+ All Categories
Home > Documents > Detailed Specifications shall be based on the existing CPRI backbone TCP/IP network with VPN-enabled...

Detailed Specifications shall be based on the existing CPRI backbone TCP/IP network with VPN-enabled...

Date post: 06-Feb-2021
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
35
DATB Specifications Page 1 of 35 CPRI Tender Specification No. CPRIBLR18MUAD39C120 Detailed Specifications Distribution Automation Test Bed (DATB) “This Tender Document shall be used only for the purpose of responding to this tender and cannot be used for any other purpose without written consent from CPRI.”
Transcript
  • DATB Specifications

    Page 1 of 35 CPRI

    Tender Specification No. CPRIBLR18MUAD39C120

    Detailed Specifications

    Distribution Automation Test Bed (DATB)

    “This Tender Document shall be used only for

    the purpose of responding to this tender and

    cannot be used for any other purpose without

    written consent from CPRI.”

  • DATB Specifications

    Page 2 of 35 CPRI

    19 M

    ar 2

    018

    Contents 1 Introduction .......................................................................................................................................... 5

    2 Abbreviations ........................................................................................................................................ 5

    3 Intended uses for the DATB .................................................................................................................. 6

    3.1 Exercise the DATB Use Cases ........................................................................................................ 6

    3.2 Demonstrate and Verify Distribution Automation functions ....................................................... 6

    3.3 Interoperability Testing ................................................................................................................. 7

    3.3.1 CIM Compliance of DA Controls per IEC 61968 .................................................................... 7

    3.4 Parts of the Distribution Automation Test Bed ............................................................................ 8

    3.4.1 A Generic Integration Model ................................................................................................ 8

    3.4.2 Small scale transient simulation ........................................................................................... 8

    3.4.3 Larger scale distribution simulation ...................................................................................... 8

    3.4.4 Integration with the SituTB SCADA/ADMS system ............................................................... 8

    3.4.5 Integration with the 11kV transformer pad .......................................................................... 8

    3.4.6 Integration with the substations ........................................................................................... 8

    3.4.7 Analysis tools ......................................................................................................................... 8

    4 DATB Components ................................................................................................................................ 9

    4.1 General Requirements for Substation Equipment ........................................................................ 9

    4.2 Small Scale Simulation ................................................................................................................ 11

    4.2.1 Small Scale Simulator specification: .................................................................................... 11

    4.2.2 Interface from Simulator to SCADA/ADMS ......................................................................... 11

    4.3 Large Scale Simulation ................................................................................................................ 12

    4.3.1 Required for Large Scale Simulation ................................................................................... 12

    4.3.2 Integration with SituTB SCADA/ADMS ................................................................................ 12

    4.4 Integration with SGTB 11kV transformer pad physical switchgear ............................................ 13

    4.4.1 Recommended 11kV equipment for the Transformer Pad (11kV Line Hardware) (supply of

    these items are not in the scope of this tender; however information is provided for ease of

    integration with these devices; the selected bidder shall support for integration with these items;

    these items will be procured through separate tender or CPRI will arrange these items) ................. 13

    4.5 Generic Integration Model .......................................................................................................... 15

    4.5.1 Uninterruptible Power Supply ............................................................................................ 16

    4.6 Analysis tools............................................................................................................................... 16

  • DATB Specifications

    Page 3 of 35 CPRI

    19 M

    ar 2

    018

    4.6.1 SCADA Simulator ................................................................................................................. 16

    4.6.2 Station Level Computer....................................................................................................... 17

    4.6.3 Gateway .............................................................................................................................. 17

    4.6.4 Time Reference (supply scope covered under Situational Awareness test bed part of this

    tender) 18

    4.6.5 Power Supply ...................................................................................................................... 18

    4.6.6 LAN Ethernet Switch ........................................................................................................... 18

    4.6.7 Portable Notebook Computers (2 recommended): ............................................................ 19

    4.6.8 Router ................................................................................................................................. 19

    4.7 Miscellaneous and Spare Parts ................................................................................................... 20

    5 RTU Specification ................................................................................................................................ 20

    5.1.1 Data Acquisition .................................................................................................................. 20

    5.1.2 Estimating RTU Point Count ................................................................................................ 23

    5.1.3 RTU Architecture ................................................................................................................. 23

    5.1.4 Power Supply ...................................................................................................................... 26

    5.1.5 Local Control Panel ............................................................................................................. 27

    5.1.6 RTU Software ...................................................................................................................... 28

    5.1.7 Enclosures ........................................................................................................................... 29

    6 Physical Structure (Rack)r ................................................................................................................... 29

    7 Communication Network .................................................................................................................... 30

    7.1 Network Performance Requirements ......................................................................................... 30

    7.2 Connection from DATB to the SGTB external transformer pad .................................................. 31

    7.2.1 Fiber Link Specification ....................................................................................................... 31

    7.3 SNMP Manager ........................................................................................................................... 31

    7.4 Redundancy Requirements ......................................................................................................... 32

    7.5 Cyber Security Requirements for Distribution Automation ....................................................... 32

    8 Reliability and Availability vs. Flexibility .............................................................................................. 32

    9 Contracting Options ............................................................................................................................ 32

    10 Feature Quantities: ............................................................................................................................. 33

    11 Mapping Functions to Features (only for information) ....................................................................... 33

  • DATB Specifications

    Page 4 of 35 CPRI

    19 M

    ar 2

    018

    Figures Figure 3-1 Interoperability Context-Setting Framework, aka GWAC Stack .................................................. 7

    Figure 4-1: DATB Components .................................................................................................................... 10

    Figure 4-2 11kV Equipment on SGTB Transformer Pad ............................................................................. 14

    Figure 4-3 Communications using VPN across the SituTB, DATB, and SASTB over the CPRI network and

    cellular connections. ................................................................................................................................... 16

    Figure 6-1 Rack mounts for DATB Equipment ............................................................................................ 30

    Tables

    Table 2-1 Abbreviations ................................................................................................................................ 6

    Table 10-1 DATB Features List .................................................................................................................... 33

    Table 11-1 Selection options for each Feature ........................................................................................... 34

    Table 11-2 Function dependency on Features ........................................................................................... 35

  • DATB Specifications

    Page 5 of 35 CPRI

    19 M

    ar 2

    018

    1 Introduction The Distribution Automation Test Bed (DATB) consists of all equipment, devices, and software

    associated with information flow within the test bed. In this respect, the DATB includes

    Small scale transient simulation of a section of the power grid using one or more Relay Test Sets

    for the simulation of distribution faults and automation actions (like the remote/ auto control

    functions used in distribution automation).

    Integration with the CPRI Power Systems Laboratory RTDS and Opal-RT simulators for larger and

    more complex simulations over LAN.

    Integration with the Situational Awareness Test Bed SCADA/ADMS system.

    Integration of distribution hardware installed on the SGTB transformer pad for visual

    demonstration of automated and remote control of feeder switchgear.

    Instrumentation used to test and verify conformance of DA devices to relevant standards.

    (Supply of instrumentation for this purpose is not in the scope of supply in this tender)

    Devices and fixtures needed to realize the integration of DATB with physical signals, including

    o Networking equipment

    o Remote Terminal Units

    o Smart power meters

    o Intelligent field device controls such as recloser, load break switch, and Communicating

    Fault Passing Indicator interface controls.

    This document provides the DATB specification. Conceptual Logical and Physical architectures of the

    Distribution Automation System are suggested.

    A brief background of the whole project is attached as Annex – 1 for reference and Pre-bid Meeting details are attached as Annexure 2.

    2 Abbreviations

    Term Meaning

    CCTB Communications and Computing Test Bed

    DATB Distribution Automation Test Bed

    DERTB Distributed Energy Resources Test Bed

    EVTB Garage of the Future Test Bed

    HANTB Home Area Network Test Bed

    HSR High-availability Seamless Redundancy (IEC 62439-3 clause 5)

    MOAB Motor operated air breaker

  • DATB Specifications

    Page 6 of 35 CPRI

    19 M

    ar 2

    018

    Term Meaning

    PRP Parallel Redundancy Protocol (IEC 62439-3 clause 4)

    PSTB Power System Test Bed

    SASTB Substation Automation System Test Bed

    SituTB Situational Awareness Test Bed

    SNMP Simple Network Maintenance Protocol

    SNTP Simple Network Time Protocol

    Table 2-1 Abbreviations

    3 Intended uses for the DATB

    3.1 Exercise the DATB Use Cases

    Per the Conceptual Design Report (SGTB Task 5) the DATB will support the following use cases:

    6 - Distribution Automation Test Bed Use Cases

    6.1 FLISR & FDI

    6.2 Volt-VAR Control

    6.3 Reconfiguration of the circuit on overloading scenario.

    6.4 Load shedding

    6.5 CIM compliance for DMS as per IEC 61968

    6.6 Demo field device operation on the SGTB Transformer Pad

    6.7 Observe 220kV and 33kV substation operation

    3.2 Demonstrate and Verify Distribution Automation functions

    The DATB will be used to stage simulated interconnecting distribution feeders to observe grid behaviour

    under load, fault and overload conditions. An overlay of RTU and physical distribution automation

    controls will interact with the simulations, allowing the analysis of the effectiveness of the automation

    scheme, the expected time span required for operation and reduction of outage time due to DA

    operation, improvement in Key Performance Indicators (SAIDI, SAIFI, CAIDI, etc. computed by the SituTB

    SCADA/ADMS), and the quality of the information available to distribution system operators and field

    service technicians. SGTB will demonstrate the remote operation of field devices by operating the

    switchgear installed on the SGTB transformer pad just outside the building.

    DATB will install Router, RTU, and selected equipment in the 33kV on campus and 220kV off campus

    substations for observation of the operation of the real power grid.

  • DATB Specifications

    Page 7 of 35 CPRI

    19 M

    ar 2

    018

    Demonstration of these techniques will be of value to CPRI associates interested in employing the

    methods on their own distribution grids, and in educational opportunities for utility and academic

    associates.

    3.3 Interoperability Testing

    In addition to conformance testing of the above standards, DATB will be used to verify Interoperability

    of multiple vendor devices within the DATB. Interoperability is categorized by the GridWise Architecture

    Council Interoperability Context Stack (GWAC Stack). The GWAC Stack separates interoperability issues

    into basic contexts:

    Figure 3-1 Interoperability Context-Setting Framework, aka GWAC Stack

    The lower four layers of the GWAC Stack map well to laboratory testing procedures:

    Basic connectivity deals with connector type, media type, electrical parameters, etc.

    Network IOP addresses the ability of signals to move correctly through the IT network.

    Syntactic IOP deals with syntax used to form messages and message parts.

    Semantic Understanding addresses the ability of different devices to make good use of the

    shared information. CIM is intended to simplify the semantic understanding between active

    devices in the distribution system.

    3.3.1 CIM Compliance of DA Controls per IEC 61968

    IEC 61968 specifies the Common Information Model (CIM) for distribution applications. This set of

    coordinated standards defines architecture, records management, information format for exchange

    between devices and systems applied to the utility distribution system, and other details related to the

    consistent treatment of information to ease integration and interoperability. Hardware and software are

    specified allowing SGTB technicians to observe and log these information flows for IEC 61968

    compliance determination.

  • DATB Specifications

    Page 8 of 35 CPRI

    19 M

    ar 2

    018

    Interoperability Testing requires the staging of devices, systems, and software from different vendors

    and verifying that these devices interoperate in reliable and predictable ways. The DATB will provide the

    structures and fixtures to facilitate this type of testing.

    3.4 Parts of the Distribution Automation Test Bed

    The DATB consists of the following parts:

    3.4.1 A Generic Integration Model

    Used for integrating CPRI facilities and laboratories into the DATB.

    3.4.2 Small scale transient simulation

    Simulation of interconnected distribution feeders interfaced to the Situational Awareness Test Bed

    SCADA/ADMS system. This small scale simulator is realized by a relay test set with sufficient analog

    outputs and digital simulation of up to 20 distribution buses with feeder loads, front-ended with the

    Generic Integration Model.

    3.4.3 Larger scale distribution simulation

    Simulation of more complex distribution feeder configurations. This larger scale simulation is realized by

    integration of the DATB and SituTB with the existing CPRI Power Systems Lab RTDS and Opal-RT

    simulators, physical distribution field controls, Hardware in Loop testing, using the Generic Integration

    Model and the CPRI IP network.

    3.4.4 Integration with the SituTB SCADA/ADMS system

    Integration with SituTB using the CPRI network and the Generic Integration Model Router and RTU.

    3.4.5 Integration with the 11kV transformer pad

    Integration with physical switchgear devices located on the SGTB building transformer pad for

    demonstration and verification of the operation of field devices by automated control and distribution

    operator command, using a 12-strand fiber optic network link, GIM Router/VPN, RTU, and other field

    controls.

    3.4.6 Integration with the substations

    Integrate the remote 220kV substation using the router cell modem and the local 33kV substation using

    the router on the CPRI campus network. Modernization hardware in both substations is assumed from

    another project.

    3.4.7 Analysis tools

    Hardware and software ools for the capture and analysis of information flows throughout the DATB

    between field components, field to station, and field to distribution control center.

    DATB will interact with the Situational Awareness Test Bed (SituTB), the Substation Automation Test Bed

    (SASTB), and the CPRI Power Systems Lab for evaluation of automation system performance in selected

    testing scenarios. Other on and off campus locations may be added using the Generic Integration Model.

  • DATB Specifications

    Page 9 of 35 CPRI

    19 M

    ar 2

    018

    4 DATB Components DATB shall be configured as indicated in figure 4-1. Integration of the several components of the DATB

    shall be based on the existing CPRI backbone TCP/IP network with VPN-enabled Routers and RTUs.

    4.1 General Requirements for Substation Equipment

    Station Level IEDs shall provide at least (2) Ethernet ports for redundant connection to the Dual Station

    LAN and for support of PRP and HSR.

    Station Level IEDs shall support IEC 61850 and other international standards, particularly:

    61850-3 General requirements (electrical and environmental stresses)

    61850-8-1 Publish and subscribe to GOOSE messaging by Ethernet Multicast

    61850-9-2 Subscribe to Sampled Value Streaming by Ethernet Multicast

    61850-9-3 Time synch per IEEE-1588

    61850-90-1 Inter-substation GOOSE messaging publication and subscription

    61850-90-2 Station to control center GOOSE messaging publication and subscription

    61850-90-5 Routing of GOOSE messages, SV streams, and synchrophasor streams outside of

    the Local Area Network

    62351 Support for Device Level Security including user authentication, multiple user

    roles, user role based functional authorization, and protected firmware revision

    62439-3 support for HSR network loops and PRP on dual station and process LAN

  • DATB Specifications

    Page 10 of 35 CPRI

    19 M

    ar 2

    018

    Figure 4-1: DATB Components

    DATB

    Generic Integration Model to Power System Lab

    Transformer Pad using fiber link

    SituTB

    Small Scale Simulation

    Small SCADA/ADMS Display (2x2)

    SCADA/ADMS

    Display Control

    OperatorOperator

    Large Scale Simulation

    IED

    FPI

    Recloser

    RMU

    LBS

    RTU

    CPRI Campus Network

    Analysis ToolsAnalysis Tools

    Routerw/Gateway

    VPNIEC-104

    RouterVPN

    RouterVPN

    RouterVPN

    Fiber LinkIEC-104

    Wireless Link

    RTU IEC-104

    IED

    RTUIEC-104

  • DATB Specifications

    Page 11 of 35 CPRI

    19 M

    ar 2

    018

    4.2 Small Scale Simulation

    Small Scale Simulation components shall be under complete control of the DATB staff. The simulator

    shall execute on Relay Test Set hardware with transient simulation capability.

    Distribution control equipment can be exercised using Relay Test Sets. The addition of simulation

    software to the test set permits more complex circuit interactions to be analysed. For example, an

    ADMS FLISR test would start with a simulation model of a circuit with protection circuit breaker and

    remotely controllable feeder switchgear. With switchgear controllers in the simulation loop, ADMS can

    issue commands through a SCADA IEC 60870-5-104 interface to locate the fault, isolate the faulted

    section, and restore service to the maximum number of customers.

    Signal Generation requirements depend on the extent of excitation of the controls required for the

    desired set of tests. (6) current and (4) voltage analog outputs can excite IEDs, metering, and field

    control devices such as Recloser, Load Break Switch, and Voltage Regulator controls. Additional

    synchronized analog or sampled value (merging units modelled in a simulator and injected into an IED

    through a local area Ethernet network) can expose more complex interactions.

    4.2.1 Small Scale Simulator specification:

    Signal Generator Programmable by connected Windows laptop computer

    Hardware In Loop capability

    COMTRADE playback

    Test scripting

    Time synchronization per 61850-9-3 (IEEE 1588 PTP)

    (6) current channels with 32 amp capacity, error =32) 61850 GOOSE messages from Device Under Test

    4.2.2 Interface from Simulator to SCADA/ADMS

    Simulator output shall be fed to different electronic devices, which in turn will be interfaced to the

    SCADA/ADMS system in the SituTB using IEC 60870-5-104 (or IEC-104) protocol. Distribution system

    conditions read by SCADA polls are available to ADMS; ADMS functions issue commands that are passed

  • DATB Specifications

    Page 12 of 35 CPRI

    19 M

    ar 2

    018

    through SCADA to the distribution automation equipment; the DA equipment feed into the simulator to

    alter the simulation results.

    Interface devices include

    IEC-104 RTU per the section 5 RTU specification

    IEC-104 Power meter or IED that can be polled directly by SCADA

    IEC-103 Power meters and IEDs with a -104 to -103 Gateway

    61850 IEDs per SASTB specification with IEC-104 to 61850 Gateway

    IEC 60870-5 Field Controllers for DA hardware with Gateway as needed

    This minimum configuration will allow the transient simulation of simpler distribution feeder

    configurations with smart field control hardware elements in the control loop of the simulator. The

    exercise of the Distribution Automation equipment coupled with protocol analysis tools will allow the

    capture and analysis of information exchanges, enabling the technician to evaluate conformance of the

    device under test to standards, including IEC-104 SCADA protocol and IEC 61968 information modelling.

    4.3 Large Scale Simulation CPRI has an on-campus Power Systems Laboratory with extended simulation capability. An existing mid-

    scale RTDS system, and a new large-scale Opal-RT system, are not under full control of SGTB staff, but

    are available for SGTB use on a scheduled basis. However, the Power System Laboratory is in another

    building on the CPRI Bangalore campus.

    CPRI has an existing high-speed IP network that extends throughout the campus. This network will be

    used for the IEC 60870-5-104 SCADA operation. By locating SCADA-compatible hardware in a Hardware-

    in-the-Loop (HIL) configuration on the Power System Laboratory simulators, SCADA/ADMS is able to

    reach out to the Power System Lab to remotely execute ADMS operations.

    Access to the Power Systems Lab over the CPRI network shall be through the application of the GIM

    Routers configured to create a Virtual Private Network (VPN) between the SituTB and the Power

    Systems Lab. The smart digital controls used in DA testing in the Small Scale Simulation may be moved

    to the Power System Lab and connected to SCADA/ADMS by VPN over the campus network.

    4.3.1 Required for Large Scale Simulation

    Power System Lab simulators must have distribution equipment modeling capabilities. If not

    existing already, buy those components from the simulator supplier (RTDS or Opal-RT).

    CPRI backbone IP network for communication from SGTB to Power Systems Lab.

    Generic Integration Model Router and

    60870-5-104 SCADA compatible field devices as specified in section 4.1.2.

    4.3.2 Integration with SituTB SCADA/ADMS

    SituTB SCADA system will employ IEC 60870-5-104 SCADA protocol. This protocol is compatible with

    network communication and will be connected to the CPRI campus IP network. Locating IEC-60870-5-

    104 compatible devices at the Power Systems Lab will allow SCADA to poll a simulation of distribution

  • DATB Specifications

    Page 13 of 35 CPRI

    19 M

    ar 2

    018

    circuits to enable ADMS functions such as FLISR and Volt-VAR Control. Integration with the IEC 60870-5-

    104 SCADA system may require the use of a Gateway device as an intermediary between -104 and the

    IED protocol (IEC 60870-5-103 or IEC 61850).

    On occasion the interface will support Distributed Energy Resources modelled on the simulator. In such

    cases, the Gateway will support the transition from IEC 60870-5-104 to the protocol supported by the

    DER device.

    4.4 Integration with SGTB 11kV transformer pad physical switchgear

    11kV switchgear located outside the SGTB building on the SGTB building power transformer pad will be

    accessed by installing an RTU on the pad. Additional equipment such as power meter, power quality

    meter, revenue meter, and 61850 merging unit may also be located in that enclosure and interfaced to

    potential and current transformers on the low voltage side of the pad mount transformer to observe

    building load. The transformer pad equipment shall be mounted in a weather tight enclosure of

    sufficient size to avoid crowding or overheating of the equipment, with power and control signal cabling

    to the pad switchgear, and twelve-strand fiber optic network cabling back to the SGTB building DATB

    space (see section 6.2). The transformer pad RTU is as specified in section 5 below.

    4.4.1 Recommended 11kV equipment for the Transformer Pad (11kV Line Hardware) (supply of

    these items are not in the scope of this tender; however information is provided for ease of

    integration with these devices; the selected bidder shall support for integration with these

    items; these items will be procured through separate tender or CPRI will arrange these items)

    CPRI desires the installation of 11kV switchgear on the transformer pad just outside the SituTB space.

    This equipment shall be positioned such that the status indications of the devices are visible from the

    South West window of the SituTB area (room 13), and shall be cabled into the SCADA/ADMS system so

    that the switchgear can be operated both by operator command and on certain ADMS functions (e.g.

    opening a physical device in the process of managing a simulated distribution automation operation).

    The equipment is to include (see Figure 4.2)

    (9) 11kV overhead mounted Wireless Communicating Fault Passing Indicators

    (1) 11kV pole mounter overhead 3-phase Recloser and auto-reclose controller

    (1) 11kV 3-position 3-phase Compact Ring Main Unit with internal RTU and power meters

    (1) 11kV Sectionalizer realized as a 3-phase Load Break Switch with LBS controller

    (5) 11kV overhead distribution poles with crossarms, brackets, insulators, riser cabling,

    overhead conductors, and all required hardware to mount the above equipment.

  • DATB Specifications

    Page 14 of 35 CPRI

    19 M

    ar 2

    018

    Figure 4-2 11kV Equipment on SGTB Transformer Pad

    4.4.1.1 Wireless Communicating Fault Passing Indicator

    The Fault Passing Indicator (FPI) is used in MV distribution circuits as an inexpensive indicator that fault

    current has been observed on the circuit. These are often located at single-phase taps from a 3-phase

    overhead circuit, helping line crews to trace the direction to the fault. The DATB will host a total of nine

    (9) FPI, located at three locations on the 3-phase overhead conductors. Since little or no current will flow

    in the overhead conductors, the FPIs must have rechargeable battery powered supplies.

    4.4.1.2 AutoRecloser

    An AutoRecloser is a fault-interrupting device installed on 3-phase circuits, configured to open the

    circuit if fault current is observed, followed by configurable attempts to reclose the circuit. The recloser

    has a controller located nearby that monitors voltage and current on the feeder and determines, based

    on protection settings, when to open and reclose the circuit. Reclosers can be manually operated locally

    by a lineman or remotely by SCADA/ADMS for reasons other than fault current (e.g. circuit

    reconfiguration).

    11kV Power Transformer

    Compact RMU

    LBSRecloser3 FPI 3 FPI 3 FPI

    Recloser Control

    LBS Control

    Enclosure

    NetworkSwitch

    RTUGateway

    MUFPI Receiver

    3-Phase 11kV Test Circuit

    3-Phase 11kV ServiceSGTB Building

    3-Phase 440V Service

    12 strand fiber

    IEC 61850

    Fiber Termination

    SituTB

    SASTB

    DATB

    CCTB

    Compact RMU

    Distrib

    utio

    n P

    ole

    Distrib

    utio

    n P

    ole

    Distrib

    utio

    n P

    ole

    Distrib

    utio

    n P

    ole

    Distrib

    utio

    n P

    ole

    Fiber Termination

    IEC 60870-5-104

  • DATB Specifications

    Page 15 of 35 CPRI

    19 M

    ar 2

    018

    4.4.1.3 Ring Main Unit

    A Ring Main Unit (RMU) is a switching device that allows the utility to remotely or locally connect and

    disconnect multiple circuits from a small section of bus. The RMU can act as a tap point for a distribution

    transformer, a sectionalizing switch, or a distribution automation element for reconfiguring a circuit.

    An automated (motor driven with remote control) 3-position Ring Main Unit (RMU) shall be located on

    the transformer pad such that a viewer from the SGTB building can see the front panel indications of

    switch state when the cabinet doors are open. The RMU positions shall be individually observable and

    controllable by commands issued through the SituTB SCADA/ADMS system.

    4.4.1.4 Sectionalizer

    A Sectionalizer is a switching element that allows a circuit to be opened, isolating the downstream

    section of the circuit from the upstream section. Sectionalizing may be accomplished with a load break

    switch (LBS) when normal load current is flowing, or may only be able to operate on a de-energized

    circuit with no current flow at the time of opening. Sectionalizers often include automation to open the

    switch in case of a loss of voltage due to the opening of an upstream circuit breaker, thus isolating any

    downstream fault an allowing the circuit breaker to be closed.

    The Sectionalizer to be installed on the SGTB Transformer Pad shall include a communication controller

    allowing local or remote operation by SCADA/ADMS, and shall automatically open upon a loss of voltage

    resulting from operation of the upstream Recloser or RMU.

    4.5 Generic Integration Model CPRI is home to a large number of test laboratories dedicated to specialization in particular areas of

    power system engineering. The Generic Integration Model (GIM) is a model for a simple, repeatable

    interface from DATB and SituTB on the campus network to other labs around the campus. The Generic

    Integration Model uses the campus network for communications when available, placing integrating

    components at remote locations for short or long term observation and/or control of other test

    environments. Communication shall be established over a Virtual Private Network (VPN), isolating the

    DATB device communications from the rest of the CPRI network. Where the campus network is not

    readily available, an integral cellular modem I the Router can be used to establish the VPN. Modification

    to the CPRI DMZ by CPRI IT personnel will be required to allow this temporary VPN connection from

    devices using the cellular connection (see figure 4.3).

  • DATB Specifications

    Page 16 of 35 CPRI

    19 M

    ar 2

    018

    Figure 4-3 Communications using VPN across the SituTB, DATB, and SASTB over the CPRI network and cellular connections.

    The Generic Integration Model locates a set of integration hardware at the remote location, connected

    to the SituTB/DATB with a VPN. A small RTU provides the most basic input and output needed to

    integrate the remote site with SituTB/DATB for observation and control. More sophisticated interface

    may be enabled by application of additional IED hardware.

    4.5.1 Uninterruptible Power Supply

    The GIM shall include an uninterruptible power supply (UPS – see section 4.6.5.1) able to operate the

    GIM for a minimum of 1 hour after loss of grid power, and a 19” 45U rack for the mounting of GIM

    devices (see section 6).

    4.6 Analysis tools

    4.6.1 SCADA Simulator

    In most cases, SCADA/ADMS functions shall be provided by integrating with the SituTB SCADA/ADMS

    system. In some cases it may simplify configuration to use a SCADA simulation tool. This tool would be a

    test set for the SCADA protocol – IEC 60870-5-104 or DNP3 – acting as the Master and issuing control

    commands to the system under test.

    SASTB DATB

    Situational Awareness Test Bed – System Components

    SCADA

    CollectProcess

    Store

    Data Acquisition Front End

    (DAFE)

    Web Server System(WSS)

    ADMS Access via

    web browser(Read Only)

    ADMS Applications

    NTPUBPFFLISRV-V-C

    ReconfigOMS

    User Interface

    Video WallWorkstation

    Printers

    Modeling

    Maintain the Network

    Operational Model(NOM)

    Data Historian

    (DHS)

    Long term archive of

    data as received by

    SCADA

    Remote Access(RAS)

    Contractor maintenance interface to

    ADMS

    CPRI Network

    Router -VPNw/Firewall

    Small Simulation

    Realy Test Set

    Simulator in SGTB

    Generic Direct

    To any CPRI location with

    Campus Network Access

    Generic External

    To any CPRI location without Network Access

    Transformer Pad

    To 11kV devices on the SGTB XFMR Pad

    Router -VPN Router -VPN Router -VPN Cellular VPN

    Substation Automation

    System

    IEC-104 to IEC 61850 Gateway

    Router -VPNRouter -VPN

    Environment

    Production

    Simulation

    Programming

    Management

    Archive

    SAS Remote Station

    IEC-104 to IEC 61850 Gateway

    Router -VPN

    CPRI Corp Firewall

    Cellular to Internet

  • DATB Specifications

    Page 17 of 35 CPRI

    19 M

    ar 2

    018

    4.6.2 Station Level Computer

    Distribution Automation schemes may be Centralized, Decentralized, or Distributed.

    Centralized: depend on SCADA to collect information and send commands. Depend on

    functions within the ADMS to process SCADA information and determine control actions.

    Decentralized: depend on a station computer to collect information from field devices and

    determine and issue control actions.

    Distributed: no central control exists – intelligent devices are distributed along the feeder and

    exchange information as needed. Control decisions are made in a distributed environment by

    pole mounted devices.

    Decentralized schemes will require a station computer configured to support the particular DA

    function, such as Fault Location, Isolation, and System Restoration (FLISR). The station computer

    shall match the SASTB specification details:

    Station Level Computer Specification:

    Adhere to requirements in SASTB section 4.1

    Hardened computing platform for 19” substation rack mount

    Fanless operation

    IEC 61850 compatible

    Windows 7 Professional or Windows 10 Pro 64 bit operating system

    Multicore processor 2GHz or higher

    8GB RAM or higher

    Hot swap RAID spinning disk – 1TB

    (4) USB 2.0 ports

    PCI or PCI Express expansion slots

    (4) Ethernet ports (2 needed for Dual Station LAN connection)

    (2) EIA-232 asynchronous serial ports

    Time synchronization to 1 microsecond using IRIB-B or IEEE1588 PTP time synchronization

    Battery backed Real time clock

    19” Rack Mount touch-screen monitor

    230 VAC 50Hz power supply

    4.6.3 Gateway

    The SCADA protocol may require translation to a protocol supported by the IED used to interface to real

    world signals. The DATB shall employ an embedded Gateway device rather than a software gateway on

    a station computer.

    Gateway Specification:

    Adhere to requirements in SASTB section 4.1

    Accept IEC 60870-5-104 SCADA Server protocol (RTU)

    Map to IEC 60870-5-103, DNP3 or IEC 61850 Client protocol

    230VAC 50Hz power

  • DATB Specifications

    Page 18 of 35 CPRI

    19 M

    ar 2

    018

    4.6.4 Time Reference (supply scope covered under Situational Awareness test bed part of this

    tender)

    Integrating measurements from multiple remote locations requires GPS time synchronization. A GPS

    clock shall be located at SCADA and at each remote location to maintain synchronization between

    SCADA and the remote locations.

    Time Reference Specification:

    GPS synchronized

    GPS antenna with 50ft cable

    230 VAC 50 Hz power

    61850-9-3 compatible

    61850-3 compliant

    IEEE1588 compliant PTP support

    1 PPS output

    IRIG-B Output +/-1 microsecond

    (4) 100BaseT Ethernet ports

    4.6.5 Power Supply

    The SGTB building will include an uninterruptible 230VAC 50Hz supply (Building UPS). All devices on the

    DATB shall be specified to operate from building 230VAC 50Hz power.

    The Generic Integration Model will include a UPS for use where building critical power supply is not

    available.

    4.6.5.1 GIM UPS Specification (not in the scope of supply under this tender)

    19” rack mounted unit

    50Hz 230 VAC UPS compatible with CPRI campus grid power

    Sine wav output with no more than 5% voltage THD

    30 minutes backup operation of the GIM rack in the event of a loss of grid power.

    Replaceable, recyclable, standard form factor batteries

    3 year expected service life of batteries

    Dry contact indicator of loss of AC

    4.6.6 LAN Ethernet Switch

    In most cases, the four (4) Ethernet ports on the remote Router will be sufficient to connect remote

    devices to the DATB VPN. In cases where greater connectivity is required, devices at remote equipment

    locations shall be integrated on a Local Area Network using an Ethernet Switch. One (1) switch is

    required at each remote location. These include the DATB (Small Scale Simulation), the Generic Interface

    Model (e.g. Large Scale Simulation at the Power Systems Lab), and the Transformer Pad.

    Specification:

  • DATB Specifications

    Page 19 of 35 CPRI

    19 M

    ar 2

    018

    o Adherence to the requirements of SASTB section 4.3.1

    o IEEE1613 / IEC 61850-3 compliant (electrical and environmental stresses)

    o 12 Small Form Factor Pluggable (SFP) ports for connection of all Bay Level and Process Level

    devices.

    o 230VAC 50Hz power supply

    o IEEE 1588v2 capable

    o Rapid Spanning Tree Protocol (RSTP) - IEEE 802.1d-2004

    o VLAN aware - IEEE 802.1q 2005

    o Multicast filtering capable

    o SNMP Management version 2c and version 3

    o Web-based and/or CLI (SSH) management

    o Syslog Logging

    4.6.7 Portable Notebook Computers (2 recommended):

    Intel i7 processor or better

    Windows 7 professional or Windows 10 Pro

    10 hour battery life

    16 GB RAM

    1TB SSD drive

    14” or larger outdoor-readable touch display

    (1) HDMI output

    (2) USB 3.0

    (2) Ethernet ports (may be via USB adapter)

    WiFi 802.11n

    Bluetooth 3.0

    4.6.8 Router

    Router Specification:

    IEEE1613 / IEC 61850-3 compliant

    230VAC 50 Hz power

    4 Ethernet ports

    VPN support for connection to the SituTB SCADA System

    Intrusion Detection capability

    Single T1/E1 interface

    Internal Cellular modem interface – LTE, 3G, GPRS

    SNMP Management version 2c and version 3

    Web-based and/or CLI (SSH) management

    Syslog Logging

    IEC 61850-9-3/IEEE 1588 PTP compliant

  • DATB Specifications

    Page 20 of 35 CPRI

    19 M

    ar 2

    018

    4.7 Miscellaneous and Spare Parts

    Ethernet cabling – (20) 100Base-TX (RJ45) and (50) 100Base-FX (Dual LC), 10’ to 25’ long

    Ethernet adapters – (50) each SFP for FX (fiber optic) and TX (copper) network cable

    terminations

    230VAC 19” rack mount surge protected power strips

    5 RTU Specification The DATB components will interface to the SCADA/DMS system in the SituTB using Routers for Layer 2

    Virtual Private Network (VPN) connections to RTUs that may be installed throughout the CPRI campus as

    a basis for demonstrating the capability of SCADA to directly monitor and control typical Smart Grid and

    substation equipment. Where the CPRI campus network is not available (e.g. in the 220kV substation or

    in remote campus locations) the Router internal 3G/4G cellular modem will be used to establish the VPN

    to ADMS. The RTUs shall support two-way data communications with the SCADA component of the

    ADMS over the VPN. In this respect, the ADMS and RTUs shall normally communicate over CPRI’s optical

    fiber IP-based WAN. The data communication protocols supported by the RTUs shall include:

    1. IEC 60870-5-104

    2. DNP 3.0

    3. IEC 61850 Client

    4. IEC 61850 Server

    5. MODBUS RTU

    5.1.1 Data Acquisition

    In accordance with each communication protocol, support for data acquisition shall include:

    1. Polling of the RTU by the ADMS for specified status and analog data points at configurable

    scan rates or on demand.

    2. Report-by-exception, i.e., polling of the RTU in such a way that for status data points only

    those that have changed are sent to the ADMS and for analog data points only those that

    have changed by a configurable dead band.

    3. Unsolicited reporting in which the RTU sends the changed data automatically without

    waiting to receive a poll command.

    4. General interrogation in which the ADMS polls the RTU for all available data.

    5.1.1.1 Analog Inputs

    The RTU shall:

    1. Acquire analog inputs directly without transducers from power system voltage and current

    terminals.

  • DATB Specifications

    Page 21 of 35 CPRI

    19 M

    ar 2

    018

    2. Apply suitable filtering to eliminate the risk of signal aliasing.

    3. Use voltage and current inputs for calculations that support acquisition of the following data

    as a minimum:

    a. Line-to-line voltages.

    b. Phase current magnitudes and phase angles.

    c. Real and reactive powers (three-phase kW and kVar totals with sign).

    d. Power factor.

    4. Accept ac voltage input signals with a normal input level of 110 V.

    5. Employ analog to digital converters with minimum of 16-bit resolution for a bipolar input

    signal.

    6. Accurately resolve ac voltage input signal levels from 0 to 150 V.

    7. Accurately resolve ac current input signals with normal ranges of 0 to 5 A or 0 to 1 A.

    8. Include the capability to report all analog values that have changed by more than their

    programmable dead bands from their last values successfully reported to the ADMS.

    9. Record maximum rms fault current signals, over a period of at least one (1) second, up to 20

    times normal (100 A) within a maximum error of 2.5% of Full Scale Deflection (FSD).

    10. Not impose a total analog input burden of more than 0.5 VA for all current and voltage

    inputs.

    11. Demonstrate an overall analog input error of no more than ±0.2% of 1.2 times normal FSD

    over the temperature range 0 to 70°C.

    12. Demonstrate an analog input linearity better than ±0.05%.

    13. Reject common mode ac (50 Hz) voltages up to 150 V.

    5.1.1.2 Status Inputs

    As a minimum, RTUs shall accept isolated wet and dry single contact two-state status inputs and two-

    state status inputs with memory, i.e., Momentary Change Detection (MCD) inputs. Input changes of

    state shall be timestamped to a precision of 1 millisecond.

    Within this context:

    1. All necessary wetting voltage, current limiting, input isolation, and bounce filtering shall be

    provided.

    2. Contact de-bounce time periods shall be individually configurable.

    3. The input circuits shall be optically isolated from the external signal.

    4. Input contact wetting voltages shall be 24 VDC as obtained from the RTU’s DC power supply.

  • DATB Specifications

    Page 22 of 35 CPRI

    19 M

    ar 2

    018

    5. Each wetting voltage circuit shall be protected with its own circuit breaker.

    5.1.1.3 Analog Outputs

    RTUs shall include the capability to receive analog output signals from the ADMS such as those that may

    be used to send set points to automatic voltage regulators.

    5.1.1.4 Control Outputs

    The RTU shall support the capability to receive commands such as those that may be used by relays to

    open and close substation circuit breakers or other switches. Such commands shall include the

    following control output features:

    1. A Select-Check Back Before-Operate (SCBO) procedure:

    a. On receipt of a control point select command, the RTU shall check that no other

    point is selected, select the requested point, acknowledge the select command, and

    start a Command Receipt Timer.

    b. Control point selection shall be canceled if the subsequent operate command is not

    received within the Control Receipt Timer’s programmable time-out period, which

    shall be adjustable from five (5) to thirty (30) seconds.

    c. On receipt of the operate command, if the control point has remained selected and

    no other point has become selected, the RTU shall then initiate the requested

    control action.

    d. The SCBO procedure shall be canceled automatically on completion of the control

    action or if not completed within an adjustable time-out period of up to 60 seconds.

    e. Any further attempt at control shall require a new SCBO procedure.

    2. Opening and closing of a switch by sending commands to a complimentary pair of contact

    outputs such that:

    a. One command activates the contact used to open the switch.

    b. The other command activates the contact used to close the switch.

    c. Only one contact output in a complimentary pair can be activated at a time.

    3. Momentary control where each output provides a contact closure pulse having an

    individually programmable duration from 1 to 60 seconds in increments of 1 second.

    The following requirements shall also apply:

    1. The voltage rating of the control output contacts shall be 24 VDC.

    2. All control power shall be obtained from the RTU’s 24 VDC power supply.

    3. RTU control outputs shall be able to drive loads of at least six (6) amps.

    4. Output relays shall be designed for 106 (one million) mechanical operations.

  • DATB Specifications

    Page 23 of 35 CPRI

    19 M

    ar 2

    018

    5. The RTU shall monitor all operations and local status information and give warnings or

    advisory messages when any wrong operational sequence is requested.

    6. Abnormal conditions shall inhibit control operations.

    5.1.2 Estimating RTU Point Count

    Point count in the RTU depends on the particular application. Unused points add cost to the RTU, but

    allow extension of the RTU to address unanticipated need. Points are typically added by the addition of

    I/O modules that each provide some number of points of one or more type.

    The Generic Integration Model (GIM) will locate a router, gateway, and RTU at a remote location to

    provide a mechanism for SCADA/DMA to acquire measurements and command control or analog

    outputs. Typical RTU application will monitor at a single location, such as the 220kV and 33kV

    substations. In such an application, an RTU with:

    (16) DI

    (8) DO

    (16) AI

    (8) AO

    The GIM will also integrate the Power System Lab simulator to DMS for modeling of distribution

    automation schemes. Assume a total of (20) observation/switching points across several circuits. Each

    observation/switching point requires:

    Digital Input (2 per location) - Switch State (Open|Closed), FPI state (Fault|NoFault)

    Control Output (3 per location) - Switch Open, Switch Close, FPI Reset

    Analog Input (4 per location) – Voltage, Current, Watts, Power Factor

    Analog Output - Not required in most cases.

    So for a total of (20) observation/switching points on a simulation model:

    Digital Input 2*20 40

    Digital Output 3*20 60

    Analog Input 4*20 80

    Analog Output 8

    This large RTU might be replaced by RTU simulation by the Power Systems Lab simulator.

    5.1.3 RTU Architecture

    The RTU shall incorporate a programming capability within an architecture that supports convenient

    installation, maintenance, and expansion features. The architecture shall include a central processing

    module, I/O module, control module, communications module, and time and date module.

    5.1.3.1 Central Processing Module

    The Central Processing Module (CPM) shall:

  • DATB Specifications

    Page 24 of 35 CPRI

    19 M

    ar 2

    018

    1. Support a high-level language processing capability per the open IEC-61131-3 standard for

    programmable logic controllers.

    2. Support management of the RTU database from a local test set.

    3. Support ADMS download and upload of RTU parameters and configuration data.

    4. Implement the communication interfaces with the ADMS.

    5. Control data acquisition and the sending of control commands using an I/O module.

    6. In accepting commands from the ADMS:

    a. Perform address recognition.

    b. Assemble response messages in accordance with the received command messages.

    c. Transmit these messages to the ADMS.

    7. Provide interfaces for a time standard and test set.

    8. Manage communications between all other functional modules of the RTU.

    9. Determine the integrity of the RTU.

    10. Provide diagnostic information in the message structure that the ADMS shall monitor.

    11. Set a flag if the RTU performs a restart for any reason including power failure.

    12. Include a watch-dog timer that is reset regularly by RTU software. If the software fails to

    reset the watch-dog timer (e.g., because of a software error causing the software to “loop”

    or “hang”), then the timer shall expire causing the CPM to reset and restart.

    5.1.3.2 I/O Module

    I/O module requirements include the following capabilities and features:

    1. Capability to accept analog and status inputs and send control outputs. This shall include

    fault current measurements.

    2. Capability of being replaced without reprogramming, redefinition of configuration

    parameters, or rewiring.

    3. A Control Switch (CS) that, if not in its normal control position, inhibits control from the

    ADMS or test set.

    4. A status input contact so that the ADMS or test set can monitor if the position of the CS is in

    its normal control position.

    5.1.3.3 Control Module

    The RTU shall include an integrated control module that can control devices without the need for

    interposing relays.

  • DATB Specifications

    Page 25 of 35 CPRI

    19 M

    ar 2

    018

    5.1.3.4 Communications Module

    The RTU shall be provided with a communications module including necessary and sufficient numbers

    and types of port that can be used to support:

    1. Remote data communications with external systems and devices over an Ethernet/IP

    network. This shall include data communications with multiple masters.

    2. Local and remote configuration with a static IP address.

    3. The fully implemented message security features of the required data communication

    protocols running over TCP/IP.

    4. Communications that is not degraded by simultaneous activity in other parts of the RTU.

    5. Temporary connection of test sets such as laptop PCs for local installation, maintenance,

    diagnostic, and test purposes for all configurations and data access functions associated

    with the RTU.

    6. SCP/SSH with respect to downloading, for example, RTU configuration parameters and

    firmware updates.

    7. Features such as HTTPS for web server functionality.

    8. Blocking or disabling of ports to prevent unauthorized access.

    9. MAC and IP filtering so that Ethernet traffic is limited to a configurable “whitelist” of

    network device MAC and IP addresses.

    10. Access control using a secure log-in procedure. As a minimum, this shall include user

    authentication based on a unique username and password.

    11. System logging (syslog) at a device or system level. Syslog alerts shall include remote user

    access activity including successful and unsuccessful login attempts.

    12. Manual configuration of a routing table with different metrics so that networks may be

    reached using locally entered alternative paths (IP redundant paths for example).

    5.1.3.5 Time and Date Module

    The RTU’s time and date module shall:

    1. Include an internal time-of-day clock for data collection coordination. The time resolution of

    the internal clock shall be one (1) ms or better and, without synchronization, the time shall

    drift by no more than 5 ms per hour.

    2. Use the RTU’s 24 VDC power supply as the only source of power for the internal clock, i.e.,

    no other source such as an internal (on-board) battery shall be used.

    3. Synchronize the internal clock whenever the RTU is powered up. This shall not prevent the

    RTU from immediately registering inputs even before the time and date reference signal has

    been received. Any such inputs shall be reported to the ADMS with the appropriate time

    and date, i.e., use of an arbitrary default time and date is not acceptable.

  • DATB Specifications

    Page 26 of 35 CPRI

    19 M

    ar 2

    018

    4. Support receipt of a DNP 3.0 compliant time and date message that contains a Greenwich

    Mean Time (GMT) reference signal, generated by the ADMS in long format and in such a

    way as to properly account for communication path delays.

    5. Support capability to synchronize the internal clock to the GMT time and date received from

    the ADMS.

    6. Support capability to synchronize to an optional Global Positioning System (GPS) receiver.

    The GPS antenna shall be of low profile type for secure and moisture-resistant mounting on

    top of the RTU enclosure. The receiver shall be used to synchronize the internal clock to the

    correct GMT time and date within a time resolution of at least 1 millisecond.

    5.1.4 Power Supply

    The RTU shall include an integrated 24 VDC regulated and protected power supply with source power

    from the 230 VAC 50 Hz mains. It shall be used to power the RTU and its local control panel. It shall also

    be capable of powering local test sets from an RTU enclosure power receptacle. The supplier shall be

    responsible for determining its maximum output capability.

    5.1.4.1 Batteries

    Under normal conditions, the DC power supply shall connect to a substation 230 VAC power supply. As

    backup, however, it shall be powered by a 24 VDC maintenance-free rechargeable battery with the

    following characteristics:

    1. Be of lead-acid gel electrolyte type.

    2. Be designed and tested per IEC 60896-21, DIN 43534, BS 6290 Part 4, or equivalent.

    3. As a minimum, have sufficient capacity to sustain operation of the RTU and its local control

    panel for not less than twelve (12) hours if the ac power source fails.

    4. Be designed using an appropriate temperature correction factor, design margin, and ageing

    factor.

    5. Have a minimum lifetime of not less than 8 (8) years at a nominal temperature of 20 °C.

    5.1.4.2 Battery Chargers

    The DC power supply shall include an intelligent battery charger, which shall:

    1. Be of switched-mode 100-240 VAC power input type.

    2. Be fully temperature compensated.

    3. Be automatically switched to charging mode when the battery voltage drops below a preset

    value and, in the following cases, be automatically switched to a “do not charge” trigger

    mode:

    a. Battery voltage is over the preset value.

    b. Ambient temperature is more than 60 °C.

  • DATB Specifications

    Page 27 of 35 CPRI

    19 M

    ar 2

    018

    c. Charging time is more than a configurable number of hours, e.g., twenty-four (24)

    hours.

    d. Battery exhibits a high impedance (battery failed) condition.

    4. Have over current, over voltage, and surge protection.

    5. Prevent deep discharge of the battery on loss of the AC power source. In this respect:

    a) The battery charger shall automatically disconnect all circuitry fed by the battery

    following a user-adjustable time or when the battery voltage falls below a preset

    value.

    b) The time to fully recharge the battery once disconnected from load shall not

    exceed twenty-four (24) hours.

    c) The direct current power will be cut off when voltage stays under the minimum

    preset value.

    In addition to the above requirements, the capability to initiate the following alarms shall be provided:

    1. Low battery voltage alarm.

    2. High battery voltage alarm.

    3. Battery failed alarm.

    4. Battery charger overvoltage alarm.

    5. Battery disconnected alarm.

    Each alarm indication shall be displayed on the RTU’s local control panel with super bright LED pilot

    lamps. These alarms shall be reported to the ADMS as an event.

    5.1.5 Local Control Panel

    The RTU shall include a local control panel, which shall include:

    1. A mimic diagram and facilities for operation of RTU local control functions.

    2. An A/C power supply on/off switch. When the A/C power source is off, operation of the RTU

    shall be possible by using its battery backup feature.

    3. A Local/Remote switch. While this switch is in the “Local” position, control shall be

    permitted only from the local control panel (i.e., remote control shall be prohibited).

    Otherwise, while the switch is in its “Remote” position, control shall be permitted only from

    the ADMS (i.e., local control shall be prohibited).

    4. LED lamps for RTU, battery, battery charger, and local/remote status indications.

    5. Battery voltage test points.

  • DATB Specifications

    Page 28 of 35 CPRI

    19 M

    ar 2

    018

    5.1.6 RTU Software

    The term “software” is used to mean software or software implemented through firmware. Complete and

    comprehensive documentation shall be provided for all software.

    5.1.6.1 Operating System

    The RTU operating system shall:

    1. Be a real-time non-proprietary operating system.

    2. Manage and support all RTU applications.

    3. Support editing and customization as needed to maintain RTU operation.

    4. Provide automatic restarts of the RTU on power restoration, memory parity errors,

    hardware failures, and manual request.

    5. Initialize the RTU on power-up and begin execution of the RTU functions without

    intervention by the ADMS.

    6. Report all restarts to the ADMS.

    5.1.6.2 Operating Software

    The RTU operating software shall be:

    1. Prepared in a high-level language such as the IEC61131 programming suite.

    2. Documented in detail.

    3. Free of additional licensing charges or license agreements.

    4. Supported by protocol, configuration, and application data contained in easily

    programmable non-volatile memory such as Flash EPROM.

    5. Independent of any data communications protocol that would impose restrictions on the

    flexibility or functionality of the RTU. In this respect, protocol changes shall be capable of

    being accomplished by locally and remotely implemented software/firmware changes only.

    5.1.6.3 Diagnostic Software

    RTU diagnostic software shall:

    1. Continuously monitor operation of the RTU.

    2. Report RTU hardware errors to the ADMS.

    3. Check for memory, processor, and input/output errors and failures.

    4. Be sufficiently detailed to detect malfunctions to the level of the smallest replaceable

    component.

    5. Facilitate isolation and correction of all failures.

    6. Include features promoting rapid fault isolation and component replacement.

  • DATB Specifications

    Page 29 of 35 CPRI

    19 M

    ar 2

    018

    7. Include integrated on-line diagnostic functions in all functional module nodes.

    8. Report diagnostic results to the CPM for store and forward to the ADMS.

    5.1.7 Enclosures

    The RTU equipment, including local control panel, batteries, and battery charger, shall be housed in a

    suitable enclosure.

    To safeguard against outdoor installation, the enclosure shall prevent moisture condensation including

    corrosive salt formations and the ingress of rain water, airborne dust, vermin, and small objects. It shall

    be designed to ensure that it remains rigid and retains its structural integrity under all operating and

    service conditions with and without the door being closed. In this respect, it shall be fabricated from

    stainless steel panels (Type 304L) of not less than 2 mm in thickness, and the door opening shall have a

    perimeter flange with a rubber or neoprene gasket. The finishing coat shall be grey (RAL 7032).

    A pocket attached to the inside of the door shall be provided to hold documentation such as

    maintenance log sheets, control unit diagrams, and operating instructions. The door shall be opened by

    a single handle, which shall be capable of being locked by use of a padlock and key. A means to remotely

    monitor the open/closed status of the enclosure’s door shall be provided. An equipment alarm shall be

    generated whenever the door is opened.

    The enclosure shall include a grounding terminal with grounding bolt and lock washer for connecting a

    50 mm2 galvanized steel grounding conductor. The grounding bolt and lock washer shall be made of

    stainless steel.

    6 Physical Structure (Rack)r DATB hardware shall be mounted in 19-inch two-post relay racks. The structure shall

    consist of one (1) 19” x 45U two-post rack on casters for mounting of the Transient

    Simulator and interface devices. The test equipment rack will be suitably stable to

    allow rolling movement of the rack without risk of tipping over. Two such racks are

    required – one for DATB and another for remote equipment at the Power Systems

    Lab.

    Rack Specification: Total (2) racks

    19” 2-post relay rack

    12-24 OR M6 threaded holes

    Black finish

    Formed steel OR Extruded aluminum construction

    1000 lbs (455 kg) weight capacity

    Base dimension approximately 20”x14”

  • DATB Specifications

    Page 30 of 35 CPRI

    19 M

    ar 2

    018

    Top cross member width 6”

    Outside dimension approximately 20”

    Threaded hole spacing 18.312” (465mm)

    Inside clearance 17.81” (452mm)

    Concrete floor installation kit Rack Accessories

    (qty 1000) compatible rack screws

    (qty 2) 3U 2-post shelf

    (qty 2) rack caster sets for mobility of (2) racks

    (qty 2) 20 amp rack mount AC surge suppression power strip, individually switched universal power socket

    Figure 6-1 Rack mounts for DATB Equipment

    7 Communication Network Communications within the CPRI campus shall utilize the CPRI backbone IP Network.

    7.1 Network Performance Requirements

    The DATB LAN and the SituTB WAN connections shall be 100/1000 Mbps Ethernet. The performance of

    the overall network architecture shall be such that the critical clearing time requirements for various

    control functions are guaranteed under all network loading conditions. The network performance shall

    be completely predictable for operational behaviour.

    19" x 45U Rack structure for DATB equipment mount.NTS - Color only denotes intended use – all racks are black.

    Racks 1 and 2 are on casters for mobility.

    84

    " (45

    U)

    Rack 1DATB

    Rack 2PS Lab

  • DATB Specifications

    Page 31 of 35 CPRI

    19 M

    ar 2

    018

    Fiber optic cabling shall be used in the DATB equipment. Integrator shall provide all required fiber optic

    cables, with a set of spare fiber optic cables sufficient to connect two additional IEDs to each rack.

    7.2 Connection from DATB to the SGTB external transformer pad

    Communication from DATB to equipment on the SGTB transformer pad shall be by fiber optic link to a

    weather tight enclosure securely mounted on the transformer pad located about 100 feet away. 2” or

    larger conduit from DATB to the transformer pad enclosure shall be installed. Pre-terminated

    indoor/outdoor 12 strand multimode flat drop fiber optic cable pulled through the conduit shall

    terminate on each end at a panel of six dual LC fiber terminations. Alternatively, CPRI may choose to

    field terminate the twelve fiber strands into the dual LC terminations.

    7.2.1 Fiber Link Specification

    Option 1 - traditional field-termination: Cable:

    OM2 or OM3 50/125 µm Multimode fiber Indoor / Outdoor rated 12-fiber count Loose Tube buffering, gel-free

    Fiber Termination (Multiply by two in order to terminate both ends of cable): Small termination enclosure, single panel LC Connector pigtails (Qty 12) Connector panel w/ 6 duplex LC-Type connectors (Based on enclosure) Heat Shrink Splice Cover (Qty 12)

    Option 2 - Use Connectorized cable with pre-terminated housing: Housing with 6 multimode Duplex-LC connectors pre-terminated to a 12-fiber multi-fiber connector (Quantity 2) Indoor/Outdoor OM3 50/125 µm multimode cable terminated with 12-fiber multi-fiber connector

    7.3 SNMP Manager

    All DATB network components shall include an SNMPv3 Agent for device management by an SNMP

    Manager. DATB shall include an SNMPv3 management system installed on the SituTB Workstation

    Computer. Additional SNMP Managers may be installed on the DATB Portable Computers. Several

    SNMP Managers are available at no or low cost for a system as small as SASTB:

    SNMP Manager shall

    Automatically detect network devices

    Map network topology

    Monitor for events (faults, availability, and performance) of network devices

    Send event alerts via console display and email

    Sequentially timestamp log entries

  • DATB Specifications

    Page 32 of 35 CPRI

    19 M

    ar 2

    018

    Provide search capability through system logs

    Concurrently manage a minimum of 50 network devices

    Run on the Windows 7 or Windows 10 station and portable computers

    7.4 Redundancy Requirements

    The DATB will not require redundancy in hardware or software.

    7.5 Cyber Security Requirements for Distribution Automation

    DATB shall utilize the existing CPRI campus IP network, with commercial cellular modems for off-campus

    communication needs. Connection from the SGTB building to other campus buildings shall be by Virtual

    Private Network (VPN), with VPN supporting routers at each end of the connection. Connection to off-

    campus locations shall be by VPN over cellular modem (see Figure 4.3).

    The exchange of any information between systems shall include authentication of BOTH the source and

    the receiver.

    For communications using IEC 60870-5-104, the IEC 60870-5-7 standard that references IEC 62351-5 and

    IEC 62351-3 shall be met.

    Cryptographic key management shall be provided based on IEC 62351-9 requirements. Alternatively,

    Public Key Infrastructure (PKI) may be used for key management.

    Compliance with the cyber security recommendations in IEEE 1686 is required, including user ID and

    password control, testing for adequate password strength, provision of audit capabilities for alarms and

    events, monitoring of security-related activities, appropriate cryptographic technologies, and IED

    configuration management.

    8 Reliability and Availability vs. Flexibility The DATB is designed to provide a high level of testability and flexibility. IEDs and test equipment shall

    be added and deleted from the DATB local and remote fixtures by CPRI Staff on a regular basis. As a

    result, availability and reliability will be more a factor of the diligence of the operators than to the

    quality of the components. Functional failures will not affect physical line hardware. The design will

    stress this need for flexibility rather than extreme availability common in utility installations. Redundant

    Requirements and definitions for reliability are defined in IEC 60870-4, chapter 3.1.

    9 Contracting Options CPRI has three options in realizing the DATB:

    Purchase, take delivery, assemble, and commission the DATB with internal CPRI staff.

  • DATB Specifications

    Page 33 of 35 CPRI

    19 M

    ar 2

    018

    Purchase and take delivery of the DATB hardware and software, then contract a knowledgeable

    consultant to assemble and commission the DATB with assistance from UARC engineering staff.

    Consultant would then provide training to UARC staff. Estimated 6-8 weeks manpower.

    CPRI can contract the DATB to a Turnkey Contractor to assemble and commission the DATB for

    delivery as a complete and working unit. A consultant would then be engaged to train UARC

    staff on operation of the DATB. Conventional estimates for turnkey work are 1/3 material, 1/3

    labor, and 1/3 profit, so a Turnkey assembly can be estimated as adding 2 * (material cost) to

    the overall project cost.

    The scope of work of the DASTB Turnkey Contractor shall include physical assembly, IED configuration,

    and provisioning of 61850 SCL files as needed. It shall also include the engineering of the GOOSE and

    Sampled Value messages as required to implement the protection schemes, connection to the SituTB

    SCADA WAN, and delivery and set-up of the DATB.

    Design, installation, and commissioning of the 11kV Transformer Pad equipment and the 12-strand fiber

    network connection from DATB to 11kV transformer pad will require a qualified integrator. This item is

    to be contracted independent of the purchase of the balance of the DATB equipment.

    10 Feature Quantities: Table 10-1 DATB Features List

    # Feature Qty Section Notes

    1 Rack 2 6 19"x45U, (4) on casters

    2 Router 4 4.6.8 Allow for (4) remote connections

    3 Ethernet Switch 4 4.6.6 Each remote connection

    4 Station Computer 1 4.6.2 Host for (1) Decentralized DA Scheme

    5 Gateway 4 4.6.3 60870-5-104 to DNP3 or 61850

    6 Remote Terminal Unit (small) 4 5 (16) DI, (8) DO, (16) AI, (8) AO

    7 Remote Terminal Unit (large) 1 5 (40) DI, (60) DO, (80) AI, (8) AO

    8 Portable computer 2 4.6.7 Dual LAN adapters

    9 SituTB SCADA simulator 1 4.6.1 60870-5-104 master on laptop

    10 SNMP Manager 1 7.3

    11 12 strand fiber network link 1 7.2 CPRI Field Splice

    12 Small Scale Simulation capability

    1 4.2.1 Use Existing SASTB unit

    11 Mapping Functions to Features (only for information) DATB enables CPRI to perform a list of Functions as specified in section 3. Each Function depends on a

    subset of test bed Features. Each Feature has a cost associated with it. As funding permits, CPRI will

    select “Buy”, “Use Existing”, or “Delay” for each Feature (Table 13-1). In this section we will create a

  • DATB Specifications

    Page 34 of 35 CPRI

    19 M

    ar 2

    018

    mapping of Functions to the required Features. This mapping will be used to populate the Function vs.

    Feature Matrix (Table 11-2).

    The Design of the DATB has generated a list of 15 Features to support 7 different Functions as itemized

    in Table 11-2. This matrix will be manipulated in an Excel Spreadsheet to select the Features to be

    realized.

    Available Add Cost

    Buy Yes Yes

    Use Existing Yes No

    Delay No No Table 11-1 Selection options for each Feature

  • DATB Specifications

    Page 35 of 35 CPRI

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    Function List DATB Functions

    Rac

    k St

    ruct

    ure

    Ro

    ute

    r

    Eth

    ern

    et S

    wit

    ch

    Stat

    ion

    Co

    mp

    ute

    r

    Gat

    eway

    Smal

    l RTU

    Larg

    e R

    TU

    IEEE

    15

    88

    tim

    e so

    urc

    e

    23

    0 V

    AC

    UP

    S

    Po

    rtab

    le c

    om

    pu

    ters

    Situ

    TB S

    CA

    DA

    sim

    ula

    tor

    Stan

    dar

    ds

    for

    refe

    ren

    ce

    SNM

    P M

    anag

    er

    11

    kV t

    ran

    sfo

    rmer

    pad

    eq

    uip

    men

    t

    12

    str

    and

    fib

    er n

    etw

    ork

    lin

    k

    Smal

    l Sca

    le S

    imu

    lati

    on

    cap

    abili

    ty

    Wir

    esh

    ark

    for

    pac

    ket

    cap

    ture

    3.4.1 Generic Interconnection Model

    3.4.2 Small scale simulation

    3.4.3 Large scale simulation

    3.4.4 Integration with SituTB SCADA/DMS

    3.4.5 Integration with transformer pad switchgear

    3.4.6 Observe 220kV and 33kV substation operation

    3.4.7 Monitor information flow Table 11-2 Function dependency on Features


Recommended