    AIR CONDITIONERS CITY MULTI

    Models PUHY-200YMF-C, 250YMF-CPUHY-P200YMF-C, P250YMF-CPUY-200YMF-C, 250YMF-CPUY-P200YMF-C, P250YMF-C

    PURY-200YMF-C, 250YMF-CPURY-P200YMF-C, P250YMF-C

    CMB-P104, P105, P106, P108, P1010, P1013, P1016V-E

    Service Handbook

  • 7/25/2019 dieu hoa ADMIN.pdf

    2/166

    1

    Contents1 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT .... 3

    [1] Storage of Piping Material ................................................................. 4

    [2] Piping Machining............................................................................... 5

    [3] Necessary Apparatus and Materials and Notes on Their Handling .. 6

    [4] Brazing .............................................................................................. 7

    [5] Airtightness Test ................................................................................ 8

    [6] Vacuuming ........................................................................................ 8

    [7] Charging of Refrigerant..................................................................... 9

    [8] Dryer ................................................................................................. 9

    2 COMPONENT OF EQUIPMENT ........................................................... 10[1] Appearance of Components ........................................................... 10

    [2] Refrigerant Circuit Diagram and Thermal Sensor ........................... 18

    [3] Electrical Wiring Diagram ................................................................ 24

    [4] Standard Operation Data ................................................................ 33

    [5] Function of Dip SW and Rotary SW................................................ 41

    3 TEST RUN ............................................................................................. 47[1] Before Test Run .............................................................................. 47

    [2] Test Run Method ............................................................................. 51

    4 GROUPING REGISTRATION OF INDOOR UNITS WITH REMOTE

    CONTROLLER....................................................................................... 52

    5 CONTROL.............................................................................................. 58[1] Control of Outdoor Unit ................................................................... 58

    [2] Control of BC Controller .................................................................. 63

    [3] Operation Flow Chart ...................................................................... 64

    [4] List of Major Component Functions ................................................ 70[5] Resistance of Temperature Sensor................................................. 73

    6 REFRIGERANT AMOUNT ADJUSTMENT ............................................ 74[1] Refrigerant Amount and Operating Characteristics ........................ 74

    [2] Adjustment and Judgement of Refrigerant Amount ........................ 74

    7 TROUBLESHOOTING ........................................................................... 84[1] Principal Parts ................................................................................. 84

    [2] BC Controller Disassembly Procedure ..........................................113

    [3] Self-diagnosis and Countermeasures Depending on the Check

    Code Displayed .............................................................................. 119

    [4] LED Monitor Display ..................................................................... 142

    8 PREPARATION, REPAIRS AND REFRIGERANT REFILLING WHEN

    REPAIRING LEAKS ............................................................................. 161[1] Location of leaks: Extension piping or indoor units (when cooling)161

    [4] Location of leaks: Outdoor unit (when heating) ............................ 163

    9 CHECK THE COMPOSITION OF THE REFRIGERANT

    (PURY-P200250YMF-C only) ................................................................ 164

  • 7/25/2019 dieu hoa ADMIN.pdf

    3/166

    2

    Safety precautions

    Before installation and electric work

    Before installing the unit, make sure you read all

    the Safety precautions.

    The Safety precautions provide very importantpoints regarding safety. Make sure you follow

    them.

    This equipment may not be applicable to

    EN61000-3-2: 1995 and EN61000-3-3: 1995.

    This equipment may have an adverse effect on

    equipment on the same electrical supply system.

    Please report to or take consent by the supply

    authority before connection to the system.

    Symbols used in the text

    Warning:Describes precautions that should be observed toprevent danger of injury or death to the user.

    Caution:

    Describes precautions that should be observed to

    prevent damage to the unit.

    Symbols used in the illustrations

    : Indicates an action that must be avoided.

    : Indicates that important instructions must be followed.

    : Indicates a part which must be grounded.

    : Beware of electric shock (This symbol is displayed on the

    main unit label.)

    Warning:

    Carefully read the labels affixed to the main unit.

    Warning:

    Use the specified cables for wiring. Make the connections

    securely so that the outside force of the cable is not

    applied to the terminals.

    - Inadequate connection and fastening may generate heat and

    cause a fire.

    Have all electric work done by a licensed electrician

    according to Electric Facility Engineering Standard and

    Interior Wire Regulationsand the instructions given in

    this manual and always use a special circuit.

    - If the power source capacity is inadequate or electric work is

    performed improperly, electric shock and fire may result.

    Securely install the cover of control box and the panel.

    - If the cover and panel are not installed properly, dust or water

    may enter the outdoor unit and fire or electric shock may

    result.

    After completing service work, make sure that refrigerant

    gas is not leaking.

    - If the refrigerant gas leaks and is exposed to a fan heater,

    stove, oven, or other heat source, it may generate noxious

    gases.

    Do not reconstruct or change the settings of the protectiondevices.

    - If the pressure switch, thermal switch, or other protection

    device is shorted and operated forcibly, or parts other than

    those specified by Mitsubishi Electric are used, fire or

    explosion may result.

  • 7/25/2019 dieu hoa ADMIN.pdf

    4/166

    3

    11111 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT

    Caution

    Do not use the existing refrigerant piping.

    The old refrigerant and refrigerator oil in the existing

    piping contains a large amount of chlorine which may

    cause the refrigerator oil of the new unit to deterio-

    rate.

    Use refrigerant piping made of phosphorus deoxi-

    dized copper and copper alloy seamless pipes and

    tubes. In addition, be sure that the inner and outer

    surfaces of the pipes are clean and free of hazardous

    sulphur, oxides, dust/dirt, shaving particles, oils,

    moisture, or any other contaminant.

    Contaminants on the inside of the refrigerant piping

    may cause the refrigerant residual oil to deteriorate.

    Store the piping to be used during installation indoors

    and keep both ends of the piping sealed until just

    before brazing. (Store elbows and other joints in a

    plastic bag.)

    If dust, dirt, or water enters the refrigerant cycle,

    deterioration of the oil and compressor trouble may

    result.

    Use ester oil, ether oil or alkylbenzene (small

    amount) as the refrigerator oil to coat flares and

    flange connections.

    The refrigerator oil will degrade if it is mixed with a

    large amount of mineral oil.

    Use liquid refrigerant to seal the system.

    If gas refrigerant is used to seal the system, the com-position of the refrigerant in the cylinder will change

    and performance may drop.

    Do not use a refrigerant other than R407C.

    If another refrigerant (R22, etc.) is used, the chlorine

    in the refrigerant may cause the refrigerator oil to de-

    teriorate.

    Use a vacuum pump with a reverse flow check valve.

    The vacuum pump oil may flow back into the refriger-ant cycle and cause the refrigerator oil to deteriorate.

    Do not use the following tools that have been used

    with conventional refrigerants.

    (Gauge manifold, charge hose, gas leak detector, re-

    verse flow check valve, refrigerant charge base,

    vacuum gauge, refrigerant recovery equipment)

    If the conventional refrigerant and refrigerator oil are

    mixed in the R407C, the refrigerant may deterio-

    rated.

    If water is mixed in the R407C, the refrigerator oil

    may deteriorate.

    Since R407C does not contain any chlorine, gas

    leak detectors for conventional refrigerants will not

    react to it.

    Do not use a charging cylinder.

    Using a charging cylinder may cause the refrigerant

    to deteriorate.

    Be especially careful when managing the tools.

    If dust, dirt, or water gets in the refrigerant cycle, the

    refrigerant may deteriorate.

    If the refrigerant leaks, recover the refrigerant in the

    refrigerant cycle, then recharge the cycle with the

    specified amount of the liquid refrigerant indicated

    on the air conditioner.

    Since R407C is a nonazeotropic refrigerant, if addi-

    tionally charged when the refrigerant leaked, the com-position of the refrigerant in the refrigerant cycle will

    change and result in a drop in performance or abnor-

    mal stopping.

  • 7/25/2019 dieu hoa ADMIN.pdf

    5/166

    4

    [1] Storage of Piping Material

    (1) Storage location

    Store the pipes to be used indoors. (Warehouse at site or owners warehouse)

    Storing them outdoors may cause dirt, waste, or water to infiltrate.

    (2) Pipe sealing before storage

    Both ends of the pipes should be sealed until immediately before brazing.Wrap elbows and Ts in plastic bags for storage.

    * The new refrigerator oil is 10 times more hygroscopic than the conventional refrigerator oil (such as Suniso). Water

    infiltration in the refrigerant circuit may deteriorate the oil or cause a compressor failure. Piping materials must be

    stored with more care than with the conventional refrigerant pipes.

  • 7/25/2019 dieu hoa ADMIN.pdf

    6/166

    5

    [2] Piping Machining

    Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.

    Use only the necessary minimum quantity of oil !

    Reason :

    1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.

    Notes :

    Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.

    Do not use oils other than ester oil, ether oil or alkylbenzene.

  • 7/25/2019 dieu hoa ADMIN.pdf

    7/166

    6

    [3] Necessary Apparatus and Materials and Notes on Their Handling

    The following tools should be marked as dedicated tools for R407C.

    Apparatus Used Use R22 R407C

    Gauge manifold Evacuating, refrigerant filling Current product

    Charging hose Operation check Current product

    Charging cylinder Refrigerant charging Current product Do not use.

    Gas leakage detector Gas leakage check Current product Shared with R134a

    Refrigerant collector Refrigerant collection R22 For R407C use only

    Refrigerant cylinder Refrigerant filling R22

    Vacuum pump Vacuum drying Current product

    Vacuum pump with a check valve Current product

    Flare tool Flaring of pipes Current product

    Bender Bending of pipes Current product

    Application oil Applied to flared parts Current product

    Torque wrench Tightening of flare nuts Current product

    Pipe cutter Cutting of pipes Current product

    Welder and nitrogen cylinder Welding of pipes Current product

    Refrigerant charging meter Refrigerant charging Current productVacuum gauge Checking the vacuum degree Current product

    Symbols : To be used for R407C only. Can also be used for conventional refrigerants.

    Tools for R407C must be handled with more care than those for conventional refrigerants. They must not come into contact

    with any water or dirt.

    Identification of dedi-

    cated use for R407C

    : Record refrigerant

    name and put brown

    belt on upper part of

    cylinder.

    Can be used byattaching an adapter

    with a check valve.

    Ester oil or Ether oil or

    Alkybenzene (Small

    amount)

  • 7/25/2019 dieu hoa ADMIN.pdf

    8/166

    7

    [4] Brazing

    No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt,

    etc.) does not enter the refrigerant circuit.

    Example : Inner state of brazed section

    When non-oxide brazing was not used When non-oxide brazing was used

    Items to be strictly observed :

    1. Do not conduct refrigerant piping work outdoors on a rainy day.

    2. Apply non-oxide brazing.3. Use a brazing material (Bcup-3) which requires no flux when brazing between copper pipes or between a copper pipe

    and copper coupling.

    4. If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends of them.

    Reasons :

    1. The new refrigerant oil is 10 times more hygroscopic than the conventional oil. The probability of a machine failure if

    water infiltrates is higher than with conventional refrigerant oil.

    2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.

    Note :

    Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When

    applying non-oxide brazing, use nitrogen.

  • 7/25/2019 dieu hoa ADMIN.pdf

    9/166

    8

    [5] Airtightness Test

    No changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407C

    leakage.

    Halide torch R22 leakage detector

    Items to be strictly observed :

    1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipments airtightness, taking

    temperature variations into account.

    2. When investigating leakage locations using a refrigerant, be sure to use R407C.

    3. Ensure that R407C is in a liquid state when charging.

    Reasons :

    1. Use of oxygen as the pressurized gas may cause an explosion.

    2. Charging with R407C gas will lead the composition of the remaining refrigerant in the cylinder to change and this

    refrigerant can then not be used.

    Note :

    A leakage detector for R407C is sold commercially and it should be purchased.

    [6] Vacuuming

    1. Vacuum pump with check valve

    A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant

    circuit when the vacuum pump power is turned off (power failure).

    It is also possible to attach a check valve to the actual vacuum pump afterwards.

    2. Standard degree of vacuum for the vacuum pump

    Use a pump which reaches 0.5 Torr (500 MICRON) or below after 5 minutes of operation.

    In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the

    vacuum pump is not properly maintained, the degree of vacuum may be too low.

    3. Required accuracy of the vacuum gauge

    Use a vacuum gauge that can measure up to 5 Torr. Do not use a general gauge manifold since it cannot measure a

    vacuum of 5 Torr.

    4. Evacuating time

    Evacuate the equipment for 1 hour after755 mmHg (5 Torr) has been reached.

    After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.

    5. Operating procedure when the vacuum pump is stopped

    In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the

    charge hose to drawn in air before stopping operation.

    The same operating procedure should be used when using a vacuum pump with a check valve.

  • 7/25/2019 dieu hoa ADMIN.pdf

    10/166

    9

    [7] Charging of Refrigerant

    R407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.

    For a cylinder with a syphon attached For a cylinder without a syphon attached

    Cylinder color identification R407C-Gray Charged with liquid refrigerant

    R410A-Pink

    Reasons :

    1. R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is

    charged with R407C gas, then the refrigerant whose evaporation temperature is closest to the outside temperature is

    charged first while the rest of refrigerants remain in the cylinder.

    Note :

    In the case of a cylinder with a syphon, liquid R407C is charged without turning the cylinder up side down. Check the

    type of cylinder before charging.

    [8] Dryer

    1. Replace the dryer when the refrigerant circuit is opened (Ex. Change the compressor, full gas leakage). Be sure to

    replace the dryer with a CITY MULTI Series Y (For use with R407C).

    If any other product is used, the unit will be damaged.

    2. Opening the refrigerant circuit after changing to a new dryer is less than 1 hour. The replacement of the dryer should

    be the last operation performed.

    Cylin-der

    Cylin-der

    ValveValve

    Liquid Liquid

  • 7/25/2019 dieu hoa ADMIN.pdf

    11/166

    10

    22222 COMPONENT OF EQUIPMENT

    [1] Appearance of Components

    Outdoor unit

    PU(H)Y-(P)200, 250YMF-C

    PUHY-YMF-C PUY-P-YMF-C

    Propeller fan

    Fan motor

    SCC Accumulator

    Compressor

    Drier

    Compressor

    Heatexchanger(front)

    Control Box

    Heatexchanger(rear)

    SCC Accumulator

    Compressor

    4way valve

  • 7/25/2019 dieu hoa ADMIN.pdf

    12/166

    11

    PURY-P200250YMF-C

    Propeller fan

    Heat exchanger(front)

    Control box

    Compressor

    Fan motor

    Heat exchanger(rear)

    PURY-YMF-C PURY-P-YMF-C

    SV3

    SV4

    SV6

    SV5

    SV block Accumulator

    CV block Compressor

    4way valve

    SV3SV4

    SV6

    SV5

    SV block4way valve

    CS circuit Accumulator

    Compressor

    Drier

    CV block

  • 7/25/2019 dieu hoa ADMIN.pdf

    13/166

    12

    Controller Box

    FANCON board

    INV board

    MAIN board

    Noise filter

    Choke coil (L2)

    Terminal block TB1A Power Source Terminal block TB7 Transmission (Centralized control)

    Terminal block TB3 Transmission

    Inteligent Power Module (IPM)

    G/A board

    Diode stack (DS)

    Magnetic contactor (52C)

    Capacitor (C2, C3)(Smoothing capacitor)

  • 7/25/2019 dieu hoa ADMIN.pdf

    14/166

    13

    MAIN board

    PUHY / PURY

    CN51Indication distance3-4CompressorON/OFF3-5Trouble

    CNRS3

    Serial transmission toINV board

    CN3D

    SW1

    CNTR CNFC1

    CNVCC4Power sourcefor control(5V)

    CN20Power supply3L11N

    SW3SW4 SW2 SWU2 SWU1

    CNS1 CNS2 CN40 CN41 CNVCC3Power Source

    for control1-230V1-330V4-612V5-65V

    CN3S

    CN3N

    LD1Service LED

  • 7/25/2019 dieu hoa ADMIN.pdf

    15/166

    14

    INV board

    CNDR2Out put toG/A board

    CNTH

    CN15V2Power supplyfor IPM control

    CNACCT

    CNAC2

    Powersource1L23N5G

    CN52CControl for52C

    CNFANControlfor MF1

    CNR

    CNRS2Serial transmissionto MAIN board

    SW1

    CNVDC1-4DC-560V

    CNVCC4Power supply (5V)

    CNL2Choke coil

    CNVCC2Power supply

    1-230V,1-330V4-612V,5-65V

  • 7/25/2019 dieu hoa ADMIN.pdf

    16/166

    15

    FANCON board

    CNFANCNPOW

    CNFC2

    CN15V1

    CNDR1

    CNIPM1

    G/A board

    CNE CNDC1

  • 7/25/2019 dieu hoa ADMIN.pdf

    17/166

    16

    BC controller

    CNTR

    CN02M-NETtransmission

    CN03

    CN12Powersupply1EARTH3N5L

    SW4 SW2 SW1

  • 7/25/2019 dieu hoa ADMIN.pdf

    18/166

    17

    RELAY 10 board

    RELAY 4 board

  • 7/25/2019 dieu hoa ADMIN.pdf

    19/166

    18

    [2] Refrigerant Circuit Diagram and Thermal Sensor1PUHY-200YMF-C, 250YMF-C

    : Solenoid valve

    : Orifice

    : Capillary

    : Check valve

    : Thermal sensor

    : Strainer

    SP : Service port

    ACC : Accumulator

    TH1

    TH6

    TH7

    TH8

    TH5

    TH2

    Indoorunit

    O/S

    63HSC

    J1

    Comp

    HEX2

    HEX1

    SCC

    LEV1

    ST4

    BV2

    ST2

    BV1

    ST1

    CJ2

    C

    V1

    ST3

    SV1

    SV2

    CP1

    SLEV

    SA

    MA

    CP2

    63H

  • 7/25/2019 dieu hoa ADMIN.pdf

    20/166

    1 9

    : Solenoid valve

    : Orifice

    : Capillary

    : Check valve

    : Thermal sensor

    : Strainer

    SP : Service port

    ACC : Accumulator

    2PUY-200YMF-C, 250YMF-C

    SA

    MA

    TH6

    HEX2

    HEX1

    TH7

    TH8

    TH5

    TH2

    CJ1

    LEV1

    SLEV

    BV2

    ST2

    BV1

    ST1

    ST3

    ST4

    SV1

    SV2

    CJ2

    O/S

    Comp

    CP1

    63HS

    SCC

    CP2

    63H

  • 7/25/2019 dieu hoa ADMIN.pdf

    21/166

    2 0

    : Solenoid valve

    : Orifice

    : Capillary

    : Check valve

    : Thermal sensor

    : Strainer

    SP : Service port

    ACC : Accumulator

    HEX1

    HEX2

    TH6

    SCC

    SV3

    CP1

    CJ1

    CJ2

    63HS

    SV1

    ST3

    CV1

    O/S

    63H

    63LS

    MA

    SA

    SLEV

    CP4

    TH9

    TH7

    ST4

    LEV1

    ST2BV2

    Indoorunits

    ST1BV1

    Comp

    Drier

    TH2

    TH10

    CP3

    SV4

    ST9

    ST8

    TH8

    TH5

    SV2

    ST5

    TH1

    3PUHY-P200YMF-C, P250YMF-C

  • 7/25/2019 dieu hoa ADMIN.pdf

    22/166

    21

    4PUY-P200YMF-C, 250YMF-C

    HEX2

    HEX1

    TH

    6

    SV3

    CJ1

    CJ2

    63H

    SV1

    SV2

    CV2

    CV1

    TH1

    ST5

    MA

    SA

    SLEV

    TH7

    ST4

    LEV1

    SCC

    Comp

    O/S

    Drier

    TH10

    CP

    TH8

    CP3

    TH5

    ST3

    TH9

    TH2

    ST2

    BV2

    Indoorunits

    ST1

    BV1

    63LS

    63HS

    : Solenoid valve

    : Orifice

    : Capillary

    : Check valve

    : Thermal sensor

    : Strainer

    SP : Service port

    ACC : Accumulator

  • 7/25/2019 dieu hoa ADMIN.pdf

    23/166

    2 2

    5PURY-200YMF-C, 250YMF-C

    TH10

    TH1

    TH5

    O/S

    63HS

    63LS

    Comp

    BV2

    BV1ST1

    CV1

    ST6

    SV1SV2

    CP1

    CJ1

    CJ2

    SLEV

    SA

    MA

    63H

    TH10

    TH6

    HEXb

    CV7HEXf3

    HEXf2

    HEXf1

    CV10

    CV3CV2

    CV5CV4CV9CV8

    CV6

    TH7

    Check Valves Block

    ACC

    Solenoid Valves Block

    SV6

    SV5SV3

    SV4

    Distributor

    TH23

    TH21

    TH22

    LEV

    SVC

    SVA

    SVB

    Indoor

    units

    BC controller

    CMB-P104V-E

    Gas/liquid separator

    63HS1

    LEV1

    63HS3

    LEV3

    TH12

    TH11

    TH15

    TH16

    : Solenoid valve

    : Orifice

    : Capillary

    : Check valve

    : Thermal sensor

    : Strainer

    SP : Service port

    ACC : Accumulator

  • 7/25/2019 dieu hoa ADMIN.pdf

    24/166

    2 3

    6PURY-P200YMF-C, P250YMF-C: Solenoid valve

    : Orifice

    : Capillary

    : Check valve

    : Thermal sensor

    : Strainer

    SP : Service port

    ACC : Accumulator

    TH23

    TH21

    TH22

    LEV

    SVC

    SVA

    SVB

    Indoor

    units

    BC controller

    CMB-P104V-E

    Gas/liquid separator

    63HS1

    LEV1

    63HS3

    LEV3

    TH12

    TH11

    TH15

    TH16

    TH1

    O/S

    63HS

    ST5

    CV1

    ST6

    SJ1

    63H63LS

    SV1 SV2

    CP1

    CJ2

    SLEV

    ACC

    SA

    MA

    CV10CV9CV8

    Check Valves Block

    TH5

    BV2

    BV1ST1

    TH6

    HEXb

    CV7HEXf3

    HEXf2

    HEXf1

    CV3CV2CV5CV4

    CV6

    TH7

    Solenoid Valves

    Block

    SV6SV5SV3

    SV4

    Distributor

    TH9Drier

    TH2

    CS(Composition Sensing) circuit

    CP2

    Comp

    TH10

  • 7/25/2019 dieu hoa ADMIN.pdf

    25/166

  • 7/25/2019 dieu hoa ADMIN.pdf

    26/166

  • 7/25/2019 dieu hoa ADMIN.pdf

    27/166

    26

    Symbolexplanation

    PE

    123123

    EARTH

    Terminalblock

    (forTransmission)

    TB02

    Terminalblock

    (forpowersource)

    TB01

    Name

    Sym

    bol

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Expansionvalve

    Thermistersensor

    Transformer

    Name

    Symbol

    SV1

    4A

    SV1

    4B

    SV1

    4C

    SVM

    TRTH11

    16

    LEV1,3

    PS1,3

    Pressuresensor

    Transmissionline

    Shieldwire /

    N

    220V

    240V5

    0Hz

    Powersource

    BCBoard

    LE

    V1

    TB0116151413121110987654321

    16

    15

    14

    13

    12

    11

    10987654321

    SVM

    SV4B

    SV4A

    SV4C

    SV3B

    SV3A

    SV3C

    SV2B

    SV2A

    SV2C

    SV1C

    SV1A

    SV1B

    }

    31

    CNTR

    CN02

    CN12

    1

    5

    3

    3

    1

    7531753175317531

    TR

    X2

    X1

    X30

    X4

    X3

    X31

    X6

    X5

    X32

    X8

    X7

    X33

    X21

    }DC

    30V

    6

    5

    4

    3

    2

    1

    6

    5

    4

    3

    2

    1

    LEV3

    1 2 3

    CNP1

    1 2 3

    CNP3

    21 1 2 3 4 5 6 7 8 4321

    1

    2

    3

    2

    1

    CN03

    CN13

    CN10

    CN11

    CN07

    CN

    05

    L N

    TH11

    TH12

    TH15

    TH16

    PS1

    PS3

    20

    22V

    TB02 M

    2M1

    CN26

    CN27

    CN28

    CN29

    TB01

    220

    240V

    C

    N36

    1

    1

    1

    1

    Note:1.TB02isterminalblockfortransmission.

    Neverconnectpowerlineto

    it.

    2.1:SVM

    isnotbuiltindepen

    dingonmodels.

    3

    CMB-P104V

    -E

  • 7/25/2019 dieu hoa ADMIN.pdf

    28/166

    27

    4

    CMB-P105V

    -E

    Symbolexplanation

    PE

    123123

    EARTH

    Terminalblock

    (forTransmission)

    TB02

    Terminalblock

    (forpowersource)

    TB01

    Name

    Sym

    bol

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Expansionvalve

    Thermistersensor

    Transformer

    Name

    Symbol

    SV1

    5A

    SV1

    5B

    SV1

    5C

    SVM

    TRTH11

    16

    LEV1,3

    PS1,3

    Pressuresensor

    Transmissionline

    Shieldwire /

    N

    220V

    240V50Hz

    Powersource

    BC

    Board

    LEV1

    TB011

    615

    21

    21

    14

    13

    12

    11

    10

    987654321

    16

    15

    14

    13

    12

    11

    10987654321

    SV4B

    SV4A

    SV4C

    SV3B

    SV3A

    SV3C

    SV2B

    SV2A

    SV2C

    SV1C

    SV1A

    SV1B

    }

    31

    CNTR

    CN02

    CN12

    1

    5

    3

    3

    1

    7531753175317531

    TR

    X2

    X1

    X3

    0

    X4

    X3

    X3

    1

    X6

    X5

    X3

    2

    X8

    X7

    X3

    3

    X21

    }DC

    30V

    6

    5

    4

    3

    2

    1

    6

    5

    4

    3

    2

    1

    LEV3

    1 2 3

    CNP1

    1 2 3

    CNP3

    21 1 2 3 4 5 6 7 8 4321

    1

    2

    3

    2

    1

    CN03

    CN13

    CN10

    CN11

    CN07

    CN05

    L N

    TH11

    TH12

    TH15

    TH16

    PS1

    PS3

    20

    22V

    TB02 M

    2M1

    CN26

    CN27

    CN28

    CN29

    TB01

    220

    240V

    SV5C

    SV5A

    SV5B

    7531

    X1

    0

    X9

    X3

    4

    CN30

    SVM

    CN36

    1

    1

    1

    1

    Note:1.TB02isterminalblockfortransmission.

    Neverconnectpowerlinetoit.

    2.

    1

    :SVM

    isnotbuiltindepen

    dingonmodels.

  • 7/25/2019 dieu hoa ADMIN.pdf

    29/166

    28

    5

    CMB-P106V

    -E

    PE

    123123

    EARTH

    Transmissionline

    Shieldwire /

    N

    220V

    240V50Hz

    Powersource

    BCBoard

    3

    1

    LEV1

    TB01

    SV6B

    SV6A

    SV6C

    16

    15

    14

    13

    12

    11

    10

    987654321

    16

    15

    14

    13

    12

    11

    10987654321

    SV5C

    SV5A

    SV5B

    SV4B

    SV4A

    SV4C

    SV3B

    SV3A

    SV3C

    SV2B

    SV2A

    SV2C

    SVM

    SV1C

    SV1A

    SV1B

    }

    4

    3

    2

    11

    2

    3

    4

    CN38

    31

    CNTR

    CN02

    CN12

    1

    5

    3

    3

    1

    753175317531753175317531

    TR

    3 CNVCC1

    1

    2

    X2

    X1

    X30

    X4

    X3

    X31

    X6

    X5

    X32

    X8

    X7

    X33

    X10

    X9

    X34

    X12

    X11

    X35

    X21

    }DC

    30V

    6

    5

    4

    3

    2

    1

    6

    5

    4

    32

    1

    LEV3

    1 2 3

    CNP1

    1 2 3

    CNP3

    21 1 2 3 4 5 6 7 8 4321

    1

    2

    3

    2

    1

    CN51

    CN50

    CNOUT1

    CNOUT3

    CN03

    CN13

    CN10

    CN11

    CN07

    CN05

    L N

    TH11

    TH12

    TH15

    TH16

    PS1

    PS3

    20

    22V

    TB02 M

    2M1

    CN26

    CN2

    7

    CN28

    CN29

    CN30

    CN31

    TB01

    220

    240V

    CN

    36

    Symbolexplanation

    Terminalblock

    (forTransmission)

    TB02

    Terminalblock

    (forpowersource)

    TB01

    Name

    Symbol

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Expansionvalve

    Thermistersensor

    Transformer

    Name

    Symbol

    SV1

    6A

    SV1

    6B

    SV1

    6C

    SVM

    TRTH11

    16

    LEV1,3

    PS1,3

    Pressuresensor

    1

    1

    1

    1

    7

    6

    5

    4

    3

    2

    1

    1

    2

    3

    4

    5

    6

    Note:1.TB02isterminalblockfortra

    nsmission.

    Neverconnectpowerlineto

    it.

    2.1:SVM

    isnotbuiltindepend

    ingonmodels.

  • 7/25/2019 dieu hoa ADMIN.pdf

    30/166

    29

    6

    CMB-P108V

    -E

    PE

    123123

    EARTH

    }Powersource

    }}L N

    Powersource

    /N

    220V

    240V50Hz

    Transmissionline

    Shieldwire

    SVM

    BCBoard

    CN38

    1

    31

    CNTR

    CN50

    CN5

    1

    7

    6

    5

    4

    3

    2

    1

    1

    2

    3

    4

    5

    6

    CN02

    CN12

    1

    5

    3

    3

    1

    753175317531753175317531

    3

    TR

    3CNVCC1

    1

    2

    X2

    X1

    X30

    X4

    X3

    X31

    X6

    X5

    X32

    X8

    X7

    X33

    X10

    X9

    X34

    X12

    X11

    X35

    X21

    }DC

    30V

    6

    5

    4

    3

    2

    1

    6

    5

    4

    3

    2

    1

    LEV3

    LEV1

    1 2 3

    CNP1

    1 2 3

    CNP3

    21 1 2 3 4 5 6 7 8 4321

    1

    2

    3

    2

    1

    CN03

    CN13

    CN10

    CN11

    CN07

    CN05

    CN36

    TH11

    TH12

    TH15

    TH16

    PS1

    PS3

    20

    22V

    TB02

    M2M1

    CN26

    CN27

    CN28

    CN29

    CN30

    CN31

    TB01

    220

    240V

    LEV1

    7

    6

    5

    4

    3

    2

    1

    TB01

    SV6B

    SV6A

    SV6C

    16

    15

    14

    13

    12

    11

    10987654321

    16

    15

    14

    13

    12

    11

    10

    987654321

    RELAY4Board

    SV5C

    SV5A

    SV5B

    SV4B

    SV4A

    SV4C

    SV3B

    SV3A

    SV3C

    SV2B

    SV2A

    SV2C

    CN32

    CN33

    CN39

    3 1

    SV7C

    SV7A

    SV7B

    SV8C

    SV8A

    SV8B

    SV1C

    SV1A

    SV1B

    X14

    X13

    X36

    X37

    X15

    X16

    9

    8

    7

    6

    5

    4

    3

    2

    1

    16

    15

    10

    11

    12

    13

    14

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    CN

    52

    7

    5

    3

    1

    7

    5

    3

    1

    Symbolexplanation

    Terminalblock

    (forTransmission)

    TB02

    Terminalblock

    (forpowersource)

    TB01

    Name

    Sym

    bol

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Expansionvalve

    Thermistersensor

    Transformer

    Name

    Symbol

    SV1

    8A

    SV1

    8B

    SV1

    8C

    SVM

    TRTH11

    16

    LEV1,3

    PS1,3

    Pressuresensor

    CNOUT1

    CNOUT3

    1

    Note:1.TB02isterminalblockfortransmission.

    1

    1

    1

    Neverconnectpowerlinetoit.

    2.1:SVM

    isnotbuiltindependingonmodels.

  • 7/25/2019 dieu hoa ADMIN.pdf

    31/166

    30

    7

    CMB-P1010

    V-E

    PE

    123123

    EARTH

    }

    Powersource

    }}L N

    Powersource

    /N

    220V

    240V50Hz

    Transmissionline

    Shieldwire

    SV10B

    SV10A

    SV10C

    SV9B

    SV9A

    SV9C

    BC

    Board

    CN38

    1

    31

    CNTR

    CN50

    CN5

    1

    7

    6

    5

    4

    3

    2

    1

    1

    2

    3

    4

    5

    6

    CN02

    CN12

    1

    5

    3

    3

    1

    753175317531753175317531

    3

    TR

    3CNVCC1

    1

    2

    X2

    X1

    X30

    X4

    X3

    X31

    X6

    X5

    X32

    X8

    X7

    X33

    X10

    X9

    X34

    X12

    X11

    X35

    X21

    }

    DC

    30V

    6

    5

    4

    3

    2

    1

    6

    54

    3

    2

    1

    LEV3

    LEV1

    1 2 3

    CNP1

    1 2 3

    CNP3

    21 1 2 3 4 5 6 7 8 4321

    1

    2

    3

    2

    1

    CN03

    CN13

    CN10

    CN11

    CN07

    CN05

    CN36

    TH11

    TH12

    TH15

    TH16

    PS1

    PS3

    20

    22V

    TB02

    M2M1

    CN26

    CN27

    CN28

    CN29

    CN30

    CN31

    TB01

    220

    240V

    LEV1

    7

    6

    5

    4

    3

    2

    1

    1

    2

    3

    4

    5

    6

    CN35

    TB01

    SV6B

    SV6A

    SV6C

    SVM

    16

    15

    14

    13

    12

    11

    10987654321

    16

    15

    14

    13

    12

    11

    10

    987654321

    RELAY4Board

    SV5C

    SV5A

    SV5B

    SV4B

    SV4A

    SV4C

    SV3B

    SV3A

    SV3C

    SV2B

    SV2A

    SV2C

    CN32

    CN33

    CN34

    CN39

    3 1

    SV7C

    SV7A

    SV7B

    SV8C

    SV8A

    SV8B

    SV1C

    SV1A

    SV1B

    X14

    X13

    X36

    X37

    X15

    X16

    9

    8

    7

    6

    5

    4

    3

    2

    1

    16

    15

    10

    11

    12

    13

    14

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    X18

    X17

    X38

    X39

    X19

    X20

    CN

    52

    CN53

    5

    7

    3

    1

    7

    5

    3

    1

    7

    5

    3

    1

    7

    5

    3

    3

    3

    1

    Symbolexplanation

    Terminalblock

    (forTransmission)

    TB02

    Terminalblock

    (forpowersource)

    TB01

    Name

    Sym

    bol

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Expansionvalve

    Thermistersensor

    Transformer

    Name

    Symbol

    SV1

    10A

    SV1

    10B

    SV1

    10C

    SVM

    TRTH11

    16

    LEV1,3

    PS1,3

    Pressuresensor

    CNOUT1

    CNOUT3

    1

    1

    1

    1

    Note:1.TB02isterminalblockfortransmission.

    Neverconnectpowerlinetoit.

    2.

    1

    :SVM

    isnotbuiltindependingonmodels.

  • 7/25/2019 dieu hoa ADMIN.pdf

    32/166

  • 7/25/2019 dieu hoa ADMIN.pdf

    33/166

    32

    9

    CMB-P1016V-E

    PE

    EARTH

    3 2 1 3 2 1

    TB02

    TB01

    Name

    S

    ymbol

    Terminalblock

    (forTransmission)

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Solenoidvalve

    Terminalblock

    (forpowersource)

    Pressuresensor

    Expansionvalve

    Thermistersensor

    Transformer

    Name

    SV1~16A

    SV1~16B

    SV1~16C

    SVM

    Symbol

    TRTH11~16

    LEV1,3

    PS1,3

    M1

    M2

    DC30V

    }Shieldwire

    Transmissionline

    Powersource

    }L N

    Powersource

    ~/N220V~240V50Hz

    CN39

    1

    3

    6

    5

    4

    3

    2

    1

    1

    2

    3

    4

    5

    6

    7

    CN51

    CN50

    1

    3

    5

    C

    N12

    1

    3

    CNOUT3

    CNOUT1

    1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7

    1 3 5 71 3 5 77531

    1

    5

    7

    1

    5

    7

    1

    3

    5

    7

    1

    3

    2

    1

    CNVCC2

    3

    CN42

    X46

    X47

    X48

    1 2 387654321 4

    CNOUT2

    CNOUT4

    CN41

    CN40

    X41

    X44

    X40

    X43

    X42

    X45

    X20

    X18

    X19

    X17

    X39

    X38

    3 CNVCC1

    1

    2

    X16

    X15

    X37

    X36

    X13

    X14

    X2

    X1

    X30

    X4

    X3

    X31

    X6

    X5

    X32

    X8

    X7

    X33

    X10

    X9

    X34

    X12

    X11

    X35

    X21

    6

    5

    4

    3

    2

    1

    6

    5

    4

    3

    2

    1

    LEV3

    LEV1

    1 2 3

    CNP1

    1 2 3

    CNP3

    21 1 2 3 4 5 6 7 8 4321

    1

    2

    3

    2

    1

    CN03

    CN02

    CN13

    CN10

    CN11

    CN07

    CN05

    3

    3

    CN34

    CN33

    1

    3

    5

    7

    CN32

    TH11

    TH12

    TH15

    TH16

    TR

    TB02

    CN38

    CN26

    CN27

    CN28

    CN29

    CN30

    CN31

    TB01

    CN35

    31

    CNTR

    41 2 3 4 5 6 7 8 321

    SV1B

    SV1A

    SV1C

    SV2C

    SV2A

    SV2B

    SV3C

    SV3A

    SV3B

    SV4C

    SV4A

    SV4B

    SV5B

    SV5A

    SV5C

    1 2 3 4 5 6 7 8 9 10

    11

    12

    13

    14

    15

    16

    1 2 3 4 5 6 7 8 9 10

    11

    12

    13

    14

    15

    16

    SV9C

    SV9A

    SV9B

    SV10C

    SV10A

    SV10B

    16

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    14

    13

    12

    11

    10

    15

    16

    1

    2

    3

    4

    5

    6

    7

    8

    9

    SV8B

    SV8A

    SV8C

    SV7B

    SV7A

    SV7C

    SVM

    SV6C

    SV6A

    SV6B

    SV11C

    SV11A

    SV11B

    16

    15

    14

    13

    12

    11

    10987654321

    98765432116

    15

    14

    13

    12

    11

    10

    SV12C

    SV12A

    SV12B

    SV13C

    SV13A

    SV13B

    PS1

    PS3

    1

    1

    1

    1

    Note:1.TB02istransmissiont

    erminalblock.

    Neverconnectpowerlinetoit.

    2.

    1:SVM

    isnotbuiltind

    ependingonmodels.

    1 2

    21

    1 3 5 71 3 5 71 3 5 7

    X57

    X53

    X52

    X56

    X55

    CN45

    CN44

    CN43

    X50

    SV14C

    SV14A

    SV14B

    SV15A

    SV15B

    SV16C

    SV16A

    SV16B

    SV15C

    X54

    X51

    X49

    RELAY10

    Board

    BC

    Bo

    ard

    20

    22V

    220

    240V

    CN36

  • 7/25/2019 dieu hoa ADMIN.pdf

    34/166

    33

    [4] Standard Operation Data

    (1) Cooling operation

    1 PU(H)Y-200250YMF-C

    Outdoor unit

    ItemsPUHY-200YMF-C

    PUY-200YMF-C

    PUHY-250YMF-C

    PUY-250YMF-C

    Indoor

    Outdoor

    Quantity

    Quantity in operation

    Model

    Main pipe

    Branch pipe

    Total piping length

    27.0/19.0 27.0/19.0

    35.0/24.0 35.0/24.0

    4 4

    4 4

    63 63 50 25 125 40 63 25

    5 5

    10 10 10 10 10 10 10 10

    45 45

    Hi Hi Hi Hi Hi Hi Hi Hi

    11.2 12.7

    440 440 380 280 430 350 440 280

    130 140

    235 235

    22.0/4.80 20.3/4.7(2.16/0.47) (1.99/0.46)

    93 95

    40 42

    7 5

    9 7

    7 10

    6 4

    69 60

    27 27

    8 6

    26 26

    10 10

    14.5 13.3 18.3 16.8

    380 415 380 415

    270/75 270/75 340/95 340/95

    Indoor unit fan notch

    Refrigerant volume

    Total current

    Volts/Frequency

    Indoor unit

    SC (LEV1)

    Oil return (SLEV)

    High pressure/Low pressure (after O/S)

    (before MA)Pressure

    DB/WB

    Set

    m

    kg

    A

    V

    V/Hz

    Pulse

    kg/cm2G(MPa)

    C

    Condition

    Sectionaltemperature

    Outdoorunit

    LEV

    opening

    Discharge (TH1)

    Heat exchanger outlet (TH5)

    Accumulator

    Suction (Comp)

    TH2

    Shell bottom (Comp)

    SCC outlet (TH7)

    Bypass outlet (TH8)

    LEV inlet

    Heat exchanger outlet

    Inlet

    Outlet

    Outdoor

    unit

    Indoorunit

    Ambient temp.

    Indoor unit

    Piping

  • 7/25/2019 dieu hoa ADMIN.pdf

    35/166

    34

    PU(H)Y-P200250YMF-C

    Outdoor unit

    ItemsPUHY-P200YMF-C

    PUY-P200YMF-C

    PUHY-P250YMF-C

    PUY-P250YMF-C

    Indoor

    Outdoor

    Quantity

    Quantity in operation

    Model

    Main pipe

    Branch pipe

    Total piping length

    27.0/19.0 27.0/19.0

    35.0/24.0 35.0/24.0

    4 4

    4 4

    63 63 50 25 125 40 63 25

    5 5

    10 10 10 10 10 10 10 10

    45 45

    Hi Hi Hi Hi Hi Hi Hi Hi

    11.7 13.2

    440 440 380 280 430 350 440 280

    130 140

    235 235

    20.5/4.0 21.9/3.9

    (2.01/0.39) (2.15/0.38)

    96 96

    40 42

    7 7

    10 10

    12 15

    1 1

    11 11

    80 85

    27 27

    8 6

    26 26

    10 10

    0.23 0.23

    14.5 13.3 18.3 16.8

    380 415 380 415

    270/75 270/75 340/95 340/95

    Indoor unit fan notch

    Refrigerant volume

    Total current

    Volts/Frequency

    Indoor unit

    SC (LEV1)

    Oil return (SLEV)

    High pressure/Low pressure (after O/S)

    (before MA)Pressure

    DB/WB

    Set

    m

    kg

    A

    V

    V/Hz

    Pulse

    kg/cm2G

    (MPa)

    C

    Condition

    Sectional

    temperature

    Outdoorunit

    LEVopening

    Inlet

    Outlet

    Outdoor

    unit

    Indoorunit

    OC

    Ambient temp.

    Indoor unit

    Piping

    Discharge (TH1)

    Heat exchanger outlet (TH5)

    Accumulator

    Suction (Comp)

    CS circuit (TH2)

    CS circuit (TH9)

    Shell bottom (Comp)

    SCC outlet (TH7)

    Bypass outlet (TH8)

    LEV inlet

    Heat exchanger outlet

  • 7/25/2019 dieu hoa ADMIN.pdf

    36/166

    35

    380 415 380 415

    270/75 270/75 340/95 340/95

    14.5 13.3 18.3 16.8

    PURY-200250YMF-C

    Outdoor unit

    ItemsPURY-P200YMF-C PURY-P250YMF-C

    Indoor

    Outdoor

    Quantity

    Quantity in operation

    Model

    Main pipe

    Branch pipe

    Total piping length

    27.0/19.0 27.0/19.0

    35.0/24.0 35.0/24.0

    4 4

    4 4

    63 63 50 25 125 40 63 25

    5 5

    5 5 5 5 5 5 5 5

    25 25

    Hi Hi Hi Hi Hi Hi Hi Hi

    13.9 14.4

    330 460 430 300 410 330 460 300

    2000 140 2000 150

    235 235

    20.7/5.0 19.4/4.0

    (2.03/0.49) (1.90/0.39)

    19.6/19.6 18.3/18.3(1.92/1.92) (1.79/1.79)

    107 110

    50 47

    7 7

    10 10

    12 12

    75 70

    26 30

    15 15

    Indoor unit fan notch

    Refrigerant volume

    Compressor volts / Frequency

    Outdoor unit

    Indoor unit

    BC controller (1, 3)

    Oil return

    High pressure/Low pressure

    BC controller liquid/IntermediatePressur

    e

    DB/WB

    Qty

    m

    kg

    V

    V/Hz

    A

    Pulse

    kg/cm2G(MPa)

    C

    Condition

    Sectionaltemperature

    LEVopening

    Discharge (TH1)

    Heat exchanger outlet (TH5)

    Accumulator

    Suction (Comp)

    Shell bottom (Comp)

    LEV inlet

    Heat exchanger outlet

    Inlet

    Outlet

    Outdoor

    unit

    Indoorunit

    Ambient temp.

    Indoor unit

    Piping

  • 7/25/2019 dieu hoa ADMIN.pdf

    37/166

    36

    PURY-P200250YMF-C

    Outdoor unit

    ItemsPURY-P200YMF-C PURY-P250YMF-C

    Indoor

    Outdoor

    Quantity

    Quantity in operation

    Model

    Main pipe

    Branch pipe

    Total piping length

    27.0/19.0 27.0/19.0

    35.0/24.0 35.0/24.0

    4 4

    4 4

    63 63 50 25 125 40 63 25

    5 5

    5 5 5 5 5 5 5 5

    25 25

    Hi Hi Hi Hi Hi Hi Hi Hi

    14.4 14.9

    330 460 430 300 410 330 460 300

    2000 140 2000 150

    235 235

    23.5/5.3 23.0/5.1

    (2.30/0.52) (2.25/0.50)

    22.4/22.4 21.9/21.9(2.20/2.20) (2.15/2.15)

    97 105

    50 47

    7 7

    10 10

    12 12

    7 5

    75 70

    26 30

    15 15

    0.23 0.23

    380 415 380 415

    270/75 270/75 340/95 340/95

    14.5 13.3 18.3 16.8

    Indoor unit fan notch

    Refrigerant volume

    Compressor volts / Frequency

    Outdoor unit

    Indoor unit

    BC controller (1, 3)

    Oil return

    High pressure/Low pressure

    BC controller liquid/IntermediatePressure

    DB/WB

    Qty

    m

    kg

    V

    V/Hz

    A

    Pulse

    kg/cm2G(MPa)

    C

    Condition

    Sectionaltemperature

    LEVopening

    Discharge (TH1)

    Heat exchanger outlet (TH5)

    Accumulator

    Suction (Comp)

    CS circuit (TH2)

    Shell bottom (Comp)

    LEV inlet

    Heat exchanger outlet

    Inlet

    OutletOutdoor

    unit

    Indoor

    unit

    OC

    Ambient temp.

    Indoor unit

    Piping

  • 7/25/2019 dieu hoa ADMIN.pdf

    38/166

    37

    2Heating operation

    PUHY-200250YMF-C

    Outdoor unit

    ItemsPUHY-200YMF-C PUHY-250YMF-C

    Indoor

    Outdoor

    Quantity

    Quantity in operation

    Model

    Main pipe

    Branch pipe

    Total piping length

    20.0/ 20.0/

    7.0/6.0 7.0/6.0

    4 4

    4 4

    63 63 50 25 125 40 63 25

    5 5

    10 10 10 10 10 10 10 10

    45 45

    Hi Hi Hi Hi Hi Hi Hi Hi

    11.2 12.7

    510 510 450 280 440 420 510 280

    0 0

    150 235

    17.5/3.7 17.5/3.7(1.72/0.36) (1.72/0.36)

    80 85

    6 8

    1 2

    1 2

    1 2

    2 2

    50 60

    71 71

    33 33

    13.4 12.3 17.1 15.6

    380 415 380 415

    280/83 280/83 355/102 355/102

    Indoor unit fan notch

    Refrigerant volume

    Total current

    Volts/Frequency

    Indoor unit

    SC (LEV1)

    Oil return (SLEV)

    High pressure/Low pressure (after O/S)(before MA)

    Pressure

    DB/WB

    Set

    m

    kg

    A

    V

    V/Hz

    Pulse

    kg/cm2G(MPa)

    C

    Condition

    Se

    ctionaltemperature

    Outdoorunit

    LEVopening

    Discharge (TH1)

    Heat exchanger outlet (TH5)

    Accumulator

    Suction (Comp)

    TH2

    Shell bottom (Comp)

    Heat exchanger outlet

    LEV inlet

    Inlet

    OutletOutdoor

    unit

    Indoor

    unit

    Ambient temp.

    Indoor unit

    Piping

  • 7/25/2019 dieu hoa ADMIN.pdf

    39/166

    38

    PUHY-P200250YMF-C

    Outdoor unit

    ItemsPUHY-P200YMF-C PUHY-P250YMF-C

    Indoor

    Outdoor

    Quantity

    Quantity in operation

    Model

    Main pipe

    Branch pipe

    Total piping length

    20.0/ 20.0/

    7.0/6.0 7.0/6.0

    4 4

    4 4

    63 63 50 25 125 40 63 25

    5 5

    10 10 10 10 10 10 10 10

    45 45

    Hi Hi Hi Hi Hi Hi Hi Hi

    11.7 13.2

    510 510 450 280 440 420 510 280

    0 0

    150 150

    18.5/3.7 21.4/3.7

    (1.81/0.36) (2.10/0.36)

    75 78

    1 1

    2 2

    2 2

    3 3

    3 3

    0 0

    60 70

    80 80

    39 39

    0.28 0.28

    13.4 12.3 17.1 15.6

    380 415 380 415

    270/75 270/75 340/95 340/95

    Indoor unit fan notch

    Refrigerant volume

    Total current

    Volts/Frequency

    Indoor unit

    SC (LEV1)

    Oil return (SLEV)

    High pressure/Low pressure (after O/S)

    (before MA)Pressure

    DB/WB

    Set

    m

    kg

    A

    V

    V/Hz

    Pulse

    kg/cm2G

    (MPa)

    C

    Condition

    Se

    ctionaltemperature

    Outdoorunit

    LEVopening

    Discharge (TH1)

    Heat exchanger inlet (TH5)

    Accumulator

    Suction (Comp)

    CS circuit (TH2)

    CS circuit (TH9)

    Shell bottom (Comp)

    Heat exchanger outlet

    LEV inlet

    Inlet

    OutletOutdoor

    unit

    Indoorunit

    OC

    Ambient temp.

    Indoor unit

    Piping

  • 7/25/2019 dieu hoa ADMIN.pdf

    40/166

    39

    PURY-200250YMF-C

    Outdoor unit

    ItemsPURY-200YMF-C PURY-250YMF-C

    Indoor

    Outdoor

    Quantity

    Quantity in operation

    Model

    Main pipe

    Branch pipe

    Total piping length

    20.0/ 20.0/

    7.0/6.0 7.0/6.0

    4 4

    4 4

    63 63 50 25 125 40 63 25

    5 5

    5 5 5 5 5 5 5 5

    25 25

    Hi Hi Hi Hi Hi Hi Hi Hi

    13.9 14.4

    600 950 750 400 750 600 950 400

    60 700 60 800

    150 235

    18.5/3.6 18.0/3.7

    (1.81/0.35) (1.76/0.36)

    17.5/14.0 17.0/14.0(1.72/1.37) (1.67/1.37)

    100 95

    2 1

    1 1

    4 2

    1 1

    45 40

    38 40

    80 85

    380 415 380 415

    285/85 285/85 360/105 360/105

    13.4 12.3 17.1 15.6

    Indoor unit fan notch

    Refrigerant volume

    Compressor volts / Frequency

    Outdoor unit total current

    Indoor unit

    BC controller (1, 3)

    Oil return

    High pressure/Low pressure

    BC controller liquid/IntermediatePressur

    e

    DB/WB

    Qty

    m

    kg

    V

    V/Hz

    A

    Pulse

    kg/cm2G(MPa)

    C

    Condition

    Sectionaltemperature

    LEVopening

    Discharge (TH1)

    Heat exchanger outlet (TH5)

    Accumulator

    Suction (Comp)

    Shell bottom (Comp)

    LEV inlet

    Heat exchanger outlet

    Inlet

    Outlet

    Outdoor

    unit

    Indoorunit

    Ambient temp.

    Indoor unit

    Piping

  • 7/25/2019 dieu hoa ADMIN.pdf

    41/166

    40

    PURY-P200250YMF-C

    Outdoor unit

    ItemsPURY-P200YMF-C PURY-P250YMF-C

    Indoor

    Outdoor

    Quantity

    Quantity in operation

    Model

    Main pipe

    Branch pipe

    Total piping length

    20.0/ 20.0/

    7.0/6.0 7.0/6.0

    4 4

    4 4

    63 63 50 25 125 40 63 25

    5 5

    5 5 5 5 5 5 5 5

    25 25

    Hi Hi Hi Hi Hi Hi Hi Hi

    14.4 14.9

    600 950 750 400 750 600 950 400

    60 700 60 800

    150 235

    18.5/3.6 18.0/3.7

    (1.96/0.38) (1.86/0.34)

    17.5/14.0 17.0/14.0(1.86/1.57) (1.76/1.47)

    100 95

    2 1

    1 1

    4 2

    1 1

    7 5

    45 40

    38 40

    80 85

    0.28 0.28

    380 415 380 415

    280/80 280/80 340/95 340/95

    13.4 12.3 17.1 15.6

    Indoor unit fan notch

    Refrigerant volume

    Compressor volts/Frequency

    Outdoor unit total current

    Indoor unit

    BC controller (1, 3)

    Oil return

    High pressure/Low pressure

    BC controller liquid/IntermediatePressur

    e

    DB/WB

    Qty

    m

    kg

    V

    V/Hz

    A

    Pulse

    kg/cm2G(MPa)

    C

    Condition

    Section

    altemperature

    LEVopening

    Discharge (TH1)

    Heat exchanger outlet (TH5)

    Accumulator

    Suction (Comp)

    CS circuit

    Shell bottom (Comp)

    LEV inlet

    Heat exchanger outlet

    Inlet

    Outlet

    (TH2)

    Outdoor

    unit

    Indoor

    unit

    OC

    Ambient temp.

    Indoor unit

    Piping

  • 7/25/2019 dieu hoa ADMIN.pdf

    42/166

    41

    [5] Function of Dip SW and Rotary SW

    (1) Outdoor unit

    1PU(H)Y-200250YMF-C

    Switch FunctionFunction according to switch operation Switch set timing

    When off When on When off When on

    SWUSW1

    SW2

    SW3

    SW4

    1~21~8

    9~10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    Unit address settingFor self diagnosis/

    operation monitoring

    Centralized control switch

    Deletion of connection

    information.

    Deletion of error history.

    Disregard ambient air

    sensor errors, liquid

    overflow errors.Forced defrosting

    Defrost prohibited timer

    -

    -

    SW3-2 Function valid/

    invalid

    Indoor unit test operation

    Defrosting start tempera-

    ture of TH5.Defrosting end tempera-

    ture of TH5.

    Opening angle of IC except

    when heater thermostat is

    ON during defrosting.

    Models

    Target Pd (High pressure)

    Models

    Set on 51~100 with the dial switch.LED monitering display

    Centralized control not

    connected.

    Storing of refrigeration

    system connection

    information.

    Errors valid.

    Ordinary control

    43 min.

    SW3-2 Function invalid

    Stop all indoor units.

    -2C

    8C

    (no operation)

    PUHY-YMF-C

    18kg/cm2G

    (1.76MPa)

    Model 200

    Centralized control

    connected.

    Deletion of refrigeration

    system connection

    information.

    Deletion

    Disregard errors.

    Start forced defrosting.

    90 min.

    SW3-2 Function valid

    All indoor units test

    operation ON.

    0C

    15C

    2000

    PUY-YMF-C

    20kg/cm2G

    (1.96MPa)

    Model 250

    Before power is turned on.During normal operation when power

    is on.

    Should be set on OFF.

    Before power is turned on.

    Before power is turned on.

    During normal operation when power

    is on.

    During normal operation when power

    is on.

    During normal operation when power

    is on. (Except during defrosting)

    During normal operation when power

    is on.

    When SW3-1 is ON after power is

    turned on.

    During normal operation when power

    is on.During normal operation when power

    is on. (Except during defrosting)

    When switching on the power.

    During normal operation when power

    is on.

    When switching on the power.

    During normal

    operation when

    power is on.

    10 minutes or

    more after

    compressor

    starts.

    Note:

    SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.

    If the address is set from 01 to 50, it automatically becomes 100.

  • 7/25/2019 dieu hoa ADMIN.pdf

    43/166

    42

    2PUHY-P200250YMF-C

    Switch FunctionFunction according to switch operation Switch set timing

    When off When on When off When onSWU

    SW1

    SW2

    SW3

    SW4

    1~2

    1~8

    9~10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    Unit address setting

    For self diagnosis/

    operation monitoring

    Centralized control switch

    Deletion of connection

    information.

    Deletion of error history.

    Disregard ambient air

    sensor errors, liquid

    overflow errors.

    Forced defrosting

    Defrost prohibited timer

    SW3-2 Function valid/

    invalid

    Indoor unit test operation

    Defrosting start tempera-

    ture of TH5.

    Defrosting end tempera-

    ture of TH5.

    Opening angle of IC except

    when heater thermostat isON during defrosting.

    Models

    Target Tc (High pressure)

    at Heating

    Models

    SW4-2 Function valid/

    invalid

    Configuration compensa-

    tion value

    Set on 51~100 with the dial switch.

    LED Monitering Display

    Centralized control not

    connected.

    Storing of refrigeration

    system connection

    information.

    Errors valid.

    Ordinary control

    39 min.

    SW3-2 Function invalid

    Stop all indoor units.

    4C

    8C

    (no operation)

    PUHY-P-YMF-C

    49C

    Model P200

    Invalid

    Centralized control

    connected.

    Deletion of refrigeration

    system connection

    information.

    Deletion

    Disregard errors.

    Start forced defrosting.

    90 min.

    SW3-2 Function valid

    All indoor units test

    operation ON.

    1C

    15C

    2000

    PUY-P-YMF-C

    53C

    Model P250

    Valid

    Before power is turned on.

    During normal operation when power

    is on.

    Should be set on OFF.

    Before power is turned on.

    Before power is turned on.

    During normal operation when power

    is on.

    During normal operation when power

    is on.

    During normal operation when power

    is on. (Except during defrosting)

    During normal operation when power

    is on.

    When SW3-1 is ON after power is

    turned on.

    During normal operation when power

    is on.

    During normal operation when power

    is on. (Except during defrosting)

    When switching on the power.

    During normal operation when power

    is on.

    When switching on the power.

    During normal operation when power

    is on.

    when SW4-1 in ON.

    During normal

    operation when

    power is on.

    10 minutes or

    more after

    compressor

    starts.

    Note:

    SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.

    If the address is set from 01 to 50, it automatically becomes 100.

    Changes as shown below by on off change

    0% 3% 6% 9% 12% 6% 3% 0%

  • 7/25/2019 dieu hoa ADMIN.pdf

    44/166

    43

    3PURY-200250YMF-C

    Switch FunctionFunction according to switch operation Switch set timing

    When off When on When off When on

    SWU

    SW1

    SW2

    SW3

    SW4

    1~2

    1~8

    9~10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    Unit address setting

    For self diagnosis/

    operation monitoring

    Centralized control switch

    Deletion of connection

    information.

    Deletion of error history.

    Disregard ambient air

    sensor errors, liquid

    overflow errors.

    Forced defrosting

    Defrost prohibited timer

    SW3-2 Function valid/

    invalid

    Indoor unit test operation

    Defrosting start tempera-

    ture of TH7.

    Defrosting end tempera-

    ture of TH5.

    Pump down operation

    Target Td (High pressure)

    at Heating

    Models

    Set on 51~100 with the dial switch.

    LED monitering display

    Centralized control not

    connected.

    Storing of refrigeration

    system connection

    information.

    Errors valid.

    Ordinary control

    43 min.

    SW3-2 Function invalid

    Stop all indoor units.

    6C

    8C

    Invalid

    49C

    Model 200

    Centralized control

    connected.

    Deletion of refrigeration

    system connection

    information.

    Deletion

    Disregard errors.

    Start forced defrosting.

    90 min.

    SW3-2 Function valid

    All indoor units test

    operation ON.

    3C

    15C

    Valid

    53C

    Model 250

    Before power is turned on.

    During normal operation when power

    is on.

    Should be set on OFF.

    Before power is turned on.

    Before power is turned on.

    During normal operation when power

    is on.

    During normal operation when power

    is on.

    During normal operation when power

    is on. (Except during defrosting)

    During normal operation when power

    is on.

    When SW3-1 is ON after power is

    turned on.

    During normal operation when power

    is on.

    During normal operation when power

    is on. (Except during defrosting)

    During compressor stop when poweris on.

    During normal operation when power

    is on.

    When switching on the power.

    During normal

    operation when

    power is on.

    10 minutes or

    more after

    compressor

    starts.

    Note:

    SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.

    If the address is set from 01 to 50, it automatically becomes 100.

  • 7/25/2019 dieu hoa ADMIN.pdf

    45/166

    44

    4PURY-P200250YMF-C

    Switch FunctionFunction according to switch operation Switch set timing

    When off When on When off When onSWU

    SW1

    SW2

    SW3

    SW4

    1~2

    1~8

    9~10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    Unit address setting

    For self diagnosis/

    operation monitoring

    Centralized control switch

    Deletion of connection

    information.

    Deletion of error history.

    Disregard ambient air

    sensor errors, liquid

    overflow errors.

    Forced defrosting

    Defrost prohibited timer

    SW3-2 Function valid/

    invalid

    Indoor Unit Test operation

    Defrosting start tempera-

    ture of TH7.

    Defrosting end tempera-

    ture of TH5.

    Pomp down operation

    Target Tc (High pressure)

    at Heating

    Models

    SW4-2 function valid/

    Invalid

    Configuration compensa-

    tion value

    Set on 51~100 with the dial switch.

    LED monitering display

    Centralized control not

    connected.

    Storing of refrigeration

    system connection

    information.

    Errors valid.

    Ordinary control

    43 min.

    SW3-2 Function invalid

    Stop all indoor units.

    8C

    8C

    Invalid

    49C

    Model P200

    Invalid

    Centralized control

    connected.

    Deletion of refrigeration

    system connection

    information.

    Deletion

    Disregard errors.

    Start forced defrosting.

    90 min.

    SW3-2 Function valid

    All indoor units test

    operation ON.

    5C

    15C

    Valid

    53C

    Model P250

    Valid

    Before power is turned on.

    During normal operation when power

    is on.

    Should be set on OFF.

    Before power is turned on.

    Before power is turned on.

    During normal operation when power

    is on.

    During normal operation when power

    is on.

    During normal operation when power

    is on. (Except during defrosting)

    During normal operation when power

    is on.

    When SW3-1 is ON after power is

    turned on.

    During normal operation when power

    is on.

    During normal operation when power

    is on. (Except during defrosting)

    During compressor stop when poweris on.

    During normal operation when power

    is on.

    When switching on the power.

    During normal operation when power

    is on.

    when SW4-1 in ON.

    During normal

    operation when

    power is on.

    10 minutes or

    more after

    compressor

    starts.

    Note:

    SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.

    If the address is set from 01 to 50, it automatically becomes 100.

    Changes as shown below by on off change

    0% 3% 6% 9% 12% 6% 3% 0%

  • 7/25/2019 dieu hoa ADMIN.pdf

    46/166

    45

    (2) Indoor unit

    DIP SW1, 3

    Model P71 P80 P100 P125 P140 P200 P250

    Capacity (model name) code 14 16 20 25 28 40 50

    SW2 setting

    Model P20 P25 P32 P40 P50 P63

    Capacity (model name) code 4 5 6 8 10 13

    SW2 setting ONOFFON

    OFFON

    OFF

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the

    table below.)

    Note 2: The DipSW setting is only effective during unit stopping (remote controller OFF) for SW1, 2, 3 and 4 commonly

    and the power source is not required to reset.)

    3: When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.

    Setting of DIP SW2

    Model

    Switch

    SW1

    SW3

    3

    6

    7

    3

    4

    6

    8

    PLFY-P

    VBM-A

    OFF

    OFF

    VLMD-A VKM-A

    OFF

    ON

    ON

    ON

    OFF

    OFF

    ON

    ON

    PEFY-P

    VML-A VMH-A 20~80VMM-A 100~140VMM-A

    OFFOFF ON

    OFF ON

    ON

    ON

    OFF

    OFF

    OFF

    OFF ON OFF

    ON OFF ON

    ON

    OFF

    PDFY-P PFFY-P PCFY-P PKFY-P

    VM-A

    ON

    VLRM-A, VLEM-A

    OFF

    VGM-A

    ON

    VAM-A VGM-A

    OFF

    OFF

    Indoor unit inlet

    None

    100h

    Ineffective

    Fan output display

    At stationary heating

    Very low speed

    SW1-7 setting

    Ineffective

    Ineffective

    Heat pump

    None

    None

    None

    1st setting

    Down blow B, C

    Effective

    Built in remote controller

    Provided

    2500h

    Effective

    Thermo. ON signal display

    Always at heat.

    Low speed

    Set airflow

    Effective

    Effective

    Cool.only

    Provided

    Provided

    Provided

    2nd setting

    Horizontal

    Ineffective

    Room temp. sensor position

    Clogged filter detect.

    Filter duration

    OA intake

    Remote display select.

    Humidifier control

    Heating thermo. OFF airflow

    Heating thermo. OFF airflow

    Power failure automatic

    return

    Power source start/stop

    Model selection

    Louver

    Vane

    Vane swing function

    Vane horizontal angle

    Vane angle set for cooling

    Heating 4deg up

    Always ineffective for PKFY-P.VAM

    Not provided for PKFY-P.VAMProvided for PLFY-P.VGM (ON) setting

    Always down blow B,C for PKFY-P.VAM

    Horizontal (ON) setting for PLFY-P.VLMD

    Ineffective (ON) setting for floorstanding

    SW1

    SW3

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    Switch SW nameOperation by SW Switch set timing

    OFF ON OFF ONRemarks

    At unit stopping(at remote

    controller OFF)

    Cooling capacity saving

    for PKFY-P. VAM,effective/ineffective

  • 7/25/2019 dieu hoa ADMIN.pdf

    47/166

    46

    Ceiling height

    3 3.5 m

    2 2.8 m

    1 2.3 m

    Setting of DIP SW4 Setting of DIP SW5

    1 2 3 4

    ON OFF ON OFF

    ON OFF ON OFF

    OFF OFF OFF ONON OFF OFF ON

    OFF ON OFF ON

    OFF OFF ON ON

    ON ON OFF OFF

    OFF OFF OFF

    ON ON ON

    OFF OFF OFF

    ON OFF OFF

    OFF OFF ON

    ON ON ON OFF

    PMFY-P-VBM-A

    PLFY-P-VLMD-A

    PDFY-P20 ~ 80VM-A

    PLFY-P40 ~ 63VKM-APLFY-P80 ~ 125VKM-A

    PCFY-P-VGM-A

    PKFY-P-VGM-A

    PKFY-P-VAM-A

    PEFY-P20 ~ 80VMM-A

    PFFY-P-VLEM-A, P-VLRM-A

    PEFY-P20 ~ 32VML-A

    PEFY-P40 ~ 140VMH-A

    PEHY-P200250VMH-A

    PDFY-P100125VM-A

    PEFY-P100 ~ 140VMM-A

    Model Circuit board usedSW4

    Switch Function Operation by switch Switch set timing

    SWA

    SWA

    SWA

    SWB

    SWC

    Ceiling height setting

    External static

    pressure setting

    For options

    Setting of air outlet opening

    Airflow control

    (PLFY-P-VKM-A) (PCFY-P-VGM-A)

    (PLFY-P-VLMD-A)

    (PLFY-P-VKM-A)

    (PLFY-P-VKM-A, PCFY-P-VGM-A, PKFY-P-VGM-A, PDFY-P-VM-A)

    Phase control

    Relay selection

    *The ceilingheight ischanged bySWB setting.

    *As this switch is used by interlocking with SWC,refer to the item of SWC for detail.

    SWASWB 1 2 3

    2-way 3.5 m 3.8 m 3.8 m

    3-way 3.0 m 3.3 m 3.5 m

    4-way 2.7 m 3.0 m 3.5 m

    * Set to the option to install the high efficiencyfilter

    Always after powering

    Always after powering

    Always after powering

    Always after powering

    Always after powering

    3

    1

    2

    2-way

    4-way

    3-way

    3

    1

    2

    3

    1

    2

    3

    1

    2

    220V

    240V

    Option

    Standard

    (PDFY-P20 ~ 80VM-A, PEFY-P20 ~ 80VMM-A)

    100Pa

    50Pa

    30Pa* For other models, change the setting of static pressure by replacing the connector.

  • 7/25/2019 dieu hoa ADMIN.pdf

    48/166

    47

    33333 TEST RUN

    [1] Before Test Run(1) Check points before test run

    1 Neither refrigerant leak nor loose power source/ transmission lines should be found.

    2 Confirm that the resistance between the power source terminal block and the ground exceeds 2Mby measur-

    ing it with a DC500V megger. Do not run if it is lower than 2M.

    Note) Never apply the megger to the MAIN board. If applied, the MAIN board will be broken.

    3 Confirm that the Ball valve at both gas and liquid sides is being fully opened.

    Note) Certainly close the cap.

    4 Be sure that the crankcase heater has been powered by turning the main power source on at least 12 hours

    before starting the test run. The shorter powering time causes compressor trouble.

    (2) Caution at inverter check

    Because the inverter power portion in outdoor unit electrical part box have a lot of high voltage portion, be sure to follow

    the instructions shown below.

    During energizing power source, never touch inverter power portion because high voltage (approx. 580V) is

    applied to inverter power portion.

    When checking,

    Shut off main power source, and check it with tester, etc.

    Allow 10 minutes after shutting off main power source.

    Open the MAIN board mounting panel, and check whether voltage of both ends of electrolytic capacitor is

    20V or less.

    1

    2

    1

    2

    3

  • 7/25/2019 dieu hoa ADMIN.pdf

    49/166

    48

    (3) Check points for test run when mounting options

    (4) Attention for mounting drain water lifting-up mechanism

    Check point

    Local remote controller displays codeNo. 2503, and the mechanism stops.

    No overflow from drain pan.

    Drain water comes out by operations ofdrain pump.

    Sound of pump operations is heard, anddrain water comes out.

    No water leak from connecting portionsof each water piping.

    Water is supplied to water supply tank,and float switch is operating.

    Built-in optional parts

    Mounting of drainwater lifting-upmechanism

    Mounting of perme-able film humidifier

    Content of test run

    Release connector of pump circuit,check error detection by pouringwater into drain pan water inlet.

    After that, connect connector ofcircuit.

    Check pump operations and drain-age status in cooling (test run) mode.

    Check humidifier operations and watersupply status in heating (test run) mode.

    1

    2

    3

    4

    5

    Result

    1

    2

    3

    Work

    Disassembling andassembling of drainwater lifting-upmechanism

    Mounting of floatswitch

    Electric wiring

    Float switch moves smoothly.

    Float switch is mounted onmounting board straightly withoutdeformation.

    Float switch does not contact withcopper pipe.

    Wiring procedure is exactly followed.

    Connector portion is tightly hooked.

    Content of test run

    Lead wire from control box notdamaged.

    Rubber cap properly inserted todrain water outlet of drain pan?

    Insulation pipe of gas and liquidpipes dealt with as shown in the rightfigure?

    Drain pan and piping cover mountedwithout gap?

    Drain pan hooked on cut projectionof the mechanism?

    Float switch installed without contactingwith drain pan?

    No mistakes in wiring?

    Connectors connected surely andtightly?

    No tension on lead wire when slidingcontrol box?

    1

    2

    3

    1

    2

    3

    Check point Result

    Insulation pipe

    No gap

  • 7/25/2019 dieu hoa ADMIN.pdf

    50/166

  • 7/25/2019 dieu hoa ADMIN.pdf

    51/166

    50

    Classification

    Transmissionline

    Portion Check item

    1 Limitation of transmission line length followed? Forexample, 200m or less (total length : 500m) at the farthest.

    2 1.25mm2or more transmission line used?(Remote controller 10m or less 0.75mm2)

    3 2-core cable used for transmission line?

    4 Transmission line apart from power source line by 5cm or more?

    5 One refrigerant system per transmission line?

    6 The short circuit connector is changed form CN41 toCN40 on the MAIN board when the system is centralized

    control? (Just one outdoor unit. Not all outdoor units.)

    7 No connection trouble in transmission line?

    8 Connection of wrong remote controller line terminals? MA Remote controller : TB15 M-NET Remote controller : TB5

    Trouble

    Erroneous operation, error stop.

    Erroneous operation, error stop.

    Error stop in case multiple-core

    cable is used.

    Erroneous operation, error stop.

    Not operate.

    Not operate.

    Error stop or not operate.

    Never finish the initial mode.

    System set

    Before starting

    Error stop or not operate.

    Can not be properly set with power

    source turned on.

    Not operate.

    Set temperature not obtained atheating operations (Thermostat

    stop is difficult)

    Error stop.

    Error stop, compressor trouble.

    1

    2

    1

    2

    3

    4

    Address setting properly done? (M-NET Remotecontroller, indoor unit and outdoor unit.)

    Setting of address No. done when shutting off power

    source?

    Address numbers not duplicated?

    Turned on SW3-8 on indoor unit circuit board whenmounting room thermistor sensor?

    Refrigerant piping ball valve (Liquid pressure pipe, gaspressure pipe) opened?

    Turn on power source 12 hours before starting operations?

    STANDBYDEFROST ERRORCODE

    D A I L YAUTOOFF

    CENTRALLYCONTROLLED

    CLOCKREMAINDER

    O NO F FC

    1Hr.

    NOT AVAILABLEC

    CHECKMODE

    FILTERCHECK

    TESTRUN

    LIMITTEMP.

    ON/OFFTEMP

    FILTER

    CHECKTEST

    O N O FFCLOCK

    PAR-F27MEATIMERSET

    2 31

    STANDBYDEFROST ERRORCODE

    D A I L YAUTOOFF

    CENTRALLYCONTROLLED

    CLOCK

    REMAINDER

    O NO F F C

    1Hr.

    NOT AVAILABLEC

    CHECKMODE

    FILTERCHECK

    TESTRUN

    LIMITTEMP.

    ON/OFFTEMP

    FILTER

    CHECKTEST

    O N O FFCLOCK

    PAR-F27MEATIMERSET

  • 7/25/2019 dieu hoa ADMIN.pdf

    52/166

    51

    [2] Test Run Method

    Operation procedure

    1Turn on universal power supply at least 12 hours before getting started Displaying HOon display panel for

    about two minutes

    2 Press TEST RUN button twiceDisplaying TEST RUNon display panel

    3 Press selection buttonMake sure that air is blowing out

    4Press select button to change from cooling to heating operation, and vice versaMake sure that

    warm or cold air is blowing out

    5 Press adjust buttonMake sure that air blow is changed

    6 Press or button to change windMake sure that horizontal or downward blow is adjustable.

    7 Make sure that indoor unit fans operate normally

    8 Make sure that interlocking devices such as ventilator operate normally if any

    9 Press ON/OFF button to cancel test run Stop operation

    Note 1: If check code is displayed on remote controller or remote controller does not operate normally.

    2: Test run automatically stops operating after two hours by activation of timer set to two hours.

    3: During test run, test run remaining time is displayed on time display section.

    4: During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temperature

    display section.5: When pressing adjust button, depending on the model, NOT AVAILABLEmay be displayed on remote

    controller. However, it is not a malfunction.

    6: When pressing or button, depending on the model, NOT AVAILABLEmay be displayed on

    remote controller. However, it is not a malfunction.

  • 7/25/2019 dieu hoa ADMIN.pdf

    53/166

    52

    4 GROUPING REGISTRATION OF INDOOR UNITS WITH M-NET REMOTE CONTROLLER

    (1) Switch function

    The switch operation to register with the remote controller is shown below:

    Registration/ordinary modeselector switch

    Registration/ordinarymode selection switch

    Switch to assign indoorunit address

    Registration switch

    Confirmation switch

    Delete switch

    Registered modeselector switch

    Switch to assigninterlocked unit address

    A+B

    C

    D

    E

    F

    G

    H

    This switch selects the ordinary mode or registered mode (ordinary

    mode represents that to operate indoor units).

    * To select the registered mode, press the FILTER +

    switch continuously for over 2 seconds under stopping state.

    [Note] The registered mode can not be obtained for a while after

    powering.

    Pressing the FILTER + switch displays CENTRALLY

    CONTROLLED.

    This switch assigns the unit address for INDOOR UNIT ADDRESS

    NO.

    This switch is used for group/interlocked registration.

    This switch is used to retr ieve/identify the content of group and inter-

    locked (connection information) registered.

    This switch is used to retr ieve/identify the content of group and inter-

    locked (connection information) registered.

    This switch selects the case to register indoor units as group (group

    setting mode) or that as interlocked (interlocked setting mode).

    *The unit address is shown at one spot for the group setting modewhile at two spots for the interlocked setting mode.

    This switch assigns the unit address of OA UNIT ADDRESS NO.

    Symbolof switch

    G Registered mode

    selector switch

    E Confirmation switch

    C Switch to assign

    indoor unit address

    H Switch to assign inter-

    locked unit address

    D Registration switch

    A

    +FILTER

    TEST RUN

    Name Name of actual switch Description

    of TEMP

    of TIMER SET

    CLOCKON OFF

    B

    Registration/ordinary modeselector switch

    STAND BYDEFROST ERROR CODE

    D A I L YAUTO OFF

    CENTRALLY CONTROLLED

    CLOCK

    REMAINDER

    ON OFF C

    1Hr

    NOT AVAILABLEC

    CHECK MODE

    FILTERCHECK

    TEST RUN

    LIMIT TEMP.

    ON/OFFTEMP

    FILTER

    CHECK TEST

    ON OFFCLOCK

    PAR-F27MEATIMER SET

    F Delete switch

  • 7/25/2019 dieu hoa ADMIN.pdf

    54/166

    53

    (2) Attribute display of unit

    At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the

    unit is displayed with two English characters.

    Display Type (Attribute) of unit/controller

    Indoor unit connectable to remote controller

    Outdoor unit

    Local remote controller

    System controller (MJ)

    [Description of registration/deletion/retrieval]

    The items of operation to be performed by the remote controller are given below. Please see the relating paragraph for

    detail.

    1Group registration of indoor unit

    The group of the indoor units and operating remote controller is registered.

    It is usually used for the group operation of indoor units with different refrigerant system.

    2Retrieval/identification of group registration information of indoor units

    The address of the registered indoor units in group is retrieved (identified).

    3Retrieval/identification of registration information

    The connection information of any unit (indoor/outdoor units, remote controller or the like) is retrieved (identified).

    4Deletion of group registration information of indoor units

    The registration of the indoor units under group registration is released (deleted).

    5Deletion of the address not existing

    This operation is to be conducted when 6607error (No ACK error) is displayed on the remote controller caused by

    the miss setting at test run, or due to the old memory remained at the alteration/modification of the group composi-

    tion.

    Caution:

    When MELANS (MJ-103MTRA for example) is being connected, do not conduct the group/pair registration using

    the remote controller. The group/pair registration should be conducted by MELANS. (For detail, refer to the instruc-

    tion exclusively prepared for MELANS.)

  • 7/25/2019 dieu hoa ADMIN.pdf

    55/166

    54

    (3) Group registration of indoor unit

    1) Registration method

    Group registration of indoor unit ........................................................................ 1

    The indoor unit to be controlled by a remote controller is registered on the remote controller.

    [Registration procedure]

    1 With the remote controller under stopping or at the display of HO, continuously press the FILTER + switch

    (A+B) at the same time for 2 seconds to change to the registration mode. (See the figure below.)

    2 Assign the indoor unit address to INDOOR UNIT ADDRESS NO.by operating the (Room temperature

    adjustment) (C).

    Then press the TEST RUN switch (D) to register. In the figure below, the INDOOR UNIT ADDRESS NO.is being set

    to 001.

    3 After completing the registration, press the FILTER + switch (A+ B) at the same time for 2 seconds to

    change to the original ordinary mode (with the remote controller under stopping).

    Remote controller under stopping HOunder displaying

    Ordinary mode

    INDOOR UNITADDRESS NO

    ERROR CODEOAUNITADDRESSNO

    CINDOOR UNITADDRESS NO

    ERROR CODEOAUNITADDRESSNO

    C

    ERROR CODEOAUNITADDRESSNO

    C

    1 1

    Group setting mode

    Confirm the indoor unit address No.

    Confirm the connection of the transmission line.

    ERROR CODEOAUNITADDRESSNO

    C

    ERROR CODEOAUNITADDRESSNO

    C

    Registration complete

    Registration error

    Indicates the type of unit(Indoor unit in this case)

    88flickers indicating registra-tion error. (when the indoor unitregistered is not existing)

    2 Assign theaddress (C)

    1 Change to theregistrationmode (A+B)

    3 Press theregistrationswitch (D)

    Remote controller

    System example

    Indoor units

    Group

    2+3

    ON/OFFTEMP

    FILTER

    CHECK TEST

    O N O F FCLOCK

    PAR-F27MEATIMER SET

  • 7/25/2019 dieu hoa ADMIN.pdf

    56/166

    55

    2) Method of retrieval/confirmation

    Retrieval/confirmation of group registration information on indoor unit ............... 2

    The address of the indoor unit being registered on the remote controller is displayed.

    [Operation procedure]

    1With the remote controller under stopping or at the display of HO, continuously press the FILTER + switch (A

    +B) at the same time for 2 seconds to change to the registration mode.

    2 In order to confirm the indoor unit address already registered, press switch (E). (See figure below.) When the group

    of plural sets is registered, the addresses will be displayed in order at each pressing of switch (E).

    3 After completing the registration, continuously press the FILTER + switch (A+ B) at the same time for 2

    seconds to change to the original ordinary mode (with the remote controller under stopping).

    Retrieval/confirmation of registration information ................................................3

    The registered information on a certain unit (indoor unit, outdoor unit, remote controller or the like) is displayed.

    [Operation procedure]

    1With the remote controller under stopping or at the display of HO, continuously press the FILTER + switch (A

    +B) at the same time for 2 seconds to change to the registration mode.

    2 Operate switch (G) for the interlocked setting mode. (See figure below.)

    3 Assign the unit address of which registration information is desired to confirm with the (TIMER SET) switch

    (H). Then press the switch (E) to display it on the remote controller. (See figure below.)

    Each pressing of switch (E) changes the display of registered content. (See figure below.)

    4 After completing the retrieval/confirmation, continuously press the FILTER + switch (A+B) at the same timefor 2 seconds to change to the original ordinary mode (with the remote controller under stopping).

    Registered

    No registration.

    ERROR CODEOAUNITADDRESSNO

    C

    ERROR CODEOAUNITADDRESSNO

    C

    1 Press the switch for confirmation (E)

    Note: Only one address will be displayedwhen the registration is one even theswitch is how often pressed

    Indicates the type of unit(Indoor unit in this case)1

    1ON/OFFTEMP

    FILTER

    CHECK TEST

    O N O F FCLOCK

    PAR-F27MEATIMER SET

  • 7/25/2019 dieu hoa ADMIN.pdf

    57/166

    56

    3) Method of deletion

    Deletion of group registration information of indoor unit ......................................4

    [Operation procedure]

    1With the remote controller under stopping or at the disp