  • DIgSILENT Project: PowerFactory 14.1.3 Date: 9/22/2015 Load Flow Calculation Busbars/Terminals AC Load Flow, unbalanced, 3-phase (ABC) Automatic Model Adaptation for Convergence No Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for Consider Reactive Power Limits No Nodes 1.00 kVA Model Equations 0.10 % Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 1 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] Substation 115.00 1.00000 66.39528 0.00000 1.00000 66.39528 -120.00000 1.00000 66.39528 120.00000 Cub_2 /Xnet External Grid A 1.34 0.59 0.91 0.02 Sk": 23.88 MVA B 0.96 0.48 0.89 0.02 C 1.25 0.21 0.99 0.02 Cub_1 /Tr2 substation A 1.34 0.59 0.91 0.02 100.58 Tap: 0.00 Min: 0 Max: 0 B 0.96 0.48 0.89 0.02 100.58 C 1.25 0.21 0.99 0.02 100.58 3 4.16 1.03457 2.48482 119.70980 Cub_1 /Lne Line 1 - 3 A 15.66 Pv: cLod: L: 0.08 km B 15.66 Pv: cLod: C -0.08 -0.04 -0.89 0.04 15.66 Pv: 0.08 kW cLod: 0.00 Mvar Cub_2 /Lne Line 3 - 4 A 7.83 Pv: cLod: L: 0.06 km B 7.83 Pv: cLod: C 0.04 0.02 0.89 0.02 7.83 Pv: 0.02 kW cLod: 0.00 Mvar Cub_3 /Lne Line 3 - 5 A 7.84 Pv: cLod: L: 0.10 km B 7.84 Pv: cLod: C 0.04 0.02 0.89 0.02 7.84 Pv: 0.03 kW cLod: 0.00 Mvar

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 2 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 4 4.16 1.03407 2.48360 119.70020 Cub_2 /Lod Spot Load 4 A Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 3 - 4 A 7.83 Pv: cLod: L: 0.06 km B 7.83 Pv: cLod: C -0.04 -0.02 -0.89 0.02 7.83 Pv: 0.02 kW cLod: 0.00 Mvar 5 4.16 1.03375 2.48283 119.69419 Cub_1 /Lne Line 3 - 5 A 7.84 Pv: cLod: L: 0.10 km B 7.84 Pv: cLod: C -0.04 -0.02 -0.89 0.02 7.84 Pv: 0.03 kW cLod: 0.00 Mvar Cub_2 /Lne Line 5 - 6 A 7.84 Pv: cLod: L: 0.08 km B 7.84 Pv: cLod: C 0.04 0.02 0.89 0.02 7.84 Pv: 0.02 kW cLod: 0.00 Mvar 6 4.16 1.03311 2.48130 119.68216 Cub_2 /Lod Spot Load 6 A Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 5 - 6 A 7.84 Pv: cLod: L: 0.08 km B 7.84 Pv: cLod: C -0.04 -0.02 -0.89 0.02 7.84 Pv: 0.02 kW cLod: 0.00 Mvar

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 3 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 150 4.16 1.00000 2.40178 -0.00000 1.00000 2.40178 -120.00000 1.00000 2.40178 120.00000 Cub_1 /Tr2 substation A -1.54 -0.66 -0.92 0.70 100.58 Tap: 0.00 Min: 0 Max: 0 B -0.92 -0.28 -0.96 0.40 100.58 C -1.09 -0.35 -0.95 0.48 100.58 Cub_2 /Tr2 RG1_A A 1.54 0.66 0.92 0.70 19.34 Tap: 7.00 Min: -16 Max: 16 B 19.34 C 19.34 Cub_3 /Tr2 RG1_B A 11.04 Tap: 7.00 Min: -16 Max: 16 B 0.92 0.28 0.96 0.40 11.04 C 11.04 Cub_4 /Tr2 RG1_C A 13.21 Tap: 7.00 Min: -16 Max: 16 B 13.21 C 1.09 0.35 0.95 0.48 13.21 149 4.16 1.04375 2.50685 -0.00000 1.04375 2.50685 -120.00000 1.04375 2.50685 120.00000 Cub_1 /Tr2 RG1_A A -1.54 -0.66 -0.92 0.67 19.34 Tap: 7.00 Min: -16 Max: 16 B 19.34 C 19.34 Cub_3 /Tr2 RG1_B A 11.04 Tap: 7.00 Min: -16 Max: 16 B -0.92 -0.28 -0.96 0.38 11.04 C 11.04 Cub_4 /Tr2 RG1_C A 13.21 Tap: 7.00 Min: -16 Max: 16 B 13.21 C -1.09 -0.35 -0.95 0.46 13.21 Cub_5 /Lne Line 149 - 1 A 1.54 0.66 0.92 0.67 126.17 Pv: 13.88 kW cLod: 0.00 Mvar L: 0.12 km B 0.92 0.28 0.96 0.38 126.17 Pv: -1.23 kW cLod: 0.00 Mvar C 1.09 0.35 0.95 0.46 126.17 Pv: 6.65 kW cLod: 0.00 Mvar

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 4 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 34 4.16 1.02103 2.45229 119.21300 Cub_2 /Lod Spot Load 34 A Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 13 - 34 A 19.84 Pv: cLod: L: 0.05 km B 19.84 Pv: cLod: C -0.10 -0.05 -0.89 0.05 19.84 Pv: 0.08 kW cLod: 0.00 Mvar Cub_3 /Lne Line 34 - 15 A 11.91 Pv: cLod: L: 0.03 km B 11.91 Pv: cLod: C 0.06 0.03 0.89 0.03 11.91 Pv: 0.02 kW cLod: 0.00 Mvar 15 4.16 1.02064 2.45136 119.20561 Cub_1 /Lne Line 34 - 15 A 11.91 Pv: cLod: L: 0.03 km B 11.91 Pv: cLod: C -0.06 -0.03 -0.89 0.03 11.91 Pv: 0.02 kW cLod: 0.00 Mvar Cub_2 /Lne Line 15 - 16 A 7.94 Pv: cLod: L: 0.11 km B 7.94 Pv: cLod: C 0.04 0.02 0.89 0.02 7.94 Pv: 0.03 kW cLod: 0.00 Mvar Cub_3 /Lne Line 15 - 17 A 3.97 Pv: cLod: L: 0.11 km B 3.97 Pv: cLod: C 0.02 0.01 0.89 0.01 3.97 Pv: 0.01 kW cLod: 0.00 Mvar

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 5 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 17 4.16 1.02019 2.45028 119.19697 Cub_2 /Lod Spot Load 17 A Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C 0.02 0.01 0.89 0.01 Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 15 - 17 A 3.97 Pv: cLod: L: 0.11 km B 3.97 Pv: cLod: C -0.02 -0.01 -0.89 0.01 3.97 Pv: 0.01 kW cLod: 0.00 Mvar 16 4.16 1.01968 2.44904 119.18709 Cub_2 /Lod Spot Load 16 A Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 15 - 16 A 7.94 Pv: cLod: L: 0.11 km B 7.94 Pv: cLod: C -0.04 -0.02 -0.89 0.02 7.94 Pv: 0.03 kW cLod: 0.00 Mvar 11 4.16 1.00100 2.40418 -1.64067 Cub_2 /Lod Spot Load 11 A 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 14 - 11 A -0.04 -0.02 -0.89 0.02 8.09 Pv: 0.02 kW cLod: 0.00 Mvar L: 0.08 km B 8.09 Pv: cLod: C 8.09 Pv: cLod:

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 6 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 2 4.16 1.04301 2.50507 -120.35577 Cub_2 /Lod Spot Load 2 A Pl0: 0.00 MW Ql0: 0.00 Mvar B 0.02 0.01 0.89 0.01 Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 1 - 2 A 3.88 Pv: cLod: L: 0.05 km B -0.02 -0.01 -0.89 0.01 3.88 Pv: 0.00 kW cLod: 0.00 Mvar C 3.88 Pv: cLod: 10 4.16 1.00133 2.40497 -1.63426 Cub_2 /Lod Spot Load 10 A 0.02 0.01 0.89 0.01 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 14 - 10 A -0.02 -0.01 -0.89 0.01 4.04 Pv: 0.01 kW cLod: 0.00 Mvar L: 0.08 km B 4.04 Pv: cLod: C 4.04 Pv: cLod: 12 4.16 1.04237 2.50354 -120.81127 Cub_2 /Lod Spot Load 12 A Pl0: 0.00 MW Ql0: 0.00 Mvar B 0.02 0.01 0.89 0.01 Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 8 - 12 A 3.88 Pv: cLod: L: 0.07 km B -0.02 -0.01 -0.89 0.01 3.88 Pv: 0.00 kW cLod: 0.00 Mvar C 3.88 Pv: cLod:

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 7 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 13 4.16 1.00182 2.40615 -2.02668 1.04190 2.50242 -121.06144 1.02200 2.45461 119.23147 Cub_1 /Lne Line 8 - 13 A -1.34 -0.50 -0.94 0.60 112.38 Pv: 8.39 kW cLod: 0.00 Mvar L: 0.09 km B -0.88 -0.24 -0.96 0.36 112.38 Pv: -0.45 kW cLod: 0.00 Mvar C -0.99 -0.29 -0.96 0.42 112.38 Pv: 3.98 kW cLod: 0.00 Mvar Cub_2 /Lne Line 13 - 34 A 19.84 Pv: cLod: L: 0.05 km B 19.84 Pv: cLod: C 0.10 0.05 0.89 0.05 19.84 Pv: 0.08 kW cLod: 0.00 Mvar Cub_3 /Lne Line 13 - 18 A 0.59 0.33 0.87 0.28 53.09 Pv: 5.70 kW cLod: 0.00 Mvar L: 0.25 km B 0.29 0.19 0.84 0.14 53.09 Pv: -0.95 kW cLod: 0.00 Mvar C 0.24 0.15 0.85 0.12 53.09 Pv: 1.14 kW cLod: 0.00 Mvar Cub_4 /Coup SW1 A 0.75 0.17 0.98 0.32 0.00 B 0.58 0.05 1.00 0.23 0.00 C 0.65 0.09 0.99 0.27 0.00 14 4.16 1.00166 2.40576 -1.62786 Cub_1 /Lne Line 9 - 14 A -0.06 -0.03 -0.89 0.03 12.13 Pv: 0.08 kW cLod: 0.00 Mvar L: 0.13 km B 12.13 Pv: cLod: C 12.13 Pv: cLod: Cub_2 /Lne Line 14 - 10 A 0.02 0.01 0.89 0.01 4.04 Pv: 0.01 kW cLod: 0.00 Mvar L: 0.08 km B 4.04 Pv: cLod: C 4.04 Pv: cLod: Cub_3 /Lne Line 14 - 11 A 0.04 0.02 0.89 0.02 8.09 Pv: 0.02 kW cLod: 0.00 Mvar L: 0.08 km B 8.09 Pv: cLod: C 8.09 Pv: cLod:

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 8 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 19 4.16 0.98543 2.36678 -2.60314 Cub_3 /Lod Spot Load 19 A 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 18 - 19 A -0.08 -0.04 -0.89 0.04 16.44 Pv: 0.09 kW cLod: 0.00 Mvar L: 0.08 km B 16.44 Pv: cLod: C 16.44 Pv: cLod: Cub_2 /Lne Line 19 - 20 A 0.04 0.02 0.89 0.02 8.22 Pv: 0.03 kW cLod: 0.00 Mvar L: 0.10 km B 8.22 Pv: cLod: C 8.22 Pv: cLod: 20 4.16 0.98456 2.36469 -2.62037 Cub_2 /Lod Spot Load 20 A 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 19 - 20 A -0.04 -0.02 -0.89 0.02 8.22 Pv: 0.03 kW cLod: 0.00 Mvar L: 0.10 km B 8.22 Pv: cLod: C 8.22 Pv: cLod:

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 9 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 7 4.16 1.01832 2.44577 -1.20475 1.04292 2.50486 -120.62480 1.03064 2.47536 119.55880 | | B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 1 - 7 A -1.48 -0.59 -0.93 0.65 122.77 Pv: 10.26 kW cLod: 0.00 Mvar L: 0.09 km B -0.90 -0.26 -0.96 0.37 122.77 Pv: -0.97 kW cLod: 0.00 Mvar C -1.00 -0.30 -0.96 0.42 122.77 Pv: 4.13 kW cLod: 0.00 Mvar Cub_2 /Lne Line 7 - 8 A 1.46 0.58 0.93 0.64 121.05 Pv: 6.64 kW cLod: 0.00 Mvar L: 0.06 km B 0.90 0.26 0.96 0.37 121.05 Pv: -0.58 kW cLod: 0.00 Mvar C 1.00 0.30 0.96 0.42 121.05 Pv: 2.73 kW cLod: 0.00 Mvar 8 4.16 1.01129 2.42889 -1.54668 1.04265 2.50422 -120.80595 1.02718 2.46706 119.43787 Cub_1 /Lne Line 7 - 8 A -1.45 -0.57 -0.93 0.64 121.05 Pv: 6.64 kW cLod: 0.00 Mvar L: 0.06 km B -0.90 -0.25 -0.96 0.37 121.05 Pv: -0.58 kW cLod: 0.00 Mvar C -1.00 -0.29 -0.96 0.42 121.05 Pv: 2.73 kW cLod: 0.00 Mvar Cub_2 /Lne Line 8 - 12 A 3.88 Pv: cLod: L: 0.07 km B 0.02 0.01 0.89 0.01 3.88 Pv: 0.00 kW cLod: 0.00 Mvar C 3.88 Pv: cLod: Cub_3 /Lne Line 8 - 9 A 0.10 0.05 0.89 0.05 20.07 Pv: 0.12 kW cLod: 0.00 Mvar L: 0.07 km B 20.07 Pv: cLod: C 20.07 Pv: cLod: Cub_4 /Lne Line 8 - 13 A 1.35 0.52 0.93 0.60 112.38 Pv: 8.39 kW cLod: 0.00 Mvar L: 0.09 km B 0.88 0.24 0.96 0.36 112.38 Pv: -0.45 kW cLod: 0.00 Mvar C 1.00 0.29 0.96 0.42 112.38 Pv: 3.98 kW cLod: 0.00 Mvar

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 10 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 9 4.16 1.00982 2.42537 -1.57498 Cub_2 /Lod Spot Load 9 A 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 8 - 9 A -0.10 -0.05 -0.89 0.05 20.07 Pv: 0.12 kW cLod: 0.00 Mvar L: 0.07 km B 20.07 Pv: cLod: C 20.07 Pv: cLod: Cub_3 /Tr2 RG2_A A 0.06 0.03 0.89 0.03 1.34 Tap: -1.00 Min: -16 Max: 16 B 1.34 C 1.34 RG2 4.16 1.00333 2.40978 -1.59525 Cub_1 /Tr2 RG2_A A -0.06 -0.03 -0.89 0.03 1.34 Tap: -1.00 Min: -16 Max: 16 B 1.34 C 1.34 Cub_2 /Lne Line 9 - 14 A 0.06 0.03 0.89 0.03 12.13 Pv: 0.08 kW cLod: 0.00 Mvar L: 0.13 km B 12.13 Pv: cLod: C 12.13 Pv: cLod:

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 11 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 21 4.16 0.98485 2.36539 -2.66606 1.04259 2.50406 -121.37969 1.01734 2.44343 119.31185 Cub_1 /Lne Line 18 - 21 A -0.20 -0.10 -0.89 0.10 17.93 Pv: 0.23 kW cLod: 0.00 Mvar L: 0.09 km B -0.04 -0.02 -0.89 0.02 17.93 Pv: -0.04 kW cLod: 0.00 Mvar C -0.04 -0.02 -0.89 0.02 17.93 Pv: 0.02 kW cLod: 0.00 Mvar Cub_2 /Lne Line 21 - 22 A 7.77 Pv: cLod: L: 0.16 km B 0.04 0.02 0.89 0.02 7.77 Pv: 0.04 kW cLod: 0.00 Mvar C 7.77 Pv: cLod: Cub_3 /Lne Line 21 - 23 A 0.20 0.10 0.89 0.10 17.93 Pv: 0.16 kW cLod: 0.00 Mvar L: 0.08 km B 0.00 -0.00 0.07 0.00 17.93 Pv: 0.00 kW cLod: 0.00 Mvar C 0.04 0.02 0.89 0.02 17.93 Pv: 0.03 kW cLod: 0.00 Mvar 22 4.16 1.04126 2.50088 -121.40454 Cub_2 /Lod Spot Load 22 A Pl0: 0.00 MW Ql0: 0.00 Mvar B 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 21 - 22 A 7.77 Pv: cLod: L: 0.16 km B -0.04 -0.02 -0.89 0.02 7.77 Pv: 0.04 kW cLod: 0.00 Mvar C 7.77 Pv: cLod:

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 12 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 23 4.16 0.98332 2.36171 -2.75115 1.04350 2.50626 -121.38537 1.01689 2.44235 119.34002 Cub_1 /Lne Line 21 - 23 A -0.20 -0.10 -0.89 0.10 17.93 Pv: 0.16 kW cLod: 0.00 Mvar L: 0.08 km B -0.00 0.00 -0.07 0.00 17.93 Pv: 0.00 kW cLod: 0.00 Mvar C -0.04 -0.02 -0.89 0.02 17.93 Pv: 0.03 kW cLod: 0.00 Mvar Cub_2 /Lne Line 23 - 24 A 7.97 Pv: cLod: L: 0.17 km B 7.97 Pv: cLod: C 0.04 0.02 0.89 0.02 7.97 Pv: 0.05 kW cLod: 0.00 Mvar Cub_3 /Lne Line 23 - 25 A 0.20 0.10 0.89 0.10 17.93 Pv: 0.22 kW cLod: 0.00 Mvar L: 0.08 km B 0.00 -0.00 0.07 0.00 17.93 Pv: 0.00 kW cLod: 0.00 Mvar C -0.00 -0.00 -0.02 0.00 17.93 Pv: 0.00 kW cLod: 0.00 Mvar 24 4.16 1.01547 2.43893 119.31265 Cub_2 /Lod Spot Load 24 A Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 23 - 24 A 7.97 Pv: cLod: L: 0.17 km B 7.97 Pv: cLod: C -0.04 -0.02 -0.89 0.02 7.97 Pv: 0.05 kW cLod: 0.00 Mvar

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 13 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 25 4.16 0.98147 2.35727 -2.84234 1.04455 2.50878 -121.40124 1.01675 2.44202 119.38776 Cub_1 /Lne Line 23 - 25 A -0.20 -0.10 -0.89 0.10 17.93 Pv: 0.22 kW cLod: 0.00 Mvar L: 0.08 km B -0.00 0.00 -0.07 0.00 17.93 Pv: 0.00 kW cLod: 0.00 Mvar C 0.00 0.00 0.03 0.00 17.93 Pv: 0.00 kW cLod: 0.00 Mvar Cub_2 /Lne Line 25 - 28 A 0.12 0.06 0.89 0.06 10.75 Pv: 0.06 kW cLod: 0.00 Mvar L: 0.06 km B 0.00 -0.00 0.07 0.00 10.75 Pv: 0.00 kW cLod: 0.00 Mvar C 0.00 -0.00 0.08 0.00 10.75 Pv: 0.00 kW cLod: 0.00 Mvar Cub_3 /Tr2 RG3_A A 0.08 0.04 0.89 0.04 1.05 Tap: 0.00 Min: -16 Max: 16 B 1.05 C 1.05 Cub_4 /Tr2 RG3_B A 0.00 Tap: -1.00 Min: -16 Max: 16 B 0.00 C -0.00 -0.00 -0.23 0.00 0.00 28 4.16 0.98067 2.35534 -2.88224 1.04501 2.50987 -121.40815 1.01669 2.44187 119.40859 Cub_1 /Lod Spot Load 28 A 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_2 /Lne Line 25 - 28 A -0.12 -0.06 -0.89 0.06 10.75 Pv: 0.06 kW cLod: 0.00 Mvar L: 0.06 km B -0.00 0.00 -0.07 0.00 10.75 Pv: 0.00 kW cLod: 0.00 Mvar C -0.00 0.00 -0.08 0.00 10.75 Pv: 0.00 kW cLod: 0.00 Mvar Cub_3 /Lne Line 28 - 29 A 0.08 0.04 0.89 0.04 7.17 Pv: 0.04 kW cLod: 0.00 Mvar L: 0.09 km B 0.00 -0.00 0.07 0.00 7.17 Pv: 0.00 kW cLod: 0.00 Mvar C 0.00 -0.00 0.08 0.00 7.17 Pv: 0.00 kW cLod: 0.00 Mvar

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 14 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 29 4.16 0.97986 2.35341 -2.92220 1.04546 2.51097 -121.41506 1.01663 2.44173 119.42942 Cub_3 /Lod Spot Load 29 A 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 28 - 29 A -0.08 -0.04 -0.89 0.04 7.17 Pv: 0.04 kW cLod: 0.00 Mvar L: 0.09 km B -0.00 0.00 -0.07 0.00 7.17 Pv: 0.00 kW cLod: 0.00 Mvar C -0.00 0.00 -0.08 0.00 7.17 Pv: 0.00 kW cLod: 0.00 Mvar Cub_2 /Lne Line 29 - 30 A 0.04 0.02 0.89 0.02 3.59 Pv: 0.01 kW cLod: 0.00 Mvar L: 0.11 km B 0.00 -0.00 0.07 0.00 3.59 Pv: 0.00 kW cLod: 0.00 Mvar C 0.00 -0.00 0.08 0.00 3.59 Pv: 0.00 kW cLod: 0.00 Mvar 30 4.16 0.97939 2.35229 -2.94554 1.04573 2.51161 -121.41909 1.01660 2.44164 119.44158 Cub_2 /Lod Spot Load 30 A 0.04 0.02 0.89 0.02 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_1 /Lne Line 29 - 30 A -0.04 -0.02 -0.89 0.02 3.59 Pv: 0.01 kW cLod: 0.00 Mvar L: 0.11 km B -0.00 0.00 -0.07 0.00 3.59 Pv: 0.00 kW cLod: 0.00 Mvar C -0.00 0.00 -0.08 0.00 3.59 Pv: 0.00 kW cLod: 0.00 Mvar Cub_4 /Lne Line 30 - 250 A -0.00 -0.00 -0.16 0.00 0.00 Pv: -0.00 kW cLod: 0.00 Mvar L: 0.11 km B 0.00 -0.00 0.07 0.00 0.00 Pv: 0.00 kW cLod: 0.00 Mvar C 0.00 -0.00 0.08 0.00 0.00 Pv: 0.00 kW cLod: 0.00 Mvar

  • Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 15 rated Active Reactive Power Voltage Bus-voltage Power Power Factor Current Loading Additional Data [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] 250 4.16 0.97939 2.35229 -2.94554 1.04573 2.51161 -121.41909 1.01660 2.44164 119.44158 Cub_4 /Lne Line 30 - 250 A -0.00 -0.00 -1.00 0.00 0.00 Pv: -0.00 kW cLod: 0.00 Mvar L: 0.11 km B -0.00 -0.00 -1.00 0.00 0.00 Pv: 0.00 kW cLod: 0.00 Mvar C -0.00 0.00 -1.00 0.00 0.00 Pv: 0.00 kW cLod: 0.00 Mvar Cub_1 /Coup SW7 A 0.00 -0.00 1.00 0.00 0.00 B 0.00 0.00 1.00 0.00 0.00 C 0.00 0.00 1.00 0.00 0.00 31 4.16 0.97919 2.35179 -2.93762 Cub_5 /Lod Spot Load 31 A 0.02 0.01 0.89 0.01 Pl0: 0.00 MW Ql0: 0.00 Mvar B Pl0: 0.00 MW Ql0: 0.00 Mvar C Pl0: 0.00 MW Ql0: 0.00 Mvar Cub_2 /Lne Line 26 - 31 A -0.04 -0.02 -0.89 0.02 8.27 Pv: cLod: L: 0.07 km B 8.27 Pv: cLod: C