of 76
7/29/2019 Distance Principles_basic Principle
1/76
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the priorwritten consent of Alstom Grid Technical Institute. All rights reserved.
Distance Protection
7/29/2019 Distance Principles_basic Principle
2/76
Distance Protection - P 2
Distance Protection
Popular, widely used on Sub-Transmission and Transmission
Systems
Virtually independent of Fault Current Level (ZS/ZL ratios)
Fast Discriminative Protection:- Zone 1 or Aided Distance Scheme
Time Delayed Remote Back-Up
7/29/2019 Distance Principles_basic Principle
3/76
Distance Protection - P 3
Advantages of Distance Protection
Measures Z, X or R correctly irrespective of System
Conditions
Compare this with Instantaneous Overcurrent Protection:-
7/29/2019 Distance Principles_basic Principle
4/76
Distance Protection - P 4
Advantages of Distance Protection
F1
115kV 50
IF1
ZS = 10 ZS = 10
ZL = 4
IF1 = 115kV/3(5+4) = 7380A Is > 7380A
7/29/2019 Distance Principles_basic Principle
5/76
Distance Protection - P 5
Advantages of Distance Protection
Consider with one source out of service:-
IF2 = 115kV/3 x 10 = 6640A
Is 7380A - IMPRACTICAL
F2
50
IF2
ZS = 10
7/29/2019 Distance Principles_basic Principle
6/76
Distance Protection - P 6
Simplified Line Diagram
XL = jL XC = -jC
at FN (50Hz) XC = large :-
LR R R RLLL
CCC
RL
7/29/2019 Distance Principles_basic Principle
7/76Distance Protection - P 7
Basic Principle of Distance Protection
ZLZS
Generation
Distance
Relay
IR
21 VR
7/29/2019 Distance Principles_basic Principle
8/76Distance Protection - P 8
Impedance Seen By Measuring Element
jX
ZL
R
7/29/2019 Distance Principles_basic Principle
9/76Distance Protection - P 9
Basic Principle of Distance Protection
LOADLR
RR ZZ
VZmeasuredImpedance
Relay
PT.
Normal
Load
IR ZLZS
VRVS ZLOAD
7/29/2019 Distance Principles_basic Principle
10/76Distance Protection - P 10
Basic Principle of Distance Protection
Ppp
Ppp
PppFault
IRZS
VRVS ZLOAD
ZL
ZF
Impedance Measured ZR = VR/IR = ZF
Relay Operates if ZF < Z where Z = setting
Increasing VR has a Restraining Effect VR calledRestraining Voltage
Increasing IR has an Operating Effect
7/29/2019 Distance Principles_basic Principle
11/76Distance Protection - P 11
Plain Impedance Characteristic
jX ZL
R
TRIP STABLE
Impedance Seen At
Measuring Location For
Line Faults
7/29/2019 Distance Principles_basic Principle
12/76Distance Protection - P 12
Impedance Characteristic Generation
Operate
IF
VF
Restrain
Spring
Trip
zF
Ampere Turns : VF IZ
Trip Conditions : VF < IFZ
jIX
IZV1V2
V3
IR
TRIP STABLE
Voltage to Relay = VCurrent to Relay = I
Replica Impedance = Z
Trip Condition : S2 < S1
where : S1 = IZ ZS2 = V ZF
7/29/2019 Distance Principles_basic Principle
13/76Distance Protection - P 13
Basic Principle of Distance Protection
Relays are calibrated in secondary ohms :-
RATIOV.T.
RATIOC.T.xZZ
/VV
/x
V
/x
/VVxV/VZ
PR
21
21
FP
FP
12FP
12FPRRR
IR
21 VR
I1/I2 ZP
V1
V2VFP
7/29/2019 Distance Principles_basic Principle
14/76Distance Protection - P 14
Example
ZP = 4; V1/V2 = 115kV/115V; I1/I2 = 600/5A
ZR(5) = 4 x (600/5) / (115x103/115) = 0.48 - 5A Relay
ZR(1) = 2.4 - 1A Relay
C.T. RATIOZR = ZP x
V.T. RATIO
7/29/2019 Distance Principles_basic Principle
15/76Distance Protection - P 15
Input Quantities for-Faults
FAULT VRESTRAINT IOPERATE
A - B VA - VB IA - IB
B - C VB - VC IB - IC
C - A VC - VA IC - IA
VRESTRAINT & IOPERATE are selected inside the relayNo setting adjustments are required apart from
Z1 = Phase Replica Impedance
7/29/2019 Distance Principles_basic Principle
16/76Distance Protection - P 16
Input Quantities for-Faults (1)
VR1 = E - I1ZS1 = 2I1{ZS1 + ZL1} - I1ZS1
= I1ZS1 + 2I1ZL1
VR2 = - I2ZS2 = I1ZS1
VRB = a2VR1 + aVR2 = a2{2I1ZL1 + I1ZS1} + aI1Zs1
VRC = aVR1 + a2VR2 = a{2I1ZL1 + I1ZS1} + a
2I1ZS1
IRB = a2I1 aI1 = (a
2 a)I1
IRC = aI1 a2
I1 = (a a2
)I1
ZS1 I1
I2
F1
N1
F2
N2
ZL1
ZS2 ZL2
IR1
IR2
vR2
vR1
E
7/29/2019 Distance Principles_basic Principle
17/76
Distance Protection - P 17
Consider a B-C Fault
VR1 = E - I1ZS1 = 2I1 {ZS1 + ZL1} - I1ZS1
= I1ZS1 + 2I1ZL1
VR2 = -I2ZS2 = I1ZS1
VRB = a2
VR1 + aVR2 = a2
{2I1ZL1 + I1ZS1}+ aI1ZS1
VRC = aVR1 + a2VR2 = a{2I1ZL1 + I1ZS1}
+ a2I1ZS1
IRB = a2I1 - aI1 = (a
2-a)I1
IRC = aI1 - a2I1 = (a-a
2)I1
ZL1ZS1
E
I1
F1
ZL1
ZS1 IR1
VR1
N1
I2
F2
ZL2ZS2 IR2
VR2
N2
7/29/2019 Distance Principles_basic Principle
18/76
Distance Protection - P 18
Using VRB & IRB to Obtain ZRB
( ) ( )( ) ( ) ( )( )
S1L1S1L1
S12
2
L12
2
1
2
S112
L112
RB
RBRB
Z.903
1Z.30
3
2Z.
903
1801Z.
903
2401.2
Z.aa
aaZ.aa
2a
IaaZIaaZ2Ia
IVZ
---
-
-
-
Relay Will Not Measure The Same Impedance Under
All Conditions If V/N And I Are Used
ZS1 Is a Variable Factor
7/29/2019 Distance Principles_basic Principle
19/76
Distance Protection - P 19
Correct Measurement for B-C Faultby Using VBVC & IB-IC
VB-VC = (a2-a) . (2I1ZL1 + I1ZS1) + (a-a
2)I1ZS1
IB - IC = 2(a2 - a)I1
ZRB = (VB-VC)/ (IB - IC) = ZL1 + ZS1/2 - ZS1/2
= ZL1
The relay can be calibrated in terms of the positive
sequence impedance of the protected line.
Distance relays are designed to use VBC & IBC and will
automatically take them from the connected 3voltages and currents.
7/29/2019 Distance Principles_basic Principle
20/76
Distance Protection - P 20
Input Quantities for Phase to Earth Faults
FAULT VRESTRAINT IOPERATE
A - E VA ? IA ?
B - E
C - E
7/29/2019 Distance Principles_basic Principle
21/76
Distance Protection - P 21
Neutral Impedance Replica Vectorial Compensation
Replica impedance circuit :-
Z1IRA
I
RN
IZN
Z1
N
Z1
ZN
Z1 = Phase replica impedance
ZN = Neutral replica impedance
IRA passes through Z1
IRN passes through ZN
ZT = Z1 + ZN
7/29/2019 Distance Principles_basic Principle
22/76
Distance Protection - P 22
Neutral Impedance Compensation
For a single phase to ground fault the total earth loop
impedance is given by :- (Z1 + Z2 + Z0)/3 = ZT
ZT = (Z1 + Z2 + Z0)/3 = Z1 + ZN
ZN = (Z1 + Z2 + Z0)/3 - Z1
= (2Z1 + Z0)/3 - Z1
= - Z1 + Z0
= KN Z1
3 3
where KN = (Z0 - Z1)
3Z1
7/29/2019 Distance Principles_basic Principle
23/76
Distance Protection - P 23
Neutral Impedance Vectorial Replica Compensation
Line CTs
A
ZPH
B
C
IAZPH
ZPH IBZPH
ZPH ICZPH
ZN INZN
Set ZPH = ZF1
Set ZN = (ZF0- Z F1)
3
Usually ZN = ZPH for OHLs
7/29/2019 Distance Principles_basic Principle
24/76
Distance Protection - P 24
Neutral Impedance Replica Compensation
For cables Z0Z1VECTORIAL COMPENSATION MUST BE USEDKN = Z0 - Z1 = KNN
3Z1
7/29/2019 Distance Principles_basic Principle
25/76
Distance Protection - P 25
Neutral Impedance Replica Vectorial Compensation
Vectorial compensation allows forZNZPH which isespecially important for cable distance protection where
ZN < ZPH and ZN is sometimes negative.
ZE = Earth-loop impedance
for - earth fault on acable
jX
R
ZE
ZPHZN
7/29/2019 Distance Principles_basic Principle
26/76
GRIDTechnical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the priorwritten consent of Alstom Grid Technical Institute. All rights reserved.
Characteristics
7/29/2019 Distance Principles_basic Principle
27/76
Distance Protection - P 27
Distance Characteristics
MHOR
Zn
jXjX
R
Zs
Zn
CROSS-
POLARISED
MHO
QUADRILATERAL
Zn
R
OFFSET
MHO
jX
Zn
Zn
R
IMPEDANCE
jX
ZnR
LENTICULAR
jX
ZnR
POLYGON
Zn
R
7/29/2019 Distance Principles_basic Principle
28/76
Distance Protection - P 28
Self Polarised Mho Relays
Very popular characteristic
Simple
Less sensitive to power swings
Inherently directional
Operates for F1, but not for F2
Mho = 1/OHM
Settings :-
Z = reach setting
= characteristic angle
jX
R
F2
F1
Z
OPERATE
RESTRAIN
7/29/2019 Distance Principles_basic Principle
29/76
Distance Protection - P 29
Offset Mho Characteristic
Normally used as backup
protection
Operates for zero faults
(close up faults)
Generally time delayed (as
not discriminative)
jX
R
Z
-Z
7/29/2019 Distance Principles_basic Principle
30/76
Distance Protection - P 30
Mho Relays
Directional circular characteristic obtained by introducing VPOLARISING
VF self polarised V
SOUND PHASE
fully cross-polarised
VF + xVS.F. partially cross-polarised VPRE-FAULT memory polarised
Purpose for this is to ensure operation for close up faults where
measured fault voltage collapses
7/29/2019 Distance Principles_basic Principle
31/76
Distance Protection - P 31
Quadrilateral Characteristic
Z
jX
ZR
RR
Load
L
1
F
S
7/29/2019 Distance Principles_basic Principle
32/76
Distance Protection - P 32
Lenticular Load Avoidance Characteristic
jIX
IR
ba
Lenticular characteristiccreated from two offset
Mho comparators
Aspect ratio = a/b
7/29/2019 Distance Principles_basic Principle
33/76
Distance Protection - P 33
Lenticular Characteristic
X
R
a
b
Z3
Aspect ratios a/b
0.41
0.67
1.00
Load impedancearea
Z3 reverse
7/29/2019 Distance Principles_basic Principle
34/76
Distance Protection - P 34
Forward Offset Characteristic
Z3
Z2
Z1
Rf
X
R
Load area
Forward blinder
Enhanced resistive coverage for remote faults
7/29/2019 Distance Principles_basic Principle
35/76
GRIDTechnical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the priorwritten consent of Alstom Grid Technical Institute. All rights reserved.
Zones of Protection
7/29/2019 Distance Principles_basic Principle
36/76
Distance Protection - P 36
Z2A Z2C
Z3A Z3C
Time
T3
T2
Z1CZ1A
Z1B DCA
Z2B
T2
Z1A = 80% of ZAB (inst.)
Z2A = 120% of ZAB (~300ms)
Z3A(FORWARD) = 120% of {ZAB + ZCD} (~600ms)
Z3A(REVERSE) = 10-25% of ZAB
B
Zones of Protection
7/29/2019 Distance Principles_basic Principle
37/76
Distance Protection - P 37
RA
D
C
B
Z1A
Z2A
Z3A
jX
Zones of Protection
7/29/2019 Distance Principles_basic Principle
38/76
Distance Protection - P 38
FAST OPERATION
Trips circuit breaker without delay as soon as
fault within Zone 1 reach is detected.
REACH SETTING
Cannot be set to 100% of protected line or may
overreach into next section.
Overreach caused by possible errors in :-
CTs
VTs
ZLINE information
Relay Measurement
Zone 1
7/29/2019 Distance Principles_basic Principle
39/76
Distance Protection - P 39
PossibleOverreach
ZONE 1 = ZL
ZL
F
ZONE 1 = 0.8ZL
ZL
Possible incorrect tripping for fault at F
Zone 1 set to 0.8ZL
Zone 1
7/29/2019 Distance Principles_basic Principle
40/76
Distance Protection - P 40
Z1C = 0.8ZACA
C
Z1A = 0.8ZABZ1B = 0.8ZBA
B
Z1C
Z1AZ1B
Zone 1 Settings for Teed Feeders
7/29/2019 Distance Principles_basic Principle
41/76
Distance Protection - P 41
Z1AReceiveSend
Trip B
Z1BReceive Send
Z1B
Z1A
ZLA
B
Zone 1 Settings for Direct Intertrip Schemes
Zone 1 Settings for Direct Intertrip Schemes
7/29/2019 Distance Principles_basic Principle
42/76
Distance Protection - P 42
Zone 1 Settings for Direct Intertrip Schemes
Effective Zone 1 reaches at A and B must overlap.
Otherwise :- No trip for fault at F
Effective Z1A and Z1B must be > 0.5ZL
Settings for Zone 1 > 0.8ZL are o.k.
Z1B
Z1A
F
A
B
Minimum Zone 1 Reach Setting
7/29/2019 Distance Principles_basic Principle
43/76
Distance Protection - P 43
Minimum Zone 1 Reach Setting
Dictated by :-
Minimum relay voltage for fault at Zone 1reach point to ensure accurate measurement.
Minimum voltage depends on relay design typically 1 3 volts.
7/29/2019 Distance Principles_basic Principle
44/76
Distance Protection - P 44
SIR = ZS/Zn
where :- ZS = Source impedance behind relay
Zn = Reach setting
VRPA
= Minimum voltage for reach point accuracy
Can be expressed in terms of an equivalent value
of SIRMAX
SIRMAX = ZS MAX
Zn MIN
Zn MIN ZS MAXSIRMAX
System Impedance Ratio :- SIR
7/29/2019 Distance Principles_basic Principle
45/76
Distance Protection - P 45
Covers last 20% of line not covered by Zone 1.
Provides back-up protection for remote busbars.
To allow for errors :-
Z2G > 1.2 ZGH
Zone 2 is time delayed to discriminate with Zone 1 on next
section for faults in first 20% of next section.
Z1H
Z2G
TIME
Z1G
G H
F
Zone 2
7/29/2019 Distance Principles_basic Principle
46/76
Distance Protection - P 46
Overlap only occurs for faults in first 20% of following line.
Faults at F should result in operation of Z1H and tripping of circuit breaker H.If H fails to trip possible causes are :-
Z1H operates but trip relays fail.
Z2H may operate but will not trip if followed by the same trip relays.
Z1H and trip relays operate but circuit breaker fails to trip.
Fault must be cleared at G by Z2G.
Zone 2 on adjacent line sections are not normally time graded
with each other
Z1G Z1H
Z2G Z2H
HG
F
Zone 2
7/29/2019 Distance Principles_basic Principle
47/76
Distance Protection - P 47
No advantage in time grading Z2G with Z2H
Unless Z2H + trip relays energise a 2nd circuit breaker trip
coil.
Zone 2
7/29/2019 Distance Principles_basic Principle
48/76
Distance Protection - P 48
Z1H fails to operate.
Results in race between breakers G and H if Z2H and Z2Ghave the same time setting.
Can only be overcome by time grading Z2G with Z2H.
Problem with this :-Zone 2 time delays near source on systems with several line
sections will be large.
End zone faults on lines nearest the infeed source point will be
cleared very slowly.
Z1G Z1H
Z2G
Z2H
HG
Zone 2
Maximum Allowable Zone 2 Reach to Allow for
7/29/2019 Distance Principles_basic Principle
49/76
Distance Protection - P 49
Z2A must not reach beyond Z1B
i.e. Z2A(EFF) MAX must not reach further than Z1B(EFF) MIN
Z1BSETTING = 0.8ZL2
Z1B(EFF) MIN = 0.8 x 0.8ZL2 = 0.64ZL2 Z2A(EFF) MAX < ZL1 + 0.64ZL2
1.2 Z2ASETTING < ZL1 + 0.64ZL2
Z2ASETTING < 0.83ZL1 + 0.53ZL2
Z2A(EFF) MAX
Z1B(EFF) MIN
ZL2ZL1BA
Maximum Allowable Zone 2 Reach to Allow forEqual Zone 2 Time Settings
Zone 2 Time Settings on Long Line Followed by
7/29/2019 Distance Principles_basic Principle
50/76
Distance Protection - P 50
Z3H
Z2G
Z3J
Z2H
Z2J
Z1H Z1JZ1G
H JG
F
Z2G reaches into 3rd line section.
To limit remote back-up clearance for a fault at F, the time
setting of Z2G must discriminate with Z3H.
Zone 2 Time Settings on Long Line Followed bySeveral Short Lines
7/29/2019 Distance Principles_basic Principle
51/76
Distance Protection - P 51
HG K
Z1G Z1H
Z2G
Z3G
REV Z3G FWD
Time
Typical settings : Z3FWD > 1.2 x (ZGH + ZHK)
Z3REV 0.1 to 0.25 of Z1G
Zone 3
Provides back-up for next adjacent line.
Provides back-up protection for busbars (reverse offset).
Actual Zone 3 settings will be scheme specified, i.e. permissive orblocking schemes.
Many modern relays have more than 3 Zones to allow the use of three
forward and an independent reverse zone.
7/29/2019 Distance Principles_basic Principle
52/76
Distance Protection - P 52
Zone 1 :- tZ1 = instantaneous (typically 15 - 35mS)
Zone 2 :- tZ2 = tZ1(down) + CB(down) + Z2(reset) + Margin
e.g. tZ2 = 35 + 100 + 40 + 100 = 275mS
Zone 3 :- tZ3 = tZ2(down) + CB(down) + Z3(reset) + Margine.g. tZ3 = 275 + 100 + 40 + 100 = 515mS
Note: Where upper and lower zones overlap, e.g. Zone 2 up
sees beyond Zone 1 down, the upper and lower zone
time delays will need to be coordinated, e.g. tZ2(up) to
exceed tZ2(down).
Zone Time Coordination - Ideal Situation
7/29/2019 Distance Principles_basic Principle
53/76
GRIDTechnical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Under / Overreach
7/29/2019 Distance Principles_basic Principle
54/76
Distance Protection - P 54
Impedance presented > apparent impedance
%age Underreach = ZR - ZF x 100%
ZR
where ZR = Reach setting
ZF = Effective reach
Under-Reach
Underreaching Due to Busbar Infeed between
7/29/2019 Distance Principles_basic Principle
55/76
Distance Protection - P 55
IA IA+IB
Relay LocationIB
ZA ZB
VR = IAZA + (IA + IB) ZB
IR =
IA
ZR = ZA + ZB + IB . ZB
IA
Underreaching Due to Busbar Infeed betweenRelay and Fault
Underreaching Due to Busbar Infeed between
7/29/2019 Distance Principles_basic Principle
56/76
Distance Protection - P 56
Relay with setting ZA + ZB will underreach withinfeed.
Relay with setting ZA + ZB + IB . ZB will measure
IAcorrectly with infeed present but if infeed is removed the
relay will overreach.
Maximum allowable setting dictated by load impedance
Underreaching Due to Busbar Infeed betweenRelay and Fault
U d R h
7/29/2019 Distance Principles_basic Principle
57/76
Distance Protection - P 57
IP
What relay reach setting is required to ensure fault at F is at
boundary of operation ?
Impedance seen for fault at F
= ZG + IG + IP . ZKIG
Limit of operation is when Impedance Seen = Reach Setting
Reach setting required= ZG + IG + IP . ZK
IG
ZK FIG+IP
ZG IG
RELAY
Under-Reach
O R h
7/29/2019 Distance Principles_basic Principle
58/76
Distance Protection - P 58
Impedance seen < apparent impedance
%age Overreach = ZF - ZR x 100%
ZR
where ZR = Reach setting
ZF = Effective reach
Over-Reach
7/29/2019 Distance Principles_basic Principle
59/76
GRIDTechnical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Mutual Coupling
M t l C li
7/29/2019 Distance Principles_basic Principle
60/76
Distance Protection - P 60
Mutual Coupling
Mutual coupling causes distance relays to eitherunderreach or overreach.
Positive and negative sequence has no impact.
Zero sequence mutual coupling can have a significantinfluence on the relay.
Only affects ground fault distance.
M t l C li E l U d R h
7/29/2019 Distance Principles_basic Principle
61/76
Distance Protection - P 61
Z2 Boost G/F
Z2 PH
Zmo
Mutual Coupling Example Under Reach
M t al Co pling E ample O er Reach
7/29/2019 Distance Principles_basic Principle
62/76
Distance Protection - P 62
Z2 reduced G/F
Z2 PH
Mutual Coupling Example Over Reach
Mutual Coupling Example Over Reach
7/29/2019 Distance Principles_basic Principle
63/76
Distance Protection - P 63
Z1 G/F (optional)
Z1 G/F (normal)
Zmo
Mutual Coupling Example Over Reach
7/29/2019 Distance Principles_basic Principle
64/76
GRIDTechnical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Ancilliary Functions
Switch on to Fault (SOTF)
7/29/2019 Distance Principles_basic Principle
65/76
Distance Protection - P 65
X
X
X
Switch on to Fault (SOTF)
Fast tripping for faults on line energisation, even where
line VTs provide no prefault voltage memory
Voltage Transformer Supervision
7/29/2019 Distance Principles_basic Principle
66/76
Distance Protection - P 66
Voltage Transformer Supervision
A VT fault and subsequent operation of VT fuses or MCBs results inmisrepresentation of primary voltages
Relay will remain stable as the current phase selector will not pick up
Subsequent system fault may cause unwanted / incorrect tripping
VTS operating from presence of V0 with no I0 or V2 with no I2 is usedto block relay if required
VT Supervision
7/29/2019 Distance Principles_basic Principle
67/76
Distance Protection - P 67
VT Supervision
Under load conditions
Loss of 1 or 2 phase voltages Loss of all 3 phase voltages
Upon line energisation Loss of 1 or 2 phase voltages Loss of all 3 phase voltages
Digital input to monitor MCB
Set to block voltage dependent functions
Zone 1 Mho Relay
7/29/2019 Distance Principles_basic Principle
68/76
Distance Protection - P 68
Will not operate for load or
stable power swing
1, 2, 3, = Anglesbetween system voltagesat K and L
increases as power
swingapproaches relay at G
J is point where power swingenters relay characteristic
At J the angle between
voltages at G & H is 90
Normal limit of angle betweenvoltages at G & H for
load is ofthe order of 30
L
K
ZS
HH
Z13 J
G
ZS
G
1
Power Swing Locus
2 LOA
D
Zone 1 Mho Relay
Comparison between Stability of Mho and Quadrilateral
7/29/2019 Distance Principles_basic Principle
69/76
Distance Protection - P 69
p yImpedance Elements during a Power Swing
jX
PowerSwingLocus
R
Illustration of Basic Power Swing
7/29/2019 Distance Principles_basic Principle
70/76
Distance Protection - P 70
jX
Power SwingLocus
R
Z3
ZP
Blocking System
Power Swing Blocking
7/29/2019 Distance Principles_basic Principle
71/76
Distance Protection - P 71
A power swing will result in continuous change of current
Continuous output from the relay superimposed current element canbe used to block for a power swing
Using this method the relay is able to operate for faults occurringduring a power swing
Power Swing Blocking
Directional Earth Fault Protection (DEF)
7/29/2019 Distance Principles_basic Principle
72/76
Distance Protection - P 72
High resistance ground faults
Instantaneous or time delayed
IEC and IEEE curves
Single or shared signalling channel
Directional Earth Fault Protection (DEF)
7/29/2019 Distance Principles_basic Principle
73/76
GRIDTechnical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Transformer Feeders
Transformer Feeders
7/29/2019 Distance Principles_basic Principle
74/76
Distance Protection - P 74
Zone 1 = ZL + 0.5ZT
T1 = Instantaneous
Zone 2 = 1.2 (ZL +ZT)
T2 = Co-ordinate with downstream protection
Zone 3
T3- Back-up use as appropriate
ZL
ZT
21
Transformer Feeders
Low Voltage VT High Voltage CT
7/29/2019 Distance Principles_basic Principle
75/76
Distance Protection - P 75
Low Voltage VT, High Voltage CT
* 1 VT may be required to account for phase shift.
Example 1
ZT = 10 , ZL = 1
Set relay Z1 = 0.8 x (ZT + ZL) = 8.8
Z1 does not reach through transformer.
Example 2
ZT = 10 , ZL = 1
Z1 = ZT + 0.8ZL = 10.8
with 20% error = 12.96 - overreach problem
ZT
21
ZL
7/29/2019 Distance Principles_basic Principle
76/76
GRIDTechnical Institute