ESC SIM PROG AUTO HOME Digi-Gage Plus Digital Constant Speed Controller SCADA-Ready | Remote Access | Backwards Compatible User Manual Digi-Gage Plus
Transcript
Page 1: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

ESCSIMPROGAUTOHOME

Digi-Gage Plus™

Digital Constant Speed Controller SCADA-Ready | Remote Access | Backwards Compatible

User Manual

Digi-Gage Plus™

Page 2: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

2

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LF O R W A R D

The information in this document reflects product features and functions at the date of printing. EG Controls Inc. reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue, change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.

All information in this document is provided “as is” without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. EG Controls Inc. assumes no responsibility for errors or omissions in the information presented in this document. In no event shall EG Controls Inc. be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this infor-mation.

The trade-names, trademarks, logos and service marks presented in this document, including their design, are the property of EG Controls Inc. or other third parties and you are not permitted to use them without the prior written consent of EG Controls Inc. or such third party as may own them.

Page 3: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

3

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LT A B L E O F C O N T E N T S

1 Introduction

2 Features2.1 Hardware Ratings SystemConfiguration SystemProcessor BaseFeatures Communications

2.2 Process Features

2.3 Features Details Six-PumpSystem Five-PumpSystem Four-PumpSystem Three-PumpSystem 2.4 Controller Functionality

2.5 Typical Wiring Diagrams

3 Modes of Operation 3.1 Clean-Out (Flush) Mode Description (For Lift Stations) TheoryofOperation

3.2 Anti-F.O.G. Mode Description (For Lift Stations) TheoryofOperation

3.3 Clog Prevention Mode (Key Shaft Pumps Only) TheoryofOperation

4 Digi-Gage Plus™ Front Bezel 4.1 System Status / Home 4.2.1 SystemStatus(Detailed)with1or2Transducers 4.2.2 SystemStatus(Detailed)withFloatsOnly 4.2.3 RetroConfiguration

4.3 System Menu

4.4 Pump Details

4.5 Process Trend 4.5.1 AutomaticTrendScaling 4.5.2 ManualTrendScaling

5

66 6 7 7 7

7

8 8 8 8 9 9

10

12 12 12

12 13

13 13

14 15 16 17 18

19

20

21 22 23

Page 4: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

4

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LT A B L E O F C O N T E N T S

4.6 System Flow with Attached Flow Meter 4.6.1 FlowBasedonCalculations

4.7 Control Setup 4.7.1 Login 4.7.2 SystemConfiguration 4.7.3 Networksetup 4.7.4 GroupNaming 4.7.5 MotorNaming 4.7.6 MixerSetup 4.7.7 ProcessSensorsetup 4.7.8 GroupSetPoints 4.7.9 FlushControl 4.7.10F.O.G.Reduction 4.7.11PurgeSetup

4.8 Pump Alternation Mode

4.9 Simulation 4.9.1 Simulationcontinued

4.10 System Diag: Digital Inputs 4.10.1SystemDiag:DigitalOutputs

4.11 Alarm Setup: Level by Set Point 4.11.1StartsperHour 4.11.2AlarmBypass 4.12 Active Alarms: Groups with Pending Alarms 4.12.1AlarmsinGroups 4.12.2AlarmDetails

4.13 Alarm History

5 Screen Navigation Map

6 TypicalWiringbyConfiguration

Appendix Glossary/Index ModbusRegisters Alarms

24 25

26 27 28 29 30 31 32 33 34 35 36 37

38

39 40

41 42

43 44 45

46 47 48

49

50

52

61 61 65 68

Page 5: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

5

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

1Section

D I G I - G A G E P L U S U S E R M A N U A LI N T R O D U C T I O N

IntroductionThankyouforpurchasingtheDigi-GagePlus™digitalconstantspeedcontrollerbyEGControls.TheDigi-GagePlus™isanaffordable,flexible,compact,SCADA-readysystemcontroller.Itisdesignedtoautomaticallycontrolamaximumofsixpumpsinuptothreeprocessgroupswithindependentstart/stopandalternationineachgroup.

The Digi-Gage Plus™ has features including:

•Remoteaccessfromsmartphones,tabletsandcomputers •Remoteviewingofthebuilt-inscreens •WellClean-Out(Flush)mode •WellF.O.G.mode •Clogpreventionmode(3pumpsorless) •Advancedgrouping •Operationofupto6pumps

TheDigi-GagePlus™isdesignedtobebackwardcompatiblewithEGControl’sclassicDigi-Gage2300,2400,and2600products.ItcanintegrateintovirtuallyanySCADAsystem.PreviousmodelsoftheDigi-Gageproductsnolongerachievetoday’ssystemrequirements,theDigi-GagePlus™can!TheDigi-GagePlus™hasbeendesignedtofitinthesamepanelcutoutofthepreviousmodel.IfapreviousDi-gi-Gagedidn’tcomeinstalledwithSCADAcompatibility,theDigi-GagePlus™can!

TheDigi-GagePlus™canbepartneredwithpopularflowmetersorcanmakebasicflowcalculationsbasedonwet-welldimensions.TheDigi-GagePlus™featuresalternationthatcanalternatetheleadandlagpumps.Itusesinformationthesystemcollectsfrompumpstartandruntimes.TheDigi-GagePluscanoperateasafloatcontrollerandalternatethepumpsunderfloatcontrolifsetupintriplexorduplexoperationsonly.TheDigi-GagePluscanalsoactasafloatmonitortoensurefloatsareoperatingcorrectlywhilethesystemisrunningwithtransducerlevelinput.

Page 6: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

6

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

SectionD I G I - G A G E P L U S U S E R M A N U A L

C O N T R O L L E R D A T A

Digi-Gage Plus™ Controller Data

22.1 Hardware Ratings:

Thehardwareratingsareasfollows:

Display 3.5″graphicaltouchscreendisplay Operating temperature 0to+60°C(32to140°F) Storage temperature -20to+60°C(-4to140°F) Relative humidity (RH) 10to95%(non-condensing) NEMA/IP rating NEMA4X/IP65/66 Voltage range 10.2to28.8VDC<10%ripple Power consumption npninputs280mA@24VDC pnpinputs190mA@24VDC Backlight20mA@24VDC Ethernetcard35mA@24VDC RelayOutputs(ea.)8mA@24VDC

SystemConfiguration:

Thecontrollerincludesanintegratedprocessor,embeddedI/O,colortouchscreenpanel,andfivesealedmembranefunctionkeys.SystemRatingsareasfollows:

•15µsscanrate •AdjustablewhiteLEDbacklightTFTLCDdisplay •Colors65,536(16-bit) •320x240pixelresolution •3.5″viewingarea;resistive,analogtouchscreen •Fivefunctionkeys,sealedmembraneswitch

Controllersupportsthefollowingfeatures:

•Remoteaccess •MicroSDcardbackup/upload/logging •Datalogging •OPCservercompliant •DDEformatread/write

Page 7: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

7

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R D A T A

System Processor:

•Removablememory:standardSDorSDHC(32GBmaximum) •Real-timeclock •Batterybackup(sevenyearstypicalat25°C) •Replaceable,coin-typelithiumbattery(CR2450)

Base Features:

•Inputvoltage24VDC •(22)digitalinputsrated24VDC(twoconfigurableasanalogcurrent/voltage) •12relayoutputsrated5Aat250VAC/30VDC •COM1port:RS232/RS485(upto32nodes) •COM2port:Ethernet

Communication Interfaces (optional):

COM1port:

•RS232/485baudratesbetween300and115,200bit/s •RS485upto32nodes/1200m(4000ft.)maximum •USB2.0compliant;fullspeed

COM2port:

•Ethernet

2.2 Process Features:

•Clean-out(flushmode)—simpletime-orcycle-basedconditions

•Fats,OilsandGrease(F.O.G.)builduppreventionmode

•Clogpreventionmode—simpletime-orcycle-basedconditionsupto3pumps.(Optionrequirestheadditionofreversingcontractors,pressurefeedback,andexpandedinputmodule;check with pump manufacturer to ensure reversing pump is allowed)

•Floats

•Pressure

•Level

Page 8: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

8

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R P R O C E S S F E A T U R E S

Process Features Continued:

•Flow

•Multi-functionalcontrol

•Pumpup

•Pumpdown

•Functioncombinations

•Advancedgroupingfeaturesupto3groups

2.3 Feature Details:

Six-PumpSystem:

•NouserselectableI/O—usestandardfixedI/Oassignments •Pump/blowergroupingfeature •Clogpreventionfeature •Greasebuildupfeature •Clean-outfeature

Five-PumpSystem:

•Allowsforthreeuser-selectableinputs •Allowsforoneuser-selectableoutput •Pump/blowergroupingfeature •Clogpreventionfeature •Greasebuildupfeature •Clean-outfeature

Four-PumpSystem:

•Allowsforsixuser-selectableinputs •Allowsfortwouser-selectableoutputs •Pump/blowergroupingfeature •Clogpreventionfeature •Greasebuildupfeature •Clean-outfeature

Page 9: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

9

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R F U N C T I O N A L I T Y

Three-PumpSystem:

•Allowsfornineuser-selectableinputs •Allowsforthreeuser-selectableoutputs •Pump/blowergroupingfeature(maximumofthreegroups) •Clogpreventionfeature(liftstationfeature) •Greasebuildupfeature(liftstationfeature) •Clean-outfeature(liftstationfeature) •Floatmonitoringfeature(liftstationfeature) •Ifenabled,fiveoftheuser-selectableinputswillbepredefinedasfloatfeedbackinputs

2.4 Controller Functionality:

•Supportsuptosixconstantspeedmotors(pumps,blowers,etc.)

•Alternation: •Alternateonmotorstop •Alternatetoequalizeruntime(indevelopment) •Fixanymotoraslead(noalternation) •Alternatemotorsindependentlywithineachgroup

•Levelsimulationtotestsetupfunctionandalarmsetpoints

•SCADAintegration

•Advancedgrouping: •Groupanynumberofthesixpumpsinuptothreegroups

•Controllercanberemotelyviewableandoperated

•Controllerstoresdatalocallythatcanbeviewedlocallyorremotely

•Controllerhaswebserverfeatures

•Controllercanbeconfiguredfordifferentmodesofoperation: •Pumpdown •Pumpup •Retro

•Controllerisconfigurableforselectablemonitoringmodes: •Floatsystemmonitoring •Backuptransducer •Sealwatersystemmonitoring

Page 10: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

10

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R F U N C T I O N A L I T Y

Controller Functionality Continued:

•Pumpmonitoring •Suctionpressure •Dischargepressure

•Calculatesinflowandoutflowdynamicallyingallonsperminuteorcubicfeetperminute(withcompatibleflowmeterinstalled)

•Controllerdisplaysthetotalpumporblowerrun-timehours,totalstarts,andstartsperhour

•Controllerallowsentryofwet-wellgeometryforflowcalculationswhennoflowmeterispresent.

•Relayoutputsforsystemfaults,pumpstart/stops,commonalarmsforhighandlowlevelsavailable

2.5 Typical Wiring Diagrams:

Digitalinputwiring

•TheDigi-GagePlus™controllerisbackwardcompatiblewiththeDigi-Gage2300,2400,and2600asmanufacturedbyEGControlsofJacksonville,Florida.

Page 11: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

11

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Analoginputwiring

Relayoutputwiring

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R W I R I N G D I A G R A M S

Page 12: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

12

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

SectionD I G I - G A G E P L U S U S E R M A N U A L

M O D E S O F O P E R A T I O N

Modes of Operation

33.1 Clean Out (Flush) Mode Description (For Lift Stations):

Thesystememploysuser-adjustabletime/cyclesetpointstoallowpumpstorunbeyondthenormallevelsetpointstoflushthewetwelltohelppreventabuildupofsolids.

Clean Out Theory of operation:

Astheliftstationoperatesbasedonconfiguredlevelsetpoints,thepumpsgothroughtheautomatedoperationstopumpdowntheliftstationtotheconfiguredlow-levelpumpshutoffsetpoint.Ascreenisprovidedfortheuserconfiguredpumpdowncycles,num-berofdaysofoperation,andaClean-Out(enable/disable)mode.

Oncethismodeisenabledandthenumberofcyclesornumberofdaysisconfigured,thesystemwilloperateasfollows:

Oncetheuser-configuredsetpoint(eitherthenumberofcyclesornumberofdays)isreached,thesystemwillignorethenormalstart/stoppumpsetpointsandallowthestationtofilltotheflushhigh-levelsetpoint.Oncethisflushhighlevelisreached,thesystemwillstarttheuser-selectedavailablepumpstopumpdowntheliftstationandflushthestationwetwell.

3.2 Anti-F.O.G. Mode Description (For Lift Stations):

Thisfeatureprovidesthesystemwithavaryingstartlevel(percentagebased)modetohelppreventF.O.G.(Fats,Oils,Grease)buildupduetothewet-welllevelreachingthesamepoint,causinganaccumulationofF.O.G.onthesidesoftheliftstation.

Ascreenisprovidedfortheusertoenable/disablethisfeatureandtosetthepercentagevariationallowedtothelevel.

ATTENTION:Useofthisfeaturerequiresunderstandingofliftstationandpumpoperations.Thisfeatureshouldbesetupbyqualifiedpersonneltoensureproperfunctionalityandpreventpotentialdamagetopumpsandlift-stationhardware.

Page 13: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

13

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Anti-F.O.G. Theory of operation:

WhentheAnti-F.O.G.modeisenabled,thepercentagevariableisset.Eachtimethepumpdowncycleisinitiated,thesystemwilladjusttheuser-definedlevelsetpointbythepercentageenteredintothevariancefield.Thenextcyclewillwaituntilthis“calculated”levelvalueisreachedandstartthepumpdowncycle.Thesystemwillrunthroughaseriesofthesecalculationstoallowasemi-randomlevelforstartingthepumpdowncycle.

Anti-F.O.G.willnotnecessarilyreducetheamountofmatteronthewellwalls.Anti-F.O.G.willeliminate“shelves”ofmatterbuildingup.

3.3 Clog Prevention Mode (Key Shaft Pumps Only):

Thisfeatureprovidesanautonomousmeansofhelpingtopreventclogsthatbuilduponapump’simpeller.

Clog Prevention Theory of Operation:

Ascreenisprovidedtoenable/disabletheClogPreventionmode.Thede-matteroperationisbasedonaconfigurablenumberofpumpingcy-clesornumberofdays.Oncethismodeisenabledandthenumberofcyclesornumberofdaysisset,thesystemwilloperateasnormaluntilthesetpointisreached.Aclogpreventioncyclewillinitiate,andthepumpwillreversedirectionandthenrunforward(basedonthenumberofcyclessetbytheuser)toattempttocleanthepumpimpeller.Thisisanopen-loopautomaticmodethatdoesnotuseanyfeedbacktodetermineaclogormatterbuildup.

ATTENTION:Useofthisfeaturerequiresunderstandingofliftstationlevels.Thisfeatureshouldbesetupbyqualifiedpersonneltoensureproperfunctionalityandpreventnuisanceactivationoffloatbackupoperations.

ATTENTION:Ensurethatreversefunctionisavailablefromthepumpmanufacturer.Useofthisfeaturewithoutkey-shaftedpumpscandamagepumps!

ATTENTION:Useofthisfeaturerequiresadditionalreversingstartersandhardwareinstalledinthecontrolpanel.

ATTENTION:Thisoptionworksonsystemsof3pumpsorless.

D I G I - G A G E P L U S U S E R M A N U A LM O D E S O F O P E R A T I O N

Page 14: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

14

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Section

4Digi-Gage Plus™ Front Bezel

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R F R O N T B E Z E L

Buttons:

HOME AUTO PROG SIM ESC

2

1

3

4

5

Returnstothetraditionalsystemstatusscreen

Terminatessimulationcontrol

DisplaystheSystemMenuscreen

DisplaystheSimulateLevelscreen

Returnstopreviousscreenor“back”button

Thesefiveblisterbuttonsareavailabletotheoperatoratanytime,fromanyscreen.

HOME

AUTO

PROG

SIM

ESC

Page 15: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

15

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.1 System Status / Home

1

2

3

4

5

11

6

7

10

9

8

1.Alarmstatus2.Sensorinuse3.Level:units(PSI,DO,FT,GPM)fortheprocessvalueassignedtothegroupdisplayed4.ScaledProcessValue:currentmeasurement;presstodisplaytheSystemStatusdetailedscreen.(4.2.1)5.BarGraph:scaledas0%–100%oftheprocessvalue6.LagPump(s)Status:white(Off),blinkingred(Starting),solidred(Running)7.LeadPumpStatus:white(Off),blinkingred(Starting),solidred(Running)8.MixerStatus:white(Off),solidred(Running)9.Low-LevelIndicator:solidred(Low-LevelAlarm)10.High-LevelIndicator:solidred(High-LevelAlarm)11.GroupStatus:displayscurrentgroupSystemStatus;presstotogglebetweentheconfiguredgroups(typicalofeachgroup;maximumofthreegroups)

Page 16: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

16

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.2.1 System Status (detailed) with 1 or 2 transducers

1

2

3

4

7

8

5

6

1.Measuredoutputoftransducer1ifpresent2.Pumpidentifier3.Startingidentifier4.Motorstatus5.Hourmeter6.Mixerstatusifpresent7.Alarmstatus8.Measuredoutputoftransducer2ifpresent blisterbuttonsnavigateoffthisdisplayHOME PROG ESC

Page 17: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

17

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.2.2SystemStatus(detailed)withfloatsonly

1

2

3

4

5

1.Statusofeachofthe6Floatsneededforpropercontrolofthepumps:•HighFloat:HighWetWellLevelAlarmFloat•LAG2Float:2ndLagPumpcalltoRunFloat•LAG1Float:LagPumpcalltoRunFloat•LeadFloat:LeadPumpcalltoRunFloat•StopFloat:PumpStopFloat•LowFloat:LowWetWellLevelAlarmFloat2.FloatStatusKey:REDFloatnotTipped;GREENFloatisTipped3.PumpNameasdefinedintheControlSetupscreensdisplayshere4.StatusofthePump;RUNNINGorSTOPPED5.PumpH-O-ASwitchstatus:AUTO,NOTAUTO blisterbuttonsnavigateoffthisdisplayHOME PROG ESC

Page 18: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

18

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.2.3RetroConfiguration1

2

34

5

10

8

9

7

6

1.Units(PSI,DO,FT,GPM)fortheProcessValueassignedtotheGroupsetintheengineeringscreens2.ScaledProcessValuecurrentmeasurement3.Abargraph,scaledas0-100%oftheProcessValue-4.PurgeCycleStatus:whiteoff,solidredPurgeinProgress(AvailableonTriplexandQuadplex)5.IsolationValveStatus:whiteValveOpen,solidredValveClosed(AvailableonTriplexandQuadplex)6.LagPump(s)Status:whiteoff,blinkingredStarting,solidredRunning7.LeadPumpStatus:whiteoff,blinkingredStarting,solidredRunning8.lowlevelindicator:solidredLow-LevelAlarm9.Highlevelindicator:solidredHigh-LevelAlarm10.DisplaysthePurgesetupscreen(AvailableonTriplexandQuadplex)(4.7.10)

Page 19: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

19

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.3 System Menu

101

2

3

4

8 97

5

6

11

13

12

1.SystemStatus:displaystheSystemStatushomescreen(4.1)2.PumpDetails:displaysPumpDetailsscreen(4.4)3.ProcessTrend:displaystheProcessTrendscreen(4.5)4.SystemFlow:displaystheSystemFlowscreen(4.6)5.ControlSetup:displaystheControlSetupscreen(4.7)6.PumpAltMode:displaystheAlternationSetupscreensforeachconfiguredgroup(4.8)7.SimulateLevel:displaystheSimulationLevelscreenforgroupprocessvariable(4.9)8.SystemDiag:Displaysinputandoutputstatus(4.10)9.HornSilence:silencesthehorninanalarmcondition10.AlarmSetup:displaystheAlarmSetupscreenforeachoftheconfiguredgroups(4.11)11.ActiveAlarms:displaystheActiveAlarmspop-upscreen(4.12)12.AlarmHistory:displaystheAlarmHistoryscreen(4.13)13.AlarmReset:resetsthealarmlogiciftheconditionhasbeencleared

Page 20: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

20

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.4 Pump Details

10

1

2

3

4 8

9

7

5

6

1.PumpName:displayspumpname,asdefinedintheControlSetupscreen2.PumpH-O-ASwitchStatus:displaysAutowhencontrolpanelisinAuto.DisplaysNotAutowhencontrolpanelisinOfforHand.3.GroupandPosition:thegroupthepumpbelongstoandthepump’spositioninthealternationsequenceofthatgroup4.StatusofthePump:RunningorStopped5.PresstotoggleEnabledorDisabled6.Displaysthenumberoftotalstarts7.Displaysthenumberofstartsperhour8.Elapsedtimemeter9.Next:displaysthenextPumpDetailsscreen(typicalforeachPumpDetailscreen;maximumoffivepumps)10.Menu:displaystheSystemMenuscreen(4.3)

Page 21: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

21

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.5 Process Trend

1.TrendName:groupprocessvalueandflowmeter,ifconfigured2.Trendoftheprocessvalue3.TapScreen:togglesbetweengroupsandflowmeter(maximumthreegroups)4.TogglestheScrollbuttonsOnandOff5.TogglesthegridOnandOff6.Trendaperture.Thisissetupin4.7.6ifthefluidlevelisoutsideofthisrange,nothingwillbedisplayed7.Menu:displaystheSystemMenuscreen(4.3)8.Scalebutton:SetupTrendScaling(4.5.1)9.Selectedengineeringunit(PSI,DO,FT,GPM)

1

2

3

4

7

5

6 89

Page 22: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

22

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.5.1 Process Trend: Automatic Trend Scaling

1.Closebutton:returnstoTrending(4.5)2.ScaleSPChange:Togglebetweenautomaticandmanual(4.5.2)

12

Page 23: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

23

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.5.2 Process Trend: Manual Trend Scaling

1.Closebutton:returnstoTrending(4.5)2.ScaleSPChange:Togglebetweenautomaticandmanual(4.5.1)3.SetmanualsetpointsMinandMax

12

3

Page 24: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

24

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.6SystemFlow:Withattachedflowmeter

1.Displaysthecurrentreadingfromtheflowmeter2.Menu:displaystheSystemMenuscreen(4.3)

1

2

Page 25: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

25

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.6.1 System Flow: Flow based on calculations

1.CalculatedDischargeFlowinGPM:calculatedwhenapumpcomesonlineandpumpsdownthewell2.CalculatedIn-FlowinGPM:calculatedbythetimeittakestofillthewell3.Menu:displaystheSystemMenuscreen(4.3)

12

3

Page 26: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

26

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7 Control Setup: Login

1.Presstoinputpassword:______contactyourrepforyourpassword2.Ifcorrectpasswordisentered,SystemSetupbuttonappears;presstodisplaythefirstSystemConfigurationscreen3.Menu:displaystheSystemMenuscreen(4.3)

1

2

3

Page 27: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

27

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.1 Control Setup: Login (continued)

1.Passwordwillbedisplayedtoindicateithasbeenaccepted2.PresstoenterSystemSetup(4.7.1)3.Menu:displaystheSystemMenuscreen(4.3)

1

2

3

Page 28: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

28

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.2ControlSetup:SystemConfiguration

1

2

3

45

6

7

1.SystemClock:displaysthecurrenttimeinthecontroller;presstochangethetime2.SystemClock:displaysthecurrentdateinthecontroller;presstochangethedate3.StartDelayAfterPowerUp:thedelay,inseconds,beforestartingpumpsafterpoweruporresetfromfloatcontrol;presstoenteranewvalue4.StopTrendtoSDCard:presstostoreprocessdatatoanSDcard(anSDcardmustbeinstalled)5.ThecontrollerdetectstheexistenceofanSDcardanddisplaystheresults6.DelayBetweenPumpStarts:thedelay,inseconds,betweenpumpstarts(preventssimultaneousstartsifmorethanonepumpiscalledatthesametime);presstoenteranewvalue7.Next:displaysthenextconfigurationscreen(4.7.3)

Page 29: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

29

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.3 Control Setup: Network Setup

1.CurrentEthernetaddress;presstoenteranewEthernetaddress2.Currentsubnetmask;presstoenteranewsubnetmask3.Currentgatewayaddress;presstoenteranewgatewayaddress4.TheControllerwilldetecttheEthernetcardanddisplaytheresults5.CurrentModbusaddress;presstoenteranewModbusad-dress6.Next:displaysthenextconfigurationscreen(4.7.4)7.ResetPLC:Foranymodificationsonthisscreentocomplete,thepowermustbecycled.PressingResetPLCwillfinalizethisprocess.

1

2

3

4 5

6

7

ATTENTION:CyclepowertothecontrollertosavetheEthernetaddress.

Page 30: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

30

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.4 Control Setup: Group Naming

1.Thelabelforeachgrouptobenamed2.Presstosetname;nine-charactermaximumforeachgroup;thenameswilldisplayonnumerousscreens3.Next:displaysthenextconfigurationscreen(4.7.5)

1

2

3

Page 31: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

31

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.5 Control Setup: Motor Naming

1.Thelabelforeachmotortobenamed2.Presstosetname;seven-charactermaximumforeachmotor;thenameswilldisplayonnumerousscreens3.Next:displaysthenextconfigurationscreen(4.7.6)

1

2

3

Page 32: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

32

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.6ControlSetup:MixerSetup(iffactoryconfigured)

1.Selectwhenthemixercanrun:•Pumpsarestopped•Pumpsarerunning•Anytime2.TimeControl:controlsthemixerbasedontime3.Thenumberofminutesthemixerruns4.Thenumberofminutesthemixerisoff5.LevelControl:selecttocontrolthemixerbaseonlevelsetpoints6.Thestartlevelforthemixer7.Thestoplevelforthemixer8.Next:displaystheSystemMenuscreen(4.7.7)

1

2

4

63

7

5

8

Page 33: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

33

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.7 Control Setup: Process Sensor Setup

1.Presstosetlevelvaluefor4mAsignal;thisdeterminestheminimumvaluefortheprocessvaluethecontroller’smeasure-ments2.Presstosetlevelvaluefor20mA;thisdeterminesthemaxi-mumvaluefortheprocessvaluethecontroller’smeasurements3.ResponseTrigger:avaluebetween0and5thatcorrespondstosamplingdelayof0–250mS;presstosetvalueforthesamplerateforthecontrollertoreadtheprocessvalue4.AnalogInput:scaledvalueofthesensorinmA5.ScaledValue:engineeringunitsbasedontheinputsabove6.Selectedengineeringunit(PSI,DO,FT,GPM)7.Thegrouporflowmeterassignedtotheprocessvalve8.Next:displaysthenextconfigurationscreen(4.7.8)

Note:ThisscreenistypicaltotheProcessSensorNo.2Scalingscreen.

1

2

3

4

8

56

7

Page 34: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

34

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.8 Control Setup: Group Set Points

1.Presstoentertheleadpumpstartlevelsetpoint(typical)2.Presstoentertheleadpumpstoplevelsetpoint(typical)3.Displaystheconfiguredengineeringunits4.Next:displaysthenextconfigurationscreen(4.7.9)

1

2

3

4

Page 35: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

35

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.9ControlSetup:FlushControl(iffactoryconfigured)

1.Displaysthecurrenttime2.Statusoftheflushprotocol:Stopped,WaitingonLevel,orRunning3.Startsetpointforleveloftheflush;presstochangethevalue4.Hourtostarttheflush;presstochangethevalue5.Dayoftheweektoruntheflush:Monday,Tuesday,Wednes-day,Thursday,Friday,orDisable6.PresstheUporDownarrowstochangethedayofweek7.Stopsetpointforleveloftheflush;presstochangethevalue8.Start:startstheflush,overridingtheautomaticconfiguration9.Stop:stopstheflush,overridingtheautomaticconfiguration10.BarGraph:displaystheactualwelllevel11.Next:displaysthenextconfigurationscreen(4.7.10)12.Menu:displaystheSystemMenuscreen(4.3)13.Numberofflushcyclesperformed14.Numberofpumpsselected-thisislimitedtothenumberofpumpsinthegroup

10

1

2

4

6

8 9

7

3

5

12

11

14

13

Page 36: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

36

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.10ControlSetup:F.O.G.Reduction(iffactoryconfigured)

1.LeadStartLevelRangebutton:Presstoenteravalue.IfthevalueexceedstheLag1StartLevelset-pointtheenteredvaluewillbeautomaticallyadjustedbelowtheLag1set-point.2.DescriptionandinstructionontheF.O.G.Reductionfeature3.NEXTbuttondisplaysGroup2LevelSetPointscreen.IfonlyoneGroupisconfiguredtheMainMenuisdisplayed(4.3)

1

2

3

Page 37: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

37

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.7.11ControlSetup:PurgeSetup(iffactoryconfigured)

1.ManualPurgebutton:PresstotriggeraPurgeCycle2.StartHour:Presstoenteravaluefrom0(Midnight)to24(Disable)3.DisplaysthecurrentconfiguredStartHour4.Exitbutton:PresstoclosethePop-upScreen(4.3)

1

2

3

4

Page 38: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

38

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.8 Control Setup: Pump Alternation Mode (in development)

1.LabelsasdefinedinProcessMotorNames(see4.7.5)andtheirpositionsinthealternationschema2.PresstoChangeAlternationMode:togglesbetweenanumberofmodes,dependingonthenumberofpumpsconfiguredforthegroup.Possiblemodes:•AlternateonPumpStop•AlternatetoEqualizePumpRuntime•Motor1LeadNoAlternation•Motor2LeadNoAlternation•Motor3LeadNoAlternation•Motor4LeadNoAlternation•Motor5LeadNoAlternation•Motor6LeadNoAlternation3.DisplayscurrentAlternationmode4.EnterOffsetSP:displaystheAlternatetoEqualizePumpRun-Timemode;presstoentervalue5.Menu:displaystheSystemMenuscreen(4.3)

1

2

4

3 5

Page 39: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

39

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.9 Simulation

1.Selectapumpgroupforsimulation(4.9.1)2.ClosereturnstotheSystemMenu(4.3) blisterbuttonwillalsonavigatedirectlytothisscreen.

1

2

SIM

Page 40: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

40

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.9.1 Simulation

1.BarGraph:displaystheactuallevel2.BarGraph:displaysthesimulatedlevel3.PumpConfigurations:•DisplayspumpnameasdefinedintheControlSetupscreens•Thegroupnumberthepumpbelongstoandthepump’spositioninthealternationsequence•Statusofthepump:RunningorStopped•PumpH-O-Aswitchstatus:AutoorNotAuto4.LevelUp:increasestheSimulationLevelbyone-tenthofaunit5.LevelDown:decreasestheSimulationLevelbyone-tenthofaunit6.ExitSimulation:exitsSimulationLevelscreenandreturnstheprocessvalueinputasthecontrollingsignal7.Menu:displaystheSystemMenuscreen(4.3)

675

1

2

4

3

Page 41: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

41

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.10 System Diag: Digital Inputs

1.Nextbutton:todisplayDigitalOutputs(4.10.1)

1

Page 42: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

42

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.10.1 System Diag: Digital Outputs

1.Menubutton:ReturnstoSystemMenu(4.3)

1

Page 43: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

43

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.11 Alarm Setup: Level Set Point by Group

1.Presstosetgroup1high-levelalarmsetpoint2.Presstosetgroup1low-levelalarmsetpoint3.Presstosetgroup2high-levelalarmsetpoint4.Presstosetgroup2low-levelalarmsetpoint5.Presstosetgroup3high-levelalarmsetpoint6.Presstosetgroup3low-levelalarmsetpoint7.Next:displaysthesecondAlarmSetupscreen(4.11.1)8.Menu:displaystheSystemMenuscreen(4.3)

Thenumberofgroupssetupwillbedisplayed

8

6

7

5

1

2

4

3

Page 44: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

44

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.11.1 Alarm Setup: Starts Per Hour

1.Presstosetpump1startsperhoursetpoint2.Presstosetpump2startsperhoursetpoint3.Presstosetpump3startsperhoursetpoint4.Presstosetpump4startsperhoursetpoint5.Presstoreturnthemainmenu(4.3)6.Presstosetpumps5and6thennextAlarmSetupscreen(4.11.2)

6

5

1

2

4

3

Page 45: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

45

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.11.2 Alarm Setup: Alarm Bypass

1.PresstosetDisable/EnableGroup1Highlevel2.PresstosetDisable/EnableGroup1Lowlevel3.PresstosetDisable/EnableGroup2Highlevel4.PresstosetDisable/EnableGroup2Lowlevel5.PresstosetDisable/EnableGroup3Highlevel6.PresstosetDisable/EnableGroup3Lowlevel7.Presstoreturntothemainmenu(4.3)

7

6

5

1

2

4

3

Page 46: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

46

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.12 Active Alarms: Groups with Pending Alarms

1.Displaysalarmgroupdetails(4.12.1)2.AlarmRefresh:presstoreset;thealarmwilltriggeragainiftheconditionthatcausedthealarmstillexists3.Esc:returnstothepreviousscreen(4.3)

1

2

3

Page 47: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

47

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.12.1 Active Alarms: Alarms in Group

1.Displaysalarmdetails(4.12.2)2.AlarmRefresh:presstoreset;thealarmwilltriggeragainiftheconditionthatcausedthealarmstillexists3.Esc:returnstothepreviousscreen(4.12)

1

2

3

Page 48: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

48

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.12.2 Active Alarms: Alarm Details

1.Priority:displaysprioritylevelofthealarm2.Group:displaysalarm’sgroupIDnumber3.Alarmgroupname4.Alarm’sID5.Alarm’sname6.Dateandtimestampwhenthealarmbecameactive7.Dateandtimestampwhenthealarmbecameinactive8.Dateandtimestampwhenthealarmwasacknowledged9.Dateandtimestampwhenthealarmwasreset10.Timestampofthedurationofalarmevents(active,inactive,acknowledged,andreset)11.Navigation:scrollsbetweenalarms12.Esc:closestheAlarmHistoryscreen(4.12.1)

10

1

2

4

6

8

9

7

3

5

12

11

Alarm Details

Page 49: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

49

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Display:

D I G I - G A G E P L U S U S E R M A N U A LC O N T R O L L E R S C R E E N S

4.13 Alarm History

1.Priority:displaysprioritylevelofthealarm2.Group:displaysalarm’sgroupIDnumber3.Alarmgroupname4.Alarm’sID5.Alarm’sname6.Dateandtimestampwhenthealarmbecameactive7.Dateandtimestampwhenthealarmbecameinactive8.Dateandtimestampwhenthealarmwasacknowledged9.Dateandtimestampwhenthealarmwasreset10.Timestampofthedurationofalarmevents(active,inactive,acknowledged,andreset)11.Navigation:scrollsbetweenalarms12.Esc:closestheAlarmHistoryscreen(4.3)

10

1

2

4

6

8

9

7

3

5

12

11

Page 50: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

D I G I - G A G E P L U S U S E R M A N U A LS C R E E N N A V I G A T I O N M A P

50

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

5Section

System Menu Screen Navigation

5

PUMP DETAILS

PROCESS MOTOR NAMES

SYSTEM STATUS /

HOME

GROUP 2 MAIN

SYSTEM STATUS / DETAILED

GROUP 3 MAIN

PUMP 2 DETAILS

PUMP 3 DETAILS

PUMP 4 DETAILS

PUMP 5 DETAILS

PUMP 6 DETAILS

PROCESS TREND

GROUP 2 TREND

GROUP 3 TREND

FLOW- METER TREND

SYSTEM FLOW

GROUP 2 TREND

GROUP 3 TREND

CONTROL SETUP

LOGIN

SYSTEM CONFIG

ETHERNET IP

GROUP NAMING

MIXER SETUP

PROC SENSOR 1 SCALING

PROC SENSOR 2 SCALING

GROUP 1 LEVEL

SETPOINTS

GROUP 1 FLUSH

CONTROLS

GROUP 1 F.O.G.

CONTROLS

GROUP 2 LEVEL

SETPOINTS

GROUP 2 FLUSH

CONTROLS

GROUP 2 F.O.G.

CONTROLS

GROUP 3 LEVEL

SETPOINTS

GROUP 3 FLUSH

CONTROLS

GROUP 3 F.O.G.

CONTROLS

Navigation of Displays

ButtonwilldisplaythesystemmenuscreenPROG

Page 51: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

D I G I - G A G E P L U S U S E R M A N U A LS C R E E N N A V I G A T I O N M A P

51

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

PUMP ALT MODE

GROUP 2 CONFIG

GROUP 3 CONFIG

ALARM RESET

HORN SILENCE

ALARM HISTORY

ACTIVE ALARMS

ALARM SETUP

ALARM SETUP

GROUP 2

SYS DIAG DIGITAL INPUTS

ALARM SETUP

GROUP 3

MOTOR STARTS

PER HOUR

MOTOR STARTS

PER HOUR

SYS DIAG DIGITAL

OUTPUTS

SIMULATE LEVEL

GROUP 1 SIMULATION

SIMULATION FOR GROUP SELECTED

GROUP 2 SIMULATION

GROUP 3 SIMULATION

Navigation of Displays

Buttonwilldisplaythesystemmenuscreen

ButtonwilldirectlyenterthesimulationareaSIM

PROG

Page 52: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

52

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Section

Typical Wiring by Configuration

6D I G I - G A G E P L U S U S E R M A N U A L

W I R I N G C O N F I G U R A T I O N S

Wiringconfigurations:

ThefollowingpagesshowfullpageterminationsforSimplex,Duplex,Triplex,Quadplex,Fiveplex,Sixplex,FloatOnlyandRetroconfigura-tions.

Page 53: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

53

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

SimplexConfiguration:

D I G I - G A G E P L U S U S E R M A N U A LW I R I N G C O N F I G U R A T I O N S

Please note:

NotUsedalsomeansNotAvailabletothefactorysetconfiguration.

Page 54: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

54

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LW I R I N G C O N F I G U R A T I O N S

DuplexConfiguration:

Please note:

NotUsedalsomeansNotAvailabletothefactorysetconfiguration.

Page 55: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

55

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

TriplexConfiguration:

D I G I - G A G E P L U S U S E R M A N U A LW I R I N G C O N F I G U R A T I O N S

Please note:

NotUsedalsomeansNotAvailabletothefactorysetconfiguration.

Page 56: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

56

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LW I R I N G C O N F I G U R A T I O N S

QuadplexConfiguration:

Please note:

NotUsedalsomeansNotAvailabletothefactorysetconfiguration.

Page 57: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

57

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

FiveplexConfiguration:

D I G I - G A G E P L U S U S E R M A N U A LW I R I N G C O N F I G U R A T I O N S

Please note:

NotUsedalsomeansNotAvailabletothefactorysetconfiguration.

Page 58: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

58

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LW I R I N G C O N F I G U R A T I O N S

SixplexConfiguration:

Please note:

NotUsedalsomeansNotAvailabletothefactorysetconfiguration.

Page 59: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

59

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

FloatsOnlyConfiguration:

D I G I - G A G E P L U S U S E R M A N U A LW I R I N G C O N F I G U R A T I O N S

Please note:

NotUsedalsomeansNotAvailabletothefactorysetconfiguration.

Page 60: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

60

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LW I R I N G C O N F I G U R A T I O N S

RetroConfiguration:

Please note:

NotUsedalsomeansNotAvailabletothefactorysetconfiguration.

Page 61: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

61

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Appendix

Glossary / Index

GD I G I - G A G E P L U S U S E R M A N U A LG L O S S A R Y

% DO EngineeringUnit:Percentagedissolved oxygen

20mA Value Maximumscaledvaluewhentheprocess valueisat20mA

4mA Value Minimumscaledvaluewhentheprocessvalueis at4mA

Ack. Time Timetakentoacknowledgethealarm

Alarm Asystemorequipmentfault

Alarm ID Identificationnumberassociatedwithanalarm

Alarm Name Thenameofanalarm

Alternate Sequencemotoroperationtoshareleadposition

Analog Input ProcessvalueinmA

Auto Thesetconditionforthecontrollerto automaticallystart/stopmotor(s)

Duration Howlonganeventtookplace

Equalize Alternationsettingtobalancetheruntimehours betweenmotors

Ethernet (IPAddress)Auniquenumberassignedtoa Address devicetocommunicateonanetwork

Ethernet Card Hardwaremodulefornetworkcommunications

Pages 15,18,21,33

Page 33

Page 33

Pages 48, 49

Pages 9, 10, 15, 16, 19, 43-49, 68,69

Pages 46-49

Pages 46-49

Pages 5, 9, 38

Pages 7, 11, 33

Pages 17, 20, 22, 23, 40

Pages 48, 49

Pages 9, 38

Page 29

Pages 6, 29

Page 62: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

62

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

External Float Floatcontrolsystemtorunpumpswithout Control thecontrollerinput

Flow meter Adevicethatcalculatesflowofmaterial

Flush Aprotocolmeanttopumpalargevolumeoffluid atonetimetoclearanyrestrictionsinthepipes

Flush Start Theflushprotocolstartsetpoint

Flush Stop Theflushprotocolstopsetpoint

F.O.G. Fats,OilsandGrease

Ft EngineeringUnits:LevelmeasuredinFeet

Gateway ArouterinterfaceconnectedtothelocalnetworkAddress thatsendsdatapacketsoutofthelocalnetwork

GPM EngineeringUnits:GallonsPerMinute

Group 1 Thefirstgroupingofmotors(1-6)

Group 2 Thesecondgroupingofmotors(1-5)

Group 3 Thethirdgroupingofmotors(1-4)

Group ID Identificationnumberagroupassociatedwithan alarm

Group Name Thenameofthegroup

Hand Thesetconditionmanuallystart/stopmotor(s)

High-Level Levelsetpointtotriggerahighlevelalarm

Horn Theaudiblenoiseassoicatedwiththealarm

D I G I - G A G E P L U S U S E R M A N U A LG L O S S A R Y

Pages 19, 21, 24, 52, 33

Pages 7, 12, 35

Page 35

Page 35

Pages 7, 12, 13, 36

Pages 15, 18, 21, 33

Page 29

Pages 15, 18, 21, 25, 33

Groups are covered on pages 8, 9, 15, 18, 19, 20, 21, 30, 33-36, 38-40, 43, 45-49

Page 20

Pages 12, 18, 45

Page 19

Page 63: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

63

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Internal Float Floatcontrolsystemtorunthepumpswith Control controllerinput

Lag 1 Secondmotortostartinthequeue

Lag 2 Thirdmotortostartinthequeue

Lag 3 Forthmotortostartinthequeue

Lag 4 Fifthmotortostartinthequeue

Lag 5 Sixthmotortostartinthequeue

Lead Firstmotortostartinthequeue

Level Theheightmeasurementoftheprocessliquid

Low-Level Measurementdeemedtoolowforappropriate function

Mixer Asingleoutputtocontrolablowerormixer basedontimeorlevel

Modbus Atypeofindustrialcommunicationprotocol overseriallinesbetweenelectronicdevices

Off Thesetconditionmanuallykeepingmotor(s) fromrunning

Priority Theseverityofatriggeredalarm

Process Sensor Adevicethattakesthemeasurementsandgives ananalogvaluetothecontroller

PSI EngineeringUnit:PressureperSquareInch

Pump Delay Theamountoftimethedevicewillwaitbefore turningonapumpormotor

Pump Down ReadslevelandpumpswateroutofthewellControl whenwaterlevelsaretoohigh

D I G I - G A G E P L U S U S E R M A N U A LG L O S S A R Y

Page 28

Lead / Lag is covered on pages 9, 15, 17, 18, 34, 36, 38

Pages 7, 9, 10, 12-15, 17-19, 21, 32-36, 40, 43, 45

Pages 12, 15, 18, 43

Pages 15, 16, 32

Pages 29, 65-67

Pages 48, 49

Page 33

Pages 15, 18, 21, 33

Page 64: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

64

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Pump Up UsespressuretodetectwhenwaterlevelsareControl lowandpumpswaterbackintothewell

Queue Asequenceofmotors

Reset Time Timetakentoresetafteranalarm

Response Adelayintheprocessvaluesampling(0-250)inTrigger Value miliseconds

Running Feedbacktothecontrollerthemotorisin operation

Scaled Value ProcessvaluedisplayedinEngineeringUnits

Start Delay Theminimumtimebetweenpumpstarts

Start Set Point Theprocessvaluehasreachedacondition wherethemotoriscalledtostart

Stop Set Point Theprocessvaluehasreachedacondition wherethemotoriscalledtostop

Stopped Feedbacktothecontrollerthemotorisnotin operation

Subnet Mask AnumberthatdefinesarangeofIPaddresses availablewithinanetwork

Trigger Rise Dateandtimestampwhenthealarmbecame Time active

Trigger Fall Dateandtimestampwhenthealarmbecame Time inactive

D I G I - G A G E P L U S U S E R M A N U A LG L O S S A R Y

Pages 48, 49

Pages 33, 37

Pages 15, 17, 18, 20, 32, 35, 40

Page 33

Page 28

Page 35

Page 35

Pages 17, 20, 32, 35, 40

Page 29

Pages 17, 33

Pages 17, 33

Page 65: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

65

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

Appendix

MModbus Registers

D I G I - G A G E P L U S U S E R M A N U A LM O D B U S R E G I S T E R S

Register Definition

MB 300 PhaseLoss

MB 301 FloatBackupActive

MB 302 Pump1Running

MB 303 Pump1Auto

MB 304 Pump1FaultorOver-tempAlarm

MB 305 Pump2Running

MB 306 Pump2Auto

MB 307 Pump2FaultorOver-tempAlarm

MB 308 Pump3Running

MB 309 Pump3Auto

MB 310 Pump3FaultorOver-tempAlarm

MB 311 Pump4Running

MB 312 Pump4Auto

MB 313 Pump4FaultAlarm

MB 316 Pump5Running

MB 317 Pump5Auto

MB 318 Pump5FaultAlarm

MB 319 Pump6Running

MB 320 Pump6Auto

MB 321 Pump6FaultAlarm

Page 66: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

66

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

MB 322 Pump1SealFail

MB 323 Pump2SealFail

MB 324 Pump3SealFail

MB 680 LeadFloatInput

MB 681 StopFloatInput

MB 682 LowLevelFloatInput

MB 683 Lag1FloatInput

MB 684 Lag2FloatInput

MB 685 3orLessPumps

MB 686 HighFloatInput

MB 330 Pump1Start/Stop

MB 331 Pump2Start/Stop

MB 332 Pump3Start/Stop

MB 333 Pump4Start/Stop

MB 334 Pump5Start/Stop

MB 335 Pump6Start/Stop

MB 336 HighLevelAlarmTriggerbyXdcr

MB 337 LowLevelalarmbyXdcr

MB 338 CommonAlarmLight

MB 340 PLCFaultedorPurgeCycle

MB 341 MixerControlorRetroIsolationSolenoid

MI 304 Pump1RunHrstoHMI

MI 305 Pump2RunHrstoHMI

MI 306 Pump3RunHrstoHMI

D I G I - G A G E P L U S U S E R M A N U A LM O D B U S R E G I S T E R S

Page 67: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

67

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

MI 307 Pump4RunHrstoHMI

MI 308 Pump5RunHrstoHMI

MI 309 Pump6RunHrstoHMI

MI 43 Group1LevelSignal

MI 75 Group2LevelSignal

MI 176 Group3LevelSignal

D I G I - G A G E P L U S U S E R M A N U A LM O D B U S R E G I S T E R S

Page 68: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

68

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LA L A R M S

Alarms

AAppendix

Alarm Definition

000 AlarmG1HighLevel

001 AlarmG1LowLevel

002 Pump1FailtoStart

003 Pump2FailtoStart

004 P1CommonAlarmorOver-temp

005 P2CommonAlarmorOver-temp

006 HighFloat

007 Phase

008 FloatsEnabled

009 AnalogSignaloutofRangeorHighFloatInput

010 Pump1Starts/HrExceeded

011 Pump2Starts/HrExceeded

012 AnalogSignal1outofRange

013 G2HighLevelAnalog

014 AlarmG2LowLevelAnalog

015 LowFloat

016 Pump1SealFailure

017 Pump2SealFailure

018 Pump3SealFailure

019 Pump3FailedtoStart

Page 69: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing

69

EG Controls Digi-Gage Plus User Manual - Version 012720-DG+UM-TJ

D I G I - G A G E P L U S U S E R M A N U A LA L A R M S

020 P3CommonalarmorOver-temp

021 Pump3Starts/HrExceeded

022 G3HighLevel

023 G3LowLevel

024 Pump4FailedtoStart

025 Pump5FailedtoStart

026 Pump6FailedtoStart

027 Pump4CommonAlarmorSealFail

028 Pump4Starts/HrExceeded

029 Pump5Starts/HrExceeded

030 AlarmP6Starts/HrExceeded

Page 70: Digital Constant Speed Controller · G Controls Digi-Gage Plus ser Manual - ersion 012720-DGM-1 DIGI - GAGE PLUS USER MANUAL Section INTRODUCTION Introduction Thank you for purchasing