TIANJIN PAUWAY POWER EQUIPMENT CO., LTD www.pauway.cn ADD: NO.130,Yongjin Road, High-End Equipment Industrial Park , Beichen District, Tianjin, 300405 P.R.China. Tel: 0086 22 86859198 Fax: 0086 22 86859100 Diesel generator(GB/T2820eqvISO8528) MTU series (220-2400KW) PWM550 standard specification Diesel engine: MTU 10V1600G20F Radiator: ambient temperature 50radiator, belt-driven fan, with fan safeguard. Alternator: single bearing alternator, IP23 protection level, H insulation level and temperature rise level. Standard control panel: self-start control panel, circuit breaker. 24V starter motor and connecting wires, starter breaker, 24V charging generator. Dry air filter, fuel filter and oil filter. Water separator, electrical heating type water jacket heater, battery charger, oil drain valve. Exhaust throat, industrial type silencer, exhaust elbow, flange, asbestos joint and screws. Accessories. Options Anti-condensation heater Fuel type water jacket heater Containerized type generator Truck type generator Synchronized control panel ATS Circuit breaker Daily fuel tank Base fuel tank Spare parts Generator specificationGenerator model PWM550 Standard type Prime KW/KVA 400/500 Standby KW/KVA 440/550 Frequency(HZ) 50 Voltage(VAC) 380/220 Connection 3P4W Specific fuel consumption 100% loadingL/H93.7 Voltage regulation range ≥±5% Steady state voltage deviation ≤±1% Silent type Transient voltage deviation /100% sudden reduce ≤25% Transient voltage deviation /sudden increase ≤-20% Voltage stable time/100% sudden reduce (S) ≤6 Voltage stable time/sudden increase (S) ≤6 Transient frequency deviation /100% sudden reduce ≤12% Transient frequency deviation /sudden increase ≤-10% Frequency stable time/100% sudden reduce(S) ≤5
Transcript
Page 1: Dieselgenerator - PAUWAY · 2017. 12. 1. · Brand/mufacturer MTU/UKRolls-Royce Power Prime Standby Power(KW) 448 493 Power(BHP) 601 661 Speed(r/min) 1500 CylinderNo.

TIANJIN PAUWAY POWER EQUIPMENT CO., LTDwww.pauway.cn

ADD: NO.130,Yongjin Road, High-End Equipment Industrial Park ,Beichen District, Tianjin, 300405 P.R.China.

Tel: 0086 22 86859198 Fax: 0086 22 86859100

Diesel generator(GB/T2820eqvISO8528)MTU series (220-2400KW)

PWM550 standard specification

Diesel engine: MTU 10V1600G20F

Radiator: ambient temperature 50℃ radiator, belt-driven fan, with fan safeguard.

Alternator: single bearing alternator, IP23 protection level, H insulation level and temperature rise level.

Standard control panel: self-start control panel, circuit breaker.

24V starter motor and connecting wires, starter breaker, 24V charging generator.

Dry air filter, fuel filter and oil filter.

Water separator, electrical heating type water jacket heater, battery charger, oil drain valve.

Exhaust throat, industrial type silencer, exhaust elbow, flange, asbestos joint and screws.

Accessories.

Options◇ Anti-condensation heater ◇Fuel type water jacket heater

◇ Containerized type generator ◇ Truck type generator

◇ Synchronized control panel ◇ ATS ◇ Circuit breaker

◇ Daily fuel tank ◇ Base fuel tank

◇ Spare parts

Generator specification:

Generator model PWM550 Standard type

Prime KW/KVA 400/500

Standby KW/KVA 440/550

Frequency(HZ) 50

Voltage(VAC) 380/220

Connection 3P4W

Specific fuel consumption 100% loading(L/H) 93.7

Voltage regulation range ≥±5%

Steady state voltage deviation ≤±1% Silent type

Transient voltage deviation /100% sudden reduce ≤25%

Transient voltage deviation /sudden increase ≤-20%

Voltage stable time/100% sudden reduce (S) ≤6

Voltage stable time/sudden increase (S) ≤6

Transient frequency deviation /100% sudden reduce ≤12%

Transient frequency deviation /sudden increase ≤-10%

Frequency stable time/100% sudden reduce(S) ≤5

Page 2: Dieselgenerator - PAUWAY · 2017. 12. 1. · Brand/mufacturer MTU/UKRolls-Royce Power Prime Standby Power(KW) 448 493 Power(BHP) 601 661 Speed(r/min) 1500 CylinderNo.

TIANJIN PAUWAY POWER EQUIPMENT CO., LTDwww.pauway.cn

ADD: NO.130,Yongjin Road, High-End Equipment Industrial Park ,Beichen District, Tianjin, 300405 P.R.China.

Tel: 0086 22 86859198 Fax: 0086 22 86859100

Diesel engineMTU diesel engine MTU is the engine sector of UK Rolls-Royce Group, well known as world famous heavy duty diesel engine manufacturer.

Perfect modularize structure design, integrated cylinder head, easy to maintain.

Excellent loading response feature, wide adaptability, 50 Centigrade radiator.

Excellent fuel consumption, low fuel and oil consumption, only 190-210g/kWh at 100% loading, low operation costs.

Excellent emission, NOx < 2000mg/m, meeting all demands of emission standards.

Long overhaul maintenance period up to 300000 hours. (Domestic brands are normally 8000 hours, while Japan and US

brands can reach up to 12000 hours)

Coupled with 10μ water separator and oil-return cooler, to optimize oil change interval up to 800 hours, 24 hours continuous

running.

No while smoke when running, low noise, low vibration, excellent size-power ratio and weight-power ratio.

ADEC-ECU8 and SMART-CONNECT system lead to better connections and default self diagnosis.

Re:The data above is based on ISO3046 standards—elevation 110m(361ft),atmosphere 100kPa (29.53inHg),

Model 10V1600G20F

Brand/mufacturer MTU/UK Rolls-Royce

Power Prime Standby

Power(KW) 448 493

Power(BHP) 601 661

Speed(r/min) 1500

Cylinder No. 10

Cylinder arrange V

Stroke Four

Induction Turbo

Fuel supply High pressure common rail

Cooling Water cooled

Intercooling Water-air

BorexStroke 122x150mm

Displacement 14 L

Compression ratio 17.5:1

Rotation direction Anti-clockwise viewed on flywheel

Lubricating capacity(L) 61

Coolant capacity(L) 120

Gas volume(L/S) 480

Exhaust volume(L/S) 1380

Exhaust temperature(℃) 540

Fuel consumption (loading

%)

25% 50% 75% 100%

Fuel consumption(g/kwh) 233 215 191 189

Lubricating system Oil filter, with separate seat, oil pump, oil dipstick.

Cooling system Double thermostate, water pump, radiator, air-air intercooler, adopting to 40

Centigrade ambient temperature.

Induction system Built-in air filter, turbocharger.

Starting system 24V starter motor, DC charging generator(built-in voltage regulator and breaker)

Sensor High coolant temperature switch, low oil pressure switch, low coolant quantity sensonr,

speed sensor.

Page 3: Dieselgenerator - PAUWAY · 2017. 12. 1. · Brand/mufacturer MTU/UKRolls-Royce Power Prime Standby Power(KW) 448 493 Power(BHP) 601 661 Speed(r/min) 1500 CylinderNo.

TIANJIN PAUWAY POWER EQUIPMENT CO., LTDwww.pauway.cn

ADD: NO.130,Yongjin Road, High-End Equipment Industrial Park ,Beichen District, Tianjin, 300405 P.R.China.

Tel: 0086 22 86859198 Fax: 0086 22 86859100Induct temperature 25°C(77°F),relative humidity 30%, using NO.2 fuel diesel or equal ASTM D2 fuel diesel.

Alternator STAMFORD/MARATHONStamfordProduction is accordance with GB755,BS5000,VDE0530,NEMAMG1-22,IEC34-1,CSA22.2 and AS1359 standard.

Voltage(V) 380/220 400/230 415/240 440/254Capacity kVA 455 500 455 450Power kW 364 400 364 360Efficiency (%) 94 93.8 94.4 94.6Bearing number 1Power factor 0.8Protection level IP23Elevation requirement ≤1000mExcitation mode Permanent Magnet excitation

Insulation level/Temperature rise level

H/H

Telephone influence factor TIF <50Telephone harmonic factor THF <2%Cooling air flow: 1.035 m3/s

Automatic control panel DEEPSEA/SMARTGEN/DEIF/COMAPEU and domestic brand single/synchronizedcontrol system Optional Smartgen, DEIF, ComAp intelligent controller.

Automatic control panel can realize unattended

operation.

Can receive remote run/stop control signal.

Large LCD display, Chinese (English) operation/ display menu.

With automatic, manual, stop, emergency stop functions, programmable output and input interface, multi-function display,

can simultaneous display parameters via data, symbol and bar chart.

Standard interface: RS-232 (Modbus communication protocol), users can remote control, test and report generators by

communication (web) or central monitor system.

Generator dimension Standard/SilentStandardDimension L*W*H(mm) Weight (KG)

Standard 3350*1630*2030 4400

Silent 4750*1680*2400 5260


Recommended