Digital Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS Flexible Communication Options For Wired or Wireless Networks RS-232, RS 485, & Serial Fiber Optic (ST or V-Pin) Ethernet Over Copper RJ-45 @ 10/100 Base-T Ethernet Over Fiber Optic (ST or V-Pin) 100 Base-FX Embedded Bluetooth, Class 1 (v2.0), 128 bit encryption, up to 1/2 mile transmission (with appropriate antenna) Supports DNP3.0 & MODBUS ® Protocols Time sync via DNP3.0 Set Time Command DNP mapping templates to match SCADA historical databases Sequence of Events (SOE) Recording Of Events - Stores 160 events, ms time-stamped with Graphic Logic Initiate from critical operational factors FULL DNP implementation – Including DNP File Transfer, multi- addressing, unsolicited response, source address validation TRUE Ethernet – Full 10/100Mbps auto-negotiable concurrent multi-session and multi-protocol support DNP+Ethernet – Send/receive DNP configuration files using DNP File Transfer Protocol Device Discovery using CapTalk DNP SCADA Heartbeat – Integrity check of communications media and/or Master. Fully programmable Quick (10 -15 second) Uploading of Configurations, Settings, Firmware Upgrades Assists in locating harmonics adversely affecting customer processes Helps mitigation measures to determine corrective filter design and location Control Cabinet – Direct Pole-Mount with Meter Socket Plug. Mount the control away from the meter socket and away from power lines and other equipment Oscillography Capture – Selectable 16, 32, or 64 samples per cycle. Captures sags, swells, CBEMA events and sub-synchronous transients Cyber Security – Authentication and Multi Level Access Codes, Smart Flash SD Card serves as Cyber Security Hard-Key with Audit Log Data Logging Continuous Recording – Data stored in non-volatile memory requiring no battery backup CBEMA Excursion Recording and Reporting Harmonics Detection, Recording, Protection and Suppression Downloading of Event Reports, Oscillography No need for battery to back up clock Smart Flash SD Card Slot Supports Control Cloning
Transcript
Page 1: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

Digital Capacitor BankControl M-62833 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection

CONTROLS

• Flexible Communication Options For Wired or Wireless Networks

•RS-232, RS 485, & Serial Fiber Optic (ST or V-Pin)

•Ethernet Over Copper RJ-45 @ 10/100 Base-T

•Ethernet Over Fiber Optic (ST or V-Pin) 100 Base-FX

•Embedded Bluetooth, Class 1 (v2.0), 128 bit encryption, up to 1/2 mile transmission (with appropriate antenna)

•Supports DNP3.0 & MODBUS® Protocols

• Time sync via DNP3.0 Set Time Command

•DNP mapping templates to match SCADA historical databases

•Sequence of Events (SOE) Recording Of Events - Stores 160 events, ms time-stamped with Graphic Logic Initiate from critical operational factors

• FULL DNP implementation – Including DNP File Transfer, multi-addressing, unsolicited response, source address validation

• TRUE Ethernet – Full 10/100Mbps auto-negotiable concurrent multi-session and multi-protocol support

•DNP+Ethernet – Send/receive DNP configuration files using DNP File Transfer Protocol

•Device Discovery using CapTalk

•DNP SCADA Heartbeat – Integrity check of communications media and/or Master. Fully programmable

•Quick (10 -15 second) Uploading of Configurations, Settings, Firmware Upgrades

•Assists in locating harmonics adversely affecting customer processes

•Helps mitigation measures to determine corrective filter design and location

•Control Cabinet – Direct Pole-Mount with Meter Socket Plug. Mount the control away from the meter socket and away from power lines and other equipment

•Oscillography Capture – Selectable 16, 32, or 64 samples per cycle. Captures sags, swells, CBEMA events and sub-synchronous transients

•Cyber Security – Authentication and Multi Level Access Codes, Smart Flash SD Card serves as Cyber Security Hard-Key with Audit Log

•Data Logging Continuous Recording – Data stored in non-volatile memory requiring no battery backup

•CBEMA Excursion Recording and Reporting

•Harmonics Detection, Recording, Protection and Suppression

•Downloading of Event Reports, Oscillography

•No need for battery to back up clock

•Smart Flash SD Card Slot

•Supports Control Cloning

Page 2: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–2–

M-6283 Digital Capacitor Bank Control

Standard Features • Three-phasesensing,onephaseoperation

-selectableregulation;operationbasedonindividualoraverageofthethreephases

• Fourcontrolmodesofoperation:

–ClassicAutomatic(Voltage,optional

VArControloroptionalCurrentControl)

–AutoAdaptivemode(FixedorAveraging)

–Remote

–Manual

• Twooverridemodesofoperation:

–Temperature

–Time

• TimeDelay–DefiniteandInverse

• Adjustable Maximum/Minimum VoltageLimits

• NeutralUnbalancecurrentdetection

–Bank/SwitchFailed

–BankClosed

–BankOpen

–Supports200mAinputtocontrol

• User selectable Overvoltage limit/Undervoltage limit and time delay forremotecontrolsupervision

• AdjustablewarningtimersforClose/Open/Re-close

• Adjustable Close/Open output pulseduration

• Real-Time Metering of measured andcalculatedparameters

• VTRatioCorrection,VT andCT (PhaseandNeutral)Multiplier

• OperationsCounter

• ResettableOperationsCounterwithAlarm

• HarmonicAnalysisofVoltageandCurrentSignals,uptothe31stplusTHD

• DataLogging

• Remote/Auto-LocalManualswitch

• Outputs:Close,OpenandAlarm

• 20 Character by 2 Row LCD display(LEDbacklit)

• Upto30unique15characterUserAccessCodes(Level1orLevel2)

• CBEMA monitoring to detect sags andswells and trigger data collection andalarmingfunctions

• SmartFlashSDCardSlotsupportingSDandSDHCSDcards

• SmartFlashSDCardcanbelinkedtooneor multiple controls providing a physicalsecurity"Key"whichprovidesUserAccessLevel2AccesstothecontrolwhentheSDCardisinsertedforsettingsmanipulation

• SequenceofEvents(SOE)recorder

• DeviceDiscovery

• SourceAddressValidation

• Oscillography

• FrontPanelLEDsforRemote/Auto,LocalManual,Alarm,Close,Open,OK,RSSI,Neutral Unbalance, (TX) Transmit and(RX)Receive

• ProgrammableAlarms

• Front Panel Hot Buttons provide directaccesstomenuheaders

• FrontPaneltesting:

–Int/ExtVoltageSourceswitch

–ExternalPowerinputterminals

–MeterOutterminals

• Communication Protocols DNP3.0 andMODBUS®

• Adaptive Delta Voltage sensing duringswitchoperations

• DailyOperationsCounterLimit

• CapTalk® S-6283 CommunicationsSoftware

• Capacitor Bank switch status inputs forphaseA,BandC

• Graphical display of real-time harmonicspectrum of voltage and current usingCapTalkCommunicationsSoftware

• CommunicationPorts:

–USB

–RS-232

All brand or product names appearing in this document are the trademark or registered trademark of their respective holders.

Page 3: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–3–

M-6283 Digital Capacitor Bank Control

Standard Features (Cont’d) • SCADA"HeartBeat"(withDNP3.0only)

• Supports Station and Feeder LevelDNP addressing in addition to individualaddressingforSmartGridapplications

• OnepushbuttonaccesstouserconfigurableWakeupscreenformanualdatarecordingwithSmartFlashSDCardsavingfeature

• Oneset(3)ofsparefusesareincluded

• CapacitorBankSwitchselection"SolenoidDriven"or"MotorDriven"forClose/OpenPulseDuration

• 200mANeutralCurrent inputforNeutralUnbalancedetection

• SCADATestMode

Optional Control Features • Automatic VAr Control Mode options

include:

–0to10VLinePostSensorinput

• Local Wireless Bluetooth® capability.Class1TypeBluetoothUSBAdapterthatsupportswirelesstransmissionupto300meters.

• EthernetPort(10/100Base-T)isavailablethrough a RJ-45 jack or Fiber Optic STConnector.This port supportsDNP overTCP/IPandUDP;MODBUSoverTCP/IP.

• 5 A Neutral Current input for NeutralUnbalancedetection

• LinePostCurrentSensorinputforNeutralUnbalancedetection(suppliesbothvoltageorcurrentunbalancedetection)

• CommunicationsPorts:

–STFiberOptic

–V-pinFiberOptic

–RS-485

• TheM-6283 can be housed in a NEMA4 Molded Lexan®, Cold Rolled Steel orStainless Steel Control cabinet. (SeeM-2980A section of this specification fordetailedinformation).

Page 4: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–4–

M-6283 Digital Capacitor Bank Control

CAPACITOR BANK CONTROL OPERATIONControl ParameterDependingonthecontrolmodeofoperation, thecontrolparametercanbeeithervoltage,VArsorcurrent.ForexamplethecontrolVoltageisthemeasurementusedinthecontrolalgorithmtomaketheloadvoltageregulationdecision.Thecontrolparametershallbeuserselectable.

Thethreeuserselectableuseroptionsshallbe:

• SinglePhaseSelection

• ThreePhaseAverage/Total

• Maximum/MinimumofThreePhase–(Future)

Single Phase SelectionThisoptionwillallowtheusertochoosewhichphaseA,BorCisusedasthecontrollingparameter.Oncethisisselected,thecontrolwillusethatphasevalueinClassicvoltagecontrolmodeorAutoAdaptivemodetomakedecisiononhowtoregulatetheloadvoltage.TheoptionisvalidforallthreemethodsofcontrolnamelyVoltage,VArsandCurrent.

Three Phase Average/TotalThisoptionwillaveragethevalueofallthreephasequantitiesandthisaveragewillbeusedtomakethecontroldecision.TheoptionisvalidforallthreemethodsofcontrolVoltage,VArsandCurrent.ItisimportanttonotethatwheninthecontrolisusingVArControl,theaveragingisreplacedbythetotalsumoftheVArsofallthreephases.

InadditionwhentheoptionisselectedtheCTMultiplier isassumedtobeequal.InControlModeLimitsthemaximumandminimumofthe3phasesisusedtoevaluatewhetherthevoltageisviolatingtheuserassignedlimits.

Control Modes of OperationThecontrolincludestwostandardmodesofAutomaticVoltageControl(ClassicVoltageControlandAutoAdaptiveVoltageControl),OptionalVAr ControlmodeandCurrent Controlmodeareavailable.

Classic Voltage Control Mode:The controlwillmake itsOpenandClose switching decisions basedonmeasuredLineVoltageconditionsandTimeand/orTemperatureoverrideswhenapplied.Voltageexcursionsbeyondthesetvalueforgreaterdurationthanthetimedelaywillresultinappropriatecontroloperation.

– Control Open Voltage:Adjustablefrom95.0to140.0Vin0.1Vincrements

– Control Close Voltage: Adjustablefrom95.0to140.0Vin0.1Vincrements

– Close and Open Time Delays:DefiniteorInverse;adjustablefrom0secondsto600seconds,in1secondincrements.Timerresetcanbeselectedasinstantaneousorintegrating.

– Time Override:IntheAutoControlModeaTimeOverridecanbeappliedtocapacitorbankOpenandCloseoperations.TheTimeOverridefeatureconsidersStartDate,StartTime,Duration,RecurrencePatternandaRangeOfOccurrencestoimplementtheoverride.

– Temperature Override: In the Auto Control Mode a Temperature Override can be applied tocapacitorbankOpenandCloseoperations.TheTemperatureOverride featureconsiderssensedambienttemperatureandimplementsoverrideaction(Open,CloseorNone)foreitheraboveorbelowtemperaturesetpointconditions.

NOTE: TimeandTemperatureOverridescanbeoverriddenbyControlModeLimits.

Page 5: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–5–

M-6283 Digital Capacitor Bank Control

Auto Adaptive Voltage Control Mode:Thisfeaturecontainstwocontrolmethods,FixedorAverage.TheFixedmethodprovidesaBandcentersettingthecontrolcomparestomeasurevoltagetoopenorclosetheCapacitorbank.TheAveragemethodusesanEffectiveBandcenterbasedonalongtermaverageoftheinputvoltagetocomparetomeasurevoltagetoopenorclosethecapacitorbank.BothmethodsemployaninversetimerandBandwidthtooptimizebankoperationandeliminateunnecessaryswitching.Also,Timeand/orTemperatureoverridescanbeapplied.

– Fixed-Band Center:Adjustablefrom100.0to135.0Vin0.1increments

– Bandwidth (Multiple of Delta V): Adjustablefrom1.0to2.0in0.1increments

– Close and Open Time Delays: Inverse only; adjustable from60 to 3600 seconds, in 1 secondincrements.Timerresetisfixedasintegrating.

– Time Override:IntheAutoControlModeaTimeOverridecanbeappliedtocapacitorbankOpenandCloseoperations.TheTimeOverridefeatureconsidersStartDate,StartTime,Duration,RecurrencePatternandaRangeOfOccurrencestoimplementtheoverride.

– Temperature Override: In the Auto Control Mode a Temperature Override can be applied tocapacitorbankOpenandCloseoperations.TheTemperatureOverride featureconsiderssensedambienttemperatureandimplementsoverrideaction(Open,CloseorNone)foreitheraboveorbelowtemperaturesetpointconditions.

NOTE: TimeandTemperatureOverridescanbeoverriddenbyControlModeLimits.

Automatic VAr Control Mode Option*:ThecontrolwillmakeitsOpenandCloseswitchingdecisionsbasedonmeasuredlineVArconditionsandTimeand/orTemperatureoverrideswhenapplied.VArexcursionsbeyondthesetvalueforgreaterdurationthanthetimedelaywillresultinappropriatecontroloperation.Thecontrolcanbeorderedwitheithera5ACTorLinePostCurrentSensorinputstoprovidephasecurrentmeasurementtothecontrol.

– Control Open VArs:–100%to100%ofsingle-phasecapacitorBanksizein1%increments

– Control Close VArs: 0%to100%ofsingle-phasecapacitorBanksizein1%increments

– Close and Open Time Delays:Definite or Inverse; adjustable from0 seconds to 600 seconds,in1secondincrements.Timerresetcanbeselectedasinstantaneousorintegrating.

– Time Override:IntheAutoControlModeaTimeOverridecanbeappliedtocapacitorbankOpenandCloseoperations.TheTimeOverridefeatureconsidersStartDate,StartTime,Duration,RecurrencePatternandaRangeOfOccurrencestoimplementtheoverride.

– Temperature Override: In the Auto Control Mode a Temperature Override can be applied tocapacitorbankOpenandCloseoperations.TheTemperatureOverride featureconsiderssensedambienttemperatureandimplementsoverrideaction(Open,CloseorNone)foreitheraboveorbelowtemperaturesetpointconditions.

NOTE: TimeandTemperatureOverridescanbeoverriddenbyControlModeLimits.

*OnlyavailablewithVArandCurrentControlModeoption.

Page 6: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–6–

M-6283 Digital Capacitor Bank Control

Automatic Current Control Mode Option*:ThecontrolwillmakeitsswitchingdecisionsbasedonmeasuredLineCurrentconditionsandTimeand/orTemperatureoverrideswhenapplied.Currentexcursionsbeyondthesetvalueforgreaterdurationthatthetimedelaywillresultinappropriatecontroloperation.Thecontrolcanbeorderedwitheither5ACTorLinePostSensorinputstoprovidephasecurrentmeasurementtothecontrol.

– Control Open Current:Adjustablefrom10to600Amps

– Control Close Current: Adjustablefrom10to600Amps

– Close and Open Time Delays:Definite or Inverse; adjustable from0 seconds to 600 seconds,in1secondincrements.Timerresetcanbeselectedasinstantaneousorintegrating.

– Time Override:IntheAutoControlModeaTimeOverridecanbeappliedtocapacitorbankOpenandCloseoperations.TheTimeOverridefeatureconsidersStartDate,StartTime,Duration,RecurrencePatternandaRangeOfOccurrencestoimplementtheoverride.

– Temperature Override: In the Auto Control Mode a Temperature Override can be applied tocapacitorbankOpenandCloseoperations.TheTemperatureOverride featureconsiderssensedambienttemperatureandimplementsoverrideaction(Open,CloseorNone)foreitheraboveorbelowtemperaturesetpointconditions.

NOTE: TimeandTemperatureOverridescanbeoverriddenbyControlModeLimits.

Remote Control Mode: Inthismode,thecontrolreceivescommandsthroughcommunicationsforClosingorOpeningoftheCapacitorBank.

Remote Control Mode Limits: These limitscanbedisabledorenabled. If controloperationwill resultinvoltageoutsideof these limitsoperationwillbeblockedandnotificationwillbesent to thesender. Ifmeasuredvoltageisoutsideoftheselimits,thecontrolwillinitiate anoperationinthedirectiontoreturnvoltagewithinlimits.

– Overvoltage Limit:Adjustablefrom95.0to140.0Vin0.1Vincrements

– Undervoltage Limit: Adjustablefrom95.0to140.0Vin0.1Vincrements

– Voltage Limits Timer:DefiniteorInverse;adjustablefrom0secondsto600seconds,in1secondincrements.Timerresetcanbeselectedasinstantaneousorintegrating.

*OnlyavailablewithVArandCurrentControlModeoption.

Page 7: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–7–

M-6283 Digital Capacitor Bank Control

Control Mode Limits:Ifcontroloperationwillresultinvoltageoutsideoftheselimits,operationwillbeblocked.Ifmeasuredvoltageisoutsideoftheselimits,thecontrolwillinitiate anoperationinthedirectiontoreturnvoltagewithinlimitsafterthesettimedelay.Onlytheblock andnottheinitiate operationisimplementedinremotemanualmodeduetopersonnelsafetyconsiderations.Thesecontrolmodelimitscanbe;"DisableAll","EnableinAuto","EnableinRemote","EnableinManual".Anycombinationof"EnableinAuto","EnableinRemote"and"EnableinManual"canbeselected.Theselimitswillapplyregardlessofthecontrolmodeofoperationselectedprovidingvoltageoverridefunctionalityinalloperationalmodes.

– Maximum Voltage Limit:Adjustablefrom95.0to140.0Vin0.1Vincrements

– Minimum Voltage Limit:Adjustablefrom95.0to140.0Vin0.1Vincrements

– Definite Time:Adjustablefrom0to60secondsin1secondincrements

Local Manual Mode:InthismodethecontrolwilldisableAutomaticandRemoteControlmodes.Inthismode,thecontrolwillrespondtothefrontpanelCLOSE/OPENswitchposition.

Bank Operational Delays:

– Close Warning Delay:Adjustablefrom0to90secondsin1secondincrements(Enable/Disable)

– Open Warning Delay:Adjustablefrom0to90secondsin1secondincrements(Enable/Disable)

– Re-Close Delay:Adjustablefrom300to600secondsin1secondincrements

– Close/Open Pulse Duration:

SolenoidDrivenSwitchType–Adjustablefrom50to100msin1msincrements

MotorDrivenSwitchType–Adjustablefrom5to15secondsin1secondincrements

NOTE: TheCloseandOpenWarningDelays"Auto"and"Remote"canbeenabledordisabled.However,"Manual"isalwaysenabled.

Page 8: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–8–

M-6283 Digital Capacitor Bank Control

Neutral Unbalance Current/Voltage DetectionCurrentandVoltagemeasuredbytheNeutralBalanceCurrentDetectionfeatureisusedtodetectbankorswitchfailuresaswellasbankOpenorClosestatus.NeutralUnbalanceCurrent/Voltageismeasuredusingoneofthefollowing:

– 200 mA CT Input:Thisoptionisofferedbydefaultintheunit.

– 5 A CT Input:Thisoptionmustbespecifiedwhenordered.

– 10 V Line Post Current Sensor: ThisoptionmustbespecifiedwhenorderedandshouldbechosenifeitheraVoltageorCurrentLinePostSensorwillbeused.

Neutral Unbalance Current Levels: Bank/Switch Failed Level 1 (can be enabled or disabled)

– Bank/Switch Failed:Adjustablefrom1.0to200.0Ain0.1Aincrementsor0.00to300.00Vin0.01increments.

Bank/Switch Failed Level 2 (can be enabled or disabled)

– Bank/Switch Failed Level 2:Adjustablefrom1.0to200.0Ain0.1Aincrementsor0.00to300.00Vin0.01increments.

– Time Delay:Adjustablefrom10to300secondsin1secondincrements

– Prior Operation:

Action Taken: RetryOperation,ReverseOperationandBlock,ResetBlock

Number of Attempts:1to9

Block Reset Time Delay: Adjustablefrom1to72hoursin1hourincrements

– No Prior Operation: (canbeenabledordisabled)

Open and Lockout Time Delay: Adjustablefrom1to4320minutesin1minuteincrements

Reset Lockout: Canbeenabledordisabled

Lockout Reset Time Delay: Adjustablefrom1to72hoursin1hourincrements

Bank Status (canbeenabledordisabled) – Bank Status Closed:Adjustablefrom0.10to10.00Ain0.01Aincrementsor0.00to30.00Vin0.01

increments.IfNeutralCurrentisgreaterthanthissetting,thebankisconfirmedtobeclosed.

– Bank Status Open:Adjustablefrom0.10to10.00Ain0.01Aincrementsor0.00to30.00Vin0.01increments..IfNeutralCurrentislessthanthissetting,thebankisconfirmedtobeopen.

– Bank Status Time Delay:Adjustablefrom10to300secondsin1secondincrementsforboth(CloseandOpen)

– Action Taken:Ifbankstatusindicatesanunsuccessfuloperation,thecontrolcanbeprogrammedtotakenoactionorretrytheoperation.

Bank Switch Status FeedbackSwitchauxiliarypositioncontactscanbeconnectedtothecontroltoconfirmindividualphaseswitchpositions.IndividualphaseswitchpositionindicatorscanbeobservedontheMeteringandStatusDialogScreen(Figure1).

BankSwitchStatusdetectioncanbedisabledorenabled.

Page 9: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–9–

M-6283 Digital Capacitor Bank Control

Additional SettingsVT/CT Setup: – Voltage Multiplier:Adjustablefrom0.1to3260.0in0.1increments

– VT Correction:Adjustablefrom-15.0Vto+15.0Vin0.1Vincrements

– Phase Current Multiplier*:Adjustablefrom1.0to200in.01increments

– NeutralCurrentMultiplier:

5ANeutralCTandLinePostSensor–Adjustablefrom1.0to150in0.1increments

200mANeutralCT–Adjustablefrom1.0to3260in0.1increments

Counters: – Resettable Counter: A software counter that increments by one count per Close or

Openoperation.Resettableto0.

– Operation Counter Preset: A software counter which increments by one count per Close orOpenoperation.Presettablefrom0to999,999.

– Resettable Counter Alarm Limit: Alimit thatalerts theusereitherbycommunicationsand/oraprogrammablealarm.Itissettablefrom0to999,999.

– Daily Operation Counter Limit: A limit that will block any further Close/Open operation until12:00AMandalertstheusereitherbycommunicationsand/oraprogrammablealarm.Itissettablefrom2to99.

Page 10: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–10–

M-6283 Digital Capacitor Bank Control

*OnlyavailablewithVArandCurrentControlModeoption.

MonitoringHarmonic Analysis:Providesthetotalharmonicdistortionandtheharmoniccontentofthevoltageandcurrentuptothe31stharmonic.

Alarms:Thealarmrelayisuser-programmablewithanon-latchingoutputcontactthatclosesononeormoreofthefollowingconditions:

•MaximumVoltageLimit •MinimumVoltageLimit •RemoteOvervoltageLimit

•RemoteUndervoltageLimit •Bank/SwitchFailed-Level2 •Bank/SwitchFailed-Level1

•ResettableCounterLimit •DailyOperationCounterLimit •VoltageHarmonics

•CurrentHarmonics* •RemoteManual •SelfTest

•DeltaVoltageAlarm

Sequence of Events: A built-in Sequence of Events (SOE)Recorder has the capability to record up to160events.ItallowstriggereventstobeAND’edandOR’edforPickupandDropout.TriggerEventsinclude:

•CloseCommand •OpenCommand •MaximumVoltageLimit

•MinimumVoltageLimit •RemoteOvervoltageLimit •RemoteUndervoltageLimit

•Bank/SwitchFailed-Level2 •Bank/SwitchFailed-Level1 •SCADAHeartBeat(withDNP3.0only)

•VoltageHarmonics •CurrentHarmonics* •CBEMA1Through4

•DeltaVoltageAlarm •PhaseOvercurrent* •PowerFactor

ParametersthatarecapturedwitheachSequenceofEventsRecordinclude:

•Voltage(PhaseA,B,C) •RMSVoltage(PhaseA,B,C)•DeltaVoltage(PhaseA,B,C)

•PrimaryVoltage(PhaseA,B,C)•Frequency •NeutralCurrent

•OperationCounter •ResetOperationCounter •Current(PhaseA,B,C)

Oscillography:Abuilt-inOscillographRecordercontinuouslyrecordsvoltageandcurrentwaveformdatainabuffermemory.Thismemorycanbeconfiguredfrom1to16partitions.Whentriggered,asnapshotofwaveformdatafrom235to2000cyclesiscaptured.Thedatacapturedcanbespecifiedfrom5%to95%post-triggerevent.Theremainderofthepercentageispre-triggerdata(samplespercycleisselectableas16,32or64samples/cycle).TriggerEventsinclude:

•CloseCommand •OpenCommand •MaximumVoltageLimit

•MinimumVoltageLimit •RemoteOvervoltageLimit •RemoteUndervoltageLimit

•Bank/SwitchFailed-Level2 •Bank/SwitchFailed-Level1 •SCADAHeartBeat(withDNP3.0only)

•VoltageHarmonics •CurrentHarmonics* •CBEMA1Through4

•DeltaVoltageAlarm •PhaseOvercurrent*

Data Logging:Abuilt-inDataLoggingRecorderthatcontinuallyrecordsdatainnon-volatilememory.Dataloggingwillcontinueindefinitelyaslongasthedataintervalissettoanon-zerovalue.Datatoberetrieved:

•Voltage •PrimaryVoltage •DeltaVoltage

•AutoAdaptive •PrimaryNeutralCurrent •Frequency

•OperationCounter •ResettableCounter •CapacitorBankStatus

•Temperature •PrimaryPhaseCurrent* •PowerFactor*

•PrimaryWatts* •PrimaryVArs* •PrimaryVA*

Page 11: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–11–

M-6283 Digital Capacitor Bank Control

MeteringFigure1providesanexampleoftheMeteringparametersthatareavailablefromthecontrol.

NOTE: PowerFactorandPrimary;PhaseCurrent,Watts,VArsandVAareonlyavailablewhentheVArControlModeoptionispresent.

Figure 1 Metering and Status Dialog Screen

InputsSwitch Power Input:Nominal120VAC,60Hz(50Hzoptional);operatesproperlyfrom95to140VAC.Ifsetat60Hz,theoperatingsystemfrequencyisfrom55to65Hz;ifsetat50Hz,theoperatingsystemfrequencyisfrom45to55Hz.Theburdenimposedontheinputis8VAorless.Theunitwillwithstandtwicethenominalvoltageforonesecondandfourtimesthenominalvoltageinputforonecycle.

V1, V2, and V3 Monitor Voltage Inputs:0–10VACLinePostVoltageSensorinput,optional0to150VACVTinput.Theseinputsaresuitableforusewithhighimpedancevoltagedividers.Inputimpedanceisapproximately1MΩ.Theinputswillwithstandtwicethemaximumvoltageratingforonesecondandfourtimesthevoltagethevoltagemaximumvoltageratingforonecycle.

Phase Current Input:0–10VACLinePostCurrentSensorinput.Externalcurrenttovoltageconversionisrequiredif5ACTistobeused.Appropriatemultiplierisutilizedtocalculatetheprimaryphasecurrent.LinePostCurrentSensoroptionalsoincludesaphaseshiftcompensationsetting.

Neutral Unbalance Current Input:0–10VACLinePostCurrentSensor,200mA,or5Ainputwillalsobesupported.Appropriatemultiplierisutilizedtocalculatetheprimaryneutralunbalancecurrent.

Page 12: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–12–

M-6283 Digital Capacitor Bank Control

OutputsClose Output:Capableofswitching10Afor30secor45Afor25ms.

Open Output:Capableofswitching10Afor30secor45Afor25ms.

User-Programmable Alarm Output:OneForm"C"contactcapableofswitching6Aat125VACor0.2Aat125Vdc.

Digital InputsThree12VdcInputsforswitchstatusandoneinternallywettedintrusiondetectioninput.

Front Panel ControlsMenu-drivenaccesstoallfunctionsbywayofsixpushbuttonsandatwo-linealphanumericdisplay.Thereareupto30programmableUserAccessCodes(Level1orLevel2)availabletoprovidevariouslevelsofaccesstothecontrolfunctions.

TheCapacitorBankcontroloffersa2-lineby20characterLCDdisplay(LEDbacklit)forenhancedviewingindirectsunlight.

CLOSE/OPENswitchallowslocalmanualCloseandOpencommandstobeinitiated.

REMOTE/AUTO - LOCAL MANUALswitchallowsAutomaticoperationofthecontrolorManualoperationfromthefrontpanelbyusingtheCLOSE/OPENtoggleswitch.

VOLTAGE SOURCEswitchdisconnectsallpowerfromtheunitwhenselectedtotheOFFposition.TheEXT positionallowsthecontroltobepoweredfromthefrontpaneltestjacks.

EXTERNAL POWERbindingpostsallowapplicationofa120VRMSnominalvoltagetotheunitfortesting.

METER OUTbindingpostsallowreadingoftheinputvoltage.

Smart Flash SD Card SlotAllowstheusertoperformthefollowingfunctions:

•LoadSetpoints •SaveSetpoints •SaveDataLog •SaveSequenceofEvents

•SaveOscillographRecords •CloneSave •CloneLoad •LoadDNPConfig

•SaveDNPConfig •FirmwareUpdate •SaveMeteringData •SaveWakeScreenData

•SDCardUserAccess(PhysicalSecurityKey) •QuickCapture

LED IndicatorsFront panel LED indicators show the following control conditions: REMOTE/AUTO, LOCAL/MANUAL, ALARM, NEUTRAL UNBALANCE, CLOSE, OPEN,CPU OK,RSSIandTX (Transmit)andRX(Receive).

Page 13: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–13–

M-6283 Digital Capacitor Bank Control

CommunicationsThecommunicationportsprovideaccesstoallfeatures,includingmetering,softwareupdates,andprogrammingofallfunctions.ThisisaccomplishedusingaconnectionfromanyWindowsTM-compatiblecomputerrunningtheCapTalk®S-6283CommunicationsSoftwareorSCADAcommunicationssoftware.

Protocols:ThestandardprotocolsincludedintheM-6283areDNP3.0andMODBUS®.TheUSBportusesMODBUS for localcommunications.TheoptionalEthernetPortsupportsDNP3.0andMODBUSprotocolssimultaneously.DNPMasterSourceAddressAuthenticationissupportedallowingmultipleSCADAMasterstocoexistonthesamecommunicationsnetwork.

Communications Via Direct Connection:CapTalksupportsdirectcommunication(MODBUSprotocol)withtheM-6283usingtheapplicableconnector(USBcable)forthecomputer.Additionally,thestandardRS-232communicationsportaswellasthe2-wireRS-485andSerialFiber(STorVpin)optionalcommunicationsportscanbeusedtocommunicateviaCapTalk.

Optional Ethernet Port:TheoptionalEthernetPortprovidesanRJ-45(10/100Base-T)ora(100Base-Fx)FiberOpticinterfaceforethernetcommunicationtotheM-6283.Theprotocolssupportedare:MODBUSoverTCP,DNP3.0overTCPandDNP3.0overUDP.Theportsupportsuptoeightconcurrentconnections.ThemaximumnumberofallowedDNPconnectionsisfiveforeachprotocol(5forUDP,5forTCP).ThemaximumnumberofMODBUSconnectionsiseight.EthernetPortsettingscanbeconfiguredmanuallyorviaDHCPprotocol.MODBUSprotocol"PortNumber"andDNPProtocol"PortNumber"canbechangedmanuallyfromdefaultvalues.DNPMasterSourceAddressAuthenticationissupportedallowingmultipleSCADAMasterstocoexistonthesamecommunicationsnetwork.Thisoptioncanbefieldinstalled.

Optional Bluetooth:TheoptionalBluetooth® (V2.0+EDRClass 1Type) provideswireless access to theM-6283.WithBluetooththeuserisabletoconfigurethecontrol,readstatusandmeteringvaluesaswellaschangesetpoints.Thisoptioncanbefieldinstalled.TherearefourmodesofoperationfortheBluetooth:

Mode 0 –Thedeviceisdiscoverableandconnectabletoanyclientstation.

Mode 1 –(Future)Thedeviceisnon-discoverablebutitisconnectabletoanyclientstationwhoknowsthecontrolBluetoothdeviceaddressindicatedunder“Control BT Device”intheHMI.

Mode 1 –HasbeenaddedtomeetCIPrequirement.(CIP-0007-4SystemSecurityManagement)(R2.3)

Communications Using Networking:TheaddressingcapabilityoftheM-6283allowsnetworkingofmultipleM-6283’s.Eachcapacitorbankcontrolcanbeassignedanaddress,FeederAddressorSubstationAddressrangingfrom1to65519.Selectedcommandsmaybebroadcasttoallcontrolsonthenetwork.Figures3,4and5illustratetypicalnetworkconfigurations.Addresses1-247canbeassignedtoMODBUSand1-65519forDNP3.0.

ApplicationUsingCapTalkCommunicationsSoftware,theoperatorhasreal-time,remoteaccesstoallfunctionsoftheM-6283. The protocols implement half-duplex, two-way communications. This allows all functions, whichwouldotherwiserequirethepresenceofanoperatoratthecontrol,tobeperformedremotely.Communicationcapabilitiesinclude:

• Interrogationandmodificationofsetpoints

• Broadcastofcommands

• Recognitionofalarmconditions,suchasvoltageextremes

• Unsolicitedexceptionreporting

• MulticastcapabilityusingUDP

Unit IdentifierA2-rowby20-characteralphanumericsequence,setbytheuser,canbeusedforunitidentification.

Page 14: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–14–

M-6283 Digital Capacitor Bank Control

COM 1, RS-485, RS-232, (2Wire),or Fiber Optic (ST or Vpin) Cable

USB Cable

Switched Capacitor Bank

PrinterComputer Running CapTalk® S-6283

Communications Software

BeckwithDigital

CapacitorControl

Figure 2 Direct Connection

Page 15: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–15–

M-6283 Digital Capacitor Bank Control

Computer Running CapTalk® S-6283Communications Software

ST Multi-mode or Vpin 62/125 or 200 Micron Optical Fiber

Connect to computer

Straight DB25Connection to ComputerRS-232 COM Port

Dymec Model No. 5843DTE = OnRepeat = Off

TX

RX

Figure 3 Fiber Optic Connection Loop

A

B

Model No. 485 LP9TBB & B ElectronicsRS-232/RS-485

120

Computer Running CapTalk® S-6283Communications Software

Connect to computer

Straight DB9 Connectionto Computer RS-232COM Port

Figure 4 RS‑485 Network Connection

Page 16: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–16–

M-6283 Digital Capacitor Bank Control

NetworkCAT 5 Twisted Pair RJ-45orFiber Optic ThroughST Connectors

Network Server

Computer Running CapTalk® S-6283Communications Software

Hub

Figure 5 Optional Ethernet Network Connection

RS232 Link RS232 Link

Cellular Tower

RS232 Link

Cellular Modem with TCP/IP or UDP capabilities usingstandards-based EDGE, GPRS, or CDMA technologies

Figure 6 Cellular Modem Network

Page 17: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–17–

M-6283 Digital Capacitor Bank Control

EnvironmentalTemperature:Controloperatesfrom–40°Cto+85°C.

NOTE: TheLCDdisplay’svisibletemperaturerangeis–20°Cto+70°C.

IEC60068-2-1Cold,–40°CIEC60068-2-2DryHeat,+80°CIEC60068-2-78DampHeat,+40°C@95%RHIEC60068-2-30DampHeatCondensingcycle25°C,+55°C@95%RH

Transient Protection

High VoltageAllinputandoutputterminalswillwithstand2000Vacrmstochassisorinstrumentgroundforoneminutewithaleakagecurrentnottoexceed25mA,forallterminalstoground.Inputandoutputcircuitsareelectricallyisolatedfromeachother,fromothercircuitsandfromground.

Surge Withstand CapabilityIEEEC37.90.1-2002 2,500VpkOscillatory 4,000VpkFastTransientBurst

IEEEC37.90.1-1989 2,500VpkOscillatory 5,000VpkFastTransient

Radiated ImmunityIEC60255-22-3 10V/M

Fast Transient/Burst ImmunityIEC60255-22-4 (4kV,5kHz)

Electrostatic DischargeIEC60255-22-2 (8kV)Pointcontactdischarge (15kV)Airdischarge

IEEEC37.90.3 (8Kv)Pointcontactdischarge (15Kv)Airdischarge

Voltage Withstand

Dielectric WithstandIEC60255-5 2,000Vacfor1minuteappliedtoeachindependentcircuittoearth 2,000Vacfor1minuteappliedbetweeneachindependentcircuit

Page 18: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–18–

M-6283 Digital Capacitor Bank Control

Impulse VoltageIEC60255-5 5,000Vpk,+/-polarityappliedtoeachindependentcircuittoearth 5,000Vpk,+/-polarityappliedbetweeneachindependentcircuit 1.2µsby50µs,500ohmsimpedance,threesurgesat1every5seconds

Insulation ResistanceIEC60255-5 >100Megaohms

Surge ImmunityIEC60255-22-5 4,000Vpk,+/-polarityapplied,1.2µsby50µs,2ohms/12ohmsimpedance,fivesurges1every5seconds

Voltage Interruptions ImmunityIEC60255-11

Mechanical EnvironmentIEC60255-21-1 VibrationResponseClass1 0.5g VibrationEnduranceClass11g

IEC60255-21-2 ShockResponseClass1 5g ShockWithstandClass1 15g BumpEnduranceClass1 10g

PhysicalM-6283Size:9.18"widex15"highx3.22"deep(23.32cmx12.5cmx7.95cm)

Approximate Weight:6lbs,5oz(2.92kg)

Approximate Shipping Weight:10lbs,5oz(4.56kg)est.

Patent & WarrantyTheCapacitorControliscoveredbypendingU.S.Patents.

TheCapacitorControliscoveredbyatenyearwarrantyfromdateofshipment.

BluetoothistheRegisteredTrademarkofBluetoothSIG,Inc.CapTalkistheRegisteredTrademarkofBeckwithElectricCo.,Inc.MODBUSistheRegisteredTrademarkofGould,Inc.Lexan®istheRegisteredTrademarkofGeneralElectricCo.NEMAistheRegisteredTrademarkofNationalElectricalManufacturersAssociationTroposistheRegisteredTrademarkofTroposNetworks,Inc,SpeedNetistheRegisteredTrademarkofS&CElectricCompanyUListheRegisteredTrademarkofUnderwritersLaboratories,Inc.WindowsistheRegisteredTrademarkofMicrosoftCorporationWindows2000istheRegisteredTrademarkofMicrosoftCorporation

WindowsVistaistheRegisteredTrademarkofMicrosoftCorporationWindowsXPistheRegisteredTrademarkofMicrosoftCorporation

Page 19: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–19–

M-6283 Digital Capacitor Bank Control

NEMA® 4X, Lexan® Meter Socket Mount Cabinet

Integrated DoorHinge With StainlessSteel Hinge Pin

External Grounding Stud

Cabinet Door AccomodatesOptional Power Supplies andCommunication Devices

Radio AntennaMounting Hole

Stainless SteelLocking Clasps

Accept up to 3/8"Hasp Locks

4, 5 or 6 BladeMeter Socket(4 Standard)

Factory CustomWiring Available

Radio AntennaMounting Hole

NEMA® 4X, Lexan® Pole Mount Cabinet

Adjustable Direct PoleMounting Bracket

Integrated DoorHinge With Stainless

Steel Hinge Pin

External Grounding Stud

Standard 5' Control Cable(Optional cable lengths in fivefoot increments up to 50 feet)

Adjustable Direct PoleMounting Bracket

Stainless Steel LockingClasps Accept up to 3/8"Hasp Locks

4, 5 or 6 BladeMeter Socket Plug

(4 Standard)Factory CustomWiring Available

Cabinet Door AccomodatesOptional Power Supplies andCommunication Devices

Radio AntennaMounting Hole

Radio AntennaMounting Hole

Figure 7 M‑6283 Digital Capacitor Control NEMA 4X Lexan Cabinet, Multiple Common Connector, Meter Socket Plug, and Meter Socket Mount

Page 20: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–20–

M-6283 Digital Capacitor Bank Control

15.00[12.5]

Smart Flash SD Card

S O UR C EV O LTAG E

INT

E X T

O F F

USB

RXTX

9.18[23.32]

0.65[0.17]

1.10[2.8]

1.0[2.54]

9.77[24.82]

1.0[2.54]

3.22[8.18]

0.88[2.24]

OK

OPEN ALARM

EXTERNALPOWER

METEROUT

REMOTE/ AUTO

LOCAL/ MANUAL

CLOSE REMOTE/

AUTO

LOCAL/ MANUAL

CLOSE

OPEN

NEUTRALUNBALANCE

RSSI

COM

!

Made in U.S.A.

M-6283 Three PhaseDigital Capacitor Bank Control

HTIWKCEB

CIRTCELE.CNI.OC

EXITWAKE

ENTUTIL

SETP

COMMMNTR

CNFG

Figure 8 M‑6283 Control Outline Dimensions

Page 21: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–21–

M-6283 Digital Capacitor Bank Control

Neutral Current Input (POL)

Capacitor Bank Close Output

Neutral

1

2

3

4

5

6

7

8

9

10

11

12

TB2

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

TB1

16

1

2

3

J3RS-485 A (+)

RS-485 B (-)

RS-485 Shield

Capacitor Bank Open Output

Neutral Current Input (RTN)

Not Used

Power Input

V2

Switch Status "C" Input

Switch Status "B" Input

Switch Status "A" Input

+12 V dc Wetting Supply

Alarm Output (NO)

Alarm Output Common

Alarm Output (NC)

Factory installed Jumper that isrequired for Close/Open output

200 mA, 5 A CT, or Line PostCurrent Sensor

Optional M-2980ACabinet Door Intrusion

Detection SwitchOpen when cabinet door is openClosed when cabinet door is closed

- 12 V dc Backup Power

+ 12 V dc Backup Power

V3

V1

I3

I2

I1

Black (GND)

Red (+5 V)

White (Vo)Optional External

Temperature SensorTS

Figure 9 M‑6283 External Connections

Page 22: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–22–

M-6283 Digital Capacitor Bank Control

TB2

1

TB1 1 162 3 4 5 6 7 8 9 10 11 12 13 14 15

!

CLO

SE

OP

EN

NEU

TRA

L

PO

L

RTN

NEUTRALCURRENT

23456789

101112

I1I2

PO

WE

R

ALARMOUTPUT COM

NO

NC

SWITCH POWER12A 250V 3AB

TEST3A 250V 3AG

VOLTAGE0.5A 250V 3AG

TB2-1

TB2-2

TB2

Jumper TB2-1 to TB2-2

RS485OPTICFIBER

SH B ARXTX

TB1-5,6,9 140V 10ATB1-1,2,4,7 12V 0.100A

V3

V2 V1

I3

50 Hz 60 HzSENSING VOLTAGE V1

0.2A CONT.0.4A 2 HR.4.0A 1 SEC.

SENSING VOLTAGE V2

SENSING VOLTAGE V3

SENSING CURRENT I1

SENSING CURRENT I2

SENSING CURRENT I3

NONE

NONE

NONE

200 mA TB1-14, 15NEUTRAL CURRENT5.0A CONT.10.0A 2 HR.50.0A 1 SEC

5A CT TB1-14, 15

10V LINE POST TB1-11

10V LINE POST TB1-10

10V LINE POST TB1-3

10V LINE POST TB2-5

10V LINE POST TB2-4

10V LINE POST TB1-16

10V LINE POST TB1-14,15

10.0V 0.1 mVA

120V TB1-11

120V TB1-10

120V TB1-3

120V 15 mVA

TB2-6,7,8 120V 6ATB2-11,12 10-16V 5W

SW

STA

T C

SW

STA

T B

SW

STA

T A

WE

TTIN

G S

UP

.

{ +-

BUPWR

BECKWITH ELECTRIC CO., INC.6190-118th Avenue North - Largo Florida 33773-3724 U.S.A.

PHONE (727)544-2326 - FAX (727)546-0121www.beckwithelectric.com

Model: M-6283A XXXXXXXXXSoftware: ____________Ser. No. XXXXXXXXXXXXXX

Figure 10 M‑6283 Rear View

Page 23: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–23–

M-6283 Digital Capacitor Bank Control

M-2980A Capacitor Control Cabinet

ConstructionMoldedLexan®

• BodiesanddoorsfabricatedfrommoldedLexan

• EPDM/Neopreneclosedcellspongegasket

• Externaladjustablemountingbracket

• Integrateddoorhingewithstainlesssteelhingepin

• Enclosuredooraccommodatesoptionalpowersuppliesandcommunicationsdevices

• ExternalGroundingstudprovided

ColdRolledSteel/StainlessSteel(304)B7B346

• Bodiesanddoorsfabricatedfrom14/16gaugesteel

• Continuouslyweldedseamsgroundsmooth

• Closedcellneoprenegasket

• Externalmountingbracket

• Stainlesssteeldoorhinge

• Enclosureaccommodatesoptionalpowersuppliesandcommunicationsdevices

• ExternalGroundingstudprovided

Cabinet to Capacitor Bank Interface Type • MeterSocketMount(NotavailableforColdRolledSteelandStainlessSteelCabinets)

–Integrated4,5or6Blade(4BladeStandard)MeterSocketPlug

–StandardMeterSocketPlugwiringisavailableinfactory4,5and6Bladeconfiguration(4S,5Sand63)(Figure11)

–OptionalcustomfactoryMeterSocketPlugwiringconfigurationsavailable(Figure11)

• DirectPole-MountwithcabledMeterSocketPlug

–4,5,or6Blade(4Bladestandard)MeterSocketPlugwithstandardfivefootcontrolcable

–StandardMeterSocketPlugwiringisavailableinfactory4,5and6Bladeconfiguration(4S,5Sand63)(Figure11)

–Optionalcablelengthsavailableinfivefootincrementsupto50feet

–OptionalcustomfactoryMeterSocketPlugwiringconfigurationsavailable(Figure11)

Page 24: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–24–

M-6283 Digital Capacitor Bank Control

• DirectPole-MountwithCannonConnector,Integrated

–5-PinCannonConnector(5EStandard)(Figure13),CannonBulkheadShell18-11P

–8-PinCannonConnector(8AStandard)(Figure14)CannonBulkheadShell20-7P

–14-PinCannonConnector(LStandard)(Figure15)CannonBulkheadShell22-19P

–Optional8and14-Pinwiringconfigurationsavailable(Figures5and6)

• DirectPole-MountwithCannonConnector,Cabled

–5-PinCannonConnectorShell18-11P(5EStandard)(Figure13)

–8-PinCannonConnector(8AStandard)(Figure14)CannonBulkheadShell20-7P

–14-PinCannonConnector(LStandard)Figure15)CannonBulkheadShell22-19P

–Optional8and14-Pinwiringconfigurationsavailable(Figures5and6)

–Optionalcablelengthsavailableinfivefootincrementsupto50feet

• DirectPole-Mountwithcableonly,noconnector

4 Blade Selection

Config

4S

1 2 3 4

41

42

43

5 Blade Selection

1 2 3 4 5Config

5S

6 Blade Selection

Config 1 2 3 4 5 6

Meter Socket Wiring

63

67

Line Neutral OPEN CLOSE

Neutral Line OPEN CLOSE

Neutral Line CLOSE OPEN

Line Neutral CLOSE OPEN

Line Neutral OPEN CLOSE NC POL

CLOSE

CLOSE

OPEN

OPEN

Neutral

Neutral

Line

Line

NC POL

NC NC

NC RTN

1 2

3 4

1 2

3 45

1 2

5 63

4

4 Jaw Base

5 Jaw Base

6 Jaw Base

View as shown, is peering into female Meter Socket NC = Not Connected

69 CLOSEOPENNeutralLine NC NC

Figure 11 Meter Socket Wiring Configurations

M-2980A Capacitor Control Cabinet (Cont’d)

Page 25: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–25–

M-6283 Digital Capacitor Bank Control

PIN

A B C

NC POL NC RTN Ground

3-Pin Cannon Connector/Control Wiring

TB1-14 TB1-15 Enclosure Ground Stud

LC POL LC RTN Ground

TB2-5 TB2-4 Enclosure Ground Stud

Config

Neutral Current50:0.2 CT

Control

Line Current LinePost Sensor

Control

A B CConfig

Wire color codingdoes not apply tocontrol terminal blockwiring.

*

Wire color coding doesnot apply to controlterminal block wiring.

*

3-Pin Socket(Cabinet Side)

B-White*(LC RTN)

C-Green* orBare Wire

A-BLACK*(LC POL)

3-Pin Plug(Cabinet Side)

B-Red*(NC RTN)

C-Shield

A-BLACK*(NC POL)

LC POL - Line Current PolarityLC RTN - Load Current Return

NC POL - Neutral Current PolarityNC RTN - Neutral Current Return

Figure 12 3-Pin Cannon Plug Configurations

M-2980A Capacitor Control Cabinet (Cont’d)

Page 26: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–26–

M-6283 Digital Capacitor Bank Control

PIN

A B C D EConfig

5E Line Neutral CLOSE OPEN NC

5-Pin Cannon Plug/Control Wiring

TB1-9 TB1-8 TB1-5 TB1-6Control NC

5-Pin PlugC-CLOSE

D-OPEN

B-NEUTRAL

A-LINE

E-NC POL NC POL - Neutral Current Polarity

A B C D EConfig

5N Line Neutral CLOSE OPEN NC POL

TB1-9 TB1-8 TB1-5 TB1-6Control TB1-14

NC = Not Connected

Figure 13 5‑Pin Cannon Plug/Control Wiring

PIN

A B C D EConfig

8-Pin Cannon Plug/Control Wiring

8A LINE NEUTRAL CLOSE

TB1-11 TB1-8 TB1-5Control

F G

A Status

TB1-7

OPEN

TB1-6

B Status

TB1-2

H

C Status

TB1-1

Status RTN

TB1-4

A B C D EConfig

8B V1 V2 V3

TB1-11 TB1-10 TB1-3Control

F G

OPEN

TB1-6

CLOSE

TB1-5

NEUTRAL

TB1-8

H

NC NC

8 PIN PLUG

(D) Open

(C) Close

(B) Neutral

(A) Line

A Status (E)

B Status (F)

C Status (G)

Status RTN (H)

NC = Not Connected

Figure 14 8‑Pin Cannon Plug/Control Wiring

M-2980A Capacitor Control Cabinet (Cont’d)

Page 27: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–27–

M-6283 Digital Capacitor Bank Control

PIN

A B C D E

14-Pin Cannon Plug/Control Wiring

F G

NeutralTB1-8

NeutralTB1-8

NC POLTB1-14

V1 POLTB1-11

V3 POLTB1-3

NC RTNTB1-15

V2 POLTB1-10

H J K L M N P

V1, 2, 3 RTNTB1-8

I1 RTNTB1-8

I2 POLTB2-4

I3 RTNTB1-8

I2 RTNTB1-8

I3 POLTB1-16

I1 POLTB2-5

(A) Neutral(B) Neutral(C) NC POL

(F) V2 POL

(E) V1 POL

(D) NC RTNV1, 2, 3 RTN (H)

I3 POL (N)

(M) I2 RTN

V3 POL (G)

I3 TRN (P)

I1 POL (J)I1 RTN (K)

I2 POL (L)

14-Pin Plug

1

Figure 15 14-Pin Cannon Plug Configurations

Page 28: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–28–

M-6283 Digital Capacitor Bank Control

M-2980A Capacitor Control Cabinet (Cont’d)

Optional Equipment/Accessories

• Polemountbracket

• 3PhaseSensorInputOptionsInclude:

–CannonConnector,CabinetSide14-Pin,MateswithSensorInterfaceCable

–Lindsey9-587/35/R-22102,Rev.000,14PinCannontothree4PinCannonconvertercable.ConnectsB-1400toLindsey9650/E1104Sensor.

–CannonConnector-14-PinStraightPlug,FemaleThreadedCollar.AllowswiringofusercabletoconnectorwhichmateswithB-1400.IncludesMainLineConnector,CableClamp,and RubberBushing.

–SensorInterfaceCable,Includes14PinCannonconnectorononeendandun-terminatedon theother.MateswithB-1400.

–Lindsey9650/E1104Rev.000,15kVMulticoreSensor.

–Lindsey9614A/35/R-22742Rev.NS,Connectorwithcableassembly.

–30FootCableforLindseyLinePostSensor(unterminatedononeend).

–1/2"HEYCOLiquidTightCordgrip

• NeutralCurrentSensorOptionsInclude:

–50:0.2CTNeutralCurrentSensorterminatedwith3-PinCannonConnector(shellsize16)usingcustomer specified(10,20,35,or45foot)lengthofshieldedtwistedpaircable.IncludesCabinetSide Connections.

–50:0.2CTNeutralCurrentSensorwithcustomerspecified(10,20,35,or45foot)lengthof shieldedtwistedpaircable.

–CannonConnector,Cabinetside3-Pin

–CannonConnector-3-PinStraightPlug,FemaleThreadedCollar.AllowswiringofcustomercabletoconnectorwhichmateswithB-1311-1.IncludesMainLineConnector,CableClamp,andRubberBushing.

–1/2"HEYCOLiquidTightCordgrip

• AntennaCable&Bulkhead(ForInstallationwithAntennasMountingDirecttoCabinet)optionsinclude:

–TNCmaletoNfemaleweatherproofbulkheadandantennacableforlidmount(12")

–TNCmaletoNfemaleweatherproofbulkheadandantennacableforcabinetmount(36")

–SMAmaletoNfemaleweatherproofbulkheadandantennacableforlidmount(12")

–SMAmaletoNfemaleweatherproofbulkheadandantennacableforcabinetmount(36")

–Double-DHolefor"N"ConnectionsinLocation1,2,3,or4ofCabinettoaccommodateAntennaExit.

Page 29: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–29–

M-6283 Digital Capacitor Bank Control

M-2980A Capacitor Control Cabinet (Cont’d)

Optional Equipment/Accessories (Cont.’d)

• LightningProtection(Forinstallationswithexternalantennas)optionsinclude:

– DSXL PolyPhaser Lightning Arrestor 700MHz - 2.7GHz N Female protected side, N FemaleBulkheadantennaside

–AL-LSXMPolyphaserLightningArrestor2GHz to6GHzNFemaleprotectedside,NFemaleBulkheadantennaside

–SMAmaletoNmaleantennacabletoconnectlightningprotectiontoaradioforcabinetmount(36")

–TNCmaletoNmaleantennacabletoconnectlightningprotectiontoaradioforcabinetmount(36")

–NmaletoNmaleantennacabletoconnectLightningProtectiontoaRadioforcabinetmount(36")

• Antennas:

– Laird FG9023, 902 MHz to 928 MHz, 3 dBi gain, fiberglass Omni-Directional antenna,NFemaleconnector

–FM2,antennaPoleMountBracketforLairdfiberglassantennas

– Laird TRAB9023NP, 902 MHz to 928 MHz, 3 dBi gain, Omni-Directional Phantom antenna,NFemalebulkheadconnector

–LairdTRAB806/1703P,Multi-Band(806MHzto2.5GHz),3dBiGain,Omni-DirectionalPhantomAntenna,NFemaleBulkheadConnector.InstalledinHoleLocation2ofCabinet

– TNC male to N male antenna cable to connect antennas with an integrated bulkhead to aradioforcabinetmount(36")

–NmaletoNmaleantennacabletoconnectLightningProtectiontoaRadio.Forcabinetmount(36")

• RadioOptionsInclude:

2 Way VHF (154 MHz) radio

–Radius

2 Way (130 MHz - 3.7 GHz) radio modems:

–SilverSpringsNetworksSSNebridgeandsbridge

–MDSINET900AP

–MDSINETII

–MDSSD9

–MDSX710

–MDSSD4

–MDS9810

–MDSTransNET

–MDSMercury3650and900

–MDSentraNET900and2400

–CellNetSeriesIII

–S&CSpeedNet™

Page 30: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–30–

M-6283 Digital Capacitor Bank Control

M-2980A Capacitor Control Cabinet (Cont’d)

Optional Equipment/Accessories (Cont.’d)

Digital Cellular Modems:

–SixnetBTseriesMobilityPro/industrialProGateways

–MultitechMultimodemseriesroutersandmodems

–AirLinkRavenII,X,XE,XT

–TelemetricsDNPRTMII

–ZyWAN3G/GPRS/GSM

Wireless Routers:

–TroposMeshRouter7320

• Radioreadyoptionsinclude:

–UniversalRadioBracket

–UniversalRadioBracketwith12VdcpowerSupply

–UniversalRadioBracketwith24VdcpowerSupply

–UniversalRadioBracketwithcustomersuppliedpowersupplyinstalled

• RadioInstallation:

–CustomersuppliedradiomountedandInstalledtoM-2980A

• RS-232RadioCommCable-30"length,MaletoMale,straightthrough.GoesfromM-6283ControltoRadio'sDB9Port.

• RS-232RadioCommCable-33"length,MaletoFemale,nullmodem.GoesfromM-6283ControltoRadio'sDB9Port.

• EthernetRadioCommCable-24"length.ConnectsM-6283Controltoradio’sRJ45Port.

• UniversalPowerCableprovidesfused120VACtopoweraradiopowersupply(Includedonallradiobrackets)

• DB9toDB25-RS-232CableConverter

• 1/2"HEYCOLiquidTightCordgriptosecurecablecomingintocabinet.

• UniversalRadio/ModemBracket(ForfieldmountinginthedooroftheM-6283)

• 12VdcPowerSupplyforradio

• 25footNmaletoNmaleLMR-400antennaextensioncable.

• Externaltemperaturesensor

• CannonConnector-5-PinStraightPlug,Femalethreadedcollar.AllowswiringofcustomercabletoconnectorwhichmateswithIntegrated5-PinCannonConnectorforInterface.IncludesMainLineConnector,CableClamp,andRubberBushing.

• CannonConnector-8-PinStraightPlug,Femalethreadedcollar.AllowswiringofcustomercabletoconnectorwhichmateswithIntegrated8-PinCannonConnectorforInterface.IncludesMainLineConnector,CableClamp,andRubberBushing.

• CannonInterfaceCable-5Pincannonconnectorwithspecifiedlengthofcablewithunterminatedend.

• IntrusionDetectionMicroswitch-TheM-2980Acabinetdoorintrusiondetectionmicroswitch(Figure9)status(Close/OpenCondition)ismonitoredbytheM-6283.IfanOpenConditionisdetected,aDNPbinary inputpoint for intrusiondetectionwillbesetandwillgenerateaDNPevent.TheintrusiondetectionwillalsobemonitoredusingMODBUSregister1791@bit3.

Page 31: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

–31–

M-6283 Digital Capacitor Bank Control

PhysicalMolded Lexan® Cabinet

Size:18.38"highx12.43"widex7.81"deep(46.7cmx31.6cmx19.84cm)

Approximate Weight:10lbs,8oz(4.76kg)

Approximate Shipping Weight:12lbs(5.44kg)

Approximate Weight with M-6280A Digital Capacitor Bank Control:18lbs(8.17kg)

Approximate Shipping Weight with M-6280A:21lbs,8oz(9.75kg)

Cold Rolled Steel/Stainless Steel (304)B7B346

Size:21.3"highx11.12"widex7.71"deep(54.1cmx28.25cmx19.58cm)

Approximate Weight:15lbs,8oz(7.03kg)

Approximate Shipping Weight:23lbs(10.4kg)

Approximate Weight with M-6280A Digital Capacitor Bank Control:22lbs,8oz(10.21kg)

Approximate Shipping Weight with M-6280A:35lbs(15.88kg)

WarrantyTheM-2980AWeatherproofCapacitorControlCabinetiscoveredbyafiveyearwarrantyfromdateofshipment.Thirdpartymountedoptionswillcarrytheirrespectivemanufacturer’swarranty,passedalongthroughBeckwithElectric.

Specification subject to change without notice.

Page 32: Digital Capacitor Bank Control M-6283 Capacitor Bank Control M-6283 3 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection CONTROLS • Flexible

800-6283-SP-01 03/13©2008BeckwithElectricCo.AllRightsReserved.PrintedinU.S.A.(09.24.02)