Cincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications www.clarkefire.com
Transcript
Page 1: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Cincinnati, Ohio USA - Glasgow, Scotland UK

Diesel Engines forNFPA-20 Fire Protection

Applications

www.clarkefire.com

Page 2: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Type•Diesel Engines for fire pump drive shall be

of the compression ignition type.•Spark-ignited internal combustion engines

shall not be used. (i.e. natural gas,propane or gasoline)

Page 3: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 - Engine Ratings

•Rated at SAE Conditions 25C (77F ) and91 m (300 ft ) above sea level.

•Engines must have at least a 10% reservein horsepower. (This is a UL-FMrequirement and all UL-FM engine ratingsreflect this requirement).

•Engines must be derated for Altitude andTemperature.•3% Derate for every 300 m (1000 ft ) above 91

m (300 ft ).•1% Derate for every 5.6C (10F ) above 25C

(77F ).

Page 4: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications
Page 5: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications
Page 6: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrument & Control

•Engines shall be regulated to have nomore the 10% speed difference betweenshutoff and maximum load. (Defined asdroop).

•Engines shall be provided with anoverspeed shutdown at 20% above ratedengine speed with a manual reset. (Onlyoverspeed shutdown or a signal from thediesel controller will shut down anengine.)

Page 7: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Derate Example•150 hp engine•Altitude 5,000 ft: CA=.86•Temperature 105F: CT=.973•Formula: (CA + CT–1) x hp = derated hp•(.86+.973-1)=.833 x 150 hp =124.95 hp

•Clarke Selection/Derate Calculatorprogram can calculate the exact sizeengine you need to use.

Page 8: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Overspeed Setting Verification

To verify the engine overspeed setting andfunction without overspeeding the engine,follow this procedure:•Start engine manually from the controller while

holding the overspeed verification switch in the‘up’position. Observe the shutdown RPM.

•Test switch returns to normal position whenreleased.

•Reset the overspeed switch on the engineinstrument panel and restart the engine fromthe controller to verity normal operation.

•EXAMPLE:Rated engine speed: 2100 rpmOverspeed setting: 2520 rpm (120% 2100 rpm)Verification shutdown: 1688 rpm (67% of 2520 rpm)

Page 9: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

JU and JW Series Instrument Panel

Page 10: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrumentation & Control

•Required Gauges:•Tachometer –indicates rpms•Oil Pressure Gauge•Coolant Temperature Gauge•Hour meter –record engine run time

•Additional Gauges:•Two voltmeters –one for each set of

batteries

Page 11: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrumentation & Control

•The engine instrument panel shall not beused as a junction box or conduit for anyac supply.

•Interconnections between the automaticcontroller and engine junction box shallbe made using stranded wire sized on acontinuous-duty basis.

•The dc interconnections between theautomatic controller and engine junctionbox and any ac power supply to theengine shall be routed in separate conduit.

Page 12: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications
Page 13: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrumentation & Control

•Main battery contactors supplyingcurrent to the starting motor shall becapable of manual mechanical operationto energize starting motor.•Manual toggles are provided on the Clarke

instrument panel and additionally manualstart contactors for only the JW6H & JX6Hseries engines.)

•Clarke electric starting standard;•One (1) starter on JW6H, JX6H units.•Two (2) starters on JU4H, JU6H units.

Page 14: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications
Page 15: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrumentation & ControlElectronic Engines

•Engines with an electronic control module(ECM) shall have an alternate ECM wiredto produce full power in the event ofprimary ECM failure.

•There shall be a single ECM SelectorSwitch, with no off position, to transitionfrom the primary ECM to the alternateECM.

•A visual indicator shall show when theengine is running with the alternate ECM.(On both the engine panel and on thediesel controller)

Page 16: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

JX Series Instrument Panel

Page 17: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrumentation & ControlElectronic Engines

•Any sensor necessary for the function ofthe ECM shall have a redundant sensorthat shall operate automatically in case offailure.

•A signal shall be provided to the dieselcontroller for fuel injector failure, low fuelpressure and any primary sensor failure.

Page 18: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrumentation & Control

•Each engine shall be provided with twostorage battery units.

•Electrolyte shall be added to the batteriesa minimum of 24 hours prior to the timethe engine has to be started.

•At 4.5C (40F ) each battery shall havetwice the capacity sufficient to maintain 3minute attempt-to-start cycle (15 secondsof cranking and 15 seconds of rest in sixconsecutive cycles).

Page 19: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrumentation & Control

•Storage batteries shall be rack supportedabove the floor to prevent water damage.

•Storage batteries shall be readilyaccessible for servicing.

•Storage batteries shall not be located infront of the engine mounted instrumentsand controls.

Page 20: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Instrumentation & Control

•There should be two means for rechargingthe storage batteries.•The battery chargers in the diesel controller is

the primary source.•The alternator on the engine is the secondary

source.

Page 21: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Cooling

•The engine cooling system shall beof the closed-circuit type.•Heat exchanger type•Radiator type

Page 22: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Cooling

•Cooling water shall be piped through athreaded rigid pipe from the discharge ofthe pump to the inlet of the heatexchanger.

•It is not permitted to use flexible tubingattached to the cooling loop.

Page 23: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Cooling

•The outlet for the wastewater coming fromthe heat exchanger shall be one sizelarger then the inlet.

•The wastewater shall be discharged into avisible open waste cone.

•Discharge can be piped to a suctionreservoir provided a visual flow indicatorand temperature indicators are installed.

Page 24: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Cooling•Heat exchanger standard equipment.•Sea water or fresh water; sacrificial anode

optional.•Engines are shipped without coolant.•Cooling water line (cooling loop) shall

have a manual by-pass.•Cooling water line and by-pass shall

include:•indicating manual shutoff valve•approved flushing-type strainer•pressure regulator•automatic valve•second indicating manual valve or check valve•pressure gauge

Page 25: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Cooling Water Line

Page 26: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Engine Coolant•Water, ethylene glycol, inhibitor coolant

mixture. 50% water 50% coolant.•Coolant to conform to ASTM D4985.

•Heat transfer•Corrosion resistance•Prevents scale and sludge build up•Provides freeze and boil over protection

•Pre-mix before installing in engine toprevent premature engine heater failure.

Page 27: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Cooling

•Coolant heater is the only AC power onengine; Separate AC junction box required.Do not use controller AC for power supply.

•Add coolant mixture before applying ACpower.

•All heaters single voltage; Optional ACvoltages available - location specific.

•Engine coolant maintained at 49C (120F ).

Page 28: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Protection

•The engine shall be protected againstpossible interruption of service throughexplosion, fire, flood, earthquake, rodents,insects, windstorm, freezing, vandalismand other adverse conditions.

•Application: The engine must be installedinside or protected from the weather andlow temperature.

Page 29: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Room Requirements•Rooms containing fire pumps shall be free

from storage & penetrations not essentialto the operation of the pump.

•Floors shall be pitched for adequatedrainage of escaping water from criticalequipment.

•The pump room shall be provided with afloor drain that will discharge to a frostfree location.

Page 30: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Air Requirements•The minimum ambient temperature for the

pump room is 4.5C (40F ).•The maximum temperature for the pump

room is 49C (120F ) at the air cleanerinlet with the engine running at rated load.

Page 31: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Air Requirements

•Inlet louver and ventilating system must:•Maintain 49C (120F ) in the room•Supply adequate air for engine

combustion•Adequate air for ventilating radiated heat;

both engine & exhaust system.•(Radiator Cooled Units shall be ducted

outdoors in a manner that will preventrecirculation and requires more air forcombustion and radiated heat removal.)

Page 32: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Installation and Operation Data

Page 33: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Installation and Operation Data

Page 34: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Heat Exchanger Ventilation

Page 35: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Radiator Ventilation

Page 36: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Radiator Ventilation

Page 37: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Radiator Ventilation

Page 38: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Fuel Tank Arrangement

•The fuel tank is sized for 5.07 liter/kW(1 gal/HP) plus 10% (5% for expansion and5% for sump).

•The fuel tank shall be reserved exclusivelyfor the fire pump diesel engine.

•There shall be one fuel tank per engine.

Page 39: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Fuel Tank Arrangement

•The fuel tank shall be located aboveground.

•The fuel tank outlet shall be located sothat its opening is no lower than the levelof the engine’s fuel transfer pump.

•The static head pressure limits shall notbe exceeded when the level of fuel in thetank is at a maximum.

•In sites where temperatures below 0C(32F ) could be encountered, the fuel tankshall be located in the pump room.

Page 40: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Fuel Arrangement

•The diesel engine must use clean #2diesel.

•#1, blended fuel, or jet fuel have a lowercetane ratings, which reduces the poweroutput by 10% of the engine comparedwith the listed power.

•Residual fuels, domestic heating furnaceoils, and drained lubrication oils shall notbe used.

•A guard, pipe protection, or approveddouble walled pipe shall be provided forall exposed fuel lines.

Page 41: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications
Page 42: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Fuel Arrangement

•Fuel supply and return lines shall beflame-resistant reinforced flexible hose.

•Fuel piping shall not be galvanized steelor copper.

•There shall be no shut-off in the fuelreturn line to the tank.

•The grade of fuel oil shall be indicated onthe fuel tank by letters that are a minimumof 152mm (6 in) in height and incontrasting color to the tank.

Page 43: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Exhaust

•Each engine shall have an independentexhaust system.

•A flex connector shall be used betweenthe engine and the exhaust pipe.

•The flex connector shall not be used formisalignment. (The purpose of the flex isto allow for thermal expansion and forisolating engine vibration from the rest ofthe exhaust system.)

Page 44: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –Engine Exhaust

•Back pressure in the exhaust systemshall not exceed the engine’s limit.•The exhaust sizing program on the Clarke

website can calculate the back pressure)

•Building supported; not enginesupported

•Insulation wrap the exhaust systems in-room components.

•Rain cap on outlet if necessary; tightconnections.

•Exhaust system shall terminate outsidewhere hot gases and sparks aredischarged to a safe location.

Page 45: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Exhaust Sizing

Page 46: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Exhaust Sizing

Page 47: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –System Operation

•Engines shall be started no less than oncea week and run for no less than 30minutes.

•The fire pump shall be started and broughtup to rated speed without interruptionwithin 20 seconds.

Page 48: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –System Operation•Batteries shall be kept charged at all times

and tested frequently (weekly test) todetermine condition.

•Only distilled water shall be used.•Battery plates shall be kept submerged at

all times.•The fuel storage tanks shall be kept as full

as practical at all times, but never below66% of tank capacity. A fuel levelindicator shall be provided to activate atthe 2/3rds tank level.

Page 49: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Basic Information –Regarding Clarke Diesel Fire

Pump Drivers

Page 50: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Clarke Engine SeriesCurrent Models

•JU4H Series -John Deere 4045 Series,4 stroke cycle; Torreon,Mexico; Saran, France•JU6H Series -John Deere 6068 Series,4 stroke cycle; Torreon,Mexico; Saran, France•JW6H Series -John Deere 6081 Series4 stroke cycle; Waterloo,Iowa USA•JX6H Series -John Deere 6125 Series4 stroke cycle; Waterloo,Iowa USA

Obsolete Models

•DDFP Series -Detroit Diesel 53 & 92Series, 2 stroke cycle;Detroit, MI, USA.•VMFP Series -VM Motori (DDC) 700 Series4 stroke cycle, Cento, Italy.•IK6H/R Series -Iveco 8000 Series,4 stroke cycle; Milan, Italy•PDFP Series -Perkins 1000 Series, 4stroke cycle, 4 & 6 cylinderfrom Petersborough,England

Page 51: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Clarke Model Nomenclature

Page 52: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

NFPA 20 –System Operation

•Oil Viscosity and Grade Specification•JU4H/JU6H/JW6H/JX6H Series engines

have a break in oil for the first year,afterwards require SAE 15W-40

•All engines are shipped with oil, unlessthe engine is shipped via airfreight.

Page 53: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Installation and Start Up Procedure

•Checklists on web-site for:•Engine Installation•Pre-Start-up•Start-Up

•Clarke Service Dealer locator on web-site.

•Warranty: Engine 24 mo./ Clarkecomponents 12 mo.

•Special preparation for long termstorage.

•Service parts shown on web-site.

Page 54: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications
Page 55: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Installation Inspection

•Engine Pump Alignment Check•Unit properly secured & grouted•Control wiring connected to junction box•Batteries serviced and charged 24 hours;

connected to the engine

Page 56: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Installation Inspection

•Cooling water connections properlyinstalled on engine heat exchanger, bothinlet and outlet; water solenoidoperational.

•Exhaust System properly sized andconnected

•Cooling System filled with premixed waterand coolant conditioner.

Page 57: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Installation Inspection

•Add engine oil to proper level•Fuel lines (supply and return) connected

to tank and engine•Fuel tank filled with clean #2 diesel, drain

water and sediment from tank•Engine jacket water heater connected to

correct AC Power•Air inlet filter installed on engine. Fresh

air supply adequate for enginecombustion and room ventilation.

Page 58: Diesel Engines for NFPA-20 Fire Protection  · PDF fileCincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for NFPA-20 Fire Protection Applications

Start Up Inspection

•Installation Inspection ChecklistVerification

•Manual start at engine panel•Manual start at controller•Cooling water line solenoid operation•Engine panel gauges operation•No leaks of fuel, engine coolant, raw water

or exhaust gases•High coolant temperature alarm•Low oil pressure alarm•Overspeed shutdown verification