU/H16 GPM

38.8°F96.8°F

45°F85°F

IHCL-18

17100/32200 BTU/H5 GPM

38.2°F97.9°F

45°F85°F

IHCL-19

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-20

34300/64400 BTU/H12 GPM

39.3°F95.8°F

45°F85°F

IHCL-21

30000/56300 BTU/H9 GPM

38.4°F97.6°F

45°F85°F

P-17

62.5 GPM32 FT

P-18

62.5 GPM32 FT

AS-3

AV-3

HSS-3

189300/355400 BTU/H62.5 GPM

39°F96.4°F

45°F85°F

ET-3

7.2 GAL

V-29

V-30

V-31

V-32

V-33

V-34

V-35

V-36

V-37

V-38

V-39

V-40

V-41

V-42

2.5 GPM15.3 FTP-19

9 GPM14.4 FTP-20

16 GPM22.9 FTP-21

5 GPM12.5 FTP-22

9 GPM14.4 FTP-23

12 GPM18.2 FTP-24

9 GPM13.7 FTP-25

39°F96.4°F

45°F85°F

39°F96.4°F

45°F85°FHS-1

2.5"

2.5"

2.5"

2"

1"

2"

1.25"

1.25"

2"

104

Page 105: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Ultimate Solution IHCL-15

6400/12100 BTU/H2.5 GPM

39.9°F94.7°F

45°F85°F

IHCL-16

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-17

50000/93900 BTU/H16 GPM

38.8°F96.8°F

45°F85°F

IHCL-18

17100/32200 BTU/H5 GPM

38.2°F97.9°F

45°F85°F

IHCL-19

25700/48300 BTU/H9 GPM

39.3°F95.8°F

45°F85°F

IHCL-20

34300/64400 BTU/H12 GPM

39.3°F95.8°F

45°F85°F

IHCL-21

30000/56300 BTU/H9 GPM

38.4°F97.6°F

45°F85°F

P-17

62.5 GPM32 FT

P-18

62.5 GPM32 FT

AS-3

AV-3

HSS-3

189300/355400 BTU/H62.5 GPM

39°F96.4°F

45°F85°F

ET-3

7.2 GAL

V-29

V-30

V-31

V-32

V-33

V-34

V-35

V-36

V-37

V-38

V-39

V-40

V-41

V-42

2.5 GPM15.3 FTP-19

9 GPM14.4 FTP-20

16 GPM22.9 FTP-21

5 GPM12.5 FTP-22

9 GPM14.4 FTP-23

12 GPM18.2 FTP-24

9 GPM13.7 FTP-25

39°F96.4°F

45°F85°F

39°F96.4°F

45°F85°FHS-1

2.5"

2.5"

2.5"

2"

1"

2"

1.25"

1.25"

2"

1. Install variable speed circulators to pump the bore field based on temperature differential

2. Install hydronic de-coupler (bridge)

3. Install circulators on each heat pump

1

2

3

105

Page 106: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Ultimate Solution: Building Energy Consumption

Degree days % savings

100 52.64%200 53.65%300 54.51%400 55.31%500 56.11%600 56.91%700 57.74%800 58.60%900 59.50%

1000 60.46%1100 61.48%1200 62.58%

y = -4.226ln(x) + 33.107

y = -8.214ln(x) + 66.64

0

5

10

15

20

25

30

35

40

150 250 350 450 550 650 750 850 950 1050

After November 2011 Before november 2011

106

Page 107: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

What have we learned?

107

Page 108: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

Lessons Learned • Pumping energy use is not an insignificant

issue. • Decoupling bore field and using

temperature differential to control bore field capacity offers significant benefits.

• Minimizing head on unit circulators is beneficial.

• Low efficiency circulators can provide high efficiency.

108

Page 109: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

109

Questions

? ? ?

?

? ?

?

?

? ?

?

Page 110: Design of Commercial Ground Source Heat Pumps - …ashraemadison.org/downloads/Meeting_Presentations/april_2014_tech...Design of Commercial Ground Source Heat Pumps . 1 ... – ASHRAE

HVAC System Designer

• Responsible for – Thermodynamics of the

system – Design of system hydronics – Specification of the entire

HVAC system • The ground HX is part of it!

– The entire system performance

110