ARRAY1 STRING1: 14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES 28 EA CANADIAN SOLAR CS6P250P MODULES 102.22 FT; R =4O5' PROP ERTY LINE ELLEN DRIVE 14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES ARRAY2 STRING2: 14 EA CANADIAN SOLAR CS6P250P MODULES ARRAY2/ARRAY3/ARRAY4 STRING3: 14 EA CANADIAN SOLAR CS6P250P MODULES 62 FT; R=175' PROPERTY LINE 119 FT PROPERTY LINE 500 FT PROPERTY LINE MSP, DC/AC DISCONNECT & MONITORING ITRON METER LOCATION AZIMUTH 225°+/(TRUE SOUTH=180°) ON 18° ROOF SLOPE; ROOF MOUNTED FLUSHED 14 EA. ENPHASE 215W @ 240V MICROINVERTERS: M215602LL 17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP250P 17 EA. ENPHASE 215W @ 240V MICROINVERTERS: M215602LL 8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP250P 8 EA. ENPHASE 215W @ 240V MICROINVERTERS: M215602LL AZIMUTH 315°+/(TRUE SOUTH=180°) ON 18° ROOF SLOPE; ROOF MOUNTED FLUSHED 3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP250P 3 EA. ENPHASE 215W @ 240V MICROINVERTERS: M215602LL AZIMUTH 135°+/(TRUE SOUTH=180°) ON 18° ROOF SLOPE; ROOF MOUNTED FLUSHED ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/(TRUE SOUTH=180°) Sunmodule Protectt SW 270 mono 14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES: Outside Face Wall Line 1 SOL02 APN: 16425405 SITE PLAN 1 SCALE = NONE G R I D - T I E D P V S Y S T E M A B D O U L I E M A N N E H , A s s o c . A I A SCALE: DRAWN BY: SYSTEM TYPE ENGINEER: REV: DATE: S O L - 0 1 NTS 0 1 0 2 3 2 0 1 3 DRAWING NUMBER: DRAWING DESCRIPTION: S I T E P L A N N SITE ADDRESS: PROJECT NAME: OWNER NAME: 287 ELLEN DRIVE SAN RAFAEL, CA94903-1602 APN: 164-254-05 DUBEN, RONALD BOX 6162, SANTA ROSA, CA 95401 PH: 7075287652 FAX: 7075286865 CA LIC# 939082 GENERAL CONTRACTOR: NORTHERN PACIFIC POWER SYSTEMS
Transcript

ARRAY1 ‐ STRING1:

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28  EA  CANADIAN SOLAR CS6P‐250P MODULES

102.22 FT; R=4O5'

PROPERTY LINE

ELLEN DRIVE

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULESARRAY2 ‐ STRING2: 14  EA  CANADIAN SOLAR CS6P‐250P MODULESARRAY2/ARRAY3/ARRAY4 ‐ STRING3: 14  EA  CANADIAN SOLAR CS6P‐250P MODULES

62 FT; R=175'

PROPERTY LINE

119 FT

PROPERTY LINE

500 FT

PROPERTY LINE

MSP, DC/AC DISCONNECT& MONITORING ITRONMETER LOCATION

AZIMUTH 225°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

14 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P17 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P8 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

AZIMUTH 315°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P3 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

AZIMUTH 135°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/‐ (TRUE SOUTH=180°)

 Sunmodule Protectt SW 270 mono14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES: 

Outside Face Wall Line

1SOL‐02

APN: 164‐254‐05

SITE PLAN1SCALE = NONE

GRID-TIED PV SYSTEM

ABDOULIE MANNEH, Assoc. AIA

SCALE:

DRAWN BY:

SYSTEM TYPE

ENGINEER:

REV: DATE:

SOL-01

NTS

0 10‐23‐2013

DRAWING NUMBER:

DRAWING DESCRIPTION:

SITE PLAN

N

SITE ADDRESS:

PROJECT NAME:

OWNER

 NAME:

287

ELL

EN

DR

IVE

SA

N R

AFA

EL,

CA

9490

3-16

02A

PN: 1

64-2

54-0

5

DU

BEN

, RO

NA

LDBOX 61

62, SANTA

 ROSA

, CA 954

01PH

: 707

‐528

‐765

2FA

X: 707

‐528

‐686

5CA

 LIC# 93

9082

GEN

ERAL CONTR

ACTO

R:

NORTH

ERN PACIFIC PO

WER

 SYSTEMS

abe
Typewritten Text
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Approved

TYPICAL ELEVATION1SCALE = NTS

GRID-TIED PV SYSTEM

ABDOULIE MANNEH, Assoc. AIA

SCALE:

DRAWN BY:

SYSTEM TYPE

ENGINEER:

REV: DATE:

SOL-02

NTS

0

DRAWING NUMBER:

DRAWING DESCRIPTION:

TYPICAL ELEVATION

5/16"X3" LAG BOLT

2X6 @ 16" O/CLOAD BEARING WALL

2X6 @ 16" O/CLOAD BEARING WALL

2X6 @ 16" O/C

TRANSPARENT SOLAR MODULES

SOLAR MODULES

LOAD BEARING WALL6x6 D.F. #1 POST W/ PC66 CAP TYP.

3X8 D.F. TRELLIS FRAMING @ 24" O.C

6X8 D.F. #1 HDR

Ground Leve'

IRONRIDG

E END / M

IDCLIPS

IRONRIDG

E XRL STAN

DARD

RAILS AND

 CLAMPS

QUICKMOUN

T PV

COMP. FO

OTINGS

5/16"X3" 

LAG BOLT

ANGLE CO

NNECTOR

2X4 Truss Rafter @ 24" O/C

SOLAR MODULES

A

SITE ADDRESS:

PROJECT

 NAME:

OWNER

 NAME:

287

ELLE

N D

RIV

ES

AN

RA

FAE

L, C

A94

903-

1602

APN

: 164

-25 4

-05

DU

BEN

, RO

NA

LD

5/16"X3" LAG BOLT

IRONRIDGE END / MIDCLIPS

IRONRIDGE XRL STANDARDRAILS AND CLAMPS

QUICKMOUNT PVTrellis FOOTINGS:

ANGLE CONNECTOR

3X8 D.F. TRELLIS FRAMING @ 24" O.C  on  6X8 D.F. #1 HDR on  6x6 D.F. #1 POST W/ PC66 CAP TYP.

TRANSPARENT SOLAR MODULES

10‐23‐2013

BOX 6162, SANTA

 ROSA

, CA 954

01PH

: 707

‐528

‐765

2FA

X: 707

‐528

‐686

5CA

 LIC# 93

9082

GEN

ERAL CONTR

ACTO

R:

NORTH

ERN PACIFIC PO

WER

 SYSTEMS

abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Approved

PV ARRAY

SITE ADDRESS:

PROJECT NAME:

SCALE:

DRAWN BY:

SYSTEM TYPE

ENGINEER:

REV: DATE:

SOL‐03

OWNER

 NAME:

DRAWING NUMBER:

DRAWING DESCRIPTION:

GRID-TIED PV SYSTEM

ABDOULIE MANNEH, Assoc. AIA

NTS

0

LAYOUT

287

ELL

EN

DR

IVE

SA

N R

AFA

EL,

CA

9490

3-16

02A

PN: 1

64-2

54-0

5

DU

BEN

, RO

NA

LD

Outside Face Wall Line

ARRAY1 ‐ STRING1:

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28  EA  CANADIAN SOLAR CS6P‐250P MODULES

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULESARRAY2 ‐ STRING2: 14  EA  CANADIAN SOLAR CS6P‐250P MODULESARRAY2/ARRAY3/ARRAY4 ‐ STRING3:14  EA  CANADIAN SOLAR CS6P‐250P MODULES

MSP, DC/AC DISCONNECT& MONITORING ITRONMETER LOCATION

AZIMUTH 225°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

14 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P17 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P8 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

AZIMUTH 315°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P3 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

AZIMUTH 135°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/‐ (TRUE SOUTH=180°)

 Sunmodule Protectt SW 270 mono14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES: 

ROOF RIDE

ROOF EAVE

3/4" EMT

1/2" EMT

VENT

VENT VENT

1SO

L‐02

PV ARRAY LAYOUT1SCALE: NTS

N 10‐23‐2013

BOX 61

62, SANTA

 ROSA

, CA 954

01PH

: 707

‐528

‐765

2FA

X: 707

‐528

‐686

5CA

 LIC# 93

9082

GEN

ERAL CONTR

ACTO

R:

NORTH

ERN PACIFIC PO

WER

 SYSTEMS

abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight

PV FOOTING

SCALE:

DRAWN BY:

SYSTEM TYPE

ENGINEER:

REV: DATE:

SOL‐04DRAWING NUMBER:

DRAWING DESCRIPTION:

GRID-TIED PV SYSTEM

ABDOULIE MANNEH, Assoc. AIA

NTS

0

LAYOUT

Outside Face Wall Line

ARRAY1 ‐ STRING1:

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28  EA  CANADIAN SOLAR CS6P‐250P MODULES

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES

ARRAY2 ‐ STRING2: 14  EA  CANADIAN SOLAR CS6P‐250P MODULES

ARRAY2/ARRAY3/ARRAY4 ‐ STRING3:14  EA  CANADIAN SOLAR CS6P‐250P MODULES

MSP,DC/AC DISCONNECT& MONITORING ITRONMETER LOCATIONAZIMUTH 225°+/‐ (TRUE SOUTH=180°)

ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P17 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P8 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

AZIMUTH 315°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P3 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

AZIMUTH 135°+/‐ (TRUE SOUTH=180°)ROOF MOUNTED FLUSHED 

14 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

ON 18° ROOF SLOPE;

ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/‐ (TRUE SOUTH=180°)

 Sunmodule Protectt SW 270 mono14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES: 

ROOF RIDGE

QTY. TOTAL= 62

QUICKMOUNT PVCOMP. FOOTINGS5/16"X3" LAG BOLT

2x4 TRUSS @ 24" O/C

2x4 T

RUSS @

 24" O

/C

2x4 T

RUSS @

 24" O

/C

ROOF EAVE

VENT

VENTVENT

6x6 D.F. #1 POST W/ PC66 CAP TYP.

6X8 D.F. #1 HDR

3X8 D.F. TRELLIS FRAMING @ 24" O.C1

SOL‐02

PV RACKING LAYOUT1SCALE: NTS

N

A

SITE ADDRESS:

PROJECT NAME:

OWNER

 NAME:

287

ELL

EN

DR

IVE

SA

N R

AFA

EL,

CA

9490

3-16

02A

PN: 1

64-2

54-0

5

DU

BEN

, RO

NA

LD

10‐23‐2013

BOX 61

62, SANTA

 ROSA

, CA 954

01PH

: 707

‐528

‐765

2FA

X: 707

‐528

‐686

5CA

 LIC# 93

9082

GEN

ERAL CONTR

ACTO

R:

NORTH

ERN PACIFIC PO

WER

 SYSTEMS

abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Approved

PV RACKING

SCALE:

DRAWN BY:

SYSTEM TYPE

ENGINEER:

REV: DATE:

SOL‐05DRAWING NUMBER:

DRAWING DESCRIPTION:

GRID-TIED PV SYSTEM

ABDOULIE MANNEH, Assoc. AIA

NTS

0

LAYOUT

Max Cantilver Recommended is 1'8"

Outside Face Wall Line

ARRAY1 ‐ STRING1:

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28  EA  CANADIAN SOLAR CS6P‐250P MODULES

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES: MUNTED ON TRELLIS

ARRAY2 ‐ STRING2: 14  EA  CANADIAN SOLAR CS6P‐250P MODULES: MOUNTED ON ROOF COMP.

ARRAY2/ARRAY3/ARRAY4 ‐ STRING3:14  EA  CANADIAN SOLAR CS6P‐250P MODULES: MOUNTED ON ROOF COMP>

MSP, DC/AC DISCONNECT& MONITORING ITRONMETER LOCATION

ROOF RIDE

ROOF EAVE

QTY. TOTAL= 62

QUICKMOUNT PVCOMP. FOOTINGS5/16"X3" LAG BOLT

IRON RIDGE RAIL 

RAIL SPLICE

RAIL SPLICE

RAIL SPLICEIRON RIDGE RAIL 

ARRAY 1: ON TRELLIS

ARRAY 2: ON ROOF A: COMP.

ARRAY 3: ON ROOF B: COMP.

ARRAY 4: ON ROOF C: COMP.

ABC

RAIL SPLICE

IRON RIDGE RAIL 

IRON 

RAIL RIDGE 

2x4 TRUSS @ 24" O/C

2x4 T

RUSS @

 24" O

/C

2x4 T

RUSS @

 24" O

/C

3X8 D.F. TRELLIS FRAMING @ 24" O.C

6x6 D.F. #1 POST W/ PC66 CAP TYP.

6X8 D.F. #1 HDR

1SO

L‐02

NPV RACKING LAYOUT1SCALE: NTS

ARRAY3 ‐ ROOF C: COMP.

MODULE WEIGHT:

MODULE LENGTH:

MODULE WIDTH:

MODULE DEPTH:

TOTAL MODULES:

SUM= MODULES WEIGHT:

INSTALLATION WEIGHT:

INSTALLATION AREA:

POINT QTY / AVG LOAD:

41.9 LBS

64.5 INCHES

38.7 INCHES

1.57 INCHES

335.28 LBS

440.69 LBS

138.68 FT²

DISTRIBUTED LOAD:

ROOF C

8 EA.

ARRAY3 ‐ ROOF B: COMP.

MODULE WEIGHT:

MODULE LENGTH:

MODULE WIDTH:

MODULE DEPTH:

TOTAL MODULES:

SUM= MODULES WEIGHT:

INSTALLATION WEIGHT:

INSTALLATION AREA:

POINT QTY / AVG LOAD:

41.9 LBS

64.5 INCHES

38.7 INCHES

1.57 INCHES

125.73 LBS

165.26 LBS

52.00 FT²

DISTRIBUTED LOAD:

ROOF B

3 EA.

ARRAY2 ‐ ROOF A: COMP.

MODULE WEIGHT:

MODULE LENGTH:

MODULE WIDTH:

MODULE DEPTH:

TOTAL MODULES:

SUM= MODULES WEIGHT:

INSTALLATION WEIGHT:

INSTALLATION AREA:

POINT QTY / AVG LOAD:

41.9 LBS

64.5 INCHES

38.7 INCHES

1.57 INCHES

712.47 LBS

936.46 LBS

294.68 FT²

DISTRIBUTED LOAD: 3.18 LBS/FT²

36.02 LBS

ROOF A

17 EA.

ARRAY1 ‐ ON TRELLIS

MODULE WEIGHT:

MODULE LENGTH:

MODULE WIDTH:

MODULE DEPTH:

TOTAL MODULES:

SUM= MODULES WEIGHT:

SUM= MOUNTS, RAILS & MICRO‐INVERTERS

INSTALLATION WEIGHT:

INSTALLATION AREA:

POINT QTY / AVG LOAD:

46.7 LBS

65.94 INCHES

39.41 INCHES

1.22 INCHES

653.80 LBS

184.46 LBS

838.26 LBS

252.65 FT²

DISTRIBUTED LOAD: 3.32 LBS/FT²

41.91 LBS

14

MICR‐INVERTER WEIGHT:

TOTAL MICRO‐INVERTERS:

ROOF1

14 EA.

3.5 LBS

SUM= MOUNTS, RAILS & MICRO‐INVERTERS 223.99.16 LBS

17

MICR‐INVERTER WEIGHT:

TOTAL MICRO‐INVERTERS:

3.5 LBS

SUM= MOUNTS, RAILS & MICRO‐INVERTERS 39.53 LBS

3

MICR‐INVERTER WEIGHT:

TOTAL MICRO‐INVERTERS:

3.5 LBS

SUM= MOUNTS, RAILS & MICRO‐INVERTERS 105.41 LBS

8

MICR‐INVERTER WEIGHT:

TOTAL MICRO‐INVERTERS:

3.5 LBS

3.18 LBS/FT²

27.54 LBS

3.18 LBS/FT²

44.07 LBS

A

SITE ADDRESS:

PROJECT NAME:

OWNER

 NAME:

287

ELL

EN

DR

IVE

SA

N R

AFA

EL,

CA

9490

3-16

02A

PN: 1

64-2

54-0

5

DU

BEN

, RO

NA

LD

10‐23‐2013

BOX 61

62, SANTA

 ROSA

, CA 954

01PH

: 707

‐528

‐765

2FA

X: 707

‐528

‐686

5CA

 LIC# 93

9082

GEN

ERAL CONTR

ACTO

R:

NORTH

ERN PACIFIC PO

WER

 SYSTEMS

abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Approved

PV STRING

SCALE:

DRAWN BY:

SYSTEM TYPE

ENGINEER:

REV: DATE:

SOL‐06DRAWING NUMBER:

DRAWING DESCRIPTION:

GRID-TIED PV SYSTEM

ABDOULIE MANNEH, Assoc. AIA

NTS

0

LAYOUT

A

SITE ADDRESS:

PROJECT NAME:

OWNER

 NAME:

287

ELL

EN

DR

IVE

SA

N R

AFA

EL,

CA

9490

3-16

02A

PN: 1

64-2

54-0

5

DU

BEN

, RO

NA

LD

10‐23‐2013

BOX 61

62, SANTA

 ROSA

, CA 954

01PH

: 707

‐528

‐765

2FA

X: 707

‐528

‐686

5CA

 LIC# 93

9082

GEN

ERAL CONTR

ACTO

R:

NORTH

ERN PACIFIC PO

WER

 SYSTEMS

Outside Face Wall Line

ARRAY1 ‐ STRING1:

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULES28  EA  CANADIAN SOLAR CS6P‐250P MODULES

14 EA SOLAR WORLD 270 SEMI TRANSPARENT MODULESARRAY2 ‐ STRING2: 14  EA  CANADIAN SOLAR CS6P‐250P MODULESARRAY2/ARRAY3/ARRAY4 ‐ STRING3:14  EA  CANADIAN SOLAR CS6P‐250P MODULES

MSP, DC/AC DISCONNECT& MONITORING ITRONMETER LOCATION

AZIMUTH 225°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

14 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

17 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P17 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

8 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P8 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

AZIMUTH 315°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

3 EA. CANADIAN SOLAR 250W SOLAR MODULES: CSP‐250P3 EA. ENPHASE 215W @ 240V MICRO‐INVERTERS: M215‐60‐2LL 

AZIMUTH 135°+/‐ (TRUE SOUTH=180°)ON 18° ROOF SLOPE;ROOF MOUNTED FLUSHED 

ON D.F. TRELLIS FRAMING @ 24" O/C; AZIMUTH 225°+/‐ (TRUE SOUTH=180°)

 Sunmodule Protectt SW 270 mono14 EA. SOLAR WORLD Semi Transparent 270W SLAR MODULES: 

ROOF RIDE

ROOF EAVE

3/4" EMT

1/2" EMT

TYP. 6" J‐BOX

1/2" EMT

TYP. 6" J‐BOX

TYP. 6" J‐BOX

VENT

VENT VENT

1SO

L‐02

PV STRING LAYOUT1SCALE: NTS

N

abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Approved

ELECTRICAL LINE DIAGRAM1SCALE = NONE

SCALE:

DRAWN BY:

SYSTEM TYPE

ENGINEER:

REV: DATE:

SOL-07DRAWING NUMBER:

ELECTRICAL LINE

DRAWING DESCRIPTION:

GRID-TIED PV SYSTEM

ABDOULIE MANNEH, Assoc. AIA

NTS

0

DIAGRAM

SITE ADDRESS:

PROJECT NAME:

OWNER

 NAME:

287

ELL

EN

DR

IVE

SA

N R

AFA

EL,

CA

9490

3-16

02A

PN: 1

64-2

54-0

5

DU

BEN

, RO

NA

LD

PRE‐WIRED CONNECTIONS

L1L2

GN

DC IN

AC OUT

DC IN

L1L2

AC OUT

GN

END CAPS INSTALLED ON LAST INVERTER CABLEOF BRANCH CIRCUIT

ENPHASE M215+‐

G (N) J‐BOX 1

+‐

G

BRANCH CIRCUIT 3 WITH(BC3)

PRE‐WIRED ASSEMBLYENPHASE ACINTERCONNECT CABLE

L1L2

GN

DC IN

AC OUT

DC IN

L1L2

AC OUT

GN

+‐

G

+‐

G

BRANCH CIRCUIT 2 WITH(BC2)

N

(MSP1)(NEW) 200A, 120/240V SERVICE PANEL

G

METER

N G

200A

BC1, BC2 OCP =

(E) 100A

NEW SOLAR DEDICATEDINVERTER LOADCENTER

MODULES AND MICRO‐INVERTERS BONDEDTO SUPPORT RAIL VIA WEEB LUG.

CANADIAN SOLAR250W MODULE

(1) #8 AWG NEUT.(1) #8 AWG CU, GRND3/4" CONDUIT MIN.FROM ( AGAC1 ) TO ( ACDC1 )

14 ENPHASE MICRO‐INVERTERS

14 ENPHASE MICRO‐INVERTERS

(AGAC1)

(JB1)

(2) #8 AWG THHN CU

FROM ( JB1, JBL2, & JBL3) TO ( AGAC1 )3/4" EMT(1) #8 AWG CU, GRND(9) #10 AWG THWN‐2 CU

END CAPS INSTALLED ON LAST INVERTER CABLEOF BRANCH CIRCUIT

MICRO‐INVERTER

ENPHASE M215MICRO‐INVERTER

ENPHASE M215MICRO‐INVERTER

ENPHASE M215MICRO‐INVERTER

@ #12 AWG TYP.

PRE‐WIRED CONNECTIONS@ #12 AWG TYP.

PRE‐WIRED ASSEMBLYENPHASE ACINTERCONNECT CABLE

TO PG&E

2‐POLE MAINEXISTINGLOADS

2‐POLE

EA. 20A 2P

G

60A FUSES, 120/240V, 3R 1PHFUSED AC DISCO W/60A GENERAL DUTYSQUARE‐D ( D221NRB )(ACDC1)

(E) GND ROD/ GROUNDINGELECTRODE SYSTEM

(1) #8 AWG NEUT.(1) #8 AWG CU, GRND3/4" CONDUIT MIN.FROM ( ACDC1 ) TO ( SP1 )

(2) #8 AWG THHN CU

CANADIAN SOLAR250W MODULE

100A, 120/240V SUB‐PANEL

L1L2

GN

DC IN

AC OUT

DC IN

L1L2

AC OUT

GN

+‐

G

+‐

G

BRANCH CIRCUIT 1 WITH(BC1)

MODULES AND MICRO‐INVERTERS BONDEDTO SUPPORT RAIL VIA WEEB LUG.

14 ENPHASE MICRO‐INVERTERS

SOLAR WORLD 270W MODULE 

END CAPS INSTALLED ON LAST INVERTER CABLEOF BRANCH CIRCUIT

ENPHASE M215MICRO‐INVERTER

ENPHASE M215MICRO‐INVERTER

PRE‐WIRED CONNECTIONS@ #12 AWG TYP.

PRE‐WIRED ASSEMBLYENPHASE ACINTERCONNECT CABLE

(Semi-Transparent)

SOLAR WORLD 270W MODULE (Semi-Transparent)

MODULES AND MICRO‐INVERTERS BONDEDTO SUPPORT RAIL VIA WEEB LUG.

CANADIAN SOLAR250W MODULE

CANADIAN SOLAR250W MODULE

INSULATION PIERCINGWIRE TAPS W/

TAP CONNECTOR(IPS 1/O‐2 AWG OR EQUIV.)

10‐23‐2013

BOX 61

62, SANTA

 ROSA

, CA 954

01PH

: 707

‐528

‐765

2FA

X: 707

‐528

‐686

5CA

 LIC# 93

9082

GEN

ERAL CONTR

ACTO

R:

NORTH

ERN PACIFIC PO

WER

 SYSTEMS

INVERTER OUTPUT DATA:

SHALL BE PLACED ON EACHAC DISCONNECT / BREAKER 1/8" LETTERING

  LOCATED AT MAIN SERVICE POINT OF INTERCONNECTION  3/8" WHITE LETTERING ON RED BACKING

  LOCATED AT MAIN SERVICE POINT OF INTERCONNECTION  3/8" WHITE LETTERING ON RED BACKING

  SHALL BE PLACED EVERY 10'   REQUIRED ON ALL DC RACEWAYS, J‐BOXES AND ENCLOSURES  3/8" WHITE LETTERING ON RED BACKING 

SHALL BE PLACED ONAC COMBINER PANEL & AC DISCONNECT "WARNING" SHALL BE 1/4" TEXT ALL OTHER TEXT IS 1/8"

SHALL BE LOCATED NEXT TO CIRCUITBREAKER AT INTERACTIVE SYSTEM POINTOF INTERCONNECTION 1/8" WHITE

CIRUIT OUTPUT DATA:

PANEL/BUS RATING X 1.20%=

ALL COMBINED SOURCES MUST BE < OR = 240A

LETTERING ON SOLID BACKING

CIRUIT OUTPUT DATA: PER BRANCH

SHALL BE PLACED ON EACHAC DISCONNECT / BREAKER 1/8" LETTERING

BRANCH CIRCUIT 1

BRANCH CIRCUIT 2

 Sunmodule Protectt SW 270 mono

CAUTION: SOLAR CIRCUIT

CAUTION: SOLAR ELECTRICSYSTEM CONNECTED

PV SYSTEM DISCONNECTFOR UTILITY OPERATION

PHOTOVOLTAIC DISCONNECTFOR UTILITY USE

       OPERATING CURRENT:OPERATING VOLTAGE: 240 V

WARNING:ELECTRIC SHOCK HAZARD.DO NOT TOUCH TERMINALS.

TERMINALS ON BOTH THE LINEAND LOAD SIDES MAY BE ENERGIZED IN

THE OPEN POSITION.

WARNING:INVERTER OUTPUT CONNECTION

DO NOT RELOCATE THISOVERCURRENT DEVICE

15.3 A

PHOTOVOLTAIC DISCONNECTFOR UTILITY USE

       OPERATING CURRENT:OPERATING VOLTAGE: 240 V

14.4 A

MODULE SPECIFICATIONBRAND

TYPE

# OF MODULES

Voc

Vmp

Isc

Imp

CANADIAN SOLAR

CS6P‐250P

28

37.2 V

30.1 V

8.87 A

8.30 A

INVERTER SPECIFICATIONBRAND

TYPE

ENPHASE M215 MICROINVERTER

M215‐60‐2LL

AC MAXIMUM OUTPUT POWER=

AC NOMINAL VOLTAGE RANGE=

AC FREQUENCY RANGE= 60Hz

POWER FACTOR @ FULL LOAD= > 0.95

215W @ 240V

AC MAXIMUM OUTPUT CURRENT= .9A @ 240V

DISCRIPTION 250W SOLAR MODULE

17 UNITS MAX PER CIR.

211‐264V AC

BRANCH CIRCUIT 1INVERTER QTY.

AC COMBINED OUTPUT POWER=

AC COMBINED OUTPUT CURRENT=

TOTAL POWER kW=

TOTAL OUTPUT CURRENT= 37.8A X 1.25= 47.25A 

TOTAL INVERTER QTY=

9,030W @ 240V

SOLAR SOURCE SELECTED OCPD=

200A

BC1, BC2, BC3; EA. 20A 2‐P

PG&E SOURCE BREAKER SIZE=

INTERCONNECTION LOCATION= LINE SIDE OF MAIN

200A

240A

PANEL/BUS RATING=

14

3,010W @ 240V

12.6A X 1.25= 15.75A 

BRANCH CIRCUIT 2 & BRANCH CIRCUIT 3INVERTER QTY.

AC COMBINED OUTPUT POWER=

AC COMBINED OUTPUT CURRENT=

14 PER BRANCH

SOLAR WORLD

39.2 V

30.9 V

9.44 A

8.81 A

270W SOLAR MODULE

14

42

3,010W @ 240V

12.6A X 1.25= 15.75A 

abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Highlight
abe
Approved
abe
Approved
abe
Approved
abe
Approved
abe
Approved

solarworld.com

Designed to withstand heavy

accumulations of snow and ice

Every component is tested to meet

3 times IEC requirements

Sunmodule Plus:

Positive performance tolerance

25-year linear performance warranty and

10-year product warranty

-0/+5 Wp

WARRANTY

TUV Power controlled:

Lowest measuring tolerance in industry

World-class qualityFully-automated production lines and seamless monitoring of the process and material ensure the quality that the company sets as its benchmark for its sites worldwide.

SolarWorld Plus-SortingPlus-Sorting guarantees highest system efficiency. SolarWorld only delivers modules that have greater than or equal to the nameplate rated power.

25 years linear performance guarantee and extension of product warranty to 10 yearsSolarWorld guarantees a maximum performance degression of 0.7% p.a. in the course of 25 years, a significant added value compared to the two-phase warranties common in the industry. In addition, SolarWorld is offering a product warranty, which has been extended to 10 years.*

*in accordance with the applicable SolarWorld Limited Warranty at purchase.www.solarworld.com/warranty

Plus SW 270 mono

SW-01-6004US 08-2013

1) Measuring tolerance (Pmax

) traceable to TUV Rheinland: +/- 2% (TUV Power Controlled).

THERMAL CHARACTERISTICS

NOCT 46 °C

TC Isc

0.004 %/K

TC Voc

-0.30 %/K

TC Pmpp

-0.45 %/K

Operating temperature -40°C to 85°C

PERFORMANCE AT 800 W/m², NOCT, AM 1.5

Maximum power Pmax

201.3 Wp

Open circuit voltage Voc

35.9 V

Maximum power point voltage Vmpp

28.3 V

Short circuit current Isc

7.63 A

Maximum power point current Impp

7.12 A

Minor reduction in efficiency under partial load conditions at 25°C: at 200 W/m², 100% (+/-2%) of the STC efficiency (1000 W/m²) is achieved.

COMPONENT MATERIALS

Cells per module 60

Cell type Mono crystalline

Cell dimensions 6.14 in x 6.14 in (156 mm x 156 mm)

Front Tempered glass (EN 12150)

Frame Clear anodized aluminum

Weight 46.7 lbs (21.2 kg)

ADDITIONAL DATA

Power sorting1 -0 Wp / +5 Wp

J-Box IP65

Connector MC4

Module efficiency 16.10 %

Fire rating (UL 790) Class C

SYSTEM INTEGRATION PARAMETERS

Maximum system voltage SC II 1000 V

Max. system voltage USA NEC 600 V

Maximum reverse current 16 A

Number of bypass diodes 3

UL Design Loads* Two rail system113 psf downward

64 psf upward

UL Design Loads* Three rail system170 psf downward

64 psf upward

IEC Design Loads* Two rail system113 psf downward

50 psf upward

* Please refer to the Sunmodule installation instructions for the details associated with these load cases.

PERFORMANCE UNDER STANDARD TEST CONDITIONS (STC)*

Maximum power Pmax

270 Wp

Open circuit voltage Voc

39.2 V

Maximum power point voltage Vmpp

30.9 V

Short circuit current Isc

9.44 A

Maximum power point current Impp

8.81 A

*STC: 1000 W/m², 25°C, AM 1.5

Independently created PAN files now available.Ask your account manager for more information.

NEW!

Plus SW 270 mono

All units provided are imperial. SI units provided in parentheses. SolarWorld AG reserves the right to make specification changes without notice.

Mo

du

le c

urr

ent

[A]

Module voltage [V]

1000 W/m²

800 W/m²

600 W/m²

400 W/m²

200 W/m²

100 W/m²

ISC

VOC

CS6P is a robust solar module with 60 solar

cells. These modules can be used for on-grid

solar applications. Our meticulous design and

production techniques ensure a high-yield,

long-term performance for every module

produced. Our rigorous quality control and

in-house testing facilities guarantee Canadian

Solar's modules meet the highest quality

standards possible.

CS6P

On-grid Module

On-grid residential roof-tops

On-grid commercial/industrial roof-tops

Solar power stations

Other on-grid applications

Applications

www.canadiansolar.com

IEC 61215, IEC 61730, UL1703, CEC Listed,

CE and MCS

ISO9001: 2008: Standards for quality

management systems

ISO/TS16949:2009: The automotive quality

management system

Quality Certificates

Key Features

Top ranked PVUSA (PTC) rating in California for higher

energy production

Industry first comprehensive warranty insurance by

AM Best rated leading insurance companies in the world

Industry leading plus only power tolerance: 0 ~ +5W

Strong framed module, passing mechanical load test

of 5400Pa to withstand heavier snow load

The 1st manufacturer in the PV industry certified for

ISO:TS16949 (The automotive quality management

system) in module production since 2003

ISO17025 qualified manufacturer owned testing lab,

fully complying to IEC, TUV, UL testing standards

ISO14001:2004: Standards for Environmental

management systems

QC080000 HSPM: The Certification for

Hazardous Substances Regulations

Environmental Certificates

10 year product warranty on materials and workmanship

25 year linear power output warranty

Backed By Our New 10/25 Linear Power Warranty Plus our added 25 year insurance coverage

5 10 15 20 250%

80%

90%

97%100%

Added Value From Warranty

230/235/240/245/250P

2Under Standard Test Conditions (STC) of irradiance of 1000W/m , spectrum AM 1.5 and cell temperature of 25

*Specifications included in this datasheet are subject to change without prior notice.

Engineering Drawings

I-V Curves (CS6P-250P)

Temperature Coefficient

About Canadian Solar

Headquarters | 650 Riverbend Drive, Suite BKitchener, Ontario | Canada N2K 3S2Tel: +1-519-954-2057Fax: [email protected]

CS6P-230/235/240/245/250PElectrical Data

Pmax

Voc

Isc

-0.43

-0.34 %/

0.065 %/

45 2

%/

Temperature Characteristics

NOCT

Nominal Maximum Power (Pmax)

Optimum Operating Voltage (Vmp)

Optimum Operating Current (Imp)

Open Circuit Voltage (Voc)

Short Circuit (Isc)Current

2Under Normal Operating Cell Temperature, Irradiance of 800 W/m , spectrum AM 1.5, ambient temperature 20 , wind speed 1 m/s

Performance at Low Irradiance

Normal Operating Cell Temperature

Mechanical DataCell Type

Cell Arrangement

Dimensions

Weight

Front Cover

Frame Material

J-BOX

Cable

Connectors

Standard Packaging (Modules per Pallet)

Module Pieces per container (40 ft . Container)

Industry leading performance at low irradiation

environment, +95.5% module efficiency from an 2 2

irradiance of 1000w/m to 200w/m

(AM 1.5, 25 )

EN-Rev 3.39 Copyright 2011 Canadian Solar Inc.

Canadian Solar Inc. is one of the world's largest solar

c o m p a n i e s . A s a l e a d i n g v e r t i c a l l y - i n t e g r a t e d

manufacturer of ingots, wafers, cells, solar modules and

solar systems. Canadian Solar delivers solar power

products of uncompromising quality to worldwide

customers. Canadian Solar's world class team of

professionals works closely with our customers to

provide them with solutions for all their solar needs.

STC

Nominal Maximum Power (Pmax)

Optimum Operating Voltage (Vmp)

Optimum Operating Current (Imp)

Open Circuit Voltage (Voc)

Short Circuit (Isc)

Module Efficiency

Operating Temperature

Maximum System Voltage

Maximum Series Fuse Rating

Application Classification

Power Tolerance

Current

Canadian Solar was founded in Canada in 2001 and was

successfully listed on NASDAQ Exchange (symbol: CSIQ) in

November 2006. Canadian Solar has already expanded its

m o d u l e m a n u f a c t u r i n g c a p a c i t y t o 2 . 0 5 G W a n d c e l l

manufacturing capacity to 1.3GW in 2011.

Section B-B

Section A-A A A

BB

CS6P-230P

230W

29.6V

7.78A

36.8V

8.34A

14.30%

CS6P-235P

235W

29.8V

7.90A

36.9V

8.46A

14.61%

CS6P-240P

240W

29.9V

8.03A

37.0V

8.59A

14.92%

CS6P-245P

245W

30.0V

8.17A

37.1V

8.74A

15.23%

CS6P-250P

250W

30.1V

8.30A

37.2V

8.87A

15.54%

-40 ~+85

1000V (IEC) /600V (UL)

15A

Class A

0 ~ +5W

CS6P-230P

167W

27.0V

6.18A

33.8V

6.76A

CS6P-235P

170W

27.2V

6.27A

33.9V

6.86A

CS6P-240P

174W

27.3V

6.38A

34.0V

6.96A

CS6P-245P

178W

27.4V

6.49A

34.1V

7.08A

CS6P-250P

181W

27.5V

6.60A

34.2V

7.19A

Poly-crystalline 156 x 156mm, 2 or 3 Busbars

60 (6 x 10)

1638 x 982 x 40mm (64.5 x 38.7 x 1.57in)

20kg (44.1 lbs)

3.2mm Tempered glass

Anodized aluminium alloy

IP65, 3 diodes

4mm (IEC)/12AWG(UL), 1100mm

MC4 or MC4 Comparable

24pcs

672pcs (40'HQ)

2

The Enphase Energy Microinverter

System improves energy harvest,

increases reliability, and dramatically

simplifies design, installation and

management of solar power systems.

The Enphase System includes the

microinverter, the Envoy Communications

Gateway, and Enlighten, Enphase’s

monitoring and analysis software.

M 2 1 5 — M I C R O I N V E R T E R

enphase.com

P R O D U C T I V E

R E L I A B L E

- Maximum energy production - Resilient to dust, debris and shading- Performance monitoring per module

- System availability greater than 99.8%

- No single point of system failure

S M A R T

S A F E

- Quick and simple design, installation and management- 24/7 monitoring and analysis

- Low voltage DC- Reduced fire risk

Pairs with most 60-cell PV modulesPower line25-year limited warrantyFree lifetime monitoring via Enlighten softrwareUL1741/IEEE1547, FCC Part 15 Class BCAN/CSA-C22.2 NO. 0-M91, 0.4-04, and 107.1-01

Output Data (AC)Maximum output powerNominal output currentNominal voltage/rangeNominal frequency/rangeExtended frequency rangePower FactorMaximum units per 20A branch circuitMaximum output fault current

Recommended input power (STC)Maximum input DC voltagePeak power tracking voltageOperating rangeMin./Max. start voltageMax. DC short circuit currentMax. input current

CEC weighted efficiencyPeak inverter efficiencyStatic MPPT efficiency (weighted, reference EN50530)Dynamic MPPT efficiency (fast irradiation changes, reference EN50530)Night time power consumption

Efficiency

M215 — MICROINVERTER TECHNICAL DATAInput Data (DC) M215-60-2LL-S22/S23 and M215-60-2LL-S22-NA/S23-NA (Ontario)

190 - 260W45V22V - 36V16V - 36V26.4V/45V15A10.5A

215W1.0A (arms at nominal duration)

208V/183-229V60.0/59.3-60.5 Hz60.0/59.2-60.6 Hz>0.9525 (three phase)1.05 Arms, over 3 cycles; 25.2 Apeak, 174ms duration

215W0.9A (arms at nominal duration)

240V/211-264V60.0/59.3-60.5 Hz60.0/59.2-60.6 Hz>0.9517 (single phase)

96.0%96.3%99.6%99.3%46mW

Mechanical Data

-40ºC to + 65ºC-40ºC to + 85ºC17.3 cm x 16.4 cm x 2.5 cm (6.8” x 6.45” x 1.0”)*1.6 kg (3.5 lbs)Natural convection - No fansOutdoor - NEMA 6

Ambient temperature rangeOperating temperature range (internal)Dimensions (WxHxD)WeightCoolingEnclosure environmental rating

Features

CompatibilityCommunicationWarrantyMonitoringCompliance

@208 Vac @240 Vac

142-00010 Rev 02Enphase Energy, Inc.201 1st StreetPetaluma, CA 94952Phone: 877-797-4743Fax: [email protected]://www.enphase.com

* without mounting bracket

SPECIFICATION SHEET

936 Detroit Ave, Suite D, Concord, Ca. 94518

Phone: (925) 687-6686 Fax: (925) 687-6689

Email: [email protected] www.quickmountpv.com

Quick Mount PV ™ is an all-in-one waterproof flashing and mount to anchor photovoltaic

racking systems, solar thermal panels, air conditioning units, satellite dishes, or anything

you may need to secure to a new or existing roof. It is made in the USA of all aluminum

and includes stainless steel hardware. It works with all standard racks, installs

seamlessly and saves labor by not needing to cut away any roofing, will out live

galvanized 2 to 1, and is a better low-profile mount.

Lag pull-out (withdrawal) capacities (lbs) in typical lumber:

Lag screw specifications

Specific 5/16” shaft* 5/16” shaft*

gravity 3” thread depth per 1” thread depth

Douglas Fir, Larch .50 798 266

Douglas Fir, South .46 705 235Engelmann Spruce, Lodgepole Pine

(MSR 1650 f & higher) .46 705 235Hem, Fir .43 636 212

Hem, Fir. (North) .46 705 235Southern Pine .55 921 307

Spruce, Pine, Fir .42 615 205Spruce, Pine, Fir

(E of 2 million psi and highergrades of MSR and MEL) .50 798 266

Sources: Uniform Building Code; American Wood CouncilNotes: 1) Thread must be embedded in a rafter or other structural roof member.

2) Pull-out values incorporate a 1.6 safety factor recommended by the American Wood Council. 3) See UBC for required edge distances.*Use flat washers with lag srews.

(2)

Hex Nuts5/16”

Patent Pending

Flat Washer (B) 1” x 5/16”

Rubber Gasket 60 Durometer EPDM

Sealing Washer (A) 3/4” x 5/16”

Hanger Bolt 5/16” x 6”

1-1/2” Machine, 1-1/2” Spacer, 3” Lag

Mount & Flashing Aluminum

Mount 2-1/4”l x 1-1/4”w x 1-1/4”h

Flashing .05” thick.

For standard composition roofs: flashing is 12”

x 12”, mount is attached 3” off center. For

shake roofs: flashing is 18” x 18”, mount is

attached 6” off center.

10-2007[SPECSHT]

(9

25

) 6

87

-66

86

ww

w.q

uic

km

ou

ntp

v.c

om

TO

OLS

NEED

ED

Measuring t

ape,

roofe

r’s

1.

LO

CA

TE R

AFTER

2.

DR

ILL P

ILO

T H

OLE

Usin

g

3.

LIFT T

ILE

4.

SEA

L H

OLE U

sin

g

5.

SLID

E Q

UIC

K M

OU

NT

IN

TO

PLA

CE

6.

SET H

AN

GER

BO

LT,

SEA

LIN

G W

AS

HER

&

NU

T

7.

AD

D R

UB

BER

G

AS

KET

8.

SEC

UR

E R

AC

K I

NTO

P

LA

CE,

WITH

FLA

T

WA

SH

ER

& N

UT

NU

T

NU

T

BLA

CK

GA

SK

ET

HA

NG

ER

BO

LT

FLA

T W

AS

HER

SEA

LIN

G W

AS

HER

QU

IC

K M

OU

NT

FLA

SH

IN

GA

ND

BLO

CK

PATEN

T P

EN

DIN

G

IN

STA

LLA

TIO

NIN

STR

UC

TIO

NS

R

Page 1 of 10

October 28, 2008 Mr. Stewart Wentworth Project Number 108443C QUICK MOUNT PV ICC-ES FILE # 08-09-16 1483 67th Street Emeryville, CA 94608 Subject: Quick Mount PV Load Testing ICC-ES AC13 & ASTM D 1761 Dear Mr. Wentworth: As requested, Applied Materials & Engineering, Inc. (AME) has completed load-testing Quick Mount PV system anchors for shear and tensile strength. The purpose of our testing was to evaluate the tensile and shear load capacity of the Quick Mount PV system in a high density (Douglas Fir) and a low density wood (Cedar). SAMPLE DESCRIPTION Twelve (12) 12"x12" samples were delivered to our laboratory on 10-16-08; six each for Douglas Fir and Cedar. A copy of the installation instructions is provided in Appendix A. Typical sample photo is provided in Appendix B. PROCEDURES & RESULTS Since an acceptance criterion (AC) has not been developed for this product, the samples were tested under the direction of Mr. Yamil Moya, P.E. with ICC-ES, and in general accordance with applicable procedures outlined in ASTM D 1761 and AC13.

a. Tensile Strength Three samples each of the two types of wood were tested for tensile strength on October 24 & 27, 2008 using a United Universal testing machine. Samples were rigidly attached to the testing machine and a tensile load was applied to the 5/16"x6" hanger bolt at a displacement rate 0.1 inches per minute without shock until failure. Detailed results are provided in Table I. Based on these results, the average tensile strength of the hanger bolt in Douglas Fir and Cedar wood species were determined to be 3934 lbs and 2214 lbs, respectively.

Page 3 of 10

TABLE I

QUICK MOUNT PV- 5/16"X6" HANGER (LAG) BOLT TENSILE LOAD TEST RESULTS

PROJECT NUMBER 108443C

SAMPLE ID WOOD SPECIES ULTIMATE LOAD IN TENSION (LBS) FAILURE MODE

T-DF-1 Douglas Fir 3963 Lag bolt pulled out

T-DF-2 Douglas Fir 4074 Lag bolt pulled out

T-DF-3 Douglas Fir 3764 Lag bolt pulled out

Average 3934

T-C-1 Cedar 2096 Lag bolt pulled out

T-C-2 Cedar 2004 Lag bolt pulled out

T-C-3 Cedar 2543 Lag bolt pulled out

Average 2214

Page 4 of 10

TABLE II

QUICK MOUNT PV- 5/16"X6" HANGER (LAG) BOLT SHEAR LOAD TEST RESULTS

PROJECT NUMBER 108443C

SAMPLE ID WOOD SPECIES ULTIMATE LOAD IN SHEAR (LBS) FAILURE MODE

S-DF-1 Douglas Fir 4306 Bent lag bolt

S-DF-2 Douglas Fir 3990 Bent lag bolt

S-DF-1(A) Douglas Fir 4799 Bent lag bolt

Average 4365

S-C-1 Cedar 3214 Bent lag bolt

S-C-2 Cedar 3456 Bent lag bolt

S-C-3 Cedar 3268 Bent lag bolt

Average 3313

Page 5 of 10

FIGURE I

QUICK MOUNT PV LOAD TEST SETUP

PROJECT NUMBER 108443C

a. Shear Test b. Tension Test

Page 6 of 10

FIGURE 2

QUICK MOUNT PV TYPICAL FAILURE MODE

PROJECT NUMBER 108443C

a. Shear Failure

a. Tension Failure

Page 7 of 10

APPENDIX A

Page 8 of 10

Page 9 of 10

APPENDIX B

Page 10 of 10

Roof Mounts

Splices (Internal)

· C

· Do

IronRidge Standard Rail

· Engineered p

· Ca

· A

IronRidge Light Rail

· Li

· Ca

IronRidge Standard Rails L

IronRidge Roof Mount System

Key Features

Longest Spans In The Industry Means

Backed By Industry Leading Warranty

Universal Clamping Components

Best Customer Service And Support

Solar Mounting Made Simple

IronRidge Roof Mounts arethe highest quality and fastest system for solar panel installers. Our customersappreciate the professional appearance found exlusively with IronRidge rail profiles.

*

· A

· A

· a

· Tilt s

Clamps

·

· M

· or t-bolt

· stainless steel

Wire Clips

Ac

Solar Mounting Made Simple

88

Maximum Span Chart: IronRidge Standard Rail

8

IronRidge Light Rail

· Video Tutorials·····

Single Sourcea

C - Customer

Why IronRidge

Sales: 800-227-9523

Application Note

Copyright Enphase Energy, Inc. 2010 Rev 3 Last Updated 06/22/10

Compatible Racking Makes/Models for Mounting

Enphase Microinverters

Purpose

This document is not intended to be an exclusive list of racking manufacturers. It lists products that have been verified either through field installations or the evaluation of

actual racking samples in the Enphase mechanical lab. Section 1 lists products that work

without modification, using the racking manufacturer’s standard hardware. Section 2

includes products that are known to work after modification or by adding a custom

adapter. Section 3 lists manufacturers that are shipping the Enphase Microinverter as part of a factory assembled proprietary racking/module solution.

Grounding Options

The ground clamp provided on the mounting flange of the Enphase Microinverter accepts

#10 through #6 AWG grounding electrode conductors. As an alternative to installing a continuous grounding electrode conductor connected to each Microinverter chassis, a

grounding washer may be used to ground the Microinverter to grounded racking.

CSA recently completed the evaluation and approval of the Wiley Electronics “WEEB”

grounding washers for use with the Enphase Microinverter. Where the compatible

racking models have listed grounding washers available, the Wiley Electronics part numbers have been included in the tables below.

Section 1 - No Modification Required

AEE

Module Rail Fastener Information Grounding Washer

SnapNRack Slide nut with 5/16 hex head

bolt

WEEB-PMC

Conergy

Module Rail Fastener Information Grounding Washer

Suntop Quickstone slide nut with M8

socket head cap screw

WEEB-CMC

Direct Power and Water

Module Rail Fastener Information Grounding Washer

Power Rail ¼” hex head bolt, washer,

nut, for top rail mount

WEEB-DMC

Copyright Enphase Energy Inc. 2010 Rev 3 Last Updated 06/22/10

IronRidge

Module Rail Fastener Information Grounding Washer

Light Rail XRL ¼” hex head bolt, washer,

nut, for top rail mount

WEEB-DMC

Standard Rail XRS ¼” hex head bolt, washer,

nut, for top rail mount

WEEB-DMC

Krannich Solar

Module Rail Fastener Information Grounding Washer

K2 Systems Slide nut with M8 socket head

cap screw

WEEB-KMC

mounts4solar

Module Rail Fastener Information Grounding Washer

Rail 6.0 M8 SS Hammer Head Bolt

NCP Solar

Module Rail Fastener Information Grounding Washer

Slide nut with 5/16” socket

head cap screw

WEEB-11.5

ProSolar

Module Rail Fastener Information Grounding Washer

Rooftrac Slide nut with 5/16” hex head

bolt

WEEB-PMC

Schuco

Module Rail Fastener Information Grounding Washer

SolarEZ ezUniversal Screws (M8x14)

ezAnchor Blocks

WEEB-SMC


Recommended