AIR CONDITIONERS CITY MULTI
Models PUHY-200YMF-C, 250YMF-CPUHY-P200YMF-C, P250YMF-CPUY-200YMF-C, 250YMF-CPUY-P200YMF-C, P250YMF-C
PURY-200YMF-C, 250YMF-CPURY-P200YMF-C, P250YMF-C
CMB-P104, P105, P106, P108, P1010, P1013, P1016V-E
Service Handbook
7/25/2019 dieu hoa ADMIN.pdf
2/166
1
Contents1 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT .... 3
[1] Storage of Piping Material ................................................................. 4
[2] Piping Machining............................................................................... 5
[3] Necessary Apparatus and Materials and Notes on Their Handling .. 6
[4] Brazing .............................................................................................. 7
[5] Airtightness Test ................................................................................ 8
[6] Vacuuming ........................................................................................ 8
[7] Charging of Refrigerant..................................................................... 9
[8] Dryer ................................................................................................. 9
2 COMPONENT OF EQUIPMENT ........................................................... 10[1] Appearance of Components ........................................................... 10
[2] Refrigerant Circuit Diagram and Thermal Sensor ........................... 18
[3] Electrical Wiring Diagram ................................................................ 24
[4] Standard Operation Data ................................................................ 33
[5] Function of Dip SW and Rotary SW................................................ 41
3 TEST RUN ............................................................................................. 47[1] Before Test Run .............................................................................. 47
[2] Test Run Method ............................................................................. 51
4 GROUPING REGISTRATION OF INDOOR UNITS WITH REMOTE
CONTROLLER....................................................................................... 52
5 CONTROL.............................................................................................. 58[1] Control of Outdoor Unit ................................................................... 58
[2] Control of BC Controller .................................................................. 63
[3] Operation Flow Chart ...................................................................... 64
[4] List of Major Component Functions ................................................ 70[5] Resistance of Temperature Sensor................................................. 73
6 REFRIGERANT AMOUNT ADJUSTMENT ............................................ 74[1] Refrigerant Amount and Operating Characteristics ........................ 74
[2] Adjustment and Judgement of Refrigerant Amount ........................ 74
7 TROUBLESHOOTING ........................................................................... 84[1] Principal Parts ................................................................................. 84
[2] BC Controller Disassembly Procedure ..........................................113
[3] Self-diagnosis and Countermeasures Depending on the Check
Code Displayed .............................................................................. 119
[4] LED Monitor Display ..................................................................... 142
8 PREPARATION, REPAIRS AND REFRIGERANT REFILLING WHEN
REPAIRING LEAKS ............................................................................. 161[1] Location of leaks: Extension piping or indoor units (when cooling)161
[4] Location of leaks: Outdoor unit (when heating) ............................ 163
9 CHECK THE COMPOSITION OF THE REFRIGERANT
(PURY-P200250YMF-C only) ................................................................ 164
7/25/2019 dieu hoa ADMIN.pdf
3/166
2
Safety precautions
Before installation and electric work
Before installing the unit, make sure you read all
the Safety precautions.
The Safety precautions provide very importantpoints regarding safety. Make sure you follow
them.
This equipment may not be applicable to
EN61000-3-2: 1995 and EN61000-3-3: 1995.
This equipment may have an adverse effect on
equipment on the same electrical supply system.
Please report to or take consent by the supply
authority before connection to the system.
Symbols used in the text
Warning:Describes precautions that should be observed toprevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to
prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Beware of electric shock (This symbol is displayed on the
main unit label.)
Warning:
Carefully read the labels affixed to the main unit.
Warning:
Use the specified cables for wiring. Make the connections
securely so that the outside force of the cable is not
applied to the terminals.
- Inadequate connection and fastening may generate heat and
cause a fire.
Have all electric work done by a licensed electrician
according to Electric Facility Engineering Standard and
Interior Wire Regulationsand the instructions given in
this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock and fire may result.
Securely install the cover of control box and the panel.
- If the cover and panel are not installed properly, dust or water
may enter the outdoor unit and fire or electric shock may
result.
After completing service work, make sure that refrigerant
gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater,
stove, oven, or other heat source, it may generate noxious
gases.
Do not reconstruct or change the settings of the protectiondevices.
- If the pressure switch, thermal switch, or other protection
device is shorted and operated forcibly, or parts other than
those specified by Mitsubishi Electric are used, fire or
explosion may result.
7/25/2019 dieu hoa ADMIN.pdf
4/166
3
11111 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT
Caution
Do not use the existing refrigerant piping.
The old refrigerant and refrigerator oil in the existing
piping contains a large amount of chlorine which may
cause the refrigerator oil of the new unit to deterio-
rate.
Use refrigerant piping made of phosphorus deoxi-
dized copper and copper alloy seamless pipes and
tubes. In addition, be sure that the inner and outer
surfaces of the pipes are clean and free of hazardous
sulphur, oxides, dust/dirt, shaving particles, oils,
moisture, or any other contaminant.
Contaminants on the inside of the refrigerant piping
may cause the refrigerant residual oil to deteriorate.
Store the piping to be used during installation indoors
and keep both ends of the piping sealed until just
before brazing. (Store elbows and other joints in a
plastic bag.)
If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may
result.
Use ester oil, ether oil or alkylbenzene (small
amount) as the refrigerator oil to coat flares and
flange connections.
The refrigerator oil will degrade if it is mixed with a
large amount of mineral oil.
Use liquid refrigerant to seal the system.
If gas refrigerant is used to seal the system, the com-position of the refrigerant in the cylinder will change
and performance may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine
in the refrigerant may cause the refrigerator oil to de-
teriorate.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refriger-ant cycle and cause the refrigerator oil to deteriorate.
Do not use the following tools that have been used
with conventional refrigerants.
(Gauge manifold, charge hose, gas leak detector, re-
verse flow check valve, refrigerant charge base,
vacuum gauge, refrigerant recovery equipment)
If the conventional refrigerant and refrigerator oil are
mixed in the R407C, the refrigerant may deterio-
rated.
If water is mixed in the R407C, the refrigerator oil
may deteriorate.
Since R407C does not contain any chlorine, gas
leak detectors for conventional refrigerants will not
react to it.
Do not use a charging cylinder.
Using a charging cylinder may cause the refrigerant
to deteriorate.
Be especially careful when managing the tools.
If dust, dirt, or water gets in the refrigerant cycle, the
refrigerant may deteriorate.
If the refrigerant leaks, recover the refrigerant in the
refrigerant cycle, then recharge the cycle with the
specified amount of the liquid refrigerant indicated
on the air conditioner.
Since R407C is a nonazeotropic refrigerant, if addi-
tionally charged when the refrigerant leaked, the com-position of the refrigerant in the refrigerant cycle will
change and result in a drop in performance or abnor-
mal stopping.
7/25/2019 dieu hoa ADMIN.pdf
5/166
4
[1] Storage of Piping Material
(1) Storage location
Store the pipes to be used indoors. (Warehouse at site or owners warehouse)
Storing them outdoors may cause dirt, waste, or water to infiltrate.
(2) Pipe sealing before storage
Both ends of the pipes should be sealed until immediately before brazing.Wrap elbows and Ts in plastic bags for storage.
* The new refrigerator oil is 10 times more hygroscopic than the conventional refrigerator oil (such as Suniso). Water
infiltration in the refrigerant circuit may deteriorate the oil or cause a compressor failure. Piping materials must be
stored with more care than with the conventional refrigerant pipes.
7/25/2019 dieu hoa ADMIN.pdf
6/166
5
[2] Piping Machining
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
Use only the necessary minimum quantity of oil !
Reason :
1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.
Notes :
Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.
Do not use oils other than ester oil, ether oil or alkylbenzene.
7/25/2019 dieu hoa ADMIN.pdf
7/166
6
[3] Necessary Apparatus and Materials and Notes on Their Handling
The following tools should be marked as dedicated tools for R407C.
Apparatus Used Use R22 R407C
Gauge manifold Evacuating, refrigerant filling Current product
Charging hose Operation check Current product
Charging cylinder Refrigerant charging Current product Do not use.
Gas leakage detector Gas leakage check Current product Shared with R134a
Refrigerant collector Refrigerant collection R22 For R407C use only
Refrigerant cylinder Refrigerant filling R22
Vacuum pump Vacuum drying Current product
Vacuum pump with a check valve Current product
Flare tool Flaring of pipes Current product
Bender Bending of pipes Current product
Application oil Applied to flared parts Current product
Torque wrench Tightening of flare nuts Current product
Pipe cutter Cutting of pipes Current product
Welder and nitrogen cylinder Welding of pipes Current product
Refrigerant charging meter Refrigerant charging Current productVacuum gauge Checking the vacuum degree Current product
Symbols : To be used for R407C only. Can also be used for conventional refrigerants.
Tools for R407C must be handled with more care than those for conventional refrigerants. They must not come into contact
with any water or dirt.
Identification of dedi-
cated use for R407C
: Record refrigerant
name and put brown
belt on upper part of
cylinder.
Can be used byattaching an adapter
with a check valve.
Ester oil or Ether oil or
Alkybenzene (Small
amount)
7/25/2019 dieu hoa ADMIN.pdf
8/166
7
[4] Brazing
No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt,
etc.) does not enter the refrigerant circuit.
Example : Inner state of brazed section
When non-oxide brazing was not used When non-oxide brazing was used
Items to be strictly observed :
1. Do not conduct refrigerant piping work outdoors on a rainy day.
2. Apply non-oxide brazing.3. Use a brazing material (Bcup-3) which requires no flux when brazing between copper pipes or between a copper pipe
and copper coupling.
4. If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends of them.
Reasons :
1. The new refrigerant oil is 10 times more hygroscopic than the conventional oil. The probability of a machine failure if
water infiltrates is higher than with conventional refrigerant oil.
2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.
Note :
Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When
applying non-oxide brazing, use nitrogen.
7/25/2019 dieu hoa ADMIN.pdf
9/166
8
[5] Airtightness Test
No changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407C
leakage.
Halide torch R22 leakage detector
Items to be strictly observed :
1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipments airtightness, taking
temperature variations into account.
2. When investigating leakage locations using a refrigerant, be sure to use R407C.
3. Ensure that R407C is in a liquid state when charging.
Reasons :
1. Use of oxygen as the pressurized gas may cause an explosion.
2. Charging with R407C gas will lead the composition of the remaining refrigerant in the cylinder to change and this
refrigerant can then not be used.
Note :
A leakage detector for R407C is sold commercially and it should be purchased.
[6] Vacuuming
1. Vacuum pump with check valve
A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant
circuit when the vacuum pump power is turned off (power failure).
It is also possible to attach a check valve to the actual vacuum pump afterwards.
2. Standard degree of vacuum for the vacuum pump
Use a pump which reaches 0.5 Torr (500 MICRON) or below after 5 minutes of operation.
In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the
vacuum pump is not properly maintained, the degree of vacuum may be too low.
3. Required accuracy of the vacuum gauge
Use a vacuum gauge that can measure up to 5 Torr. Do not use a general gauge manifold since it cannot measure a
vacuum of 5 Torr.
4. Evacuating time
Evacuate the equipment for 1 hour after755 mmHg (5 Torr) has been reached.
After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
5. Operating procedure when the vacuum pump is stopped
In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the
charge hose to drawn in air before stopping operation.
The same operating procedure should be used when using a vacuum pump with a check valve.
7/25/2019 dieu hoa ADMIN.pdf
10/166
9
[7] Charging of Refrigerant
R407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.
For a cylinder with a syphon attached For a cylinder without a syphon attached
Cylinder color identification R407C-Gray Charged with liquid refrigerant
R410A-Pink
Reasons :
1. R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is
charged with R407C gas, then the refrigerant whose evaporation temperature is closest to the outside temperature is
charged first while the rest of refrigerants remain in the cylinder.
Note :
In the case of a cylinder with a syphon, liquid R407C is charged without turning the cylinder up side down. Check the
type of cylinder before charging.
[8] Dryer
1. Replace the dryer when the refrigerant circuit is opened (Ex. Change the compressor, full gas leakage). Be sure to
replace the dryer with a CITY MULTI Series Y (For use with R407C).
If any other product is used, the unit will be damaged.
2. Opening the refrigerant circuit after changing to a new dryer is less than 1 hour. The replacement of the dryer should
be the last operation performed.
Cylin-der
Cylin-der
ValveValve
Liquid Liquid
7/25/2019 dieu hoa ADMIN.pdf
11/166
10
22222 COMPONENT OF EQUIPMENT
[1] Appearance of Components
Outdoor unit
PU(H)Y-(P)200, 250YMF-C
PUHY-YMF-C PUY-P-YMF-C
Propeller fan
Fan motor
SCC Accumulator
Compressor
Drier
Compressor
Heatexchanger(front)
Control Box
Heatexchanger(rear)
SCC Accumulator
Compressor
4way valve
7/25/2019 dieu hoa ADMIN.pdf
12/166
11
PURY-P200250YMF-C
Propeller fan
Heat exchanger(front)
Control box
Compressor
Fan motor
Heat exchanger(rear)
PURY-YMF-C PURY-P-YMF-C
SV3
SV4
SV6
SV5
SV block Accumulator
CV block Compressor
4way valve
SV3SV4
SV6
SV5
SV block4way valve
CS circuit Accumulator
Compressor
Drier
CV block
7/25/2019 dieu hoa ADMIN.pdf
13/166
12
Controller Box
FANCON board
INV board
MAIN board
Noise filter
Choke coil (L2)
Terminal block TB1A Power Source Terminal block TB7 Transmission (Centralized control)
Terminal block TB3 Transmission
Inteligent Power Module (IPM)
G/A board
Diode stack (DS)
Magnetic contactor (52C)
Capacitor (C2, C3)(Smoothing capacitor)
7/25/2019 dieu hoa ADMIN.pdf
14/166
13
MAIN board
PUHY / PURY
CN51Indication distance3-4CompressorON/OFF3-5Trouble
CNRS3
Serial transmission toINV board
CN3D
SW1
CNTR CNFC1
CNVCC4Power sourcefor control(5V)
CN20Power supply3L11N
SW3SW4 SW2 SWU2 SWU1
CNS1 CNS2 CN40 CN41 CNVCC3Power Source
for control1-230V1-330V4-612V5-65V
CN3S
CN3N
LD1Service LED
7/25/2019 dieu hoa ADMIN.pdf
15/166
14
INV board
CNDR2Out put toG/A board
CNTH
CN15V2Power supplyfor IPM control
CNACCT
CNAC2
Powersource1L23N5G
CN52CControl for52C
CNFANControlfor MF1
CNR
CNRS2Serial transmissionto MAIN board
SW1
CNVDC1-4DC-560V
CNVCC4Power supply (5V)
CNL2Choke coil
CNVCC2Power supply
1-230V,1-330V4-612V,5-65V
7/25/2019 dieu hoa ADMIN.pdf
16/166
15
FANCON board
CNFANCNPOW
CNFC2
CN15V1
CNDR1
CNIPM1
G/A board
CNE CNDC1
7/25/2019 dieu hoa ADMIN.pdf
17/166
16
BC controller
CNTR
CN02M-NETtransmission
CN03
CN12Powersupply1EARTH3N5L
SW4 SW2 SW1
7/25/2019 dieu hoa ADMIN.pdf
18/166
17
RELAY 10 board
RELAY 4 board
7/25/2019 dieu hoa ADMIN.pdf
19/166
18
[2] Refrigerant Circuit Diagram and Thermal Sensor1PUHY-200YMF-C, 250YMF-C
: Solenoid valve
: Orifice
: Capillary
: Check valve
: Thermal sensor
: Strainer
SP : Service port
ACC : Accumulator
TH1
TH6
TH7
TH8
TH5
TH2
Indoorunit
O/S
63HSC
J1
Comp
HEX2
HEX1
SCC
LEV1
ST4
BV2
ST2
BV1
ST1
CJ2
C
V1
ST3
SV1
SV2
CP1
SLEV
SA
MA
CP2
63H
7/25/2019 dieu hoa ADMIN.pdf
20/166
1 9
: Solenoid valve
: Orifice
: Capillary
: Check valve
: Thermal sensor
: Strainer
SP : Service port
ACC : Accumulator
2PUY-200YMF-C, 250YMF-C
SA
MA
TH6
HEX2
HEX1
TH7
TH8
TH5
TH2
CJ1
LEV1
SLEV
BV2
ST2
BV1
ST1
ST3
ST4
SV1
SV2
CJ2
O/S
Comp
CP1
63HS
SCC
CP2
63H
7/25/2019 dieu hoa ADMIN.pdf
21/166
2 0
: Solenoid valve
: Orifice
: Capillary
: Check valve
: Thermal sensor
: Strainer
SP : Service port
ACC : Accumulator
HEX1
HEX2
TH6
SCC
SV3
CP1
CJ1
CJ2
63HS
SV1
ST3
CV1
O/S
63H
63LS
MA
SA
SLEV
CP4
TH9
TH7
ST4
LEV1
ST2BV2
Indoorunits
ST1BV1
Comp
Drier
TH2
TH10
CP3
SV4
ST9
ST8
TH8
TH5
SV2
ST5
TH1
3PUHY-P200YMF-C, P250YMF-C
7/25/2019 dieu hoa ADMIN.pdf
22/166
21
4PUY-P200YMF-C, 250YMF-C
HEX2
HEX1
TH
6
SV3
CJ1
CJ2
63H
SV1
SV2
CV2
CV1
TH1
ST5
MA
SA
SLEV
TH7
ST4
LEV1
SCC
Comp
O/S
Drier
TH10
CP
TH8
CP3
TH5
ST3
TH9
TH2
ST2
BV2
Indoorunits
ST1
BV1
63LS
63HS
: Solenoid valve
: Orifice
: Capillary
: Check valve
: Thermal sensor
: Strainer
SP : Service port
ACC : Accumulator
7/25/2019 dieu hoa ADMIN.pdf
23/166
2 2
5PURY-200YMF-C, 250YMF-C
TH10
TH1
TH5
O/S
63HS
63LS
Comp
BV2
BV1ST1
CV1
ST6
SV1SV2
CP1
CJ1
CJ2
SLEV
SA
MA
63H
TH10
TH6
HEXb
CV7HEXf3
HEXf2
HEXf1
CV10
CV3CV2
CV5CV4CV9CV8
CV6
TH7
Check Valves Block
ACC
Solenoid Valves Block
SV6
SV5SV3
SV4
Distributor
TH23
TH21
TH22
LEV
SVC
SVA
SVB
Indoor
units
BC controller
CMB-P104V-E
Gas/liquid separator
63HS1
LEV1
63HS3
LEV3
TH12
TH11
TH15
TH16
: Solenoid valve
: Orifice
: Capillary
: Check valve
: Thermal sensor
: Strainer
SP : Service port
ACC : Accumulator
7/25/2019 dieu hoa ADMIN.pdf
24/166
2 3
6PURY-P200YMF-C, P250YMF-C: Solenoid valve
: Orifice
: Capillary
: Check valve
: Thermal sensor
: Strainer
SP : Service port
ACC : Accumulator
TH23
TH21
TH22
LEV
SVC
SVA
SVB
Indoor
units
BC controller
CMB-P104V-E
Gas/liquid separator
63HS1
LEV1
63HS3
LEV3
TH12
TH11
TH15
TH16
TH1
O/S
63HS
ST5
CV1
ST6
SJ1
63H63LS
SV1 SV2
CP1
CJ2
SLEV
ACC
SA
MA
CV10CV9CV8
Check Valves Block
TH5
BV2
BV1ST1
TH6
HEXb
CV7HEXf3
HEXf2
HEXf1
CV3CV2CV5CV4
CV6
TH7
Solenoid Valves
Block
SV6SV5SV3
SV4
Distributor
TH9Drier
TH2
CS(Composition Sensing) circuit
CP2
Comp
TH10
7/25/2019 dieu hoa ADMIN.pdf
25/166
7/25/2019 dieu hoa ADMIN.pdf
26/166
7/25/2019 dieu hoa ADMIN.pdf
27/166
26
Symbolexplanation
PE
123123
EARTH
Terminalblock
(forTransmission)
TB02
Terminalblock
(forpowersource)
TB01
Name
Sym
bol
Solenoidvalve
Solenoidvalve
Solenoidvalve
Solenoidvalve
Expansionvalve
Thermistersensor
Transformer
Name
Symbol
SV1
4A
SV1
4B
SV1
4C
SVM
TRTH11
16
LEV1,3
PS1,3
Pressuresensor
Transmissionline
Shieldwire /
N
220V
240V5
0Hz
Powersource
BCBoard
LE
V1
TB0116151413121110987654321
16
15
14
13
12
11
10987654321
SVM
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SV1C
SV1A
SV1B
}
31
CNTR
CN02
CN12
1
5
3
3
1
7531753175317531
TR
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X21
}DC
30V
6
5
4
3
2
1
6
5
4
3
2
1
LEV3
1 2 3
CNP1
1 2 3
CNP3
21 1 2 3 4 5 6 7 8 4321
1
2
3
2
1
CN03
CN13
CN10
CN11
CN07
CN
05
L N
TH11
TH12
TH15
TH16
PS1
PS3
20
22V
TB02 M
2M1
CN26
CN27
CN28
CN29
TB01
220
240V
C
N36
1
1
1
1
Note:1.TB02isterminalblockfortransmission.
Neverconnectpowerlineto
it.
2.1:SVM
isnotbuiltindepen
dingonmodels.
3
CMB-P104V
-E
7/25/2019 dieu hoa ADMIN.pdf
28/166
27
4
CMB-P105V
-E
Symbolexplanation
PE
123123
EARTH
Terminalblock
(forTransmission)
TB02
Terminalblock
(forpowersource)
TB01
Name
Sym
bol
Solenoidvalve
Solenoidvalve
Solenoidvalve
Solenoidvalve
Expansionvalve
Thermistersensor
Transformer
Name
Symbol
SV1
5A
SV1
5B
SV1
5C
SVM
TRTH11
16
LEV1,3
PS1,3
Pressuresensor
Transmissionline
Shieldwire /
N
220V
240V50Hz
Powersource
BC
Board
LEV1
TB011
615
21
21
14
13
12
11
10
987654321
16
15
14
13
12
11
10987654321
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SV1C
SV1A
SV1B
}
31
CNTR
CN02
CN12
1
5
3
3
1
7531753175317531
TR
X2
X1
X3
0
X4
X3
X3
1
X6
X5
X3
2
X8
X7
X3
3
X21
}DC
30V
6
5
4
3
2
1
6
5
4
3
2
1
LEV3
1 2 3
CNP1
1 2 3
CNP3
21 1 2 3 4 5 6 7 8 4321
1
2
3
2
1
CN03
CN13
CN10
CN11
CN07
CN05
L N
TH11
TH12
TH15
TH16
PS1
PS3
20
22V
TB02 M
2M1
CN26
CN27
CN28
CN29
TB01
220
240V
SV5C
SV5A
SV5B
7531
X1
0
X9
X3
4
CN30
SVM
CN36
1
1
1
1
Note:1.TB02isterminalblockfortransmission.
Neverconnectpowerlinetoit.
2.
1
:SVM
isnotbuiltindepen
dingonmodels.
7/25/2019 dieu hoa ADMIN.pdf
29/166
28
5
CMB-P106V
-E
PE
123123
EARTH
Transmissionline
Shieldwire /
N
220V
240V50Hz
Powersource
BCBoard
3
1
LEV1
TB01
SV6B
SV6A
SV6C
16
15
14
13
12
11
10
987654321
16
15
14
13
12
11
10987654321
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SVM
SV1C
SV1A
SV1B
}
4
3
2
11
2
3
4
CN38
31
CNTR
CN02
CN12
1
5
3
3
1
753175317531753175317531
TR
3 CNVCC1
1
2
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}DC
30V
6
5
4
3
2
1
6
5
4
32
1
LEV3
1 2 3
CNP1
1 2 3
CNP3
21 1 2 3 4 5 6 7 8 4321
1
2
3
2
1
CN51
CN50
CNOUT1
CNOUT3
CN03
CN13
CN10
CN11
CN07
CN05
L N
TH11
TH12
TH15
TH16
PS1
PS3
20
22V
TB02 M
2M1
CN26
CN2
7
CN28
CN29
CN30
CN31
TB01
220
240V
CN
36
Symbolexplanation
Terminalblock
(forTransmission)
TB02
Terminalblock
(forpowersource)
TB01
Name
Symbol
Solenoidvalve
Solenoidvalve
Solenoidvalve
Solenoidvalve
Expansionvalve
Thermistersensor
Transformer
Name
Symbol
SV1
6A
SV1
6B
SV1
6C
SVM
TRTH11
16
LEV1,3
PS1,3
Pressuresensor
1
1
1
1
7
6
5
4
3
2
1
1
2
3
4
5
6
Note:1.TB02isterminalblockfortra
nsmission.
Neverconnectpowerlineto
it.
2.1:SVM
isnotbuiltindepend
ingonmodels.
7/25/2019 dieu hoa ADMIN.pdf
30/166
29
6
CMB-P108V
-E
PE
123123
EARTH
}Powersource
}}L N
Powersource
/N
220V
240V50Hz
Transmissionline
Shieldwire
SVM
BCBoard
CN38
1
31
CNTR
CN50
CN5
1
7
6
5
4
3
2
1
1
2
3
4
5
6
CN02
CN12
1
5
3
3
1
753175317531753175317531
3
TR
3CNVCC1
1
2
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}DC
30V
6
5
4
3
2
1
6
5
4
3
2
1
LEV3
LEV1
1 2 3
CNP1
1 2 3
CNP3
21 1 2 3 4 5 6 7 8 4321
1
2
3
2
1
CN03
CN13
CN10
CN11
CN07
CN05
CN36
TH11
TH12
TH15
TH16
PS1
PS3
20
22V
TB02
M2M1
CN26
CN27
CN28
CN29
CN30
CN31
TB01
220
240V
LEV1
7
6
5
4
3
2
1
TB01
SV6B
SV6A
SV6C
16
15
14
13
12
11
10987654321
16
15
14
13
12
11
10
987654321
RELAY4Board
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
CN32
CN33
CN39
3 1
SV7C
SV7A
SV7B
SV8C
SV8A
SV8B
SV1C
SV1A
SV1B
X14
X13
X36
X37
X15
X16
9
8
7
6
5
4
3
2
1
16
15
10
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
CN
52
7
5
3
1
7
5
3
1
Symbolexplanation
Terminalblock
(forTransmission)
TB02
Terminalblock
(forpowersource)
TB01
Name
Sym
bol
Solenoidvalve
Solenoidvalve
Solenoidvalve
Solenoidvalve
Expansionvalve
Thermistersensor
Transformer
Name
Symbol
SV1
8A
SV1
8B
SV1
8C
SVM
TRTH11
16
LEV1,3
PS1,3
Pressuresensor
CNOUT1
CNOUT3
1
Note:1.TB02isterminalblockfortransmission.
1
1
1
Neverconnectpowerlinetoit.
2.1:SVM
isnotbuiltindependingonmodels.
7/25/2019 dieu hoa ADMIN.pdf
31/166
30
7
CMB-P1010
V-E
PE
123123
EARTH
}
Powersource
}}L N
Powersource
/N
220V
240V50Hz
Transmissionline
Shieldwire
SV10B
SV10A
SV10C
SV9B
SV9A
SV9C
BC
Board
CN38
1
31
CNTR
CN50
CN5
1
7
6
5
4
3
2
1
1
2
3
4
5
6
CN02
CN12
1
5
3
3
1
753175317531753175317531
3
TR
3CNVCC1
1
2
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}
DC
30V
6
5
4
3
2
1
6
54
3
2
1
LEV3
LEV1
1 2 3
CNP1
1 2 3
CNP3
21 1 2 3 4 5 6 7 8 4321
1
2
3
2
1
CN03
CN13
CN10
CN11
CN07
CN05
CN36
TH11
TH12
TH15
TH16
PS1
PS3
20
22V
TB02
M2M1
CN26
CN27
CN28
CN29
CN30
CN31
TB01
220
240V
LEV1
7
6
5
4
3
2
1
1
2
3
4
5
6
CN35
TB01
SV6B
SV6A
SV6C
SVM
16
15
14
13
12
11
10987654321
16
15
14
13
12
11
10
987654321
RELAY4Board
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
CN32
CN33
CN34
CN39
3 1
SV7C
SV7A
SV7B
SV8C
SV8A
SV8B
SV1C
SV1A
SV1B
X14
X13
X36
X37
X15
X16
9
8
7
6
5
4
3
2
1
16
15
10
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
X18
X17
X38
X39
X19
X20
CN
52
CN53
5
7
3
1
7
5
3
1
7
5
3
1
7
5
3
3
3
1
Symbolexplanation
Terminalblock
(forTransmission)
TB02
Terminalblock
(forpowersource)
TB01
Name
Sym
bol
Solenoidvalve
Solenoidvalve
Solenoidvalve
Solenoidvalve
Expansionvalve
Thermistersensor
Transformer
Name
Symbol
SV1
10A
SV1
10B
SV1
10C
SVM
TRTH11
16
LEV1,3
PS1,3
Pressuresensor
CNOUT1
CNOUT3
1
1
1
1
Note:1.TB02isterminalblockfortransmission.
Neverconnectpowerlinetoit.
2.
1
:SVM
isnotbuiltindependingonmodels.
7/25/2019 dieu hoa ADMIN.pdf
32/166
7/25/2019 dieu hoa ADMIN.pdf
33/166
32
9
CMB-P1016V-E
PE
EARTH
3 2 1 3 2 1
TB02
TB01
Name
S
ymbol
Terminalblock
(forTransmission)
Solenoidvalve
Solenoidvalve
Solenoidvalve
Solenoidvalve
Terminalblock
(forpowersource)
Pressuresensor
Expansionvalve
Thermistersensor
Transformer
Name
SV1~16A
SV1~16B
SV1~16C
SVM
Symbol
TRTH11~16
LEV1,3
PS1,3
M1
M2
DC30V
}Shieldwire
Transmissionline
Powersource
}L N
Powersource
~/N220V~240V50Hz
CN39
1
3
6
5
4
3
2
1
1
2
3
4
5
6
7
CN51
CN50
1
3
5
C
N12
1
3
CNOUT3
CNOUT1
1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
1 3 5 71 3 5 77531
1
5
7
1
5
7
1
3
5
7
1
3
2
1
CNVCC2
3
CN42
X46
X47
X48
1 2 387654321 4
CNOUT2
CNOUT4
CN41
CN40
X41
X44
X40
X43
X42
X45
X20
X18
X19
X17
X39
X38
3 CNVCC1
1
2
X16
X15
X37
X36
X13
X14
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
6
5
4
3
2
1
6
5
4
3
2
1
LEV3
LEV1
1 2 3
CNP1
1 2 3
CNP3
21 1 2 3 4 5 6 7 8 4321
1
2
3
2
1
CN03
CN02
CN13
CN10
CN11
CN07
CN05
3
3
CN34
CN33
1
3
5
7
CN32
TH11
TH12
TH15
TH16
TR
TB02
CN38
CN26
CN27
CN28
CN29
CN30
CN31
TB01
CN35
31
CNTR
41 2 3 4 5 6 7 8 321
SV1B
SV1A
SV1C
SV2C
SV2A
SV2B
SV3C
SV3A
SV3B
SV4C
SV4A
SV4B
SV5B
SV5A
SV5C
1 2 3 4 5 6 7 8 9 10
11
12
13
14
15
16
1 2 3 4 5 6 7 8 9 10
11
12
13
14
15
16
SV9C
SV9A
SV9B
SV10C
SV10A
SV10B
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
14
13
12
11
10
15
16
1
2
3
4
5
6
7
8
9
SV8B
SV8A
SV8C
SV7B
SV7A
SV7C
SVM
SV6C
SV6A
SV6B
SV11C
SV11A
SV11B
16
15
14
13
12
11
10987654321
98765432116
15
14
13
12
11
10
SV12C
SV12A
SV12B
SV13C
SV13A
SV13B
PS1
PS3
1
1
1
1
Note:1.TB02istransmissiont
erminalblock.
Neverconnectpowerlinetoit.
2.
1:SVM
isnotbuiltind
ependingonmodels.
1 2
21
1 3 5 71 3 5 71 3 5 7
X57
X53
X52
X56
X55
CN45
CN44
CN43
X50
SV14C
SV14A
SV14B
SV15A
SV15B
SV16C
SV16A
SV16B
SV15C
X54
X51
X49
RELAY10
Board
BC
Bo
ard
20
22V
220
240V
CN36
7/25/2019 dieu hoa ADMIN.pdf
34/166
33
[4] Standard Operation Data
(1) Cooling operation
1 PU(H)Y-200250YMF-C
Outdoor unit
ItemsPUHY-200YMF-C
PUY-200YMF-C
PUHY-250YMF-C
PUY-250YMF-C
Indoor
Outdoor
Quantity
Quantity in operation
Model
Main pipe
Branch pipe
Total piping length
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0
4 4
4 4
63 63 50 25 125 40 63 25
5 5
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.2 12.7
440 440 380 280 430 350 440 280
130 140
235 235
22.0/4.80 20.3/4.7(2.16/0.47) (1.99/0.46)
93 95
40 42
7 5
9 7
7 10
6 4
69 60
27 27
8 6
26 26
10 10
14.5 13.3 18.3 16.8
380 415 380 415
270/75 270/75 340/95 340/95
Indoor unit fan notch
Refrigerant volume
Total current
Volts/Frequency
Indoor unit
SC (LEV1)
Oil return (SLEV)
High pressure/Low pressure (after O/S)
(before MA)Pressure
DB/WB
Set
m
kg
A
V
V/Hz
Pulse
kg/cm2G(MPa)
C
Condition
Sectionaltemperature
Outdoorunit
LEV
opening
Discharge (TH1)
Heat exchanger outlet (TH5)
Accumulator
Suction (Comp)
TH2
Shell bottom (Comp)
SCC outlet (TH7)
Bypass outlet (TH8)
LEV inlet
Heat exchanger outlet
Inlet
Outlet
Outdoor
unit
Indoorunit
Ambient temp.
Indoor unit
Piping
7/25/2019 dieu hoa ADMIN.pdf
35/166
34
PU(H)Y-P200250YMF-C
Outdoor unit
ItemsPUHY-P200YMF-C
PUY-P200YMF-C
PUHY-P250YMF-C
PUY-P250YMF-C
Indoor
Outdoor
Quantity
Quantity in operation
Model
Main pipe
Branch pipe
Total piping length
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0
4 4
4 4
63 63 50 25 125 40 63 25
5 5
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.7 13.2
440 440 380 280 430 350 440 280
130 140
235 235
20.5/4.0 21.9/3.9
(2.01/0.39) (2.15/0.38)
96 96
40 42
7 7
10 10
12 15
1 1
11 11
80 85
27 27
8 6
26 26
10 10
0.23 0.23
14.5 13.3 18.3 16.8
380 415 380 415
270/75 270/75 340/95 340/95
Indoor unit fan notch
Refrigerant volume
Total current
Volts/Frequency
Indoor unit
SC (LEV1)
Oil return (SLEV)
High pressure/Low pressure (after O/S)
(before MA)Pressure
DB/WB
Set
m
kg
A
V
V/Hz
Pulse
kg/cm2G
(MPa)
C
Condition
Sectional
temperature
Outdoorunit
LEVopening
Inlet
Outlet
Outdoor
unit
Indoorunit
OC
Ambient temp.
Indoor unit
Piping
Discharge (TH1)
Heat exchanger outlet (TH5)
Accumulator
Suction (Comp)
CS circuit (TH2)
CS circuit (TH9)
Shell bottom (Comp)
SCC outlet (TH7)
Bypass outlet (TH8)
LEV inlet
Heat exchanger outlet
7/25/2019 dieu hoa ADMIN.pdf
36/166
35
380 415 380 415
270/75 270/75 340/95 340/95
14.5 13.3 18.3 16.8
PURY-200250YMF-C
Outdoor unit
ItemsPURY-P200YMF-C PURY-P250YMF-C
Indoor
Outdoor
Quantity
Quantity in operation
Model
Main pipe
Branch pipe
Total piping length
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0
4 4
4 4
63 63 50 25 125 40 63 25
5 5
5 5 5 5 5 5 5 5
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
13.9 14.4
330 460 430 300 410 330 460 300
2000 140 2000 150
235 235
20.7/5.0 19.4/4.0
(2.03/0.49) (1.90/0.39)
19.6/19.6 18.3/18.3(1.92/1.92) (1.79/1.79)
107 110
50 47
7 7
10 10
12 12
75 70
26 30
15 15
Indoor unit fan notch
Refrigerant volume
Compressor volts / Frequency
Outdoor unit
Indoor unit
BC controller (1, 3)
Oil return
High pressure/Low pressure
BC controller liquid/IntermediatePressur
e
DB/WB
Qty
m
kg
V
V/Hz
A
Pulse
kg/cm2G(MPa)
C
Condition
Sectionaltemperature
LEVopening
Discharge (TH1)
Heat exchanger outlet (TH5)
Accumulator
Suction (Comp)
Shell bottom (Comp)
LEV inlet
Heat exchanger outlet
Inlet
Outlet
Outdoor
unit
Indoorunit
Ambient temp.
Indoor unit
Piping
7/25/2019 dieu hoa ADMIN.pdf
37/166
36
PURY-P200250YMF-C
Outdoor unit
ItemsPURY-P200YMF-C PURY-P250YMF-C
Indoor
Outdoor
Quantity
Quantity in operation
Model
Main pipe
Branch pipe
Total piping length
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0
4 4
4 4
63 63 50 25 125 40 63 25
5 5
5 5 5 5 5 5 5 5
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
14.4 14.9
330 460 430 300 410 330 460 300
2000 140 2000 150
235 235
23.5/5.3 23.0/5.1
(2.30/0.52) (2.25/0.50)
22.4/22.4 21.9/21.9(2.20/2.20) (2.15/2.15)
97 105
50 47
7 7
10 10
12 12
7 5
75 70
26 30
15 15
0.23 0.23
380 415 380 415
270/75 270/75 340/95 340/95
14.5 13.3 18.3 16.8
Indoor unit fan notch
Refrigerant volume
Compressor volts / Frequency
Outdoor unit
Indoor unit
BC controller (1, 3)
Oil return
High pressure/Low pressure
BC controller liquid/IntermediatePressure
DB/WB
Qty
m
kg
V
V/Hz
A
Pulse
kg/cm2G(MPa)
C
Condition
Sectionaltemperature
LEVopening
Discharge (TH1)
Heat exchanger outlet (TH5)
Accumulator
Suction (Comp)
CS circuit (TH2)
Shell bottom (Comp)
LEV inlet
Heat exchanger outlet
Inlet
OutletOutdoor
unit
Indoor
unit
OC
Ambient temp.
Indoor unit
Piping
7/25/2019 dieu hoa ADMIN.pdf
38/166
37
2Heating operation
PUHY-200250YMF-C
Outdoor unit
ItemsPUHY-200YMF-C PUHY-250YMF-C
Indoor
Outdoor
Quantity
Quantity in operation
Model
Main pipe
Branch pipe
Total piping length
20.0/ 20.0/
7.0/6.0 7.0/6.0
4 4
4 4
63 63 50 25 125 40 63 25
5 5
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.2 12.7
510 510 450 280 440 420 510 280
0 0
150 235
17.5/3.7 17.5/3.7(1.72/0.36) (1.72/0.36)
80 85
6 8
1 2
1 2
1 2
2 2
50 60
71 71
33 33
13.4 12.3 17.1 15.6
380 415 380 415
280/83 280/83 355/102 355/102
Indoor unit fan notch
Refrigerant volume
Total current
Volts/Frequency
Indoor unit
SC (LEV1)
Oil return (SLEV)
High pressure/Low pressure (after O/S)(before MA)
Pressure
DB/WB
Set
m
kg
A
V
V/Hz
Pulse
kg/cm2G(MPa)
C
Condition
Se
ctionaltemperature
Outdoorunit
LEVopening
Discharge (TH1)
Heat exchanger outlet (TH5)
Accumulator
Suction (Comp)
TH2
Shell bottom (Comp)
Heat exchanger outlet
LEV inlet
Inlet
OutletOutdoor
unit
Indoor
unit
Ambient temp.
Indoor unit
Piping
7/25/2019 dieu hoa ADMIN.pdf
39/166
38
PUHY-P200250YMF-C
Outdoor unit
ItemsPUHY-P200YMF-C PUHY-P250YMF-C
Indoor
Outdoor
Quantity
Quantity in operation
Model
Main pipe
Branch pipe
Total piping length
20.0/ 20.0/
7.0/6.0 7.0/6.0
4 4
4 4
63 63 50 25 125 40 63 25
5 5
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.7 13.2
510 510 450 280 440 420 510 280
0 0
150 150
18.5/3.7 21.4/3.7
(1.81/0.36) (2.10/0.36)
75 78
1 1
2 2
2 2
3 3
3 3
0 0
60 70
80 80
39 39
0.28 0.28
13.4 12.3 17.1 15.6
380 415 380 415
270/75 270/75 340/95 340/95
Indoor unit fan notch
Refrigerant volume
Total current
Volts/Frequency
Indoor unit
SC (LEV1)
Oil return (SLEV)
High pressure/Low pressure (after O/S)
(before MA)Pressure
DB/WB
Set
m
kg
A
V
V/Hz
Pulse
kg/cm2G
(MPa)
C
Condition
Se
ctionaltemperature
Outdoorunit
LEVopening
Discharge (TH1)
Heat exchanger inlet (TH5)
Accumulator
Suction (Comp)
CS circuit (TH2)
CS circuit (TH9)
Shell bottom (Comp)
Heat exchanger outlet
LEV inlet
Inlet
OutletOutdoor
unit
Indoorunit
OC
Ambient temp.
Indoor unit
Piping
7/25/2019 dieu hoa ADMIN.pdf
40/166
39
PURY-200250YMF-C
Outdoor unit
ItemsPURY-200YMF-C PURY-250YMF-C
Indoor
Outdoor
Quantity
Quantity in operation
Model
Main pipe
Branch pipe
Total piping length
20.0/ 20.0/
7.0/6.0 7.0/6.0
4 4
4 4
63 63 50 25 125 40 63 25
5 5
5 5 5 5 5 5 5 5
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
13.9 14.4
600 950 750 400 750 600 950 400
60 700 60 800
150 235
18.5/3.6 18.0/3.7
(1.81/0.35) (1.76/0.36)
17.5/14.0 17.0/14.0(1.72/1.37) (1.67/1.37)
100 95
2 1
1 1
4 2
1 1
45 40
38 40
80 85
380 415 380 415
285/85 285/85 360/105 360/105
13.4 12.3 17.1 15.6
Indoor unit fan notch
Refrigerant volume
Compressor volts / Frequency
Outdoor unit total current
Indoor unit
BC controller (1, 3)
Oil return
High pressure/Low pressure
BC controller liquid/IntermediatePressur
e
DB/WB
Qty
m
kg
V
V/Hz
A
Pulse
kg/cm2G(MPa)
C
Condition
Sectionaltemperature
LEVopening
Discharge (TH1)
Heat exchanger outlet (TH5)
Accumulator
Suction (Comp)
Shell bottom (Comp)
LEV inlet
Heat exchanger outlet
Inlet
Outlet
Outdoor
unit
Indoorunit
Ambient temp.
Indoor unit
Piping
7/25/2019 dieu hoa ADMIN.pdf
41/166
40
PURY-P200250YMF-C
Outdoor unit
ItemsPURY-P200YMF-C PURY-P250YMF-C
Indoor
Outdoor
Quantity
Quantity in operation
Model
Main pipe
Branch pipe
Total piping length
20.0/ 20.0/
7.0/6.0 7.0/6.0
4 4
4 4
63 63 50 25 125 40 63 25
5 5
5 5 5 5 5 5 5 5
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
14.4 14.9
600 950 750 400 750 600 950 400
60 700 60 800
150 235
18.5/3.6 18.0/3.7
(1.96/0.38) (1.86/0.34)
17.5/14.0 17.0/14.0(1.86/1.57) (1.76/1.47)
100 95
2 1
1 1
4 2
1 1
7 5
45 40
38 40
80 85
0.28 0.28
380 415 380 415
280/80 280/80 340/95 340/95
13.4 12.3 17.1 15.6
Indoor unit fan notch
Refrigerant volume
Compressor volts/Frequency
Outdoor unit total current
Indoor unit
BC controller (1, 3)
Oil return
High pressure/Low pressure
BC controller liquid/IntermediatePressur
e
DB/WB
Qty
m
kg
V
V/Hz
A
Pulse
kg/cm2G(MPa)
C
Condition
Section
altemperature
LEVopening
Discharge (TH1)
Heat exchanger outlet (TH5)
Accumulator
Suction (Comp)
CS circuit
Shell bottom (Comp)
LEV inlet
Heat exchanger outlet
Inlet
Outlet
(TH2)
Outdoor
unit
Indoor
unit
OC
Ambient temp.
Indoor unit
Piping
7/25/2019 dieu hoa ADMIN.pdf
42/166
41
[5] Function of Dip SW and Rotary SW
(1) Outdoor unit
1PU(H)Y-200250YMF-C
Switch FunctionFunction according to switch operation Switch set timing
When off When on When off When on
SWUSW1
SW2
SW3
SW4
1~21~8
9~10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
Unit address settingFor self diagnosis/
operation monitoring
Centralized control switch
Deletion of connection
information.
Deletion of error history.
Disregard ambient air
sensor errors, liquid
overflow errors.Forced defrosting
Defrost prohibited timer
-
-
SW3-2 Function valid/
invalid
Indoor unit test operation
Defrosting start tempera-
ture of TH5.Defrosting end tempera-
ture of TH5.
Opening angle of IC except
when heater thermostat is
ON during defrosting.
Models
Target Pd (High pressure)
Models
Set on 51~100 with the dial switch.LED monitering display
Centralized control not
connected.
Storing of refrigeration
system connection
information.
Errors valid.
Ordinary control
43 min.
SW3-2 Function invalid
Stop all indoor units.
-2C
8C
(no operation)
PUHY-YMF-C
18kg/cm2G
(1.76MPa)
Model 200
Centralized control
connected.
Deletion of refrigeration
system connection
information.
Deletion
Disregard errors.
Start forced defrosting.
90 min.
SW3-2 Function valid
All indoor units test
operation ON.
0C
15C
2000
PUY-YMF-C
20kg/cm2G
(1.96MPa)
Model 250
Before power is turned on.During normal operation when power
is on.
Should be set on OFF.
Before power is turned on.
Before power is turned on.
During normal operation when power
is on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
During normal operation when power
is on.
When SW3-1 is ON after power is
turned on.
During normal operation when power
is on.During normal operation when power
is on. (Except during defrosting)
When switching on the power.
During normal operation when power
is on.
When switching on the power.
During normal
operation when
power is on.
10 minutes or
more after
compressor
starts.
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
7/25/2019 dieu hoa ADMIN.pdf
43/166
42
2PUHY-P200250YMF-C
Switch FunctionFunction according to switch operation Switch set timing
When off When on When off When onSWU
SW1
SW2
SW3
SW4
1~2
1~8
9~10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
Unit address setting
For self diagnosis/
operation monitoring
Centralized control switch
Deletion of connection
information.
Deletion of error history.
Disregard ambient air
sensor errors, liquid
overflow errors.
Forced defrosting
Defrost prohibited timer
SW3-2 Function valid/
invalid
Indoor unit test operation
Defrosting start tempera-
ture of TH5.
Defrosting end tempera-
ture of TH5.
Opening angle of IC except
when heater thermostat isON during defrosting.
Models
Target Tc (High pressure)
at Heating
Models
SW4-2 Function valid/
invalid
Configuration compensa-
tion value
Set on 51~100 with the dial switch.
LED Monitering Display
Centralized control not
connected.
Storing of refrigeration
system connection
information.
Errors valid.
Ordinary control
39 min.
SW3-2 Function invalid
Stop all indoor units.
4C
8C
(no operation)
PUHY-P-YMF-C
49C
Model P200
Invalid
Centralized control
connected.
Deletion of refrigeration
system connection
information.
Deletion
Disregard errors.
Start forced defrosting.
90 min.
SW3-2 Function valid
All indoor units test
operation ON.
1C
15C
2000
PUY-P-YMF-C
53C
Model P250
Valid
Before power is turned on.
During normal operation when power
is on.
Should be set on OFF.
Before power is turned on.
Before power is turned on.
During normal operation when power
is on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
During normal operation when power
is on.
When SW3-1 is ON after power is
turned on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
When switching on the power.
During normal operation when power
is on.
When switching on the power.
During normal operation when power
is on.
when SW4-1 in ON.
During normal
operation when
power is on.
10 minutes or
more after
compressor
starts.
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
Changes as shown below by on off change
0% 3% 6% 9% 12% 6% 3% 0%
7/25/2019 dieu hoa ADMIN.pdf
44/166
43
3PURY-200250YMF-C
Switch FunctionFunction according to switch operation Switch set timing
When off When on When off When on
SWU
SW1
SW2
SW3
SW4
1~2
1~8
9~10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
Unit address setting
For self diagnosis/
operation monitoring
Centralized control switch
Deletion of connection
information.
Deletion of error history.
Disregard ambient air
sensor errors, liquid
overflow errors.
Forced defrosting
Defrost prohibited timer
SW3-2 Function valid/
invalid
Indoor unit test operation
Defrosting start tempera-
ture of TH7.
Defrosting end tempera-
ture of TH5.
Pump down operation
Target Td (High pressure)
at Heating
Models
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not
connected.
Storing of refrigeration
system connection
information.
Errors valid.
Ordinary control
43 min.
SW3-2 Function invalid
Stop all indoor units.
6C
8C
Invalid
49C
Model 200
Centralized control
connected.
Deletion of refrigeration
system connection
information.
Deletion
Disregard errors.
Start forced defrosting.
90 min.
SW3-2 Function valid
All indoor units test
operation ON.
3C
15C
Valid
53C
Model 250
Before power is turned on.
During normal operation when power
is on.
Should be set on OFF.
Before power is turned on.
Before power is turned on.
During normal operation when power
is on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
During normal operation when power
is on.
When SW3-1 is ON after power is
turned on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
During compressor stop when poweris on.
During normal operation when power
is on.
When switching on the power.
During normal
operation when
power is on.
10 minutes or
more after
compressor
starts.
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
7/25/2019 dieu hoa ADMIN.pdf
45/166
44
4PURY-P200250YMF-C
Switch FunctionFunction according to switch operation Switch set timing
When off When on When off When onSWU
SW1
SW2
SW3
SW4
1~2
1~8
9~10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
Unit address setting
For self diagnosis/
operation monitoring
Centralized control switch
Deletion of connection
information.
Deletion of error history.
Disregard ambient air
sensor errors, liquid
overflow errors.
Forced defrosting
Defrost prohibited timer
SW3-2 Function valid/
invalid
Indoor Unit Test operation
Defrosting start tempera-
ture of TH7.
Defrosting end tempera-
ture of TH5.
Pomp down operation
Target Tc (High pressure)
at Heating
Models
SW4-2 function valid/
Invalid
Configuration compensa-
tion value
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not
connected.
Storing of refrigeration
system connection
information.
Errors valid.
Ordinary control
43 min.
SW3-2 Function invalid
Stop all indoor units.
8C
8C
Invalid
49C
Model P200
Invalid
Centralized control
connected.
Deletion of refrigeration
system connection
information.
Deletion
Disregard errors.
Start forced defrosting.
90 min.
SW3-2 Function valid
All indoor units test
operation ON.
5C
15C
Valid
53C
Model P250
Valid
Before power is turned on.
During normal operation when power
is on.
Should be set on OFF.
Before power is turned on.
Before power is turned on.
During normal operation when power
is on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
During normal operation when power
is on.
When SW3-1 is ON after power is
turned on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
During compressor stop when poweris on.
During normal operation when power
is on.
When switching on the power.
During normal operation when power
is on.
when SW4-1 in ON.
During normal
operation when
power is on.
10 minutes or
more after
compressor
starts.
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
Changes as shown below by on off change
0% 3% 6% 9% 12% 6% 3% 0%
7/25/2019 dieu hoa ADMIN.pdf
46/166
45
(2) Indoor unit
DIP SW1, 3
Model P71 P80 P100 P125 P140 P200 P250
Capacity (model name) code 14 16 20 25 28 40 50
SW2 setting
Model P20 P25 P32 P40 P50 P63
Capacity (model name) code 4 5 6 8 10 13
SW2 setting ONOFFON
OFFON
OFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the
table below.)
Note 2: The DipSW setting is only effective during unit stopping (remote controller OFF) for SW1, 2, 3 and 4 commonly
and the power source is not required to reset.)
3: When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.
Setting of DIP SW2
Model
Switch
SW1
SW3
3
6
7
3
4
6
8
PLFY-P
VBM-A
OFF
OFF
VLMD-A VKM-A
OFF
ON
ON
ON
OFF
OFF
ON
ON
PEFY-P
VML-A VMH-A 20~80VMM-A 100~140VMM-A
OFFOFF ON
OFF ON
ON
ON
OFF
OFF
OFF
OFF ON OFF
ON OFF ON
ON
OFF
PDFY-P PFFY-P PCFY-P PKFY-P
VM-A
ON
VLRM-A, VLEM-A
OFF
VGM-A
ON
VAM-A VGM-A
OFF
OFF
Indoor unit inlet
None
100h
Ineffective
Fan output display
At stationary heating
Very low speed
SW1-7 setting
Ineffective
Ineffective
Heat pump
None
None
None
1st setting
Down blow B, C
Effective
Built in remote controller
Provided
2500h
Effective
Thermo. ON signal display
Always at heat.
Low speed
Set airflow
Effective
Effective
Cool.only
Provided
Provided
Provided
2nd setting
Horizontal
Ineffective
Room temp. sensor position
Clogged filter detect.
Filter duration
OA intake
Remote display select.
Humidifier control
Heating thermo. OFF airflow
Heating thermo. OFF airflow
Power failure automatic
return
Power source start/stop
Model selection
Louver
Vane
Vane swing function
Vane horizontal angle
Vane angle set for cooling
Heating 4deg up
Always ineffective for PKFY-P.VAM
Not provided for PKFY-P.VAMProvided for PLFY-P.VGM (ON) setting
Always down blow B,C for PKFY-P.VAM
Horizontal (ON) setting for PLFY-P.VLMD
Ineffective (ON) setting for floorstanding
SW1
SW3
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
Switch SW nameOperation by SW Switch set timing
OFF ON OFF ONRemarks
At unit stopping(at remote
controller OFF)
Cooling capacity saving
for PKFY-P. VAM,effective/ineffective
7/25/2019 dieu hoa ADMIN.pdf
47/166
46
Ceiling height
3 3.5 m
2 2.8 m
1 2.3 m
Setting of DIP SW4 Setting of DIP SW5
1 2 3 4
ON OFF ON OFF
ON OFF ON OFF
OFF OFF OFF ONON OFF OFF ON
OFF ON OFF ON
OFF OFF ON ON
ON ON OFF OFF
OFF OFF OFF
ON ON ON
OFF OFF OFF
ON OFF OFF
OFF OFF ON
ON ON ON OFF
PMFY-P-VBM-A
PLFY-P-VLMD-A
PDFY-P20 ~ 80VM-A
PLFY-P40 ~ 63VKM-APLFY-P80 ~ 125VKM-A
PCFY-P-VGM-A
PKFY-P-VGM-A
PKFY-P-VAM-A
PEFY-P20 ~ 80VMM-A
PFFY-P-VLEM-A, P-VLRM-A
PEFY-P20 ~ 32VML-A
PEFY-P40 ~ 140VMH-A
PEHY-P200250VMH-A
PDFY-P100125VM-A
PEFY-P100 ~ 140VMM-A
Model Circuit board usedSW4
Switch Function Operation by switch Switch set timing
SWA
SWA
SWA
SWB
SWC
Ceiling height setting
External static
pressure setting
For options
Setting of air outlet opening
Airflow control
(PLFY-P-VKM-A) (PCFY-P-VGM-A)
(PLFY-P-VLMD-A)
(PLFY-P-VKM-A)
(PLFY-P-VKM-A, PCFY-P-VGM-A, PKFY-P-VGM-A, PDFY-P-VM-A)
Phase control
Relay selection
*The ceilingheight ischanged bySWB setting.
*As this switch is used by interlocking with SWC,refer to the item of SWC for detail.
SWASWB 1 2 3
2-way 3.5 m 3.8 m 3.8 m
3-way 3.0 m 3.3 m 3.5 m
4-way 2.7 m 3.0 m 3.5 m
* Set to the option to install the high efficiencyfilter
Always after powering
Always after powering
Always after powering
Always after powering
Always after powering
3
1
2
2-way
4-way
3-way
3
1
2
3
1
2
3
1
2
220V
240V
Option
Standard
(PDFY-P20 ~ 80VM-A, PEFY-P20 ~ 80VMM-A)
100Pa
50Pa
30Pa* For other models, change the setting of static pressure by replacing the connector.
7/25/2019 dieu hoa ADMIN.pdf
48/166
47
33333 TEST RUN
[1] Before Test Run(1) Check points before test run
1 Neither refrigerant leak nor loose power source/ transmission lines should be found.
2 Confirm that the resistance between the power source terminal block and the ground exceeds 2Mby measur-
ing it with a DC500V megger. Do not run if it is lower than 2M.
Note) Never apply the megger to the MAIN board. If applied, the MAIN board will be broken.
3 Confirm that the Ball valve at both gas and liquid sides is being fully opened.
Note) Certainly close the cap.
4 Be sure that the crankcase heater has been powered by turning the main power source on at least 12 hours
before starting the test run. The shorter powering time causes compressor trouble.
(2) Caution at inverter check
Because the inverter power portion in outdoor unit electrical part box have a lot of high voltage portion, be sure to follow
the instructions shown below.
During energizing power source, never touch inverter power portion because high voltage (approx. 580V) is
applied to inverter power portion.
When checking,
Shut off main power source, and check it with tester, etc.
Allow 10 minutes after shutting off main power source.
Open the MAIN board mounting panel, and check whether voltage of both ends of electrolytic capacitor is
20V or less.
1
2
1
2
3
7/25/2019 dieu hoa ADMIN.pdf
49/166
48
(3) Check points for test run when mounting options
(4) Attention for mounting drain water lifting-up mechanism
Check point
Local remote controller displays codeNo. 2503, and the mechanism stops.
No overflow from drain pan.
Drain water comes out by operations ofdrain pump.
Sound of pump operations is heard, anddrain water comes out.
No water leak from connecting portionsof each water piping.
Water is supplied to water supply tank,and float switch is operating.
Built-in optional parts
Mounting of drainwater lifting-upmechanism
Mounting of perme-able film humidifier
Content of test run
Release connector of pump circuit,check error detection by pouringwater into drain pan water inlet.
After that, connect connector ofcircuit.
Check pump operations and drain-age status in cooling (test run) mode.
Check humidifier operations and watersupply status in heating (test run) mode.
1
2
3
4
5
Result
1
2
3
Work
Disassembling andassembling of drainwater lifting-upmechanism
Mounting of floatswitch
Electric wiring
Float switch moves smoothly.
Float switch is mounted onmounting board straightly withoutdeformation.
Float switch does not contact withcopper pipe.
Wiring procedure is exactly followed.
Connector portion is tightly hooked.
Content of test run
Lead wire from control box notdamaged.
Rubber cap properly inserted todrain water outlet of drain pan?
Insulation pipe of gas and liquidpipes dealt with as shown in the rightfigure?
Drain pan and piping cover mountedwithout gap?
Drain pan hooked on cut projectionof the mechanism?
Float switch installed without contactingwith drain pan?
No mistakes in wiring?
Connectors connected surely andtightly?
No tension on lead wire when slidingcontrol box?
1
2
3
1
2
3
Check point Result
Insulation pipe
No gap
7/25/2019 dieu hoa ADMIN.pdf
50/166
7/25/2019 dieu hoa ADMIN.pdf
51/166
50
Classification
Transmissionline
Portion Check item
1 Limitation of transmission line length followed? Forexample, 200m or less (total length : 500m) at the farthest.
2 1.25mm2or more transmission line used?(Remote controller 10m or less 0.75mm2)
3 2-core cable used for transmission line?
4 Transmission line apart from power source line by 5cm or more?
5 One refrigerant system per transmission line?
6 The short circuit connector is changed form CN41 toCN40 on the MAIN board when the system is centralized
control? (Just one outdoor unit. Not all outdoor units.)
7 No connection trouble in transmission line?
8 Connection of wrong remote controller line terminals? MA Remote controller : TB15 M-NET Remote controller : TB5
Trouble
Erroneous operation, error stop.
Erroneous operation, error stop.
Error stop in case multiple-core
cable is used.
Erroneous operation, error stop.
Not operate.
Not operate.
Error stop or not operate.
Never finish the initial mode.
System set
Before starting
Error stop or not operate.
Can not be properly set with power
source turned on.
Not operate.
Set temperature not obtained atheating operations (Thermostat
stop is difficult)
Error stop.
Error stop, compressor trouble.
1
2
1
2
3
4
Address setting properly done? (M-NET Remotecontroller, indoor unit and outdoor unit.)
Setting of address No. done when shutting off power
source?
Address numbers not duplicated?
Turned on SW3-8 on indoor unit circuit board whenmounting room thermistor sensor?
Refrigerant piping ball valve (Liquid pressure pipe, gaspressure pipe) opened?
Turn on power source 12 hours before starting operations?
STANDBYDEFROST ERRORCODE
D A I L YAUTOOFF
CENTRALLYCONTROLLED
CLOCKREMAINDER
O NO F FC
1Hr.
NOT AVAILABLEC
CHECKMODE
FILTERCHECK
TESTRUN
LIMITTEMP.
ON/OFFTEMP
FILTER
CHECKTEST
O N O FFCLOCK
PAR-F27MEATIMERSET
2 31
STANDBYDEFROST ERRORCODE
D A I L YAUTOOFF
CENTRALLYCONTROLLED
CLOCK
REMAINDER
O NO F F C
1Hr.
NOT AVAILABLEC
CHECKMODE
FILTERCHECK
TESTRUN
LIMITTEMP.
ON/OFFTEMP
FILTER
CHECKTEST
O N O FFCLOCK
PAR-F27MEATIMERSET
7/25/2019 dieu hoa ADMIN.pdf
52/166
51
[2] Test Run Method
Operation procedure
1Turn on universal power supply at least 12 hours before getting started Displaying HOon display panel for
about two minutes
2 Press TEST RUN button twiceDisplaying TEST RUNon display panel
3 Press selection buttonMake sure that air is blowing out
4Press select button to change from cooling to heating operation, and vice versaMake sure that
warm or cold air is blowing out
5 Press adjust buttonMake sure that air blow is changed
6 Press or button to change windMake sure that horizontal or downward blow is adjustable.
7 Make sure that indoor unit fans operate normally
8 Make sure that interlocking devices such as ventilator operate normally if any
9 Press ON/OFF button to cancel test run Stop operation
Note 1: If check code is displayed on remote controller or remote controller does not operate normally.
2: Test run automatically stops operating after two hours by activation of timer set to two hours.
3: During test run, test run remaining time is displayed on time display section.
4: During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temperature
display section.5: When pressing adjust button, depending on the model, NOT AVAILABLEmay be displayed on remote
controller. However, it is not a malfunction.
6: When pressing or button, depending on the model, NOT AVAILABLEmay be displayed on
remote controller. However, it is not a malfunction.
7/25/2019 dieu hoa ADMIN.pdf
53/166
52
4 GROUPING REGISTRATION OF INDOOR UNITS WITH M-NET REMOTE CONTROLLER
(1) Switch function
The switch operation to register with the remote controller is shown below:
Registration/ordinary modeselector switch
Registration/ordinarymode selection switch
Switch to assign indoorunit address
Registration switch
Confirmation switch
Delete switch
Registered modeselector switch
Switch to assigninterlocked unit address
A+B
C
D
E
F
G
H
This switch selects the ordinary mode or registered mode (ordinary
mode represents that to operate indoor units).
* To select the registered mode, press the FILTER +
switch continuously for over 2 seconds under stopping state.
[Note] The registered mode can not be obtained for a while after
powering.
Pressing the FILTER + switch displays CENTRALLY
CONTROLLED.
This switch assigns the unit address for INDOOR UNIT ADDRESS
NO.
This switch is used for group/interlocked registration.
This switch is used to retr ieve/identify the content of group and inter-
locked (connection information) registered.
This switch is used to retr ieve/identify the content of group and inter-
locked (connection information) registered.
This switch selects the case to register indoor units as group (group
setting mode) or that as interlocked (interlocked setting mode).
*The unit address is shown at one spot for the group setting modewhile at two spots for the interlocked setting mode.
This switch assigns the unit address of OA UNIT ADDRESS NO.
Symbolof switch
G Registered mode
selector switch
E Confirmation switch
C Switch to assign
indoor unit address
H Switch to assign inter-
locked unit address
D Registration switch
A
+FILTER
TEST RUN
Name Name of actual switch Description
of TEMP
of TIMER SET
CLOCKON OFF
B
Registration/ordinary modeselector switch
STAND BYDEFROST ERROR CODE
D A I L YAUTO OFF
CENTRALLY CONTROLLED
CLOCK
REMAINDER
ON OFF C
1Hr
NOT AVAILABLEC
CHECK MODE
FILTERCHECK
TEST RUN
LIMIT TEMP.
ON/OFFTEMP
FILTER
CHECK TEST
ON OFFCLOCK
PAR-F27MEATIMER SET
F Delete switch
7/25/2019 dieu hoa ADMIN.pdf
54/166
53
(2) Attribute display of unit
At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the
unit is displayed with two English characters.
Display Type (Attribute) of unit/controller
Indoor unit connectable to remote controller
Outdoor unit
Local remote controller
System controller (MJ)
[Description of registration/deletion/retrieval]
The items of operation to be performed by the remote controller are given below. Please see the relating paragraph for
detail.
1Group registration of indoor unit
The group of the indoor units and operating remote controller is registered.
It is usually used for the group operation of indoor units with different refrigerant system.
2Retrieval/identification of group registration information of indoor units
The address of the registered indoor units in group is retrieved (identified).
3Retrieval/identification of registration information
The connection information of any unit (indoor/outdoor units, remote controller or the like) is retrieved (identified).
4Deletion of group registration information of indoor units
The registration of the indoor units under group registration is released (deleted).
5Deletion of the address not existing
This operation is to be conducted when 6607error (No ACK error) is displayed on the remote controller caused by
the miss setting at test run, or due to the old memory remained at the alteration/modification of the group composi-
tion.
Caution:
When MELANS (MJ-103MTRA for example) is being connected, do not conduct the group/pair registration using
the remote controller. The group/pair registration should be conducted by MELANS. (For detail, refer to the instruc-
tion exclusively prepared for MELANS.)
7/25/2019 dieu hoa ADMIN.pdf
55/166
54
(3) Group registration of indoor unit
1) Registration method
Group registration of indoor unit ........................................................................ 1
The indoor unit to be controlled by a remote controller is registered on the remote controller.
[Registration procedure]
1 With the remote controller under stopping or at the display of HO, continuously press the FILTER + switch
(A+B) at the same time for 2 seconds to change to the registration mode. (See the figure below.)
2 Assign the indoor unit address to INDOOR UNIT ADDRESS NO.by operating the (Room temperature
adjustment) (C).
Then press the TEST RUN switch (D) to register. In the figure below, the INDOOR UNIT ADDRESS NO.is being set
to 001.
3 After completing the registration, press the FILTER + switch (A+ B) at the same time for 2 seconds to
change to the original ordinary mode (with the remote controller under stopping).
Remote controller under stopping HOunder displaying
Ordinary mode
INDOOR UNITADDRESS NO
ERROR CODEOAUNITADDRESSNO
CINDOOR UNITADDRESS NO
ERROR CODEOAUNITADDRESSNO
C
ERROR CODEOAUNITADDRESSNO
C
1 1
Group setting mode
Confirm the indoor unit address No.
Confirm the connection of the transmission line.
ERROR CODEOAUNITADDRESSNO
C
ERROR CODEOAUNITADDRESSNO
C
Registration complete
Registration error
Indicates the type of unit(Indoor unit in this case)
88flickers indicating registra-tion error. (when the indoor unitregistered is not existing)
2 Assign theaddress (C)
1 Change to theregistrationmode (A+B)
3 Press theregistrationswitch (D)
Remote controller
System example
Indoor units
Group
2+3
ON/OFFTEMP
FILTER
CHECK TEST
O N O F FCLOCK
PAR-F27MEATIMER SET
7/25/2019 dieu hoa ADMIN.pdf
56/166
55
2) Method of retrieval/confirmation
Retrieval/confirmation of group registration information on indoor unit ............... 2
The address of the indoor unit being registered on the remote controller is displayed.
[Operation procedure]
1With the remote controller under stopping or at the display of HO, continuously press the FILTER + switch (A
+B) at the same time for 2 seconds to change to the registration mode.
2 In order to confirm the indoor unit address already registered, press switch (E). (See figure below.) When the group
of plural sets is registered, the addresses will be displayed in order at each pressing of switch (E).
3 After completing the registration, continuously press the FILTER + switch (A+ B) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
Retrieval/confirmation of registration information ................................................3
The registered information on a certain unit (indoor unit, outdoor unit, remote controller or the like) is displayed.
[Operation procedure]
1With the remote controller under stopping or at the display of HO, continuously press the FILTER + switch (A
+B) at the same time for 2 seconds to change to the registration mode.
2 Operate switch (G) for the interlocked setting mode. (See figure below.)
3 Assign the unit address of which registration information is desired to confirm with the (TIMER SET) switch
(H). Then press the switch (E) to display it on the remote controller. (See figure below.)
Each pressing of switch (E) changes the display of registered content. (See figure below.)
4 After completing the retrieval/confirmation, continuously press the FILTER + switch (A+B) at the same timefor 2 seconds to change to the original ordinary mode (with the remote controller under stopping).
Registered
No registration.
ERROR CODEOAUNITADDRESSNO
C
ERROR CODEOAUNITADDRESSNO
C
1 Press the switch for confirmation (E)
Note: Only one address will be displayedwhen the registration is one even theswitch is how often pressed
Indicates the type of unit(Indoor unit in this case)1
1ON/OFFTEMP
FILTER
CHECK TEST
O N O F FCLOCK
PAR-F27MEATIMER SET
7/25/2019 dieu hoa ADMIN.pdf
57/166
56
3) Method of deletion
Deletion of group registration information of indoor unit ......................................4
[Operation procedure]
1With the remote controller under stopping or at the disp