Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
Property of Sto Corp.All Rights Reserved.
3800 Camp Creek Pkwy. SWBldg. 1400 • Suite 120Atlanta, GA 30331Tel: (800) 221-2397Fax: (404) 346-3119helpdesk.stocorp.com
Sto Corp.
StoVentec RenderApril 2019
Detail Booklet
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR-0011
.
Rev. no.StoVentec Rrainscreen cladding facade
≥ 10
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
Sto-Primer if necessary
A
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
H ventilation airspace in accordance with DIN 18516-1 – H ≥ 20 mm; recommendation for the planning of the facade: H ≥ 30 mm
anchoring element inaccordance with structuralanalysis
Sto-Stainless Steel Wall Bracket in accordancewith the structural analysisA
≥ 10
≥ 25
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
.12H E
Sto-Insulation Dowel orSto-Insulation Dowel DH
length of the wall bracket (see VR-SAR-0015)
.
≥ 20
.
System build-up (horizontal section): System build-up of a facade
E system coating
reinforced base coat
Apply a finishing render and, if necessary, a paintcoat.
intermediate coat if necessary, e.g. StoPrep Miralor Sto-Primer
vertical board joint
Screw head must beflush with the carrierboard.
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket FP/GP
anchoring element in accordance with structural analysis
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec Carrier Board
Sto-Primer if necessary
Sto-Stainless Steel Wall Bracket GP
≈ 50
≈ 50
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
E .12
A
A length of the wall bracket (see VR-SAR-0015)
VR-SAR-0012System build-up (vertical section): System build-up of a facade
reinforced base coat
Apply a finishing render and, if necessary, a paint coat.
intermediate coat if necessary, e.g. StoPrep Miralor Sto-Primer
horizontal board joint
E system coating (see table in VR-SAR-0011)
Screw head must beflush with the carrierboard.
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
53
≥ 10 10
.A
wall construction
anchoring element in accordance with structural analysis
.
10 30
Sto-Stainless Steel Wall Bracket in accordancewith the structural analysis
Sto-Aluminium-T-Profile
optimal length of wall bracket
W
A length of the wall bracket
W total system build-up: W min. = A + E + 15 mm, W max. = A + E + 45 mm
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
.
.
12 .E
StoVentec Carrier Board
Sto-Primer if necessary
VR-SAR-0015System build-up (vertical section): Determining the length of the wall bracket
E
reinforced base coat
intermediate coat if necessary, e.g. StoPrep Miralor Sto-Primer
Apply a finishing render and, if necessary, a paint coat.
E + 30
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
system coating (see table in VR-SAR-0011)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR-0017
.
Rev. no.
System build-up (vertical section in transverse direction): System build-up of aceiling with wall bracket
StoVentec Rrainscreen cladding facade
1)
.12 .
≤ 40
0
≥ 25
≥ 10
≥ 20
.
E system coating (see table in VR-SAR-0011) with an approved total weight of ≤ 8 kg/m²
Sto-Primer if necessary
reinforced base coat
intermediate coat if necessary, e.g. StoPrep Miral or Sto-Primer
Apply a finishing render and, if necessary, a paint coat.
board joint (running lengthwise)
Sto-Insulation Dowel DH
StoVentec Carrier Board
Sto-Stainless Steel Wall Bracket in accordancewith the structural analysis
observe project-specific requirements for fire resistance where necessary.
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Screw head must beflush with the carrierboard.
A
bare ceiling
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
H
A length of the wall bracket (see VR-SAR-0015)
H ventilation airspace in accordance with DIN 18516-1 – H ≥ 20 mm; recommendation for the planning of the facade: H ≥ 30 mm
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-ProfileE≥ 10
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR-0018
.
Rev. no.StoVentec Rrainscreen cladding facade
.
1)
12 .
≤ 40
0
System build-up (vertical section in longitudinal direction): System build-up of aceiling with wall bracket
≈ 50 ≈ 50
Apply a finishing render and, if necessary, a paint coat.
intermediate coat if necessary, e.g. StoPrep Miralor Sto-Primer
reinforced base coat
Sto-Primer if necessary
StoVentec Carrier Board
board joint (running transverse)
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
E system coating (see table in VR-SAR-0011) with an approved total weight of ≤ 8 kg/m²
observe project-specific requirements for fire resistance where necessary.
Screw head must beflush with the carrierboard.
A
E
bare ceiling
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket GP
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
A length of the wall bracket (see VR-SAR-0015)
Sto-Stainless Steel Wall Bracket FP/GP
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR-0019
.
Rev. no.
System build-up (vertical section in transverse direction): System build-up of aceiling with two-force member
StoVentec Rrainscreen cladding facade
1)
2)
12 .
≥ 25
E system coating (see table in VR-SAR-0011) with an approved total weight of ≤ 8 kg/m²
observe project-specific requirements for fire resistance where necessary.Screw head must beflush with the carrierboard.
A
bare ceiling tension-zone-compatibleanchoring element inaccordance with thestructural analysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
E
A length of the wall bracket (see VR-SAR-0015)
Sto-Stainless Steel Wall Bracket in accordance with the structuralanalysisSto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile or Sto-Aluminium-L-Profile as two-forcemember (see VR-SAR-0019)
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Insulation Dowel DH
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
board joint (running lengthwise)
StoVentec Carrier Board
Sto-Primer if necessary
reinforced base coat
intermediate coat if necessary, e.g. StoPrep Miral or Sto-Primer
Apply a finishing render and, if necessary, a paint coat.
diagonal bracing if necessary in accordance with VR-SAR-0032
Sto-Aluminium-T-Profile
.
≥ 10
1)
2)
© S
to S
E &
Co. K
GaA
≥ 10
≥ 10
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
≈ 50≈ 50
System build-up (vertical section in longitudinal direction): System build-up of aceiling with two-force member VR-SAR-0020
≥ 10
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
bare ceiling
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Insulation Dowel DH
Sto-Stainless Steel Wall Bracket GP for use asfixed point
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile as two-force memberwith fixed point
Sto-Stainless Steel Wall Bracket GP for use assliding point
Sto-Aluminium-L-Profile as two-force member
Sto-Aluminium-T-Profile
Sto Drilling Screw stainless steel (5.5 x 24 mm)
board joint (running transverse)
Apply a finishing render and, if necessary, a paint coat.
intermediate coat if necessary, e.g. StoPrep Miral or Sto-Primer
reinforced base coat
Sto-Primer if necessary
StoVentec Carrier Board
Screw head must beflush with the carrierboard.
E system coating (see table in VR-SAR-0011) with an approved total weight of ≤ 8 kg/m²
3)
2)
1) observe project-specific requirements for fire resistance where necessary.
1)
observe the positioning of the screws
2)
diagonal bracing if necessary in accordance with VR-SAR-0032
3)
3)
12.
E
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
. . . . . . . . .600 600 600 600 600 600300 -600 ≥ 200
.< 600
.< 1200
StoVentec Carrier Board
Sto-Aluminium-T-Profile
VR-SAR-0030
System build-up (facade surface): Axial configuration of the carrier profiles for arated value of building element resistance at wind load ≤ 2.4 kN/m²
rod layout for the carrier profiles in accordance with structural analysis and/or working drawings (see also VR-SAR-0040)
≤ 400
external corner of thefinished facade
area to be fittedcarrier profile joint
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
. . . . . . . . . . . .400 ≥ 200
.< 800
.< 1200
400 400 400 400 400 400 400
StoVentec Carrier Board
Sto-Aluminium-T-Profile
VR-SAR-0031
400 ≤ 400
System build-up (facade surface): Axial configuration of the carrier profiles for arated value of building element resistance at wind load ≤ 3.9 kN/m²
rod layout for the carrier profiles in accordance with structural analysis and/or working drawings (see also VR-SAR-0040 and -0041)
external corner of the finished facade
area to be fitted
400
carrier profile joint
© S
to S
E &
Co. K
GaA
Sto-HQ-EN
Rev. no. 2017-06-01
.rainscreen cladding facade
System build-up (facade surface): Arrangement and fixing of the diagonalbracing on the bare ceiling
StoVentec R
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
VR-SAR-0032
≤ 30
00
10 -
15
≤ 30
00
400 / 600 400 / 600 400 / 600 400 / 600
≤ 15
00≤
1200
Sto-Aluminium-L-Profile(diagonal bracing intransverse direction)
Sto-Aluminium-L-Profile (diagonalbracing in transverse direction)
Sto-Aluminium-T-Profileas two-force memberwith fixed point (seeVR-SAR-0020)
Sto-Aluminium-L-Profile (diagonalbracing in longitudinal direction) St
o-Al
umin
ium
-L-P
rofil
e (d
iago
nal
brac
ing
in lo
ngitu
dina
l dire
ctio
n)
Sto-Aluminium-L-Profileas two-force memberwith sliding point (seeVR-SAR-0020)
Recommendation: In the case of increasedrequirements regarding the evenness of the ceilingand/or in case of wind loads > 2.4 kN/m², arrangethe carrier profiles with an axis distance ≤ 400 mm(see VR-SAR-0030 and -0031).
Fix a minimum of 2 bracings in longitudinal andtransverse direction on the connected, seamlessceiling area (max. 25 x 25 m). Arrange the bracingsas close to the edges of the partial surfaces aspossible.
1)
2)
1)
2)
2)
2)
2)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
wall construction
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Ventilation Profile
Sto-Starter Profile PH-K
Sto-Hammer Dowel S UEZ 8
StoVentec Carrier Board
5 - 1
0
.
≥ 10
.
A
VR-SAR-0035
1)
≈ 40
50 -
85
System build-up (vertical section): Determination of the base point of the facade
anchoring element in accordance with structural analysis
Sto-Stainless Steel Wall Bracket in accordancewith the structural analysis
Sto-Primer if necessary
reinforced base coat
intermediate coat if necessary, e.g. StoPrep Miralor Sto-Primer
Apply a finishing render and, if necessary, a paint coat.
A
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
Sto-Edge Protection ProfileG PVC white, 12 mm
≥ 15
0
If the StoVentec Carrier Board projects into the splash zone when it is installed, provide the system with additional protection against moisture penetrationand ensure constant system ventilation by taking structural and maintenance measures. Constant, excessive stress from moisture can damage the system. Theplanner must determine the height and position of the splash zone on a project-specific basis.
1)
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
length of the wall bracket (see VR-SAR-0015)
KT
alternative: withSto-Edge ProtectionProfile GT, PVC white,12 mm
≈ 40
24≥
150
2)
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
© S
to S
E &
Co. K
GaA
rainscreen cladding facade StoVentec RRev. no. 2017-06-01
.
Sto-HQ-EN
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
300 - 600 ≥ 200 ≤ 400.
≤ 40
0
< 600
< 1200
600
.
.
X
X
400 ≥ 200 ≤ 400
≤ 40
0
< 800
< 1200
.
.
X
X
VR-SAR-0037
.400
System build-up (horizontal section): Axial configuration of the carrier profiles onan external corner
rated value of building element resistance at wind load up to 2.4 kN/m²
rated value of building element resistance at wind load up to 3.9 kN/m²
recommended screwing direction for connection of the wall brackets to the T-profile and alignment of the wall brackets
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
© S
to S
E &
Co. K
GaA
Sto-HQ-EN
Rev. no. 2017-06-01
.rainscreen cladding facade StoVentec R
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
≤ 30
00
.≤
1200
≤ 1
200
.
≤ 15
00
≤ 30
00
≤ 12
00≤
1200
≤ 12
00≤
1200
≤ 15
00
.
.≤
1200
.
≤ 15
00
.
.
≤ 12
00.
.
1)
GP
GP
GP
FP
GP/GP
GP
FP
GP
GP/GP
GP
FP
GP
FP/GP
FP/GP
VR-SAR-0040
System build-up (vertical section): Rod layout of the carrier profiles for a ratedvalue of building element resistance at wind load ≤ 3.3 kN/m²
GP = sliding point
GP/GP = sliding point/sliding point
FP = fixed point
FP/GP = fixed point/sliding point
PST = joint between the carrier profiles
KTKT KT
KT
version 1 version 2
version 3
version 4
number of anchoring and connecting elements, rod lengths, cantilever lengths, and distances between the wall brackets in accordance with structural analysis
KT = cantilever of the T-profile
formtaion of the fixed and sliding points, see VR-SAR-0045
PST
= 5
- 10
PST
= 5
- 10
PST
= 5
- 10
PST
= 5
- 10
PST
= 5
- 10
max. permitted transverse deformation at wind load = KT/300
1)1)
1)1)
© S
to S
E &
Co. K
GaA
Sto-HQ-EN
Rev. no. 2017-06-01
.rainscreen cladding facade StoVentec R
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
≤ 30
00
.≤
800
≤ 8
00.
≤ 15
00
≤ 30
00
≤ 80
0≤
800
≤ 80
0≤
800
≤ 15
00
.
.≤
800
.
≤ 15
00
.
.
≤ 12
00.
.
1)
GP
GP
GP
FP
GP/GP
GP
FP
GP
GP/GP
GP
FP
GP
FP/GP
FP/GP
VR-SAR-0041
System build-up (vertical section): Rod layout of the carrier profiles for a ratedvalue of building element resistance at wind load ≤ 3.9 kN/m²
GP = sliding point
GP/GP = sliding point/sliding point
FP = fixed point
FP/GP = fixed point/sliding point
PST = joint between the carrier profiles
KTKT KT
KT
version 5
version 6
version 7
version 8
number of anchoring and connecting elements, rod lengths, cantilever lengths, and distances between the wall brackets in accordance with structural analysis
KT = cantilever of the T-profile
formtaion of the fixed and sliding points, see VR-SAR-0045
PST
= 5
- 10
PST
= 5
- 10
PST
= 5
- 10
PST
= 5
- 10
PST
= 5
- 10
max. permitted transverse deformation at wind load = KT/300
1)1)
1)1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
10-1
5≥
10
≥ 10
10-1
5≥
10
≥ 10
≥ 10
≥ 10
1
3
5
3
2
1 1
5
5
3
3
54
4 4
4
fixed point (FP)
fixed point/sliding point (FP/GP) sliding point/sliding point (GP/GP)
1
2
3
Sto-Stainless Steel Wall Bracket FP/GP
Sto-Stainless Steel Wall Bracket GP
4
5 Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
sliding point (GP)
VR-SAR-0045System build-up (vertical section): Producing fixed points and sliding points
Sto-Aluminium-T-Profile
anchoring element in accordance with structuralanalysis
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
. . . . . . . . .600 600 600 600 600 600300 -600 ≥ 200 ≤ 400
. .
50 -
60
≥ 25
50 -
85
≈ 40
≥ 25 ≥ 25
≤ 23
4
≤ 11
7.
. .
. ≈ 50
Sto-Aluminium-T-Profile
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
.
.
≥ 25
≈ 50
VR-SAR-0060
StoVentec Carrier Board
≥ 25 ≥ 25
System build-up (facade surface): Arrangement and fixing of the StoVentecCarrier Board (1200 x 800 x 12 mm) for a rated value of building elementresistance at wind load ≤ 1.65 kN/m² and ≤ 2.4 kN/m²
area to be fitted
external corner of thefinished facadecarrier profile joint
rated value of building element resistance at windload up to 1.65 kN/m²
rated value of building element resistance at windload up to 2.4 kN/m²
additional screw connection of the carrier boards at the end of the system transverse to the T-profile axis with a screw edge distance > 50 mm
(Z) StoVentec Carrier Board cut to size for the area to be fitted
(Z)(Z)
(Z)
1) rod layout for the carrier profiles in accordance with structural analysis and/or working drawings (see also VR-SAR-0040)
1)
≈ 50
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
. . . . . . . . .. .400 ≥ 200
50 -
60
≥ 25
≈ 40
Sto-Aluminium-T-Profile
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
StoVentec Carrier Board
.
.
≥ 25
≈ 50
400 400 400 400 400 400 400 400
VR-SAR-0061
≤ 11
7
.≥ 25 ≥ 25
≈ 50.
System build-up (facade surface): Arrangement and fixing of the StoVentecCarrier Board (1200 x 800 x 12 mm) for a rated value of building elementresistance at wind load ≤ 3.9 kN/m²
≤ 400
area to be fitted
external corner of thefinished facade
carrier profile joint
additional screw connection of the carrier boards at the end of the system transverse to the T-profile axis with a screw edge distance > 50 mm
(Z) StoVentec Carrier Board cut to size for the area to be fitted
(Z)(Z)
(Z)
rod layout for the carrier profiles in accordance with structural analysis and/or working drawings (see also VR-SAR-0040 and -0041)1)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
. . . . . . . . .600 600 600 600 600 600300 -600 ≥ 200
. .
50 -
60
≥ 25
Sto-Aluminium-T-Profile
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
.
.
≥ 25
≈ 50
VR-SAR-0062
StoVentec Carrier Board
. ≈ 50
.≥ 25 ≥ 25
≤ 23
450
- 85
≈ 40
≥ 25 ≥ 25
≤ 11
7
.
System build-up (facade surface): Arrangement and fixing of the StoVentecCarrier Board (2400 x 1200 x 12 mm) for a rated value of building elementresistance at wind load ≤ 1.65 kN/m² and ≤ 2.4 kN/m²
≤ 400
area to be fitted
external corner of thefinished facade
carrier profile joint
rated value of building element resistance at windload up to 1.65 kN/m²
rated value of building element resistance at windload up to 2.4 kN/m²
additional screw connection of the carrier boards at the end of the system transverse to the T-profile axis with a screw edge distance > 50 mm
(Z) StoVentec Carrier Board cut to size for the area to be fitted
(Z)
(Z)
rod layout for the carrier profiles in accordance with structural analysis and/or working drawings (see also VR-SAR-0040)
1)
≈ 50
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
. . . . . . . . .. .400 ≥ 200
50 -
60
≥ 25
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
StoVentec Carrier Board
.
.
≥ 25
≈ 50
400 400 400 400 400 400 400 400
VR-SAR-0063
≤ 11
7
.≥ 25 ≥ 25 ≈ 50.
≈ 40
≤ 400
System build-up (facade surface): Arrangement and fixing of the StoVentecCarrier Board (2400 x 1200 x 12 mm) for a rated value of building elementresistance at wind load ≤ 3.9 kN/m²
Sto-Aluminium-T-Profilearea to be fitted
external corner of thefinished facade
carrier profile joint
additional screw connection of the carrier boards at the end of the system transverse to the T-profile axis with a screw edge distance > 50 mm
(Z) StoVentec Carrier Board cut to size for the area to be fitted
rod layout for the carrier profiles in accordance with structural analysis and/or working drawings (see also VR-SAR-0040 and -0041)
(Z)
(Z)
1)
1)
© S
to S
E &
Co. K
GaA
rainscreen cladding facade
Sto-HQ-EN
Rev. no.2017-06-01StoVentec R
.
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
≥ 20
0≥
200
.≤ 150
400 / 600StoVentec Carrier Board
Sto-Aluminium-T-Profile
1)
VR-SAR-0064
1)
System build-up (facade surface): Notching the StoVentec Carrier Board onbuilding openings and/or recesses
carrier profile joint
notched StoVentec Carrier Board
outer edge of the building shell
larger board cantilevers if applicable (see system-related standard details window connection)
© S
to S
E &
Co. K
GaA
rainscreen cladding facade
Sto-HQ-EN
Rev. no.2017-06-01StoVentec R
.
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
≥ 20
0.
.
.
≤ 23
4
400
800
==
≥ 10
≥ 10 ≤
117
. . . .. .
.
≥ 25 ≥ 25
≈50
≈ 50
600600600 400 / 600
1)
Sto Drilling Screw stainless steel(5.5 x 24 mm)
Sto-Aluminium-T-Profile
VR-SAR-0065
400 / 600 400 / 600
1)
10 -
15
≥ 20
0
System build-up (facade surface): Arrangement and fixing of the StoVentecCarrier Board on the carrier profile joint
rated value of building element resistance at windload up to 1.65 kN/m²
rated value of building element resistance at windload up to 3.9 kN/m²
Fix the carrier boards on the carrier profiles above and below the carrier profile joint for each axis with min. 3 Sto-Facade Drilling Screws and additionalscrews if necessary.
carrier profile joint
additional screwconnection
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
1000 / 1250
625
/ 600
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
VR-SAR-0090
System build-up (facade surface): Arrangement and fixing of insulation boardswith nonwoven fabric facing on the facade and on the ceiling in accordancewith DIN 18516-1
On the facade, use the Sto-Insulation Dowel, the Sto-InsulationDowel DH, or the Sto-Screw Dowel H 60, if necessary withSto-Dowel Head H.
external corner of the building shell
external corner of the insulation board
Use an average of 5 insulation fasteners/m² in accordance with DIN 18516-1. Use 1 to 2 insulation fasteners in the centre of the board.
If the ventilation airspace is < 6 cm (see VR-SAR-0011 and -0012), fix the insulation fasteners adjacent to the carrier profile axes.
On ceilings use the Sto-Insulation Dowel DH, the Sto-Screw DowelH 60, if necessary with Sto-Dowel Head H, or the Sto-CeilingInsulation Screw SW with Sto-Ceiling Insulation Retaining Disk.
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
.
number of insulation fasteners: min. 1.6 pieces/m²
VR-SAR-0091
1000
625
Sto-Stone Wool Insulation Board with nonwovenfabric facing in accordance with the TechnicalData Sheet
System build-up (facade surface): Arrangement and fixing of the Sto-Stone WoolInsulation Boards with nonwoven fabric facing on the facade with theone-anchor technique
Use the Sto-Insulation Dowel, the Sto-Insulation Dowel DH, or theSto-Screw Dowel H 60, if necessary, with Sto-Dowel Head H.
external corner of the building shell
external corner of the insulation board
If the insulation board thickness ≥ 10 cm, the one-anchor technique can only be applied after project-specific tests and with approval of the insulantmanufacturer; otherwise fix the anchor in accordance with DIN 18516-1 (see VR-SAR-0090).
If the ventilation airspace is < 6 cm (see VR-SAR-0011 and -0012), fix the insulation fasteners adjacent to the carrier profile axes.
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
.
number of insulation fasteners: in normal zone min. 1.4 pieces/m², in edge zone min. 2.7 pieces/m²
normal zone edge zone min. 2 m ..
VR-SAR-0092
1250
600
Sto-Glass Wool Board RSC, with nonwoven fabricfacing in accordance with the Technical DataSheet
System build-up (facade surface): Arrangement and fixing of the Sto-Glass WoolBoards with nonwoven fabric facing on the facade with the one-anchortechnique
Use the Sto-Insulation Dowel DH, the Sto-Screw Dowel H 60, ifnecessary with Sto-Dowel Head H, or the Sto-Ceiling InsulationScrew SW with Sto-Ceiling Insulation Retaining Disk.
external corner of the building shell
external corner of the insulation board
If the insulation board thickness ≥ 8 cm, only use insulation fasteners after project-specific tests (building height ≤ 100 mand pull-out strength of insulation fasteners > 200 N) and with approval of the insulant manufacturer; otherwise fix withanchors in accordance with DIN 18516-1 (see VR-SAR-0090).
If the ventilation airspace is < 6 cm (see VR-SAR-0011 and -0012), fix the insulation fasteners adjacent to the carrierprofile axes.
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
1000 / 1250
625
/ 600
VR-SAR-0093
System build-up (facade surface): Arrangement and fixing of insulation boardswith nonwoven fabric facing in two layers on the facade and on the ceiling inaccordance with DIN 18516-1
Sto-Insulation Dowel DH with insulation anchorplates for the first and second insulation layer
Sto-Stone Wool Insulation Boards or Sto-GlassWool Insulation Boards with nonwoven fabricfacing in accordance with the Technical DataSheet for the second insulation layer
Sto-Insulation Dowel DH with insulation anchorplate for the first insulation layer
Sto-Stone Wool Insulation Boards or Sto-GlassWool Insulation Boards with nonwoven fabricfacing in accordance with the Technical DataSheet for the first insulation layer
Sto-Insulation Dowel DHwith insulation anchor platefor the second insulationlayer
Use an average of 5 insulation fasteners/m² in accordance with DIN 18516-1. Use 1 to 2 insulation fasteners in the centre of the board.
If the ventilation airspace is < 6 cm (see VR-SAR-0011 and -0012), fix the insulation fasteners adjacent to the carrier profile axes.
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR-0101
.
Rev. no.StoVentec Rrainscreen cladding facade
anchoring element in accordance with structural analysis
1)
≥10
.
3)
1)
plinth insulation in accordance with technicalapproval and Technical Data Sheet
5 - 1
0
4)
Plinth (vertical section): Connection to a set-back plinth with plinth insulationboard and Sto-Starter Profile PH-K
system coating inaccordance with thetechnical approval andTechnical Data Sheet
≥ 15
0
≈ 40
50 -
85
Sto-Extension Profile PH if necessary
Sto-Edge Protection Profile G PVC white, 12 mm
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
KT
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
3) If the StoVentec Carrier Board projects into the splash zone when it is installed, provide the system with additional protection against moisture penetrationand ensure constant system ventilation by taking structural and maintenance measures. Constant, excessive stress from moisture can damage the system. Theplanner must determine the height and position of the splash zone on a project-specific basis.
4) If the insulant thickness is larger than 160 mm and max. 200 mm additionally install the Sto-Extension Profile PH.
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
StoVentec Carrier Board
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Ventilation Profile
Sto-Joint Sealing Tape in accordance with theTechnical Data Sheet
Sto-Starter Profile PH-K
Sto-Hammer Dowel S UEZ 8
alternative: withSto-Edge ProtectionProfile GT, PVC white,12 mm
≥ 202)
2) free airflow cross-section ≥ 50 cm²/m
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
≈ 40
24≥
150
4)
3)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
1)
≥ 10
3)
5-10
anchoring element in accordance with structural analysis
VR-SAR-0110
Plinth (vertical section): Connection to a set-back plinth with plinth insulationboard
≈ 40
.
system coating inaccordance with thetechnical approval andTechnical Data Sheet
Sto-Edge Protection Profile G PVC white, 12 mm
≥ 15
0
50 -
85
plinth insulation in accordance with technicalapproval and Technical Data Sheet
Apply StoFlexyl twice as slurry.
Sto-Mesh Corner Roll Ideal
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
KT1)
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
2)
If the StoVentec Carrier Board projects into the splash zone when it is installed, provide the system with additional protection against moisture penetrationand ensure constant system ventilation by taking structural and maintenance measures. Constant, excessive stress from moisture can damage the system. Theplanner must determine the height and position of the splash zone on a project-specific basis.
wall constructionSto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
StoVentec Carrier Board
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Ventilation Profile
≥ 202)
3)
free airflow cross-section ≥ 50 cm²/m
alternative: withSto-Edge ProtectionProfile GT, PVC white,12 mm
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
≈ 40
24≥
150
3)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
≥ 10
VR-SAR-0111
Plinth (vertical section): Connection to a plinth flush with the facade with plinthinsulation board
.≥
150
system coating in accordance with the technicalapproval and Technical Data Sheet
anchoring element in accordance with structural analysis
1)
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
KT
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
2) If the StoVentec Carrier Board projects into the splash zone when it is installed, provide the system with additional protection against moisture penetrationand ensure constant system ventilation by taking structural and maintenance measures. Constant, excessive stress from moisture can damage the system. Theplanner must determine the height and position of the splash zone on a project-specific basis.
plinth insulation in accordance with technicalapproval and Technical Data Sheet
Apply StoFlexyl twice as slurry.
Sto-Mesh Corner Roll Ideal
1)
2)
wall constructionSto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
StoVentec Carrier Board
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto Drilling Screw stainless steel (5.5 x 24 mm)
10
-20
≈ 40
50 -
85
≈ 25
≈ 40
alternative: ventilationjoint with Sto-EdgeProtection Profile GT,PVC white, 12 mm
10
-20
Sto-Edge Protection Profile G PVC white, 12 mm
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
24≈
40
© S
to S
E &
Co. K
GaA
rainscreen cladding facade
Plinth (vertical section): Connection to a set-back plinth with plinth insulationboard in the splash zone
Sto-HQ-EN
Rev. no. 2017-06-01
.
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
StoVentec R
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheetanchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
.
Apply StoFlexyl twice as slurry.
≤ 20
Sto-Mesh Corner Roll Ideal
plinth insulation in accordance with technicalapproval and Technical Data Sheet
aluminium L-profile
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Edge Protection Profile GT
folded aluminium ventilation profile (alreadyavailable on-site and coated black)
splash protection strip (splash zone strip) withdrainage in accordance with DIN 4095
KT
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis
1)
1)
2)
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
2) If the StoVentec Carrier Board projects into the splash zone when it is installed, provide the system with additional protection against moisture penetrationand ensure constant system ventilation by taking structural and maintenance measures. Constant, excessive stress from moisture can damage the system. Theplanner must determine the height and position of the splash zone on a project-specific basis.
VR-SAR-0120
≥ 15
0
≈ 40
≥ 50
24
50 -
80
3) free airflow cross-section ≥ 50 cm²/m
3)
4)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particular constructionproject. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance with the technicalspecifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN2017-10-10
.Rev. no.
StoVentec Rrainscreen cladding facade
.
.
anchoring element inaccordance with structuralanalysis
≥ 25
≥ 25
X
XVR-SAR-0200
External wall/system transition (horizontal section): Connection of an external corner
≤ 40
0
≤ 400
system coating in accordancewith the technical approvaland Technical Data Sheet
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
wall constructionSto-Stone Wool InsulationBoard or Sto-Glass WoolInsulation Board withnonwoven fabric facing inaccordance with theTechnical Data Sheet
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
StoVentec Carrier Board
InstallSto-Aluminium-L-Profile witha max. installation length of3 m without torsional stress.
Sto-Mesh Angle Bead SO
X
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particular constructionproject. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance with the technicalspecifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN2017-10-10
.Rev. no.
StoVentec Rrainscreen cladding facade
anchoring element inaccordance with structuralanalysis
≥ 25
≥ 25
Sto-Stainless Steel Corner Bracket
.X
VR-SAR-0202
External wall/system transition (horizontal section): Connection of an external cornerwith Sto-Stainless Steel Corner Bracket
system coating in accordancewith the technical approvaland Technical Data Sheet
≤ 40
0
≤ 400
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
wall construction
Sto-Stone Wool InsulationBoard or Sto-Glass WoolInsulation Board withnonwoven fabric facing inaccordance with theTechnical Data Sheet
Sto-Self-Drilling FacadeScrew with over-tighteningprotection (5.5 x 19 mm)
StoVentec Carrier Board
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
InstallSto-Aluminium-L-Profile witha max. installation length of3 m without torsional stress.
Sto-Mesh Angle Bead SO
X
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
anchoring element in accordance with structuralanalysis
≥ 25
≥ 25
Sto-Thermal Blocking Element PH orSto-Thermocouple
fixing element in accordance with structuralanalysis
Sto-Insulation Dowel DH
VR-SAR-0204
External wall/system transition (horizontal section): Connection of an externalcorner with corner support
≤ 40
0
≤ 400
system coating in accordance with the technicalapproval and Technical Data Sheet
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
aluminium U-profile as corner support inaccordance with structural analysis
X
X
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainless steel (5.5 x 24 mm)
StoVentec Carrier Board
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
InstallSto-Aluminium-L-Profilewith a max. installationlength of 3 m withouttorsional stress.
Sto-Mesh Angle Bead SO
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheetanchoring element in accordance with structuralanalysis
Sto-Stainless Steel Lintel Bracket
Install Sto-Aluminium-L-Profile with a max.installation length of 3 m without torsional stress.
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Mesh Angle Bead SO
external wall insulationsystem in accordance withsystem approval
StoVentec Carrier Board
≈ 40 ≥ 25
≤ 30
0
1)
VR-SAR-0210
External wall/system transition (horizontal section): Connection of an externalcorner to an external wall insulation system
≤ 30
0
≤ 400
system coating in accordance with the technicalapproval and Technical Data Sheet
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
1)
Sto-Stainless Steel Wall Bracket
Sto-Primer if necessary
X
X
external wall insulation system with EPS insulation boards or speed lamellas
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Lintel Bracket
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Mesh Angle Bead SO
StoVentec Carrier Board
≈ 35 ≥ 25
≤ 30
0
VR-SAR-0215
External wall/system transition (horizontal section): Connection of an externalcorner to a solid wall
≤ 400
system coating in accordance with the technicalapproval and Technical Data Sheet
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Sto-Stainless Steel Wall Bracket
≥ 25
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Mesh Angle Bead SO
InstallSto-Aluminium-L-Profilewith a max. installationlength of 3 m withouttorsional stress.
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
X
Sto-Joint Sealing Tape in accordance with theTechnical Data Sheet
X
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
anchoring element in accordance with structuralanalysis
≈ 40
≤ 15
0
≈ 40
1)
≤ 150
VR-SAR-0220
External wall/system transition (horizontal section): Connection of an internalcorner with Sto-Joint Sealing Tape
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
system coating in accordance with the technicalapproval and Technical Data Sheet
1) Screw the StoVentec Carrier Board onto min. two carrier profile axes.
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Joint Sealing Tape in accordance with theTechnical Data Sheet
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stainless Steel Wall Bracket
StoVentec Carrier Board
wall construction
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
anchoring element in accordance with structuralanalysis
≤ 15
0
≈ 40
2)
VR-SAR-0225
External wall/system transition (horizontal section): Connection of an internalcorner to an external wall insulation system with Sto-Joint Sealing Tape
system coating in accordance with the technicalapproval and Technical Data Sheet
2) Screw the StoVentec Carrier Board onto min. two carrier profile axes.
Complete the external wall insulation system up until the reinforced base coat and only then install the rainscreen cladding facade.
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
external wall insulationsystem in accordance withsystem approval
Sto-Joint Sealing Tape in accordance with theTechnical Data Sheet
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
wall construction
1)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
anchoring element in accordance with structural analysis
≤ 15
0
≈ 40
1)
VR-SAR-0231
External wall/system transition (horizontal section): Connection of an internalcorner to a solid wall with Sto-Joint Sealing Tape
system coating in accordance with the technicalapproval and Technical Data Sheet
Caution: thermal bridge!
1) Screw the StoVentec Carrier Board onto min. two carrier profile axes.
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
wall construction
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
anchoring element in accordance with structural analysis
≤ 15
0
≈ 40
2)
VR-SAR-0235
External wall/system transition (horizontal section): Connection of an internalcorner to a post and beam construction with Sto-Joint Sealing Tape
system coating in accordance with the technicalapproval and Technical Data Sheet
2) Screw the StoVentec Carrier Board onto min. two carrier profile axes.
airtightness and fixing the post and beam construction in accordance with manufacturer information
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
wall construction
post and beam construction (already available on-site)
1)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
≥ 25
≥ 25
≤ 30
0
≤ 400
≈ 40
VR-SAR-0240
External wall/system transition (horizontal section): Transition betweenStoVentec R and a set-back external wall insulation system
anchoring element inaccordance with structuralanalysis
P
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Mesh Angle Bead SO
external wall insulation system in accordancewith system approval
wall construction
Sto-Stainless Steel Lintel Bracket
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
InstallSto-Aluminium-L-Profilewith a max. installationlength of 3 m withouttorsional stress.
Sto-Joint Sealing Tape in accordance with theTechnical Data Sheet
Sto-Edge Protection Profile G PVC white, 12 mm
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
≈ 40
VR-SAR-0241
External wall/system transition (horizontal section): Connection to an externalwall insulation system in the facade surface with Sto-Expansion Joint Profile E
external wall insulation system in accordancewith system approval
Sto-Expansion Joint Profile E
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
anchoring element in accordance with structuralanalysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
F
wall construction
Use a Sto-Aluminium-L-Profile if KP is greaterthan 150 mm.
1)
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
joint width: 20 - 30 mm in accordance with anticipated deformations
KP cantilever length of the StoVentec Carrier Board
Screw the StoVentec Carrier Board onto min. two carrier profile axes.
F
≈ 40
..
80 ≤
KP ≤
300
alternative: with Sto-ExpansionJoint Profile E
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
≥ 25
≥ 25
≤ 30
0
≤ 400
≈ 40
anchoring element inaccordance with structuralanalysis
system coating in accordance with the technicalapproval and Technical Data Sheet
VR-SAR-0245
External wall/system transition (horizontal section): Connection to a set-backsolid wall
Sto-Mesh Angle Bead SO
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Caution: thermal bridge!
wall construction
Sto-Stainless Steel Lintel Bracket
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
InstallSto-Aluminium-L-Profilewith a max. installationlength of 3 m withouttorsional stress.
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
VR-SAR-0250
External wall/system transition (horizontal section): Connection to a StoVentecpanel facade in the facade surface
..
..
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structural analysis
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
.
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Stainless Steel Wall Bracket
Use a Sto-Aluminium-L-Profile if KP is greater than 150 mm.
Cspan width of the StoVentec Aluminium Agraffe Profile inaccordance with technical approval, structural analysis, andproject-specific planning
E thickness of the panel or the system coating (see table in VR-SAR-0011)
F joint width: 10 - 20 mm in accordance with anticipated deformations
KAcantilever length of the agraffe profile in accordance withtechnical approval, structural analysis, and project-specificplanning
KP cantilever length of the StoVentec Carrier Board
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mmrated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
12
Sto-Aluminium-T-Profile
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
StoVentec Aluminium Agraffe Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
adjustment screw (M5 x 10)
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Board Carrier Profile
StoVentec panel
32 .
E
E
80 ≤
KP ≤
300
FKA
C
≈ 40
≈ 40
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
External wall/system transition (vertical section): Transition between StoVentec Rand a set-back external wall insulation system VR-SAR-0260
1)
≈ 30
0
external wall insulationsystem in accordance withsystem approval
wall construction
Sto-Plinth Insulation Board
Apply StoFlexyl twice asslurry.
intermediate coat if necessary
Apply a finishing render and, if necessary, a paint coat.
reinforced base coat
e.g. StoFentra Window Sill Bracket RSC
Sto-Hammer Dowel S UEZ 8 with thermal stop
Sto-Rain Guard Profile G, PVC white, 12 mm
10-2
0
≈ 40
50-8
5
.
≥ 10
aluminium sheet metal cover with expanding endprofiles and thermal stop
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
anchoring element in accordance with structural analysis
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
30-50
KT
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
≈ 5
Sto-Render Stop Profile
joint sealant in accordance withthe Technical Data Sheet andexecution in accordance with IVDdata sheet
Sto-Joint Sealing Tape inaccordance with the TechnicalData Sheet
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
1) screw and screw-edge distances in accordance with VR-SAR-0060 to -0063
2) with a copper sheet ≥ 50 mm
2)
≥ 5°
≈ 25
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Glassrainscreen cladding facade
external wall insulation system in accordancewith system approval
Sto-Hammer Dowel S UEZ 8
Sto-Starter Profile PH-K withSto-Packing Shim
Sto-Drip Edge Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
anchoring element in accordance with structuralanalysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
1)
VR-SAR-0261
External wall/system transition (vertical section): Transition between StoVentec Rand a set-forward external wall insulation system with ventilation gap
≈ 40
≥ 10
50 -
85 ≥ 10
.
10 -
20
Sto-Rain Guard Profile G,PVC white, 12 mm
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
wall construction
≈ 25
KT
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
1) screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
50
30 -
≈ 40
≥ 10
VR-SAR-0265
External wall/system transition (vertical section): Transition between StoVentec Rand a set-forward external wall insulation system with ventilation gap
10- 20
50 -
85
.KT
wall constructionSto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheetanchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Joint Sealing Tape in accordance with theTechnical Data Sheet
aluminium sheet metal cover with flexible endprofiles and thermal stop (already availableon-site)
e.g. StoFentra Window Sill Bracket
Sto-Hammer Dowel S UEZ 8
external wall insulation system in accordancewith system approval
≈ 25
KTcantilever length of the Sto-Aluminium-T-Profile in accordancewith structural analysis (see also VR-SAR-0040 and -0041)
1) screw and screw-edge distances and, if necessary, additionalscrew connection in accordance with VR-SAR-0060 to -0063
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
1)
≥ 5°
with a copper sheet ≥ 50 mm2)
2)
alternative: ventilationjoint with Sto-EdgeProtection Profile GT,PVC white, 12 mm
10
-20
24 ≈ 40 ≈
40
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
VR-SAR-0280
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
External wall/system transition (horizontal section): Wall bracket installation withcantilever beam on vertical joints in case of anchorage on multi-layer boards
..
XP
wall construction made from of a multi-layerboard consisting of an interior load-bearing shell,an exterior rain screen, and intermediateinsulation as necessary
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
fixing element in accordance with structural analysis
Sto-Thermal Blocking Element PH or Sto-Thermocouple
anchoring element in accordance with structuralanalysis
aluminium U-profile as cantilever beam inaccordance with structural analysis
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Incorporate structural expansion joints in the facade.
Plan and execute the anchorage of the cantilever beam in the rain screen or load-bearing shell in accordance with the specifications of the planner inaccordance with the results of the on-site building diagnostics. The building diagnostics must statically verify that the rain screen has sufficient stability andload-bearing capacity. Additional structural or static measures may be necessary.
2)
2)
building element joint between multi-layer boards
1)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
VR-SAR-0290
External wall/system transition (vertical section): Closed, horizontal fielddemarcation joint with Sto-Edge Protection Profile GT and Sto-Edge ProtectionProfile GF
wall construction
anchoring element inaccordance with structuralanalysis
≈ 40
≥ 10
..
≈ 40
50 -
8550
- 85
.32 -
38
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
KTKT
F
Sto-Edge Protection ProfileGT, PVC white, 12 mm
Sto-Edge Protection ProfileGF, PVC white, 12 mm
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
F joint width: approx. 6 - 12 mm in accordance with anticipated deformations
Note: max. seamless field length of the cladding: 25 m
1)
1)1)
≥ 10
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particular constructionproject. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance with the technicalspecifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN2017-06-01
.Rev. no.
StoVentec Rrainscreen cladding facade
VR-SAR-0292
External wall/system transition (vertical section): Closed, vertical field demarcationjoint in the facade surface with Sto-Expansion Joint Profile E
F≈
40
80 ≤
KP ≤
300
wall construction
Sto-Stone Wool InsulationBoard or Sto-Glass WoolInsulation Board withnonwoven fabric facing inaccordance with theTechnical Data Sheet
anchoring element inaccordance with structuralanalysis
Use a Sto-Aluminium-L-Profile if KP is greater than 150 mm.
Sto-Expansion Joint Profile E
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw with over-tighteningprotection (5.5 x 19 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
KP cantilever length of the StoVentec Carrier Board
F joint width: 20 - 30 mm in accordance with anticipated deformations
Note: max. seamless field length of the cladding: 25 m; adopt existing structural expansion joints.
1)
150200
3,33,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
XX
Screw the StoVentec Carrier Board onto min. two carrier profile axes.
≈ 40
.
.
1)
alternative: withSto-Expansion JointCover E
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
VR-SAR-0293
External wall/system transition (horizontal section): Closed, vertical fielddemarcation joint in the facade surface with Sto-Edge Protection Profile GT andSto-Edge Protection Profile GF
F≈
40
80 ≤
KP ≤
300
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element inaccordance with structuralanalysis
Use a Sto-Aluminium-L-Profile if KP is greater than 150 mm.
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
KP cantilever length of the StoVentec Carrier Board
F joint width: approx. 6 - 12 mm in accordance with anticipated deformations
Note: max. seamless field length of the cladding: 25 m; adopt existing structural expansion joints.
1)
1)
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
Screw the StoVentec Carrier Board onto min. two carrier profile axes.
.
≈ 40
.
≈ 40
Sto-Edge Protection Profile GT, PVC white, 12 mm
Sto-Edge Protection Profile GF, PVC white, 12 mm
32 -
38
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
VR-SAR-0294
External wall/system transition (horizontal section): Open, vertical fielddemarcation joint in the facade surface with Sto-Edge Protection Profile G
F≈
40
80 ≤
KP ≤
300
wall constructionSto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Use a Sto-Aluminium-L-Profile if KP is greater than 150 mm.
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
KP cantilever length of the StoVentec Carrier Board
F joint width: max 20 mm in accordance with anticipated deformations
Note: max. seamless field length of the cladding: 25 m; adopt existing structural expansion joints.
1)
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
Screw the StoVentec Carrier Board onto min. two carrier profile axes.
.
.
Sto-Edge Protection Profile G PVC white, 12 mm≈ 40
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
X
≥ 5°
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structural analysis
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
StoVentec Carrier Board
building height
in accordance with regulations for metalwork in the roofing trade
≤ 8 m ≥ 20 mm8-20 m ≥ 30 mm≥ 20 m ≥ 40 mm
B
1)
A
≥ 50 mm≥ 80 mm≥ 100 mm
.
≥ 10
2)
VR-SAR-0300Roof (vertical section): Connection to a parapet with ventilation joint
≥ 10
.
system coating in accordance with the technicalapproval and Technical Data Sheet
.
Sto-Rain Guard Profile G, PVC white, 12 mm
A
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
B≈ 40
50-8
5
2)
1)
2)
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
for copper sheet: ≥ 50 mm
parapet (already available on-site)
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
KT
≥ 25
10- 2
0
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket
anchoring element inaccordance with structuralanalysis
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Edge Protection ProfileG PVC white, 12 mm
StoVentec Carrier Board
Sto-Stainless Steel Lintel Bracket
Sto-Aluminium-L-Profile
X
≈ 40
≤ 150
≥ 25
≥ 25
Reveal (horizontal section): Connection to a reveal with a set-back window and atotal system build-up ≤ 400 mm
≤ 30
0
Sto-Joint Sealing Tape in accordance with theTechnical Data Sheet
≤ 400
system coating in accordance with the technicalapproval and Technical Data Sheet
Use a Sto-Aluminium-T-Profile orSto-Aluminium-L-Profile, depending on theinstallation situation.
VR-SAR-0400
StoFentra Upstand Profile Uni
StoFentra Window Sill Profile
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1)
1) connection between end profile and reveal panel in accordance with VR-SAR-0502 to -0503
X
Sto-Mesh Angle Bead SO
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR-0401
.
Rev. no.Reveal (horizontal section): Connection to a reveal with a set-back window,reveal insulation board fixed with adhesive, and joint sealing tape, with a totalsystem build-up ≤ 200 mm
StoVentec Rrainscreen cladding facade
.
≥25
≤200≥100
≤150
≥25
≥30
X
wall construction
Sto-Stone Wool InsulationBoard or Sto-Glass WoolInsulation Board withnonwoven fabric facing inaccordance with theTechnical Data Sheet
StoVentec Carrier Board
system coating inaccordance with thetechnical approval andTechnical Data Sheet
fixing element inaccordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-L-Profile
StoFentra Upstand Profile Uni
Sto-Mesh Angle Bead SO
StoFentra Window Sill Profile
StoLevell Uni
Sto-Insulation Board Top32 or Sto-Speed Lamella Type II
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Joint Sealing Tape in accordance with the Technical Data Sheet
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysisX
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1)
2)
connection between end profile and reveal panel in accordance with VR-SAR-0502 to -0503
only Sto-Speed Lamella Type II permitted in non-combustible systems
1)
2)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR-0402
.
Rev. no.Reveal (horizontal section): Connection to a reveal with a set-back window,reveal insulation board fixed with adhesive, and seal bead, with a total systembuild-up ≤ 400 mm
StoVentec Rrainscreen cladding facade
≤ 400
.
≤ 30
0
≥25ca.40
≥ 30
X
wall construction
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Lintel Bracket
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stone Wool InsulationBoard or Sto-Glass WoolInsulation Board withnonwoven fabric facing inaccordance with theTechnical Data Sheet
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Aluminium-L-Profile
StoFentra Upstand Profile Uni
StoFentra Window Sill Profile
Sto-Mesh Angle Bead SO
Sto-PrimerStoLevell Uni
Sto-Insulation Board Top32 or Sto-Speed Lamella Type II
Sto-Seal Bead in accordance with the Technical Data Sheet
1)
2)
connection between end profile and reveal panel in accordance with VR-SAR-0502 to -0503
only Sto-Speed Lamella Type II permitted in non-combustible systems
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysisX
1)
2)
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket
anchoring element in accordance with structuralanalysis
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Edge Protection ProfileG PVC white, 12 mm
StoVentec Carrier Board
Sto-Stainless Steel Lintel Bracket
Sto-Aluminium-L-Profile
X
≥ 25
≈ 40
≥ 25
Reveal (horizontal section): Connection to a reveal with a window flush with thebuilding shell and a total system build-up ≤ 400 mm VR-SAR-0410
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
≤ 400
≤ 30
0
system coating inaccordance with thetechnical approval andTechnical Data Sheet
StoFentra Upstand Profile Uni
StoFentra Window Sill Profile1)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysismin. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1) connection between end profile and reveal panel in accordance with VR-SAR-0502 to -0503
Sto-Mesh Angle Bead SO
X
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
StoVentec Carrier Board
X
≥ 25
anchoring element in accordance with structuralanalysis
Sto-Edge Protection ProfileG PVC white, 12 mm
.
≥ 25
Reveal (horizontal section): Connection to a reveal with a window set forwardfrom the building shell and a reveal depth ≤ 150 mm VR-SAR-0420
≤ 30
0
Sto-Aluminium-L-Profile
≤ 150
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
StoFentra Upstand Profile Uni
StoFentra Window Sill Profile1)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1) connection between end profile and reveal panel in accordance with VR-SAR-0502 to -0503
Sto-Mesh Angle Bead SO
X
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.rigid claddingsrainscreen cladding facade
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
StoVentec Carrier Board
X
≥ 25
anchoring element in accordance with structuralanalysis
Sto-Edge Protection ProfileG PVC white, 12 mm
≈ 40
.
≥ 25
fixing element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
≤ 20
0
≤ 300
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
StoFentra Upstand Profile Uni
StoFentra Window Sill Profile2)
Reveal (horizontal section): Connection to a reveal with a window set forwardfrom the building shell and a reveal depth ≤ 300 mm VR-SAR-0421
1)
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Insulation Dowel orSto-Insulation Dowel DH
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
2) connection between end profile and reveal panel in accordance with VR-SAR-0502 to -0503
1) Join the reveal wall bracket with the facade wall bracket and then fix to the building shell.
Sto-Aluminium-L-Profile
Sto-Mesh Angle Bead SO
X
2)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR- 0430
.
Rev. no.
Reveal (horizontal section): Connection to a reveal with a window flush with thefacade
StoVentec Rrainscreen cladding facade.
≥ 40
.
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
Sto-Stainless Steel Wall Bracket
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Use aSto-Aluminium-L-Profile ifKP is greater than 150 mm.
X
Sto-Edge Protection ProfileG PVC white, 12 mm
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
80 ≤
KP ≤
300
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
KP cantilever length of the StoVentec Carrier Board
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1) Screw the StoVentec Carrier Board onto min. two carrier profile axes.
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
StoVentec Carrier Board
Sto-Stainless Steel Lintel Bracket
Sto-Aluminium-T-Profile
≥ 10
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
X≥
30
≤ 150
≈ 40
≈ 40
.
50-8
5
≈ 5
≥ 10
≈ 25
2)
≥ 25
Sto-Joint Sealing Tape in accordance with theTechnical Data Sheet
Lintel (vertical section): Connection to a lintel with set-back window and a totalsystem build-up ≤ 400 mm VR-SAR-0450
10-20
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Aluminium-L-Profile
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
KT
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
2) screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
≤ 400
≈ 25
X
Use a Sto-Aluminium-T-Profile orSto-Aluminium-L-Profile, depending on theinstallation situation.
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
1)
1) Fix the profile with the L-profile elements without torsional stress and, if necessary, partially notch the webs of the T-profiles.
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
≤ 200≥ 100
≈ 40
≥ 10
50 -
85
≥ 30
Lintel (vertical section): Connection to a lintel with set-back window, a lintelinsulation board fixed with adhesive, and joint sealing tape, with a total systembuild-up ≤ 200 mm VR-SAR-0451
.
10 - 20
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling FacadeScrew with over-tighteningprotection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Stainless Steel Lintel Bracket
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Edge Protection ProfileG PVC white, 12 mm
Sto-Aluminium-L-Profile
StoLevell Uni
Sto-Insulation Board Top32 or Sto-Speed Lamella Type II
Sto-Joint Sealing Tape in accordance with the Technical Data Sheet
X.
≈ 25
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysisX
KT
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1) screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -00632) only Sto-Speed Lamella Type II permitted in non-combustible systems
1)
2)
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
StoVentec Carrier Board
Sto-Stainless Steel Lintel Bracket
Sto-Aluminium-T-Profile
≥ 10
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
X
≈ 40
.
50-8
5
≈ 5
≥ 10
≈ 25
2)
≥ 25
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
Lintel (vertical section): Connection to a lintel with a window flush with thebuilding shell and a total system build-up ≤ 400 mm VR-SAR-0460
10-20
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Aluminium-L-Profile
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
KT
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
2) screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
≤ 400
X
1) Fix the profile with the L-profile elements without torsional stress and, if necessary, partially notch the webs of the T-profiles.
≈ 25
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec Carrier Board
Sto-Aluminium-T-Profile
≥ 10
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
X
≈ 40
.50
-85
1)
anchoring element in accordance with structuralanalysis
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Aluminium-T-Profile
.
≥ 30
2)
Lintel (vertical section): Connection to a lintel with a window set forward fromthe building shell and a lintel depth ≤ 150 mm
aluminium gusst plate in accordance withstructural analysis (already blackened on-site)
system coating in accordance with the technicalapproval and Technical Data Sheet
≥ 25
10-20≤ 150
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
KT
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1) screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
2) lateral free cantilever of the lintel board: ≤ 150 mm
VR-SAR-0470
X
≈ 25
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
≥ 10
≥ 10
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
.X
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Aluminium-T-Profile
StoVentec Carrier Board
anchoring element inaccordance with structuralanalysis
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-L-Profile as two-force member
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
≥ 25
Sto-Aluminium-T-Profile
≈ 40
.
50-8
51)
≥ 10
Sto-Stainless Steel Wall Bracket
≥ 10
system coating in accordance with the technicalapproval and Technical Data Sheet
aluminium gusst plate in accordance withstructural analysis (already blackened on-site)
10-20≤ 300
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
≥ 30
KT
VR-SAR-0471
Lintel (vertical section): Connection to a lintel with a window set forward fromthe building shell and a lintel depth ≤ 300 mm
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -00631)
2)
2) lateral free cantilever of the lintel board: ≤ 150 mm
X
≈ 25
Sto-Edge Protection Profile G PVC white, 12 mm
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
≥ 10
≥ 10
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
VR-SAR-0480
.
Rev. no.
Lintel (vertical section): Connection to a lintel with a window flush with thefacade
StoVentec Rrainscreen cladding facade
.
≥10
≈ 40
≥ 10
50 -
8510
- 20
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
X
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Aluminium-T-Profile
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
.
waterproofing profile with tightly welded-onupstanding edges at the sides (already availableon-site)
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
X
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -00631)
2) Form the upstanding edge and waterproofing profile so that no water can get behind the cladding, leaving the water to run off safely at the front.
1)
2)
KT
≈ 40
alternative: ventilationjoint with Sto-EdgeProtection Profile GT,PVC white, 12 mm
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
24≈
4010
-20 ≈
25
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
.
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
X
≥ 10
.
Window sill (vertical section): Connection to the StoFentra Window Sill Profilewindow sill and StoFentra Upstand Profile Uni with ventilation joint VR-SAR-0502
≥ 10
StoFentra Window Sill Bracket RSC
StoFentra Screw
10-2
0≈
40Sto-Rain Guard Profile G, PVC white, 12 mm
StoFentra Upstand Profile Uni
StoFentra Window Sill Profile
50-8
5
system coating in accordance with the technicalapproval and Technical Data Sheet
StoVentec Carrier Board
Sto-Window Sill Tape
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
KT
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
X
screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
2)
3)
Select a horizontal ventilation joint in accordance with VR-SAR-0503 approx. 5–10 cm narrower than the clear window sill width.
installation to the side of every T-profile web below the window sill
1)
3)
≈ 25
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
2)
1)
30-50
≥ 10
2)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
Window sill (facade surface): Connection to the StoFentra Window Sill Profilewindow sill and StoFentra Upstand Profile Uni with ventilation joint VR-SAR-0503
50 - 100
StoVentec Carrier Board(shown without systemcoating)
Sto-Joint Sealing Tape inaccordance with theTechnical Data Sheet
StoFentra Upstand Profile Uni
StoFentra Screw
StoFentra Window Sill Profile
Sto-Rain Guard Profile G,PVC white, 12 mm
ventilation joint
50 - 100
alternative: ventilation joint with Sto-Roof Vent Profile G, PVC white, 12 mm
10-2
0
≈ 25
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
30 - 50
≥ 10
Window sill (vertical section): Connection to the window sill with window flushwith the facade and ventilation joint VR-SAR-0510
≈ 40
≥ 10
50 -
85
.
.X
KT
flashing (already availableon-site)
Sto-Rain Guard Profile G,PVC white, 12 mm
10 -
20
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling FacadeScrew with over-tighteningprotection (5.5 x 19 mm)
anchoring element inaccordance with structuralanalysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
wall construction
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
Note: Ensuring reliable water flow, wind-proofing, waterproofing, and fixing the windows in accordance with the RAL directive and information of the windowmanufacturer.
1) screw and screw-edge distances and, if necessary, additional screw connection in accordance with VR-SAR-0060 to -0063
1)
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
≈ 25
2) Select a horizontal ventilation joint approx. 5–10 cm narrower than the clear window width.
2)
2)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Aluminium-T-Profile
StoVentec Carrier Board
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
anchoring element in accordance with structuralanalysis
Sto-Aluminium-L-Profile
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
≥ 55
.
VR-SAR-0600
Roller shutter/window blind (vertical section): Connection to a window blind boxwith ventilation joint
≤ 10010 - 20
≥ 25
≥ 10
.
system coating in accordance with the technicalapproval and Technical Data Sheet
Clarify installation, fixing, and coating of theinsulation in the area of the window blind on-site.
window blind box with cover (already availableon-site)
Sto-Edge Protection Profile G PVC white, 12 mm
X
KT
≥ 25Sto-Mesh Angle Bead SO
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
2) free airflow cross-section ≥ 50 cm²/m
Prevent humidity stress on the top of the lintel board by taking structural measures on-site.
≥ 20
alternative: ventilationjoint withSto-Ventilation Profile(coated in black onsite if necessary)
alternative: withSto-Drip Edge Profile
2)
1)
1)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-DE-DE
rainscreen cladding facade StoVentec R
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Aluminium-T-Profile
StoVentec Carrier Board
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
anchoring element in accordance with structuralanalysis
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
.
VR-SAR-0601
Roller shutter/window blind (vertical section): Connection to a window blind boxwith ventilation joint, Sto-Ventilation Profile, and notched T-profile
≥ 10
.
system coating in accordance with the technicalapproval and Technical Data Sheet
Clarify installation, fixing, and coating of theinsulation in the area of the window blind on-site.
window blind box with cover (already availableon-site)
X
KT
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
≥ 40
≈ 40
≤ 20
50 -
85
Sto-Edge Protection Profile G PVC white, 12 mm
Note: Wind-proofing, waterproofing, and fixing the window in accordance with the RAL directive and information of the window manufacturer.
1) depth and length of the notch in the T-profile web subject to structural analysis
2) screw and screw-edge distances in accordance with VR-SAR-0060 to -0063
alternative: withSto-Edge ProtectionProfile GT, PVC white,12 mm
Sto-Ventilation Profile (coated in black on site ifnecessary)
1)
2)
≈ 40
24
Sto-Ventilation Profile(coated in black onsite if necessary)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Stainless Steel Wall Bracket
≈ 40
anchoring element in accordance with structuralanalysis
1)
structural expansion joint
F
..
XX
Structural expansion joint (horizontal section): Structural expansion joint in thefacade surface with Sto-Expansion Joint Profile E VR-SAR-0810
Use a Sto-Aluminium-L-Profile if KP is greaterthan 150 mm.
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Expansion Joint Profile E
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
KP cantilever length of the StoVentec Carrier Board
80 ≤
KP ≤
300
X min. distance to the building shell edge in accordance withthe approval of the anchoring elements and structural analysis
Note: max. seamless field length of the cladding: 25 m
Screw the StoVentec Carrier Board onto min. two carrier profile axes.1)
F joint width: 20 - 30 mm in accordance with anticipateddeformations; installation of the profile in accordance with theTechnical Data Sheet
.≈
40
.
alternative: with Sto-ExpansionJoint Profile E
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
StoVentec Carrier Board
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Stainless Steel Wall Bracket
≈ 40
anchoring element in accordance with structuralanalysis
1)
structural expansion joint
F
..
XX
Structural expansion joint (horizontal section): Open structural expansion joint inthe facade surface with Sto-Edge Protection Profile G VR-SAR-0811
Use a Sto-Aluminium-L-Profile if KP is greaterthan 150 mm.
system coating in accordance with the technicalapproval and Technical Data Sheet
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
KP cantilever length of the StoVentec Carrier Board
80 ≤
KP ≤
300
X min. distance to the building shell edge in accordance withthe approval of the anchoring elements and structural analysis
Note: max. seamless field length of the cladding: 25 m
Screw the StoVentec Carrier Board onto min. two carrier profile axes.
.
≈ 40
.
Sto-Edge Protection Profile G PVC white, 12 mm
joint width: max 20 mm in accordance with anticipated deformationsF
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
wall construction
Sto-Stone Wool Insulation Board RSC withnonwoven fabric facing in accordance with theTechnical Data Sheet
anchoring element in accordance with structuralanalysis
Sto-Aluminium-T-Profile
StoVentec Carrier Board
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
≥ 10
≥ 10
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
5 - 10
≥ 20
≈ 50
.
self-tapping screw made ofstainless steel (e.g. 5.5 x 13mm)
Install the Sto-Fire BarrierProfile so their jointsoverlap by 30 mm.
3)
10
2)
Fire protection (vertical section): Horizontal fire barrier with Sto-Fire BarrierProfile and Sto-Stone Wool Insulation Board with nonwoven fabric facing VR-SAR-0900
system coating inaccordance with thetechnical approval andTechnical Data Sheet
Sto-Stainless Steel Wall Bracket (horizontal axisspacing ≤ 60 cm)
KT
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
Select the distance between the Sto-Fire Barrier Profile and the StoVentec Carrier Board to ensure a free airflow cross-section of 50-100 cm²/m.
1)
2)
Observe national fire protection requirements.
melting point ≥ 1000 °C
3)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
wall construction
anchoring element in accordance with structuralanalysis
Sto-Aluminium-T-Profile
StoVentec Carrier Board
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
≥ 10
≥ 10
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
5 - 10
≈ 50
.≥ 20
self-tapping screw made ofstainless steel (e.g. 5.5 x 13mm)
Install the Sto-Fire BarrierProfile so their jointsoverlap by 30 mm.
3)
≥ 10
≥ 10
2)
Fire protection (vertical section): Horizontal fire barrier with Sto-Fire BarrierProfile and Sto-Glass Wool Board with nonwoven fabric facing VR-SAR-0901
Sto-Glass Wool Board RSC, with nonwoven fabricfacing in accordance with the Technical DataSheet
Install the Sto-Fire BarrierProfile so their profile jointsoverlap by 30 mm(horizontal spacing betweenthe anchoring elements: ≤60 cm).
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
Select the distance between the Sto-Fire Barrier Profile and the StoVentec Carrier Board to ensure a free airflow cross-section of 50-100 cm²/m.
1)
2)
Observe national fire protection requirements.
KT
system coating inaccordance with thetechnical approval andTechnical Data Sheet
2)
melting point < 1000 °C
3)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
wall construction
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Stainless Steel Wall Bracket
Sto-Aluminium-T-Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
anchoring element inaccordance with structuralanalysis
≤ 40
0 m
m / ≤
600
mm
fire wall
≤ 320
VR-SAR-0910
Fire protection (horizontal section): Fire wall with vertical fire barrier made ofstone lamella
StoLevell Uni
Sto-Speed Lamella Type II orSto-Stone Wool Lamella
StoVentec Carrier Board A
system coating inaccordance with thetechnical approval andTechnical Data Sheet
Ensure on-site that no moisture comes between the carrier board and the lamella board, particularly at the upper end of the system.
Markings on the fire barrier due to building physical characteristics cannot be excluded.
1) axis spacing between the T-profiles of max. 60 cm in case of a rated value of the building element resistance at a wind load of ≤ 2.4 kN/m² or max. 40 cmin case of a value of ≤ 3.9 kN/m² respectively (see VR-SAR-0030 and -0031)
1)
2)
3)
2); 3)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
Ceiling (vertical section in longitudinal direction): Connection of the soffit to aStoVentec R facade leading downwards VR-SAR-1000
.
bare ceilingtension-zone-compatibleanchoring element inaccordance with thestructural analysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet KT
KT
≈ 40 ≥ 10
10 -20 50 - 85
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Aluminium-T-Profile
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
wall construction
screw and screw-edge distances in accordance with VR-SAR-0060 to -00632)
observe project-specific requirements for fire resistance where necessary.
2)
1)
≈ 25
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
.
1)
50 -
852)
≈ 40
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
Ceiling (vertical section in transverse direction): Connection of the soffit to aStoVentec R facade leading downwards VR-SAR-1001
10 -20 ≤ 150
≈ 40
≥ 10
≈ 40
bare ceiling
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
50 -
85
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
.KT
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
wall construction
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
screw and screw-edge distances in accordance with VR-SAR-0060 to -00632)
observe project-specific requirements for fire resistance where necessary.
1)2)
≈ 25
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
Ceiling (vertical section in longitudinal direction): Connection of the soffit to aStoVentec R facade leading upwards VR-SAR-1005
.
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element inaccordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling FacadeScrew with over-tighteningprotection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
≈ 40
50 -
85
≥ 10
.
50 - 85 10-20
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
X
X
KT
KT
≥ 10
≈ 40
≈ 25
Sto-Edge Protection ProfileG PVC white, 12 mm
tension-zone-compatible anchoring element inaccordance with the structural analysis
bare ceiling
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
screw and screw-edge distances in accordance with VR-SAR-0060 to -00632)
observe project-specific requirements for fire resistance where necessary.
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
1)
2)
3)
.
.
≥ 10
≥ 10
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
Ceiling (vertical section in transverse direction): Connection of the soffit to aStoVentec R facade leading upwards VR-SAR-1006
.
X
X
bare ceiling
anchoring element inaccordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
≈ 40
≥ 10
.
≈ 40
≥ 10
50 -
85
10-20
≈ 40
.
≥ 10
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
tension-zone-compatible anchoring element inaccordance with the structural analysis
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
KT
80 ≤ KP ≤ 300
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
KP cantilever length of the StoVentec Carrier Board
screw and screw-edge distances in accordance with VR-SAR-0060 to -0063
1)
2)
observe project-specific requirements for fire resistance where necessary.
1)
2)
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
Use a Sto-Aluminium-L-Profile if KP is greater than 150 mm.
≈ 25
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
.
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
VR-SAR-1007
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
Ceiling (vertical section in transverse direction): Connection of the soffit to aStoVentec R facade leading upwards with Sto-Stainless Steel Corner Bracket
.
50-8
5
≈ 40
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
.X
anchoring element inaccordance with structuralanalysis
Sto-Stainless Steel Corner Bracket
Sto-Aluminium-T-Profile
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
≥ 10
≥ 10
≥ 10
≈ 40 10-20
.
≈ 40
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
KT
80 ≤ KP ≤ 300
Use a Sto-Aluminium-L-Profile if KP is greater than 150 mm.
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
KP cantilever length of the StoVentec Carrier Board
screw and screw-edge distances in accordance with VR-SAR-0060 to -0063
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mm
rated value of buildingelement resistance incase of a wind load[kN/m²]
X
≈ 25
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
X
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
wall construction
1)
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
VR-SAR-1008
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
Ceiling (vertical section): Connection of a ceiling projection from the externalwall insulation system to a StoVentec R facade leading upwards
.
wall construction
≈ 40
.
50-8
5
≤ 20
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
X
X
≥ 10
KT
..
.
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Edge Protection Profile G PVC white, 12 mm
Sto-Ventilation Profile (adjust projection on siteand coat in black if necessary)
Apply StoFlexyl twice as slurry.
insulation wedge
Sto-Drip Edge Profile
Sto-Render Carrier Board, 20 mm
plate-equipped anchor
external wall insulation system made from speed lamella
L
1/3 L (≤ 400)2/3 L
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
1)
screw and screw-edge distances in accordance with VR-SAR-0060 to -00632)
3)
1)
2)
3)
depth and length of the notch in the T-profile web subject to structural analysis
ratio of the projection length of the render carrier board to the length of the bonding based on the leading edge of the building shell: 1/3 to 2/3
L edge length of the Sto-Render Carrier Board
.
anchors in accordance with technical approval
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
VR-SAR-1010
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
Ceiling (vertical section in longitudinal direction): Connection of the soffit to aStoVentec panel facade leading downwards
≈ 40 ≥ 10
50-85
KT
Sto-Edge Protection Profile G PVC white, 12 mm
Sto Drilling Screw stainless steel (5.5 x 24 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
10 - 20
adjustment screw
Sto-Board Carrier Profile
fixing in accordance with technical approvaland/or structural analysis
StoVentec Aluminium Agraffe Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stainless Steel Wall Bracket
anchoring element in accordance with structuralanalysis
wall construction
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec panel
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
Rdistance between the board carrier profile and the edge of the StoVentec panel in accordance with technical approval, structural analysis, andproject-specific planning
.R
screw and screw-edge distances in accordance with VR-SAR-0060 to -00632)
observe project-specific requirements for fire resistance where necessary.
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
bare ceiling1)
2)
≈ 25
.
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
VR-SAR-1011
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
Ceiling (vertical section in transverse direction): Connection of the soffit to aStoVentec panel facade leading downwards
Sto-Edge Protection Profile G PVC white, 12 mm
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
10 - 20
adjustment screw
Sto-Board Carrier Profile
fixing in accordance with technical approvaland/or structural analysis
StoVentec Aluminium Agraffe Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stainless Steel Wall Bracket
anchoring element in accordance with structural analysis
wall construction
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
StoVentec panel
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
Rdistance between the board carrier profile and the edge of the StoVentec panel in accordance with technical approval, structural analysis, andproject-specific planning
.R
1) observe project-specific requirements for fire resistance where necessary.
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
bare ceiling1)
≈ 25
≤ 150
≈ 40
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
VR-SAR-1015
Ceiling (vertical section in longitudinal direction): Connection of the soffit to theStoVentec panel facade leading upwards
≥ 10
≈ 40
≥ 10 ≥ 10
≥ 10
50-85
.
.
bare ceiling
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheetanchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
StoVentec panel
Sto-Board Carrier Profile
fixing in accordance withtechnical approval and/orstructural analysis
StoVentec Aluminium Agraffe Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
X
X
Install the folded aluminiumsheet (already availableon-site) as flashing withouttorsional stress.
Sto-Edge Protection ProfileG PVC white, 12 mm
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Aluminium-L-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
KT
R
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
Rdistance between the board carrier profile and the edge of the StoVentec panel in accordance with technical approval, structural analysis, andproject-specific planning
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
1)
2)
2)
observe project-specific requirements for fire resistance where necessary.
screw and screw-edge distances in accordance with VR-SAR-0060 to -0063
.
.
1)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
VR-SAR-1016
Ceiling (vertical section in longitudinal direction): Connection of the soffit to aStoVentec Glass facade leading upwards
≥ 10
≈ 40
≥ 10
≥ 10
50-85
.
bare ceiling
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysis
Sto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
StoVentec Glass
Sto-Board Carrier Profile
StoVentec Aluminium Agraffe Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
X
X
Install the folded aluminiumsheet (already availableon-site) as flashing withouttorsional stress.
Sto-Edge Protection ProfileG PVC white, 12 mm
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Sto-Aluminium-L-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
KT
R
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
Rdistance between the board carrier profile and the edge of the StoVentec panel in accordance with technical approval, structural analysis, andproject-specific planning
X min. distance to the building shell edge in accordance with the approval of the anchoring elements and structural analysis
1)
3)
observe project-specific requirements for fire resistance where necessary.
screw and screw-edge distances in accordance with VR-SAR-0060 to -0063
≥ 10
.
≥ 10
≤ 40
3)
Depending on the light, the colour shade of the glass projection may differ from that of the glass panel.
.
.
2)
1)
2)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Rev. no. 2017-06-01
.
Sto-HQ-EN
rainscreen cladding facade StoVentec R
VR-SAR-1017
Ceiling (vertical section in transverse direction): Connection of the soffit to aStoVentec panel facade leading upwards
.
.
.
bare ceiling
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
anchoring element in accordance with structuralanalysisSto-Stainless Steel Wall Bracket
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Aluminium-T-Profile
StoVentec panel
Sto-Board Carrier Profile
fixing in accordance with technical approvaland/or structural analysis
StoVentec Aluminium Agraffe Profile
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
X
X
Install the folded aluminiumsheet (already availableon-site) as flashing withouttorsional stress.
Sto-Edge Protection ProfileG PVC white, 12 mm
Sto Drilling Screw stainless steel (5.5 x 24 mm)
Use a Sto-Aluminium-L-Profile if KP is greater than 150 mm.
StoVentec Carrier Board
system coating in accordance with the technical approval and Technical Data Sheet
KP
R
KP cantilever length of the StoVentec Carrier Board
R distance between the board carrier profile and the edge of theStoVentec panel in accordance with technical approval,structural analysis, and project-specific planning
X min. distance to the building shell edge in accordance withthe approval of the anchoring elements and structural analysis
1)
≈ 40
.
150
200
3,3
3,9
-
300 2,4
L-profilemax. KP in mmrated value of buildingelement resistance incase of a wind load[kN/m²]
X
X
P min. pair spacing in accordance with the approval of theanchoring elements and structural analysis
observe project-specific requirements for fire resistance where necessary.
Sto-Aluminium-L-Profile with Sto-ThermalBlocking Element
.P
aluminium folded profile (already availableon-site)
1)
≥ 10≥ 10
≈ 40
.X
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
Ceiling (vertical section in longitudinal direction): Connection of the soffit to anexternal wall insulation system leading downwards VR-SAR-1030
≈ 40 ≥ 10
10 -20 50 - 85
KT
Sto-Edge Protection Profile G PVC white, 12 mm
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stainless Steel Wall Bracket
≈ 25
external wall insulation system in accordancewith system approval
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
bare ceiling
KT cantilever length of the Sto-Aluminium-T-Profile in accordance with structural analysis (see also VR-SAR-0040 and -0041)
Complete external wall insulation system before installing the rainscreen cladding facade (RSC).
screw and screw-edge distances in accordance with VR-SAR-0060 to -0063
3)
observe project-specific requirements for fire resistance where necessary.
1)
2)
.
2)
1)
3)
© S
to S
E &
Co. K
GaA
Note: This drawing is a general, non-binding planning suggestion which depicts the execution only schematically, but is no substitute for the required working and detail drawing as well asthe installation plans. The applicator/planner/customer is independently responsible for determining the suitability, completeness and dimensions of the product for the particularconstruction project. Neighbouring works are described only schematically. All specifications and assumptions must be adjusted or agreed in the light of local conditions. Compliance withthe technical specifications contained in the Technical Data Sheets, application guidelines, and system approvals is mandatory.
Sto-HQ-EN
2017-06-01
.
Rev. no.StoVentec Rrainscreen cladding facade
Ceiling (vertical section in transverse direction): Connection of the soffit to anexternal wall insulation system leading downwards VR-SAR-1031
Sto-Edge Protection Profile G PVC white, 12 mm
tension-zone-compatibleanchoring element inaccordance with thestructural analysis
Sto-Stone Wool Insulation Board or Sto-GlassWool Insulation Board with nonwoven fabricfacing in accordance with the Technical DataSheet
Sto-Aluminium-T-Profile
StoVentec Carrier Board
system coating in accordance with the technicalapproval and Technical Data Sheet
Sto-Self-Drilling Facade Screw withover-tightening protection (5.5 x 19 mm)
Sto-Stainless Steel Wall Bracket
≈ 25
external wall insulation system in accordancewith system approval
alternative: ventilationjoint with Sto-RoofVent Profile G, PVCwhite, 12 mm
bare ceiling
Complete external wall insulation system before installing the rainscreen cladding facade (RSC).
observe project-specific requirements for fire resistance where necessary.
1)
≈ 40
10 -20 ≤ 150
Sto Drilling Screw stainlesssteel (5.5 x 24 mm)
2)
1)
2)