ARRAY1 ‐ STRING1:
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28 EA CANADIAN SOLAR CS6P‐250P MODULES
102.22 FT; R=4O5'
PROPERTY LINE
ELLEN DRIVE
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULESARRAY2 ‐ STRING2: 14 EA CANADIAN SOLAR CS6P‐250P MODULESARRAY2/ARRAY3/ARRAY4 ‐ STRING3: 14 EA CANADIAN SOLAR CS6P‐250P MODULES
62 FT; R=175'
PROPERTY LINE
119 FT
PROPERTY LINE
500 FT
PROPERTY LINE
MSP, DC/AC DISCONNECT& MONITORING ITRONMETER LOCATION
AZIMUTH 225°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
14 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P17 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P8 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
AZIMUTH 315°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P3 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
AZIMUTH 135°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/‐ (TRUE SOUTH=180°)
Sunmodule Protectt SW 270 mono14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES:
Outside Face Wall Line
1SOL‐02
APN: 164‐254‐05
SITE PLAN1SCALE = NONE
GRID-TIED PV SYSTEM
ABDOULIE MANNEH, Assoc. AIA
SCALE:
DRAWN BY:
SYSTEM TYPE
ENGINEER:
REV: DATE:
SOL-01
NTS
0 10‐23‐2013
DRAWING NUMBER:
DRAWING DESCRIPTION:
SITE PLAN
N
SITE ADDRESS:
PROJECT NAME:
OWNER
NAME:
287
ELL
EN
DR
IVE
SA
N R
AFA
EL,
CA
9490
3-16
02A
PN: 1
64-2
54-0
5
DU
BEN
, RO
NA
LDBOX 61
62, SANTA
ROSA
, CA 954
01PH
: 707
‐528
‐765
2FA
X: 707
‐528
‐686
5CA
LIC# 93
9082
GEN
ERAL CONTR
ACTO
R:
NORTH
ERN PACIFIC PO
WER
SYSTEMS
TYPICAL ELEVATION1SCALE = NTS
GRID-TIED PV SYSTEM
ABDOULIE MANNEH, Assoc. AIA
SCALE:
DRAWN BY:
SYSTEM TYPE
ENGINEER:
REV: DATE:
SOL-02
NTS
0
DRAWING NUMBER:
DRAWING DESCRIPTION:
TYPICAL ELEVATION
5/16"X3" LAG BOLT
2X6 @ 16" O/CLOAD BEARING WALL
2X6 @ 16" O/CLOAD BEARING WALL
2X6 @ 16" O/C
TRANSPARENT SOLAR MODULES
SOLAR MODULES
LOAD BEARING WALL6x6 D.F. #1 POST W/ PC66 CAP TYP.
3X8 D.F. TRELLIS FRAMING @ 24" O.C
6X8 D.F. #1 HDR
Ground Leve'
IRONRIDG
E END / M
IDCLIPS
IRONRIDG
E XRL STAN
DARD
RAILS AND
CLAMPS
QUICKMOUN
T PV
COMP. FO
OTINGS
5/16"X3"
LAG BOLT
ANGLE CO
NNECTOR
2X4 Truss Rafter @ 24" O/C
SOLAR MODULES
A
SITE ADDRESS:
PROJECT
NAME:
OWNER
NAME:
287
ELLE
N D
RIV
ES
AN
RA
FAE
L, C
A94
903-
1602
APN
: 164
-25 4
-05
DU
BEN
, RO
NA
LD
5/16"X3" LAG BOLT
IRONRIDGE END / MIDCLIPS
IRONRIDGE XRL STANDARDRAILS AND CLAMPS
QUICKMOUNT PVTrellis FOOTINGS:
ANGLE CONNECTOR
3X8 D.F. TRELLIS FRAMING @ 24" O.C on 6X8 D.F. #1 HDR on 6x6 D.F. #1 POST W/ PC66 CAP TYP.
TRANSPARENT SOLAR MODULES
10‐23‐2013
BOX 6162, SANTA
ROSA
, CA 954
01PH
: 707
‐528
‐765
2FA
X: 707
‐528
‐686
5CA
LIC# 93
9082
GEN
ERAL CONTR
ACTO
R:
NORTH
ERN PACIFIC PO
WER
SYSTEMS
PV ARRAY
SITE ADDRESS:
PROJECT NAME:
SCALE:
DRAWN BY:
SYSTEM TYPE
ENGINEER:
REV: DATE:
SOL‐03
OWNER
NAME:
DRAWING NUMBER:
DRAWING DESCRIPTION:
GRID-TIED PV SYSTEM
ABDOULIE MANNEH, Assoc. AIA
NTS
0
LAYOUT
287
ELL
EN
DR
IVE
SA
N R
AFA
EL,
CA
9490
3-16
02A
PN: 1
64-2
54-0
5
DU
BEN
, RO
NA
LD
Outside Face Wall Line
ARRAY1 ‐ STRING1:
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28 EA CANADIAN SOLAR CS6P‐250P MODULES
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULESARRAY2 ‐ STRING2: 14 EA CANADIAN SOLAR CS6P‐250P MODULESARRAY2/ARRAY3/ARRAY4 ‐ STRING3:14 EA CANADIAN SOLAR CS6P‐250P MODULES
MSP, DC/AC DISCONNECT& MONITORING ITRONMETER LOCATION
AZIMUTH 225°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
14 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P17 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P8 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
AZIMUTH 315°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P3 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
AZIMUTH 135°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/‐ (TRUE SOUTH=180°)
Sunmodule Protectt SW 270 mono14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES:
ROOF RIDE
ROOF EAVE
3/4" EMT
1/2" EMT
VENT
VENT VENT
1SO
L‐02
PV ARRAY LAYOUT1SCALE: NTS
N 10‐23‐2013
BOX 61
62, SANTA
ROSA
, CA 954
01PH
: 707
‐528
‐765
2FA
X: 707
‐528
‐686
5CA
LIC# 93
9082
GEN
ERAL CONTR
ACTO
R:
NORTH
ERN PACIFIC PO
WER
SYSTEMS
PV FOOTING
SCALE:
DRAWN BY:
SYSTEM TYPE
ENGINEER:
REV: DATE:
SOL‐04DRAWING NUMBER:
DRAWING DESCRIPTION:
GRID-TIED PV SYSTEM
ABDOULIE MANNEH, Assoc. AIA
NTS
0
LAYOUT
Outside Face Wall Line
ARRAY1 ‐ STRING1:
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28 EA CANADIAN SOLAR CS6P‐250P MODULES
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES
ARRAY2 ‐ STRING2: 14 EA CANADIAN SOLAR CS6P‐250P MODULES
ARRAY2/ARRAY3/ARRAY4 ‐ STRING3:14 EA CANADIAN SOLAR CS6P‐250P MODULES
MSP,DC/AC DISCONNECT& MONITORING ITRONMETER LOCATIONAZIMUTH 225°+/‐ (TRUE SOUTH=180°)
ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P17 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P8 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
AZIMUTH 315°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P3 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
AZIMUTH 135°+/‐ (TRUE SOUTH=180°)ROOF MOUNTED FLUSHED
14 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
ON 18° ROOF SLOPE;
ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/‐ (TRUE SOUTH=180°)
Sunmodule Protectt SW 270 mono14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES:
ROOF RIDGE
QTY. TOTAL= 62
QUICKMOUNT PVCOMP. FOOTINGS5/16"X3" LAG BOLT
2x4 TRUSS @ 24" O/C
2x4 T
RUSS @
24" O
/C
2x4 T
RUSS @
24" O
/C
ROOF EAVE
VENT
VENTVENT
6x6 D.F. #1 POST W/ PC66 CAP TYP.
6X8 D.F. #1 HDR
3X8 D.F. TRELLIS FRAMING @ 24" O.C1
SOL‐02
PV RACKING LAYOUT1SCALE: NTS
N
A
SITE ADDRESS:
PROJECT NAME:
OWNER
NAME:
287
ELL
EN
DR
IVE
SA
N R
AFA
EL,
CA
9490
3-16
02A
PN: 1
64-2
54-0
5
DU
BEN
, RO
NA
LD
10‐23‐2013
BOX 61
62, SANTA
ROSA
, CA 954
01PH
: 707
‐528
‐765
2FA
X: 707
‐528
‐686
5CA
LIC# 93
9082
GEN
ERAL CONTR
ACTO
R:
NORTH
ERN PACIFIC PO
WER
SYSTEMS
PV RACKING
SCALE:
DRAWN BY:
SYSTEM TYPE
ENGINEER:
REV: DATE:
SOL‐05DRAWING NUMBER:
DRAWING DESCRIPTION:
GRID-TIED PV SYSTEM
ABDOULIE MANNEH, Assoc. AIA
NTS
0
LAYOUT
Max Cantilver Recommended is 1'8"
Outside Face Wall Line
ARRAY1 ‐ STRING1:
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28 EA CANADIAN SOLAR CS6P‐250P MODULES
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES: MUNTED ON TRELLIS
ARRAY2 ‐ STRING2: 14 EA CANADIAN SOLAR CS6P‐250P MODULES: MOUNTED ON ROOF COMP.
ARRAY2/ARRAY3/ARRAY4 ‐ STRING3:14 EA CANADIAN SOLAR CS6P‐250P MODULES: MOUNTED ON ROOF COMP>
MSP, DC/AC DISCONNECT& MONITORING ITRONMETER LOCATION
ROOF RIDE
ROOF EAVE
QTY. TOTAL= 62
QUICKMOUNT PVCOMP. FOOTINGS5/16"X3" LAG BOLT
IRON RIDGE RAIL
RAIL SPLICE
RAIL SPLICE
RAIL SPLICEIRON RIDGE RAIL
ARRAY 1: ON TRELLIS
ARRAY 2: ON ROOF A: COMP.
ARRAY 3: ON ROOF B: COMP.
ARRAY 4: ON ROOF C: COMP.
ABC
RAIL SPLICE
IRON RIDGE RAIL
IRON
RAIL RIDGE
2x4 TRUSS @ 24" O/C
2x4 T
RUSS @
24" O
/C
2x4 T
RUSS @
24" O
/C
3X8 D.F. TRELLIS FRAMING @ 24" O.C
6x6 D.F. #1 POST W/ PC66 CAP TYP.
6X8 D.F. #1 HDR
1SO
L‐02
NPV RACKING LAYOUT1SCALE: NTS
ARRAY3 ‐ ROOF C: COMP.
MODULE WEIGHT:
MODULE LENGTH:
MODULE WIDTH:
MODULE DEPTH:
TOTAL MODULES:
SUM= MODULES WEIGHT:
INSTALLATION WEIGHT:
INSTALLATION AREA:
POINT QTY / AVG LOAD:
41.9 LBS
64.5 INCHES
38.7 INCHES
1.57 INCHES
335.28 LBS
440.69 LBS
138.68 FT²
DISTRIBUTED LOAD:
ROOF C
8 EA.
ARRAY3 ‐ ROOF B: COMP.
MODULE WEIGHT:
MODULE LENGTH:
MODULE WIDTH:
MODULE DEPTH:
TOTAL MODULES:
SUM= MODULES WEIGHT:
INSTALLATION WEIGHT:
INSTALLATION AREA:
POINT QTY / AVG LOAD:
41.9 LBS
64.5 INCHES
38.7 INCHES
1.57 INCHES
125.73 LBS
165.26 LBS
52.00 FT²
DISTRIBUTED LOAD:
ROOF B
3 EA.
ARRAY2 ‐ ROOF A: COMP.
MODULE WEIGHT:
MODULE LENGTH:
MODULE WIDTH:
MODULE DEPTH:
TOTAL MODULES:
SUM= MODULES WEIGHT:
INSTALLATION WEIGHT:
INSTALLATION AREA:
POINT QTY / AVG LOAD:
41.9 LBS
64.5 INCHES
38.7 INCHES
1.57 INCHES
712.47 LBS
936.46 LBS
294.68 FT²
DISTRIBUTED LOAD: 3.18 LBS/FT²
36.02 LBS
ROOF A
17 EA.
ARRAY1 ‐ ON TRELLIS
MODULE WEIGHT:
MODULE LENGTH:
MODULE WIDTH:
MODULE DEPTH:
TOTAL MODULES:
SUM= MODULES WEIGHT:
SUM= MOUNTS, RAILS & MICRO‐INVERTERS
INSTALLATION WEIGHT:
INSTALLATION AREA:
POINT QTY / AVG LOAD:
46.7 LBS
65.94 INCHES
39.41 INCHES
1.22 INCHES
653.80 LBS
184.46 LBS
838.26 LBS
252.65 FT²
DISTRIBUTED LOAD: 3.32 LBS/FT²
41.91 LBS
14
MICR‐INVERTER WEIGHT:
TOTAL MICRO‐INVERTERS:
ROOF1
14 EA.
3.5 LBS
SUM= MOUNTS, RAILS & MICRO‐INVERTERS 223.99.16 LBS
17
MICR‐INVERTER WEIGHT:
TOTAL MICRO‐INVERTERS:
3.5 LBS
SUM= MOUNTS, RAILS & MICRO‐INVERTERS 39.53 LBS
3
MICR‐INVERTER WEIGHT:
TOTAL MICRO‐INVERTERS:
3.5 LBS
SUM= MOUNTS, RAILS & MICRO‐INVERTERS 105.41 LBS
8
MICR‐INVERTER WEIGHT:
TOTAL MICRO‐INVERTERS:
3.5 LBS
3.18 LBS/FT²
27.54 LBS
3.18 LBS/FT²
44.07 LBS
A
SITE ADDRESS:
PROJECT NAME:
OWNER
NAME:
287
ELL
EN
DR
IVE
SA
N R
AFA
EL,
CA
9490
3-16
02A
PN: 1
64-2
54-0
5
DU
BEN
, RO
NA
LD
10‐23‐2013
BOX 61
62, SANTA
ROSA
, CA 954
01PH
: 707
‐528
‐765
2FA
X: 707
‐528
‐686
5CA
LIC# 93
9082
GEN
ERAL CONTR
ACTO
R:
NORTH
ERN PACIFIC PO
WER
SYSTEMS
PV STRING
SCALE:
DRAWN BY:
SYSTEM TYPE
ENGINEER:
REV: DATE:
SOL‐06DRAWING NUMBER:
DRAWING DESCRIPTION:
GRID-TIED PV SYSTEM
ABDOULIE MANNEH, Assoc. AIA
NTS
0
LAYOUT
A
SITE ADDRESS:
PROJECT NAME:
OWNER
NAME:
287
ELL
EN
DR
IVE
SA
N R
AFA
EL,
CA
9490
3-16
02A
PN: 1
64-2
54-0
5
DU
BEN
, RO
NA
LD
10‐23‐2013
BOX 61
62, SANTA
ROSA
, CA 954
01PH
: 707
‐528
‐765
2FA
X: 707
‐528
‐686
5CA
LIC# 93
9082
GEN
ERAL CONTR
ACTO
R:
NORTH
ERN PACIFIC PO
WER
SYSTEMS
Outside Face Wall Line
ARRAY1 ‐ STRING1:
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28 EA CANADIAN SOLAR CS6P‐250P MODULES
14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULESARRAY2 ‐ STRING2: 14 EA CANADIAN SOLAR CS6P‐250P MODULESARRAY2/ARRAY3/ARRAY4 ‐ STRING3:14 EA CANADIAN SOLAR CS6P‐250P MODULES
MSP, DC/AC DISCONNECT& MONITORING ITRONMETER LOCATION
AZIMUTH 225°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
14 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P17 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P8 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
AZIMUTH 315°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P3 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL
AZIMUTH 135°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED
ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/‐ (TRUE SOUTH=180°)
Sunmodule Protectt SW 270 mono14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES:
ROOF RIDE
ROOF EAVE
3/4" EMT
1/2" EMT
TYP. 6" J‐BOX
1/2" EMT
TYP. 6" J‐BOX
TYP. 6" J‐BOX
VENT
VENT VENT
1SO
L‐02
PV STRING LAYOUT1SCALE: NTS
N
ELECTRICAL LINE DIAGRAM1SCALE = NONE
SCALE:
DRAWN BY:
SYSTEM TYPE
ENGINEER:
REV: DATE:
SOL-07DRAWING NUMBER:
ELECTRICAL LINE
DRAWING DESCRIPTION:
GRID-TIED PV SYSTEM
ABDOULIE MANNEH, Assoc. AIA
NTS
0
DIAGRAM
SITE ADDRESS:
PROJECT NAME:
OWNER
NAME:
287
ELL
EN
DR
IVE
SA
N R
AFA
EL,
CA
9490
3-16
02A
PN: 1
64-2
54-0
5
DU
BEN
, RO
NA
LD
PRE‐WIRED CONNECTIONS
L1L2
GN
DC IN
AC OUT
DC IN
L1L2
AC OUT
GN
END CAPS INSTALLED ON LAST INVERTER CABLEOF BRANCH CIRCUIT
ENPHASE M215+‐
G (N) J‐BOX 1
+‐
G
BRANCH CIRCUIT 3 WITH(BC3)
PRE‐WIRED ASSEMBLYENPHASE ACINTERCONNECT CABLE
L1L2
GN
DC IN
AC OUT
DC IN
L1L2
AC OUT
GN
+‐
G
+‐
G
BRANCH CIRCUIT 2 WITH(BC2)
N
(MSP1)(NEW) 200A, 120/240V SERVICE PANEL
G
METER
N G
200A
BC1, BC2 OCP =
(E) 100A
NEW SOLAR DEDICATEDINVERTER LOADCENTER
MODULES AND MICRO‐INVERTERS BONDEDTO SUPPORT RAIL VIA WEEB LUG.
CANADIAN SOLAR250W MODULE
(1) #8 AWG NEUT.(1) #8 AWG CU, GRND3/4" CONDUIT MIN.FROM ( AGAC1 ) TO ( ACDC1 )
14 ENPHASE MICRO‐INVERTERS
14 ENPHASE MICRO‐INVERTERS
(AGAC1)
(JB1)
(2) #8 AWG THHN CU
FROM ( JB1, JBL2, & JBL3) TO ( AGAC1 )3/4" EMT(1) #8 AWG CU, GRND(9) #10 AWG THWN‐2 CU
END CAPS INSTALLED ON LAST INVERTER CABLEOF BRANCH CIRCUIT
MICRO‐INVERTER
ENPHASE M215MICRO‐INVERTER
ENPHASE M215MICRO‐INVERTER
ENPHASE M215MICRO‐INVERTER
@ #12 AWG TYP.
PRE‐WIRED CONNECTIONS@ #12 AWG TYP.
PRE‐WIRED ASSEMBLYENPHASE ACINTERCONNECT CABLE
TO PG&E
2‐POLE MAINEXISTINGLOADS
2‐POLE
EA. 20A 2P
G
60A FUSES, 120/240V, 3R 1PHFUSED AC DISCO W/60A GENERAL DUTYSQUARE‐D ( D221NRB )(ACDC1)
(E) GND ROD/ GROUNDINGELECTRODE SYSTEM
(1) #8 AWG NEUT.(1) #8 AWG CU, GRND3/4" CONDUIT MIN.FROM ( ACDC1 ) TO ( SP1 )
(2) #8 AWG THHN CU
CANADIAN SOLAR250W MODULE
100A, 120/240V SUB‐PANEL
L1L2
GN
DC IN
AC OUT
DC IN
L1L2
AC OUT
GN
+‐
G
+‐
G
BRANCH CIRCUIT 1 WITH(BC1)
MODULES AND MICRO‐INVERTERS BONDEDTO SUPPORT RAIL VIA WEEB LUG.
14 ENPHASE MICRO‐INVERTERS
SOLAR WORLD 270W MODULE
END CAPS INSTALLED ON LAST INVERTER CABLEOF BRANCH CIRCUIT
ENPHASE M215MICRO‐INVERTER
ENPHASE M215MICRO‐INVERTER
PRE‐WIRED CONNECTIONS@ #12 AWG TYP.
PRE‐WIRED ASSEMBLYENPHASE ACINTERCONNECT CABLE
(Semi-Transparent)
SOLAR WORLD 270W MODULE (Semi-Transparent)
MODULES AND MICRO‐INVERTERS BONDEDTO SUPPORT RAIL VIA WEEB LUG.
CANADIAN SOLAR250W MODULE
CANADIAN SOLAR250W MODULE
INSULATION PIERCINGWIRE TAPS W/
TAP CONNECTOR(IPS 1/O‐2 AWG OR EQUIV.)
10‐23‐2013
BOX 61
62, SANTA
ROSA
, CA 954
01PH
: 707
‐528
‐765
2FA
X: 707
‐528
‐686
5CA
LIC# 93
9082
GEN
ERAL CONTR
ACTO
R:
NORTH
ERN PACIFIC PO
WER
SYSTEMS
INVERTER OUTPUT DATA:
SHALL BE PLACED ON EACHAC DISCONNECT / BREAKER 1/8" LETTERING
LOCATED AT MAIN SERVICE POINT OF INTERCONNECTION 3/8" WHITE LETTERING ON RED BACKING
LOCATED AT MAIN SERVICE POINT OF INTERCONNECTION 3/8" WHITE LETTERING ON RED BACKING
SHALL BE PLACED EVERY 10' REQUIRED ON ALL DC RACEWAYS, J‐BOXES AND ENCLOSURES 3/8" WHITE LETTERING ON RED BACKING
SHALL BE PLACED ONAC COMBINER PANEL & AC DISCONNECT "WARNING" SHALL BE 1/4" TEXT ALL OTHER TEXT IS 1/8"
SHALL BE LOCATED NEXT TO CIRCUITBREAKER AT INTERACTIVE SYSTEM POINTOF INTERCONNECTION 1/8" WHITE
CIRUIT OUTPUT DATA:
PANEL/BUS RATING X 1.20%=
ALL COMBINED SOURCES MUST BE < OR = 240A
LETTERING ON SOLID BACKING
CIRUIT OUTPUT DATA: PER BRANCH
SHALL BE PLACED ON EACHAC DISCONNECT / BREAKER 1/8" LETTERING
BRANCH CIRCUIT 1
BRANCH CIRCUIT 2
Sunmodule Protectt SW 270 mono
CAUTION: SOLAR CIRCUIT
CAUTION: SOLAR ELECTRICSYSTEM CONNECTED
PV SYSTEM DISCONNECTFOR UTILITY OPERATION
PHOTOVOLTAIC DISCONNECTFOR UTILITY USE
OPERATING CURRENT:OPERATING VOLTAGE: 240 V
WARNING:ELECTRIC SHOCK HAZARD.DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH THE LINEAND LOAD SIDES MAY BE ENERGIZED IN
THE OPEN POSITION.
WARNING:INVERTER OUTPUT CONNECTION
DO NOT RELOCATE THISOVERCURRENT DEVICE
15.3 A
PHOTOVOLTAIC DISCONNECTFOR UTILITY USE
OPERATING CURRENT:OPERATING VOLTAGE: 240 V
14.4 A
MODULE SPECIFICATIONBRAND
TYPE
# OF MODULES
Voc
Vmp
Isc
Imp
CANADIAN SOLAR
CS6P‐250P
28
37.2 V
30.1 V
8.87 A
8.30 A
INVERTER SPECIFICATIONBRAND
TYPE
ENPHASE M215 MICROINVERTER
M215‐60‐2LL
AC MAXIMUM OUTPUT POWER=
AC NOMINAL VOLTAGE RANGE=
AC FREQUENCY RANGE= 60Hz
POWER FACTOR @ FULL LOAD= > 0.95
215W @ 240V
AC MAXIMUM OUTPUT CURRENT= .9A @ 240V
DISCRIPTION 250W SOLAR MODULE
17 UNITS MAX PER CIR.
211‐264V AC
BRANCH CIRCUIT 1INVERTER QTY.
AC COMBINED OUTPUT POWER=
AC COMBINED OUTPUT CURRENT=
TOTAL POWER kW=
TOTAL OUTPUT CURRENT= 37.8A X 1.25= 47.25A
TOTAL INVERTER QTY=
9,030W @ 240V
SOLAR SOURCE SELECTED OCPD=
200A
BC1, BC2, BC3; EA. 20A 2‐P
PG&E SOURCE BREAKER SIZE=
INTERCONNECTION LOCATION= LINE SIDE OF MAIN
200A
240A
PANEL/BUS RATING=
14
3,010W @ 240V
12.6A X 1.25= 15.75A
BRANCH CIRCUIT 2 & BRANCH CIRCUIT 3INVERTER QTY.
AC COMBINED OUTPUT POWER=
AC COMBINED OUTPUT CURRENT=
14 PER BRANCH
SOLAR WORLD
39.2 V
30.9 V
9.44 A
8.81 A
270W SOLAR MODULE
14
42
3,010W @ 240V
12.6A X 1.25= 15.75A
solarworld.com
Designed to withstand heavy
accumulations of snow and ice
Every component is tested to meet
3 times IEC requirements
Sunmodule Plus:
Positive performance tolerance
25-year linear performance warranty and
10-year product warranty
-0/+5 Wp
WARRANTY
TUV Power controlled:
Lowest measuring tolerance in industry
World-class qualityFully-automated production lines and seamless monitoring of the process and material ensure the quality that the company sets as its benchmark for its sites worldwide.
SolarWorld Plus-SortingPlus-Sorting guarantees highest system efficiency. SolarWorld only delivers modules that have greater than or equal to the nameplate rated power.
25 years linear performance guarantee and extension of product warranty to 10 yearsSolarWorld guarantees a maximum performance degression of 0.7% p.a. in the course of 25 years, a significant added value compared to the two-phase warranties common in the industry. In addition, SolarWorld is offering a product warranty, which has been extended to 10 years.*
*in accordance with the applicable SolarWorld Limited Warranty at purchase.www.solarworld.com/warranty
Plus SW 270 mono
SW-01-6004US 08-2013
1) Measuring tolerance (Pmax
) traceable to TUV Rheinland: +/- 2% (TUV Power Controlled).
THERMAL CHARACTERISTICS
NOCT 46 °C
TC Isc
0.004 %/K
TC Voc
-0.30 %/K
TC Pmpp
-0.45 %/K
Operating temperature -40°C to 85°C
PERFORMANCE AT 800 W/m², NOCT, AM 1.5
Maximum power Pmax
201.3 Wp
Open circuit voltage Voc
35.9 V
Maximum power point voltage Vmpp
28.3 V
Short circuit current Isc
7.63 A
Maximum power point current Impp
7.12 A
Minor reduction in efficiency under partial load conditions at 25°C: at 200 W/m², 100% (+/-2%) of the STC efficiency (1000 W/m²) is achieved.
COMPONENT MATERIALS
Cells per module 60
Cell type Mono crystalline
Cell dimensions 6.14 in x 6.14 in (156 mm x 156 mm)
Front Tempered glass (EN 12150)
Frame Clear anodized aluminum
Weight 46.7 lbs (21.2 kg)
ADDITIONAL DATA
Power sorting1 -0 Wp / +5 Wp
J-Box IP65
Connector MC4
Module efficiency 16.10 %
Fire rating (UL 790) Class C
SYSTEM INTEGRATION PARAMETERS
Maximum system voltage SC II 1000 V
Max. system voltage USA NEC 600 V
Maximum reverse current 16 A
Number of bypass diodes 3
UL Design Loads* Two rail system113 psf downward
64 psf upward
UL Design Loads* Three rail system170 psf downward
64 psf upward
IEC Design Loads* Two rail system113 psf downward
50 psf upward
* Please refer to the Sunmodule installation instructions for the details associated with these load cases.
PERFORMANCE UNDER STANDARD TEST CONDITIONS (STC)*
Maximum power Pmax
270 Wp
Open circuit voltage Voc
39.2 V
Maximum power point voltage Vmpp
30.9 V
Short circuit current Isc
9.44 A
Maximum power point current Impp
8.81 A
*STC: 1000 W/m², 25°C, AM 1.5
Independently created PAN files now available.Ask your account manager for more information.
NEW!
Plus SW 270 mono
All units provided are imperial. SI units provided in parentheses. SolarWorld AG reserves the right to make specification changes without notice.
Mo
du
le c
urr
ent
[A]
Module voltage [V]
1000 W/m²
800 W/m²
600 W/m²
400 W/m²
200 W/m²
100 W/m²
ISC
VOC
CS6P is a robust solar module with 60 solar
cells. These modules can be used for on-grid
solar applications. Our meticulous design and
production techniques ensure a high-yield,
long-term performance for every module
produced. Our rigorous quality control and
in-house testing facilities guarantee Canadian
Solar's modules meet the highest quality
standards possible.
CS6P
On-grid Module
On-grid residential roof-tops
On-grid commercial/industrial roof-tops
Solar power stations
Other on-grid applications
Applications
www.canadiansolar.com
IEC 61215, IEC 61730, UL1703, CEC Listed,
CE and MCS
ISO9001: 2008: Standards for quality
management systems
ISO/TS16949:2009: The automotive quality
management system
Quality Certificates
Key Features
Top ranked PVUSA (PTC) rating in California for higher
energy production
Industry first comprehensive warranty insurance by
AM Best rated leading insurance companies in the world
Industry leading plus only power tolerance: 0 ~ +5W
Strong framed module, passing mechanical load test
of 5400Pa to withstand heavier snow load
The 1st manufacturer in the PV industry certified for
ISO:TS16949 (The automotive quality management
system) in module production since 2003
ISO17025 qualified manufacturer owned testing lab,
fully complying to IEC, TUV, UL testing standards
ISO14001:2004: Standards for Environmental
management systems
QC080000 HSPM: The Certification for
Hazardous Substances Regulations
Environmental Certificates
10 year product warranty on materials and workmanship
25 year linear power output warranty
Backed By Our New 10/25 Linear Power Warranty Plus our added 25 year insurance coverage
5 10 15 20 250%
80%
90%
97%100%
Added Value From Warranty
230/235/240/245/250P
2Under Standard Test Conditions (STC) of irradiance of 1000W/m , spectrum AM 1.5 and cell temperature of 25
*Specifications included in this datasheet are subject to change without prior notice.
Engineering Drawings
I-V Curves (CS6P-250P)
Temperature Coefficient
About Canadian Solar
Headquarters | 650 Riverbend Drive, Suite BKitchener, Ontario | Canada N2K 3S2Tel: +1-519-954-2057Fax: [email protected]
CS6P-230/235/240/245/250PElectrical Data
Pmax
Voc
Isc
-0.43
-0.34 %/
0.065 %/
45 2
%/
Temperature Characteristics
NOCT
Nominal Maximum Power (Pmax)
Optimum Operating Voltage (Vmp)
Optimum Operating Current (Imp)
Open Circuit Voltage (Voc)
Short Circuit (Isc)Current
2Under Normal Operating Cell Temperature, Irradiance of 800 W/m , spectrum AM 1.5, ambient temperature 20 , wind speed 1 m/s
Performance at Low Irradiance
Normal Operating Cell Temperature
Mechanical DataCell Type
Cell Arrangement
Dimensions
Weight
Front Cover
Frame Material
J-BOX
Cable
Connectors
Standard Packaging (Modules per Pallet)
Module Pieces per container (40 ft . Container)
Industry leading performance at low irradiation
environment, +95.5% module efficiency from an 2 2
irradiance of 1000w/m to 200w/m
(AM 1.5, 25 )
EN-Rev 3.39 Copyright 2011 Canadian Solar Inc.
Canadian Solar Inc. is one of the world's largest solar
c o m p a n i e s . A s a l e a d i n g v e r t i c a l l y - i n t e g r a t e d
manufacturer of ingots, wafers, cells, solar modules and
solar systems. Canadian Solar delivers solar power
products of uncompromising quality to worldwide
customers. Canadian Solar's world class team of
professionals works closely with our customers to
provide them with solutions for all their solar needs.
STC
Nominal Maximum Power (Pmax)
Optimum Operating Voltage (Vmp)
Optimum Operating Current (Imp)
Open Circuit Voltage (Voc)
Short Circuit (Isc)
Module Efficiency
Operating Temperature
Maximum System Voltage
Maximum Series Fuse Rating
Application Classification
Power Tolerance
Current
Canadian Solar was founded in Canada in 2001 and was
successfully listed on NASDAQ Exchange (symbol: CSIQ) in
November 2006. Canadian Solar has already expanded its
m o d u l e m a n u f a c t u r i n g c a p a c i t y t o 2 . 0 5 G W a n d c e l l
manufacturing capacity to 1.3GW in 2011.
Section B-B
Section A-A A A
BB
CS6P-230P
230W
29.6V
7.78A
36.8V
8.34A
14.30%
CS6P-235P
235W
29.8V
7.90A
36.9V
8.46A
14.61%
CS6P-240P
240W
29.9V
8.03A
37.0V
8.59A
14.92%
CS6P-245P
245W
30.0V
8.17A
37.1V
8.74A
15.23%
CS6P-250P
250W
30.1V
8.30A
37.2V
8.87A
15.54%
-40 ~+85
1000V (IEC) /600V (UL)
15A
Class A
0 ~ +5W
CS6P-230P
167W
27.0V
6.18A
33.8V
6.76A
CS6P-235P
170W
27.2V
6.27A
33.9V
6.86A
CS6P-240P
174W
27.3V
6.38A
34.0V
6.96A
CS6P-245P
178W
27.4V
6.49A
34.1V
7.08A
CS6P-250P
181W
27.5V
6.60A
34.2V
7.19A
Poly-crystalline 156 x 156mm, 2 or 3 Busbars
60 (6 x 10)
1638 x 982 x 40mm (64.5 x 38.7 x 1.57in)
20kg (44.1 lbs)
3.2mm Tempered glass
Anodized aluminium alloy
IP65, 3 diodes
4mm (IEC)/12AWG(UL), 1100mm
MC4 or MC4 Comparable
24pcs
672pcs (40'HQ)
2
The Enphase Energy Microinverter
System improves energy harvest,
increases reliability, and dramatically
simplifies design, installation and
management of solar power systems.
The Enphase System includes the
microinverter, the Envoy Communications
Gateway, and Enlighten, Enphase’s
monitoring and analysis software.
M 2 1 5 — M I C R O I N V E R T E R
enphase.com
P R O D U C T I V E
R E L I A B L E
- Maximum energy production - Resilient to dust, debris and shading- Performance monitoring per module
- System availability greater than 99.8%
- No single point of system failure
S M A R T
S A F E
- Quick and simple design, installation and management- 24/7 monitoring and analysis
- Low voltage DC- Reduced fire risk
Pairs with most 60-cell PV modulesPower line25-year limited warrantyFree lifetime monitoring via Enlighten softrwareUL1741/IEEE1547, FCC Part 15 Class BCAN/CSA-C22.2 NO. 0-M91, 0.4-04, and 107.1-01
Output Data (AC)Maximum output powerNominal output currentNominal voltage/rangeNominal frequency/rangeExtended frequency rangePower FactorMaximum units per 20A branch circuitMaximum output fault current
Recommended input power (STC)Maximum input DC voltagePeak power tracking voltageOperating rangeMin./Max. start voltageMax. DC short circuit currentMax. input current
CEC weighted efficiencyPeak inverter efficiencyStatic MPPT efficiency (weighted, reference EN50530)Dynamic MPPT efficiency (fast irradiation changes, reference EN50530)Night time power consumption
Efficiency
M215 — MICROINVERTER TECHNICAL DATAInput Data (DC) M215-60-2LL-S22/S23 and M215-60-2LL-S22-NA/S23-NA (Ontario)
190 - 260W45V22V - 36V16V - 36V26.4V/45V15A10.5A
215W1.0A (arms at nominal duration)
208V/183-229V60.0/59.3-60.5 Hz60.0/59.2-60.6 Hz>0.9525 (three phase)1.05 Arms, over 3 cycles; 25.2 Apeak, 174ms duration
215W0.9A (arms at nominal duration)
240V/211-264V60.0/59.3-60.5 Hz60.0/59.2-60.6 Hz>0.9517 (single phase)
96.0%96.3%99.6%99.3%46mW
Mechanical Data
-40ºC to + 65ºC-40ºC to + 85ºC17.3 cm x 16.4 cm x 2.5 cm (6.8” x 6.45” x 1.0”)*1.6 kg (3.5 lbs)Natural convection - No fansOutdoor - NEMA 6
Ambient temperature rangeOperating temperature range (internal)Dimensions (WxHxD)WeightCoolingEnclosure environmental rating
Features
CompatibilityCommunicationWarrantyMonitoringCompliance
@208 Vac @240 Vac
142-00010 Rev 02Enphase Energy, Inc.201 1st StreetPetaluma, CA 94952Phone: 877-797-4743Fax: [email protected]://www.enphase.com
* without mounting bracket
SPECIFICATION SHEET
936 Detroit Ave, Suite D, Concord, Ca. 94518
Phone: (925) 687-6686 Fax: (925) 687-6689
Email: [email protected] www.quickmountpv.com
Quick Mount PV ™ is an all-in-one waterproof flashing and mount to anchor photovoltaic
racking systems, solar thermal panels, air conditioning units, satellite dishes, or anything
you may need to secure to a new or existing roof. It is made in the USA of all aluminum
and includes stainless steel hardware. It works with all standard racks, installs
seamlessly and saves labor by not needing to cut away any roofing, will out live
galvanized 2 to 1, and is a better low-profile mount.
Lag pull-out (withdrawal) capacities (lbs) in typical lumber:
Lag screw specifications
Specific 5/16” shaft* 5/16” shaft*
gravity 3” thread depth per 1” thread depth
Douglas Fir, Larch .50 798 266
Douglas Fir, South .46 705 235Engelmann Spruce, Lodgepole Pine
(MSR 1650 f & higher) .46 705 235Hem, Fir .43 636 212
Hem, Fir. (North) .46 705 235Southern Pine .55 921 307
Spruce, Pine, Fir .42 615 205Spruce, Pine, Fir
(E of 2 million psi and highergrades of MSR and MEL) .50 798 266
Sources: Uniform Building Code; American Wood CouncilNotes: 1) Thread must be embedded in a rafter or other structural roof member.
2) Pull-out values incorporate a 1.6 safety factor recommended by the American Wood Council. 3) See UBC for required edge distances.*Use flat washers with lag srews.
(2)
Hex Nuts5/16”
Patent Pending
Flat Washer (B) 1” x 5/16”
Rubber Gasket 60 Durometer EPDM
Sealing Washer (A) 3/4” x 5/16”
Hanger Bolt 5/16” x 6”
1-1/2” Machine, 1-1/2” Spacer, 3” Lag
Mount & Flashing Aluminum
Mount 2-1/4”l x 1-1/4”w x 1-1/4”h
Flashing .05” thick.
For standard composition roofs: flashing is 12”
x 12”, mount is attached 3” off center. For
shake roofs: flashing is 18” x 18”, mount is
attached 6” off center.
10-2007[SPECSHT]
(9
25
) 6
87
-66
86
ww
w.q
uic
km
ou
ntp
v.c
om
TO
OLS
NEED
ED
Measuring t
ape,
roofe
r’s
1.
LO
CA
TE R
AFTER
2.
DR
ILL P
ILO
T H
OLE
Usin
g
3.
LIFT T
ILE
4.
SEA
L H
OLE U
sin
g
5.
SLID
E Q
UIC
K M
OU
NT
IN
TO
PLA
CE
6.
SET H
AN
GER
BO
LT,
SEA
LIN
G W
AS
HER
&
NU
T
7.
AD
D R
UB
BER
G
AS
KET
8.
SEC
UR
E R
AC
K I
NTO
P
LA
CE,
WITH
FLA
T
WA
SH
ER
& N
UT
NU
T
NU
T
BLA
CK
GA
SK
ET
HA
NG
ER
BO
LT
FLA
T W
AS
HER
SEA
LIN
G W
AS
HER
QU
IC
K M
OU
NT
FLA
SH
IN
GA
ND
BLO
CK
PATEN
T P
EN
DIN
G
IN
STA
LLA
TIO
NIN
STR
UC
TIO
NS
R
Page 1 of 10
October 28, 2008 Mr. Stewart Wentworth Project Number 108443C QUICK MOUNT PV ICC-ES FILE # 08-09-16 1483 67th Street Emeryville, CA 94608 Subject: Quick Mount PV Load Testing ICC-ES AC13 & ASTM D 1761 Dear Mr. Wentworth: As requested, Applied Materials & Engineering, Inc. (AME) has completed load-testing Quick Mount PV system anchors for shear and tensile strength. The purpose of our testing was to evaluate the tensile and shear load capacity of the Quick Mount PV system in a high density (Douglas Fir) and a low density wood (Cedar). SAMPLE DESCRIPTION Twelve (12) 12"x12" samples were delivered to our laboratory on 10-16-08; six each for Douglas Fir and Cedar. A copy of the installation instructions is provided in Appendix A. Typical sample photo is provided in Appendix B. PROCEDURES & RESULTS Since an acceptance criterion (AC) has not been developed for this product, the samples were tested under the direction of Mr. Yamil Moya, P.E. with ICC-ES, and in general accordance with applicable procedures outlined in ASTM D 1761 and AC13.
a. Tensile Strength Three samples each of the two types of wood were tested for tensile strength on October 24 & 27, 2008 using a United Universal testing machine. Samples were rigidly attached to the testing machine and a tensile load was applied to the 5/16"x6" hanger bolt at a displacement rate 0.1 inches per minute without shock until failure. Detailed results are provided in Table I. Based on these results, the average tensile strength of the hanger bolt in Douglas Fir and Cedar wood species were determined to be 3934 lbs and 2214 lbs, respectively.
Page 3 of 10
TABLE I
QUICK MOUNT PV- 5/16"X6" HANGER (LAG) BOLT TENSILE LOAD TEST RESULTS
PROJECT NUMBER 108443C
SAMPLE ID WOOD SPECIES ULTIMATE LOAD IN TENSION (LBS) FAILURE MODE
T-DF-1 Douglas Fir 3963 Lag bolt pulled out
T-DF-2 Douglas Fir 4074 Lag bolt pulled out
T-DF-3 Douglas Fir 3764 Lag bolt pulled out
Average 3934
T-C-1 Cedar 2096 Lag bolt pulled out
T-C-2 Cedar 2004 Lag bolt pulled out
T-C-3 Cedar 2543 Lag bolt pulled out
Average 2214
Page 4 of 10
TABLE II
QUICK MOUNT PV- 5/16"X6" HANGER (LAG) BOLT SHEAR LOAD TEST RESULTS
PROJECT NUMBER 108443C
SAMPLE ID WOOD SPECIES ULTIMATE LOAD IN SHEAR (LBS) FAILURE MODE
S-DF-1 Douglas Fir 4306 Bent lag bolt
S-DF-2 Douglas Fir 3990 Bent lag bolt
S-DF-1(A) Douglas Fir 4799 Bent lag bolt
Average 4365
S-C-1 Cedar 3214 Bent lag bolt
S-C-2 Cedar 3456 Bent lag bolt
S-C-3 Cedar 3268 Bent lag bolt
Average 3313
Page 5 of 10
FIGURE I
QUICK MOUNT PV LOAD TEST SETUP
PROJECT NUMBER 108443C
a. Shear Test b. Tension Test
Page 6 of 10
FIGURE 2
QUICK MOUNT PV TYPICAL FAILURE MODE
PROJECT NUMBER 108443C
a. Shear Failure
a. Tension Failure
Roof Mounts
Splices (Internal)
· C
· Do
IronRidge Standard Rail
· Engineered p
· Ca
· A
IronRidge Light Rail
· Li
· Ca
IronRidge Standard Rails L
IronRidge Roof Mount System
Key Features
Longest Spans In The Industry Means
Backed By Industry Leading Warranty
Universal Clamping Components
Best Customer Service And Support
Solar Mounting Made Simple
IronRidge Roof Mounts arethe highest quality and fastest system for solar panel installers. Our customersappreciate the professional appearance found exlusively with IronRidge rail profiles.
*
· A
· A
· a
· Tilt s
Clamps
·
· M
· or t-bolt
· stainless steel
Wire Clips
Ac
Solar Mounting Made Simple
88
Maximum Span Chart: IronRidge Standard Rail
8
IronRidge Light Rail
· Video Tutorials·····
Single Sourcea
C - Customer
Why IronRidge
Sales: 800-227-9523
Application Note
Copyright Enphase Energy, Inc. 2010 Rev 3 Last Updated 06/22/10
Compatible Racking Makes/Models for Mounting
Enphase Microinverters
Purpose
This document is not intended to be an exclusive list of racking manufacturers. It lists products that have been verified either through field installations or the evaluation of
actual racking samples in the Enphase mechanical lab. Section 1 lists products that work
without modification, using the racking manufacturer’s standard hardware. Section 2
includes products that are known to work after modification or by adding a custom
adapter. Section 3 lists manufacturers that are shipping the Enphase Microinverter as part of a factory assembled proprietary racking/module solution.
Grounding Options
The ground clamp provided on the mounting flange of the Enphase Microinverter accepts
#10 through #6 AWG grounding electrode conductors. As an alternative to installing a continuous grounding electrode conductor connected to each Microinverter chassis, a
grounding washer may be used to ground the Microinverter to grounded racking.
CSA recently completed the evaluation and approval of the Wiley Electronics “WEEB”
grounding washers for use with the Enphase Microinverter. Where the compatible
racking models have listed grounding washers available, the Wiley Electronics part numbers have been included in the tables below.
Section 1 - No Modification Required
AEE
Module Rail Fastener Information Grounding Washer
SnapNRack Slide nut with 5/16 hex head
bolt
WEEB-PMC
Conergy
Module Rail Fastener Information Grounding Washer
Suntop Quickstone slide nut with M8
socket head cap screw
WEEB-CMC
Direct Power and Water
Module Rail Fastener Information Grounding Washer
Power Rail ¼” hex head bolt, washer,
nut, for top rail mount
WEEB-DMC
Copyright Enphase Energy Inc. 2010 Rev 3 Last Updated 06/22/10
IronRidge
Module Rail Fastener Information Grounding Washer
Light Rail XRL ¼” hex head bolt, washer,
nut, for top rail mount
WEEB-DMC
Standard Rail XRS ¼” hex head bolt, washer,
nut, for top rail mount
WEEB-DMC
Krannich Solar
Module Rail Fastener Information Grounding Washer
K2 Systems Slide nut with M8 socket head
cap screw
WEEB-KMC
mounts4solar
Module Rail Fastener Information Grounding Washer
Rail 6.0 M8 SS Hammer Head Bolt
NCP Solar
Module Rail Fastener Information Grounding Washer
Slide nut with 5/16” socket
head cap screw
WEEB-11.5
ProSolar
Module Rail Fastener Information Grounding Washer
Rooftrac Slide nut with 5/16” hex head
bolt
WEEB-PMC
Schuco
Module Rail Fastener Information Grounding Washer
SolarEZ ezUniversal Screws (M8x14)
ezAnchor Blocks
WEEB-SMC