Getting results using the 1756-DNB And RSNetWorx for DeviceNet Getting results using The 1756-DNB and RSNetWorx for DeviceNet This Document will allow a user to quickly setup and get started using the 1756-DNB module for DeviceNet applications. Basic configuration and usage information will be detailed for some common devices. Page 1 of 68
Transcript

Getting results using the 1756-DNB

And RSNetWorx for DeviceNet

Getting results using

The 1756-DNB and

RSNetWorx for DeviceNetThis Document will allow a user to quickly setup and get started using the 1756-DNB module for DeviceNet applications. Basic configuration and usage information will be detailed for some common devices.

Last updated

December 2002

Table of Contents

1. Configuring RSLogix 5000 to Include a 1756-DNB Module

32. Adding the 1756-DNB to the I/O configuration tree for the ControlLogix Processor

33. Adding a Remote 1756-DNB to the I/O Configuration tree

44. Configuring RSNetWorx for DeviceNet

55. Going On-line and selecting a driver

56. Unrecognized Device Configuration

67. Creating, Registering or Finding EDS files.

78. Uploading From the Network

139. Uploading from Devices

1510. Missing Devices

16

11. Device Mismatches

1612. Looking at Device Properties

1813. Configuring the Series 9000 Photoeye

1914. Configuring the 1734-IV4 Module

2015. Looking at the Parameter Help

2016. Configuring the 1734-OW2

2217. Configuring an 855T Stack Light

2318. Configuring the 1792D-VT0D MaXum Block

2419. Using the Monitor on the Parameters Tab

2420. Configuring a 1794-ADN with 4 modules

2621. Configuring a 1794-ID2 in RSNetWorx for DeviceNet

2722. Configuring a 1794-OE4 in RSNetWorx for DeviceNet

2923. Configuring a 1794-IB16 in RSNetWorx for DeviceNet

3024. Configuring a Bulletin 160 Drive with a DN2 module

3225. Scaled Parameters

3426. Locked Parameters

3427. Configuring the 1756-DNB Module

3528. Configuring the Module Tab of the 1756-DNB

3529. Slave Mode for the 1756-DNB

3530. Foreground to Background Ratio

3531. Configuring the Scanlist

3632. Configuring Shared Inputs for devices

3633. Automapping

3734. Data Definitions in the I/O Table

3935. Manually Mapping (Advanced Mapping)

3936. Summary Tab for the 1794-ADN

4237. Getting a mapping error for the 1794 ADN module

4238. Downloading the Scanlist to the 1756-DNB Scanner

44

39. ADR (Auto Device Replacement)

4440. 1756-DNB Summary Tab

45

41. Using RSLogix 5000 to Trigger and Monitor Data

4642. Idle Scanner and the Run Bit

4643. Input Data Structure

4644. Output Data Structure

4745. Status Data Structure

4846. Common LED error descriptions

4947. Creating Aliases

5148. Turning on Lights on the 855T Stack Light

5249. Operating the Bulletin 160 Drive

5250. Looking at Input from the Photoeye

5451. Turning on Analog Outputs from the 1794-OE4 Module

5552. Node Address/Status Indicator

5853. Device Failure Table

58Configuring RSLogix 5000First well configure RSLogix 5000 to accept the 1756-DNB Module.

Open RSLogix 5000 and go to the IO configuration folder in the left hand window near the bottom. Right click and choose New Module. Well configure a Local 1756-DNB here.

Select the 1756-DNB module from the list.

Click OK to select the new module and follow though the rest of the screens to finish configuring the module. Once the module has been added you should now see the module in the I/O tree.

Ive added an L1 Processor here as well.

To configure a remote 1756-DNB first select the network for the remote rack. Ill show 2 remote connections a remote ControlNet rack and a remote EtherNet rack.

You should also see that Tags for the module have been created under the Controller Tags.

Here are the tags Created for the Remote Modules

Well look more at these later on.

Save the file with the New 1756-DNB module added.

On-Line Configuration of RSNetWorx for DeviceNetFirst, open RSNetWorx for DeviceNet.

For a first time user, youll have no file of the network, so you must go online.

If you have a file, open it now.

To go online do one of three things:

Click the Online Button

Go to the toolbar then to Online

Or Press the F10 function key on the keyboard.

Choose the path you use to get to the DeviceNet Network (1784-PCD, 1770-KFD, 1784-PCID, etc). Here we are using the 1784-PCD card.

Then Click Ok. RSNetWorx will then begin to browse the network. RSNetWorx will see all the devices that are listed under the driver, including the 1784-PCD card.

Once the browse is completed, all the devices on the network, that are communicating properly, will be shown as an Icon on the network Graph.

As you can see all the devices that were shown in the RSLinx Browse window in the above step are shown here on the Network Graph view. Here we have an Unrecognized Device as shown by the Icon below.

Youll also get an error message in the message box at the bottom of the window.

To resolve the unrecognized (Unregistered) device, we need to obtain the EDS file for it.

Creating, Registering, Finding EDS file

There are several places to get EDS files. First, you could ask the vendor of the device for the EDS file. They should be happy to get that for you. All Rockwell Automation EDS files can be found at the Internet address:

http://www.ab.com/networks/edsSecond you could check at the ODVA (Open DeviceNet Vendors Association) website:

http://www.odva.orgor you could try to upload the EDS file information from the device. Some devices allow this option. Some do not. This particular device is an Allen Bradley Bulletin 160 Drive. It allows uploading of the device parameters so that RSNetWorx can create a usable EDS file.

First right click on the Unrecognized Device Icon and choose Register Device.

Next the EDS wizard will automatically be launched to help you register the device.

Choose Next to continue

Then choose Create EDS file

Once you have done this, follow the prompts to complete the EDS file information.

Youll be asked to enter a catalog number. You may do so at this time or just leave it blank. Leaving it blank will not affect how the device operates on the network.

I have chosen to leave mine blank. Again, it does not effect proper device operation.

Next well be prompted to select the type of default connection (Polled, COS [Change Of State], or Strobed). By default most drives are polled, so well click on the polled connection checkbox and then enter the default sizes for the drive. The sizes are 4 receive (input) and 4 transmit (output). These sizes can vary especially on these and other drives.

But for now, well select the default values.

Click Next to continue on At this point, RSNetWorx should be uploading the parameter information from the drive and start building the EDS file. If you get an error you may have to check the connection to the device and start this process over again. If you continue to have communication problems while uploading you may have larger network trouble. Visit our Knowledge base at http://support.rockwellautomation.com and look at document G15098. This is our DeviceNet Trouble Shooting Guide. It addresses many commons communication issues due to cabling problems, as well as, termination and grounding.

Once all the parameters have been uploaded, youll be prompted to select a graphic image, or icon, for the device, sometimes an appropriate Icon will be selected by default. If this choice is Ok with you, just click next. Otherwise, click the change icon button and choose from the built in selection of icons or point to a location that contains the icon file by clicking the browse button.

Here the image of the 160 drive is already selected from the built in database of icons, so well just leave it alone and click next.

Finally, it will ask you to register the device, go ahead and click next. This step is crucial. RSNetWorx will add this file to its list of known device types as well as create a registry entry in the Operating system (Windows 98, NT 4.0, 2000, etc..)

Once you click next here, it may take a few minutes to update RSNetWorxs files as well as update the registry information.

If you find that you are unable to upload the file, you have to get the EDS file from the vendor of that product and the Register the file.

Again, go to the EDS Wizard; select Tools from the toolbar, then EDS Wizard

Then hit Next after the Splash Screen comes up.

Then Select Register and EDS File from the four available options.

Then select whether you want to register a Single file or a directory of files.

Then either type in the path to the EDS file you want to configure or use the Browse button to browse out to the folder where the file(s) is (are) stored.

Complete the Wizard by following to the prompts (Next and Finish).

Once you click next here, it may take a few minutes to update RSNetWorxs files as well as update the registry information.

You may also need to shut down and restart RSNetWorx for the update to fully complete. If the Icon shows up automatically after the hourglass disappears then you should not have to restart RSNetWorx. Otherwise, if the unrecognized device Icon remains, close RSNetWorx and restart it. Then, follow the above procedures again to get back Online. It should be as easy as restarting and clicking the online button or hitting the F10 function key.

OK! Now we have all the devices registered and we can move on

Uploading from the Network

Now we can upload the devices information from the device the software. If you have an offline file skip the following section. If you upload now, to your preconfigured file, youll lose all your configuration information.

To upload from the network, right click in the background and choose Upload from Network.

It may take a few minutes to upload all of the devices information.

If you want to upload from a particular device the select the device by double clicking on the Icon. Youll get a window that looks similar to the scanners upload window. Just click the upload button to upload.

Uploading from Devices

To upload from a single device, right click on the icon for that device and then choose Upload from Device.

After the Network information has been uploaded you may double click on any of the devices to configure them.

Also Note: The message window at the bottom of the screen will have information about the upload for each device.

If the device was successfully uploaded then youll see a message like the following messages for each node.

Missing Devices

If the software cannot find a device it will show and Icon that has a red box with a yellow minus sign.

And the messaged below will be displayed in the message window at the bottom of the window.

Device Mismatches

If you are using an Off-Line file and you get the following error message and Icon, this means that more than likely the devices firmware is different.

With version 3.21 of RSNetWorx for DeviceNet youll get a device mismatch dialog box.

If the Vendor, Device and Product Types are the same, it is just a revision difference and youll only need to click the OK button.

If online identity and offline identity information other than Revision is different, then the whole device is different. It should tell you what is out there and what RSNetWorx was expecting. If this is the case then you should double check dip switches and consult with the people that created your offline file to verify what should really be there. Ladder Logic depends on a particular device to be there.

If the mismatch can be resolved by the software then the following message will appear in the message window.

First well look at the non-scanner modules.

Looking at the Properties of Devices

You may right Click and go to Properties

Well look at the simplest device first

Configuring the Series 9000 PhotoEye

This device is probably the most basic device you can have.

After we open the properties window we want to go the parameters tab. As you can see there are only three parameters here. Configure those now or leave them alone. We are going to leave them alone.

Note the Lock Icons next to the parameter information. This means this parameter is a READ ONLY parameter and it cannot be changed. Usually this is a value or an internal state of the device.

Now click the Apply button to save the information to RSNetWorx. If you dont click the Apply button the default information will be used when it comes time to download to the device. So always make sure you click the Apply to save the information. Also, the information is automatically applied if you click OK.

Configuring Point I/O 1734-IV4 Module

Now well look at the 1734-IV4 4pt DC input module.

Open the Properties of the module. Note there are a few locked READ ONLY parameters. These are the input values of the module.

Since there are more parameters than the window can show the lower screen capture shows the additional parameter.

Parameters 5 through 12 are filter values for the inputs the module.

Help for the Off-to-On delays (parameters 5, 7, 9 and11) can be found by right clicking on the parameter and selecting Parameter Help.

The help window will be displayed for that parameter.

Since I know my input signal will be high for 10ms every time it comes and I want to know when it is on for 5ms, I can set these parameters for 5 ms. So after 5ms the Input on the IV4 module will be turned on. To change the value of the parameter, left click in the current value portion of the window and type in the desired value. Here I selected 5ms.

Configure the rest of the parameters as desired. I have no further changes, so Ill leave the rest of the parameters at their default values. Ill then click the apply button and Ill get the Query window that asks if Id like to download to the device. I prefer to download at this time since I know everything I want to configure is completed for this module.

So Ill click Yes and download the changes the module. Then click Ok to close the device properties Box.

Configuring the 1734-OW2 Module

Next, well configure the 1734-OW2 module, 2 point relay module.

Again open the properties and the parameters tab for the 1734-OW2 module.

I have selected a few of the parameters to explain them.

First, fault actions and values should be determined. They have been configured as shown above. Next the Idle values should be configured. These values will be used if the system is switched out of run mode OR parameter 11, the Run/Idle Command is used. Normally the module will be set to the Idle setting for scanner control. If you wish to manually test the outputs, set parameter 11 to RUN. This will allow output to be toggled from Parameters 1 and 2, the Output values.

Now that the changes are made, click Apply and download.

Configuring the 855T StackLight

Now well configure the 855T StackLight

Open the properties and the parameters tab configure the module appropriately.

Since I have no changes Ill just Click Ok.

Configuring the 1792D-VT0D MaXum BlockNext well visit the Armor Block MaXum, 1792D-VT0D

Again go to the Properties and then to the parameters.

The Parameters I have chosen to look at are the Connector Fault Status and the Connector Diagnostics. Since I am only going to be using 8 inputs I have chosen to group them to the first 4 connectors. There are two input points per connector. I have disabled the Diagnostics for the last four connectors (E through H) so the block does not indicate an Open condition (OFF Wire). If I leave the Diagnostics enabled, the block would sense there is nothing connected to those connectors and set the fault bit and Flash the MS (module status) LED RED the Output LED, too, would flash red. With the Diagnostics disabled for those connectors, there wont be any false alarm condition generated.

If the connectors to on the MaXum are removed then, in RSNetWorx you can also monitor the parameters to see if there is an OFF WIRE condition. First, choose whether you want to monitor one or all parameters. Then, start the monitor by clicking the Start Monitor button.

Then watch the scrolling blue ball as it moves through the parameters. This will display the state of the parameter, as it is currently help within the device.

Once the parameter information is display you can shut off the monitor by clicking the Stop Monitor button.

So if the inputs are disconnected from the Armor Block, well get the following display from the monitor.

So again, click apply to save the configuration information to the software and download to the module.

Configuring the 1794-ADN Flex I/O Adapter

Next, well configure the 1794-ADN Flex I/O Adapter Module.

These can be somewhat tricky if they have already been configured.

Well configure four modules in the scanlist of the 1756-DNB module.

Open the properties to the Flex Module, then go to the Module Configuration tab.

Under the Module configuration tab, there will be a list of the modules the ADN module sees connected to the right if itself.

Here we have three modules connected. They are all being displayed correctly.

We have a 1794-ID2/A, an incremental Encoder, a 1794-OE4/B, and analog output module, a 1794-IB16, a 16 pt 24V DC sink input module and Ill leave the fourth module, a 1794-OB16 and 16 point output module up to the reader.

To configure the 1794-ID2 Module click on the slot 0 button next to the module type name.

Here is the Module configuration tab that shows the I/O sizes for the module.

The manual for the module is available from http://www.theautomationbookstore.com or www.ab.com/manuals and search for the 1794-ID2 manual.

Here is the channel 0 tab configuration. I have enabled the Rollover and Count Enable bits. I have also configured the preset to be 1000. Since I want channel 1 to be the same Ill repeat these settings there.

Once the module is configured Click OK to close the window.

Next well configure the 1794-OE4 module. This is the analog output module.

By default, many the available parameters on the module are shut off. Well take a look at these additional parameters and make use of some of them.

Click on the data description button to gain access to the additional data.

Check all the buttons you want to use then click OK. I have chosen to use them all now from the ControlLogix Processor I can control how the module operates.

Otherwise, if I had chosen Set for I/O Only, then I would be able to configure the module through RSNetWorx. Use the Pulldown to configure the input signal type.

Finish configuring the module for the application.

Next well configure the 1794-IB16 module.

I have again chosen to control the module from the ControlLogix processor by clicking on the Data Description button and selected to add the Input delay time to my data being transferred to the 1794-ADN mapping.

Click to Ok button once you are finished here.

Click the apply button and download.

If do not click the apply button none of the information will be applied when we look at the summary screen. It will contain the default of 2 input bytes or 1 input word.

Then go to the Summary tab. This will show all the modules in the rack and the total I/O data in both Words and Bytes. It will also show the order of the data, as it will appear in the scanner module. Well refer back to this table when we map the 1794-ADN module.

These are the values for the 1794-ADN flex I/O adapter.

Again, Ill leave the 1794-OB16 Module as an Exercise for the user.

Configuring the Bulletin 160 Drive

Now well configure the Bulletin 160 Drive with the DN2 interface module.

Since we are online, weve already set the address and baud rate with the dipswitch on the DN2 module. If you havent done this yet refer to publication 0160-5.18 at http://www.ab.com/manualsSet the baud rate and the node address according to the charts shown in the manual.

They have been added here for convenience if you cannot see the drive, or is it being displayed at the incorrect address.

Once the 160 shows up in RSLinx and RSNetWorx, open the properties up for the drive and go to the properties for that drive.

There are several parameters that are very important to note for operation on DeviceNet.

First is parameter 46. This parameter MUST be set to Network Control.

Next is parameter 59. This parameter MUST be set to Internal Frequency

Next are the data Assemblies that are to be used

Youll want to consult the manual again at this point in Appendix B, pages 24 to 28. These assemblies will determine what data will be sent back to the 1756-DNB and processor from the drive.

Here I have used Input assembly 71. This corresponds to:

I have also used Output assembly 21. This corresponds to:

To make the Drive operate, in the output assembly I have to set bit 5 for the Net Reference (for the Speed Reference) and bit 6 for the Net Control (Network Control).

Then once these bits are set I can set bits 0 or 1 for run forward or reverse, respectively.

Some of the parameters have a symbol next to them that looks like a scale. This means the parameter is being displayed as a scaled value rather than its raw data form.

So when we look at parameter 1 the output frequency, we see the value as a scaled frequency value instead of the raw data coming back from the drive. Youll also notice that this parameter is a READ ONLY parameter. This is known from the Lock symbol.

Set up the remaining parameters as necessary for your application.

Click the Apply button to download the new information to the drive.

Configuring the 1756-DNB Module

Last but not lease comes the 1756-DNB scanner configuration.

Open the Properties of the scanner. First well look at the Module tab of the 1756-DNB module. Most of these parameters will not be changed and most should not be changed, unless directed to do so. Improper network operation may result if the module is improperly configured.

Two Parameters that may be of interest are the Slave Mode button. By enabling this feature data from this scanner (set up as a Slave device) can be sent to another Master Scanner Module. This is useful for non-Critical data transfers between two or more processors over DeviceNet.

The other parameter is the Foreground to Background Poll Ratio. This parameter is useful if:

1. You have very slow devices on the network that do not update their data often.

2. You do not require data from a particular device as often as the other devices.

3. Or, if the device has many bytes of data to transfer and bandwidth usage is an issue.

Next, well configure the Scanlist then we can look at some of the other information that is available for this scanner module. Since were configuring the scanlist first, click on the scanlist tab.

Youll see that all the devices are in the available devices window.

To add all the devices to the scanlist at one time use the Double Arrow pointing to the scanlist window, otherwise use the single arrow to add just one device at a time. If you choose to add them all, they will be automatically added to the scanlist in node order and the data will be as compacted into the I/O tables as possible.

Sometimes, as shown in the pictures data can be split in, not so friendly ways as shown by the bulletin 160 drive mapping. The words have been split and the speed reference has been split.

Note: If you right click on an Icon in the Available Devices window you can choose to share the Inputs for that device (Or in the white background for all the devices). This means that you can monitor the inputs of that device in another scanner on the same Network. It is like a listen only mode.

Then when you go to the second scanners Scanlist and choose Shared Inputs, youll get the following Icon

For more information on configuring Shared Inputs, refer to knowledgebase Document ID G17769.

http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/$$Search?OpenForm&Seq=1

You can leave this mapped this way and correct it in the logic, but that can increase the scan time of the processor or you can Unmap the devices you want to and change the locations and ways they are mapped.

To Unmap go back to the scanlist and click the device to Unmap then click the single arrow pointing back to the available devices.

Here Im going to move everything around because I have particular requirements for certain devices. So Ill click the double arrow to remove all the devices from the scanlist.

First Ill Automap the StackLight. It has 1 byte of input data and one word of output data. Then Ill map the Photoeye. It has only 1 byte of input.

Then Ill map the armor block. It has 4 bytes of input data.

Next Ill map the IV4 module. Something interesting to note here, is the plus + sign next to the device. If the device is expanded (click on the plus), an explanation of the data for this module is available.

In addition to this information, if we select one of those input values, its position can be seen in the data table below. Not all devices have this additional functionality within the software. The devices that do will have the plus + sign next to the module name.

We can see then that the 2nd input point of the module will be available at address:

:I.Data[17] here, 1:I.Data[17] since the 1756-DNB Module is in slot one of the ControlLogix Processor rack.

Next, Ill map the 1734-OW2 module.

But I want to manually map this module to the next available word.

So by default, the 1734-OW2 module will be mapped to the second byte of Dword 0

I want to map it to the last 2 bits of Dword 0

So Ill click the advanced button on the output tab and Ill get a window with the location of the module in a tabular kind of form.

Ill need to change some of these values. Since I dont need to make any changes to the Map From location, Ill make only changes to the Map To location.

First Ill need to change the Bit from 8 to 30.

Also, since only 2 bits are being used for this module Ill change the bit length to 2 also.

This mode allows you to take a block of data and segment it into at most 4 parts.

In the Map From location, this shows the message type (Polled, COS, Strobed) and the starting location from within the module that you need start the new mapped segment.

Next Ill map the Bulletin 160 Drive

In order to get it lined up properly on a Word (16 bit) boundary Ill have to manually map the drive.

Ill map it to Dwords 2 and 3 of the input and Ill map it to Dword 2 and 3 on the output.

Here is how the Input table looks now.

Here is how the output table looks now.

I mapped the 160 drives output data in the same word location to make it easier to keep track of. I could have easily mapped it the next available word, (1:O.Data[1]) but this can make for difficult troubleshooting later on.

Next Ill map the 1794-ADN Flex adapter.

We have already configured the individual Flex modules previously, so the only thing left to do is add the 1794-ADN module to the scanlist.

Looking first to the summary tab of the 1794-ADN module, we will see the order of the RX and TX data as it appears for this module in the 1756-DNB scanner.

Im going to map the 1794-ADN in the following way.

Im going to map all 10 words of data from the 1794-ADN together in the DNBs Scanlist

Ill do the same for the Output. Then, in my ladder logic, Ill pull the data out to make it easier to work with.

Note: If you are adding the 1794-ADN to the scanlist and you get the following error.

Communication Error 12: Error Response received: Object State conflict

What this means is the 1794-ADN is mapped to a master scanner module, here the 1756-DNB module. First we have to Unmap the module and download to the 1756-DNB module to make the changes to the 1794-ADN. Once the module has been removed from the scanlist, the changed can be downloaded to the 1794-ADN module. Once the changes have been made, the module can be added back into the scanlist.

Input and Output Tables

The I/O tables should now look something like the following:

Input table

Output table

Now that the scanlist is finished, we need to download the information to the 1756-DNB scanner module.

Go back to the scanlist tab on the 1756-DNB and download All records when prompted to do so.

There thats done. The entire DeviceNet Network has been configured using RSNetWorx for DeviceNet.

There are a couple of more Tabs for the Scanner Module. I wont go into great detail here.

There is the ADR tab. By selecting this tab you can set up the Auto Device Replacement feature.

This allows out of the box, new devices that are software configurable, to be replaced on the network with no user intervention. In my case I could use ADR to automatically configure a new Photoeye from out the box when placed on the network if the old Photoeye fails.

http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/$$Search?OpenForm&Seq=1For Information on ADR refer to Knowledgebase Document ID 18168 and ID A17690 for configuring ADR

The other Tab is the Summary Tab. This shows a general table for the mapping of the scanner module. One thing to note:

The Summary Tab will show the 1756-DNB . In the column next to the Node column, it will say Active and No. This means the scanner is NOT in slave mode.

If the Active column said yes then the scanner would be in slave mode. Under normal operation the scanner should not be in slave mode.

Triggering Outputs and Monitoring Inputs

Now comes the fun part.

If you look at the 1756-DNB module, it should be flashing between its node number (by default A00) and the IDLE. There is a bit (CommandRegister.Run bit) that must be set to 1 to put the scanner in Run mode.

This bit, the run bit, is located in the command register for the scanner module. This is listed in publication 1756-IN566B-EN-P.

Below are descriptions for the data tables available in the 1756-DNB.

You can see that the command word is the In the Local Output, under the Command Register in the ControlLogix Processor data table.

In general the address for the 1756-DNB is as follows:

Local::I or O.Data[X]

So now well set this bit in our ladder logic. Open RSLogix 5000, if it is not already open. Go to the Output table and set bit 0 of word 0.

The CommandRegister.Run Bit It will look like this:

Here, the bit is used with an Unlatch command for safety reasons. I want the module to be put in Idle mode under certain circumstances. Youre application may vary.

Now that weve set the run bit for the scanner take a look at the LED display on the front of the 1756-DNB Module. You should now see the scanners node address as a solid display (by default the display is A00 since the module is set to node 00).

If you dont have A00 and RUN flashing (or alternate node address) youll have a flashing error code and node address of the node having a problem instead.

Below is the table for the Alphanumeric codes the 1756-DNB Module can display.

A few of the Common error codes are listed here for convenience. There are many error codes that can be displayed. Refer to publication 1756-IN5668B-EN-P for a list of those error codes

77 means there is a size mismatch and most likely the module is configured improperly. Go back and check the module in question, also verify the scanlist entry.

78 or 72 means the module in question is not communicating properly. A 72 means the connection is very intermittent and a 78 means the module is not responding at all. Usually faulty wiring or power are the causes of these errors.

Bus Off condition.

This can mean several things:

1. There is a short between one or both of the CAN lines (Blue or White) to either Ground (Shield or Black) or to 24v (Red). (Verify wiring with an ohmmeter or the 1788-MCHKR media checker).

2. It could mean there are devices on the network with the incorrect baud rate. Removed devices and cycle power after each device is removed. Check the 1756-DNBs baud rate refer the knowledge base and download the troubleshooting guide (document ID number G15098).

3. It could mean that there is a large amount of noise on your network. This could be due to High Voltage power cables being too close. Improper or lack of termination. Improper grounding (again refer Knowledge base document ID G15098 or to the DeviceNet Media installation guide, publication DN-6.7.2.

No Network Power (24V). Verify cabling or use an isolated, regulated, power supply rated for DeviceNet usage.

Once all the error codes have been resolved we can control the outputs and monitor the slave modules.

Im not going to go into writing ladder logic here, but rather I will show the bits that should be used to set outputs, set the reference speed on the bulletin 160 drive and start it running, how to see the status of the Photoeye.

Back in the scan list we mapped all the devices on our network. Each device now has its place in the processors data tables.

To make our lives much easier, RSLogix 5000 allows us to configure Alias data tables so that we know Exactly what bit does what. Some choose not to take advantage of this powerful feature. We will, however, take advantage if this feature.

Creating Aliases is easy. Ill walk through a couple and leave the rest as Exercises for the reader.

Then enter the information as follows, and then click Apply

Then the New tag will be added to the List of available tags

I have created a few more tags as follows.

The StackLight is mapped to the low byte of output Dword 0. I have created a single tag for the StackLight. This will help me conserve some memory in my L1 processor. But in doing this, I am forced to use ladder. Ill need to add a rung of ladder to move or copy the data from the Local Data array to the StackLight data array.

Since the StackLight has 5 lights attached to the base the first 1 bit of that byte will turn on lights

Ill set bits 0, 2 and 4 so that every other light is on.

Heres how it looks in the data table

Here I have, again, used Alias tags to clearly identify the 1734- OW2 Outputs.

Well set both relay outputs to 1.

Now well turn on the drive and set the reference speed.

First I have added four tags, each 1 INT long to accept the command word, speed Reference of the Drive for the output and the Command status and Speed reference status. Ill leave creating the ladder as an exercise for the user to get the data to and from the Local:1.Data array to the Tags created here.

First well set the reference speed. Here well be sending a raw unscaled value. Refer back to the data table mappings for the DN2 module attached to the drive.

Ill need to set a reference speed Ill just pick a random value to make the drive run.

So Ill set the register speed reference word to 345. This should give a decent visual speed.

Next Ill set the Net Reference and Net Control bits, bits 5 and 6. Without these bits set using these instances the drive will not function.

Lastly Ill set the run forward bit, bit 0. Once I set the run forward bit the drive begins to run forward.

You can see the status of the drive in the tags I have created for the command and speed reference data coming back from the drive. Ill leave the Flex module as an exercise.

Well look at the bulletin 160 drive status first.

Looking now at the command and speed reference status tags in the Controller tags:

Well see the Running Forward bit, bit 2 of the first word, is set to 1, As well as bits 5 and 6 set, Reference from Net and Control from Net.

After some time well see the At Reference Bit set, Bit 7 of word one

In the second word well see the speed of the drive. If, At Reference (bit 7) is set, then the reference speed will match the set control speed. Well look at the drive at reference.

Next well look at is the Input from the Photoeye. The other inputs, Ill leave as an exercise.

Well see our Aliased tag we crated toggle from 1 to 0 and back again as the Photoeye is triggered.

ON:

OFF:

Lastly well look at the Analog Output data table for the 1794-OE4 Module.

We are using the following data from the 1794-ADN configuration when we set up the modules in the modules configuration tab.

Since we are not using all the data for the 1794-OE4, we will create tags to correspond to the data table below.

So, our output tags will look like the following

Ill leave creating the tags and setting the delay time for the 1794-IB4 module as an Exercise.

Ill also leave creating tags and monitoring the 1794-ID2 module as an exercise.

Aliases for the Remote 1756-DNB

Ill create a couple of Aliases for the Remote 1756-DNB modules as well as an Alias for the CommandRegister.Run bit for each of them.

Device Address/Status Indicator and Device Failure Registers

Other status data of interest available in the 1756-DNB module is from the Status Tags is shown in the table below:

Description of this table can be found either in the Help In RSLogix 5000 or in publication 1756-UM515B-EN-P.

The Scrolling DeviceAddress and ScrollingDeviceStatus tags are a reflection of what is displayed on the LED display on the 1756-DNB Module.

The Device Failure table has one bit for each node in order. I.e. Bit 0 of word 216 is for node 0, bit 1 of 216 is for node 1 etc. The table shows if there is any problem with any node. Not communicating, having trouble communication, returning error responses, etc.

Those are the most used tables, for details on the other tables refer to publication 1756-UM515B-EN-P.